Lighting Control Catalog

Lighting Contactors
Catalog Supplement 2012
Control Products
www.usa.siemens.com/controls
Lighting Contactors
Siemens comprehensive line of lighting contactors offer a wide
range of control solutions for lighting applications. These
contactors can be used individually for simple control schemes
or as integral components in full-featured lighting control
systems. They provide reliable and efficient means of local
or remote switching of lighting as well as non-inductive loads.
Rugged construction, heavy-duty ratings and a wide selection
of control options and accessories makes the Siemens lighting
and heating contactors the right choice for your applications.
Contents
Class LE Electrically Held Lighting Contactors
Features
Catalog numbering system
Selection
Technical Data
2
3
4-5
6-7
Class LC Electrically Held Lighting Contactors
(convertible to mechanically held)
Features
Catalog numbering system
Selection
Technical data
8
9
10 - 11
12
Accessories, factory mods and replacement parts
Dimensions
Wiring diagrams
13 - 16
17 - 21
22 - 24
Class CLM mechanically held lighting contactors are
not included in this supplemental catalog. Please refer
to either Speedfax PDPC-01000 or Industrial Control
CPPC-06000 catalogs.
This supplemental catalog to be discontinued once the
Speedfax and Industrial Control catalogs have been
updated with the new Class LE and Class LC products.
Lighting Control Supplement 2012
Typical applications include:
• Schools
• Hospitals
• Office buildings
• Industrial plants
• Hotels
• Shopping centers
• Airports
• Stadiums
• Resistive heaters
Class LE Electrically Held Lighting Contactors
Features
The new Siemens Class LE lighting contactors is the latest
generation of our lighting contactors. Simplicity and its
compact lightweight design makes this an attractive solution
to your budgeting challenges.
• Used in applications where it is not critical that contacts
remain closed if control power is lost
• Rated for tungsten lighting (incandescent filament), ballast
lighting (fluorescent, HID, metal halide, mercury vapor, quartz
halogen and sodium-lamp), resistive and general use loads
• Contacts are rated 20 - 400 amps at 600 volts
• Wide range of coil voltages from 24 to 600 VAC 50/60Hz
• Compact design allows for smaller panels and more
wiring room
• Finger and back-of-hand safe terminals
• Panel and DIN rail mounting
• 3 and 4 pole (up to 12 pole for 30 and 60 amp contactors)
• Full line of enclosures including NEMA 1, 3/3R, 4, 4/4X
stainless steel and 12
• Most contactors have built-in auxiliary contacts for convenient
3-wire control
• Available in combination form with choice of non-fusible
disconnect, fusible disconnect or circuit breaker
• Full line of factory and field modifications
2
Lighting Catalog Supplement 2012
Class LE Electrically Held Lighting Contactors
Catalog Numbering System
LE
0
Disconnect Type
B = Combination Circuit Breaker
D = Combination Non-Fused Disconnect
F = Combination Fusible Disconnect
N = Non-Combination
Disconnect Rating
0 = N/A
A = 30A/250V Disconnect
B = 30A/600V Disconnect
C = 60A/250V Disconnect
D = 60A/600V Disconnect
E = 100A/250V Disconnect
F = 100A/600V Disconnect
G = 200A/250V Disconnect
H = 200A/600V Disconnect
J = 400A/250V Disconnect
K = 400A/600V Disconnect
T = 20A Circuit Breaker
V = 30A Circuit Breaker
Y = 60A Circuit Breaker
Z = 100A Circuit Breaker
Enclosure Type
0 = Open
1 = NEMA 1
2 = NEMA 12/3R
4 = NEMA 4/4X SS
Contactor Rating (Amp)
B = 20
C = 30
D = 60
E = 100
F = 200
G = 300
H = 400
N.C. Poles
0 = None
N.O. Poles
03 = Three
04 = Four
06 = Six
09 = Nine
12 = Twelve
Coil Voltage (AC 60Hz)
024 = 24
120 = 120
208 = 208
240 = 240
277 = 277
347 = 347
480 = 480
600 = 600
Series
A = 200 – 400A Contactors
B = 20 – 100A Contactors
Lighting Catalog Supplement 2012
3
Class LE Electrically Held Lighting Contactors
Selection
Coil Table
VAC 60Hz
***
24
024
120
120
208
208
240
240
277
277
347 1)
347
480
480
600
600
Replace the (***)
with a number from
the coil table.
Non-Combination Contactor
Max. Amp
Rating
Number
of Poles
Normally
Closed
Contacts
Normally
Open
Contacts
Enclosure Type
Open
1
3/3R/12 2)
4/4X 304 S.S.
LEN04B003***B
Catalog Number
3
0
3
LEN00B003***B
LEN01B003***B
LEN02B003***B
4
0
4
LEN00B004***B
LEN01B004***B
LEN02B004***B
LEN04B004***B
3
0
3
LEN00C003***B
LEN01C003***B
LEN02C003***B
LEN04C003***B
4
0
4
LEN00C004***B
LEN01C004***B
LEN02C004***B
LEN04C004***B
6
0
6
LEN00C006***B
LEN01C006***B
LEN02C006***B
LEN04C006***B
9
0
9
LEN00C009***B
LEN01C009***B
LEN02C009***B
LEN04C009***B
12
0
12
LEN00C012***B
LEN01C012***B
LEN02C012***B
LEN04C012***B
3
0
3
LEN00D003***B
LEN01D003***B
LEN02D003***B
LEN04D003***B
6
0
6
LEN00D006***B
LEN01D006***B
LEN02D006***B
LEN04D006***B
9
0
9
LEN00D009***B
LEN01D009***B
LEN02D009***B
LEN04D009***B
12
0
12
LEN00D012***B
LEN01D012***B
LEN02D012***B
LEN04D012***B
100
3
0
3
LEN00E003***B
LEN01E003***B
LEN02E003***B
LEN04E003***B
200
3
0
3
LEN00F003***A
LEN01F003***A
LEN02F003***A
LEN04F003***A
300
3
0
3
LEN00G003***A
LEN01G003***A
LEN02G003***A
LEN04G003***A
400
3
0
3
LEN00H003***A
LEN01H003***A
LEN02H003***A
LEN04H003***A
20
30
60
1)
2)
4
Not available on 200 - 400A contactors.
Type 12 field convertible to type 3/3R.
Lighting Catalog Supplement 2012
Class LE Electrically Held Lighting Contactors
Selection
Coil Table
VAC 60Hz
***
24
024
120
120
208
208
240
240
277
277
347 1)
347
480
480
600
600
Replace the (***)
with a number from
the coil table.
Combination Contactor
Disconnect Type
Non-Fusible
Max.
Amp
Rating
Disc.
Amp
Rating
Enclosure Type
Disc Amp/
Fuse Clip
Rating
Circuit
Breaker
Rating
Catalog Number
1
3/3R/12 2), 4 3)
4/4X 304 S.S.
