MJ-4TM Communications Module Fiber Optic and RS-232/485 Installation Manual for MJ-4ATM, MJ-XL TM and MJ-XTM Control Panels RS - 232 / 485 G R N T D N Communications Module POWER Watchdog Communications IN - + R x d T x d OUT Rxd MJ-4 Communications Module Manual No. 21-115-527-024 rev01 Data Txd C T S R T S ! DANGER Hazardous Voltage. Will cause death, serious injury, or equipment damage. De-energize and maintenance. ground the equipment before Only qualified personnel should work on this equipment after becoming thoroughly familiar with all warnings, safety notices, instructions and maintenance procedures contained herein. The successful and safe operation of this equipment Is dependent upon proper handling, installation, operation and maintenance. The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the user of responsibility to use sound practices in application, installation, operation, and maintenance of the equipment purchased. Siemens reserves the right to make changes in the specifications shown herein or to make improvements at any time without notice or obligations. Should a conflict arise between the general information contained in this publication and the contents of drawings or supplementary material or both, the latter shall take precedence. NOTE Authorized and qualified Personnel For the purpose of this manual a qualified person is one who is familiar with the installation, construction or operation of the equipment and the hazards involved. In addition, he has the following qualifications: (a) Is trained and authorized to de-energize, clear, ground, and tag circuits and equipment in accordance with established safety practices. (b) Is trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices. (c) Is trained in rendering first aid. SUMMARY These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the local sales office, listed on the back of this instruction guide. The contents of this instruction manual should not become part of or modify any prior or existing agreement, commitment or relationship. The sales contract contains the entire obligation of Siemens Power Transmission & Distribution Inc. The warranty contained in the contract between the parties is the sole warranty of Siemens Power Transmission & Distribution Inc. Any statements contained herein do not create new warranties or modify the existing warranty. DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. Table of Contents 1 INTRODUCTION ...............................................................................................................................................1 1.1 DESCRIPTION ..................................................................................................................................................1 1.2 LED INDICATORS ...........................................................................................................................................1 2 TRANSMISSION METHODS ...........................................................................................................................1 2.1 FIBER OPTIC TRANSMISSION ..........................................................................................................................2 2.2 WIRE TRANSMISSION......................................................................................................................................2 2.2.1 RS-232 ...................................................................................................................................................2 2.2.2 RS-485 ...................................................................................................................................................3 3 COMMUNICATION PROTOCOLS ................................................................................................................4 4 5 6 7 8 INSTALLING THE COMMUNICATIONS MODULE IN MJ- 4 CONTROL PANELS ...........................4 4.1 REMOVING THE MJ-4 REAR COVER................................................................................................................4 4.2 MOUNTING THE COMMUNICATIONS MODULE.................................................................................................5 4.3 SETTING THE COMMUNICATIONS MODULE JUMPERS ......................................................................................6 4.3.1 Fiber Optic Interface .............................................................................................................................6 4.3.2 RS-232/485 Interface .............................................................................................................................6 4.4 REPLACING THE MJ-4 REAR COVER ...............................................................................................................7 4.5 MOUNTING THE COMMUNICATIONS MODULE LABEL .....................................................................................7 INSTALLING THE COMMUNICATIONS MODULE IN MJ-X CONTROL PANELS............................8 5.1 SETTING THE COMMUNICATIONS MODULE JUMPERS ......................................................................................8 5.2 MOUNTING THE COMMUNICATIONS MODULE IN MJ-X CONTROL PANELS .....................................................8 VERIFYING THE COMMUNICATIONS MODULE INSTALLATION ..................................................10 6.1 PERFORMING THE INITIAL DIAGNOSTIC CHECKOUT .....................................................................................11 6.2 PERFORMING THE LOOPBACK DIAGNOSTIC TEST .........................................................................................11 CABLING THE COMMUNICATIONS MODULE TO THE POWER SYSTEM.....................................12 7.1 FIBER OPTIC CABLE TYPE ............................................................................................................................12 7.1.1 Fiber Optic Cable Lengths ..................................................................................................................12 7.1.2 Fiber Optic Connector.........................................................................................................................12 7.1.3 Fiber Optic Connections......................................................................................................................13 7.2 RS-485 TWISTED-PAIR CABLE .....................................................................................................................13 7.2.1 RS-485 Cable Type ..............................................................................................................................13 7.2.2 RS-485 Cable Grounding ....................................................................................................................13 7.2.3 RS-485 Connector................................................................................................................................14 7.2.4 RS-485 Cabling Considerations ..........................................................................................................14 7.3 RS-232 CONNECTIONS .................................................................................................................................15 7.3.1 RS-232 Multi-drop Wiring...................................................................................................................16 7.4 RS-232/485 CONNECTIONS ..........................................................................................................................17 7.5 COMMUNICATIONS MODULE CONFIGURATION .............................................................................................17 7.5.1 Communications Menu Item Descriptions...........................................................................................18 7.6 TROUBLESHOOTING COMMUNICATIONS PROBLEMS .....................................................................................19 7.6.1 Using LEDs to Help Diagnose Communications Problems ................................................................20 7.6.2 Using MJXplorer to Troubleshoot Communications Problems...........................................................20 SETTING THE DNP POINTS .........................................................................................................................21 8.1 USING THE DNP CONFIGURE PROGRAM FOR A CUSTOM DNP POINT SET ......................................................21 8.2 SELECTING A PREDEFINED DNP POINT SET ...................................................................................................21 8.2.1 DNP point set for MJ-4A or MJ-4B.....................................................................................................21 8.2.2 DNP Point set for other Control Panels..............................................................................................21 8.2.3 2.x4 ......................................................................................................................................................22 8.2.4 Small 2.x3 ............................................................................................................................................23 8.2.5 Simple ..................................................................................................................................................24 8.2.6 Metering...............................................................................................................................................24 Manual No. 21-115-527-024 rev01 8.2.7 Active ...................................................................................................................................................26 8.2.8 Set 7 .....................................................................................................................................................27 8.2.9 2.x3 ......................................................................................................................................................27 9 COMMUNICATIONS MODULE FIRMWARE VERSIONS......................................................................34 9.1 MJ-4 COMMUNICATIONS MODULE FIRMWARE VERSION ...............................................................................34 9.2 MJ-XL COMMUNICATIONS MODULE FIRMWARE VERSIONS..........................................................................34 10 SPECIFICATIONS ...........................................................................................................................................35 10.1 PHYSICAL DIMENSIONS ................................................................................................................................35 10.2 FIBER