Intelligent Modules Data Sheet

SWIFT™
Intelligent Wireless
Modules
Description
SWIFT™ (Smart Wireless Integrated Fire Technology)
wireless modules are intelligent (addressable) modules
that provide secure, reliable communication to the Fire
Alarm Control Panel (FACP) using a Class A, mesh network. Wireless modules can be used in the following types
of conditions, where it is costly, obtrusive, or possibly dangerous to use traditional wired devices.
• concrete walls/ceilings
• surface-mount conduit
• buried wires
• asbestos
In addition, both wired and wireless devices can be present on the same FACP providing an integrated wired-wireless solution to offer increased installation potential.
The mesh network (within the SWIFT System) creates a
child-parent relationship (for example, backup communication) between the devices, so that each device has two
parents providing a secondary path to transmit communications on every device. If one device can no longer operate for any reason, the remaining devices can continue to
communicate directly with each other, or they can communicate through one or more intermediate devices. After an
initial mesh network is formed, mesh restructuring automatically occurs. The mesh restructuring locates the strongest paths possible within the network.
SWIFT Monitor Module
The SWIFT monitor module is intended for use with a wireless gateway or wireless FACP to interface with a device
having contacts used to signal status conditions. It is
designed to provide an interface to the following types of
contact devices.
• security contacts
• waterflow switches
• pull stations.
The input to the monitor module is non-latching and does
not require a reset. The device has a panel controlled LED
indicator. The monitor module must be within 3 feet of the
monitored device.
SWIFT Relay Module
The SWIFT relay module allows a compatible control panel
to switch discreet contacts by code command. The relay
contains an isolated set of Form-C contacts, which operate
as a DPDT switch. Circuit connections to the relay are not
supervised by the module. The SWIFT relay module can
be used to activate the following functions:
• remote power supply (in conjunction with a monitor
module).
• elevator recall.
• door holders and fan shutdown of wired devices.
• SWIFT devices within the same mesh network.
The module also includes a panel-controlled LED indicator.
SWIFT, Smart Wireless Integrated
Fire Technology
SWIFT Intelligent Wireless Modules
Features
• Complies with UL® Standard 864 Listing.
• Connects to E3 Series® or S3 Series fire alarm control
panels.
• Each mesh supports up to 48 wireless devices per gateway.
• Uses redundant wireless mesh technology to support
Class A survivability.
• Employs frequency hopping to eliminate outside
interference.
• Engages each device to act as a signal repeater/
booster, avoiding large and costly separate repeater
units.
• Combines mixed wired Velociti® devices and wireless
devices on the same SLC loop.
• Includes multi-device alarm activation.
• Designed with tamper-proof construction.
• Has addressable code wheels.
• Applies low battery, signal pre-warning.
Ordering Information
Part Number Description
WAM-MM
Wireless Monitor Module
WAM-RC
Wireless Addressable Module-Relay Control
Accessory:
SWIFT Tools USB Adapter
W-USB
*Note: Consult the Fire Alarm Control Panel Manufacturer
to obtain the complete system requirements.
E3 Series® and Velociti® are registered trademarks and SWIFT™ and Acclimate™ are trademarks of Honeywell International Inc.
UL® is a registered trademark of Underwriter’s Laboratories Inc.
SIGNALING
FM
APPROVED
S1949 3053714 7300-1703:0181
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60819 Rev. D page 1 of 2
©2015 by Honeywell International Inc. All rights reserved.
DEVICE 4
E3 OR S3 FACP
DEVICE 1
GATEWAY
U DRIVER
DEVICE 3
DEVICE 2
ANNUNCIATOR
USB
SWIFT TOOLS
DEVICE 5
PARENT
CHILD
Note: An optional USB
wireless transceiver that
communicates with the
GATEWAY and SWIFT Tools
software aids in the site
survey, mesh formation, and
diagnostics of the system.
Figure 1 SWIFT Mesh Network
Description (Continued)
All sensors offer addressable code wheels and one LED.
The LED is controlled by the panels. Operational modes
include red, green and amber colors with various solid or
blink patterns.
The devices transmit communication signals across the
mesh network through a gateway to the FACP. Some systems may require a user interface and annunciator to display wireless specific messages. The FACP identifies the
SWIFT wireless device as another addressable device on
the system providing similar detection functions and outputs as a wired counterpart. In addition, both wired and
wireless devices can be present on the same FACP to
meet the needs of a given application. A SWIFT wireless
System can use any combination of modules, smoke or
heat detectors.
The SWIFT System also engages frequency hopping to
prevent system interference whether intentional or accidental.The operation of each device is subject to the following conditions in compliance with the FCC Standards,
Part 15.
1. The device may not cause harmful interference.
2. The device must accept any interference received
including interference that may cause undesired
operation.
SWIFT Intelligent Wireless Modules
Specifications (Continued)
Electrical Specifications
Maximum Operating Voltage:
Average Operating Current:
Maximum Current Draw:
EOL Resistance:
Maximum IDC Wiring Resistance:
Maximum IDC Voltage:
Maximum Average IDC Current:
Maximum Transmit RF Power:
Radio Frequency Range:
Relay Module Specifications
Electrical Specifications
Maximum Operating Voltage:
Average Operating Current:
Maximum Current Draw:
Maximum Transmit RF Power:
Radio Frequency Range:
Current
Rating
2A
3A
2A
0.46 A
0.7 A
0.9 A
0.5 A
0.3 A
SWIFT Intelligent Wireless Modules
Specifications
Physical/Operating Specifications
Dimensions:
Device Weight with 4
batteries & face-plate:
Operating
Temperature Range:
Operating Humidity
Range:
H:4¼” x W:4¼” x D:1½”
(H:10.79 x W:10.79 x D:3.8 cm)
7.9 oz (224 g)
32°F to 120°F (0°C to 49°C)
10% to 93% non-condensing
3.3 VDC
210 µA, 3.9k EOL
5.0 mA (LED on)
3.9K Ohms
10 Ohms
3.2 Volts
5.5 µA
17dBm
902-928 MHz
3.3 VDC
210 µA
5 mA (LED on)
17 dBm
902-928 MHz
Maximum
Load
Voltage
Description Application
25 VAC
PF = 0.35
Non-coded
30 VDC
Resistive
Non-coded
30 VDC
Resistive
Coded
30 VDC
(L/R = 20ms) Non-coded
70.7 VAC
PF = 0.35
Non-coded
125 VDC
Resistive
Non-coded
125 VAC
PF = 0.75
Non-coded
125 VAC
PF = 0.35
Non-coded
Table 1: Relay Contact Ratings
Battery Specifications
Battery Type:
4 Panasonic CR123A or
4 Duracell DL123A
Battery Life:
2 year minimum
Battery Replacement: Upon TROUBLE BATTERY LOW
display and/or during annual
maintenance
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60819 Rev. D page 2 of 2
www.gamewell-fci.com