20
3
30A
—
—
LEDB1B003***B
LEDB2B003***B
LEDB4B003***B
30
3
30A
—
—
LEDB1C003***B
LEDB2C003***B
LEDB4C003***B
60
3
60A
—
—
LEDD1D003***B
LEDD2D003***B
LEDD4D003***B
100
3
100A
—
—
LEDF1E003***B
LEDF2E003***B
LEDF4E003***B
200
3
200A
—
—
LEDH1F003***A
LEDH2F003***A
LEDH4F003***A
300
3
400A
—
—
LEDK1G003***A
LEDK2G003***A
LEDK4G003***A
3
—
30A/250V
—
LEFA1B003***B
LEFA2B003***B
LEFA4B003***B
3
—
30A/600V
—
LEFB1B003***B
LEFB2B003***B
LEFB4B003***B
3
—
30A/250V
—
LEFA1C003***B
LEFA2C003***B
LEFA4C003***B
3
—
30A/600V
—
LEFB1C003***B
LEFB2C003***B
LEFB4C003***B
3
—
60A/250V
—
LEFC1D003***B
LEFC2D003***B
LEFC4D003***B
3
—
60A/600V
—
LEFD1D003***B
LEFD2D003***B
LEFD4D003***B
3
—
100A/250V
—
LEFE1E003***B
LEFE2E003***B
LEFE4E003***B
3
—
100A/600V
—
LEFF1E003***B
LEFF2E003***B
LEFF4E003***B
3
—
200A/250V
—
LEFG1F003***A
LEFG2F003***A
LEFG4F003***A
3
—
200A/600V
—
LEFH1F003***A
LEFH2F003***A
LEFH4F003***A
3
—
400A/250V
—
LEFJ1G003***A
LEFJ2G003***A
LEFJ4G003***A
—
20
30
60
Fusible
100
200
300
Circuit Breaker
Number
of NO
Poles
3
—
400A/600V
LEFK1G003***A
LEFK2G003***A
LEFK4G003***A
20
3
—
—
20A
LEBT1B003***B
LEBT2B003***B
LEBT4B003***B
30
3
—
—
30A
LEBV1C003***B
LEBV2C003***B
LEBV4C003***B
60
3
—
—
60A
LEBY1D003***B
LEBY2D003***B
LEBY4D003***B
100
3
—
—
100A
LEBZ1E003***B
LEBZ2E003***B
LEBZ4E003***B
Not available on 200 - 400A contactors.
Type 12 field convertible to type 3/3R.
3) Type 4 painted enclosure through 100 Amp only.
1)
2)
Lighting Catalog Supplement 2012
5
Class LE Electrically Held Lighting Contactors
Technical Data
Contactor
General technical data:
Finger-safe (main circuit / control circuit)
Degree of pollution
Altitude (m)
Ambient storage temperature (°C)
Ambient operating temperature (°C)
Humidity (% non-condensing)
Shock resistance at rectangular impulse (g/ms)
Shock resistance at sine pulse (g/ms)
Rated impulse voltage resistance (kV)
Rated insulation voltage (V)
Mechanical operating cycles as operating time:
of contactor
of contactor with additional aux contacts
Main circuit:
Number of NC / NO main contacts
Typical power loss per conductor (W)
Off-load operating frequency (cycles per hour)
Current ratings:
Tungsten (poles per phase)
Ballast (poles per phase)
General and resistive (poles per phase)
Coil ratings:
Nominal voltage
Inrush / sealed power (VA)
Coil voltage tolerance factor
Internal/standard auxiliary contact:
Number of NC / NO auxiliary contacts
Rating
Installation/mounting/dimensions:
Mounting orientation
Type of mounting: screw / DIN rail
Height x Width x Depth (mm)
Minimum clearance to sides (mm)
Minimum clearance to earthed parts (mm)
Connection type / torque for main circuit terminals
Connection type / torque for control circuit terminals
Solid and stranded conductors for
main contacts (AWG)
Solid and stranded conductors for
control circuit (AWG)
Conductor type for main and control circuits
Short circuit current rating of main circuit:
Short circuit current rating
Max fuse / circuit breaker (Amp)
Certificates:
1) Must
2) Refer
6
use an external (optional) auxiliary contact.
to catalog selection tables for coil voltages.
Lighting Catalog Supplement 2012
LEN00B003
LEN00B004
LEN00C003
LEN00C004
yes / yes
3
2,000
-55 to 80
0 to 40
10 to 95
6.7 / 5, 4.2 / 10
10.5 / 5, 6.6 / 10
no data
no data
yes / yes
3
2,000
-55 to 80
0 to 40
10 to 95
6.7 / 5, 4.2 / 10
10.5 / 5, 6.6 / 10
no data
no data
yes / yes
3
2,000
-55 to 80
0 to 40
10 to 95
7.5 / 5, 4.7 / 10
11.8 / 5, 7.4 / 10
no data
no data
yes / yes
3
2,000
-55 to 80
0 to 40
10 to 95
7.5 / 5, 4.7 / 10
11.8 / 5, 7.4 / 10
no data
no data
30,000,000
10,000,000
30,000,000
10,000,000
10,000,000
10,000,000
10,000,000
10,000,000
0NC / 3NO
0.7
10,000
0NC / 4NO
0.7
10,000
0NC / 3NO
0.9
5,000
0NC / 4NO
0.9
5,000
20A @277V 1p 1ph
20A @480V 2p 1ph
20A @480V 3p 3ph
20A @347V 1p 1ph
20A @600V 2p 1ph
20A @600V 3p 3ph
20A @600V 1p 1ph
20A @600V 2p 1ph
20A @600V 3p 3ph
20A @277V 1p 1ph
20A @480V 2p 1ph
20A @480V 3p 3ph
20A @347V 1p 1ph
20A @600V 2p 1ph
20A @600V 3p 3ph
20A @600V 1p 1ph
20A @600V 2p 1ph
20A @600V 3p 3ph
30A @277V 1p 1ph
30A @480V 2p 1ph
30A @480V 3p 3ph
30A @347V 1p 1ph
30A @600V 2p 1ph
30A @660V 3p 3ph
30A @600V 1p 1ph
30A @600V 2p 1ph
30A @600V 3p 3ph
30A @277V 1p 1ph
30A @480V 2p 1ph
30A @480V 3p 3ph
30A @347V 1p 1ph
30A @600V 2p 1ph
30A @600V 3p 3ph
30A @600V 1p 1ph
30A @600V 2p 1ph
30A @600V 3p 3ph
2)
2)
2)
2)
31.7 / 4.8
0.8 - 1.1
31.7 / 4.8
0.8 - 1.1
87 / 9.4
0.8 - 1.1
87 / 9.4
0.8 - 1.1
0NC / 1NO
A600 / Q600
NA1)
NA
1NC / 1NO
A600 / Q600
1NC / 1NO
A600 / Q600
vertical
yes / yes
57.5 x 45 x 73
0
6
screw / 7-10 lb in
screw / 7-10 lb in
vertical
yes / yes
57.5 x 45 x 73
0
6
screw / 7-10 lb in
screw / 7-10 lb in
vertical
yes / yes
85 x 45 x 97
0
6
screw / 18-22 lb in
screw / 7-10 lb in
vertical
yes / yes
85 x 60 x 97
0
6
screw / 18-22 lb in
screw / 7-10 lb in
2x(20-16),
2x(18-14), 2x(12)
2x(20-16),
2x(18-14)
75°C CU
2x(20-16),
2x(18-14), 2x(12)
2x(20-16),
2x(18-14)
75°C CU
2x(6-12),
2x(14-8)
2x(20-16),
2x(18-14)
75°C CU
2x(6-12),
2x(14-8)
2x(20-16),
2x(18-14)
75°C CU
5kA @ 600V
30 / 25
UL, CSA
5kA @ 600V
30 / 25
UL, CSA
5kA @ 600V
60 / 40
UL, CSA
5kA @ 600V
60 / 40
UL, CSA
Class LE Electrically Held Lighting Contactors
Technical Data
LEN00D003
LEN00E003
LEN00F003
LEN00G003
LEN00H003
no / yes
3
2,000
-55 to 80
0 to 40
10 to 95
10 / 5, 5 / 10
15 / 5, 8 / 10
no data