OPTIC LINK INTERFACE SPECIFICATIONS ...........................................................................................35 10.3 RS-232/RS-485 INTERFACE SPECIFICATIONS ...............................................................................................35 Figures FIGURE 1-1 MJ-4 COMMUNICATIONS MODULE. .............................................................................................................1 FIGURE 2-1 FIBER OPTIC NETWORK. ..............................................................................................................................2 FIGURE 2-2 RS-232 CONNECTION. .................................................................................................................................2 FIGURE 2-3 MODEM CONNECTION. ................................................................................................................................2 FIGURE 2-4 RS-485 CONFIGURATION – LOOP NETWORK. ..............................................................................................3 FIGURE 2-5 RS-485 CONFIGURATION – STAR NETWORK. ..............................................................................................3 FIGURE 4-1 MJ-4 REAR COVER. .....................................................................................................................................5 FIGURE 4-2 COMMUNICATIONS MODULE INSTALLATION. ..............................................................................................5 FIGURE 4-3 FIBER OPTIC INTERFACE JUMPER LOCATIONS. ............................................................................................6 FIGURE 4-4 RS-232/485 INTERFACE JUMPER LOCATIONS. .............................................................................................6 FIGURE 4-5 MJ-4 WITH MJ-4 COMMUNICATIONS MODULE LABEL INSTALLED. .............................................................7 FIGURE 5-1 MJ-X CONTROL PANEL REAR COVER. ........................................................................................................8 FIGURE 5-2 COMMUNICATIONS MODULE INSTALLATION IN MJ-X. ................................................................................9 FIGURE 5-3 MEMBRANE SWITCH CABLE ROUTING (TOP DOWN VIEW). ..........................................................................9 FIGURE 5-4 MJ-X COMMUNICATIONS MODULE CABLE ROUTING. ...............................................................................10 FIGURE 7-1 FIBER OPTIC CONNECTIONS.......................................................................................................................13 FIGURE 7-2 RS-485 CONNECTION ................................................................................................................................13 FIGURE 7-3 SCREW TERMINAL BLOCK CONNECTOR ....................................................................................................14 FIGURE 7-4 RS-485 LOOP TOPOLOGY ..........................................................................................................................14 FIGURE 7-5 COMMUNICATION CABLE ROUTING ...........................................................................................................15 FIGURE 7-6 RS-232 MULTI-DROP CONFIGURATION .....................................................................................................16 FIGURE 7-7 RS-232 CONNECTOR PINOUT ....................................................................................................................17 FIGURE 7-8 SCREW TERMINAL CONNECTION ...............................................................................................................17 FIGURE 7-9 MJXPLORER TROUBLESHOOTING CONNECTIONS ......................................................................................20 Tables TABLE 4-1 FIBER OPTIC INTERFACE JUMPER SETTINGS..................................................................................................6 TABLE 4-2 RS-232/485 INTERFACE JUMPER SETTINGS ..................................................................................................7 TABLE 7-1 RS-485 CABLE SPECIFICATIONS .................................................................................................................13 TABLE 7-2 RS-232 INTELLIGENT ELECTRONIC DEVICE WIRING ..................................................................................16 TABLE 7-3 MODEM WIRING .........................................................................................................................................16 TABLE 7-4 COMMUNICATIONS MENU ITEMS ................................................................................................................17 MJ-4A, MJ-4B, MJ-XL, MJ-X, MJXtra, and MJXplorer are trademarks of Siemens Energy, Inc. Siemens is a registered trademark of Siemens AG. © 1994 - 2008 Siemens Energy, Inc. ii MJ-4 Communications Module 1 Introduction This manual describes the installation and connection procedures for the MJ-4ATM & MJ-4BTM (here after referred to collectively as MJ-4 TM) Communications Module which has the Fiber Optic and the RS-232/485 interfaces combined in one single printed circuit board. The operation and functionality of the Fiber Optic and the RS-232/485 interfaces are quite similar, only one of the interfaces can be used at a time. The manual covers the procedures for connecting the module to a system of networked MJ-4 Tap Changer Control Panels. 1.1 Description The Siemens MJ-4 Communications Module is the communication interface used to connect the MJ-4 Control Panel to a network of regulator controllers, control devices, and supervisory equipment. Figure 1-1 illustrates the MJ4 Communications Module. The fiber optic interface enables connection of the tap changer control panel to the supervisory equipment via multimode fiber optic cable. The RS-232/485 interface enables connection of the tap changer control panel to the supervisory equipment via electrical wire. The MJ-4 Communications Module is installed in MJ-4 Tap Changer Control Panels. This allows you to easily network the control panels and other field devices to a remote terminal unit (RTU) or other supervisory device. An adapter kit is available for mounting MJ-4 Communications Modules in MJ-X Control Panels. RS - 232 / 485 G R N T D N Communications Module POWER Watchdog Communications IN Data - + R x d T x d C T S R T S OUT Rxd Txd Figure 1-1 MJ-4 Communications Module. 1.2 LED Indicators The MJ-4 Communications Module has five LED indicators. • Power indicates the MJ-4 Communications Module is powered on. • Watchdog when blinking steadily, indicates the MJ-4 Communications Module microprocessor and software are functioning properly. • Communications indicates communications activity with this module. (The Communications Module turns on this indicator when it receives a valid message with a valid address.) • Rxd indicates the communications module is receiving data. • Txd indicates the communications module is transmitting data. 2 Transmission Methods There are two transmission mediums available for sending data to the RTU: • fiber optic • wire 1 2.1 Fiber Optic Transmission The primary benefits of fiber optic communications are its immunity to induced electrical interference and relatively low signal loss. Electrical noise cannot be induced into the cable to generate transient spikes that disrupt data communications. The Fiber Optic interface on the Communications Module uses multi-mode fiber optic cable. The electrical signals are converted to optical signals by the communication unit. The optical signals are then transmitted via the fiber optic cable to the RTU. Communications modules in the path between the transmitting communications module and the RTU act as repeaters and simply regenerate the signals and forward them to the next device, Figure 2-1. MJ-4 In MJ-4 Out In MJ- 4 Out In Out Out RTU Fiber Optic Cables In Figure 2-1 Fiber Optic Network. 2.2 Wire Transmission The advantage of wire transmission is simple installation. The MJ-4 supports two popular wire interfaces: RS-232 and RS-485. The screw terminal block connector supplied with the module can be wired for either interface. Connection to the supervisory device is typically accomplished using either a DB-9 or DB-25 connector for RS-232, while the connector used for RS-485 will vary with the application. 2.2.1 RS-232 Direct RS-232 connections are limited to a maximum distance of 50 feet, Figure 2-2. The RS-232/485 interface on the MJ-4 Communications Module supports RS-232 multi-drop configurations. The distance between devices may be extended with modems, Figure 2-3. Modem connections are either dial-up, short-haul, or radio-based. Dial-up modems are typically deployed when there is easy access to the telephone connections, while short-haul modems are useful within a facility where there is access to the wiring. Consider using a radio modem when laying cable for a land-line modem is impractical. RS-232 Cable 50 ft Max. RTU MJ- 4 MJ-4 50 Feet Figure 2-2 RS-232 Connection. RS-232 Cable 50 ft Max. RS-232 Cable 50 ft Max. RTU MJ- 4 Modem Modem Figure 2-3 Modem Connection. 2 MJ-4 Communications Module 2.2.2 RS-485 The maximum distance for RS-485 is 4000 feet, either from device to device or for an entire loop. The recommended cable for RS-485 is shielded, two twisted-pair, 22 AWG. This type of cable consists of jacketed wire that is twisted together and wrapped in a shield to prevent electromagnetic interference from affecting the data signal. A maximum of 32 devices can be connected to an RS-485 network. Typical network configurations are loop, star, and open-ended. These are shown in Figures 2-4 to 2-6. The recommended network configuration is a loop. This will ensure that all devices remain connected to the master unit in the event of a line break. If the loop configuration does not allow you to place the equipment in the desired location, connect the network open ended. If either the star or open-ended configurations are used, termination resistors must be installed at the end devices. For more information on installing RS-485 networks, refer to Section 7.2 RS-485 Twisted-pair Cable. The following characteristics determine the maximum length and data rate of an RS-485 network. Impedance: The maximum transfer of energy occurs when the cable’s terminating impedance matches the characteristic impedance of the cable. If the cable’s characteristic impedance is 120 ohms, use a 120 ohm terminating resistor. Capacitance: Wire capacitance affects the rise and fall times of a transmitted signal and, as a result, limits the signaling (baud) rate of the data. The higher the capacitance, the lower the maximum baud rate. Additionally, higher capacitance requires higher output current to drive the line. Since capacitance is proportional to wire length, it can limit the maximum cable length for a given baud rate. Cable Size: Cable size along with capacitance and DC resistance determine whether the cable is suitable for the application. A 22-gauge cable will provide a proper balance of capacitance and resistance. DC Resistance: DC resistance determines the maximum length of wire allowed for an application. The maximum length is determined by the resistance of each twisted pair along with the device termination resistance. The use of surge protectors with series resistance also contributes to loop resistance. Twisted-pair Cabling 4000 ft max. total MJ- 4 RTU MJ- 4 MJ- 4 Figure 2-4 RS-485 Configuration – Loop Network. Twisted-pair Cabling 4000 ft max. total MJ- 4 RTU MJ- 4 MJ- 4 Figure 2-5 RS-485 Configuration – Star Network. Twisted-pair Cabling 4000 ft max. total MJ- 4 RTU MJ- 4 MJ- 4 Figure 2-6 RS-485 Configuration – Open-Ended Network. 