Download

Datasheet
Non-Incendive Barrier
Te r m i n a l B l o c k
This terminal block allows circuits to be designated “Non-Incendive”. A typical application
would involve 24Vdc PLC input signals. By rating
the signal as non-incendive, non-explosion proof
devices and wiring can be used in Class 1,
Division 2, Groups A, B, C and D hazardous
locations. The temperature rating is T3C (160°C).
Standard installation and wiring practices apply
such as installation in an approved enclosure.
Features:
• combifoot mounting for 32mm and 35mm
DIN rails
• only 12mm wide
• clear marking of terminals for easy installation
• CSA certified for Class 1, Division 2, Groups
A, B, C and D, T3C (160°C)
United States
Canada
Mexico
Weidmuller Inc.
Weidmuller Ltd.
Weidmuller, S.A. de C.V.
821 Southlake Blvd.
10 Spy Court
5 Sur No. 4311
Richmond, Virginia 23236
Markham, Ontario L3R 5H6
Col. Huexotitla
Telephone: (800) 849-9343
Telephone: (800) 268-4080
72534 Puebla, Pue. Mexico
Facsimile: (804) 379-2593
Facsimile: (905) 475-2798
Telephone: (22) 37 2549
Email: [email protected]
Email: [email protected]
Facsimile: (22) 43 1981
Website: www.weidmuller.com
Website: www.weidmuller.ca
Email: [email protected]
5/1
Non-Incendive Barrier Terminal Block
Rated data
Rated voltage
24Vdc nominal
35Vdc maximum
Rated current
75mA maximum
Resistance
470M ±1%
Wire Size
22-12AWG
Dimensions
width 12mm
length 88.4mm
height on TS32 x 15 rail 75.0mm
height on TS35 x 7.5 rail 71.5mm
height on TS35 x 15 rail 78.5mm
Approvals
CSA for Class 1, Division 2, Groups A, B, C and D, T3C (160°C)
Ordering Data
Non-Incendive Barrier TS35
2
Cat.No.
W
/ TS 32/Y
991629 0000
Subject to technical changes · Printed in Canada · 99990139 · 01/2002