no data
no / yes
3
2,000
-55 to 80
0 to 40
10 to 95
6.8 / 5, 4 / 10
10.6 / 5, 6.2 / 10
no data
no data
no / yes
3
2,000
-55 to 80
0 to 40
10 to 95
8.5 / 5, 4.2 / 10
13.4 / 5, 6.5 / 10
no data
no data
no / yes
3
2,000
-55 to 80
0 to 40
10 to 95
8.5 / 5, 4.2 / 10
13.4 / 5, 6.5 / 10
no data
no data
no / yes
3
2,000
-55 to 80
0 to 40
10 to 95
8.5 / 5, 4.2 / 10
13.4 / 5, 6.5 / 10
no data
no data
10,000,000
10,000,000
10,000,000
10,000,000
10,000,000
10,000,000
10,000,000
10,000,000
10,000,000
10,000,000
0NC / 3NO
2.6
5,000
0NC / 3NO
7.7
5,000
0NC / 3NO
13
2,000
0NC / 3NO
18
2,000
0NC / 3NO
35
2,000
60A @277V 1p 1ph
60A @480V 2p 1ph
60A @480V 3p 3ph
60A @600V 1p 1ph
60A @600V 2p 1ph
60A @600V 3p 3ph
60A @600V 1p 1ph
60A @600V 2p 1ph
60A @600V 3p 3ph
100A @277V 1p 1ph
100A @480V 2p 1ph
100A @480V 3p 3ph
100A @600V 1p 1ph
100A @600V 2p 1ph
100A @600V 3p 3ph
100A @600V 1p 1ph
100A @600V 2p 1ph
100A @600V 3p 3ph
200A @277V 1p 1ph
200A @480V 2p 1ph
200A @480V 3p 3ph
200A @600V 1p 1ph
200A @600V 2p 1ph
200A @600V 3p 3ph
200A @600V 1p 1ph
200A @600V 2p 1ph
200A @600V 3p 3ph
300A @277V 1p 1ph
300A @480V 2p 1ph
300A @480V 3p 3ph
300A @600V 1p 1ph
300A @600V 2p 1ph
300A @600V 3p 3ph
300A @600V 1p 1ph
300A @600V 2p 1ph
300A @600V 3p 3ph
400A @277V 1p 1ph
400A @480V 2p 1ph
400A @480V 3p 3ph
400A @600V 1p 1ph
400A @600V 2p 1ph
400A @600V 3p 3ph
400A@600V 1p 1ph
400A @600V 2p 1ph
400A @600V 3p 3ph
2)
2)
2)
2)
2)
166 / 12.6
0.8 - 1.1
300 / 21
0.8 - 1.1
300 / 5.8
0.8 - 1.1
590 / 6.7
0.8 - 1.1
830 / 9.2
0.8 - 1.1
NA 1)
NA
NA 1)
NA
2NC / 2NO
A300 / Q300
2NC / 2NO
A300 / Q300
2NC / 2NO
A300 / Q300
vertical
yes / yes
112 x 55 x 115
6
6
screw / 27-40 lb in
screw / 7-10 lb in
vertical
yes / yes
146 x 70 x 139
6
6
screw / 36-53 lb in
screw / 7-10 lb in
vertical
yes / no
172 x 120 x 180
10
10
screw / 90-110 lb in
screw / 7-10 lb in
vertical
yes / no
210 x 145 x 202
10
10
screw / 180-195 lb in
screw / 7-10 lb in
vertical
yes / no
214 x 160 x 225
10
10
screw / 180-195 lb in
screw / 7-10 lb in
2x(18-3),
1x(18-2)
2x(18-14)
2x(10-1/0),
1x(10-2/0)
2x(18-14)
2x(6-3/0)
2x(2/0-500MCM)
2x(2/0-500MCM)
2x(18-14)
2x(18-14)
2x(18-14)
75°C CU
75°C CU
75°C CU
75°C CU
75°C CU
5kA @ 600V
100 / 80
UL, CSA
10kA @ 600V
200 / 125
UL, CSA
10kA @ 600V
400 / 250
UL, CSA
18kA @ 600V
600 / 400
UL, CSA
18kA @ 600V
800 / 500
UL, CSA
Lighting Catalog Supplement 2012
7
Class LC Electrically Held Lighting Contactors
Features
Siemens expands upon its lighting contactor offering with the
new Class LC lighting contactor. These lighting contactors
deliver unprecedented versatility in application, simplicity in
Convenient side access field
power wiring.
configuration and performance in operation. Ingenious design,
rugged construction and a host of truly useful features make
them uniquely appealing to all those who use them.
Contact position indication – when
button protrudes, contact is closed .
Power poles can easily be added at
any time based on changing needs.
Furthermore, they may be converted
from NO to NC (or vice versa) simply
by repositioning.
A simple kit easily converts
electrically held units to
mechanically held and
includes a 2- or 3-wire
control module.
Standard base enables contactor
to be field expandable for
flexibility and future needs.
Plug-in auxiliary contacts
are NO when installed on
the left side of the contactor,
NC on the right.
Finger and back-of-hand
safe terminals.
• Used in all applications where either electrically or mechanically
held contactors are specifically suited and also ideal for
maximum flexibility and future expansion
• Can be ordered as either electrically or mechanically held and can
also be converted from electrically to mechanically held in the
field with a simple conversion kit
• Rated for tungsten lighting (incandescent filament), ballast
lighting (fluorescent, HID, metal halide, mercury vapor, quartz
halogen and sodium-lamp), resistive and general use loads
• Modular design enables you to stock the building block
components to assemble all configurations of both the
electrically and mechanically held contactors thus dramatically
reducing inventory
• Contacts are rated up to 30 amps at 600 volts
• Up to 12 poles (maximum of 8 normally closed)
• Wide range of coil voltages from 24 to 600 VAC 50/60Hz
• Full line of enclosures including NEMA 1, 3/3R, 4, 4/4X stainless
steel and 12
• Full line of factory and field modifications
8
Lighting Catalog Supplement 2012
Class LC Electrically Held Lighting Contactors
Catalog Numbering System
LC
E0
C
A
Controller Type
E0 = Electrically Held
(Convertible to MH)
Enclosure Type
0 = Open
1 = NEMA 1
2 = NEMA 12/3R
4 = NEMA 4/4X Stainless Steel
Contactor Rating (Amp)
C = 30
N.C. Poles
0 = None
1 = One
2 = Two
3 = Three
4 = Four
5 = Five
6 = Six
7 = Seven
8 = Eight
N.O. Poles
00 = None
01 = One
02 = Two
03 = Three
04 = Four
05 = Five
06 = Six
07 = Seven
08 = Eight
09 = Nine
10 = Ten
11 = Eleven
12 = Twelve
Coil Voltage
024 = 24V 60Hz / 20V 50Hz
120 = 115-120V 60Hz / 110V 50Hz
208 = 200-208V 60Hz
240 = 230-240V 60Hz / 220V 50Hz
277 = 277V 60Hz / 240V 50Hz
347 = 347V 60Hz
480 = 460-480V 60Hz / 440V 50Hz
600 = 575-600V 60Hz / 550V 50Hz
Lighting Catalog Supplement 2012
9
Class LC Electrically Held Lighting Contactors
Selection
• To order standard electrically held contactor, simply
select catalog number from tables below.
