Advantech AE Technical Share Document Date Category Abstract Keyword Related Product 2015 / 04 / 08 SR# ■ FAQ □ SOP Related OS Microsoft Windows7 Siemens S7 and WebAccess address mapping table. SCADA Node Fixed Public IP Address. N/A Problem Description: Siemens S7 and WebAccess address mapping table. Brief Solution: 1. . 2. COM port type: TCPIP Device type: SiemS7 Port Number: 102 Manually Switch Primary/Backup: it working only for that PLC has the Redundancy function. TSAP in Hex :Device ID, RackSlot: 03.02 for S7-300 TSAP in Hex :Device ID, RackSlot: 03.03 for S7-400 Digital data address sample: S7 PLCaddress Address Sample DB1.DBX 2.0 DB1.DBX 3.5 DB1.DBB 2.1 取 3 bits DB1.DBB 3.4 取 2 bits Analog data address sample: S7 PLCaddresss Address Sample DB2.DBW 4 DB2.DBB 1 DB2.DBW 64 float Text data address sample: S7 PLC address Address Sample DB9.DBW 0 format DBX1,2 DBX1,3 DBB1,2 DBB1,3 WebAccess address Start bit length Conversion Code 0 1 Unsigned Integer 5 1 Unsigned Integer 1 3 Unsigned Integer 4 2 Unsigned Integer format DBW2,4 DBB2,1 DBW2,64 WebAccess address Start bit length Conversion Code 0 16 Unsigned Integer 0 8 Unsigned Integer 0 32 Real format DBW9,0 WebAccess address TextLen Conversion Code 32 Text Reference: Page 1