SITRANS TF Catalog Specifications Sheet

© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
■ Overview
■ Function
Configuration
The communication capability over the HART protocol V 5.9 of
the SITRANS TF with an integrated SITRANS TH300 permits parameterization using a PC or HART communicator (hand-held
communicator). The SIMATIC PDM makes it easy.
Parameterization is carried out using a PC for SITRANS TF with
the integrated and programmable SITRANS TK. Available for
this purpose are a special modem and the software tool
SIPROM T.
Mode of operation
Mode of operation of SITRANS TF as temperature transmitter
The sensor signal, whether resistance thermometer, thermocouple element or  or mV signal, is amplified and linearized. Sensor and output side are electrically isolated. An internal cold
junction is integrated for measurements with thermocouple elements.
Our field devices for heavy industrial use
• HART, Universal
• 4 to 20 mA, universal
• Field indicator for 4 to 20 mA signals
The temperature transmitter SITRANS TF works where others
feel uncomfortable.
■ Benefits
• Universal use
- as transmitter for resistance thermometer, thermocouple element,  or mV signal
- as field indicator for any 4 to 20 mA signals
• Local sensing of measured values over digital display
• Rugged two-chamber enclosure in die-cast aluminium or
stainless steel
• Degree of protection IP66/67/68
• Test terminals for direct read-out of the output signal without
breaking the current loop
• Can be mounted elsewhere if the measuring point
- is hard to access,
- is subject to high temperatures,
- is subject to vibrations from the system,
- or if you want to avoid long neck tubes and/or protective
tubes.
• Can be mounted directly on American-design sensors
• Wide range of approvals for use in potentially explosive atmospheres. "Intrinsically safe, non-sparking and flameproof" type
of protections, for Europe and USA.
• SIL2 (with Order code C20), SIL2/3 (with C23)
■ Application
SITRANS TF can be used everywhere where temperatures need
to be measured under particularly adverse conditions, or where
a convenient local display is ideal. Which is why users from all
industries have opted for this field device. The rugged enclosure
protects the electronics. The stainless steel model is almost
completely resistant to sea water and other aggressive elements. The inner workings offer high measuring accuracy, universal input and a wide range of diagnostic options.
The device outputs a temperature-linear direct current of 4 to
20 mA. As well as the analog transmission of measured values
from 4 to 20 mA, the HART version also supports digital communication for online diagnostics, measured value transmission
and configuration.
SITRANS TF automatically detects when a sensor should be interrupted or is indicating a short-circuit. The practical test terminals allow direct measurement of 4 to 20 mA signals over an ammeter without interrupting the output current loop.
Mode of operation of SITRANS TF as field indicator
Any 4 to 20 mA signal can be applied to the generous terminal
block. As well as a range of predefined measurement units, the
adjustable indicator also supports the input of customized units.
This means that any 4 to 20 mA signal can be represented as
any type of unit, e.g. pressure, flow rate, filling level or temperature.
Power supply
SITRANS TF
Sensor
TC RTD
SITRANS TH300
1
3
2
A
D
μP
0000
00°C
4
8
9
5
D
Load
A
7
6
1 Analog-to-digital converter
2 Electrical isolation
3 Microprocessor
4 Digital-to-analog converter
5 Power supply
6 PC/laptop
7 HART modem
8 Digital display (option)
9 Test connector
Mode of operation: SITRANS TF with integrated transmitter and digital
display
Siemens FI 01 · 2016
2/171
2
© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
■ Technical specifications
Measuring range
parameterizable max. 0 ... 2200 
(see table "Digital measuring
errors")
Temperature
Min. measured span
5 ... 25  (see Table "Digital measuring errors")
• to IEC 60751
Pt25 … Pt1000
Characteristic curve
• to JIS C 1604; a=0.00392 K-1
Pt25 … Pt1000
Resistance-linear or special characteristic
• to IEC 60751
Ni25 … Ni1000
Units
°C and °F
Input
Resistance thermometer
2
Measured variable
Sensor type
Connection
• Normal connection
1 resistance thermometer (RTD)
in 2-wire, 3-wire or 4-wire system
• Generation of average value
Series or parallel connection of
several resistance thermometers in
a two-wire system for the generation of average temperatures or for
adaptation to other device types
• Generation of difference
2 resistance thermometers (RTD)
in 2-wire system (RTD 1 – RTD 2
or RTD 2 – RTD 1)
Interface
• Two-wire system
Parameterizable line resistance
 100  (loop resistance)
• Three-wire system
No balancing required
• Four-wire system
No balancing required
Thermocouples
Measured variable
Temperature
Sensor type (thermocouples)
• Type B
• Type C
• Type D
• Type E
• Type J
• Type K
• Type L
• Type N
• Type R
• Type S
• Type T
• Type U
Pt30Rh-Pt6Rh to DIN IEC 584
W5 %-Re acc. to ASTM 988
W3 %-Re acc. to ASTM 988
NiCr-CuNi to DIN IEC 584
Fe-CuNi to DIN IEC 584
NiCr-Ni to DIN IEC 584
Fe-CuNi to DIN 43710
NiCrSi-NiSi to DIN IEC 584
Pt13Rh-Pt to DIN IEC 584
Pt10Rh-Pt to DIN IEC 584
Cu-CuNi to DIN IEC 584
Cu-CuNi to DIN 43710
Units
°C or °F
Connection
• Normal connection
1 thermocouple (TC)
 0.45 mA
• Generation of average value
2 thermocouples (TC)
Response time
 250 ms for 1 sensor with opencircuit monitoring
