Mitsubishi_FX2N

WebAccess Configuration Manual
Mitsubishi FX2N
Mitsubishi FX2N Driver
Configuration Manual
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 1
WebAccess Configuration Manual
Mitsubishi FX2N
Table of Contents
Mitsubishi FX2N Driver Configuration Manual
1
1.
2
Mitsubishi FX2N Configuration
1.1
1.2
2.
Mitsubishi FX2N ........................................................................... 2
Module Settings ............................................................................ 2
WebAccess Configuration
7
2.1
Port.............................................................................................. 7
2.1.1
Check the port number...................................................... 7
2.1.2
WebAccess Comport Page................................................ 9
2.1.3
Comport Number .............................................................. 9
2.1.4
Description ..................................................................... 10
2.1.5
Baud Rate ...................................................................... 10
2.1.6
Data Bits ........................................................................ 10
2.1.7
Stop Bits ........................................................................ 10
2.1.8
Parity ............................................................................. 10
2.1.9
Scan Time...................................................................... 10
2.1.10
Timeout .......................................................................... 10
2.1.11
Retry Count .................................................................... 11
2.1.12
Auto Recover Time ......................................................... 11
2.1.13
Hand Shake RTS ............................................................ 11
2.1.14
Hand Shake DTR ........................................................... 11
2.1.15
Backup Port ................................................................... 12
2.2
Device ....................................................................................... 12
2.2.1
Unit Number ................................................................... 12
2.2.2
Use RS-485 Port ............................................................ 12
2.3
Tag ............................................................................................ 13
2.3.1
Parameter ...................................................................... 13
2.3.2
Address ......................................................................... 13
2.3.3
Scaling Type .................................................................. 13
2.4
Main Parameter List .................................................................... 14
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 1-1
WebAccess Configuration Manual
Mitsubishi FX2N
1. Mitsubishi FX2N
Configuration
1.1
Mitsubishi FX2N
Mitsubishi FX series are compact PLC. They connect to the computer through
serial link. As the FX protocol evolved through versions WebAccess has 3
different drivers to connect to the different Models.
The FX PLC contain 3 potential connection ports. The programming port is the
only one that can communicate with the configuration software so you should
connect this one first. It is a RS-422 port but Mitsubishi usually sells a 422 to
232 converting cable with the PLC.
The two expansion boards can also be used to read the variable w ith
WebAccess, we will explain their usage later in this document.
For FX2N series please use the FX2 driver in WebAccess. FX2 and FX2C PLC
should use FX driver.
1.2
Module Settings
To configure the PLC you will have to install the GX Developer software.
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 2
WebAccess Configuration Manual
Mitsubishi FX2N
The first step is to upload the program currently on the PLC, this will also
allow you to check that the PLC is connected properly.
Choose the Comport and select 9.6Kbps speed.
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 3
WebAccess Configuration Manual
Mitsubishi FX2N
Upload the data from the PLC:
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 4
WebAccess Configuration Manual
Mitsubishi FX2N
Now we know that the connection through the programming port is working.
If you want to use the programming port to connect the PLC with WebAccess
go directly to the next chapt er.
If you want to use an expansion board you have to set it up properly. The
expansion board 1 is set through the PLC settings in GX, the expansion board
two has to be set using ladder. In both case you need to select the settings
depending on your board (RS-485 or RS-232) and the Serial settings you
want to use.
The protocol setting is fixed, you need to use “Dedicated Protocol” with
“Format 4”.
For the other parameters the default values are: 7 data bits, Even parity, 1
stop bit, 9600 bps, no Header character, no Terminator character, Checksum
active.
For the expansion board 2 you have to set three addresses using ladder:
D8120 for the settings: (E086 value works with WebAccess and a RS-485
board)
D8121 Station number: 0
D8129 Timeout value: 0
Here is a ladder example:
You should calculate your settings value using the follow ing table (remember
the high bit- the bit on the left- is bit 15 at the bottom of this table)
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 5
WebAccess Configuration Manual
Mitsubishi FX2N
After building your ladder or changing the settings please download the
program again and restart the PLC (unplug and re-plug).
If you are using an RS-232 expansion board here is the recommended wiring
for the cable:
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 6
WebAccess Configuration Manual
Mitsubishi FX2N
2. WebAccess Configuration
2.1
Port
The Mitsubishi FX protocol uses a serial port. Even if you use a serial port
server or a USB to serial converter the apparent port in your computer (and
therefore the port to select in WebAccess) is a serial port.
2.1.1
Check the port number
If you are using a comport emulator and you do not know the port number
then open the “Start Menu” and right clic k on “Computer” and select
“Manage”
In the device manager section you can see the list of COM ports on your
computer and recognize the virtual port by its driver name
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 7
WebAccess Configuration Manual
Version 7.0 rev 0a
Mitsubishi FX2N
Ad vantech Corp., Ltd.
page 8
WebAccess Configuration Manual
2.1.2
Mitsubishi FX2N
WebAccess Comport Page
Open your WebAccess Configuration and select the SCADA node you want to
add the device to. Then select “Add a new Comport”
All the settings in this page must match the settings in all the modules
attached to the port. So all the modules attached to the same comport must
have the same settings.
2.1.3 Comport Number
The Serial Comport requires the comport number to match that of the
physical interface (e.g. COM1, COM2, COM3, etc) on the SCADA Node.
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 9
WebAccess Configuration Manual
Mitsubishi FX2N
2.1.4 Description
This is an optional field used for user reference.
2.1.5 Baud Rate
For the Mitsubishi FX modules the typical baud rat e is 9600.
