Τεχνικός κατάλογος Chiara Κατεβάστε το α�χείο

Chiara - Technical details
General information
Main technical data and reference standards for the devices in the range
Component
Reference standards
Prolonged
operation
No.
changes
of position
Insulation
resistance
Breaking capacity or
utilization category
(MW)
>5
1.25 In
40000
for 1 minute
(200 changes
at In 250V~
CEI 23-5/CEI 23-50/CEI 23-16
2000 at 50Hz
of position)
1.25 In
cosϕ = 0.6)
10000
(EN 60884-1)
for 1 minute
(100 changes
at In 250V~
CEI 23-9/CEI 23-62
2000 at 50Hz
of position)
-
cosϕ = 0,8)
50000
(EN 60669-1/EN 60669-2-2)
for 1 minute
CEI 94-4/CEI-EN 61810-1
2000 at 50Hz
(EN 60669-1/EN 60669-2-2)
for 1 minute
Automatic
CEI 23-3
2000 at 50Hz
MCBs
Automatic
(EN 60898)
CEI 23-95
CEI 23-9
Test
voltage
withstand
(V)
2000 at 50Hz
Operating mechanisms CEI 23-9
(EN 60669-1)
Socket outlets
5
Basic electrical data*
Latching relay
Monostable relays
RCDs
Supports and frames
>5
>5
Resistance to abnormal heat
and fire
Termopressione Glow wire
con biglia
tests
(°C)
125
(°C)
850
125
850
125
850
125
850
a In 250V~
1.25 In
cosϕ = 0,6)
50000
(200 changes
at In 250V~
-
of position)
1.5...3kA
cosϕ = 0,6)
8000
125
850
for 1 minute
2000 at 50Hz
-
1.5...3kA
4000
125
850
for 1 minute
-
-
-
-
75
650
>5
(EN 60669-1)
*For the rated voltages and currents see the specifications for the individual part codes.
Clamping capacity of the terminals
Flexible wires
Min. 0.75 mm²
5/22
Rigid wires
Max. 2x4 mm²
Min. 0.5 mm²
2CSC600290D0201 | Mylos, Élos, Chiara
Cable traction resistance of terminals: > 50N
Max. 2x2.5 mm²
Adhesion of switches and device to the support: > 0.6J
Chiara - Technical details
Installation solutions
Composition method for devices and supports
5
Installing and removing switches from the support
- Frontal installation of the
switches on the frame
- Modularity of the switches:
22 mm
Specifications of screws and terminals
– Captive screws with open position captive screws
with cross and slot head and clamping plate.
– Double input protected terminals for one or two
conductors (rigid or flexible).
Mylos, Élos, Chiara | 2CSC600290D0201
5/23
Chiara - Technical details
Installation solutions
Installation on concrete walls
No. Modules
Screw distance
Recommended box
2 (with claws)
-
00 050
2 (with screws)
60 mm
00 050
3
83.5 mm
1SL006A00
4
108 mm
00 053
7
100 mm
1SL0064A00
Note: For further information on ABB boxes for concrete walls please refer to the
catalog 1SLC001001D0905 - Insulating Enclosures and Installation Materials
(see page 5/66)
5
Installation of plasterboard walls
No. Modules
Screw distance
Recommended box
2 (with screws)
-
10801/10802/10807
2 (with claws)
60 mm
10801/10802/10807
3
83.5 mm
10804
4
108 mm
Ave 254CG,
BTicino PS564N,
Gewiss GW24245
Vimar V71604
7
100 mm
Bticino PS567N
Gewiss 24246
Vimar V71606
Note: For further information on ABB boxes for plasterboard walls please refer to the
catalog 1SLC001001D0905 - Insulating Enclosures and Installation Materials
(see page 5/66).
5/24
2CSC600290D0201 | Mylos, Élos, Chiara
Protected installation with IP40/55 wall-mounted enclosures
No. Modules
IP40 enclosure
IP55 enclosure
1 (on 2-module enclosure)
2CSK2140CH
2CSK2155CH
2
2CSK2240CH
2CSK2255CH
3
2CSK2340CH
2CSK2355CH
4
2CSK2440CH
2CSK2455CH
The watertight enclosures allow the direct assembly of devices without the aid of supports.
The devices are inserted from the rear. See technical details on page 5/57.
For further information on IP40/IP55 wall-mounted enclosures, please refer to the
catalog 1SLC001001D0905 - Insulating Enclosures and Installation Materials
(see page 5/66).
5
IP40 wall-mounted enclosure
IP55 wall-mounted enclosure
Protected installation with watertight escutcheon plate
No. Modules
IP55 escutcheon plate
2 (on a square or round box with screws, center
2CSK3255CH
distance 60mm)
3
2CSK3355CH
Note: The watertight escutcheon plates provide a self-supporting solution that allows
direct assembly of devices without the aid of supports. The devices are inserted from
the rear.
IP55 wall-mounted escutcheon plate
Mylos, Élos, Chiara | 2CSC600290D0201
5/25
Chiara - Technical details
Installation solutions
Installation on raised floors with Undernet under-floor turrets
No. Modules
Dedicated adapter
Undernet tower
5 (max 20 contact blocks)
2CSK1625CH
10900 e 10901
6 (max 12 contact blocks)
2CSK1626CH
10902 e 10903
Note: The dedicated adapter provides a self-supporting solution that allows direct
assembly of devices without the aid of supports. The devices are inserted from the rear.
The use of finishing plates is not required.
For further information on Undernet under-floor turrets, please refer to the catalog
1SLC006001D0903 - Under-floor Distribution Systems (see page 5/66).
5
Installation on surface mounted boxes
No. Modules
Wall box
Frame
2
42 096
Use a 2M self-supporting frame
3
41 823
Use a 3M self-supporting frame
3
41 822
Use a 3M self-supporting frame
4
41 830
Use a 4M self-supporting frame
Note: The self-supporting frames allow the direct assembly of devices without the aid
of supports. The devices are inserted from the rear.
For further information on the wall boxes and duct systems, please refer to the catalog
1SLC800001D0905 - Plastic and Metal Duct Systems (see page 5/66).
5/26
2CSC600290D0201 | Mylos, Élos, Chiara
Installation on Lusy table towers
No. Modules
Lusy tower
Frame
4
10 507
Use a 4M self-supporting frame
Note: The self-supporting frames allow the direct assembly of devices without the aid of
supports. The devices are inserted from the rear.
For further information on the Lusy table towers, please refer to the catalog
1SLC006001D0903 - Under-floor Distribution Systems (see page 5/66).
5
Installation
sta at o o
on DIN rail
a adapter
No. Modules
Dedicated adapter
1
2CSK1608CH
2
2CSK1608CH
3
2CSK1608CH
Note: The DIN rail adapter allows devices to be assembled without the aid of supports.
The devices are inserted from the front. See technical details on page 5/59.