• Generation of difference
2 thermocouples (TC)
(TC 1 – TC 2 or TC 2 – TC 1)
Open-circuit monitoring
Always active (cannot be disabled)
Response time
 250 ms for 1 sensor with opencircuit monitoring
Short-circuit monitoring
can be switched on/off (default
value: ON)
Open-circuit monitoring
Can be switched off
Measuring range
parameterizable (see table "Digital measuring errors")
• Internal
With integrated Pt100 resistance
thermometer
Min. measured span
10 °C (18 °F)
• External
Characteristic curve
Temperature-linear or special
characteristic
With external Pt100 IEC 60751
(2-wire or 3-wire connection)
• External fixed
Cold junction temperature can be
set as fixed value
Sensor current
Cold junction compensation
Resistance-based sensors
Measured variable
Actual resistance
Measuring range
Sensor type
Resistance-based, potentiometers
parameterizable (see table "Digital measuring errors")
Min. measured span
Units

Min. 40 ... 100 °C (72 ... 180 °F)
(see table "Digital measuring
errors")
Characteristic curve
Temperature-linear or special
characteristic
Connection
• Normal connection
1 resistance-based sensor (R) in
2-wire, 3-wire or 4-wire system
• Generation of average value
2 resistance-based sensors in
2-wire system for generation of
average value
Measured variable
DC voltage
Sensor type
2 resistance-based sensor in
2-wire system (R 1 – R 2 or
R 2 – R 1)
DC voltage source (DC voltage
source possible over an externally connected resistor)
Units
mV
Response time
 250 ms for 1 sensor with opencircuit monitoring
• Generation of difference
Interface
mV sensor
• Two-wire system
Parameterizable line resistance
 100  (loop resistance)
Open-circuit monitoring
Can be switched off
• Three-wire system
No balancing required
Measuring range
• Four-wire system
No balancing required
-10 ... +70 mV
-100 ... +1100 mV
Sensor current
 0.45 mA
Min. measured span
2 mV or 20 mV
Response time
 250 ms for 1 sensor with opencircuit monitoring
Overload capability of the input
-1.5 ... +3.5 V DC
Input resistance
 1 M
Open-circuit monitoring
Can be switched off
Characteristic curve
Short-circuit monitoring
Can be switched off (value is
adjustable)
Voltage-linear or special characteristic
2/172
Siemens FI 01 · 2016
© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Output
Auxiliary power
Output signal
4 ... 20 mA, 2-wire
Communication with SITRANS
TH300
acc. to HART Rev. 5.9
Without digital display
11 ... 35 V DC (30 V for Ex ib;
32 V for Ex ic and Ex nA)
With digital display
13.1 ... 5 V DC (30 V for Ex ib;
32 V for Ex ic and Ex nA)
Electrically isolated
Between input and output
• Test voltage
U eff = 1 kV, 50 Hz, 1 min
Digital display
Digital display (optional)
In current loop
Display
Max. 5 digits
Digit height
9 mm (0.35 inch)
Display range
-99 999 ... + 99 999
Units
any (max. 5 char.)
Setting:
Zero point, full-scale value and unit
with 3 buttons
Load voltage
2.1 V
Certificates and approvals
Explosion protection ATEX
• "Intrinsic safety" type of protection
Measuring accuracy
Digital measuring errors
See table "Digital measuring
errors"
Reference conditions
• Auxiliary power
24 V  1 %
• Load
500 
• Ambient temperature
23 °C (73.4 °F)
• Warming-up time
> 5 min
Error in the analog output (digital/analog converter)
< 0.025 % of span
Error due to internal cold junction
< 0.5 °C (0.9 °F)
Influence of ambient temperature
• Analog measuring error
- EC type test certificate
• "Operating equipment that is nonignitable and has limited energy
for zone 2" type of protection
- EC type test certificate
• "Flame-proof enclosure" type of
protection
- EC type test certificate
- with thermocouples
0.6 °C (1.1 °F)/10°C (18 °F)
II 3 G Ex ic IIC T6/T4 Gc
II 3 G Ex nA IIC T6/T4 Gc
II 3 G Ex nA [ic] IIC T6/T4 Gc
ZELM 11 ATEX 0471 X
II 2 G Ex d IIC T6/T5 Gb
II 2 D Ex tb IIIC T100 °C Db
ZELM 11 ATEX 0472 X
Certificate of Compliance
3017742
• Identification (XP, DIP, NI, S)
• XP/I/1/BCD/T5 Ta = 85 °C
(185 °F), T6 Ta = 60 °C (140 °F),
Type 4X
• Digital measuring errors
0.06 °C (0.11 °F)/10°C (18 °F)
ZELM 11 ATEX 0471 X
Explosion protection to FM
0.02 % of span/10 °C (18 °F)
- with resistance thermometers
with digital display:
II 2 (1) G Ex ib [ia Ga] IIC T4 Gb
II 2 G Ex ib IIC T4 Gb
II 1D Ex ia IIIC T100 °C Da
without digital display:
II 2 (1) G Ex ib [ia Ga] IIC T6 Gb
II 2 G Ex ib IIC T6 Gb
II 1D Ex ia IIIC T100 °C Da
• DIP/II, III/1/EFG/T5 Ta = 85 °C
(185 °F), T6 Ta = 60 °C (140 °F),
Type 4X
Auxiliary power effect
< 0.001 % of span/V
Effect of load impedance
< 0.002 % of span/100 
• NI/I/2/ABCD/T5 Ta = 85 °C
(185 °F), T6 Ta = 60 °C (140 °F),
Type 4X
• In the first month
< 0.02 % of span
• S/II, III/2/FG/T5 Ta = 85 °C
(185 °F), T6 Ta = 60 °C (140 °F),
Type 4X
• After one year
< 0.3 % of span
• After 5 years
< 0.4 % of span
Long-term drift
Other certificates
IECEx, EAC Ex(GOST),
INMETRO, NEPSI, KOSHA
Hardware and software requirements
Conditions of use
Ambient conditions
Storage temperature
-40 ... +85 °C (-40 ... +185 °F)
Condensation
Permissible
Electromagnetic compatibility
According to EN 61326 and
NAMUR NE21
Degree of protection to EN 60529
IP66/67/68
Construction
Weight
Approx. 1.5 kg (3.3 lb) without
options
Dimensions
See "Dimensional drawings"
Enclosure material
Die-cast aluminum, low in copper,
GD-AlSi 12 or stainless steel,
polyester-based lacquer, stainless steel rating plate
Electrical connection, sensor connection
Screw terminals, cable inlet via
M20 x 1.5 or ½-14 NPT screwed
