データシート

For more information, please visit the product page.
date
08/13/2013
page
1 of 5
SERIES: VF-S250-XXA │ DESCRIPTION: AC-DC POWER SUPPLY
FEATURES
•
•
•
•
•
•
•
•
•
up to 250 W continuous power
600 W peak power within 500 μs duty duration
passive power factor correction
power good signal
remote on/off control
3000 Vac isolation voltage
over load, over voltage, over temperature, and short circuit protections
ions
UL, cUL, and TUV 60950-1 safety approvals
efficiency up to 85%
RoHS
MODEL
VF-S250-05A
output
voltage
output
current
output1
power
ripple and
noise 2,3
efficiency
(Vdc)
max
(A)
max
(W)
max
(mVp-p)
typ
(%)
5
40
200
50
75%
VF-S250-09A
9
25
225
90
83%
VF-S250-12A
12
20.83
250
120
80%
VF-S250-15A
15
16.67
250
150
83%
VF-S250-18A
18
13.89
250
180
83%
VF-S250-24A
24
10.42
250
240
83%
VF-S250-28A
28
8.93
250
280
83%
VF-S250-36A
36
6.93
250
360
83%
VF-S250-48A
48
5.21
250
480
83%
VF-S250-54A
54
4.63
250
540
83%
Notes:
1. Maximum power must not exceed 135 W with convection cooling or 250 W for forced air. 5 and 9 V models maximum current listed.
2. 1% minimum load is required to maintain the ripple and regulation.
3. Ripple and noise is measured from 10 KHz to 20 MHz at output terminals with a 0.1 μF ceramic capacitor and a 22 μF electrolytic capacitor in parallel.
PART NUMBER KEY
VF - S250 - XX A - X X
Base Number
Output Voltage
Low leakage option:
“blank” = standard specification
L = low leakage (contact factory)
Input/Output connector:
“blank” = Terminal block input / Terminal block output
1 = Molex input / Molex output
2 = Molex input / Terminal block output
3 = Terminal block input / Molex output
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: VF-S250-XXA │ DESCRIPTION: AC-DC POWER SUPPLY
date 08/13/2013 │ page 2 of 5
INPUT
parameter
conditions/description
voltage
90-132/180-264 auto selectable
min
frequency
max
units
90/180
typ
132/264
Vac
47
63
Hz
6
3
A
A
35
70
A
A
current
at 110~120 Vac, cold start
at 200~240 Vac, cold start
inrush current
at 115 Vac, cold start
at 230 Vac, cold start
power factor
compliant to EN 61000-3-2 class A
remote on/off
designated as RMSW on the CN1, requires a low signal to inhibit output, hiccup mode
OUTPUT
parameter
conditions/description
min
line regulation
low line to high line
±1
%
load regulation
all other outputs
±1
%
0.25
mV/°C
temperature coefficient
typ
transient response
output voltage returns to within 1% in less than 2.5 ms for a 50% load change
peak transient does not exceed 5%.
start-up time
at 120 Vac
rise time
hold-up time
0.2
at 120 Vac and 80% of rated maximim load
max
1
s
20
ms
20
adjustability
units
ms
±5
power good
designated as PG on the CN1, signal goes high 100~500 ms after the output
reaches regulation, signal goes low at least 1 ms before loss of regulation
fan drive
12 Vdc / 300 mA for external fan
%
PROTECTIONS
parameter
conditions/description
min
typ
max
over voltage protection
AC input needs to be reset to restart the power supply
over current protection
automatically recovers
short circuit protection
short circuit can be continuous, recovers automatically upon removal of short
over temperature protection
auto recovery
units
130
%
110
140
%
85
°C
max
units
SAFETY & COMPLIANCE
parameter
conditions/description
isolation voltage
for 3 seconds at 10 mA max
primary to secondary:
primary to transformer core:
primary to earth chassis:
min
safety approvals
UL 60950-1, CSA C22.2 No. 60950-1, TUV EN 60950-1 and CB
EMI/EMC
CISPR 22/EN 55022 class B, EN 61000-3-2, 3,
EN 61000-4-2, 3, 4, 5, 6, 8, 11, EN 55024 CE marked (LVD)
leakage current
at 240 Vac, (optional for 500 μA at 240 Vac,
300 μA at 120 Vac)
typ
3,000
1,500
1,500
MTBF
according to MIL-HDBK-217 at 30ºC
RoHS compliant
yes
cui.com
Vac
Vac
Vac
1.5
100,000
mA
hrs
For more information, please visit the product page.
CUI Inc │ SERIES: VF-S250-XXA │ DESCRIPTION: AC-DC POWER SUPPLY
date 08/13/2013 │ page 3 of 5
ENVIRONMENTAL
parameter
conditions/description
min
operating temperature
0
storage temperature
typ
max
units
70
°C
-20
85
°C
non-condensing
5%
90%
%
storage humidity
non-condensing
5%
95%
%
vibration
acceleration ±7.35 M/(SxS), on X, Y and Z Axis
5
50
Hz
operating humidity
DERATING CURVE
output power vs. ambient temperature
Load (%)
100
80
60
50
40
20
0
10
20
30
40
50
60
Ambient Temperature (°C)
cui.com
70
For more information, please visit the product page.
CUI Inc │ SERIES: VF-S250-XXA │ DESCRIPTION: AC-DC POWER SUPPLY
date 08/13/2013 │ page 4 of 5
MECHANICAL
parameter
conditions/description
dimensions
127.00 x 81.28 x 38.10 (5 x 3.2 x 1.5 inch)
min
typ
max
units
mm
weight
400
g
MECHANICAL DRAWING
50.80 2.000
6.35 0.250
6.35 0.250
19.05 0.750
13.90 0.547
(2 PLCS)
68.58 2.700
(2 PLCS)
mounting hole
M3x0.5 (7 PLCS)
44.52 1.753
(2 PLCS)
LED
CN1
1
ground
2
ac neutral
3
FAN
64.76 2.550
CN3
FG
CN2
81.28 3.200
RTN
RMSW
P.G
VO-
NEUTRAL
ac line
VO+
LINE
CN1
CN2
1
Vo+
2
Vo+
3
Vo+
4
Vo-
5
Vo-
6
Vo-
molex part no.
26-48-1051
(5 pins, 3 used)
8.26 0.325
terminal block
M3 screw
3pins 6.35mm center
CN3
1
Power Good
2
remote switch
3
RTN
38.10 1.500
127.00 5.000
Notes:
1.
2.
3.
4.
5.
CN1 mates with molex part no. 09-93-0500 and molex 2478, 2578, 8818 crimp pins.
CN2 mates with molex part no. 09-93-0600 and molex 2478, 2578, 8818 crimp pins.
CN3 mates with JST part no. XHP-3 or equivalent (Chyao Shiunn JS-2001-03) and JST SXH-002T-P0.6 mating pins
Fan drive connector mates with JST part no. XHP-2 or equivalent.
Mounting hole maximum M3 screw depth 3.8mm
cui.com
molex part no.
26-48-1061
(6 pins)
terminal block
M3 screw
4pins 6.35mm center
For more information, please visit the product page.
CUI Inc │ SERIES: VF-S250-XXA │ DESCRIPTION: AC-DC POWER SUPPLY
date 08/13/2013 │ page 5 of 5
REVISION HISTORY
rev.
description
date
1.0
initial release
05/5/2009
1.01
new template applied
12/16/2011
1.02
V-Infinity branding removed
08/28/2012
1.03
updated Molex mating connector part numbers
07/11/2013
1.04
updated spec
08/13/2013
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
[email protected]
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical
component is any component of a life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to
affect its safety or effectiveness.