This must match the baud rate configured in the module and the eventual RS 485 to RS-232 converter.
2.1.6 Data Bits
The packets can have 7 or 8 Data Bits. The typical setting for Mitsubishi FX is
7 bits.
2.1.7 Stop Bits
The packets can have 1 or 2 Stop Bits. The typical setting for Mitsubishi FX is
1 Stop bit.
2.1.8 Parity
The Parity can be None, Odd, Even or Disabled. The typical setting for
Mitsubishi FX is Parity = Even.
2.1.9 Scan Time
This is the time in milliseconds to scan the Devices. This must match the
ability of the device to respond. A typical scan rate is 1 per second.
If the Device cannot respond as fast as the SCAN Time entered, WebAccess
will scan at a slower rate.
2.1.10 Timeout
With a 1 second scan rate, a typical Time Out = 200 Milliseconds.
Timeout is the time waited before re-sending a communications packet that
did not have a reply.
Timeout specifies how long the software waits for a response to a data
request, specifically to wait for a reply from one packet. A recommended
value is one-fifth the scan rate, longer if the communication device is slow.
Combined w ith Retry count, Timeout also determines time to consider a
device or port as BAD. Timeout is the time to wait since last communication
packet sent without a reply. Time is in milliseconds. Slow or poor quality
communications require longer timeout. The faster the communications, the
shorter the timeout required. Shorter timeouts result in faster reconnects
after communication failures.
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 10
WebAccess Configuration Manual
Mitsubishi FX2N
2.1.11 Retry Count
A typical Retry count = 3.
Number of times to retry communications if no reply is received from a device.
Combined with Timeout, also determines time to consider a device or port as
BAD.
This is the number of times after the first attempt has failed that
communication should be attempted before indicating a failure. (If Retry
count is 3, a total of 4 failed requests have occurred before tags are marked
bad). Specifically, this is how many times to send a single packet after the
field device fails to respond to the first packet. After the ret ry count is
exceeded, all the tags in the packet are marked w ith asterisks and the next
packet of requests is sent. A reasonable value is 3 to 5 times. After this
number of tries, the tags in this packet are marked as "fail to respond" (i.e.
asterisks) and are disabled. In reality, increasing the number of retries hides
failures on the part of the field device to respond to a request. Essentially,
increasing the retries gives the field device more chances to reply.
2.1.12 Auto Recover Time
A typical Auto Recover Time = 60 Seconds.
Auto Recover Time is the time to wait before attempting to re -establish
communications with a BAD device or port.
If communications to the PLC is unusually slow due to hardware,
communications or network issues, you might consider increasing this value.
If communications to the PLC or RTU fails frequently, you may want to
decrease this number in order to have WebAccess try to re -establish
communications sooner.
If communications to the PLC, RTU or device Fails (i.e. exceeds Ti meout)
WebAccess will wait the Auto Recover Time before trying to re -establish
communications.
2.1.13 Hand Shake RTS
The typical setting for Mitsubishi FX is HandShakeRts = No.
The RTS (Request To Send) signal is raised and lowered on the Serial
Communications Port if this value set to Yes. RTS is determined by settings
in the field device. Refer to your device interface manual to determine the
value for this field and the type of cable used.
2.1.14 Hand Shake DTR
The typical setting for Mitsubishi FX is HandShakeDtr = No.
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 11
WebAccess Configuration Manual
Mitsubishi FX2N
The DTR (Data Terminal Ready) signal raised and lowered on the Serial
Communications Port if this value is set to Yes. DTR is determined by settings
in the field device and the type of cable used.
2.1.15 Backup Port
The Backup Port has not been tested for Mitsubishi FX
2.2
Device
Then Go to the port page and select “Add a new device”. Select the Mitsubishi
FX device Type.
2.2.1
Unit Number
The Unit number must match the “unit number” (or “address”) set in the PLC.
2.2.2
Use RS-485 Port
If you are using the Programming po rt set Use RS-485 Port to 0, if you are
using an expansion board set Use RS-485 to 1.
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 12
WebAccess Configuration Manual
2.3
Mitsubishi FX2N
Tag
You can now access to the memory addresses of you PLC using “Add tag”.
2.3.1
Parameter
The parameter gives the type of tag you want to import. Try to select a
parameter as close to the tag type as possible because it will fill the other
option with the default parameters.
In Mitsubishi FX we made a parameter for each type of data available in the
PLC.
2.3.2
Address
For Mitsubishi FX the address starts with the data type (X for input, Y for
output…) and is followed by the byte and bit position of the data (X000 to
X007 then X010 to X017 and so on) for I/O and the position in the memory
for memory types (type M).
2.3.3
Scaling Type
If the data sent by the module is not in a human readable unit you can use
the scaling to change the unit and display a more convenient unit in the node.
In most cases a linear scaling type will be sufficient.
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 13
WebAccess Configuration Manual
2.4
Mitsubishi FX2N
Main Parameter List
Parameter
Description
Address
Start
Bit
Length
X
Digital Input
X000
0
1
Y
Digital Output
Y000
0
1
M
Internal Relay
M0000
0
1
D
Data Register
D000
0
16
S
Internal Status
S0000
0
1
TEXT
Data Register String
D0000
0
12
CN
Current Counter Value
CN000
0
16
CR
Counter Reset
CR000
0
1
CS
Counter Contacts
CS000
0
1
TN
Current Timer Value
TN000
0
16
TR
Timer Reset
TR000
0
1
TS
Timer Contacts
TS000
0
1
Version 7.0 rev 0a
Ad vantech Corp., Ltd.
page 14