gland
Mounting bracket (optional)
Steel, galvanized and chromeplated or stainless steel
• For the parameterization software
SIPROM T for SITRANS TF with
TH200
- Personal computer
PC with CD-ROM drive and USB
- PC operating system
Windows 98, NT, 2000, XP, 7 and
Win 8
• For the parameterization software See chapter 8 "Software",
SIMATIC PDM for SITRANS TH300 "SIMATIC PDM"
Communication
Load for HART connection
230 ... 1100 
• Two-core shielded
 3.0 km (1.86 mi)
• Multi-core shielded
 1.5 km (0.93 mi)
Protocol
HART protocol, version 5.9
Factory setting (transmitter):
• Pt100 (IEC 751) with 3-wire circuit
• Measuring range: 0 ... 100 °C (32 ... 212 °F)
• Error signal in the event of sensor breakage: 22.8 mA
• Sensor offset: 0 °C (0 °F)
• Damping 0.0 s
Siemens FI 01 · 2016
2/173
2
© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Digital measuring errors
Thermocouples
Resistance thermometer
Input
Input
2
Measuring range
Min. measured span
Digital
accuracy
°C / (°F)
°C)
(°F)
°C
(°F)
Pt25
-200 ... +850
(-328 ... +1562)
10
(18)
0.3
(0.54)
Pt50
-200 ... +850
(-328 ... +1562)
10
(18)
0.15
(0.27)
Pt100 ... Pt200
-200 ... +850
(-328 ... +1562)
10
(18)
0.1
(0.18)
Pt500
-200 ... +850
(-328 ... +1562)
10
(18)
0.15
(0.27)
Pt1000
-200 ... +350
(-328 ... +662)
10
(18)
0.15
(0.27)
Pt25
-200 ... +649
(-328 ... +1200)
10
(18)
0.3
Pt50
-200 ... +649
(-328 ... +1200)
10
(18)
Pt100 ... Pt200
-200 ... +649
(-328 ... +1200)
10
Pt500
-200 ... +649
(-328 ... +1200)
Pt1000
Ni 25 ... Ni1000
Measuring range
Min. measured span
Digital
accuracy
°C
°C / (°F)
°C
(°F)
Type B
100 ... 1820
(212 ... 3308)
100
(180) 21)
(3.6)1)
Type C (W5)
0 ... 2300
(32 ... 4172)
100
(180) 2
(3.6)
Type D (W3)
0 ... 2300
(32 ... 4172)
100
(180) 12)
(1.8)2)
Type E
-200 ... +1000
(-328 ... +1832)
50
(90)
1
(1.8)
Type J
-210 ... +1200
(-346 ... +2192)
50
(90)
1
(1.8)
Type K
-200 ... +1370
(-328 ... +2498)
50
(90)
1
(1.8)
Type L
-200 ... +900
(-328 ... +1652)
50
(90)
1
(1.8)
(0.54)
Type N
-200 ... +1300
(-328 ... +2372)
50
(90)
1
(1.8)
0.15
(0.27)
Type R
-50 ... +1760
(-58 ... +3200)
100
(180) 2
(3.6)
(18)
0.1
(0.18)
Type S
-50 ... +1760
(-58 ... +3200)
100
(180) 2
(3.6)
10
(18)
0.15
(0.27)
Type T
-20 ... +400
(-328 ... +752)
40
(72)
1
(1.8)
-200 ... +350
(-328 ... +662)
10
(18)
0.15
(0.27)
Type U
-200 ... +600
(-328 ... +1112)
50
(90)
2
(3.6)
-60 ... +250
(-76 ... +482)
10
(18)
0.1
(0.18)
to IEC 60751
to JIS C1604-81
(°F)
1)
The digital accuracy in the range 100 to 300 °C (212 to 572 °F) is 3 °C
(5.4 °F).
2)
The digital accuracy in the range 1750 to 2300 °C (3182 to 4172 °F) is 2 °C
(3.6 °F).
Resistance-based sensors
Input
Measuring range
Min. measured span
Digital
accuracy
mV sensor
Input



Resistance
0 ... 390
5
0.05
Resistance
0 ... 2200
25
0.25
Measuring span
Min. measured span
Digital
accuracy
mV
mV
V
mV sensor
-10 ... +70
2
40
mV sensor
-100 ... +1100
20
400
The digital accuracy is the accuracy after the analog/digital conversion including linearization and calculation of the measured
value.
An additional error is generated in the output current 4 to 20 mA
as a result of the digital/analog conversion of 0.025 % of the set
span (digital-analog error).
The total error under reference conditions at the analog output is
the sum from the digital error and the digital-analog error (poss.
with the addition of cold junction errors in the case of thermocouple measurements).
2/174
Siemens FI 01 · 2016
© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Selection and Ordering data
Article No.
Temperature transmitter in field housing
Two-wire system 4 ... 20 mA, with electrical
isolation, with documentation on MiniDVD
7 NG 3 1 3 7 - 77777
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Integrated transmitter
SITRANS TH200, programmable
• Without Ex protection
• With Ex ia
• With Ex nAL for zone 2
• Total device SITRANS TF Ex d1)
• Total device SITRANS TF according to FM
(XP, DIP, NI, S)1)
SITRANS TH300, communication capability
according to HART V 5.9
• Without Ex-protection
• With Ex ia
• With Ex nAL for zone 2
• Total device SITRANS TF Ex d1)
• Total device SITRANS TF according to FM
(XP, DIP, NI, S)1)
Enclosure
Die-cast aluminium
Stainless steel precision casting
Connections/cable inlet
Screwed glands M20x1.5
Screwed glands ½-14 NPT
Digital indicator
Without
With
Mounting bracket and securing parts
Without
Made of steel
Made of stainless steel
5
5
5
5
5
0
1
2
4
5
6
6
6
6
6
0
1
2
4
5
A
E
B
C
0
1
0
1
2
Further designs
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
Order code
Test protocol (5 measuring points)
Functional safety SIL2
Functional safety SIL2/3
Explosion protection
• Explosion protection Ex ia to INMETRO
(Brazil) (only with 7NG313.-1....)
• Explosion protection Ex d to INMETRO
(Brazil) (only with 7NG313.-4....)
• Explosion protection Ex nA to INMETRO
(Brazil) (only with 7NG313.-2...)
• Explosion protection Ex i to NEPSI
(China) (only with 7NG313.-1...)
• Explosion protection Ex d to NEPSI
(China) (only with 7NG313.-4....)
• Explosion protection Ex nA to NEPSI
(China) (only with 7NG313.-2...)
• Explosion protection Ex d to KOSHA
(Korea) (only with 7NG313.-4...)
C11
C20
C23
• Explosion protection Ex i according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-1...)
E81
• Explosion protection Ex d according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-4...)
E82
• Explosion protection Ex nA according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-2...)
