SITRANS TH400 Catalog Sheet

© Siemens AG 2016
Temperature Measurement
Transmitters for mounting in sensor head
SITRANS TH400 fieldbus transmitter
■ Overview
■ Application
• Linearized temperature measurement with resistance thermometers or thermal elements
• Differential, mean-value or redundant temperature measurement with resistance thermometers or thermal elements
• Linear resistance and bipolar millivolt measurements
• Differential, mean-value or redundant resistance and bipolar
millivolt measurements
2
■ Function
Features
• Mounting in connection head, type B, to DIN 43729, or larger
• Polarity-neutral bus connection
• 24-bit analog-digital converter for high resolution
• Electrically isolated
• Intrinsically-safe version for use in potentially explosive areas
• Special characteristic
• Sensor redundance
SITRANS TH400 fieldbus transmitters
Versions:
• For FOUNDATION fieldbus
• For PROFIBUS PA
With PROFIBUS PA communication
• Function blocks: 2 x analog
The SITRANS TH400 temperature transmitter is a small field bus
transmitter for mounting in the connection head of form B. Extensive functionality enables the temperature transmitter to be precisely adapted to the plant’s requirements. Operation is very
simple in spite of the numerous setting options. Thanks to its universal concept it can be used in all industries and is easy to integrate in the context of Totally Integrated Automation applications.
Transmitters of the "intrinsically safe" type of protection can be installed within potentially explosive atmospheres. The devices
comply with the Directive 2014/34/EU (ATEX), as well as FM and
CSA regulations.
With FOUNDATION fieldbus communication
• Function blocks: 2 x analog and 1 x PID
• Functionality: Basic or LAS
Mode of operation
The following function diagram explains the mode of operation
of the transmitter.
The only difference between the two versions of the SITRANS
TH400 (7NG3214-... and 7NG3215-...) is the type of fieldbus
protocol used (PROFIBUS PA or FOUNDATION fieldbus).
Installing SITRANS TH400 in temperature sensors turns them
into complete, bus-capable measuring points; compact - and in
a single device.
Transformer
Input 1
Input 2
Differential
Mean value
Redundancy
Terminal temperature
Engineering units
Diagnostic functions
Table linearization
Polynomial linearization
Process calibration
Optional inputs:
- Resistance thermometer
- Thermocouple
- mV sensor
- Resistance-based sensors
Input 1
5
4
Input 2
A/D
converter
Communication
3
Internal
Pt100
SITRANS TH400, function diagram
2/134
CPU
Siemens FI 01 · 2016
EEPROM
Complex configuration
Correction coefficient
Factory settings
- PROFIBUS protocol (7NG3214)
or
- Foundation Fieldbus protocol (7NG3215)
Ex power circuit
Electrically
isolated
6
1
Bus connection
2
© Siemens AG 2016
Temperature Measurement
Transmitters for mounting in sensor head
SITRANS TH400 fieldbus transmitter
System communication
Thermocouple
to IEC 584
Measuring range
• Type B
400 .. +1820 °C (752 ... 3308 °F)
• Type E
-100 ... +1000 °C (-148 ... +1832 °F)
PROFIBUS PA
• Type J
-100 ... +1000 °C (-148 ... +1832 °F)
Segment
coupler
• Type K
-100 ... +1200 °C (-148 ... +2192 °F)
• Type N
-180 ... +1300 °C (-292 ... +2372 °F)
• Type R
-50 ... +1760 °C (-58 ... +3200 °F)
• Type S
-50 ... +1760 °C (-58 ... +3200 °F)
• Type T
-200 ... +400 °C (-328 ... +752 °F)
Output:
Bus
terminator
2
1
s
SITRANS
TH400 PA
to DIN 43710
Bus connection
Bus
terminator
FOUNDATION Fieldbus
• Type L
-200 ... +900 °C (-328 ... +1652 °F)
• Type U
-200 ... +600 °C (-328 ... +1112 °F)
to ASTM E988-90
Segment
coupler
2
1
s
SITRANS
TH400 FF
• Type W3
0 ... 2300 °C (32 ... +4172 °F)
• Type W5
0 ... 2300 °C (32 ... +4172 °F)
External cold junction compensation
-40 ... +135 °C (-40 ... +275 °F)
Sensor fault detection
Bus connection
SITRANS TH400, communication interface
■ Technical specifications
• Sensor break detection
Yes
• Sensor short-circuit detection
Yes, < 3 mV
• Sensor current in the event of
open-circuit monitoring
4 A
mV sensor - voltage input
Input
Measuring range
-800 ... +800 mV
Analog-to-digital conversion
Input resistance
10 M
• Measurement rate
< 50 ms
• Resolution
24-bit
Output
Filter time (programmable)
0 ... 60 s
Resistance thermometer
Update time
< 400 ms
Pt25 ... Pt1000 to IEC 60751/JIS C
1604
Measuring accuracy
• Measuring range
-200 ... +850 °C
(-328 ... +1562 °F)
General values
Ni25 ... Ni1000 to DIN 43760
• Measuring range
Accuracy is defined as the higher
value of general values and basic
values.