Mylos, Élos, Chiara | 2CSC600290D0201
5/27
Chiara - Technical details
Selection of lights
Control devices
5
Lamps
2CSK1001CH
Single-pole switch, 16A - 250V~
2CSK1002CH
Double-pole switch, 16A - 250V~
2CSK1004CH
Single-pole switch, 16A - 250V~, 2 modules
2CSK1003CH
Single-pole two-way switch, 16A - 250V~
2CSK1007CH
Single-pole two-way switch, 16A - 250V~, 2 modules
2CSK1010CH
Intermediate switch, 16A - 250V~
2CSK1008CH
Intermediate switch, 16A - 250V~, 2 modules
2CSK1005CH
Single-pole push switch NO, 16A
2CSK1016CH
Single-pole push switch NC, 16A
2CSK1020CH
Single-pole push switch NO with cord pull, 16A with 2.25 m cord
Filament
2CSK1021CH
Single-pole push switch NC with cord pull, 16A with 2.25 m cord
2CSK1613CH White
2CSK1022CH
Single-pole push switch 1 NO and 1 NC, 16A, with ON
230V
2CSK1023CH
Single-pole push switch 1 NO and 1 NC, 16A, with OFF symbol
0.4W
2CSK1024CH
Single-pole push switch NO, 16A, with red diffuser
2CSK1025CH
Single-pole push switch NO, 16A, with green diffuser
2CSK1026CH
Single-pole push switch NO, 16A, with orange diffuser
2CSK1027CH
Single-pole push switch NO, 16A, with white diffuser
2CSK1028CH
Single-pole push switch NO, 16A, with BELL
2CSK1029CH
Single-pole push switch NO, 16A, with KEY
2CSK1030CH
Single-pole push switch NO, 16A, with STAIR LIGHT
2CSK1031CH
Single-pole push switch NO, 16A, with backlit label holder plate
2CSK1032CH
Single-pole push switch NO, 16A, with backlit label holder plate, 3 modules
Signalling devices
Lamps
2CSK1310CH
Warning light, ORANGE colour
2CSK1311CH
Warning light, WHITE colour
2CSK1312CH
Warning light, RED colour
230V
2CSK1313CH
Warning light, GREEN colour
0.4W
Switch
illumination
5/28
2CSC600290D0201 | Mylos, Élos, Chiara
Filament
2CSK1613CH White
Chiara - Technical details
Control devices
Switches, two-way switches, intermediate switches and pushbuttons
Area of application
Control (on and off) of ohmic-inductive loads:
Backlighting of the control devices
Night-time location
- with filament and fluorescent lamps (corrected and
uncorrected);
- dedicated circuits for powered equipment (aspirators, range
hoods, shutters, blinds, fans, etc..) and controllable outlets.
To eliminate architectural barriers in creating installations, we
recommend the use of luminous controls (Article 4 of Italian
Ministerial Decree no. 236 del 14.06.1989).
Characteristics
- It allows the command key to be identified in the dark.
- We recommend the use of white, blue, green or red
Chiara lamps.
Applications
- Bedrooms
- Corridors
Functional signalling
Characteristics
- This allows the command key to be identified and the
ON/OFF status of a circuit to be signalled in the dark.
Technical specifications
Rated voltage
250V~
Rated current
10A (16A for pushbuttons)
Opening distance of the contacts
> 3 mm
Dielectric strength
> 2000V~
Reference standards
LV Directive EN 60669-1.
Customization of the control device keys
The illuminable keys of the Chiara wiring accessories’ range
are supplied with all most widely used functional symbols.
Wiring diagrams
The diagrams provided below are the most widely applied
installation solutions in creating lighting points.
Applications
- General services of a building complex (entrance halls,
stair lights, landings etc.)
- Public environments (cinemas, theatres etc.)
Signalling with symbols
Characteristics
- This allows the command key and its specific function
to be identified in the dark.
Applications
- Warehouses, shops, offices
- Hotels
- Nursing homes, hospitals
With warning light
Characteristics
- Allows the ON/OFF status of an appliance or a lighting
circuit, even at a distance.
- Visible from both a front and side position.
Applications
- Signalling the switching on of lighting points outside the
environment in which the control device is installed
Mylos, Élos, Chiara | 2CSC600290D0201
5/29
5
Chiara - Technical details
Control devices
Example of functional signalling
L
L
LOAD
LOAD
N
N
Warning light on when the switch is OFF (if the switch is in the ON state,
the warning light is off while the load is ON).
The two warning lights switch on and off respectively
when the load is in the OFF and ON state.
5
Example of remote signalling
L
L
LOAD
LOAD
N
N
Warning light placed in parallel to the load, of which indicates
the ON/OFF state (it is on when the switch is ON).
Two warning lights placed in parallel with the load
(they switch on and off with it).
Instructions for installation in systems with relays and
illuminable push switches
The lamps must be connected in parallel.
Using single-pole latching relays 2CSK1012CH, it is possible
to connect up to four fluorescent lamps: by adding a 0.94μF
capacitor to the heads of the relay, up to twelve fluorescent
lamps can be connected.
5/30
2CSC600290D0201 | Mylos, Élos, Chiara
Using double-pole latching relays 2CSK1014CH, it is possible
to connect two fluorescent lamps: by adding a 1.41μF
capacitor to the heads of the relay, up to twelve fluorescent
lamps can be connected.
Relays
Relay with latching operation for control and adjustment from
multiple lamp points by means of single-pole push switches
with NO (normally open) contact.
Wiring diagrams
2CSK1012CH
STEP 1
STEP 2
N
Technical specifications
Power supply voltage (coil)
230V - 50/60Hz
Output contact
2CSK1012CH 1NO /
2CSK1014CH 2NO;
10A (AC1) / 7A (AC15) - 250V~
L
2CSK1014CH
STEP 1
Reference standards
EN 60669-1, EN 60669-2-2.
N
1
STEP 2
3
5
L
2
4
Examples of application
The flush-mounted relays of the Chiara wiring accessories’ range can be used to implement numerous functions. The example
illustrates a disabled bathroom calling system with cancellation via a key operated push switch:
N
NC
Monostable
relay
E259
(code M273653)
2CSK1009CH
Single-pole
push switch,
NO, with
cord pull
NO
2CSK1009CH
Double-pole
push switch
with key control
2CSK1012CH
Single-pole
latching relay
2CSK1312CH
Warning light
2CSK1322CH
Buzzer
L (230V~)
Mylos, Élos, Chiara | 2CSC600290D0201
5/31
Chiara - Technical details
Socket outlets
Plug sockets
Area of application
Powering of household appliances, lighting equipment etc.
Technical specifications
Main features Italian and German standard sockets.
The cells of the sockets are segregated and protected when
the plug is disconnected: the live parts are accessible only
with the corresponding plug fully inserted.
Rated voltage
250V~
Rated current
10A o 16A
Shuttered and elastic live cells
Possibility of coupling Chiara sockets with the various types of plugs on the market
20
ø5
American
2P, 15A
25
=
25
=
Schuko
2P+T, 16A
ø5
2P+T, 16A
ø5
2P, 16A
20
20
20
ø3
5
2P+T, 10A
ø3
2P, 2,5A
ø3
2P, 10A
ø5
ø5
ø5
ø3
ø3
ø3
6mm
1mm
Plug sockets, 250V~, Italian standard with safety shutters
P 11
Q
Q
Q
2CSK1101CH
P 17
Q
Q
Q
Q
2CSK1102CH
P 17/11
Q
Q
Q
2CSK1103CH
Plug sockets, 250V~, Italian/German standard with safety shutters and side/central earth
P 30
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
2CSK1108CH
P 30/17
Q
2CSK1109CH
Interlocked socket outlets with automatic MCB
P 17/11
2CSK1324CH
P 30
Q
2CSK1325CH
Special sockets
Shaver
socket
(1)
Q
2CSK1113CH
(1)
Shaver socket, European/American standard with insulating transformer 230V~ - 50/60 Hz
Reference standards
CEI 23-5, CEI 23-50, CEI 23-16 (IEC 60884-1).
