データシート

For more information, please visit the product page.
date
11/20/2015
page
1 of 11
SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
FEATURES
• up to 12,000 W continuous power
• operation from a wide range AC input
(90~260 Vac) incoming (Line-Neutral) AC
source on a per module basis
• 19” four slot power shelf
• 48 or 54 Vdc output voltage (from PSE-3000
modules)
• single or dual output configurations
• integral forced cooling, from internal fans
housed within the power modules
• front to back & back to front airflow versions
, I
nc
rt
Rheinla
.
T
o
of N
C
3.3 Vdc (2 A) standby voltage
redundant (N+1) operation
blind mate connections for hot-swap
adjustable mounting brackets
racks can share with on additional rack in a
master slave arrangement
• EMI filtering of the AC input directly in line
with the IEC 320 inlet connetors to meet
Class A performance
• user accessible dip-switch for setting master
or slave shelf
nd
UV
•
•
•
•
•
h A
ca
meri
US
MODEL1
output
voltage1
airflow
direction
output
configuration2
(Vdc)
output power
(max)
110 Vin
(W)
220 Vin
(W)
PPR-1U
48 or 54
front to back
single output,
configuration A
6,000
12,000
PPR-1U-A
48 or 54
front to back
dual output
6,000
12,000
PPR-1U-B
48 or 54
back to front
single output,
configuration A
5,400
12,000
PPR-1U-C
48 or 54
back to front
dual output
5,400
12,000
PPR-1U-D
48 or 54
front to back
single output,
configuration B
6,000
12,000
PPR-1U-E
48 or 54
back to front
single output,
configuration B
5,400
12,000
Notes:
1. Rack assembly requires (4) PSE-3000-48 or PSE-3000-54 units (sold separately). Refer to the PSE-3000 datasheet for specification details.
2. See page 3 for configuration details.
3. All specifications measured at: Ta=25°C and 220 Vac input voltage unless otherwise specified.
PART NUMBER KEY
PPR-1U - X
Rack Configuration
“blank” = Front to Back Airflow, All Parallel, Single Output, A
A = Front to Back Airflow, Dual Output
B = Back to Front Airflow, All parallel, Single Output, A
C = Back to Front Airflow, Dual Output
D = Front to Back Airflow, All Parallel, Single Output, B
E = Back to Front Airflow, All Parallel, Single Output, B
Base Number
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 2 of 11
POWER SHELF
Shelf Power
Power Shelf
Model Number
Power Module
Model Number
Airflow
Direction
110 Vin
220 Vin
Standby
Output
IEC Inlet
Type
PPR-1U
PSE-3000-48-F or PSE-3000-54-F
Front to Back
6,000 W
12,000 W
All Parallel,
single output,
configuration A
C22
PPR-1U-A
PSE-3000-48-F or PSE-3000-54-F
Front to Back
6,000 W
12,000 W
dual output
C22
PPR-1U-B
PSE-3000-48-B or PSE-3000-54-B
Back to Front
5,400 W
12,000 W
All Parallel,
single output
configuration A
C20
PPR-1U-C
PSE-3000-48-B or PSE-3000-54-B
Back to Front
5,400 W
12,000 W
dual output
C20
PPR-1U-D
PSE-3000-48-F or PSE-3000-54-F
Front to Back
6,000 W
12,000 W
All Parallel,
single output
configuration B
C22
PPR-1U-E
PSE-3000-48-B or PSE-3000-54-B
Back to Front
5,400 W
12,000 W
All Parallel,
single output
configuration B
C20
PPR-1U, PPR-1U-A, PPR-1U-D - FRONT TO BACK AIRFLOW
PPR-1U-B, PPR-1U-C, PPR-1U-E - BACK TO FRONT AIRFLOW
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 3 of 11
POWER SHELF (CONTINUED)
PPR-1U & PPR-1U-B Output Terminal Block Configuration (Single Output, Configuration A)
All 4 power modules wired in parallel inside the power shelf, 6 kW available from each output terminal block set
+
-
+
-
PPR-1U-A & PPR-1U-C Output Terminal Block Configuration (Dual Output)
Each terminal block wired to 2 power modules, 6 kW available from each output
+
-
+
-
PPR-1U-D & PPR-1U-E Output Terminal Block Configuration (Single Output, Configuration B)
All 4 power modules wired in parallel inside the power shelf, 6 kW available from each output terminal block set
-
+
+
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 4 of 11
MECHANICAL DRAWING
PPR-1U, PPR-1U-A, PPR-1U-D - FRONT TO BACK AIRFLOW
units: inches [mm]
tolerance: ±0.02 [0.50]
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 5 of 11
MECHANICAL DRAWING (CONTINUED)
PPR-1U-B, PPR-1U-C, PPR-1U-E - BACK TO FRONT AIRFLOW
units: inches [mm]
tolerance: ±0.02 [0.50]
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 6 of 11
MECHANICAL DRAWING (CONTINUED)
Bracket Attachment
The mounting brackets are factory attached in the flush position. The mounting brackets can be repositioned by customer,
however the #6-32 mounting screws to be reattached with typical torque of 6 to 8 in-lbs.