3 3 Communication Protocols The MJ-4 Control Panel is designed to be used in a network of intelligent power control devices communicating with a supervisory device or remote terminal unit (RTU). Each device on the network has a specific communications address assigned to allow messages to be directed to and from the device. Messages are transmitted from the RTU to all devices and only the device with the specified address will respond. The MJ-4 Communications Module supports the following protocols. Refer to the documents listed for details about the protocols. • Distributed Network Protocol (DNP 3.0). (See User’s Group website: www.dnp.org) • The Cooper 2200 Protocol (with or without address byte) • The 2179 Protocol ( Based on the PG&E Protocol) • MJ-3A Format “A”, “B1”, and “B2” 4 Installing the Communications Module in MJ- 4 Control Panels The MJ-4 Communications Module is mounted directly on the MJ-4 Main Processor Board. Follow these steps to install the communications module. Details are provided in the sections below. 1. Turn off power to the MJ-4. 2. If in a regulating device, then disconnect the polarized disconnect switch (PDS). 3. Remove the MJ-4 rear cover. 4. Install the communications module. 5. Set the communications module jumpers. 6. Remount the MJ-4 rear cover. 7. Install the communications module label. WARNING 120 volts on terminal block, leads, and inside control panel housing. May result in death or serious injury from electric shock including equipment damage. Disconnect all power sources before opening the control panel. 4.1 Removing the MJ-4 Rear Cover Turn off the power to the MJ-4 and remove the four screws holding the rear cover to the case, see Figure 4-1 below. Uncurl the cable clamp at the center of the rear cover and slide the cable out. 4 MJ-4 Communications Module Remove 4 Case Screws Uncurl cable-clamp and slide cable out Figure 4-1 MJ-4 Rear Cover. 4.2 Mounting the Communications Module Hold the communications module in place over the five standoffs on the main PCB and insert the 24-pin connector on the ribbon cable into the 24-pin connector (P8) on the main PCB. See Figure 4-2 below. Mount the communications module on the threaded standoffs on the main PCB using the five screws provided. 6-32 x 3/8" Screw (5) Ribbon Cable with 24-Pin Connector Comm Mod PCB 24-Pin Connector P8 P9 MJ-4Main MainPCB PCB MJ-XL Figure 4-2 Communications Module Installation. 5 4.3 Setting the Communications Module Jumpers Prior to installing the Communications Module into the MJ-4 Control Panel, ensure that the jumpers are properly installed on the printed circuit board. Jumper selections for the Fiber Optic interface and RS232/485 interface are described in separate sections below. 4.3.1 Fiber Optic Interface The jumper locations for the fiber optic interface are shown in Figure 4-3. The view of the module is from the component side. The fiber optic receiver (RX) and transmitter (TX) are shown for reference. The jumper settings are listed in Table 4-1. Set Auto Repeat to “No Repeat” when only one unit is installed in the network. J10 J12 J14 J11 2 1 1 2 3 Figure 4-3 Fiber Optic Interface Jumper Locations. Table 4-1 Fiber Optic Interface Jumper Settings Jumper Name Position Function Selected J14 Auto Repeat 1-2 Auto Repeat J12 Range 2-3 Out No Repeat No Repeat Out In Normal Long State Description Repeat message from Host and any responses from other IEDs (Auto repeat for mark 0 or mark 1) Transmit continuously ON (for testing) (Force 0) Only transmit a response if being addressed by Host (no jumper installed at 1-2 or 2-3) (Force 1) Set Low Power Transmitter Output Set High Power Transmitter Output (See Note 2) Note 1: Default pin settings are shown in bold text. Note 2: If 50/125 µm cable is used, J12 must be jumpered (In). 4.3.2 RS-232/485 Interface Figure 4-4 shows the jumper locations for the RS-232/485 interface, viewed from the component side. Jumpers and their default settings are listed in Table 4-2. 2 1 J10 1 2 3 J11 J12 J14 Figure 4-4 RS-232/485 Interface Jumper Locations. 6 MJ-4 Communications Module In an RS-485 application, connect Signal Return (RTN) between the communication devices when there is a ground potential rise between the connected devices. When the device RTN pins are connected, jumper J11 should be Out (unless required by safety codes) to prevent ground loop currents. (If it is necessary to connect the RTN to GND after the Communications Module is installed, you can make this connection at the 8-pin terminal block connector with a wire jumper.) Table 4-2 RS-232/485 Interface Jumper Settings Jumper Name J10 RS-485 RCV EN Position Function Selected 1-2 Receive Enable Auto Enable 2-3 J11 Safety Not grounded Out Ground Strap In Grounded Note: Default pin settings are shown in bold text. State Description RS-485 receiver is always enabled RS-485 receiver is automatically enabled by MJ-X Communications Module microprocessor control. Signal Return not connected to frame ground Signal Return connected to frame ground The Jumpers for the Fiber Optic and RS-232/485 interfaces are specific to their operation or functionality, i.e. J14 and J12 (Fiber Optic interface Jumpers) will not affect the working of the RS-232/485 interface and J10 and J11 (RS-232/485 Jumpers will not affect the working of the Fiber Optic interface. Though the jumpers J14 & J12 and J10 & J11 may be placed in the required operational position, only one interface can be used at a time. 4.4 Replacing the MJ-4 Rear Cover Remove the adhesive strip covering the rectangular opening for the RS-232/485 Connector, and remove the two plastic caps covering the holes for the Fiber Optic "In" and "Out" connectors. Make sure that all of the cables and wires are inside the enclosure and carefully place the rear cover over the communications module and main PCB and fasten with the four case screws. Uncurl the cable clamp and slide the cable into place. 4.5 Mounting the Communications Module Label Remove the backing from the label and place it on the rear cover. Make sure that the holes in the label are lined up with the indicator and connector holes on the rear cover. When the label is in place, rub the label to secure it in position. The rear cover with labels installed is shown in Figures 4-5 below. RS - 232 / 485 G N D Communications Module POWER Watchdog Communications IN R T N Data l - l + R x d T x d C T S R T S OUT Rxd Txd Figure 4-5 MJ-4 with MJ-4 Communications Module Label Installed. 7 5 Installing the Communications Module in MJ-X Control Panels The MJ-4 Communications Module is installed in the Accessory Section on the back of the MJ-X Control Panel. Before installing the communications module, set the jumpers on the communications module printed circuit board for proper operation. Install the communications module in the MJ-X, connect the cables, and test the unit. Once these tasks have been performed the system is ready for operation. The following sections describe how to set the jumpers and install the communications module. 5.1 Setting the Communications Module Jumpers Prior to installing the Communications Module into the MJ-X Control Panel, ensure that the jumpers are properly installed on the printed circuit board. Jumper selections for the Fiber Optic interface and RS232/485 interface are described in Section 4.3.1 and Section 4.3.2 respectively. 5.2 Mounting the Communications Module in MJ-X Control Panels Follow these steps to install the communications module in the MJ-X Control Panel. 1. If the control panel is installed on a Siemens regulating device, first turn off the power to the MJ-X, then disconnect the polarized disconnect switch (PDS) terminal block and remove the control panel from the control box. WARNING 120 volts on leads and inside control panel housing. May result in death or serious injury from electric shock including equipment damage. Disconnect all power sources before opening the control panel. 2. Loosen the PDS cable strain relief on the rear cover and rotate the strain relief plate to the open position, Figure 5-1. Accessory Cover Plate PDS Strain Relief Plate Figure 5-1 MJ-X Control Panel Rear Cover. 3. 8 Remove the six screws on the side of the rear cover that hold it to the control panel. MJ-4 Communications Module 4. Feed the PDS cable harness through the strain relief cutout while removing the rear cover. 5. Remove the accessory cover plate from the rear cover. Discard the accessory cover plate and mounting hardware. If an Expansion Rack is installed in the accessory area, remove the rack and discard. 6. Mount the communications module printed circuit board to the MJ-X base with six 6-32 x 7/16” standoffs, Figure 5-2. Ensure that the membrane switch cable is folded over itself and under the communications module printed circuit board as shown in Figure 5-3. 6-32 x 3/8" Screw ( Hexnuts (5) Cover Pan Cover Pan Cover Pan Spacers(5) Mal 6-32 x 7/16" Male/F Standoff (6) e/Fem Standoff PCB (6) PCB Threaded Studs(5) MJ-X Base MJ-X Base MJ-X Base Figure 5-2 Communications Module Installation in MJ-X. MJ-X Control Panel Processor Board Communications Module Membrane Switch Cable Figure 5-3 Membrane Switch Cable Routing (top down view). 9 7. Mount the communications module pan cover (if provided) with six 6-32 x 3/8” screws as shown in Figure 5-2. 8. Plug the ribbon connector into J105 on the MJ-X Processor Board as shown in Figure 5-4. POWER W dog Com m Connector J105 GND RTN Membrane Switch Cable Txd Rxd Data Rxd Tx d CTS RTS Processor Board Connector J411 Power Board Figure 5-4 MJ-X Communications Module Cable Routing. 9. Feed the PDS cable through the PDS strain relief opening in the rear cover. 10. Reinstall the rear cover of the control panel, attaching it using the six screws. 