Note: In general terms, no plug sockets of any standard for domestic use fall under the European low voltage directive, because there is no harmonized European standard for
these types of sockets: in fact, each country has its own standard and therefore a single standard is impossible. For this reason the plug sockets do not bear the CE mark. All the
sockets of the Chiara wiring accessories’ range conforming to CEI 23-50 are however are certified by IMQ as a further guarantee of their quality and compliance with standards.
5/32
2CSC600290D0201 | Mylos, Élos, Chiara
Plug sockets for dedicated lines
Plug sockets for dedicated lines allow outlet points to
be differentiated according to their particular application,
avoiding incorrect connection of unsupported appliances.
Different coloured enclosures (red, orange, green) distinguish
them from common power sockets.
There are as yet no standard regulations on the
correspondence between the colour of the socket and the
type of power supply. In order to distinguish the area of
application, the following usage customs are adopted.
Red: continuous power supply with UPS (uninterruptible
power supply) through an insulating transformer.
Orange: power supply protected by network-generator unit
through an insulating transformer.
Green: safety power supply with network/generator unit.
5
Special sockets
Description
2P shaver socket with insulating transformer. Power supply 230V~ -
Code
2CSK1113CH
50/60Hz. Output voltage 125V~ (American standard 2P socket)
or 230V~ (2P socket P11 type)
Components
Operating pushbutton
The socket is suitable for the insertion Italian standard plugs
of the P11 type (2P) and American standard plugs (2P).
The shaver socket is protected against overload with a
thermal interruption device without auto-reclosing.
After the protection is tripped, the cells of the socket are not
energized. To reclose the circuit, the plug of the device that
caused the overload must be disconnected, waiting a few
minutes in order to allow the transformer to cool down.
Technical specifications
Socket for plug P11 type (2P)
Power supply
230 V~ 50-60 Hz
Output voltage
230 V~ for plugs P11(2P) 2,5 A
120 V~ for plugs 2P 15 A 125 V~
Socket for 2P plug 15A 125V~
American standard
The shaver socket incorporates an insulating transformer
with a power rating of 20 VA, protected against overload and
resistant to short-circuits.
Power supply is guaranteed by a pushbutton that is operated
automatically whenever the plug is inserted in the socket.
The secondary circuit, to which the cells of the socket are
connected, is isolated from the primary power supply circuit
by double insulation:
additional protections (shutter devices) on the cells of the
socket are therefore superfluous.
American standard with nonAvailable power
polarized flat pins
20VA
Operation with auto-protected
temperature
Reference standards
EN 61558-2-5, EN 61000-3-2, EN 55014-1, EN 55014-2.
Mylos, Élos, Chiara | 2CSC600290D0201
5/33
Chiara - Technical details
Socket outlets
Description
Code
Flush-mounted USB charger 500-650mA, with male type A connector, 2CSK1160CH
power supply 230~ 50/60Hz, output voltage 5V DC
Components
Power supply
terminals
USB connector
type A - female
Power supply
terminals
5
The flush-mounted USB charger allows you supply and
recharge the most common portable electronic devices.
Using only a USB cable with Type A male connector it is
possible to power mobile phones, smartphones, tablets and
cameras that support standard USB power supply (up to
650mA), independently of the manufacturer.
Operating method
Connect the USB cable with the type A male connector to the
charger and the opposite end to the device to be powered.
Type A, B, miniUSB and microUSB USB connectors
can be used indifferently. The device is now being charged.
Caution: the device supplies power according to the USB
data transmission protocol, with a maximum current of
. Some devices may require a higher power
650mA at 5V
supply current. Look up the manual of the connected device
to check its absorption specifications.
The charging time depends on the connected device and may
vary compared with the original charger.
Examples of application
USB cable
with type A
male.
Wiring diagrams
L
N
Caution!
The device absorbs up to 60mW in
the absence of connected electronic
devices. To exclude this absorption, it
is recommended to use a double-pole
switch.
Technical specifications
Power supply
125-250V - 50/60 Hz
Input current
5A 230V
Output current
500-650mA at 5V DC
Max absorption in standby
60mW
Operating temperature
-20 +50°C
Storage temperature
-20 +80°C
Protection class
IP20
Place of use
indoors, dry
The device is protected against short-circuits by an internal fuse
(not replaceable).
5/34
2CSC600290D0201 | Mylos, Élos, Chiara
Interlocked socket outlets
Description
2P+E socket outlet, 16A - 250V~, interlocked with MCB, P17/11
Code
2CSK1324CH
2P+E socket outlet, 16A - 250V~, interlocked with MCB, P30
2CSK1325CH
2P+E socket outlet, 16A - 250V~, with RCD 10mA, P17/11
2CSK1326CH
Components
Interlocked socket outlets with automatic MCB (PIA)
Socket
Manual reset control
Indication of the Characteristic curve
Interlocked socket outlets with automatic MCD (PID)
Socket
- terminal user devices in rooms where there is a greater risk
of electrocution (bathrooms, showers, etc.)
- sockets that power class 1 users with electronic circuits
- sockets for portable user devices in domestic or similar
environments (irons, drills, etc.).
Operation
The MCB or RCD interlocked with the socket energises the
cells of the socket only after the plug has been inserted and
automatically cuts off voltage to the socket before the plug is
fully extracted.
Therefore the plug is always inserted and extracted without an
electrical arc.
The lever of the circuit-breaker can be closed only after the
plug is inserted; without the plug, the lever operates without
effect and does not close the switch.
Current-time tripping diagrams for circuit-breakers
of the Chiara range
300
200
Normal operation signal
100
80
60
40
Manual reset control
20
Interlocked socket outlets with automatic RCD (PID).
These sockets are suitable for installation in the system
terminations for protection of the load supplied from the outlet
against dangers of short circuits and overloads, as well as
protection of the user against contact voltages.
The residual current function with sensitivity of 10 mA
also acts in the presence of non-sinusoidal fault currents
(alternating currents mixed with unidirectional pulsating
currents).
In compliance with installation standards, they are particularly
suitable for the protection of:
10
8
6
4
2
1
SECONDS
Interlocked socket outlets with automatic MCB (PIA)
These sockets are suitable for installation in the system
terminations for protection of the load supplied from the outlet
against dangers of short circuits and overloads..