E83
Marine approvals
• Det Norske Veritas Germanischer Lloyd
(DNV GL)
• Bureau Veritas (BV)
• Lloyd’s Register of Shipping (LR)
• American Bureau of Shipping (ABS)
Two coats of lacquer on casing and cover (PU
on epoxy)
2
E25
E26
E27
E55
E56
E57
E70
D01
D02
D04
D05
G10
Transient protection
J01
Cable gland CAPRI 1/2 NPT ADE 4F,
nickle-plated brass (CAPRI 848694 and
810634) included
D57
Cable gland 1/2 NPT ADE 1F,
cable diam. 6 ... 12 (CAPRI 818694 and
810534) included
D58
Cable gland 1/2 NPT ADE 4F, stainless steel
(CAPRI 848699 and 810634) included
D59
Cable gland 1/2 NPT ADE 1F,
cable diam. 4 ... 8.5 (CAPRI 818674 and
810534) included
D60
Siemens FI 01 · 2016
2/175
© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Selection and Ordering data
Order code
Customer-specific programming
Add "-Z" to Article No. and specify Order
code(s)
2
Selection and Ordering data
Article No.
Accessories
Modem for SITRANS TH100, TH200, TR200 }
and TF with TH200 incl. parameterization
software T
with USB interface
7NG3092-8KU
A5E00364512
Y224)
MiniDVD for temperature measuring
}
instruments
with documentation in German, English,
French, Spanish, Italian and Portuguese, and
parameterization software SIPROM T
(included in delivery with SITRANS TF)
Pt100 (IEC) 2-wire, RL = 0 
U025)
Pt100 (IEC) 3-wire
U035)
HART modem
With USB interface
Pt100 (IEC) 4-wire
U045)
Thermocouple type B
U205)6)
Thermocouple type C (W5)
U215)6)
Thermocouple type D (W3)
U225)6)
Thermocouple type E
U235)6)
Thermocouple type J
U245)6)
Thermocouple type K
U255)6)
Thermocouple type L
U265)6)
Thermocouple type N
U275)6)
Thermocouple type R
U285)6)
Thermocouple type S
U295)6)
Thermocouple type T
U305)6)
Thermocouple type U
U315)6)
With TC: CJC external (Pt100, 3-wire)
U41
With TC: CJC external with fixed value, specify in plain text
Y50
Special differing customer-specific programming, specify in plain text
Y097)
Fail-safe value 3.6 mA (instead of 22.8 mA)
U363)
Measuring range to be set
Specify in plain text (max. 5 digits):
Y01: ... to ... °C, °F
Y012)
Measuring point no. (TAG), max. 8 characters
Y173)
Meas. point descriptor, max. 16 characters
Y234)
Meas. point message, max. 32 characters
Y244)
Only inscription on measuring point label:
specify in plain text: Measuring range
Supply units see Chapter "Supplementary Components".
1)
Without cable gland.
2)
For customer-specific programming for RTD and TC, the start value and
the end value of the required measuring span must be specified here.
3)
For this selection, Y01 or Y09 must also be selected.
4)
If only Y22, Y23 or Y24 are ordered and the label only has to be on the tag
plate, Y01 does not have to be specified.
5)
For this selection, Y01 must also be selected.
6)
Internal cold junction compensation is selected as the default for TC.
7)
For customer-specific programming, for example mV and ohm, the start
value and the end value of the required measuring span and the unit must
be entered here.
2/176
Siemens FI 01 · 2016
}
SIMATIC PDM parameterization software
also for SITRANS TH300
Mounting bracket and securing parts
Made of steel for 7NG313.-..B..
Made of steel for 7NG313.-..C..
Made of stainless steel for 7NG313.-..B..
Made of stainless steel for 7NG313.-..C..
7MF4997-1DB
see chapter 8
}
7MF4997-1AC
7MF4997-1AB
7MF4997-1AJ
7MF4997-1AH
Digital indicator1)
7MF4997-1BS
Connection board
A5E02226423
} Available ex stock.
Supply units see Chapter "Supplementary Components".
1)
It is not possible to upgrade devices with Ex protection
Ordering example 1:
7NG3135-0AB11-Z Y01+Y23+U03
Y01: -10 ... +100 °C
Y23: TICA1234HEAT
Ordering example 2:
7NG3136-0AC11-Z Y01+Y23+Y24+U25
Y01: -10 ... +100 °C
Y23: TICA 1234 ABC
Y24: HEATING BOILER 56789
Factory setting (transmitter):
• Pt100 (IEC 751) with three-wire circuit
• Measuring range: 0 ... 100 °C (32 ... 212 °F)
• Fault current 22.8 mA
• Sensor offset: 0 °C (0 °F)
• Damping 0.0 s
© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
Selection and Ordering data
Article No.
Selection and Ordering data
SITRANS TF field indicator
for 4 ... 20 mA signals,
with documentation on MiniDVD
7 NG 3 1 3 0 - 77777
Customer-specific programming
Add "-Z" to Article No. and specify Order
code(s)
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
0
1
2
4
5
Without Ex-protection
With Ex ia
With Ex nAL for zone 2
Total device SITRANS TF Ex d1)
Total device SITRANS TF according to FM
(XP, DIP, NI, S)1)
Enclosure
Die-cast aluminium
Stainless steel precision casting
A
E
Connections/cable inlet
Screwed glands M20x1.5
Screwed glands ½-14 NPT
Measuring range to be set
Specify in plain text (max. 5 digits):
Y01: ... to ... °C, °F
Y012)
Only inscription on TAG plate: specify in plain
text: Measuring range
Y223)
Only inscription on TAG plate: Measuring
point descriptor, max. 16 characters
Y233)
Only inscription on TAG plate: Measuring
point message, max. 27 characters
Y243)
Special differing customer-specific programming, specify in plain text
Y094)
1
Mounting bracket and securing parts
Without
Made of steel
Made of stainless steel
0
1
2
1)
Without cable gland.
2)
For customer-specific programming for RTD and TC, the start value and
the end value of the required measuring span must be specified here.
3)
If only Y22, Y23 or Y24 are ordered and the label only has to be on the tag
plate, Y01 does not have to be specified.
4)
For customer-specific programming, for example mV and ohm, the start
value and the end value of the required measuring span and the unit must
be entered here.
Order code
Selection and Ordering data
C11
• Explosion protection Ex i according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-1...)
E81
• Explosion protection Ex d according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-4...)
E82
Ordering example 1:
• Explosion protection Ex nA according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-2...)
E83
7NG3130-0AB10-Z Y01+Y23
Y01: -5...100 °C
Y23: TICA1234HEAT
E25
E26
E27
E55
E56
E57
E70
Article No.
Accessories
Test protocol (5 measuring points)
Explosion protection
• Explosion protection Ex ia to INMETRO
(Brazil) (only with 7NG313.-1....)
• Explosion protection Ex d to INMETRO
(Brazil) (only with 7NG313.-4....)
• Explosion protection Ex nA to INMETRO
(Brazil) (only with 7NG313.-2...)
