LEN Ratings

File E27683
Project 02NK48488
2003-01-10
REPORT
on
INDUSTRIAL CONTROL SWITCHES
Siemens Energy & Automation Inc.
Siemens & Furnas Control Products
Batavia, IL
Copyright © 2003 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above named company to
reproduce this Report provided it is reproduced in its entirety.
File E27683
Vol. 5
Vol. 6
Sec. 6
Sec. 1
and Report
Page 1
Issued:
Revised:
2003-01-10
2006-09-07
DESCRIPTION
PRODUCT COVERED:
Lighting and heating contactors,
N, followed by O, A, B, C, D, E, F, G,
1, 2, 4 or D, followed by B, CC, D, E,
4, followed by 00, 01, 02, 03, 04, 06,
024, 120, 208, 240, 277, 480 or 600.
Cat. No. LE, followed by B, D, F, or
H, J, K, T, V, Y, or Z, followed by 0,
F, G, or H, followed by 0, 1, 2, 3, or
07, 08, 09, 10, or 12, followed by
GENERAL:
These devices are open or enclosed type magnetically operated lighting
& heating contactors.
Ratings - They are rated as follows. All tungsten and ballast ratings
are 1 phase, 2-pole and 3-phase, 3-pole. Resistive ratings are per pole,
including 1 pole, 1 phase; 2-poles, 1 phase; 3-poles, 3 phase. (Wye or
inside the delta, normally open).
All resistive ratings were tested for 250,000 operations to cover
resistance heating applications:
Cat. No.
LENOB
B
C
C
D
D
E
E
F
F
G
G
H
H
Maximum
Voltage, AC
480
600
480
600
480
600
480
600
480
600
480
600
480
600
A, Tungsten
20
30
60
100
200
300
400
-
A, Ballasts
20
20
30
30
60
60
100
100
200
200
300
400
-
A, Resistive
20
20
30
30
60
60
100
100
200
200
300
300
400
400
File E27683
Vol. 5
Vol. 6
Sec. 6
Sec. 1
and Report
Page 1A
Issued:
New:
2003-01-10
2007-01-19
Short Circuit Current Ratings – These devices were tested for the following shortcircuit current ratings.
Cat. No. Suffix
LE***
B
B
B
B
B
C
C
C
C
C
D
D
D
D
D
E
F
F
G
G
G
H
H
H
Voltage
Protective Device +
Type/Max. Amp Rating
Short-Circuit Current
RMS Symmetrical Amperes
600
480
480
480
240
600
480
480
480
240
600
480
480
480
240
600
Class J Fuse/60
NEG/50
NGG/50
HEG/50
BQ3B/50
Class J Fuse/60
NEG/60
NGG/60
HEG/60
BQ3B/60
Class J Fuse/100
NEG/100
NGG/100
HEG/100
BQ3B/100
Class J Fuse/200
100,000
65,000
65,000
65,000
24,000
100,000
65,000
65,000
65,000
24,000
100,000
65,000
65,000
65,000
24,000
100,000
600
480
600
600
480
600
600
480
++JD63B250/250
++JD63B250/250
Class J Fuse/400
++JD63B300/300
++JD63B300/300
Class J Fuse/600
++JD63B400/400
++JD63B400/400
25,000
100,000
100,000
42,000
100,000
100,000
42,000
100,000
+ - Siemens Listed Cat. No. BQ3B, NGG3B, NEG3B and HEG3B circuit breakers
++ - Indicates circuit breakers with interchangeable trip units. May also be provided with circuit
breakers with an “X” in the second position of the Catalog number, which indicates fixed trip