11. Rotate the PDS strain relief plate to the closed position and tighten the screws for the strain relief plate. 12. Follow the procedure in section 6 to test the communications module. 6 Verifying the Communications Module Installation Once the MJ-4 Communications Module is installed in the MJ-4 control panel, test the module as follows to ensure proper operation and performance. 1. Visually inspect the MJ-4 Communications Module for proper mechanical assembly and cable connections. 2. Apply power to the MJ-4 Control Panel and observe the LEDs on the communications module. The Power LED should light immediately and stay lit. After 10 to 15 seconds, the Watchdog LED should start flashing without a long pause between flashes, that is, about twice per second. If this does not occur, check for the following: 3. 10 The MJ-4 Control Panel is receiving power. Check that the front panel display is active. The communications module is installed properly. Connections between the MJ-4 and the Communications Module are correct. Disassemble, inspect, and reassemble the unit as required. After verifying that the communications module is receiving power, perform the diagnostic tests described in Section 6.1 and 6.2. MJ-4 Communications Module 6.1 Performing the Initial Diagnostic Checkout Prior to performing these tests, become familiar with operating and configuring the MJ-4 Control Panel. See the MJ-4A & MJ-4B Voltage Regulator Control Panel Installation and Operations Manual (Siemens manual no. 21115527-023). 1. On the MJ-4 Control Panel, under the < DIAGNOSTICS > menu, go to the “CM Test?:” screen. 2. Press the Change key and toggle from “OFF” to “INTERN,” and then press the Save key. (If the password is requested, enter the password as described in the note below and proceed.) The “CM Test:?” screen should display “INTERN” for several seconds before changing to “OFF.” If the display does not change to “OFF,” then check the physical installation of the communications module before proceeding. Note: When you try to change the “CM Test?:” value, the MJ-4 Control Panel may request that the password be entered. If the default passwords are in effect, then the password for the Diagnostics menu is “3333.” For more information refer to the MJ-4A & MJ-4B Installation and Operations Manual. 3. Once the “CM Test?:” screen value has returned to “OFF,” press the down arrow key to display the next data item, “CM TestStat.” This screen indicates the status of the Communications Module test. The possible test value results are shown below. A value of xxx2 (where x may be 0-9 or a-f), indicates that the test passed. A value of xxx0 or xxx1indicates a failure. (Note that in firmware versions of 2.xx (e.g., 2.13, 2.44, etc) xxx3 indicates the test passed and xxx2 indicates an internal problem.) • xxx0 indicates the test did not run at all. Run the test again, allowing extra time for the communications module to power up. This should take about 15 seconds. The Watchdog LED will blink after the module successfully completes self test and initialization. • xxx1 indicates an internal problem with the MJ-4 Communications Module. Contact Siemens for assistance. 6.2 Performing the Loopback Diagnostic Test The loopback test evaluates the MJ-4 for communications readiness. For this test, connect the transmit output to the receive input of the communications module. When testing the fiber optic interface, ensure that the cable used meets the requirements outlined in section 7.1. When testing the RS-232/485 interface, only the RS-232 portion of the circuit can be tested by connecting a wire from the transmit pin (Txd) to the receive pin (Rxd) of the screw terminal block connector. 1. Scroll to the “CM Test?:” data item in the <DIAGNOSTICS> menu on the MJ-4 Control Panel display. 2. Press the Change key, then the up arrow key to select “LOOPBK.” If the password is requested, enter the password and proceed. 3. Press the Save key. “LOOPBK” will display for several seconds before changing automatically to “OFF.” If this does not occur, then recheck the physical installation of the communications module and retry. 4. Once the “CM Test?:” screen displays “OFF,” press the down arrow key to display the “CM TestStat” data item. This screen gives the status of the communications module test. A value of xxx6 (where x may be 0-9 or a-f), indicates that the loopback test passed. A value of xxx0 – xxx5 indicates a failure. (Note that in firmware versions of 2.xx (e.g., 2.13, 2.44, etc) xxx7 indicates the test passed, xxx3 indicates failure, and xxx6 is a communication problem.) • xxx0 indicates the test did not run at all. Run the test again, allowing extra time for the communications module to power up. This should take about 15 seconds. The Watchdog LED will blink after the module successfully completes self test and initialization. • xxx1 indicates an internal problem with the MJ-4 Communications Module. Contact Siemens for assistance. • xxx2 indicates the loopback test failed. Check the loopback connectors and repeat the test. • xxx3, xxx4, or xxx5 indicate a communication problem. Contact Siemens for assistance. 11 7 Cabling the Communications Module to the Power System Connect the communications modules using the recommended cable as described in sections 7.1 to 7.3 below. The following sections provide some general guidelines for cable selection and explain the different cable parameters. Make connections between the device and the communications unit with the appropriate connector. Typically, RS-485 requires custom wiring to the other devices. Consult the device’s pin assignments to determine the applicable connections. Typically, a DB-9 or DB-25 will be needed for making RS-232 connections to the RTU, personal computer, or other device. Use the supplied Phoenix Contact Screw Terminal Block (MSTBT 2, 5/8-ST-5, 08) for connections to the RS-232/485 interface. Use an ST optical connector when making connections to the fiber optic interface. Though the cabling for the Fiber Optic and the RS-232-/485 interfaces may be done and either interface may be made available for communication, only one of the interfaces may be used at a time. 7.1 Fiber Optic Cable Type The recommended cable is 62.5/125 µm diameter fiber optic cable with a maximum attenuation of 5dB/km at a wavelength of 820-850 nm. If this is not available use 50/125 µm diameter glass cable, but only for cable lengths less than 1500 feet. Use of 50/125 µm diameter cable requires that the range jumper J12 be set for long range. This will provide protection against under driving the receiver. When using 50/125 µm cable, install the long range jumper (J12) even for very short cable lengths. A 100/140 µm diameter cable can also be used for cable lengths less than 1500 feet. Use of this cable requires that the range jumper J12 be set to normal. This setting will provide protection against overdriving the receiver. Plastic cable is not recommended due to the coupling efficiency of the cable, which at short lengths will overload the optical receiver. In addition, the large cable attenuation normally associated with plastic cable limits the useful link lengths to a fraction of that achievable with glass cable. 7.1.1 Fiber Optic Cable Lengths Calculate cable length by determining the output power of the transmitter (PTX) and the input receive level (Peak Input Power Logic Level Low Receiver Sensitivity, PRX). The difference between the two numbers is the optical power budget (PB’). PB’ = PTX – PRX For example, if transmitter output power is -16 dBm and the input receive level is -24 dBm, the optical power budget is then 8 dBm. Subtract from this value the fixed losses (i.e. connector losses, splice losses, PLoss) to obtain the real power budget (PB). PB = PB’ – PLoss Divide the result by the cable attenuation (Att) in dB/km to arrive at the maximum cable length. Note that the transmitter output power data given in the specifications already includes connector loss when using precision ceramic ST connectors. Length = PB / Att 7.1.2 Fiber Optic Connector The fiber optic cables (or “patch cords”) used with the MJ-4 Fiber Optic Communications Module must be terminated with ST style connectors and have a numerical aperture of 0.275 ± 0.015. (If pre-terminated cables are not used, follow the instructions supplied by the manufacturer to attach the connector to the fiber cable using the cable type recommended in section 7.1.) 12 MJ-4 Communications Module 7.1.3 Fiber Optic Connections When making connections to the transmitter and receiver inputs/outputs, ensure that the transmit output from one device is connected to the receive input of the next device. Figure 7-1 shows how to insert the connector. The tip of the cable on the ST connector must be clean and free of dust. Dust on the tip of the cable will cause signal attenuation. Use care when handling the fiber optic connector, especially the exposed ceramic ferrule. Figure 7-1 Fiber Optic Connections 7.2 RS-485 Twisted-pair Cable The following sections provide the information necessary to select and install cable between an MJ-4 Control Panel, RTU, and other field devices in an RS-485 network. 7.2.1 RS-485 Cable Type Listed in Table 7-1 are the cable characteristics necessary for proper electrical performance in an RS-485 communications network. Use cable with a shield that provides 100 percent RFI/EMI coverage. Table 7-1 RS-485 Cable Specifications Characteristic Impedance Capacitance (pF/ft) Cable Size DC Resistance Velocity of Propagation 7.2.2 Value 120 ohms 35 22 AWG 17 ohms/1000 ft 80% Maximum/Typical Typical Maximum Typical Maximum Maximum RS-485 Cable Grounding Ground the cable shield for all devices on the network. Ground the cable shield at only one end to prevent induced interference that may result from circulating ground currents. If a cable shield is grounded at both ends, a ground loop can exist between the components. This ground loop can cause induced interferences that result in signal distortion. If there is a ground potential rise between the connected devices, connect the Signal Return (RTN) between the communication devices. Figure 7-2 illustrates the preferred field device connection method. See section 4.3.2 for jumper considerations. MJ-4 Communications Module Data RTN GND Shield attached at this end only Shield grounded At other end only RS-485 Twisted-Pair Cable RS-485 Twisted-Pair Cable From RTU or other device To next device Figure 7-2 RS-485 Connection 13 7.2.3 RS-485 Connector The required connector for connecting to the MJ-4 RS-232/485 Interface is the Weidmuller Contact Screw Terminal Block BLT 5.08/8/180 or equivalent. Wire the connector as shown in Figure 7-2. This connector is supplied with the communications module and is shown in Figure 7-3. .3” Weidmuller Terminal Block BT 5.08/8/180 12 Gauge Wire (maximum) Figure 7-3 Screw Terminal Block Connector 7.2.4 RS-485 Cabling Considerations The cable used for connecting the Communications Module to other communication devices is a twisted pair of insulated conductors. The pair is twisted to minimize pickup of random signals between the conductors, particularly those signals induced by electromagnetic interference (EMI). To further protect against external electrical interference, the pair is shielded by a grounded outer covering. The shield conducts radio frequency interference (RFI) to the ground, thus reducing its effect on the twisted pair. Concern over RFI and EMI is important given the high electrical current and electrically noisy environment through which the communication wires are routed. Follow the rules below to properly install the RS-485 cables. 