MINUTES
Indication of the Characteristic curve
40
20
10
8
6
4
2
1
0,8
0,6
0,4
0,2
0,1
0,08
0,06
0,04
0,02
0,01
1 1.11.2
1.5
2
2.5
3
4
5
6
7
8
9 10 11 12
MULTIPLES OF RATED CURRENT In
Mylos, Élos, Chiara | 2CSC600290D0201
5/35
5
Chiara - Technical details
Socket outlets
Technical specifications
Wiring diagrams
Power supply voltage
230 V~ - 50 Hz
Residual current (sensitivity)
IΔn 10 mA
Operation dependent on the line voltage
they must be installed
downstream of a general
residual current circuitbreaker
Thermomagnetic tripping
2CSK1324CH
2CSK1325CH
with characteristic C
Double-pole isolation
with 1 protected pole
Breaking capacity
3000 A
Rated current corresponding to the standard of the socket
5
Type A RCBO for alternating and unidirectional pulsating currents
Front LED with green light indicates normal operation with the presence
of network power supply and contact closed
2CSK1326CH
5/36
2CSC600290D0201 | Mylos, Élos, Chiara
Reference standards:
Interlocked socket outlets with MCB:
LV Directive, Standard CEI 23-97.
Interlocked socket outlets with RCD:
LV Directive, Standard CEI 23-96.
TV/SAT sockets
The TV/SAT coaxial sockets for the Chiara series offer a
complete range of products for implementing the terminal part
of modern antenna systems. Manufactured fully from die cast
Zama, they include a pressure terminal with safety screw in
order to guarantee proper grip of the cable. Individual sockets
are available with male IEC or female F bushing, and double
demixed sockets with both connection possibilities. Various
levels of attenuation are available, ensuring that solutions are
available for every type of installation.
Components
F female connector
Coaxial cable housing
IEC male connector
TV/SAT
coaxial sockets
Double demixed
TV/SAT coaxial
sockets
Attenuation values of the TV/SAT coaxial sockets
Code
Bushing
Passing attenuation
[dB]
5÷40
47÷862
MHz
MHz
950÷2402
Bridging attenuation
[dB]
5÷40
47÷862
950÷2400
MHz
MHz
MHz
MHz
Inverse
attenuation
Direct
current transit
[dB]
2CSK1117CH
Male IEC Terr.
-
-
-
0,5
0,5
0,5
-
NO
2CSK1118CH
Male IEC Terr.
-
-
-
0,5
0,5
0,5
-
YES
2CSK1132CH
Male IEC Terr.
≤2
≤2
≤3
≤7
≤7
≤8
≥35
NO
2CSK1136CH
Male IEC Terr.
≤2
≤2
≤2,5
≤10,5
≤10
≤11
≥35
NO
NO
2CSK1137CH
Male IEC Terr.
≤1,5
≤1,5
≤2,5
≤14,5
≤14
≤14,5
≥35
2CSK1138CH
Male IEC Terr.
≤1,5
≤1,5
≤2,5
≤18,5
≤18
≤18,5
≥35
NO
2CSK1119CH
Female SAT
-
-
-
≤0,5
≤0,5
0,5
-
YES
Attenuation values of double demixed TV/SAT coaxial sockets
Code
Bushing
Passing attenuation
[dB]
TV
SAT
Bridging attenuation
[dB]
TV
SAT
Inverse
attenuation
[dB]
Direct
current transit
2CSK1133CH
Male IEC Terr.
Female SAT
Male IEC Terr.
Female SAT
Male IEC Terr.
Female SAT
Male IEC Terr.
Female SAT
Male IEC Terr.
Female SAT
-
-
≤2
≤2
-
YES
≤4
≤5
≤6,5
≤7
≥35
YES
≤3
≤4,5
≤10
≤11
≥35
YES
≤2
≤3
≤14
≤15
≥35
YES
≤1
≤2
≤18
≤19
≥35
YES
2CSK1120CH
2CSK1132CH
2CSK1131CH
2CSK1139CH
Mylos, Élos, Chiara | 2CSC600290D0201
5/37
5
Chiara - Technical details
Socket outlets
Instructions for installation
5
ø5 mm
5-7 mm
2CSK1130CH
2CSK1131CH
2CSK1132CH
2CSK1135CH
2CSK1136CH
2CSK1137CH
2CSK1138CH
2CSK1139CH
10 mm 2 mm
5-7 mm
Technical specifications
Manufactured from die cast Zama.
Pressure terminal.
Available with bushing of type: male CEI, female F.
Reference standards
EN 50083-1, EN 50083-2, EN 50083-4
5/38
2CSK1117CH
2CSK1118CH
2CSK1119CH
2CSK1133CH
7 mm
ø7 mm
Direct socket
10 mm 2 mm
Feedthrough socket
converted to
terminal socket
Feedthrough
socket
2CSC600290D0201 | Mylos, Élos, Chiara
Closing
terminal
resistance
75ohm
2CSE1610EL
8CH
9CH
Wiring diagrams
TV
TV/SAT
TV system with branched sockets
from the central unit
TV/SAT system with feedthrough demixed
sockets from the central unit
TV/SAT system with branched demixed
sockets from the central unit
2CSK1139CH
2CSK1133CH
2CSK1137CH
2CSK1131CH
2CSK1133CH
2CSK1136CH
2CSK1130CH
2CSK1133CH
2CSK1118CH
2CSK1132CH
2CSK1120CH
2CSK1133CH
Closing resistance 75ohm
Closing resistance 75ohm
Closing resistance 75ohm
Closing resistance 75ohm
2CSK1118CH
TV system with feedthrough sockets
from the central unit
2CSK1138CH
2CSK1118CH
2CSK1118CH
2CSK1118CH
5
TV/SAT
Mixed TV/SAT system, single consumer
Multiswitch radial TV/SAT system
SAT system, single consumer
Terr. amplifier
220V
TV amplifier
MIX TV/SAT
2CSK1133CH
2CSK1133CH
2CSK1133CH
SAT decoder
2CSK1133CH
SAT
SAT system, single consumer
SAT and feedthrough Multiswitch system
SAT and radial Multiswitch system
220V
2CSK1139CH
2CSK1139CH
2CSK1139CH
SAT decoder
2CSK1119CH
Mylos, Élos, Chiara | 2CSC600290D0201
5/39
Chiara - Technical details
Socket outlets
Network and telephone sockets
The range includes devices for the implementation of
telephone and computer networks, RJ11 4-contact telephone
connectors for telephones, telefax, modems and RJ12
6-contact telephone connectors for intercommunicating
telephone installations.
RJ45 category 5e and 6 connectors are also available. These
devices allow computer equipment (computers, modems,
printers, etc) to be connected in a network and connection of
multimedia devices.
5
Components
Adapter for
connector
RJ connector
RJ connector
Adapter for
connector
Code
Connector type
No. contacts
Cable type
Shielded
Category
Speed
2CSK1121CH
RJ11
4
twin core
NO
3
up to 16 Mb/s
2CSK1122CH
RJ12
6
twin core
NO
3
up to 16 Mb/s
2CSK1124CH
RJ45
8
UTP
NO
5e
up to 100 Mb/s
2CSK1125CH
RJ45
8
FTP
YES
5e
up to 100 Mb/s
2CSK1127CH
RJ45
8
UTP
NO
6
up to 10 Mb/s
2CSK1128CH
RJ45
8
FTP
YES
6
up to 10 Mb/s
FTP = cable shielded with aluminium tape
UTP = unshielded cable
Instructions for installation
Unshielded connectors:
1. wire the connector making sure that the connection
terminals match;
2. operate the lever wiring device on the connector;
3. latch the connector on the adapter and proceed with the
installation on the frame.