-60 ... +250 °C
(-76 ... +482 °F)
Cu10 ... Cu1000,  = 0.00427
• Measuring range
-50 ... +200 °C
(-58 ... +392 °F)
Line resistance per sensor cable
Max. 50 
Sensor current
Nominal 0.2 mA
Type of input
Absolute accuracy
Temperature
coefficient
All
  0.05 % of the   0.002 % of
measured value the measured
value/°C
Basic values
Type of input
Basic accuracy
Temperature
coefficient
Pt100 and Pt1000
  0.1 °C
  0.002 °C/°C
• Sensor break detection
Yes
Ni100
  0.15 °C
  0.002 °C/°C
• Sensor short-circuit detection
Yes, < 15 
Cu10
  1.3 °C
  0.02 °C/°C
Sensor fault detection
Resistance-based sensors
  0.05 
  0.002 /°C
Measuring range
0  ... 10 k
Voltage source
  10 V
  0.2 % V/°C
Line resistance per sensor cable
Max. 50 
  0.5 °C
  0.01 °C/°C
Sensor current
Nominal 0.2 mA
Thermocouple, type:
E, J, K, L, N, T, U
Thermocouple, type:
B, R, S, W3, W5
  1 °C
  0.025 °C/°C
Cold junction compensation
  0.5 °C
Resistance-based sensors
Sensor fault detection
• Sensor break detection
Yes
• Sensor short-circuit detection
Yes, < 15 
Reference conditions
Warming-up time
30 s
Signal-to-noise ratio
Min. 60 dB
Calibration condition
20 ... 28 °C (68 ... 82 °F)
Siemens FI 01 · 2016
2/135
2
© Siemens AG 2016
Temperature Measurement
Transmitters for mounting in sensor head
SITRANS TH400 fieldbus transmitter
Conditions of use
Certificates and approvals
Ambient conditions
2
Explosion protection ATEX
Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
EC type test certificate
KEMA 06 ATEX 0264
Permissible storage temperature
-40 ... +85 °C (-40 ... +185 °F)
• "Intrinsic safety" type of protection
Relative humidity
 98 %, with condensation
II 1 G Ex ia IIC T4...T6
II 2(1) G Ex ib[ia] IIC T4...T6
II 1 D Ex iaD
EC type test certificate
KEMA 06 ATEX 0263 X
• Type of protection for "equipment
is non-arcing"
II 3 GD Ex nA[nL] IIC T4...T6
II 3 GD Ex nL IIC T4...T6
II 3 GD Ex nA[ic] IIC T4...T6
II 3 GD Ex ic IIC T4...T6
Insulation resistance
• Test voltage
500 V AC for 60 s
Mechanical testing
• Vibrations (DIN class B) to
IEC 60068-2-6 and
IEC 60068-2-64
4 g/2 ... 100 Hz
Explosion protection: FM for USA
• FM approval
FM 3027985
EMC noise voltage influence
<  0.1 % of span
• Degree of protection
Extended EMC noise immunity:
NAMUR NE 21, criterion A, Burst
<  1 % of span
EMC 2014/30/EU Emission and
Noise Immunity to
EN 61326
• IS Class I, Div 1, Groups A, B, C,
D T4/T5/T6, FISCO
• IS Class I, Zone 0, AEx ia, IIC
T4/T5/T6, FISCO
• NI Class I, Div 2, Groups A, B, C,
D T4/T5/T6, FNICO
Electromagnetic compatibility
Construction
Explosion protection CSA for
Canada
Material
Molded plastic
Weight
55 g (0.12 lb)
• CSA approval
