• WebAccess_Set Siemens 7 Address and parameter in WebAccess

Advantech AE Technical Share Document
Date
Category
Abstract
Keyword
Related Product
2015 / 3 / 20
SR#
□FAQ ■ SOP
Related OS
Microsoft Windows7 SP1
Set Siemens 7 Address and parameter in WebAccess
Siemens 7, Address, parameter, WebAccess, SCADA
WebAccess V7.2, V8.0

Problem Description:
Set Siemens 7 Address and parameter in WebAcces

Brief Solution - Step by Step:
Step1: Open Internet Explorer browser.
Step2: Create Project Node : Enter project name, IP and then click Submit.
Step3: Add SCADA Node.
Step4: Choose Add Comport, as shown in Picture1.
Picture1. Choose Add Comport
Step5: Add Comport: TCPIP.
Interface Name : TCPIP. Set the parameters as required, as shown in Pictrue2:
Picture2. Create New Comport
Page 1
Step6: Choose Add Device., as shown in Picture3:
Picture3. Add Device
Step7: Enter Device Name and set the parameter as shown in Picture4.
Picture4: Create new device
TSAP: 03.02 or 03.03 ( period (.),not comma )
0: Auto switch;1: Manual switch
Step8: Device
Device Type: SiemS7
jjjjjjj((
( not
com
ma )
Port Number: 102
Manually Switch Primary/Backup: When PLC supports redundancy function, it works.
Page 2
TSAP in Hex: Device ID, RackSlot: 03.02
for S7-300
TSAP in Hex: Device ID, RackSlot: 03.03
for S7-400
Step9: Choose Add Tag, as shown in Picture5.
Picture5
Step10: Enter Tags parameters as shown in Picture6
Picture6. Create New Tags
Page 3
Appendix: Comparison PLC I/O with WebAccess and Siemens
Digital data address sample:
S7 PLC Address
Address Sample
Define in WebAccess
Address Format
Start
Length
Conversion Code
Address
DB1.DBX 2.0
DBX1,2
0
1
Unsigned Integer
DB1.DBX 3.5
DBX1,3
5
1
Unsigned Integer
DB1.DBB 2.1 retrieve 3 bits DBB1,2
1
3
Unsigned Integer
DB1.DBB 3.4 retrieve 2 bits DBB1,3
4
2
Unsigned Integer
Analog data address sample:
S7 PLC Address
Address Sample
Define in WebAccess
Address
Start
Format
Address
Length
Conversion Code
DB2.DBW 4
DBW2,4
0
16
Unsigned Integer
DB2.DBB 1
DBB2,1
0
8
Unsigned Integer
0
32
Real
DB2.DBW 64 retrieve float DBW2,64
Text data address sample:
S7 PLC Address
Address Sample
DB9.DBW 0
Define in WebAccess
Address Format TextLen
DBW9,0
32
Conversion Code
Text
Page 4