Shielded connectors:
1. wire the connector making sure that the connection
terminals match;
2. position the cover of the connector and squeeze with pliers
to make sure the contacts are tight;
3. apply the shielding, ensuring insulation of the connector;
4. latch the connector on the adapter and proceed with the
installation on the support.
A
2
1
Keystone adapter 2CSK1135CH:
the structured wiring systems for data transmission are
distinguished by their flexibility of use, installation independent
of location and the use of the terminal outputs. The suppliers
of components for wiring, when dealing with installations
of a certain complexity and size, must be in able to show
certification of conformity of the installation, directly or
through accredited installations.
ABB meets this requirement with the adapter of the Chiara
wiring accessories’ range, which is compatible with various
Keystone coupling connectors available on the market and
enables integration between the Chiara wiring accessories’
range and data transmission components of systems with
structured wiring.
1. latch the connector on the adapter and proceed with the
installation on the frame.
3
5
B
A
2
1
Unshielded connectors
5/40
2CSC600290D0201 | Mylos, Élos, Chiara
Shielded connectors
4
5
B
Keystone adapter 2CSK1135CH
Wiring diagrams for RJ11 and RJ12 telephone connectors
RJ11
Wiring diagrams for RJ45 data connectors
To obtain the EIA/TIA 568A or 568B configuration included below, follow the
colour code shown on the terminal box.
RJ12
568A
2345
568B
123456
12345678
12345678
2 3 4 5
1 2 3 4 5 6
5
For telephone use, 2 wires of the
telephone connectors, use the central
contacts 3-4
Connection in series
568A
connect pin
2 3 4 5
connect pin
2 3 4 5
2
8
connect pin
2 3 4 5
568B
L1
A
3
5
6
4
A
B
Terminals 3 and 4 are connected via the internal contact to the telephone
(closed with the receiver hung up). Lifting the receiver causes interruption of the
downstream line (L1), guaranteeing secrecy of the conversation.
B
7
1
Telephone pair
L2
Connection in parallel
60 mm
5 mm
connect pin
2 3 4 5
connect pin
2 3 4 5
connect pin
2 3 4 5
L1
Telephone pair
L2
Each socket captures the line signal (there is no secrecy of conversation).
2345
Note: extracting one of the plugs causes disconnection of
sockets located downstream. In order to prevent this, you just
need to insert a plug in the socket from which the telephone
device was removed with a jumper between terminal 3 and 4.
Technical specifications
Connections
With perforated insulation
Conductors
non-butted, inserted in the appropriate blade slots
Reference standards
EN 50083-1, EN 50083-2, EN 50083-4, ISO 11801.
Mylos, Élos, Chiara | 2CSC600290D0201
5/41
Chiara - Technical details
Protection devices
Fuse holders and overvoltage limiters
Description
Fuse holder, for fuses Ø5x20 / Ø6.3x32 mm, max. 16A
Code
2CSK1301CH
Components
Removable cover for
removal of the fuse
5
Replacement fuses
Fuses with dimension Ø5x20mm or Ø6.3x32 mm can be
installed.
The use of the fuses on page 4/23 is recommended.
5/42
2CSC600290D0201 | Mylos, Élos, Chiara
Replacement of the fuse
After removing the removable cover with a screwdriver,
proceed with replacement as in the drawing:
Description
Overvoltage limiter, 75J, 230V~
Code
2CSK1315CH
Components
Examples of application
Over-voltages in domestic networks can be caused both
by atmospheric interference and by control, operation or
programming of connected inductive loads (air conditioners,
burner motors, water pumps, reactors of fluorescent or
discharge lamps, washing machines, etc.).
Removable cover
5
Signalling LED
This device provides protection for power supply sockets for
all types of household appliances and in particular for those
containing electronic components (Hi-Fi, TV, computers, video
recorders, programming mechanisms, cash registers etc.) from
damage caused by over-voltages present in power supply
networks.
Wiring diagram
Instructions for installation and operation
The protection device is housed in the removable front
cover. To replace it, after disconnecting the voltage from the
installation, extract the cover from the limiter and separate
the SPD block from the plastic cover, levering it with a
screwdriver. Replace it with spare part 2CSY1302MY.
L
N
Technical specifications
Functions
When the red warning light is on, it indicates that the
protection has tripped and needs to be replaced (the load
remains energised but it is not protected).
Residual current limiting
protection (line-to-neutral)
Rated voltage (Un)
120-230 V~ 50/60 Hz
Number of ports
1
Rated load current IL
16 A
Tensione max continuativa (Uc)
250 V~
Test class
III
Protection level (Up)
< 1,2 kV
Test voltage of combined wave
2,5 kV
generator Uoc
Rated flashover current (In)
1 kA (8/20 ns) 20 times
Max flashover current (Imax)
2 kA (8/20 ns) once
Temperature range
-5 °C - +40 °C
Internal integrated protection
fuse
Reference standards
LV Directive, Standard EN 61643-11
Mylos, Élos, Chiara | 2CSC600290D0201
5/43
Chiara - Technical details
Protection devices
Miniature circuit-breakers and Residual current circuit-breakers
Description
Automatic MCB, 1P+N, C6, breaking capacity 1.5kA
5
Code
2CSK1304CH
Automatic MCB, 1P+N, C10, breaking capacity 3kA
2CSK1305CH
Automatic MCB, 1P+N, C16, breaking capacity 3kA
2CSK1306CH
Automatic RCD, 1P+N, C6 - 10 mA, breaking capacity 1.5kA
2CSK1307CH
Automatic RCD, 1P+N, C10 - 10 mA, breaking capacity 3kA
2CSK1308CH
Automatic RCD, 1P+N, C16 - 10 mA, breaking capacity 3kA
2CSK1309CH
Automatic RCD, 1P+N, C6 - 30 mA, breaking capacity 1.5kA
2CSK1328CH
Automatic RCD, 1P+N, C10 - 30 mA, breaking capacity 3kA
2CSK1329CH
Automatic RCD, 1P+N, C16 - 30 mA, breaking capacity 3kA
2CSK1330CH
Components
Automatic RCD
Normal operation signal
–
Manual reset control
Test key (TEST)
Indication of the Characteristic curve
–
Automatic MCB
–
Manual reset control
Indication of the Characteristic curve
–
–
Automatic MCBs and automatic RCDs provide protection
against over-currents and earth fault currents of terminal
circuits. Protection class with the device embedded in smooth
vertical walls with the associated support, frame and blank
covers, if required: IP41.
Instructions for installation and operation
Use in dry and dust-free locations.
– Temperature between -5 °C and +40 °C..
– Suitability for installation on the supply side of a socket
or device for the protection against overloads and short
circuits of the equipment and, at the same time, for
protection of the users against contact voltages.