1. Connect all field devices in a loop technology so that all devices are connected to the master in case of a line break. The basic loop topology is shown below. MJ- 4 RTU Twisted-pair Cabling 4000 ft max. total MJ- 4 MJ- 4 Figure 7-4 RS-485 Loop Topology One of the advantages of the loop topology is that if a line is cut, communication is not interrupted. By completing the loop in the RS-485 cable, one break can be made anywhere in the line without compromising communication with the master device (RTU). To maintain redundancy, avoid open ended runs of the bus. Each installation method (see Figures 2-4 to 2-6) has advantages and disadvantages. The loop method requires more cable than does the single-ended run method. This extra cable is needed to run from the last device on the run to the master device (RTU). The additional cable adds expense and shortens the total distance the farthest device can be located from the master device. The advantage of the loop method is in the ability to communicate with all devices when there is a break in the loop. The single-ended run allows larger distances between the master device and the farthest slave device, but it does not allow the master device to communicate with devices on the far side of a break. This method also requires the use of terminating resistors. 2. A maximum of 32 devices may be connected in a single RS-485 bus with a total cable run no longer than 4000 feet. 3. Always ground the shield at only one end of a cable segment. For all devices, ground the cable shield at one end only to prevent induced interference that may result from circulating ground currents. If a cable’s shield is grounded at both ends, a ground lop can exist between the components. This ground loop can result in induced interference that causes signal distortion. Figure 7-2 shows the proper method for terminating the shield at the Communications Module connector. 14 MJ-4 Communications Module 4. When the Communications Module is mounted in the MJ-4 Control Panel, it is grounded internally through the MJ-4 to the equipment ground. A separate connection to the equipment ground is not required. 5. The recommended twisted-pair cable for an RS-485 bus has a characteristic impedance of 120 ohms. Any change in the type of cable, or an open-ended length of cable, creates a discontinuity in the impedance and causes a reflection. Placing resistors that match the characteristic impedance of the cable at the open end of a twisted-pair stub eliminates reflection. For long, single-ended runs (over 1000 Forwarding ft.), you may need to install a 120 ohm terminating resistor between the data (+) and (-) terminals of the farthest device from the RTU or master end. Adding the terminating resistor is not an absolute requirement, but using it minimizes reflected interference on the communication cable. 6. Do not route signal cabling parallel to power conductors. Wherever possible, place the communication cable perpendicular to the power conductor as shown below. Power conductors are any cables or bus conductors carrying currents greater than 20 amperes. Magnetic Field Around Conductor Current Flow Electric Power Conductor Communication Cable Figure 7-5 Communication Cable Routing Electrical current flowing through a conductor forms a magnetic field around the wire as shown above. Interference is coupled into the wires in the cable through electromagnetic fields. Just as current through a wire causes a magnetic field to form around it, a magnetic field can cause current to flow in a wire. This induction of current is a function of the geometry or orientation of the wires. If the communication cable is at a right angle with the power conductor, it is aligned with the direction of the magnetic field and no current is induced. 7. 7.3 Follow these guidelines when you route communications cables between electrical equipment: • Run communications cables in the same cable raceways (cable routes, cable trays, or cable gutters) as unshielded digital and analog signal cables up to 60 V. • Run communications cables in the same cable raceway with shielded signal and supply cables up to 230 V. • Run communications cables 4 inches away from unshielded signal and supply cables of up to 230 V. • Run cables with voltages greater than 230 V in separate ducts (routes, conduits). RS-232 Connections The following section describes the connection requirements for RS-232 cable. This cable will allow you to connect the MJ-4 Control Panel to an RTU or personal computer. Five of the standard RS-232 wires are used for this application. • Signal Return (RTN) • RXD • TXD • CTS • RTS 15 Table 7-2 lists the connections that must be made to connect the RS232/485 interface to a personal computer, RTU, or other supervisory device. The MJ-4 Communications Module defaults to no-handshaking-required mode. However, the communications module asserts RTS while it transmits data, but the module will ignore the CTS input signal. Table 7-2 RS-232 Intelligent Electronic Device Wiring MJ-4 RS-232/485 Communications Interface RTN RXD TXD Personal computer, supervisory device, or other network device Signal Ground TXD RXD Table 7-3 lists the connections that must be made to connect the RS232/485 interface to a modem. Table 7-3 Modem Wiring MJ-4 RS-232/485 Communications Interface RTN RXD TXD RTS CTS Modem Signal Return RXD TXD RTS CTS “RXD” is an input for Data Terminal Equipment (DTE) and an output for Data Communications Equipment (DCE). “TXD” is an output for the DTE and an input for the DCE. Personal computer serial ports are configured as DTE and the modems are configured as DCE. The communications module RS-232 connections implement DTE. 7.3.1 RS-232 Multi-drop Wiring Multi-drop configurations require that the respective pins of the DTE devices be connected in parallel, Figure 7-6. The standard pin assignments for RS-232 connectors are shown in Figure 7-7. Note: For Figure 7-6, the RTU port is wired as “DTE”. When networking devices together, make sure the RTU “data out” connects to the communications module Rxd, and the RTU “data in” connects to the communications module Txd. RTU MJ-4 MJ-4 MJ-4 Signal Return Signal Return Signal Return Signal Return TX RX RX RX RX TX TX TX Figure 7-6 RS-232 Multi-drop Configuration 16 MJ-4 Communications Module DE9 1 5 6 9 Pin 1 2 3 4 5 6 7 8 9 * Signal DCD Rxd Txd DTR Ground (Signal) DSR RTS CTS RI Shell (Frame Ground) DB25 1 13 14 25 * For Shielded Cable Connectors Pin 1 2 3 4 5 6 7 8 20 22 * Signal Ground (Frame) Txd Rxd RTS CTS DSR Ground (Signal) DCD DTR RI Shell (Frame Ground) Figure 7-7 RS-232 Connector Pinout 7.4 RS-232/485 Connections RTS CTS Txd Rxd Data RTN GND The screw terminal block connector is keyed for proper insertion. Figure 7-8 shows the proper connector orientation. Align the keys and insert the connector to interface to the RS-232/485 interface. Figure 7-8 Screw Terminal Connection 7.5 Communications Module Configuration Prior to using the MJ-4 Communications Module in the network, the communications module needs to be configured properly for communications. The < COMMUNICATIONS > menu of the MJ-4 Control Panel provides all the required communications configuration items for the communications module. Table 7-4 lists the communications menu items in the order in which they appear on the MJ-4 Control Panel; default settings are in bold. 1. Program the communications parameters of the MJ-4 Communications Module by pressing the Menu key twice to display the < METER > menu. 2. Then press the left arrow key until the < COMMUNICATIONS > menu appears. Use the up and down arrow keys to access the individual menu items. 3. To change the value of the parameter, press the Change key, and then use the arrow keys to toggle the choices or set the value for the parameter. Press the Save key after changing the value of a menu item to enter the changes, or press the Cancel Reset key to cancel the change. Each time a configuration menu item is changed, the communications module is reset by the main MJ-4 Control Panel. This reset is part of the process of updating the communications module with the new configuration. Table 7-4 Communications Menu Items Menu Item Data Stat = XXXXX DatPortBaud Data Parity DataPortAddr Reg Id Description Data Port status Selections Not Applicable (This is a Status Item) Data Port baud (in bits/second) Data Port parity Data Port address enable Regulator Identification 300, 1200, 2400, 4800, 9600, 19200 None, Even OFF, ON 0 - 32,766 17 Protocol Communications Module protocol Comm Baud Communications Module baud (transmission rate) Communications Module parity Communications Module address Communications Module resync time (in characters) Communications Module Transmit Enable Delay (in milliseconds) Confirm DNP Data Link Enable software auto-repeat in Comm Module Host Address of RTU for unsolicited responses Comm Module can send unsolicited response Require Auto Inhibit to be active before a remote raise or lower request is acknowledged Choose to set up your own DNP points or use a preconfigured set Comm Parity Comm Addr Resync Time Tx En Delay DNP dl Confirm CM SW Repeat En Host Addr CM Unsolicited AutoInhEnRemRL DNPset CM Vers Communications Module software version DNP3.0, 2200, 2200NOA, MJ3A A, MJ3A B1, MJ3A B2, 2179, 2179 MJX, 2179 5A, SPECIAL 300, 1200, 2400, 4800, 9600, 19200 None, Odd, Even 0 – 65,535 0-250 0-250 No, Yes No, Yes 0 – 65,535 No, Yes No, Yes DNPcfg, 2.x4, 2.x3, small2.x3, Simple, Metering, Active, set7, set8, set9, set10, set11, set12, set13, set14, set15 X.XX 7.5.1 Communications Menu Item Descriptions Data Stat, DatPortBaud, Data Parity, and DataPortAddr These menu items apply only to the Data Port located on the front of the MJ-4 Control Panel, and do not require modification. Reg Id (Regulator Identification) This item allows you to uniquely identify each regulator in the system. The Regulator Id is accessible as a data item via the communications module for most of the protocol selections. Protocol This item defines the protocol selection for the MJ-4 Communications Module. The selections are listed in Table 7-4. 