• Explosion protection Ex i to NEPSI
(China) (only with 7NG313.-1...)
• Explosion protection Ex d to NEPSI
(China) (only with 7NG313.-4....)
• Explosion protection Ex nA to NEPSI
(China) (only with 7NG313.-2...)
• Explosion protection Ex d to KOSHA
(Korea) (only with 7NG313.-4...)
Marine approvals
• Det Norske Veritas Germanischer Lloyd
(DNV GL)
• Bureau Veritas (BV)
• Lloyd’s Register of Shipping (LR)
• American Bureau of Shipping (ABS)
Two coats of lacquer on casing and cover
(PU on epoxy)
Transient protection
Cable gland CAPRI 1/2 NPT ADE 4F,
nickle-plated brass (CAPRI 848694 and
810634) included
Cable gland 1/2 NPT ADE 1F, cable diam.
6 ... 12 (CAPRI 818694 and 810534) included
Cable gland 1/2 NPT ADE 4F, stainless steel
(CAPRI 848699 and 810634) included
Cable gland 1/2 NPT ADE 1F, cable diam.
4 ... 8.5 (CAPRI 818674 and 810534) included
2
Supply units see Chapter "Supplementary Components".
B
C
Digital indicator
With
Further designs
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
1
1
1
1
1
Order code
MiniDVD for temperature measuring
}
instruments
with documentation in German, English,
French, Spanish, Italian and Portuguese, and
parameterization software SIPROM T
(included in delivery with SITRANS TF)
Mounting bracket and securing parts
Made of steel for 7NG313.-..B..
Made of steel for 7NG313.-..C..
Made of stainless steel for 7NG313.-..B..
Made of stainless steel for 7NG313.-..C..
}
A5E00364512
7MF4997-1AC
7MF4997-1AB
7MF4997-1AJ
7MF4997-1AH
Digital indicator1)
7MF4997-1BS
Connection board
A5E02226423
} Available ex stock.
1)
It is not possible to upgrade devices with Ex protection
Ordering example 2:
D01
D02
D04
D05
G10
7NG3130-0AC10-Z Y01+Y23+Y24
Y01: 0 ... 20 BAR
Y23: PICA 1234 ABC
Y29: HEATING BOILER 67890
Factory setting (field indicator):
4 ... 20 mA
J01
D57
D58
D59
D60
Siemens FI 01 · 2016
2/177
© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
■ Dimensional drawings
55
(2.17)
52 (2.05)
28
(1.10)
2
237 (9.33)
a
3
36.5 (1.44)
a: max. 164 (6.46) (M20x1.5)
max. 189 (7.44) (½-14 NPT)
120 (4.72)
1
68 (2.68)
4
5
72 (2.83)
8
80 (3.15)
100* (3.94)
6
50
(1.97)
117 (4.61)
50* (1.97)
b
20
(0.79)
138* (5.43)
80 (3.15)
2
144 (5.67)
13 (0.51)
15* (0.59)
b: max. 25 (0.98) (M20x1.5)
max. 50 (1.97) (½-14 NPT)
*) Dimensions for stainless
steel enclosure
123 (4.84)
Ø 50 ... 60
(1.97 ... 2.36)
7
105 (4.13)
1 Sensor connection (screwed gland M20x1.5 or ½-14 NPT)
2 Blanking plug
3 Electrical connection (screwed gland M20x1.5 or ½-14 NPT)
7 Mounting bracket (option) with clamp for securing to a
vertical or horizontal pipe
4 Terminal side, output signal
8 Cover with window for digital display
5 Terminal side, sensor
SITRANS TF, dimensions in mm (inches)
2/178
6 Protective cover (without function)
Siemens FI 01 · 2016
© Siemens AG 2016
Temperature Measurement
Transmitter for field mounting/field indicator
SITRANS TF - Transmitter, two-wire system and SITRANS TF - Field indicator for 4 to 20 mA
■ Schematics
6
5
4
3
3
5
4
3
5
4
6
+ -
6
5
4
2
5
+ TC -
6
+ -
6
5
4
Cold junction compensation
Internal/fixed value
Two-wire system 1)
3
3
5
4
3-W
3-W
4
3
R
Two-wire system 1)
3
6
5
4
RTD
3
6
+ -
3-W
4
6
+ -
6
+ -
6
5
4
5
RTD
3
3
4
3-W
3
3-W
3
Thermocouple
Resistance
3-W
Resistance thermometer
6
+ -
6
5
4
5
+ TC -
R
RTD
6
+ -
6
5
4
3
3
4
Cold junction compensation with
external Pt100 in two-wire system 1)
3
3
6
+ -
4
6
5
3-W
4
3-W
3
3
Three-wire system
3-W
Three-wire system
6
+ -
4
5
4
6
5
5
5
+ TC -
4
3-W
3
6
+ -
6
5
4
Cold junction compensation with
external Pt100 in three-wire system
Four-wire system
3
3
5
4
3-W
Four-wire system
3
RTD
R
6
+ -
6
5
4
5
RTD2
3
3
4
4
+ TC2 -
R2
3-W
RTD
6
+ -
6
5
5
+ TC1 -
R1
RTD1
Generation of average
value / difference 1)
Generation of average value / difference
with internal cold junction compensation
Programmable line resistance for the purpose of correction.
Voltage measurement
4
4
3-W
3
3
6
+ -
Current measurement
6
5
4
6
+ -
6
5
4
5
+
3
3
3-W
1)
Generation of average
value / difference 1)
5
-
R
U
+
-
I
SITRANS TF, sensor connection assignment
Siemens FI 01 · 2016
2/179
© Siemens AG 2016
Temperature Measurement
Transmitters for field mounting
SITRANS TF fieldbus transmitter
■ Overview
■ Application
The SITRANS TF can be used everywhere where temperatures
need to be measured under particularly harsh conditions. Which
is why users from all industries have opted for this field device.
2
The rugged enclosure protects the electronics. The stainless
steel model is almost completely resistant to sea water and other
aggressive elements.
The inner workings offer high measuring accuracy, universal input and a wide range of diagnostic options.
■ Function
Our field devices for heavy industrial use
• FOUNDATION fieldbus
• PROFIBUS PA
The SITRANS TF temperature transmitter works where others
can’t cope.
■ Benefits
• For universal use as a transmitter for resistance thermometers,
thermocouple elements,  or mV signals
• Rugged two-chamber enclosure in die-cast aluminium or
stainless steel
• Degree of protection IP66/67/68
• Can be mounted elsewhere if the measuring point
- is hard to access,
- is subject to high temperatures,
- is subject to vibrations from the system,
- or if you want to avoid long neck tubes and/or protective
tubes.