– The sensitivity (operating residual current) of 10mA and
5/44
2CSC600290D0201 | Mylos, Élos, Chiara
–
–
–
the suitability for operation also in the presence of nonsinusoidal fault currents (alternating currents mixed with
unidirectional pulsating currents) allow the protection
devices of the Chiara range to be classified as “type A
RCBOs” (identified by the symbol), particularly suitable for
the protection of:
• terminal uses in rooms where there is a greater risk of
electrocution (bathrooms, showers, kitchens etc.), as
prescribed by the CEI standards;
• class I consumer power sockets with electronic
circuits (computers and accessories, electronic scales,
electronic typewriters, cash registers etc.). In domestic
and service industry networks non-sinusoidal fault
currents are often present because of the use of
electronic boards in domestic appliances.
The electromagnetic part of the circuit breakers guarantees
protection against overloads and short circuits; the residual
current part of the devices, for current values of 10mA,
guarantees protection of persons against the contact
voltages.
Closing the circuit: manually press the lever of the circuit
breaker at the “I” symbol.
Opening the circuit:
• manually, by pressing the lever of the circuit breaker at
the “0” symbol or the yellow test button (test);
• automatically, due to thermal (overload), magnetic
(short-circuit) or residual current (earth fault current)
tripping.
The device must not be used as a control breaker.
To check that the circuit breaker is installed and behaving
correctly, the yellow test button (test) must be pressed
every month. If the device is correctly installed and
powered, the circuit breaker trips; if it does not, you must
immediately inform the installation technician because
safety will be compromised. After the test, you need to
press the main key near the “I” symbol in order to reset the
circuit breaker.
Thermomagnetic tripping with characteristic “C” (see the
current-time tripping diagram provided below).
Double-pole operation with one protected pole + N, type A
for alternated fault currents and unidirectional pushbuttons.
Operating residual current (sensitivity) IΔn 10mA; the circuit
breaker must be connected according to the electrical
diagram provided below.
The supply line can be connected to either the upper or the
lower terminals of the circuit breaker, which must be installed
downstream of a general residual current circuit breaker
(Standard CEI 64-8/5, paragraph 532.2.2.2).
The line voltage determines operation (Standard IEC 1009-1,
paragraph 4.1.2).
10000000
1000000
Specific through energy I2t
100000
C13
C16
C10
C13
C6
C13
10000
5
1000
100
10
1
10
100
1000
1500
Short circuit current
Current-time tripping diagrams for circuit-breakers
of the Chiara range
300
200
100
80
60
40
20
MINUTES
Characteristics
– Main lever operated control part: “I” symbol (closed
circuit); “0” symbol (open circuit).
– Front LED for signalling the presence of line voltage and
closed circuit.
– Yellow test button (test) for checking that the device is
functioning properly.
– Terminals protected with captive screws for clamping two
conductors up to 4 mm 2 each
– Construction of the thermo magnetic part as prescribed by
Standards EN 60898 and IEC 60898.
– Construction of the residual current part according to
Standards EN 61009 and IEC 61009.
– Power supply voltage: 120-230V~ ±10% 50-60Hz.
Characteristic curves
10
8
6
4
2
1
SECONDS
Functions
– Green front LED for signalling normal operation: presence
of line voltage and closed circuit.
– Internal temperature checking: the circuit breaker
automatically operates the opening of the circuit as soon
as the safety threshold is exceeded.
– Self-test function to check the electrical continuity of the
internal residual current circuit (in the absence of continuity,
the circuit breaker will open).
– Opening the circuit if voltages occur higher than the
predefined threshold at the circuit breaker input(for
example, in 380V~ three-phase systems the circuit breaker
prevents an erroneous “line-to line ” connections, instead
of “line-to-neutral”).
40
20
10
8
6
4
2
1
0,8
0,6
0,4
Wiring diagram
0,2
0,1
0,08
0,06
0,04
0,02
0,01
1 1.11.2
1.5
2
2.5
3
4
5
6
7
8
9 10 11 12
MULTIPLES OF RATED CURRENT In
DEVICES
DEVICES
Mylos, Élos, Chiara | 2CSC600290D0201
5/45
Chiara - Technical details
Protection devices
Examples of application
5
Technical specifications
Type of circuit breaker
MCB
Rated voltage
230V
RCD
230V
Rated frequency
50 ÷ 60Hz
50 ÷ 60Hz
Rated residual current
-
10mA or 30mA
6A 1500A
6A 1500A
10A 3000A
10A 3000A
Correnti nominali
16A 3000A
6 -10 -16A
16A 3000A
6 -10 -16A
Number of poles
1P + N
1P + N
- Overcurrent protection
Type C
Type C
- Limitation class
3
3
- Residual current protection
-
Class A
Short-circuit breaking capacity
Tripping characteristic
Reference standards
Thermomagnetic: EN 60898-1 - Differential: IEC 61009-1
5/46
2CSC600290D0201 | Mylos, Élos, Chiara
Chiara - Technical details
Safety and comfort devices
Thermostats and time-programmed thermostats
Description
Summer/winter electronic thermostat, relay output,
Code
2CSK1202CH
1 contact NO 8A (AC1)/2A (AC15) - Power supply 230V~ 50/60Hz
Components
Current value of the AMBIENT TEMPERATURE in °C.
While adjusting the value of the DESIRED TEMPERATURE,
it value is displayed (flashing).
About 5 seconds after the last time the keys were pressed, it
returns to displaying the AMBIENT TEMPERATURE.
Display indicating the value of the
DESIRED TEMPERATURE
RELAY ENERGISED icon.
This icon is displayed when
power is requested from the system
controlled by the thermostat.
)
The type of icon displayed ( or
depends on the operating mode
of the thermostat (heating
or air conditioning).
Key to INCREASE the
DESIRED TEMPERATURE (in steps of
0.5°C). The maximum value that can be set
is 30 °C.
Key to DECREASE the
DESIRED TEMPERATURE (in steps of 0.5 °C)
The minimum value that can be set is
5.0 °C (anti-freeze temperature)
ANTI-FREEZE icon. This is displayed
when the DESIRED TEMPERATURE is set
to the minimum value (5.0 °C)
The electronic thermostats of the Chiara series are equipped
with a summer/winter switch for heating and air conditioning
systems.
Characteristics
- Display of the current ambient temperature
- Display of the comfort temperature
- Display of the night-time temperature set
- Possibility to increase or decrease of temperature
in steps of 0.5°C
- Minimum configurable value that can be set 5°C (anti-freeze
temperature) and maximum configurable value 30°C
- Display of the operating status of the thermostat by means
of symbols
- Anti-freeze function set to 5°C
Instructions for installation and operation
For correct operation, the thermostat must be installed at a
height of approximately 1.5 metres from the floor, on internal
walls, protected from direct sunlight and from any thermal
interference such as heaters, lamps, televisions or any object
that generates heat.
This device for controlling heating or air conditioning systems,
uses a special technique that allows greater stability of the
ambient temperature to be achieved while guaranteeing better
comfort.
Areas of application
The environmental thermostats can be used for both heating
and conditioning systems to control burners, pumps, valves,
and refrigeration compressors.