2200NOA is a variation of the 2200 protocol with the address field suppressed. It is provided for testing the MJ-4 Communications Module with the MJXplorer™ software. The SPECIAL item allows a new protocol handler to be included in the Communications Module code without forcing a modification to the Main Processor code (for the protocol selection front panel screen). Comm Baud This menu item defines the data rate for the MJ-4 Communications Module. The standard asynchronous communications data rates are available for selection. For proper communications, the Comm Baud setting must match the baud setting of the other communicating device(s) in the network. Comm Parity This configuration item defines the parity selection for the communications module. For proper communications, the Comm Parity setting must match the parity setting of the other communicating device(s) in the system. 18 MJ-4 Communications Module This parity selection will override any default or inherent parity defined in the selected protocol. [For example, the 2200 protocol specification document defines the parity as even. The Comm Parity configuration item allows even parity to be selected, but it also permits the system designer/installer to use an alternate parity selection if desired.] Comm Address This configuration item defines the communications address for the communications module. Each device connected on the communications link must have a unique communications address. The Comm Address setting must correspond with the address programmed into the RTU or other supervisory device so that it can request information from and write data to a particular MJ-4 Control Panel. Resync Time This configuration item defines the Communications Module resync time (in characters). This item is used for Communications Module protocols 2200 and 2179 to determine when one message ends and another message begins. If a new character is not received within the period specified by this parameter, the control panel assumes that the next received character is the start of a new message. Tx En Delay This configuration item defines the Communications Module Transmit Enable Delay (in milliseconds), specifies the amount of time between the RTS output being activated and the start of transmit (output) data. DNP dl Confirm This configuration item defines whether or not to request confirmation from the master station for all responses for the DNP3.0 protocol CM SW RepeatEn This configuration item controls whether software repeat is used for the MJ3A A, B1, and B2 protocols. Host Addr This configuration item defines the communications address for the RTU or other supervisory device to which unsolicited responses are sent. CM Unsolicited This configuration item defines whether or not the communications module should send unsolicited responses. Note that if this parameter is “Y”, an “enable unsolicited responses” message must also be sent from the master station to start them. AutoInhEnRemRL This configuration item controls whether the auto inhibit must be active before a remote raise or lower request will be followed. Setting “Y” prevents accidental fighting against the automatic tap changes with remote commands. DNPset This configuration item selects what DNP points will be used. Choose “DNPcfg” to configure your own points with the DNP Configure program or choose from the preconfigured DNP point sets. See Section 8. 7.6 Troubleshooting Communications Problems This section explains how to troubleshoot the MJ-4 Communications Module using the front panel LED indicators and the MJXplorer software. The MJXplorer software allows you to access the communications module parameters via the MJ-4 Control Panel. 19 7.6.1 Using LEDs to Help Diagnose Communications Problems The communications module’s Txd and Rxd LEDs can be useful indicators to help isolate system communications problems. The LEDs are directly activated by the transmit and receive signals and provide an immediate indication of line activity. If the Rxd LED is not illuminated, then no receive signal activity is being detected at the communications module Terminal Block connector. If the Txd LED is not illuminated but the Rxd LED is illuminated, then the communications module is not responding to communication attempts. This may occur for a variety of reasons, including: 1) the communications module and/or MJ-4 Control Panel has not been configured properly, and 2) the unit is not being addressed. If the Comm LED is not illuminated, then the communications module is not being addressed. If the Rxd LED is illuminated but the Comm LED is not illuminated, this indicates that the module is receiving the transmission but does not detect its address in the message. Recheck the communications address, because it may not be set properly. Verify that the MJ-4 communications configuration items have been set to match the system settings. (See section 7.5, Communications Module Configuration.) 7.6.2 Using MJXplorer to Troubleshoot Communications Problems The MJXplorer software is a menu-driven application program that allows interfacing to the MJ-4 Communications Module. Up to three MJ-4 units may be connected at a time. When connecting the Fiber Optic interface to MJXplorer, the auto repeat function must match the setting in the ConfigureÆConfigure MJXplorer menu. See section 4.3.1 for setting the Fiber Optic interface jumpers. A Fiber Optic to RS-232 driver/receiver is required in order to perform these tests on the fiber optic interface. The driver/receiver is an optical to electrical signal converter with an ST connector interface and an RS-232 interface. Connect the optical side to the fiber optic interface via ST fiber optic patch cords. Connect the RS-232 interface to the personal computer, Figure 7-9. Use MJXplorer to help pinpoint communications problems in a system. MJXplorer permits testing of the MJ-4 communications functions independent of other system components. Once the physical connections are complete, from the MJ-4 front panel select the “2200NOA” protocol for connecting to only one panel or select “2200” protocol and set comm addresses for connections to multiple panels. In addition, match the Comm Parity and Comm Baud with the MJXplorer settings. Use MJXplorer to verify that data can be retrieved from as well as written to the MJ-4 Control Panel. MJ-4 Fiber Optic Interface In Out RS-232 DB9 2 3 4 5 6 7 RS-232 DB9 2 3 7 RS-232 DB9 to Fiber Optic oTx / oRx oTx oRx 8 Personal Computer Running MJXplorer Power Supply MJ-4 RS-232/485 Interface RS-232 DB9 Txd Rxd RTN 2 3 4 5 6 7 8 Personal Computer Running MJXplorer Figure 7-9 MJXplorer Troubleshooting Connections 20 MJ-4 Communications Module 8 Setting the DNP points This section describes how to set the DNP points that will be used on the control panel, You can use the DNP Configure program to customize your DNP point set or you can use one of the predefined point sets listed in section 8.2. In order to use a customized point set, an MJ-XL must have version 3.06 and the MJ-X must have 2.52. In order to use predefined point sets (except Set 7), an MJ-XL must have version 3.07 and a MJ-X must have 2.53. Set 7 is only available on the MJ-4 Control. It is recommended that a Latching Relay command be used for all Binary Outputs (e.g., remote raise/lower, auto inhibit, etc.). 8.1 Using the DNP Configure program for a custom DNP point set The DNP Configure program is used to place a custom set of user-defined DNP points on the control panel. You can obtain this program free-of-charge from your Siemens representative. After installing the program, run it and follow the steps below to set your DNP points. 1. Connect your computer’s com port to the panel’s Data Port with a “straight-thru” male-female DB9 cable. 2. If you already have a DNP points profile, open it and go to Step 8. To open an existing points profile, in the menu bar: click File Æ Open and select your file. Otherwise go to Step 3 to create a points profile. 3. Click the Class 0 button. Move between the tabs and checkmark the points you want. Click OK. 4. If Class 1, 2, or 3 polls are desired, these can now be set the same way. 5. Click the Send button. Drag and drop the points up and down in the list boxes to change their point number if desired. The top point in each box is point # 0, the point below that is point # 1, etc. Click the Cancel button after points are ordered as desired. 6. In the menu bar: click File Æ Save and save your file as XXXX.dnp 7. Click the Setting button. 8. Match the baud rate and parity between the computer and the panel. Choose the COM port your computer is using. Set Addressing to be Disabled (if MJ-4’s “DataPortAddr” setting is OFF). Click OK. 9. Click the Send button. 10. Click the Send button on the bottom of the points list screen. 11. If successful, a window will pop up displaying “Send Communication Status: OK…” Click OK. 12. DNP Configure can be closed or you can use the same point set to configure other panels. 8.2 8.2.1 Selecting a predefined DNP point set DNP point set for MJ-4A or MJ-4B When the MJ-4 Communications Module with firmware version 3.10 (initial release) or higher is interfaced with a MJ-4A or MJ-4B, you will be able to choose from a number of DNP point sets, including Set 7. Sets 8 through 15 are not defined at this time. 8.2.2 DNP Point set for other Control Panels The MJ-4 Communications Module may be used with the MJ-XL or MJ-X control panels, but the DNP sets available may be limited. The operation and functionality of the MJ-4 Communications Module is similar to older versions of the Communications Module though either the Fiber Optic or the RS-232/485 interfaces may be used at a time. If the control panel is an MJ-XL with firmware version 3.07 or higher (or an MJ-X with version 2.53 or 21 higher) and the Communications Module has firmware 3.07 or higher, you will be able to use predefined DNP point sets. Go to the <COMMUNICATIONS> menu and scroll to “DNPset.” The complete list of points for each set is listed below. Two of the most popular point sets are 2.x4 set and 2.x3 set. 2.x4 is backwards compatible with versions 2.04, 2.14, 2.44, etc. Likewise, 2.x3 is backwards compatible with 2.03, 2.13, 2.43, etc. For more information about the DNP3.0 Level 2 implementation, please contact your Siemens representative. 