• Can be mounted directly on American-design sensors
• Wide range of approvals for use in potentially explosive atmospheres. "Intrinsically safe, non-sparking and flameproof" type
of protection, for Europe and USA
- Resistance thermometer
- Thermocouple
- mV sensor
- Resistance-based sensors
Mode of operation
The following function diagram explains the mode of operation
of the transmitter.
The only difference between the two versions of the SITRANS TF
(7NG3137-... and 7NG3138-...) is the type of field bus protocol
used (PROFIBUS PA or FOUNDATION fieldbus).
A/D
converter
CPU
Communication
3
Internal
Pt100
SITRANS TF with TH400, function diagram
Siemens FI 01 · 2016
EEPROM
Complex configuration
Correction coefficient
Factory settings
- PROFIBUS PA protocol (7NG3137)
or
- FOUNDATION Fieldbus protocol
(7NG3138)
Ex power circuit
5
4
2/180
Transmitter with FOUNDATION fieldbus communication
• Function blocks: 2 x analog and 1 x PID
• Functionality: Basic or LAS
Electrically
isolated
6
Input 2
Transmitter with PROFIBUS PA communication
• Function blocks: 2 x analog
Transformer
Input 1
Input 2
Differential
Mean value
Redundancy
Terminal temperature
Engineering units
Diagnostic functions
Table linearization
Polynomial linearization
Process calibration
Optional inputs:
Input 1
Features
• Polarity-neutral bus connection
• 24-bit analog-digital converter for high resolution
• Electrically isolated
• Version for use in hazardous areas
• Special characteristic
• Sensor redundance
1
Bus connection
2
© Siemens AG 2016
Temperature Measurement
Transmitters for field mounting
SITRANS TF fieldbus transmitter
System communication
Thermocouple
Bus terminator
PROFIBUS PA
Segment
coupler
SITRANS TF
with TH400 PA
Bus terminator
FOUNDATION Fieldbus
Segment
coupler
SITRANS TF
with TH400 FF
to IEC 584
Measuring range
• Type B
400 ... 1820 °C (752 ... 3308 °F)
• Type E
-100 ... +1000 °C
(-148 ... +1832 °F)
• Type J
-100 ... +1000 °C
(-148 ... +1832 °F)
• Type K
-100 ... +1200 °C
(-148 ... +2192 °F)
• Type N
-180 ... +1300 °C
(-292 ... +2372 °F)
• Type R
-50 ... +1760 °C (-58 ... +3200 °F)
• Type S
-50 ... +1760 °C (-58 ... +3200 °F)
• Type T
-200 ... +400 °C (-328 ... +752 °F)
to DIN 43710
• Type L
-200 ... +900 °C (-328 ... +1652 °F)
• Type U
-200 ... +600 °C (-328 ... +1112 °F)
to ASTM E988-90
SITRANS TF with TH400, communication interface
■ Technical specifications
• Type W3
0 ... 2300 °C (32 ... 4172 °F)
• Type W5
0 ... 2300 °C (32 ... 4172 °F)
External cold junction compensation
-40 ... +135 °C (-40 ... +275 °F)
Sensor fault detection
Input
Analog/digital conversion
• Sensor break detection
Yes
• Sensor short-circuit detection
Yes, < 3 mV
4 A
• Measurement rate
< 50 ms
• Sensor current in the event of
open-circuit monitoring
• Resolution
24-bit
mV sensor - voltage input
Resistance thermometer
Measuring range
-800 ... +800 mV
Pt25 ... 1000 to IEC 60751/JIS C
1604
Input resistance
10 M
• Measuring range
2
Output
-200 ... +850 °C
(-328 ... +1562 °F)
Filter time (programmable)
0 ... 60 s
Ni25 ... 1000 to DIN 43760
Update time
< 400 ms
• Measuring range
-60 ... +250 °C (-76 ... +482 °F)
Measuring accuracy
• Measuring range
-50 ... +200 °C (-58 ... +392 °F)
Accuracy is defined as the higher
value of general values and basic
values.
Line resistance per sensor cable
Max. 50 
General values
Sensor current
Nominal 0.2 mA
Type of input
Absolute accuracy
• Sensor break detection
Yes
All
• Sensor short-circuit detection
Yes, < 15 
  0.05 % of the   0.002 % of
measured value the measured
value/°C
Cu10 ... 1000,  = 0.00427
Sensor fault detection
Resistance-based sensors
Basic values
Measuring range
0 ... 10 k
Line resistance per sensor cable
Max. 50 
Sensor current
Nominal 0.2 mA
Sensor fault detection
• Sensor break detection
• Sensor short-circuit detection
Temperature
coefficient
Yes
Yes, < 15 
Type of input
Basic accuracy
Temperature
coefficient
Pt100 and Pt1000
  0.1 °C
  0.002 °C/°C
Ni100
  0.15 °C
  0.002 °C/°C
Cu10
  1.3 °C
  0.02 °C/°C
Resistance-based sensors
  0.05 
  0.002 /°C
Voltage source
  10 V
  0.2 V/°C
Thermocouple, type:
E, J, K, L, N, T, U
  0.5 °C
  0.01 °C/°C
Thermocouple, type:
B, R, S, W3, W5
  1 °C
  0.025 °C/°C
Cold junction compensation
  0.5 °C
Reference conditions
Warming-up time
30 s
Signal-to-noise ratio
Min. 60 dB
Calibration condition
20 ... 28 °C (68 ... 82 °F)
Siemens FI 01 · 2016
2/181
© Siemens AG 2016
Temperature Measurement
Transmitters for field mounting
SITRANS TF fieldbus transmitter
Conditions of use
Certificates and approvals
Ambient conditions
2
Explosion protection ATEX
Permissible ambient temperature
-40 ... +85 °C (-40 ... +185 °F)
EC type test certificate
Permissible storage temperature
-40 ... +85 °C (-40 ... +185 °F)
Relative humidity
 98 %, with condensation
• Type of protection "intrinsic safety i" II 2 (1) G Ex ib [ia Ga] IIC T6 Gb
II 2 G Ex ib IIC T6 Gb
(version: 7NG313x-1xxxx)
II 1D Ex ia IIIC T100 °C Da
Insulation resistance
ZELM 11 ATEX 0471 X
Conformity statement
ZELM 11 ATEX 0471 X
50 V AC/75 V DC
• "Operating equipment that is nonignitable and has limited energy"
type of protection
(version: 7NG313x-2xxxx)
II 3 G Ex ic IIC T6/T4 Gc
II 3 G Ex nA IIC T6/T4 Gc
