Datasheet Non-Incendive Barrier Te r m i n a l B l o c k This terminal block allows circuits to be designated “Non-Incendive”. A typical application would involve 24Vdc PLC input signals. By rating the signal as non-incendive, non-explosion proof devices and wiring can be used in Class 1, Division 2, Groups A, B, C and D hazardous locations. The temperature rating is T3C (160°C). Standard installation and wiring practices apply such as installation in an approved enclosure. Features: • combifoot mounting for 32mm and 35mm DIN rails • only 12mm wide • clear marking of terminals for easy installation • CSA certified for Class 1, Division 2, Groups A, B, C and D, T3C (160°C) United States Canada Mexico Weidmuller Inc. Weidmuller Ltd. Weidmuller, S.A. de C.V. 821 Southlake Blvd. 10 Spy Court 5 Sur No. 4311 Richmond, Virginia 23236 Markham, Ontario L3R 5H6 Col. Huexotitla Telephone: (800) 849-9343 Telephone: (800) 268-4080 72534 Puebla, Pue. Mexico Facsimile: (804) 379-2593 Facsimile: (905) 475-2798 Telephone: (22) 37 2549 Email: [email protected] Email: [email protected] Facsimile: (22) 43 1981 Website: www.weidmuller.com Website: www.weidmuller.ca Email: [email protected] 5/1 Non-Incendive Barrier Terminal Block Rated data Rated voltage 24Vdc nominal 35Vdc maximum Rated current 75mA maximum Resistance 470M ±1% Wire Size 22-12AWG Dimensions width 12mm length 88.4mm height on TS32 x 15 rail 75.0mm height on TS35 x 7.5 rail 71.5mm height on TS35 x 15 rail 78.5mm Approvals CSA for Class 1, Division 2, Groups A, B, C and D, T3C (160°C) Ordering Data Non-Incendive Barrier TS35 2 Cat.No. W / TS 32/Y 991629 0000 Subject to technical changes · Printed in Canada · 99990139 · 01/2002 5/2