CSA 1861385
Dimensions
See Dimensional drawings
• Degree of protection
Cross-section of cables
Max. 2.5 mm2 (AWG 13)
• IS Class I, Div 1, Groups A, B, C,
D T4/T5/T6
• Ex ia IIC T4/T5/T6 and
Ex ib [ia] IIC T4/T5/T6
• NI Class I, Div 2, Groups A, B, C,
D T4/T5/T6
• Ex nA II T4/T5/T6
Other certificates
EAC Ex(GOST), NEPSI, IECEx
Degree of protection
• Transmitter enclosure
IP40
• Terminal
IP00
Auxiliary power
Power supply
Communication
• Standard, Ex "nA", Ex "nL", NI
9.0 ... 32 V DC
• ATEX, FM, UL and CSA
9.0 ... 30 V DC
• In FISCO/FNICO installations
9.0 ... 17.5 V DC
Power consumption
< 11 mA
Max. increase in power consumption in the event of a fault
< 7 mA
Parameterization interface
• PROFIBUS PA connection
- Protocol
Profile 3.0
- Address (for delivery)
126
• FOUNDATION fieldbus connection
- Protocol
FF protocol
- Functionality
Basic or LAS
- Version
ITK 4.6
- Function blocks
2 x analog and 1 x PID
Factory setting
only for SITRANS TH400 PA
Sensor
Pt100 (IEC)
Type of connection
3-wire circuit
Unit
°C
Failure mode
Last valid value
Filter time
0s
PA address
126
PROFIBUS Ident No.
Manufacturer-specific
only for SITRANS TH400 FF
2/136
Siemens FI 01 · 2016
Sensor
Pt100 (IEC)
Type of connection
3-wire circuit
Unit
°C
Failure mode
Last valid value
Filter time
0s
Node address
22
© Siemens AG 2016
Temperature Measurement
Transmitters for mounting in sensor head
SITRANS TH400 fieldbus transmitter
■ Selection and Ordering data
Article No.
Temperature transmitter SITRANS TH400
for installation in connection head, with
electrical isolation, order operating instructions separately.
- With explosion protection "Intrinsically
safe to ATEX/FM/CSA/IECEX/NEPSI"
} 
} 
7NG3214-0NN00
2
SIMATIC PDM operating software
See Chapter 8
DIN rail adapters for head transmitters
7NG3092-8KA
7NG3214-0AN00
Connecting cable
4-wire, 150 mm, for sensor connections
when using head transmitters in the high
hinged cover (set with 5 units)
7NG3092-8KC
for additional PA components
See Catalog IK PI
- No explosion protection or Zone 2/Div 2
to ATEX/FM/CSA/IECEX/NEPSI
} 
7NG3215-0NN00
- With explosion protection "Intrinsically
safe to ATEX/FM/CSA/IECEX/NEPSI"
} 
7NG3215-0AN00
} Available ex stock.
Order code
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
With test protocol (5 measuring points)
A5E00364512
(Quantity delivered: 5 units)
• Bus-compatible to FOUNDATION Fieldbus
Further designs
}
With documentation in German, English,
French, Spanish, Italian, Portuguese and
SIPROM T parameterization software
• Bus-compatible to PROFIBUS PA
- No explosion protection or Zone 2/Div 2
to ATEX/FM/CSA/IECEX/NEPSI
Article No.