II 3 G Ex nA [ic] IIC T6/T4 Gc
NAMUR
NE21
EC type test certificate
ZELM 11 ATEX 0472 X
EMC 2014/30/EU Emission and
Noise Immunity
EN 61326-1, EN 61326-2-5
• "Flame-proof enclosure" type of
protection (version: 7NG313x4xxxx)
II 2 G Ex d IIC T6/T5 Gb
II 2 D Ex tb IIIC T100 °C Db
Weight
Approx. 1.5 kg (3.3 lb) without
options
Explosion protection: FM for USA
Dimensions
See "Dimensional drawings"
Enclosure materials
• Die-cast aluminum, low in copper, GD-AlSi 12 or stainless steel
• Polyester-based lacquer for GD
AlSi 12 enclosure
• Stainless steel rating plate
• Type of protection XP, DIP, NI and S XP / I / 1 / BCD / T5,T6; Type 4X
(version 7NG313x-5xxxx)
DIP / II, III / 1 / EFG / T5,T6;
Type 4X
NI / I / 2 / ABCD / T5,T6; Type 4X
S / II, III / 2 / FG T5,T6; Type 4X
Electrical connection, sensor connection
• screw terminals
• Cable inlet via M20 x 1.5 or ½
-14 NPT screwed gland
• Bus connection with M12 plug
(optional)
• Test voltage
500 V AC for 60 s
• Continuous operation
Electromagnetic compatibility
Construction
Mounting bracket (optional)
Degree of protection
Steel, galvanized and chromeplated or stainless steel
IP66/67 to EN 60529
Auxiliary power
Power supply
• Standard, Ex "d", Ex "nA", Ex "nL",
XP, NI
10.0 ... 32 V DC
• Ex "ia", Ex "ib"
10.0 ... 30 V DC
• In FISCO/FNICO installations
10.0 ... 17.5 V DC
Power consumption
< 11 mA
Max. increase in power consumption in the event of a fault
< 7 mA
• FM approval
Other certificates
FM 3017742
EAC Ex(GOST), INMETRO,
NEPSI, KOSHA
Communication
Parameterization interface
• PROFIBUS PA connection
- Protocol
A&D profile, Version 3.0
- Protocol
EN 50170 Volume 2
- Address (for delivery)
126
- Function blocks
2 x analog
• FOUNDATION fieldbus connection
- Protocol
FF protocol
- Protocol
FF design specifications
- Functionality
Basic or LAS
- Version
ITK 4.6
- Function blocks
2 x analog and 1 x PID
Factory setting
for SITRANS TH400 PA
Sensor
Pt100 (IEC)
Type of connection
3-wire circuit
Unit
°C
Failure mode
Last valid value
Filter time
0s
PA address
126
PROFIBUS Ident No.
Manufacturer-specific
for SITRANS TH400 FF
2/182
Siemens FI 01 · 2016
Sensor
Pt100 (IEC)
Type of connection
3-wire circuit
Unit
°C
Failure mode
Last valid value
Filter time
0s
Node address
22
© Siemens AG 2016
Temperature Measurement
Transmitters for field mounting
SITRANS TF fieldbus transmitter
Selection and Ordering data
Article No.
Temperature transmitter in field enclosure
with fieldbus communication and electrical
isolation, with documentation on MiniDVD
7 NG 3 1 3 7 - 777 0 7
Enclosure
Die-cast aluminium
Stainless steel precision casting
Connections/cable inlet
Screwed glands M20x1.5
Screwed gland s ½-14 NPT
Mounting bracket and fastening parts
None
Made of steel
Stainless steel
Order code
Test report (5 measuring points)
C11
2
Bus connection
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Integrated transmitter
SITRANS TH400 with PROFIBUS PA
• Without Ex protection
• With Ex ia (ATEX)
• With Ex nAL for zone 2 (ATEX)
• Total device SITRANS TF Ex d1)
• Total device SITRANS TF according to FM
(XP, DIP, NI, S)1)
SITRANS TH400, with FOUNDATION fieldbus
• Without Ex protection
• With Ex ia (ATEX)
• With Ex nAL for zone 2 (ATEX)
• Total device SITRANS TF Ex d1)
• Total device SITRANS TF according to FM
(XP, DIP, NI, S)1)
Further designs
Please add "-Z" to Article No. and specify
Order code(s) and plain text.
7
7
7
7
7
0
1
2
4
5
8
8
8
8
8
0
1
2
4
5
• M12 plug (metal), without mating connector
M002)
• M12 plug (metal), with mating connector
M012)
Explosion protection
A
E
B
C
0
1
2
• Explosion protection Ex ia to INMETRO
(Brazil) (only with 7NG313.-1....)
E25
• Explosion protection Ex d to INMETRO
(Brazil) (only with 7NG313.-4....)
E26
• Explosion protection Ex nA to INMETRO
(Brazil) (only with 7NG313.-2...)
E27
• Explosion protection Ex i to NEPSI
(China) (only with 7NG313.-1...)
E55
• Explosion protection Ex d to NEPSI
(China) (only with 7NG313.-4....)
E56
• Explosion protection Ex nA to NEPSI
(China) (only with 7NG313.-2...)
E57
• Explosion protection Ex d to KOSHA
(Korea) (only with 7NG313.-4...)
E70
• Explosion protection Ex i according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-1...)
E81
• Explosion protection Ex d according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-4...)
E82
• Explosion protection Ex nA according to EAC
(Russia/Belarus/Kazahstan)
(only for 7NG313.-2...)
E83
Marine approvals
• Det Norske Veritas Germanischer Lloyd
(DNV GL)
• Bureau Veritas (BV)
• Lloyd’s Register of Shipping (LR)
• American Bureau of Shipping (ABS)
D01
D02
D04
D05
Two coats of lacquer on casing and cover (PU
on epoxy)
G10
Transient protection
J01
Cable gland CAPRI 1/2 NPT ADE 4F,
nickle-plated brass (CAPRI 848694 and
810634) included
D57
Cable gland 1/2 NPT ADE 1F,
cable diam. 6 ... 12 (CAPRI 818694 and
810534) included
D58
Cable gland 1/2 NPT ADE 4F, stainless steel
(CAPRI 848699 and 810634) included
D59
Cable gland 1/2 NPT ADE 1F,
cable diam. 4 ... 8.5 (CAPRI 818674 and
810534) included
D60
Siemens FI 01 · 2016
2/183
© Siemens AG 2016
Temperature Measurement
Transmitters for field mounting
SITRANS TF fieldbus transmitter
Selection and Ordering data
Order code.