Coil Table
VAC 60Hz
***
• To order mechanically held contactor, select catalog
number from tables below and specify conversion
module from factory modification section from page 14.
24
024
• To convert standard electrically held contactor to
mechanically held in the field, select catalog number
from tables below and select conversion module kit
from page 15.
240
240
277
277
347
347
480
480
600
600
120
120
208
208
Replace the (***) with
a number from the
coil table.
Non-Combination Contactor (30 Amp max.)
Enclosure Type
No. of Poles
N.C.
Open
N.O.
1
3/3R/12 1)
4/4X 304 S.S.
Catalog Number
2
LCE00C200***A
LCE01C200***A
LCE02C200***A
LCE04C200***A
3
LCE00C300***A
LCE01C300***A
LCE02C300***A
LCE04C300***A
4
LCE00C400***A
LCE01C400***A
LCE02C400***A
LCE04C400***A
LCE00C500***A
LCE01C500***A
LCE02C500***A
LCE04C500***A
6
LCE00C600***A
LCE01C600***A
LCE02C600***A
LCE04C600***A
7
LCE00C700***A
LCE01C700***A
LCE02C700***A
LCE04C700***A
8
LCE00C800***A
LCE01C800***A
LCE02C800***A
LCE04C800***A
1
LCE00C101***A
LCE01C101***A
LCE02C101***A
LCE04C101***A
2
LCE00C201***A
LCE01C201***A
LCE02C201***A
LCE04C201***A
3
LCE00C301***A
LCE01C301***A
LCE02C301***A
LCE04C301***A
4
LCE00C401***A
LCE01C401***A
LCE02C401***A
LCE04C401***A
LCE00C501***A
LCE01C501***A
LCE02C501***A
LCE04C501***A
6
LCE00C601***A
LCE01C601***A
LCE02C601***A
LCE04C601***A
7
LCE00C701***A
LCE01C701***A
LCE02C701***A
LCE04C701***A
8
LCE00C801***A
LCE01C801***A
LCE02C801***A
LCE04C801***A
0
LCE00C002***A
LCE01C002***A
LCE02C002***A
LCE04C002***A
1
LCE00C102***A
LCE01C102***A
LCE02C102***A
LCE04C102***A
2
LCE00C202***A
LCE01C202***A
LCE02C202***A
LCE04C202***A
3
LCE00C302***A
LCE01C302***A
LCE02C302***A
LCE04C302***A
LCE00C402***A
LCE01C402***A
LCE02C402***A
LCE04C402***A
5
LCE00C502***A
LCE01C502***A
LCE02C502***A
LCE04C502***A
6
LCE00C602***A
LCE01C602***A
LCE02C602***A
LCE04C602***A
7
LCE00C702***A
LCE01C702***A
LCE02C702***A
LCE04C702***A
8
LCE00C802***A
LCE01C802***A
LCE02C802***A
LCE04C802***A
0
LCE00C003***A
LCE01C003***A
LCE02C003***A
LCE04C003***A
1
LCE00C103***A
LCE01C103***A
LCE02C103***A
LCE04C103***A
2
LCE00C203***A
LCE01C203***A
LCE02C203***A
LCE04C203***A
3
LCE00C303***A
LCE01C303***A
LCE02C303***A
LCE04C303***A
LCE00C403***A
LCE01C403***A
LCE02C403***A
LCE04C403***A
5
LCE00C503***A
LCE01C503***A
LCE02C503***A
LCE04C503***A
6
LCE00C603***A
LCE01C603***A
LCE02C603***A
LCE04C603***A
7
LCE00C703***A
LCE01C703***A
LCE02C703***A
LCE04C703***A
8
LCE00C803***A
LCE01C803***A
LCE02C803***A
LCE04C803***A
5
5
4
4
0
1
2
3
1)
Type 12 field convertible to Type 3/3R.
10
Lighting Catalog Supplement 2012
Class LC Electrically Held Lighting Contactors
Selection
Non-Combination Contactor (30 Amp max.)
Enclosure Type
No. of Poles
N.C.
Open
N.O.
1
3/3R/12 1)
4/4X 304 S.S.
Catalog Number
0
LCE00C004***A
LCE01C004***A
LCE02C004***A
LCE04C004***A
1
LCE00C104***A
LCE01C104***A
LCE02C104***A
LCE04C104***A
2
LCE00C204***A
LCE01C204***A
LCE02C204***A
LCE04C204***A
3
LCE00C304***A
LCE01C304***A
LCE02C304***A
LCE04C304***A
LCE00C404***A
LCE01C404***A
LCE02C404***A
LCE04C404***A
5
LCE00C504***A
LCE01C504***A
LCE02C504***A
LCE04C504***A
6
LCE00C604***A
LCE01C604***A
LCE02C604***A
LCE04C604***A
7
LCE00C704***A
LCE01C704***A
LCE02C704***A
LCE04C704***A
8
LCE00C804***A
LCE01C804***A
LCE02C804***A
LCE04C804***A
0
LCE00C005***A
LCE01C005***A
LCE02C005***A
LCE04C005***A
1
LCE00C105***A
LCE01C105***A
LCE02C105***A
LCE04C105***A
2
LCE00C205***A
LCE01C205***A
LCE02C205***A
LCE04C205***A
3
LCE00C305***A
LCE01C305***A
LCE02C305***A
LCE04C305***A
4
LCE00C405***A
LCE01C405***A
LCE02C405***A
LCE04C405***A
5
LCE00C505***A
LCE01C505***A
LCE02C505***A
LCE04C505***A
6
LCE00C605***A
LCE01C605***A
LCE02C605***A
LCE04C605***A
0
LCE00C006***A
LCE01C006***A
LCE02C006***A
LCE04C006***A
1
LCE00C106***A
LCE01C106***A
LCE02C106***A
LCE04C106***A
LCE00C206***A
LCE01C206***A
LCE02C206***A
LCE04C206***A
LCE00C306***A
LCE01C306***A
LCE02C306***A
LCE04C306***A
4
LCE00C406***A
LCE01C406***A
LCE02C406***A
LCE04C406***A
5
LCE00C506***A
LCE01C506***A
LCE02C506***A
LCE04C506***A
6
LCE00C606***A
LCE01C606***A
LCE02C606***A
LCE04C606***A
0
LCE00C007***A
LCE01C007***A
LCE02C007***A
LCE04C007***A
LCE00C107***A
LCE01C107***A
LCE02C107***A
LCE04C107***A
LCE00C207***A
LCE01C207***A
LCE02C207***A
LCE04C207***A
3
LCE00C307***A
LCE01C307***A
LCE02C307***A
LCE04C307***A
4
LCE00C407***A
LCE01C407***A
LCE02C407***A
LCE04C407***A
0
LCE00C008***A
LCE01C008***A
LCE02C008***A
LCE04C008***A
LCE00C108***A
LCE01C108***A
LCE02C108***A
LCE04C108***A
LCE00C208***A
LCE01C208***A
LCE02C208***A
LCE04C208***A
3
LCE00C308***A
LCE01C308***A
LCE02C308***A
LCE04C308***A
4
LCE00C408***A
LCE01C408***A
LCE02C408***A
LCE04C408***A
0
LCE00C009***A
LCE01C009***A
LCE02C009***A
LCE04C009***A
LCE04C109***A
4
4
5
2
3
6
1
2
7
1
2
1
8
9
LCE00C109***A
LCE01C109***A
LCE02C109***A
2
LCE00C209***A
LCE01C209***A
LCE02C209***A
LCE04C209***A
0
LCE00C010***A
LCE01C010***A
LCE02C010***A
LCE04C010***A
LCE00C110***A
LCE01C110***A
LCE02C110***A
LCE04C110***A
LCE00C210***A
LCE01C210***A
LCE02C210***A
LCE04C210***A
1
10
2
0
11
LCE00C011***A
LCE01C011***A
LCE02C011***A
LCE04C011***A
0
12
LCE00C012***A
LCE01C012***A
LCE02C012***A
LCE04C012***A
1)
Type 12 field convertible to Type 3/3R.