Wiring diagrams
L
N
230V~
Contact
Technical specifications
Power supply
230V~ ±15% - 50Hz
Consumption
< 0.5 W
Output
Clean contact of 8A resistive relay
Operating temperature
from 0°C to +50°C
Adjustment range
from +5°C to +30°C
Precision
±1°C
Area of use
heating and air conditioning
Type of adjustment
PI
Proportional band
2.5°C
Reference standards
EN60730-1, EN60730-2-9, EN61000-3-2, EN61000-3-3,
EN55014-1,EN55014-2
Mylos, Élos, Chiara | 2CSC600290D0201
5/47
5
Chiara - Technical details
Safety and comfort devices
Description
Summer/winter electronic time-programmed thermostat with
Code
2CSK1201CH
4 temperature levels, relay output, 1 NO/NC change-over contact
8A (AC1)/2A (AC15) - Power supply 230V~ 50/60Hz
Components
Temperature levels
Ambient temperature detected
Pushbuttons for selecting
the temperature levels
5
Summer/winter switching
Diagram of the set temperature
Setting pushbuttons
Used in heating and air conditioning systems, the electronic
time-programmed thermostats of the Chiara series include
the possibility of summer/winter switching and the choice
four levels of temperature: comfort, activity, reduction and
anti-freeze. Each level is already preset in the memory of the
device according to specific standards, that can be modified
with the maximum simplicity of according to daily needs.
On the display, values are displayed in real time for the
programme activated, the current temperature, the time
and the status of all the other functions set. It is possible to
programme the desired temperature for every hour of the day
(programming at 30 minute intervals is also possible), and for
every day of the week. In addition, using a special function,
the time-programmed thermostat of the Chiara series is
able to automatically advance or delay switching on or off of
systems in order to reach the ideal temperature exactly at the
moment for which it was programmed.
Adjustment of the thermal residual current device from 0.2°C
to 2°C.
Characteristics
- Preset, adjustable and modifiable temperature levels:
comfort, activity, reduction, anti-freeze fixed at +5°C
- Change-over switching: winter for heating, summer for air
conditioning
- Limitation of the temperature values that can be set
- Possibility to change at any time from comfort temperature
to activity, reduction or anti-freeze
- Display of the time and the ambient temperature
- Temporary or permanent manual operation
- Deletion from memory or modification of all the set
information (day, time, temperature levels, etc.)
- Availability of a totally free program, which can be
programmed according to the strictest personal
requirements
- Possibility to suspend the program in progress for a set time
cycle (maximum 999 hours)
- Connection to a telephonic programming device for remote
control
- Possibility to activate the pump for 2 minutes every day
of the year
- Signalling of faults during operation of the installation
(for example, boiler blocked)
- Signalling that the battery for maintaining data in memory
is low
Preset temperature settings
- T1 Comfort temperature 20°C adjustable
- T2 Activity temperature 18°C adjustable
- T3 Reduction temperature 16°C adjustable
- T Anti-freeze temperature 5°C fixed
Shown on the display
- Days, hours, minutes
- Ambient temperature detected
- Temperature levels
- Daily programming
- Type of operation: manual, automatic, summer, winter
Programming
- 4 fixed programs
- 1 free program
- Programming at intervals of 30 minutes
- Holidays program
- Switching on or off with automatic management
5/48
2CSC600290D0201 | Mylos, Élos, Chiara
Areas of application
In residential applications, such as apartments and villas with
independent heating, apartments with centralized heating,
apartments or villas with independent air conditioning.
In the services sector in environments equipped with air
conditioning systems with fan coils and in environments
equipped with centralized heating and zone valves.
Wiring diagrams
Example of connection to a motorized solenoid valve
Open N Close
C
NO
NC
Power supply 230V~
1
Technical specifications
Power supply voltage
230 V - 50/60 Hz
Maintenance of programs
during power outages
Output contact
72 hours minimum
NO/COM/NC 8(2)A / 250 V~
Type of insulation
Class II
Protection class
IP 30 (flush-mounted)
Temperature adjustment range
from + 5 °C to + 39 °C
Temperatures setting
resolution
Temperature display
resolution
Thermal gradient
0.5 °C
max 1°K/15 min.
Differential operation
T modifiable from 0,2 °C to 2 °C
Updating of the temperature display
Once every 60 seconds
Operating temperature limits
-5°C + 50°C
0.°C
5
2
3
N
4
L
5
Inputs for commands
from telephonic
programming device
L
N
230V~
Reference standards
LVD EN60730-2-7, EN60730-2-9, EMC EN60730-2-7,
EN60730-2-9
Example of connection to a boiler and telephonic programmer
Boiler
C
NA
NC
Power supply 230V~
1
2
3
N
4
L
5
Inputs for commands
from telephonic
programming device
6
7
L N
230V~
Telephonic programming device
Contact for the
thermostat’s control
Mylos, Élos, Chiara | 2CSC600290D0201
5/49
Chiara - Technical details
Safety and comfort devices
Dimmer
Loads that can be controlled with the dimmer
Dimmer type
Loads
Fluorescent or
halogen lamps
230V
Dimmer
code
2CSK1205CH
2CSK1207CH
5
2CSK1204CH
Description
Electronic dimmer
YES
with rotary control
YES
Electronic dimmer
with button
control
YES
Electronic dimmer
with rotary control
and two-way switch
Description
Electronic dimmer with rotary control for resistive loads
Fluorescent
lamps
Toroidal
transformers
Electronic
transformers
Electromechanical
transformers
Drills
Air
agitators
NO
NO
NO
NO
NO
NO
NO
YES
NO
YES
NO
NO
NO
NO
NO
NO
NO
NO
Code
2CSK1205CH
100-500W, 230V~ - 50/60Hz
Wiring diagram
The connection can be made between phase and neutral or
between phase and phase, always in series with the load.
Control with dimmer
Components
L
N
Location indicator light
230V~
500VA
ON/OFF command button with adjustment by rotation
1
2
3
Line voltage presence indicator light
2CSK1205CH
Electronic dimmer with rotary control for resistive loads 100500W 230V~ 50/60Hz (visible in the dark).
Control with a switch and adjustment with a dimmer
L
N
230V~
500VA
Operation
The load can be controlled and adjusted by rotating the knob.
The light intensity of the location LED is attenuated as the
brightness of the controlled lamps increases.
1
2
3
2CSK1205CH
Technical specifications
Rated voltage
2CSC600290D0201 | Mylos, Élos, Chiara
110V - 50/60Hz
Resistive load power
100 - 500W
50 – 250W
Inductive load power
100 – 500VA
50 – 250VA
Technology
TRIAC
TRIAC
Operating temperature
-5 °C ÷ +35 °C.
Adjustable load
Filament and halogen lamps
Reference standards
CEI 23-9 (EN 60669-1)
5/50
230V - 50/60Hz
Description
Electronic dimmer with pushbutton control for resistive and inductive
Code
2CSK1207CH
loads 60-500W, (60-500VA) 230V~ - 50/60Hz
Wiring diagram
The connection can be made between phase and neutral or
between phase and phase, always in series with the load.
Control and adjustment with a dimmer pushbutton
Components
Location indicator light
L
N
230V~
500VA
ON/OFF command button with adjustment by pressing
Line voltage presence indicator light
1
2
3
5
2CSK1207CH
Electronic dimmer with pushbutton control for resistive and
inductive loads 60-500W 60-500VA 230V~ -50/60Hz (visible
in the dark).
