File S789 Project 04ME15779 December 20, 2005 REPORT on CONTROL UNIT (UOJZ) * * * * * * * * * * * * * * * * * * * * * Complementary Product Categories CENTRAL STATION ALARM UNITS (AMCX, AMCX7) POLICE STATION ALARM UNITS (APAW, APAW7) Alarm Device Manufacturing Co. Syosset, NY Copyright © 2005 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above named company to reproduce this Report provided it is reproduced in its entirety. File S789 Vol. 24 Sec. 2 and Report Page 1 Issued: 2005-12-20 DESCRIPTION PRODUCT COVERED: USL, CNL - Control unit Model 7810iR-ent Internet Central Station Receiver. The Model 7810iR-ent ("AlarmNet") Internet Central Station Receiver when used with or without the separately Listed Model 685 digital receiver and associated protected premises units in order to provide central station fire for USL and burglar alarm service for USL/CNL. Can also provide PoliceConnect service. For Central Station Fire Alarm Service, the Model 7810iR-ent must connect to a UL Listed Receiver/Central Station Automation System (Protective Signaling Service) which automatically annunciates unrestored, off-normal conditions during the 24 hour test report. Models 7810iR-ent is NIST Certified for encryption and are used in conjunction with models 7845i, 7845i-Ent, 8132 and 8142 premise equipment to provide encrypted line security. ENGINEERING CONSIDERATION: General - The product covered by this Report forms a portion of the Alarm Net I System. The unit allows the Listed 685 Receiver to connect to the internet to receive alarm signals from Alarm Net I or may be utilized as a stand alone Central Station Receiver. Remote Access features have not been evaluated by UL. This unit is to be powered by an appropriately rated Listed Commercial Fire Alarm Power Supply or UPS. See Installation Instructions for Power Supply ratings. Ratings - The 7810iR – ENT unit is rated as follows: 12.0 Vdc 400 mA Component Servicing - All high-voltage parts within the units are insulated to prevent unintentional contact by service personnel. Evaluated in accordance with the following Standards: 1. UL 864 Eighth ("Control Unit for Fire Protective Signaling Systems"). 2. UL1610 (Central Station Alarm Units) 3. UL 365 ("Police Station-Connected Burglar Alarm Units and System"). 4. CAN/ULC-S304-M88 - Standard for Central and Monitoring Station Burglar Alarm Units. 5. NFPA 70 ("National Electrical Code"). 6. NFPA 72 National Fire Alarm Code. 7. In accordance with the requirements of the equipment installation literature and installation wiring diagram. 8. In accordance with any additional requirements imposed by the local authority having jurisdiction. File S789 Vol. 24 Sec. 2 and Report Page 2 Issued: 2005-12-20 CONSTRUCTION DETAILS: General - The general product design, shape and arrangement shall conform to that shown in the following photographs and associated descriptive pages, and the general product construction shall adhere to the following guidelines unless otherwise specifically indicated. Corrosion Protection - All ferrous metal parts shall be painted, plated or otherwise suitably coated to resist corrosion. Internal Wiring - All internal wiring shall be Labeled Appliance Wiring Material having 1/64 in. (0.04 mm) minimum insulation wall thickness or the equivalent, rated 300 V minimum and a temperature rating consistent with the intended operating environment. The wiring shall be arranged in an orderly fashion, routed away from moving parts and sharp projections and held in place with clamps, string ties or the equivalent unless of sufficient rigidity to maintain a shaped form. All internal wiring shall be routed, cabled and clamped as shown in the following photographs unless otherwise specifically indicated. Splice Connections - All splices and electrical connections shall be made mechanically secure and bonded electrically by soldering or by the use of Component Recognized splicing devices (wire connectors). A splice shall be provided with insulation equivalent to that of the wires involved if permanence of spacings between the splice and uninsulated metal parts is not assured. (See Spacings.) Splices shall be located, enclosed and supported so that the splice is not