Lighting Catalog Supplement 2012
11
Class LC Electrically Held Lighting Contactors
Technical Data
General technical data:
Finger-safe (main circuit / control circuit)
yes / yes
Degree of pollution
3
Altitude (m)
2,000
Ambient storage temperature (°C)
-30 to 65
Ambient operating temperature (°C)
-25 to 40
Humidity (% non-condensing)
no data
Shock resistance at rectangular impulse (g/ms) no data
Shock resistance at sine pulse (g/ms)
no data
Rated impulse voltage resistance (kV)
no data
Rated insulation voltage (V)
600
Mechanical operating cycles as operating time:
of contactor
100,000
of contactor with additional aux contacts
100,000
Main circuit:
Number of main contacts
2 - 12 (maximum of 8 NC)
Typical power loss per conductor (W)
no data
Off-load operating frequency (cycles per hour) 60 for continued operation
Current ratings:
20A @277V 1p 1ph
Tungsten (poles per phase)
20A @480V 2p 1ph
20A @480V 3p 3ph
30A @347V 1p 1ph
Ballast (poles per phase)
30A @600V 2p 1ph
30A @600V 3p 3ph
30A @600V 1p 1ph
General and resistive (poles per phase)
30A @600V 2p 1ph
30A @600V 3p 3ph
Coil ratings:
Nominal voltage
(refer to coil voltage table)
Inrush / sealed power (VA)
248 / 28
Coil voltage tolerance factor
0.85 - 1.1
External/optional auxiliary contact:
Number of NC / NO auxiliary contacts
Rating
Installation/mounting/dimensions:
Mounting orientation
Type of mounting: screw / DIN rail
Height x Width x Depth (mm)
Minimum clearance to sides (mm)
Minimum clearance to earthed parts (mm)
Connection type / torque:
Main contact terminals
Coil terminals
Auxiliary contact terminals
Control module terminals
Solid and stranded conductors (AWG):
Main contact terminals
2NC / 2NO max
A600, 24VDC, 24VAC
vertical
yes / no
188 x 106 x 98
12.7
12.7
screw / 35 lb in
screw / 15 lb in
screw / 7-12 lb in
screw / 5 lb in
1x(14-8), #8 solid or stranded
2x(14-8), #8 stranded only
2x(18-14)
2x(22-12)
1x(22-12)
75°C CU / 60-75°C CU
Coil terminals
Auxiliary contact terminals
Control module terminals
Conductor type for main / control circuits
Short circuit current rating of main circuit:
Short circuit current rating
(see SCCR tables)
Certificates:
cUL, CE
12
Lighting Catalog Supplement 2012
Coil voltages:
24V 60Hz / 20V 50Hz
115-120V 60Hz / 110V 50Hz
200-208V 60Hz
230-240V 60Hz / 220V 50Hz
277V 60Hz / 240V 50Hz
347V 60Hz
460-480V 60Hz / 440V 50Hz
575-600V 60Hz / 550V 50Hz
Short circuit current ratings with fuses:
Max.
Volt.
Fuse
Max.
Device
Rating
(Amps)
600
RK fuse
60
SCCR
(kA)
100
Short circuit current ratings with circuit breakers:
Max.
Volt.
Siemens
Listed
Circuit
Breaker
Max.
Device
Rating
(Amps)
SCCR
(kA)
600
NGG3B040L
40
14
480
HEG3B040L
40
65
480
ED63B040L
40
25
480
NGG3B040L
40
25
Conversion module:
Input Volt.
(AC)
Steady State
Current @ Rated
Volts (mA)
Max.
VA
24
80
5
115-120
83
12
200-277
91
30
Conversion module:
Min. pulse duration (3-wire module)
250ms
Max. allowable leakage current
1.8 mA
EMI
35 V/m
Surge transient peak
6 kV
Frequency range
40-70 Hz
Accessories, Factory Mods & Replacement Parts
Selection
Push Buttons and
Selector Switches
Class
Enclosure type
Contactor
Size (Amp)
1 (non-combination)
20 - 100
1 (non-combination)
12, 4/4X (non-com.)
1, 12, 4/4X (com.)
200 - 400
20 - 400
20 - 400
Enclosure type
Contactor
Size (Amp)
All
Pilot Lights
Class
1 (non-combination)
1 (non-combination)
20 - 100
20 - 100
All
1 (non-combination)
12, 4/4X (non-com.)
1, 12, 4/4X (com.)
1, 12, 4/4X
Auxiliary
Contact Kits
200 - 400
20 - 400
20 - 400
All
Class
Enclosure type
Contactor
Size (Amp)
LC
Open, 1, 12, 4/4X
30
LE
Open, 1, 12, 4/4X
Description
Start, Stop Push Buttons
Hand-Off-Auto Selector Switch
Off-On Selector Switch
Start, Stop Push Buttons
Field Kit
Catalog No.
49SBPB5
49SBSB1
49SBSB4
49SAP05
Factory
Mod Suffix
A1
A3
A4
A1
Hand-Off-Auto Selector Switch
Keyed Hand-Off-Auto
Off-On Selector Switch
49SAS01
49SAS09
49SAS04
A3
A9
A4
Description
Field Kit
Catalog No.