8.2.3 2.x4 Binary Inputs Point # Description 0 Tap Pos Known 1 Power Flow Direction 2 Auto Inhibit Status 3 Remote Control occurring 4 Neutral (U12) Signal 5 VRC1 contacts 6 VRC2 contacts 7 Remote Switch position 8 Manual Switch position Binary Outputs Point # Description 0 Tap Raise 1 Tap Lower 2 Auto Inhibit (Latch On/Off) Analog Inputs Point # Description 0 R/A/M switch position 1 Power Flow Direction Indicator 2 VRC contacts status 3 Tap Position 4 Load Current 5 Load Voltage 6 KW 7 Power Factor 8 KW Fwd Dmd 9 KW Rev Dmd 10 Vld Total Harm Distortion % 11 Ild Total Harm Distortion % 12 Vs Total Harm Distortion % 13 VRC Status 14 VLC Status 15 Band Status Indicators 16 Tap Control Mode 17 Op Count Last Month 18 Op Count Last 24 hrs 19 Op Count Last 30 days 20 Op Count Month-to-Date 21 Load Voltage Inst Fwd Min 22 Load Voltage Inst Fwd Max 23 Load Voltage Inst Rev Min 24 Load Voltage Inst Rev Max 25 Tap Position Min 26 Tap Position Max Analog Outputs Point # Description 0 Upper Voltage Limit 22 MJ-4 Communications Module 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 8.2.4 Lower Voltage Limit Local Voltage Reduction % VRC Stage1 VRC Stage2 VRC Stage3 Auto VRC1 %I Auto VRC2 %I Auto VRC set1 Auto VRC set2 Rev Bandwidth Setting Rev Reactive Compensation Rev Resistive Compensation Rev Voltage Level Rev Time Delay Fwd Bandwidth Setting Fwd Reactive Compensation Fwd Resistive Compensation Fwd Voltage Level Fwd Time Delay Voltage Limit Control Enable Voltage Reduction Control Mode Log Setup Alert Status part 1 Alert Status part 2 Small 2.x3 Binary Inputs Point # Description 0 Tap Pos Known 1 Power Flow Direction 2 Auto Inhibit Status 3 Raise (J) Motor Signal 4 Lower (K) Motor Signal 5 Remote Control occurring 6 U2/P2 Switch Position 7 Neutral (U12) Signal 8 Operations Count (U10) Signal 9 Auto Inhibit Terminal Block Input 10 VRC1 contacts 11 VRC2 contacts 12 Remote Switch position 13 Manual Switch position 14 Auto Inhibit Out Status Binary Outputs Point # Description 0 Tap Raise 1 Tap Lower 2 Auto Inhibit (Latch On/Off) Analog Inputs Point # Description 0 Op Count Last Year 1 N/A 2 R/A/M switch position 3 Power Flow Direction Indicator 4 VRC contacts status 23 5 6 7 8 9 10 11 12 13 14 15 Band, VRC, VLC status Tap Position Load Current Load Voltage Load Voltage (primary) Source Voltage Source Voltage (primary) KVA KVAR KW Power Factor Analog Outputs Point # Description 0 Op Count Total 8.2.5 Simple Binary Inputs Point # Description 0 Auto Inhibit Status 1 Remote Switch position 2 Manual Switch position Binary Outputs Point # Description 0 Tap Raise 1 Tap Lower 2 Auto Inhibit (On/Off) Analog Inputs Point # Description 0 Tap Position 1 Load Voltage 2 Load Current 3 Source Voltage Analog Outputs No Analog Outputs in the Simple set currently. 8.2.6 Metering Binary Inputs Point # 0 1 2 3 4 5 6 7 8 9 10 11 24 Description LOW Voltage Limiting, [1=On] HIGH Voltage Limiting, [1=On] Automatic Operation, [1=Inhibited] Power Flow Direction, [0=Fwd, 1=Rev] R/A/M Switch, [0=Off/Manual, 1=Auto/Remote] Voltage Reduction Input 1, [0=Open, 1=Closed] Voltage Reduction Input 2, [0=Open, 1=Closed] Supervisory Switch, [0=Off, 1=On (Remote)] Neutral Position Status, [0=inactive, 1=active] Low Battery Status, [0=inactive, 1=active] Raise Limit Reached, [0=inactive, 1=active] Lower Limit Reached, [0=inactive, 1=active] MJ-4 Communications Module Binary Outputs Point # Description 0 Control Raise (1=raise) 1 Control Lower (1=lower) 2 Remote Auto/Manual (1=block) 3 Fwd Voltage Level (+/-.1V) (0=dec, 1=inc) 4 Bandwidth Voltage (+/-.1V) (0=dec, 1=inc) 5 Fwd Time Delay (+/- 5s) (0=dec, 1=inc) 6 Fwd Reactive Comp (+/- 1V) (0=dec, 1=inc) 7 Local Voltage Reduct (1=Active) 8 Remote Volt Reduct (1=Active) 9 Local Volt Reduct % (+/-.5V) (0=dec, 1=inc) 10 Remote Volt Red. % (+/-.5V) (0=dec, 1=inc) 11 Fwd Resistive Comp (+/- 1V) (0=dec, 1=inc) 12 Reset Demands & min/max (AI 20-26) 13 Reset Energies (AI 27-28) Analog Inputs Point # Description 0 Operations Counter (100's) 1 Operations Counter (10's and 1's) 2 kVA Load 3 kW Load 4 Hardware Status (0=All Good) 5 Primary Load Current in Amps 6 Secondary Load Voltage 7 Primary Load Voltage 8 Primary Source Voltage 9 kVAR Load 10 Power Factor 11 Compensated Voltage (Sec.) 12 % Voltage Reduction in Effect 13 Tap Position 14 Voltage Reduction Status 15 Voltage Limit Status 16 Tap Control Mode Status 17 R/A/M switch position 18 Load Voltage Harmonics % 19 Load Current Harmonics % 20 Fwd Voltage Level Setting 21 Fwd Bandwidth Setting 22 Fwd Time Delay Setting 23 Fwd Reactive Compensation 24 Local Voltage Reduction % 25 Remote Voltage Reduction % 26 Fwd Resistive Compensation 27 Load Current Demand (fwd. max.) 28 KVAR Load Demand (fwd. min.) 29 KVAR Load Demand (fwd. max.) 30 KW Load Demand (fwd. max.) 31 Load Voltage Inst. Fwd. Min 32 Load Voltage Inst. Fwd. Max 33 Load Current Inst. Fwd. Max 34 KWHR Forward (0-999) 35 MWHR Forward (0-999) 25 Analog Outputs Point # Description 0 Fwd Voltage Level 1 Fwd Bandwidth 2 Fwd Time Delay 3 Fwd Reactive Compensation 4 Local Voltage Reduction % 5 VRC Stage2 6 Fwd Resistive Compensation 8.2.7 Active Binary Inputs Point # Description 0 Tap Pos Known 1 Power Flow Direction 2 Auto Inhibit Status 3 Neutral (U12) Signal 4 Remote Switch position 5 Manual Switch position Binary Outputs Point # Description 0 Tap Raise 1 Tap Lower 2 Auto Inhibit (Latch On/Off) 3 Active Auto Inhibit Analog Inputs Point # Description 0 Tap Position 1 Load Current 2 Load Voltage 3 KVAR 4 KW 5 Power Factor 6 Band Status Indicators 7 Tap Control Mode 8 Op Count Elapsed 9 CM firmware version Analog Outputs Point # Description 0 Fwd Bandwidth 1 Fwd Voltage Level 2 Fwd Time Delay 3 Fwd Resistive Compensation 4 Fwd Reactive Compensation 5 Active Bandwidth 6 Active Voltage Level 7 Active Time Delay 8 Active Resistive Compensation 9 Active Reactive Compensation 10 Active Timer (mins) 26 MJ-4 Communications Module 8.2.8 Set 7 Binary Inputs Point # Description 0 Tap Raise 1 Tap Lower 2 Auto Inhibit (On/Off) Binary Outputs Point # Description 0 Auto Inhibit Status 1 Remote Switch position 2 Manual Switch position 3 Neutral (U12) Signal 4 Power Flow Direction Analog Inputs Point # Description 0 Tap Position 1 Load Voltage 2 Load Current 3 Source Voltage 4 kW Load 5 kVA Load 6 kVAR Load 7 Op Count Last Month 8 Op Count Month-to-Date 9 Maintain Records of Contacts 10 Tap Changer Type 11 Balance Winding 12 Range of Regulation 13 Lower Led Solid/Blink 14 U2-P2 Terminal Out 15 Fixed RL On time 16 Log Min Max 17 PT Calc Enable Analog Outputs Point # Description 0 Fwd Voltage Level 1 Fwd Bandwidth 2 Fwd Time Delay 3 Clear Contact Statuses and Op Counters 4 Read Overall Status of Contacts 8.2.9 2.x3 Binary Inputs Point # 0 1 2 3 4 5 6 7 8 9 Scale Factor SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 Description Tap Pos Known Power Flow Direction Auto Inhibit Status Raise (J) Motor Signal Lower (K) Motor Signal Remote Control occurring U2/P2 Switch Position Neutral (U12) Signal Operations Count (U10) Signal Auto Inhibit Terminal Block Input 27 10 11 12 13 14 Binary Outputs Point # 0 1 2 Analog Inputs Point # 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 28 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 VRC1 contacts VRC2 contacts Remote Switch position Manual Switch position Auto Inhibit Out Status Scale Factor SF = 1 SF = 1 SF = 1 Description Tap Raise Tap Lower Auto Inhibit (Latch On/Off) Scale Factor Description Op Count Last Year N/A R/A/M switch position Power Flow Direction Indicator VRC contacts status Band, VRC, VLC status Tap Position Load Current Load Voltage Load Voltage (primary) Source Voltage Source Voltage (primary) KVA KVAR KW Power Factor P2 Ratio Ld Current Dmd (Fwd Present) kVA Dmd (Fwd Present) kVAR Dmd (Fwd Present) kW Dmd (Fwd Present) Load Volts Dmd (Fwd Present) CompVolts Dmd (Fwd Present) Load I Dmd (Rev Present) (Amps) kVA Load Dmd (Rev Present) kVAR Load Dmd (Rev Present) kW Load Dmd (Rev Present) Load Volts Dmd (Rev Present) (Volts) Comp Volts Dmd (Rev Present) Max % Boost or Min % Buck (%) Max % Buck or Min % Boost (%) Motor Voltage Vsrc Fwd Dmd Vsrc Rev Dmd Vload dc offset Vload fundamental, RMS Vload 2nd harmonic, RMS Vload 3rd harmonic, RMS Vload 4th harmonic, RMS Vload 5th harmonic, RMS Vload 6th harmonic, RMS Vload 7th harmonic, RMS Vload 8th harmonic, RMS Vload 9th harmonic, RMS Vload 10th harmonic, RMS SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF= 10 SF= 0.1 SF= 10 SF= 0.1 SF = 1 SF = 1 SF = 1 SF= 100 SF = 10 variable SF = 1 SF = 1 SF = 1 SF= 10 SF= 10 variable SF = 1 SF = 1 SF = 1 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 MJ-4 Communications Module 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 Vload 11th harmonic, RMS Vload 12th harmonic, RMS Vload 13th harmonic, RMS Vload 14th harmonic, RMS Vload 15th harmonic, RMS Vload 16th harmonic, RMS Vload 17th harmonic, RMS Vload 18th harmonic, RMS Vload 19th harmonic, RMS Vload 20th harmonic, RMS Vload 21st harmonic, RMS Vload 22nd harmonic, RMS Vload 23rd harmonic, RMS Vload 24th harmonic, RMS Vload 25th harmonic, RMS Vload 26th harmonic, RMS Vload 27th harmonic, RMS Vload 28th harmonic, RMS Vload 29th harmonic, RMS Vload 30th harmonic, RMS Vload 31st harmonic, RMS Iload dc offset Iload fundamental, RMS Iload 2nd harmonic, RMS Iload 3rd harmonic, RMS Iload 4th harmonic, RMS Iload 5th harmonic, RMS Iload 6th harmonic, RMS Iload 7th harmonic, RMS Iload 8th harmonic, RMS Iload 9th harmonic, RMS Iload 10th harmonic, RMS Iload 11th harmonic, RMS Iload 12th harmonic, RMS Iload 13th harmonic, RMS Iload 14th harmonic, RMS Iload 15th harmonic, RMS Iload 16th harmonic, RMS Iload 17th harmonic, RMS Iload 18th harmonic, RMS Iload 19th harmonic, RMS Iload 20th harmonic, RMS Iload 21st harmonic, RMS Iload 22nd harmonic, RMS Iload 23rd harmonic, RMS Iload 24th harmonic, RMS Iload 25th harmonic, RMS Iload 26th harmonic, RMS Iload 27th harmonic, RMS Iload 28th harmonic, RMS Iload 29th harmonic, RMS Iload 30th harmonic, RMS Iload 31st harmonic, RMS Vsource dc offset Vsource fundamental, RMS Vsource 2nd harmonic, RMS Vsource 3rd harmonic, RMS Vsource 4th harmonic, RMS Vsource 5th harmonic, RMS 29 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 30 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF= 10 SF = 1 SF = 1 SF=10 SF=10 SF=10 SF=10 SF = 1 SF=1000 SF = 10 SF=1000 SF = 10 SF=1000 SF = 10 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 Vsource 6th harmonic, RMS Vsource 7th harmonic, RMS Vsource 8th harmonic, RMS Vsource 9th harmonic, RMS Vsource 10th harmonic, RMS Vsource 11th harmonic, RMS Vsource 12th harmonic, RMS Vsource 13th harmonic, RMS Vsource 14th harmonic, RMS Vsource 15th harmonic, RMS Vsource 16th harmonic, RMS Vsource 17th harmonic, RMS Vsource 18th harmonic, RMS Vsource 19th harmonic, RMS Vsource 20th harmonic, RMS Vsource 21st