Datasheet

SDA1 - 60 - 80
DIN rail 60A & 80A solid-state relays
● High load voltage - up to 480VAC
● 4 ~ 32VDC or 90 ~ 250VAC control voltage
● Single Phase, Zero cross-over switching
● LED control input indicator
● Integrated heatsink
● RoHS Compliant
Pending
Output (load)
Load type
SPST-NO (1 N/O) Resistive
Load current
60A, 80A
Load switching voltage
Maximum peak voltage
Minimum load current
Inrush Current (max.)
AC Vrms 40 - 480V
AC Vpk 900V
0.1A
10ms 60A: 650A / 80A: 900A
It
60A: 2100A2s / 80A: 4050A2s
Switch type
Zero Cross (Consult factory for Random)
2
On voltage drop
V AC 1.6V
Leakage current off
mA ≤ 10mA
Input (control)
Control voltage (rated)
Control current
V DC Control: 4 - 32VDC / AC Control: 90 - 250VAC
mA < 20mA
Turn-on voltage (min)
Vmin DC Control: 3.5VDC / AC Control: 80VAC
Turn-on voltage (max)
Vmax DC Control: 35VDC / AC Control: 280VAC
Turn-off voltage
V DC Control: 2VDC / AC Control: 40VAC
Insulation
Insulation resistance
Dielectric strength
≤ 500MΩ at 500VDC, 50%RH
V AC ≥ 2500V
General Data
Operating time (typical)
mS Approximately 1/2 cycle of load frequency + ≤1ms
Release time (typical)
mS Approximately 1/2 cycle of load frequency + ≤1ms
Dimensions
L x W x H 100 x 110 x 127mm
Weight
approx. 940g
Ambient temperature
storage -30 to 100°C (No icing or condensation)
operating -30 to 80°C (with derating). (No icing or condensation)
Relative Humidity
Page 1 of 2
www.durakoolrelays.com
Ref: SDA1 60 80 040616 JHM
45 - 85% RH
Sales Department Tel: (888) 847-6552
Specifications are subject to change without notice. E&OE.
SDA1 - 60 - 80
DIN rail 60A & 80A solid-state relays
Dimensions
Ordering Code
S
D
A
1
Z
-
60
K
-
Fig. 1
D
Switch Function
Z
-
Zero Crossover
R
-
Random
Load Current Rating
60
-
60A
80
-
80A
Load Voltage
K
-
DC Control Input
40 to 480VAC
AC Control Input
Control Voltage Input
A
-
90 to 250VAC
D
-
4 to 32VDC
Load or Fuse
Control Input
Dimensions in mm
Fig. 2
Page 2 of 2
Input Current v. Control Voltage: 4 ~ 32VDC
Input Current v. Control Voltage: 90 ~ 250VAC
Load Current Derating v. Ambient Temperature
Load Output v. Input Control Action (Zero X-over)
www.durakoolrelays.com
Ref: SDA1 60 80 040616 JHM
Sales Department Tel: (888) 847-6552
Specifications are subject to change without notice. E&OE.