Factory
Mod Suffix
Red On 24 VAC
49SBLBJ
Red On 120 VAC
49SBLBF
Red On 208/240/277 VAC
49SBLBG
Red On 347 VAC
NA
Red On 480 VAC
49SBLBH
Red On 600 VAC
49SBLBE
Green Off 24 VAC
49SBLBJ
Green Off 120 VAC
49SBLBF
Green Off 208/240/277 VAC
49SBLBG
Green Off 347 VAC
NA
Green Off 480 VAC
49SBLBH
Green Off 600 VAC
49SBLBE
Red On 24 VAC
49SPL0BRJ
Red On 120 VAC
49SPL0BRF
Red On 208/240 VAC
49SPL0BRG
Red On 277 or 347 VAC
NA
Red On 480 VAC
49SPL0BRH
Red On 600 VAC
49SPL0BRE
Green Off 24 VAC
49SPL0AGJ
Green Off 120 VAC
49SPL0AGF
Green Off 208/240 VAC
49SPL0AGG
Green Off 277 or 347 VAC
NA
Green Off 480 VAC
49SPL0AGH
Green Off 600 VAC
49SPL0AGE
FA
FK
FA
FK
Green On (all except 277 & 347 VAC)
FB
Red Off (all except 277 & 347 VAC)
FJ
Red On PTT (all except 277 & 347 VAC)
NA
FS
Grn On PTT (all except 277 & 347 VAC)
FT
Grn Off PTT (all except 277 & 347 VAC)
FU
Field Kit
Catalog No.
Factory
Mod Suffix
1 NO/NC
49LCAC1PA
G11
2 NO/NC
49LCAC2PA
G22
Description
20
Front Mounted 1 NO/NC
3RH2911-1HA11
G11
30
Side Mounted 1 NO/NC
3RH2911-1DA11
G11
60-400
Side Mounted 1 NO/NC
3RH1921-1DA11
G11
Lighting Catalog Supplement 2012
13
Accessories, Factory Mods & Replacement Parts
Selection
Power Pole Kits
Electrically Held
to Mechanically Held
Conversion Modules
Class
LC
Enclosure type
Open, 1, 12, 4/4X
Contactor
Size (Amp)
30
Class
Enclosure type
Contactor
Size (Amp)
LC
Miscellaneous Kits
Open, 1, 12, 4/4X
30
Class
Enclosure type
Contactor
Size (Amp)
All
1, 12, 4/4X
All
All
1, 12, 4/4X
All
1, 12, 4/4X
Description
Single power pole
Double power pole
Field Kit
Catalog No.
49LCPP1A
49LCPP2A
Factory
Mod Suffix
N/A
Description
Field Kit
Catalog No.
Factory
Mod Suffix
2-wire, 24VAC
49LCCM1A
M1
2-wire, 110-120VAC
49LCCM2A
M2
2-wire, 200-277VAC
49LCCM3A
M3
3-wire, 24VAC
49LCCM4A
M4
3-wire, 110-120VAC
49LCCM5A
M5
3-wire, 200-277VAC
49LCCM6A
M6
Field Kit
Catalog No.
Factory
Mod Suffix
Ground Lug Kit
Ground Lug Kit Meets CSA Standard
22.2 No 14-1973. 1 Conductor 2-14
For AL/CU Wire.
49D11960001
L10
All
Single pole control circuit fuse and
holder. 250V Midget fuse block for
domestic fusing.
KCCF1G
F1
All
Double pole control circuit fuse and
holder. Class CC 600V fuse block for
domestic fusing.
KCCFP2RG
F2
Description
Control relay with 4 NO contacts
Control relay with 2 NO/2 NC
All
1, 12, 4/4X
All
Control relay with 4 NC contacts
R40
(Refer to Industrial
Control Catalog
for selection)
R22
R04
24 hour time clock
T7
24 hour time clock with day omission
All
1, 12, 4/4X
All
7 day time clock
T8
N/A
T9
All
All
14
1, 12, 4/4X
1, 12, 4/4X
Lighting Catalog Supplement 2012
All
All
3 Point terminal
TC3
6 Point Terminal
(Refer to Industrial
Control Catalog
for selection)
TC6
N/A
N1
9 Point Terminal
Function identification plate, with
marking as specified
TC9
Accessories, Factory Mods & Replacement Parts
Selection
Control Power Transformers (Field Modification Kits)
Step 1
Recommended Minimum
Transformer Size
Step 2
Voltage Code
Contactor
Primary
Volts
CPT VA
Secondary
Volts
Code
Step 3
VA Rating
Catalog
Number
LC 30A 2-12P
45
120
24
1
45 VA
KT*050
LE 20,30,60A 3P
45
208
24
G
50 VA
KT*050P
LE 30A 6P
45
208
120
H
100 VA
KT*100
KT*150
LE 30A 9-12P
100
240/480
24
4
150 VA
LE 60A 6-9P
100
240/480
120
8
200 VA
KT*200
LE 60A 12P
150
277
24
5
300 VA
KT*300
LE 100,200A 3P
100
277
120
7
500 VA
KT*500
LE 300,400A 3P
150
600
24
6
600
120
9
To select CPT field kit:
1. Determine recommended minimum CPT size (VA) based on contactor size and poles.
2. Determine voltage code based on required CPT primary and secondary voltages.
3. Complete the catalog number by replacing the (*) with the voltage code.
45VA transformer kits will include secondary but not primary fusing. Sizes 50VA and
higher include 2-pole primary fusing and 1-pole secondary fusing.
Control Power Transformers (Factory Modification)
Class
AB
Enclosure
type
1, 12, 4/4X
Contactor
Size (Amp)
All
Step 1
Description
Step 3
Factory
Mod Suffix
Standard Capacity with 1-Secondary Fuse (45VA only)
B*
Standard Capacity with 2-Primary and 1-Secondary Fuse
D*
100VA Extra Capacity with 2-Primary and 1-Secondary Fuse
C*
150VA Extra Capacity with 2-Primary and 1-Secondary Fuse
C*1
To select CPT factory modification suffix:
1. Select factory mod suffix based on capacity requirements. Select extra capacity if
field installed devices will be powered from CPT. Otherwise, select standard capacity.
The factory will determine the actual size of the CPT.
2. Determine voltage code based on required CPT primary and secondary voltages.
3. Complete the mod suffix by replacing the (*) with the voltage code.
Step 2
Voltage Code
Primary
Volts
Secondary
Volts
Code
120
24
B
208
24
S
208
120
T
240
24
J
240
120
F
277
24
N
277
120
P
380
110
U
415
100
W
480
240
R
480/240
24
D
480/240
120
A
600
24
E
600
120
C
Lighting Catalog Supplement 2012
15
Accessories, Factory Mods & Replacement Parts
Selection
Enclosure Kits
Contactor
Type 1 1)
Type 4/4X Stainless Steel 2)
Type 3/3R/12 3)
Without CPT
With CPT
Max.
