MTU3R0096DS30 27kW Prime

DIESEL GENERATOR SET
MTU 3R0096 DS30
27 kWe /60 Hz /Prime
208 - 600V
Reference MTU 3R0096 DS30 (30 kWe) for Standby Rating Technical Data
SYSTEM RATINGS
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
240V**
1
1
60
27
27
112.5
208V**
3
0.8
60
27
33
94
240V**
3
0.8
60
27
33
81
380V**
3
0.8
60
27
33
51
480V**
3
0.8
60
27
33
40
600V**
3
0.8
60
27
33
32
65
284PSL1700
105 °C/40 °C
142
284PSL1700
105 °C/40 °C
142
284PSL1700
105 °C/40 °C
187
284PSL1700
105 °C/40 °C
187
284PSL1700
105 °C/40 °C
142
284PSL5252
105 °C/40 °C
12 LEAD
DOUBLE DELTA
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
12 LEAD WYE
4 LEAD WYE
** UL 2200 Offered
CERTIFICATIONS AND STANDARDS
// Emissions – EPA Tier 4 Interim Certified
// Generator set is designed and manufactured in
facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
// Seismic Certification – Optional
– IBC Certification
// UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
// Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
// Power Rating
- Accepts Rated Load in One Step Per NFPA 110
2
/ // / MTU 3R0096 DS30 (27 kWe) - Prime
STANDARD FEATURES*
MTU Onsite Energy is a single source supplier
Global Product Support
2 Year Standard Warranty
3029TFG89 Diesel Engine
- 2.9 Liter Displacement
- 4-Cycle
// Engine-generator resilient mounted
// Complete Range of Accessories
// // // // Generator
- Brushless, Rotating Field Generator
- 2/3 Pitch Windings
- 300% Short Circuit Capability with Optional Permanent
Magnet Generator (PMG)
// Digital Control Panel(s)
- UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine-Driven Fan
// STANDARD EQUIPMENT*
// Engine
Air Cleaners
Oil Pump
Oil Drain Extension and S/O Valve
Full Flow Oil Filter
Fuel Filter with Water Separator
Jacket Water Pump
Thermostat
Blower Fan and Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 12V
Governor – Mechanical Droop
Base - Formed Steel
SAE Flywheel and Bell Housing
Charging Alternator - 12V
Battery Box and Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
// Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Solid State, Volts-per-Hertz Regulator
±1% Voltage Regulation No Load to Full Load
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
105 °C Max. Prime Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
100% of Rated Load - One Step
5% Max. Total Harmonic Distortion
// Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
Windows®-Based Software
Multilingual Capability
Remote Communications to RDP-110 Remote Annunciator
Programmable Input and Output Contacts
UL Recognized, CSA Certified, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Compatible
* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3
/ // / MTU 3R0096 DS30 (27 kWe) - Prime
APPLICATION DATA
// Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Max. Power: kWm (bhp)
Speed Regulation
Air Cleaner
// 8 (2.1)
5.7 (1.5)
11.4 (3)
12
925
Fuel System
Fuel Supply Connection Size
Fuel Return Connection Size
Max. Fuel Lift: m (ft)
Recommended Fuel
Total Fuel Flow: L/hr (gal/hr)
Fuel Consumption
At 100% of Power Rating: L/hr (gal/hr)
At 75% of Power Rating: L/hr (gal/hr)
At 50% of Power Rating: L/hr (gal/hr)
// 9.1 (2.4)
6.8 (1.8)
4.9 (1.3)
Cooling - Radiator System
Ambient Capacity of Radiator: °C (°F)
Max. Restriction of Cooling Air: Intake
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
Heat Rejection to Coolant: kW (BTUM)
Heat Radiated to Ambient: kW (BTUM)
Fan Power: kW (hp)
50 (122)*
0.12 (0.5)
110 (29)
20.1 (1,144)
4.3 (245)
0.7 (0.94)
*Installation of a gravity exhaust louver in a Level 3 enclosure will
reduce the ambient capacity of the cooling system by 5 °C (9 °F).
Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
// John Deere
3029TFG89
4-Cycle
3-Inline
2.9 (177)
10.6 (4.2)
11 (4.3)
17.2:1
1,800
Mechanical Droop
31 (42)
±1%
Dry
Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
// // 3/8” ID/-6 JIC
1/4” ID/-6 JIC
2 (6.6)
Diesel #2
111.3 (29.4)
// Air Requirements
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Generator Set Heat for a
Max. of 25 °F Rise: *m3/min (SCFM)
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
// 3.6 (127)
46.7 (1,636)
15.8 (553)
Exhaust System
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Max. Allowable
Back Pressure: kPa (in. H20)
580 (1,076)
8.3 (293)
7.5 (30)
4
/ // / MTU 3R0096 DS30 (27 kWe) - Prime
WEIGHTS AND DIMENSIONS
Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.
System
Open Power Unit (OPU)
Dimensions (L x W x H)
1,581 x 749 x 1,226 mm (62.25 x 29.5 x 48.25 in)
Weight (dry/less tank)
727 kg (1,600 lb)
SOUND DATA
Unit Type
Level 0: Open Power Unit dB(A)
Prime Full Load
71.3
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
EMISSIONS DATA
NOx + NMHC
4.41
CO
0.44
RATING DEFINITIONS AND CONDITIONS
PM
0.11
All units are in g/hp-hr and shown at 100% load
(not comparable to EPA weighted cycle values).
Emission levels of the engine may vary with ambient
temperature, barometric pressure, humidity, fuel type and
quality, installation parameters, measuring instrumentation, etc.
The data was obtained in compliance with US EPA regulations.
The weighted cycle value (not shown) from each engine
is guaranteed to be within the US EPA Standards. 5-mode
emission data per 40 CFR 89 or 40 CFR 1039 (as applicable) is
available upon request.
C/F = Consult Factory/MTU Onsite Energy Distributor
N/A = Not Available
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
Prime power ratings apply to installations where utility power
is unavailable or unreliable. At varying load, the number of
generator set operating hours is unlimited. A 10% overload
capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, overload power in accordance
with ISO 3046-1, BS 5514, and AS 2789. Average load
factor: ≤ 75%.
// Deration Factor:
Altitude: Consult your local MTU Onsite Energy Power
Generation Distributor for altitude derations.
Temperature: Consult your local MTU Onsite Energy Power
Generation Distributor for temperature derations.
// © MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 826 (77 3E) 2015-10
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.