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 7 of 11
CONNECTIONS
Back to Front Airflow
Front to Back Airflow
Chassis Grounding
DC OUTPUT
AC INPUT
V Standby Output
Connector
A2 Address
Switch
D-Sub 9 I C communication
The 2 D-Sub connector
signals are parallel inside
the power shelf
2
AC Line Cord Connection
The power shelf is not shipped with AC line cords and the customer is responsible to provide its own AC line cords to
meet the respective local electrical code requirements.
Chassis Grounding
A ground stud is provided at the rear of the power shelf as shown below. Earth ground stud nut #10-32 to be torqued 16
to 19 in-lbs typical.
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 8 of 11
CONNECTIONS (CONTINUED)
DC Output Cable Connection
The Output and Return Cables (#2 AWG wire on 1/4” stud - not provided) connected to output studs provided at the rear
of the power shelf as shown below.
Standby Output Connections
V Standby Output Connector, Mating Connector Molex 39-01-2020, terminals 39-00-0038
Connector - Pin#
Signal Name
Function
1 (lower position)
+3.3 STANDBY
+3.3 VDC +VE Output
2 (upper position)
+3.3 STANDBY RTN
+3.3 VDC –VE Output
Signal Interface Connections (System to Shelf; Shelf to Shelf):
The shelf signals are provided with a 9 Pin female D-SUB connector for system communication and another 9 Pin female
D-SUB connector for shelf to shelf communication:
D-SUB 9 pin
System to Shelf
Shelf to Shelf
SDA
1
Yes
Yes
SCL
2
Yes
Yes
Not used
3
--
--
Vpgm
4
Yes
Yes
Vpgm Return
5
Yes
Yes
Digital Return
6
Yes
Yes
SMB Alert
7
Yes
Yes
Not used
8
--
--
I-Share
9
Yes
Yes
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 9 of 11
CONNECTIONS (CONTINUED)
A2 Address Switch Connections
Address
A2 Address Switch
Down
Up
A2
A1
A0
Slot 1
0
0
0
Slot 2
0
0
1
Slot 3
0
1
0
Slot 4
0
1
1
Slot 1
1
0
0
Slot 2
1
0
1
Slot 3
1
1
0
Slot 4
1
1
1
Slot 1
Slot 2
Slot 3
cui.com
Slot 4
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 10 of 11
ACCESSORIES
The PPR-1U Series requires the following additional accessories that can be purchased separately or as a kit.
Description
QTY
CUI Part Number
Vendor/Part Number
AC power line cordset, C22 type
4
Schurter C21.6051.5002
AC power line cordset, C20 type
4
Schurter C19.6009.5195
Aux Output Mating Connector
1
Molex 39-01-2020
Aux Output Contact Terminal
2
Molex 46055-0007
I C dongle
1
Microchip DV164122
I C dongle to D sub 9 cable
1
1
2
2
3
2
014-157401-4
Notes:
1. Used with PPR-1U, PPR-1U-A, PPR-1U-D
2. Used with PPR-1U-B, PPR-1U-C, PPR-1U-E
3. The PICkit Serial Analyzer is an USB-based tool used to direct communication between a PC and an external serial device. The kit comes complete with hardware (supporting I2C™, SMBus, SPI and USART protocols), an easy-to-use GUI (to configure and display communications) and a target demonstration board for out-of-the-box functionality.
Accessory-kit-1
Description
QTY
Vendor/Part Number
AC power line cordset, C22 type
4
Schurter C21.6051.5002
Aux Output Mating Connector
1
Molex 39-01-2020
Aux Output Contact Terminal
2
Molex 46055-0007
I C dongle
1
Microchip DV164122
I C dongle to D sub 9 cable
1
2
3
2
Notes:
1. Compatible with PPR-1U, PPR-1U-A, PPR-1U-D
Accessory-kit-2
Description
QTY
Vendor/Part Number
AC power line cordset, C20 type
4
Schurter C19.6009.5195
Aux Output Mating Connector
1
Molex 39-01-2020
Aux Output Contact Terminal
2
Molex 46055-0007
I C dongle
1
Microchip DV164122
I2C dongle to D sub 9 cable
1
2
Notes:
3
1. Compatible with PPR-1U-B, PPR-1U-C, PPR-1U-E
cui.com
For more information, please visit the product page.
CUI Inc │ SERIES: PPR-1U │ DESCRIPTION: RACK ACCESSORY
date 11/20/2015 │ page 11 of 11
REVISION HISTORY
rev.
1.0
description
date
initial release
11/20/2015
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
[email protected]
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.