Without CPT
With CPT
Max. Without CPT
With CPT
Max
Catalog
Number
Catalog
Number
CPT
VA
Catalog
Number
Catalog
Number
CPT
VA
Catalog
Number
CPT
VA
49EC14GB140807R
49EC14IB201208R
200
49EB22GW161406R
49EB22GW161406R
49EB22G0161406R
49EB22G0161406R
LE 20, 30A 3-4P 49EC14EB110705R
49EC14IB201208R
200
49EB22GW161406R
49EB22GW161406R
49EB22G0161406R
49EB22G0161406R
LC 30A 2-12P
LE 30A 6-9P
49EC14IB201208R
49EC14IB201208R
200
49EB14JW261408R
49EB14JW261408R
LE 30A 12P
49EC14IB201208R
49EC14JB251409R
250
49EB14JW261408R
NA
LE 60A 3P
49EC14GB140807R
49EC14IB201208R
200
49EB22GW161406R
49EB22GW161406R
NA
LE 60A 6-9P
49EC14IB201208R
49EC14IB201208R
200
49EB14JW261408R
49EB14JW261408R
LE 60A 12P
49EC14IB201208R
49EC14JB251409R
250
49EB14JW261408R
NA
LE 100A 3P
49EC14IB201208R
49EC14IB201208R
200
49EB14JW261408R
49EB14JW261408R
NA
Hole plug for the cover overload reset button is included with enclosure.
Install NEMA 4X hole plug cat. no. 52ABHS (not included) over the hole for the overload reset button.
3) Install NEMA 12 hole plug cat. no. 52ABH6 (not included) over the hole for the overload reset button.
1)
2)
Replacement
Coil Kits
Class
LC
Contactor
Size (Amp)
30
20, 30
60
LE
100
Replacement
Contact Kits
Description
Catalog No.
24V 60Hz / 20V 50Hz
75LCC024A
115-120V 60Hz / 110V 50Hz
75LCC120A
200-208V 60Hz
75LCC208A
230-240V 60Hz / 220V 50Hz
75LCC240A
277V 60Hz / 240V 50Hz
75LCC277A
347V 60Hz
75LCC347A
460-480V 60Hz / 440V 50Hz
75LCC480A
575-600V 60Hz / 550V 50Hz
75LCC600A
NA
NA
24VAC 50/60HZ
3RT19355AC21
110VAC 50HZ / 120VAC 60HZ
3RT19355AK61
208VAC 50/60HZ
3RT19355AM21
220VAC 50HZ / 240VAC 60HZ
3RT19355AP61
277VAC 60HZ
3RT19355AU61
347VAC 60HZ
3RT19355AW61
480VAC 60HZ
3RT19355AV61
600VAC 60HZ
3RT19355AT61
24VAC 50/60HZ
3RT19455AC21
110VAC 50HZ / 120VAC 60HZ
3RT19455AK61
208VAC 50/60HZ
3RT19455AM21
220VAC 50HZ / 240VAC 60HZ
3RT19455AP61
277VAC 60HZ
3RT19455AU61
347VAC 60HZ
3RT19455AW61
480VAC 60HZ
3RT19455AV61
600VAC 60HZ
3RT19455AT61
Class
Contactor
Size (Amp)
Description
Catalog No.
LC
30
NA
NA
20, 30
NA
60
LE
16
100
200
300
400
Lighting Catalog Supplement 2012
NA
3RT1935-6A
1 contact kit
includes 3
moving and 6
fixed contacts.
3RT1945-6A
3RT1956-6A
3RT1965-6A
3RT1975-6A
Catalog
Number
49EB14J0261408R
49EB14J026140BR
49EB14J026140BR
NA
49EB22G0161406R
49EB22G0161406R
49EB14J0261408R
49EB14J0261408R
49EB14J0261408R
NA
49EB14J0261408R
49EB14J0261408R
NA
NA
Dimensions
Class LC Open Contactors
.35
[9.0]
POWER POLE
OPTIONAL
POWER POLES
7.39
[187.7]
6.50
[165.1]
OPTIONAL "NC"
AUX-CONTACTS
OPTIONAL "NO"
AUX-CONTACTS
P1 P2 P3 P4 P5
MOUNTING HOLES
ACCEPT #10 SCREWS
A1
.35
[9.0]
.22
[5.5]
3.86
[98.0]
A2
3.75
[95.3]
.59
[14.9]
4.18
[106.2]
2 "NO" AUX
CONTACTS
2 "NC" AUX
CONTACTS
1 "NO" AUX
CONTACT
P1 P2 P3 P4 P5
3.86
[98.0]
1 "NC" AUX
CONTACT
Note:
1) Mounting Dimensions remain the same for 1 to 12 Poles
2) Line and Load terminals are inter-changeable
3) Up to 2NO and 2NC auxiliary contacts can be added onto the base product
4) Same Power Pole can be configured as NO type or NC type
Lighting Catalog Supplement 2012
17
Dimensions
Class LE Open Contactors
LEN00B (20A 3 Pole and 4 Pole)
73
5
35
50
57.5
29.8
45
5
LEN00C003 (30A 3 Pole)
45
35.1
97
7.5
75
5
2.5
85
43
4.8
5
5
LEN00C004 (30A 4 Pole)
60
45
97
35.1
7.5
75
5
2.5
87
43
4.8
5
18
Lighting Catalog Supplement 2012
5
Dimensions
Class LE Open Contactors
LEN00D003 (60A 3 Pole)
55
35
17
110
5
64
45
95
64
111
5
LEN00E003 (100A 3 Pole)
134
86
22,5
22,5
46
5
60
5
22,5
70
LEN00C006 (30A 6 Pole)
LEN00D006 (60A 6 Pole)
130
104
140
SIEMENS
7
8
LEN00C009 (30A 9 Pole) and LEN00D009 (60A 9 Pole)
LEN00C012 (30A 12 Pole) and LEN00D012 (60A 12 Pole)
Note – Only the 12 pole contactor is shown. However, the dimensions of the mounting plate are the same for the 9 pole contactor.
Lighting Catalog Supplement 2012
19
Dimensions
Class LE Open Contactors
LEN00F003 (200A 3 Pole)
169
107
17
61
37
9
100
130
170
140
SIEMENS
7
120
LEN00G003 (300A 3 Pole)
96
48
71
120
9
180
168
210
SIEMENS
145
132
202
LEN00H003 (400A 3 Pole)
96
48
89
130
9
20
25
1
51
160
Lighting Catalog Supplement 2012
180
182
200
SIEMENS
150
224
Dimensions
Class LC and LE Enclosed Contactors
Figure 2
Figure 1
Enclosure
Type
1 without CPT
1 with CPT
12/3R & 4/4X
without CPT
12/3R & 4/4X
with CPT
Contactor
Rating
Fig.