subject to damage, flexing, motion or vibration. Solder Connections - All joints and connections shall be made mechanically secure by twisting, bending, crimping or the like prior to soldering. File S789 Vol. 24 Sec. 2 and Report Page 3 Issued: 2005-12-20 Printed Wiring Boards - All printed wiring boards utilized in this product shall be fabricated of Recognized Component Printed Wiring Material (ZPMV2) having 1/16 in. (1.6 mm) nominal material thickness, a flammability rating of min 94V-2 and an operating temperature rating of 105°C or greater. If wave soldering techniques are employed, the solder bath temperature and duration as specified in the Recognition for the particular material being utilized shall not be exceeded. MARKING: General - All markings shall be plainly and permanently applied to a location readily visible after installation. They may be on the outside of the unit or may be behind a door or cover which may be opened or removed after installation. All markings shall utilize Recognized Component Marking and Labeling System Material (PGGU2). Nameplate - Contains Listee's name or registered trademark, model number designation, date code, reference to applicable NFPA Standards and reference to installation wiring diagram by drawing number and/or issue date. Controls - All user operated controls shall be adjacently marked to indicate function and position. Indicators - All visual indicators shall be adjacently marked to indicate function (exception LED’s on right side of display are not utilized). The following markings shall also be provided: Electrical Ratings “Terminals 1-9 are power limited” “For dry, indoor use only.” “Do not install in air-handling spaces” “For wiring information, See instructions K9581V2” Installation Wiring Terminals - The installation wiring terminals shall be adjacently marked to correspond with the installation wiring diagram and installation instructions unless complete installation instructions are provided at the installation wiring terminals. INSTALLATION LITERATURE: Installation Manual/Instructions for Model 7810iR-ent Rev A, Dated: 8/05. Designated K9581 File S789 Vol. 24 Sec. 2 and Report Page 4 MODEL 7810iR Issued: 2005-12-20 FIG. 1 (M02-0017928) FIG. 1A (M02-0017929) 1. Enclosure - R/C (QMFZ2), ABS, Cycolac PLN6000, GE Plastics, 94V-0. (tested to the requirements for the 5 inch flame test in File S1632 Report 8/1/01). 206 x 50 x 12 mm. Min 2.3 mm thick. 2. Enclosure Back - Same as above 206 x 50 x 25 mm. Provided with a 63 x 45 mm opening for wiring, 4 keyhole slots for wall mounting, and 8 additional oblong holes for optional mounting methods. 3. PWB – See construction details - Marked K5856 Rev 2. 4. LCD Screen - Sharp Liquid Crystal Display Model LM057QCTT03 5. High Voltage Transformer T2 - Cooper Electronic Technologies Model K4125 rated 900 V ac out. See Illustration 2 for details. 6. Transformer T1 - Designated K4159, marked CTX02-14121. Coated copper wire wound on thermoplastic bobbin. Dimensions 11 mm x 5.5 mm. See Illustration 2 for details 7. Inductor L1 - Designated K4127, Coiltronics, Type CTX100-4 rated 100 mH. 8. Transformer T3 - Designated K4126, marked CTX02-12403. Coated copper wire wound on thermoplastic bobbin. Dimensions 11 mm x 5.5 mm. See Illustration 2 for details. 9. Varistors - MOV1 to MOV8 – (Designated N20-MOV22-1.5J) Mfg. by KekoVaricon Type ZV14K1210501R1, rated 22 V, 1.5 J. 10. Micro U7 - Designated N40-34119, Intel Type KU80386EX25. 11. RJ45 Connector - R/C (DUXR2) 8 pin, soldered to PWB. 12. Insulation Sheet - Marked K5132V1 positioned over High Voltage circuit for display. Constructed of Kraft Paper min 0.90 mm thick, "Marked Warning High Voltage" 13. Software ( for encryption ) – Alarm-Neti AES Encryption Software Module Version 1.0 14. Capacitors – See Illustration 3 for voltage and temperature ratings for all capacitors which shall be verified. All voltage and temperature ratings are considered minimum ratings and any decrease in voltage or temperature ratings requires further evaluation. 15. 9 pin terminal block connector – R/C XCFR2 rated min. 20 Vdc, Min 1 A. 16. Isolation Transformer (U28 – Mfg. by Pulse Type PE-68026. Alternate – Mfg. by Tamura Type TTC-8157