Customer-specific programming
Add "-Z" to Article No. and specify Order
code(s)
2
Selection and Ordering data
Article No.
Accessories
MiniDVD for temperature measuring
instruments
} A5E00364512
Measuring range to be set
Specify in plain text (max. 5 digits):
Y01: ... to ... °C, °F
Y013)
Meas. point no. (TAG), max. 8characters
Y154)
Meas. point descriptor, max. 16 characters
Y234)
Meas. point message, max. 32 characters
Y245)
Bus address, specify in plain text
Y254)
Pt100 (IEC) 2-wire, RL = 0 
U026)
Pt100 (IEC) 3-wire
U036)
Pt100 (IEC) 4-wire
U046)
Thermocouple type B
U206)7)
Thermocouple type C (W5)
U216)7)
Thermocouple type D (W3)
U226)7)
Thermocouple type E
U236)7)
Thermocouple type J
U246)7)
Thermocouple type K
U256)7)
Thermocouple type L
U266)7)
Ordering example 2:
Thermocouple type N
U276)7)
Thermocouple type R
U286)7)
Thermocouple type S
U296)7)
7NG3137-0AC01-Z Y01+Y15+Y25+U25
Y01: -10 ... +100 °C
Y15: TICA 1234 ABC 5678
Y25: 35
Thermocouple type T
U306)7)
Thermocouple type U
U316)7)
With TC: CJC: external (Pt100, 3-wire)
U41
With TC: CJC: external with fixed value, specify in plain text
Y50
Special differing customer-specific programming, specify in plain text
Y098)
1)
Without cable gland
2)
Not available for explosion protection Ex d or XP.
3)
For customer-specific programming for RTD and TC, the start value and
the end value of the required measuring span must be specified here.
4)
If only Y15, Y23 or Y25 are ordered and the label only has to be on the tag
plate, Y01 does not have to be specified.
5)
For this selection, Y01 or Y09 must also be selected.
6)
For this selection, Y01 must also be selected.
7)
Internal cold junction compensation is selected as the default for TC.
8)
For customer-specific programming, for example mV and ohm, the start
value and the end value of the required measuring span and the unit must
be entered here.
2/184
Siemens FI 01 · 2016
with documentation in German, English,
French, Spanish, Italian and Portuguese, and
parameterization software SIPROM T
(included in delivery with SITRANS TF)
SIMATIC PDM parameterization software
also for SITRANS TF with TH400 PA
Mounting bracket and fastening parts
Made of steel for 7NG313.-..B..
Made of steel for 7NG313.-..C..
Made of stainless steel for 7NG313.-..B..
Made of stainless steel for 7NG313.-..C..
see Sec. 8
7MF4997-1AC
7MF4997-1AB
} 7MF4997-1AJ
7MF4997-1AH
Connection board
A5E02391790
} Available ex stock.
Ordering example 1:
7NG3137-0AB01-Z Y01+Y15+Y25+U03
Y01: -10 ... +100 °C
Y15: TICA1234HEAT
Y25: 33
Factory setting:
• for SITRANS TH400 PA:
- Pt100 (IEC) with 3-wire circuit
- Unit: °C
- Failure mode: last valid value
- Filter time: 0 s
- PA address: 126
- PROFIBUS Ident No.: manufacturer-specific
• for SITRANS TH400 FF:
- Pt100 (IEC) with 3-wire circuit
- Unit: °C
- Failure mode: last valid value
- Filter time: 0 s
- Node address: 22
© Siemens AG 2016
Temperature Measurement
Transmitters for field mounting
SITRANS TF fieldbus transmitter
55 (2.17)
28
(1.10)
80 (3.15)
100* (3.94)
6
2
2
3
36.5 (1.44)
120 (4.72)
1
a: max. 164 (6.46) (M20x1.5)
max. 189 (7.44) (½-14 NPT)
68 (2.68)
4
72 (2.83)
5
237 (9.33)
a
Ø 80 (3.15)
50 (1.97)
52 (2.05)
50* (1.97)
b
117 (4.61)
144 (5.67)
138* (5.43)
20 (0.79)
■ Dimensional drawings
b: max. 25 (0.98) (M20x1.5)
max. 50 (1.97) (½-14 NPT)
123 (4.84)
*) Dimensions for stainless
steel enclosure
Ø 50 ... 60
(1.97 ... 2.36)
7
1 Sensor connection (screwed gland M20x1.5 or ½-14 NPT)
2 Blanking plug
3 Electrical connection (screwed plug M20x1.5 orr ½-14 NPT),
optional M12 plug
4 Terminal side, bus connection
105 (4.13)
5 Terminal side, sensor
6 Protective cover (without function)
7 Mounting bracket (optional) with clamp securing to
a vertical or horizontal pipe
SITRANS TF with TH400, dimensions in mm (inches)
Siemens FI 01 · 2016
2/185
© Siemens AG 2016
Temperature Measurement
Transmitters for field mounting
SITRANS TF fieldbus transmitter
■ Schematics
Thermocouple
Resistance thermometer
2
Resistance
+ Internal
cold junction compensation
Two-wire system 1)
+
Three-wire system
Three-wire system
-
Four-wire system
Cold junction compensation
with external Pt100 in three-wire system
2
1
+
Mean-value/differential or
redundancy generation
2 x two-wire system 1)
-
Cold junction compensation
with external Pt100 in two-wire system 1)
+
Four-wire system
Two-wire system 1)
1
+
2
-
-
Mean value, differential or
redundancy generation with internal
cold junction compensation
2
1
Mean value, differential or redundancy generation
1 resistor in two-wire system 1)
1 resistor in three-wire system
Voltage measurement
2
1
Mean-value/differential or
redundancy generation
1 sensor in two-wire system 1)
1 sensor in three-wire system
1)
Siemens FI 01 · 2016
+
2
-
Mean value, differential or
redundancy generation and
cold junction compensation
with internal Pt100
in two-wire system 1)
Programmable line resistance for the purpose of correction.
SITRANS TF with TH400, sensor connection assignment
2/186
+1 -
+
-
One voltage source
+
1
-
2
+ -
Measurement of mean value, differential and
redundancy with 2 voltage sources