LE 20/30A 3-4P
Figure 3
Outline Dimensions
Mounting
Conduit Size
A
B
C
D
E
K1
K2
K3
K4
K5
1
10.97
6.41
5.03
8.22
4.62
0.5
0.50-0.75
0.75–1
—
—
LC 30A 2-12P, LE 60A 3P
1
13.53
7.97
6.38
10.25
6.00
0.50-0.75
0.75-1
1-1.25
—
—
LE 30/60A 6-12P, LE 100A 3P
1
19.12
11.38
7.69
15.62
8.25
0.50-0.75
1-1.25
1.5-2
—
—
LE 200-400A 3P
2
26.00
17.62
12.50
25.19
15.50
0.50-0.75
1.25-1.5
1.25-1.5
—
—
LC 30A 2-12P, LE 20A 3-4P,
LE 30A 3-9P, LE 60A 3-9P,
LE 100A 3P
1
19.12
11.38
7.69
15.62
8.25
0.50-0.75
1-1.25
1.5–2
—
—
LE 30/60A 12P
1
24.88
13.38
8.12
21.75
9.00
0.50-0.75
1.25-1.5
2-2.5
—
—
LE 200-400A 3P
2
26.00
17.62
12.50
25.19
15.50
—
1.25-1.5
1.25-1.5
—
—
LE 20/30A 3-4P, LC 30A 2-12P,
LE 60A 3P
2
16.00
13.25
6.12
15.25
11.00
—
—
—
—
—
LE 30/60A 6-12P, LE 100A 3P
2
26.00
13.12
7.56
25.25
10.00
—
—
—
—
—
LE 200-400A 3P
2
26.00
17.62
12.50
23.19
15.50
—
—
—
—
—
LE 20/30A 3-4P, LC 30A 2-12P,
LE 60A 3P
2
16.00
13.25
6.12
15.25
11.00
—
—
—
—
—
LE 30/60A 6-12P, LE 100A 3P
2
26.00
13.12
7.56
25.25
10.00
—
—
—
—
—
LE 200-400A 3P
2
26.00
17.62
12.50
25.19
15.50
—
—
—
—
—
Enclosure Type
1, 12 & 4/4X with
& without CPT
Type
Fusible and Non-fusible
Disconnect
Circuit Breaker
Outline Dimensions
Contactor
Rating
Fig.
A
B
20–60A
3
24
11
100A
3
24
20
8
200A
3
46
20
10
300A
3
76
22
13
200-100A
3
24
11
8
C
8
Dimensions are in inches.
1) G designates mounting screw size.
Lighting Catalog Supplement 2012
21
Wiring Diagrams
Class LC and LE Electrically Held Contactors
LEN00D003 (60A 3 Pole)
LEN00E003 (100A 3 Pole)
LEN00B003 (20A 3 Pole)
A1
1 /L1
3 /L2
5 L3
13
A2
2 /T1
4 /T2
6 /T3
14
1 /L1
3 /L2
5 /L3
1/L1
3/L2
5/L3
A2
2/T1
4/T2
6/T3
LEN00F003 (200A 3 Pole)
LEN00G003 (300A 3 Pole)
LEN00H003 (400A 3 Pole)
LEN00B004 (20A 4 Pole)
A1
A1
7 /L4
A1
1 /L1
3 /L2
5 /L3
13
21
31
43
A2
2 /T1
4 /T2
6 /T3
14
22
32
44
U
A2
2 /T1
4 /T2
6 /T3
8 /T4
LEN00C003 (30A 3 Pole)
A1
1 /L1
3 /L2
5 /L3
13
21
LCE00C (30A 2-12 Pole)
LINE
LOAD
1
2
A2
2 /T1
4 /T2
6 /T3
14
22
3
4
LEN00C004 (30A 4 Pole)
A1
1 /L1
3 /L2
5 /L3
7 /L4
13
21
5
6
A1
A2
COIL
A2
2 /T1
4 /T2
6 /T3
8 /T4
14
22
COIL
VOLTAGE
OPTIONAL
AUXILIARY
CONTACTS
22
Lighting Catalog Supplement 2012
Wiring Diagrams
Class LC and LE Electrically Held Contactors
Optional Pilot Devices for Electrically Held Contactor
ON
ON PB
OFF PB
ON and OFF
Push buttons
L1
FUSE
*
COIL
A2
FUSE
A1
*
L2
REMOTE OFF
AUXILIARY
CONTACT
REMOTE
ON
AUXILIARY
CONTACT
OFF
SS
OFF-ON or
OFF-AUTO
Selector
Switch
REMOTE
DEVICE
L1
ON
AUTO
OFF
*
FUSE
COIL
A2
A1
FUSE
*
L2
AUXILIARY
CONTACT
OFF
ON
OFF-ON-AUTO
HAND-OFF-AUTO
Selector
Switch
L1
FUSE
*
ON
REMOTE
DEVICE OFF
A2
AUTO
COIL
A1
FUSE
* L2
AUXILIARY
CONTACT
OFF
* -- IF USED
Lighting Catalog Supplement 2012
23
Wiring Diagrams
Class LC Contactor (converted to mechanically held)
LINE
LOAD
4!",%!
7)2%#/.42/,
%,%#42/.)#-/$5,%
2%&%24/4!",%"&/2
#/.42/,#/..%#4)/.3
2
00000
./453%$
/04)/.!,./
!58#/.4!#4
#
3
!
/04)/.!,g.#g
!58),)!29#/.4!#4
1
!
#/),
#/),6/,4!'%
4
7)2%#/.42/,
%,%#42/.)#-/$5,%
2%&%24/4!",%#&/2
#/.42/,#/..%#4)/.3
5
00000
/04)/.!,./
!58#/.4!#4
!
REFER TO TABLE A FOR
2/3 WIRE CONTROL OPTIONS
/04)/.!,g.#g
!58),)!29#/.4!#4
,
6
!
#/),
/
#/),6/,4!'%
#
TABLE B : OPTIONAL PILOT DEVICES FOR 2 WIRE CONTROL
ON
(AUTO)
ELECTRONIC-MODULE
P1 P2
P3
P5
P4
*
CONTROL
VOLTAGE
FUSE
OFF
COIL
ON
*
FUSE
A1
A2
COIL
VOLTAGE
SELECTOR SWITCH
OFF-AUTO
OFF-ON or
SS
OFF
P3
P4
P5
FUSE
OFF
AUTO
REMOTE
DEVICE
ON
COIL
A2
*
COIL
VOLTAGE
P1 P2
OFF
CONTROL
VOLTAGE
SELECTOR SWITCH
ON-OFF-AUTO
HAND-OFF-AUTO or
ELECTRONIC-MODULE
ON
FUSE
*
A1
TABLE C : OPTIONAL PILOT DEVICES FOR 3 WIRE CONTROL
"NO"
AUXILIARY
REMOTE
OFF
P2
P3
P4
P5
OFF
ON
COIL
REMOTE
ON
"NC" AUXILIARY
"NO"
AUXILIARY
A2
FUSE
*
A1
ELECTRONIC-MODULE
P1
P2
P3
P4
P5
FUSE
OFF
ON
"NC" AUXILIARY
A2
COIL
ON
FUSE
A1
* -- IF USED
24
Lighting Catalog Supplement 2012
*
OFF
*
COIL
VOLTAGE
CONTROL
VOLTAGE
ON
*
COIL
VOLTAGE
P1
FUSE
CONTROL
VOLTAGE
PUSH BUTTONS
RETURN TO CENTER
OFF-ON SELECTOR
SWITCH WITH SPRING
ON & OFF
ELECTRONIC-MODULE
OFF
Siemens Industry, Inc.
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-241-4453
[email protected]
www.usa.siemens.com/controls
Subject to change without prior notice.
Order No. NECS-LTGCT-1211
All rights reserved.
Printed in USA.
©2011 Siemens Industry, Inc.
The information provided in this brochure contains merely
general descriptions or characteristics of performance
which in case of actual use do not always apply as described
or which may change as a result of further development
of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the
terms of contract.
All product designations may be trademarks or product
names of Siemens AG or supplier companies whose use by
third parties for their own purposes could violate the rights
of the owners.