Model 353 loop controller brochure

353 Process Automation Controller
The Model 353 Process
Automation Controller (PAC) is
designed for a broad range of
process applications. It can
serve as an advanced singleloop controller or as a multiloop controller with complete
control functions, including
indication, control, logic, or
sequencing for a small unit
process.
The 353 controller’s Ethernet and MODBUS communications
enable it to function as an integral element in a plant system.
Ethernet (MODBUS TCP/IP protocol) supports peer-to-peer
communication. The front configuration port allows connection
to a PC for configuration.
The 353 Basic unit provides sufficient analog I/O to support dual
loop or cascade control applications. It also supports digital inputs
and outputs. The 353 Expanded unit provides complementary I/O
for thermocouple, RTD, pulse, and frequency inputs and relay
outputs.
The design includes the Modbus RS-485 and Modbus Ethernet
communications as standard. Ethernet I/O modules extend the
controller I/O density and that allows the user to take advantage
of the controller’s powerful and versatile control capability.
The Model 353 controller supports function block programming
language. It has an extensive library of function blocks for analog
process control, Boolean logic, and specialty applications. The
controller can be configured either through faceplate or with the
iConfig Graphical Configuration software. Loop data is mapped to
the Modbus communication registers in accordance with the
configured loop application.
Process Instrumentation & Analytics
Answers for industry.
Specifications
Inputs
Outputs
Electrical and Environmental
Analog Inputs (non-isolated)
1-5 Vdc, 4-20 mA with included 250
resistor
Analog Outputs (non-isolated)
4-20 mA into 800 ohms (max.)
Power Supply
Standard: 120/240 Vac (85 to 264 Vac);
47 to 63 Hz
Optional: 24 Vdc, +20%, –15%
Power Requirements
25 Watts, 40 VA (max.)
2-Wire Transmitter Power
Voltage: 25 Vdc ±3V
Current: 120 mA, short circuit protected
Digital Outputs (non-isolated)
Open Collector Transistor
(emitter@station common)
Load Voltage: 30 Vdc (max.)
Load Current: 100 mA (max.)
Digital Inputs (isolated)
0-1 Vdc OFF, 15-30 Vdc ON
Analog Input, Universal (isolated)
Thermocouple, RTD, Ohms, Slidewire,
Millivolt
Digital/Frequency Input,
Universal (isolated)
Frequency Range: 0 to 25,000 Hz
Minimum Operating Frequency: 0.05 Hz
ON Voltage: 4-30 Vdc
OFF Voltage: 0-1 Vdc
Input Current: <5 mA @ 30 Vdc
Relay Outputs (SPDT)
Contact Rating: 5A @ 120 Vac,
2.5 A @ 230 Vac, Resistive Load
PAC 353 Design B
PAC 353 Design B
with Expanded I/O
Analog Input
3
4
Universal Analog Input
0
2
Analog Output
2
3
Discrete Input
3
4
Universal Discrete Input
0
2
Discrete Output
2
2
Relay Output
0
2
Configuration Port
Standard
Standard
MODBUS Interface
Standard
Standard
Ethernet Interface
Standard
Standard
Real-time Clock
Standard
Standard
Removable Configuration Media
Standard
Standard
Siemens Industry, Inc.
3333 Old Milton Parkway
Alpharetta, GA 30005
1-800-964-4114
Subject to change without prior notice
Order No.: PIFL-00009-1109
All rights reserved
Printed in USA
©2009 Siemens Industry, Inc.
The information provided in this brochure contains merely
general descriptions or characteristics of performance
which in case of actual use do not always apply as described
or which may change as a result of further development
of the products. An obligation to provide the respective
characteristics shall only exist if expressly agreed in the
terms of contract.
[email protected]
www.usa.siemens.com/ia
All product designations may be trademarks or product
names of Siemens AG or supplier companies whose use by
third parties for their own purposes could violate the rights
of the owners.