Accessories
MiniDVD for temperature measuring
instruments
C11
Customer-specific programming
Add "-Z" to Article No. and specify Order
code(s)
Measuring range to be set
Specify in plain text (max. 5 digits):
Y01: ... to ... °C, °F
Y011)
Measuring point no. (TAG), max. 8 characters
Y172)
Measuring point descriptor,
max. 16 characters
Y232)
Measuring point message,
max. 32 characters
Y242)
Bus address, specify in plain text
Y252)
Pt100 (IEC) 2-wire, RL = 0 
U023)
Pt100 (IEC) 3-wire
U033)
Pt100 (IEC) 4-wire
U043)
Thermocouple type B
U203)4)
Thermocouple type C (W5)
U213)4)
Thermocouple type D (W3)
U223)4)
Thermocouple type E
U233)4)
Thermocouple type J
U243)4)
Thermocouple type K
U253)4)
Thermocouple type L
U263)4)
Thermocouple type N
U273)4)
Thermocouple type R
U283)4)
Thermocouple type S
U293)4)
Thermocouple type T
U303)4)
Thermocouple type U
U313)4)
With TC: CJC external (Pt100, 3-wire)
U41
With TC: CJC external with fixed value, specify in plain text
Y50
Special differing customer-specific programming, specify in plain text
Y095)
 We can offer shorter delivery times for configurations designated with
the Quick Ship Symbol . For details see page 9/5 in the appendix.
1)
For customer-specific programming for RTD and TC, the start value and
the end value of the required measuring span must be specified here.
2)
For this selection, Y01 or Y09 must also be selected.
3)
For this selection, Y01 must also be selected.
4)
Internal cold junction compensation is selected as the default for TC.
5)
For customer-specific programming, for example mV and ohm, the start
value and the end value of the required measuring span and the unit must
be entered here.
Ordering example 1:
7NG3214-0NN00-Z Y01+Y17+U03
Y01: 0...100 °C
Y17: TICA1234HEAT
Ordering example 2:
7NG3214-0NN00-Z Y01+Y17+Y25+U25
Y01: 0...500 °C
Y17: TICA5678HEAT
Y25: 33
Factory setting:
• For SITRANS TH400 PA:
- Pt100 (IEC 751) with 3-wire circuit
- Unit: °C
- Failure mode: Last valid value
- Filter time: 0 s
- PA address: 126
- PROFIBUS Ident No.: Manufacturer-specific
• For SITRANS TH400 FF:
- Pt100 (IEC 751) with 3-wire circuit
- Unit: °C
- Failure mode: Last valid value
- Filter time: 0 s
- Node address: 22
Siemens FI 01 · 2016
2/137
© Siemens AG 2016
Temperature Measurement
Transmitters for mounting in sensor head
SITRANS TH400 fieldbus transmitter
■ Dimensional drawings
2
s
2
1
M4 x 30
3
6
3-W
4 + -
5
Ø 6.3 (0.25)
26.3 (1.04)
33 (1.3)
Ø 44 (1.73)
Terminals 1, 2: fieldbus connection
Terminals 3 ... 6: sensor connection
SITRANS TH400 dimensions in mm (inches) and connections
Mounting on DIN rail
SITRANS TH400, mounting of transmitter on DIN rail
50.5 (1.99)
33 (1.30)
59.6 (2.35)
14 (0.55)
DIN rail adaptor, dimensions in mm (inch)
2/138
Siemens FI 01 · 2016
© Siemens AG 2016
Temperature Measurement
Transmitters for mounting in sensor head
SITRANS TH400 fieldbus transmitter
■ Schematics
Resistance thermometer
Thermocouple
Resistance
2
+ Two-wire system 1)
Internal
cold junction compensation
+
Three-wire system
Four-wire system
Cold junction compensation
with external Pt100 in three-wire system
+
Mean-value/differential or
redundancy generation
2 x two-wire system 1)
Three-wire system
-
2
1
-
Cold junction compensation
with external Pt100 in two-wire system 1)
+
Four-wire system
Two-wire system 1)
1
+
2
-
-
Mean value, differential or
redundancy generation with internal
cold junction compensation
2
1
Mean value, differential or redundancy generation
1 resistor in two-wire system 1)
1 resistor in three-wire system
Voltage measurement
2
1
Mean-value/differential or
redundancy generation
1 sensor in two-wire system 1)
1 sensor in three-wire system
1)
+1 -
+
2
-
Mean value, differential or
redundancy generation and
cold junction compensation
with internal Pt100
in two-wire system 1)
Programmable line resistance for the purpose of correction.
+
-
One voltage source
+
1
-
2
+ -
Measurement of mean value, differential and
redundancy with 2 voltage sources
SITRANS TH400, sensor connection assignment
Siemens FI 01 · 2016