harmonic, RMS Vsource 22nd harmonic, RMS Vsource 23rd harmonic, RMS Vsource 24th harmonic, RMS Vsource 25th harmonic, RMS Vsource 26th harmonic, RMS Vsource 27th harmonic, RMS Vsource 28th harmonic, RMS Vsource 29th harmonic, RMS Vsource 30th harmonic, RMS Vsource 31st harmonic, RMS MJ-X Main Proc. SW Version Number of Resets Compensated Voltage (Secondary) Line Frequency Percent Regulation % Voltage Reduction in Effect Number of Interval Logs Stored Vld Total Harm. Distortion (%) Vload Harmonics RMS value Iload Total Harm. Distortion (%) Iload Harmonics RMS value Vsrc Total Harm. Distortion (%) Vsource Harmonics RMS value VRC Status VLC Status Auto Tap Command Status Band Status Tap Control Mode Status R/A/M switch position Alert Status Time period for Interval Log (minutes) Number of Event Logs Stored MJX Reset Status Register Diagnostics Results Register 1 Diagnostics Results Register 2 Previous Month Ops Count MP Board Hardware version Power Board HW version MP HC16 Mask version Elapsed Operations Count Year-To-Date Ops Count KWHR Forward KVARHR fwd lead MJ-4 Communications Module 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 100 SF = 100 SF = 100 SF = 100 variable variable SF =1 SF =1 SF =1 SF =1 SF =1 SF =1 SF = 10 SF = 10 SF = 10 SF = 10 variable variable SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 SF = 10 variable variable variable variable SF = 100 SF = 100 SF = 1 SF = 1 KVARHR fwd lag KWHR Reverse KVARHR rev lead KVARHR rev lag Operations Count for last 24 hours Operations Count for last 30 days Month-To-Date Operations Count PF at Min. kVA Dmd (Fwd) PF at Max. kVA Dmd (Fwd) PF at Min. kVA Dmd (Rev) PF at Max. kVA Dmd (Rev) Load Current Dmd (Fwd Min) (Amps) Load Current Dmd (Fwd Max) (Amps) kVA Load Dmd (Fwd Min) kVA Load Dmd (Fwd Max) kVAR Load Dmd (Fwd Min) kVAR Load Dmd (Fwd Max) kW Load Dmd (Fwd Min) kW Load Dmd (Fwd Max) Load Voltage Dmd (Fwd Min) Load Voltage Dmd (Fwd Max) Comp Voltage Dmd (Fwd Min) (Volts) Comp Voltage Dmd (Fwd Max) (Volts) Load Current Dmd (Rev Min) (Amps) Load Current Dmd (Rev Max) (Amps) kVA Load Dmd (Rev Min) kVA Load Dmd (Rev Max) kVAR Load Dmd (Rev Min) kVAR Load Dmd (Rev Max) kW Load Dmd (Rev Min) kW Load Dmd (Rev Max) Load Voltage Dmd (Rev Min) (Volts) Load Voltage Dmd (Rev Max) (Volts) Comp. Voltage Dmd (Rev Min) (Volts) Comp. Voltage Dmd (Rev Max) (Volts) Vsrc Dmd (Fwd Min) Vsrc Dmd (Fwd Max) Vsrc Dmd (Rev Min) Vsrc Dmd (Rev Max) Load Voltage Inst. Fwd Min Load Voltage Inst. Fwd Max Load Voltage Inst. Rev Min Load Voltage Inst. Rev Max Source Voltage Inst. Fwd Source Voltage Inst. Fwd Max Source Voltage Inst. Rev Min Source Voltage Inst. Rev Max Comp Volts Inst. Fwd Min Comp Volts Inst. Fwd Max Comp Volts Inst. Rev Min Comp Volts Inst. Rev Max Load Current Inst. Fwd Min (Amps) Load Current Inst. Fwd Max (Amps) Load Current Inst. Rev Min (Amps) Load Current Inst. Rev Max (Amps) PF Inst. Fwd Min PF Inst. Fwd Max KVA Inst. Fwd Min KVA Inst. Fwd Max 31 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 10 SF = 10 SF = 1 SF = 1 SF =1 SF = 1 SF = 1 SF =1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 Analog Outputs Point # Scale Factor 0 SF = 1 1 SF = 1 2 SF = 1 3 SF = 1 4 SF = 1 5 SF = 1 6 SF = 1 7 SF = 1 8 SF = 1 9 SF = 1 10 SF = 1 11 SF = 1 12 SF = 1 13 SF = 1 14 SF = 1 15 variable 16 SF = 1 17 SF = 10 18 SF = 10 19 SF = 10 20 SF = 10 21 SF = 10 22 SF = 10 23 SF = 1 24 SF = 1 32 KVA Inst. Rev Min KVA Inst. Rev Max KW Inst. Fwd Min KW Inst. Fwd Max KW Inst. Rev Min KW Inst. Rev Max KVAR Inst. Fwd Min KVAR Inst. Fwd Max KVAR Inst. Rev Min KVAR Inst. Rev Max Frequency Inst. Fwd Min (Hz) Frequency Inst. Fwd Max (Hz) Tap position Inst. Fwd Min Tap position Inst. Fwd Max CM self test result Vref a/d value Raise Limit Reached status Lower Limit Reached status CM Response (to Init) Status CM Software Revision CM Hardware Revision CM microprocessor Mask rev. CM I/O Board Type CM Options (to be defined) CM I/O Board Revision CM QSPI MP to CM Errors CM QSPI no. of Failed Writes CM QSPI no. of Xfer Cycles CM DNP no. of requests for not supported items CM RAM Error High Address CM RAM Error Low Address Description Total Operations Count Level 1 PW characters Cfg. PW characters Reg. PW characters Meter PW characters Dmd PW characters Alert PW characters Ops PW characters LogSet PW characters Event/Interval PW characters Harm PW characters Comm PW characters Diag. PW characters Syskey PW characters Raise/Lower Operation CT Primary Ratio (Amps) System Line Voltage (Volts) High Voltage Limit (Volts) Low Voltage Limit (Volts) Local Voltage Reduction (%) VRC Remote Setting #1 (%) VRC Remote Setting #2 (%) VRC Remote Setting #3 (%) Auto VRC #1 %Current (%) Auto VRC #2 %Current (%) MJ-4 Communications Module 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 SF = 10 SF = 10 SF = 1 SF = 1 SF = 1000 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 10 SF = 1 SF = 1 SF = 1 SF = 10 SF = 10 SF = 10 SF = 10 SF = 1 SF = 10 SF = 1 SF = 10 SF = 10 SF = 10 SF = 1 SF = 10 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 Auto VRC #1 % Setting (%) Auto VRC #2 % Setting (%) P2 primary (from P2 PT ratio) (Volts) P2 secondary (Volts) CT secondary (Amps) Current Shift (in º, relative to voltage) U2 primary (Volts) U2 secondary (from U2 PT ratio) (Volts) (Range: 100-150) PT Threshold (Volts) Date Format Demand Subperiods MJ3A remote mode %VRC Min/Max Time-out(sec) Screen Timeout(minutes) Harm. Show as: RMS/%T/fund. N/A N/A Dmd Time Interval (minutes) Bandwidth (Reverse) (Volts) Line Comp. React. (Rev) (Volts) Line Comp. Resist. (Rev) (Volts) Reverse Sensing Method Set Voltage (Reverse) (Volts) Time Delay (Reverse) (seconds) Reverse Threshold Value (%) Bandwidth (Forward) (Volts) Line Comp. React. (Fwd) (Volts) Line Comp. Resist. (Fwd) (Volts) Control Operating Modes Set Voltage (Forward) (Volts) Time Delay (Forward)(seconds) Control Communications Address Comm Port Baud Rate Comm Port Handshake Mode Communications Port Re-Synch Time Characters (no. characters) Communications Port-Transmit Enable Delay (msec) Regulator Type Utility Winding Polarity Meter Display Volts Demand Type VRC Remote Basis Voltage Harm: Odd Only/Odd & Even Regulator Configuration Voltage Limiting Mode Voltage Reduction Mode Event/Interval Log Setup Status Password Enables, Bit mapped Alert Status word 1 (encoded) Alert Status word 2 (encoded) Memo1 - chars 1-2 Memo1 - chars 3-4 Memo1 - chars 5-6 Memo1 - chars 7-8 Memo1 - chars 9-10 Memo2 - chars 1-2 Memo2 - chars 3-4 Memo2 - chars 5-6 Memo2 - chars 7-8 33 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 SF = 1 Memo2 - chars 9-10 "NN" Raise/Lower Value Regulator Id (Range: 0 - 32766) Tap Changer Mechanism Max. Load Current % (Range: 0-350) Full Load Current (50-7200) (A) CM Pre-tx delay for DNP CM Post-tx delay for DNP CM transmit delay for DNP CM number of retries (DNP) CM protocol CM parity CM self test request Raise Limit % (0=10%, 1=8.75%, 2=7.5%, 3=6.25%, 4=5%) Lower Limit % (0=10%, 1=8.75%, 2=7.5%, 3=6.25%, 4=5%) Data Port Baud 9 Communications Module Firmware Versions 9.1 MJ-4 Communications Module firmware version Version 3.10 9.2 : Supports all DNP points including Set 7, supports AMD Flash memory. MJ-XL Communications Module firmware versions The principle firmware version released for the MJ-4 Communications Module is the 3.10, an abbreviated list of the principle firmware versions that have were released for use on the MJ-XL communications module follows. For questions regarding firmware versions not included in this list, please contact your Siemens representative. Version 2.13: Contains “full set” of 370 DNP3.0 points (see 2.x3 points list in Section 8.2.9). Version 2.14: Contains “limited set” of 64 DNP3.0 points (see 2.x4 points list in Section 8.2.3). Version 3.01: Level 2 implementation of DNP3.0, no DNP points by default; must use the DNP Configure program to load the desired DNP points onto the control panel. Supports unsolicited responses. Version 3.07: Level 2 implementation of DNP3.0, can use DNP Configure program to load user-defined DNP points or choose to use one of the predefined DNP point sets (if used in conjunction with MJXL version 3.07 or higher). Version 3.0701: Added short delay after CM initialization so all values are online before polling can start Version 3.0702: Added full support for Trip/Close operations on Binary Outputs. If using a Trip/Close operation for a tap raise or lower, the TRIP command should be used to activate. Also, a Trip to the Tap Raise point will raise the tap one position; a Close to the Tap Raise point will lower the tap one position. Version 3.0703: Added support for alternate AMD flash memory. Removed support for ATMEL Flash memory. 34 MJ-4 Communications Module 10 Specifications This section contains the MJ-4 Communications Module specifications. Contained in this section are the parameters for both the fiber optic and RS-232/485 interfaces. The data provided in the fiber optic section was obtained using 62.5/125 µm cable. Typical, maximum, and minimum lengths are given for normal and long range cable lengths. Except for the maximum and minimum parameters, the numbers provided are for room temperature. The maximum and minimum lengths are for temperature extremes. 10.1 Physical Dimensions Height Width Depth 8.4 inches ( 21.34 cm ) 2.89 inches ( 7.34 cm ) 2.84 inches ( 7.21 cm ) 10.2 Fiber Optic Link Interface Specifications Transmitter Maximum Output Power Typical Output Power Minimum Output Power Numerical Aperture Optical Port Diameter Receiver Peak Input Power Logic Level Low Peak Input Power Logic Level High System Wavelength Connector Type Fiber Type Data Rate Maximum Optical Power Budget Typical Optical Power Budget Minimum Optical Power Budget Link Lengths Maximum Link Length Typical Link Length Minimum Link Length Operating Temperature Range Jumper J12 In -13.0 dBm (Long Range) -16.0 dBm (Long Range) -20.0 dBm (Long Range) 0.49 290 µm Jumper J12 Out -16.0 dBm (Normal Range) -19.0 dBm (Normal Range) -23.0 dBm (Normal Range) -24.0 dBm Min to -9.2 dBm Max -40.0 dBm Max 820 nanometers (nominal) ST Glass 62.5/125 µm, 5dB/m 5 Mbaud (design) 11 dBm (Long Range) 8 dBm (Long Range) 4 dBm (Long Range) 19.2 Kbaud (tested) 8 dBm (Normal Range) 5 dBm (Normal Range) 1 dBm (Normal Range) 2.2 km (Long Range) 1.6 km (Long Range) 0.8 km (Long Range) -40ºC to +85ºC (excluding cable) 1.6 km (Normal Range) 0.6 km (Normal Range) 0.2 km (Normal Range) 10.3 RS-232/RS-485 Interface Specifications Parameter Data Rate (maximum) Distance (maximum) Nodes (maximum) Isolation RS-232 19200 baud 50 ft 72 500 VAC, 1 minute RS-485 19200 baud 4000 ft 32 500 VAC, 1 minute 35 Siemens Energy, Inc. P.O. Box 6289 Jackson MS 39288 21-115527-024 rev01 Manual 10/08 ©1994-2008 Siemens Energy, Inc.