Operation
The load can be controlled and adjusted using a pushbutton.
The light intensity of the location LED is attenuated as the
brightness of the controlled lamps increases.
The load can be turned on, adjusted and turned off
using the pushbutton present on the dimmer or with normal
non-luminous NO pushbuttons connected to the dimmer.
– Storage of the adjustment set when the load was switched
off (apart from network outages).
– Switch-on and switch-off of the load is gradual.
– Pressing the pushbutton quickly causes the load to be
switched on or off. Adjustment is obtained by keeping it
pressed. To reverse the direction of adjustment, interrupt
and then resume pressing the pushbutton.
– If the pushbutton is pressed approximately between 0.3
s and 1 s, the dimmer will light up the controlled lamps,
automatically and gradually, to their maximum brightness.
Control and adjustment with a dimmer pushbutton and NO button
connected in parallel
L
N
230V~
500VA
1
2
3
2CSK1207CH
Technical specifications
Rated voltage
230V - 50/60Hz
110V - 50/60Hz
Resistive load power
60 - 500W
30 – 250W
Inductive load power
60 – 500VA
30 – 250VA
Technology
TRIAC
TRIAC
Operating temperature
-5 °C ÷ +35 °C.
Adjustable load
Filament and halogen lamps, ferromagnetic
transformers for halogen lamps
Reference standards
CEI 23-9 (EN 60669-1)
Mylos, Élos, Chiara | 2CSC600290D0201
5/51
Chiara - Technical details
Safety and comfort devices
Description
Electronic dimmer with rotary control and with two-way switch for
Code
2CSK1204CH
resistive loads 100-500W, 230V~ - 50/60Hz
Wiring diagram
The connection can be made between phase and neutral or
between phase and phase, always in series with the load.
Control and adjustment with a dimmer
Components
L
N
Location indicator light
230V~
500VA
ON/OFF command button with adjustment by rotation
1
2
3
Line voltage presence indicator light
2CSK1204CH
5
Electronic dimmer with rotary control and two-way switch
for resistive loads 100-500W 230V~ -50/60Hz
(visible in the dark).
Operation
The load is controlled directly by means of a pressed two-way
switch. Adjustment is performed by rotating the knob.
The light intensity of the location LED is attenuated as the
brightness of the controlled lamps increases.
Once the desired lighting level has been set, pressing the
knob will switch the light source off, while pressing it again will
switch it back on at the set lighting level.
Control with two-way switch and dimmer, adjustment with dimmer
L
N
230V~
500VA
1
2
3
2CSK1204CH
Control with two-way switch, intermediate switch and dimmer, adjustment
with dimmer
L
N
230V~
500VA
1
2
3
2CSK1204CH
Technical specifications
Rated voltage
230V - 50/60Hz
110V - 50/60Hz
Resistive load power
100 - 500W
50 – 250W
Inductive load power
100 – 500VA
50 – 250VA
Technology
TRIAC
TRIAC
Operating temperature
-5 °C ÷ +35 °C.
Adjustable load
Filament and halogen lamps
Reference standards
CEI 23-9 (EN 60669-1)
5/52
2CSC600290D0201 | Mylos, Élos, Chiara
Gas detectors
Description
Code
Electronic natural gas detector with acoustic and indicator signal, relay 2CSK1210CH
output, 1 NO/NC change-over contact 6A (AC1)/2A (AC15) - 250V~.
Power supply 230V~ - 50Hz.
Equipped with dedicated frame for installation on type 503 box
Electronic LPG gas detector with acoustic and indicator signal, relay
2CSK1211CH
Positioning of the detector
The installation of the gas detector does not exonerate users
from observance of all current laws and standards in the
country of installation regarding the specifications, installation
and use gas powered equipment, the ventilation of rooms and
the release of combustion products.
output, 1 NO/NC change-over contact 6A (AC1)/2A (AC15) - 250V~.
Power supply 230V~ - 50Hz.
30 cm
Equipped with dedicated frame for installation on type 503 box
min. 1 m
max. 4 m
Natural gas detector
Components
5
Frame
Yellow LED 1 Malfunction of the device
Pre-heating / Fault signalling
Yellow LED 2 - Replacement of the
probe module (after the first 5 years) replacement of the entire product
(after another 5 years) consisting
of the power supply module
and the replaced probe module
Green LED - Socket without network
“Test/Reset” key: cancellation
of the alarm memory, silencing
the probe module or entire product
replacement alarm,
test to check the installation
Red LED Alarm tripping / alarm memory completed
LPG gas detector
min. 1 m
max. 4 m
30 cm
- Install the natural gas detector at a maximum of 30 cm from
the ceiling
- Install the LPG detector at a maximum of 30 cm from the
floor surface.
- Install the detectors between 1 m and 4 m from the gas
appliances.
- Do not install the detectors outdoors or in places exposed
to atmospheric agents
- Do not install the detectors close to: sinks, air intakes,
heating and air conditioning devices, windows and
ventilation devices; in addition, the detectors must not be
installed in closed spaces, such as behind a curtain or inside
a cabinet.
Holder for the label specifying the probe module replacement date
The wiring accessories natural gas (CH4) or LPG gas
detectors, flush-mounted with 3 modules (503 box embedded
in the wall) contribute to guarantee the safety of civil
environments where gas operated domestic appliances are
installed, such as: boilers, cookers.
The equipment consists of a fixed power supply module and
removable sensor module, which must be replaced after 5
years of continuous use. This allows a saving on the purchase
and installation costs, with a lower impact on the environment
due to the extension of the life time of the power supply/relay
module for a further 5 years.
magnet valve
Boiler
Illustrative example: installation with 3 gas detectors (natural gas) that
command the solenoid valve for shutting off the gassupply.
Mylos, Élos, Chiara | 2CSC600290D0201
5/53
Chiara - Technical details
Safety and comfort devices
Extraction of the probe module (for example: to replace it)
CAUTION: always deactivate the line voltage 230V~
1. Remove the frame.
2. Delicately insert the flat blade of a small screwdriver and
use it as a lever to uncouple the sensor module.
3. Rotate the sensor module upwards in order to uncouple it
completely.
Replacement probe modules:
2CSY1220MC: Natural Gas replacement probe module
2CSY1223MC: LPG Gas replacement probe module
The diagrams (illustrative examples) show the position of the
relay contacts at rest (no alarm).
5
rivel. fughe gas
sostituire prodottoentro
06mese 2021
anno
rivel. fughe gas
06
rivel. fughe gas
06
2016
mese anno
sostituire modulo sonda
06
mese anno
sonda
sostituiremodulo
Test / Reset
Connection
with solenoid valve
normally closed
2016
mese anno
sostituire modulo sonda
16
Wiring diagrams
CAUTION: the power supply network must incorporate a
device to guarantee omnipolar disconnection.
The detector must be powered by a voltage of 230V~ 50Hz
with continuity in order to guarantee maximum safety and
correct signalling of replacement within the declared time
limits.
For the electrical connections, bring cables with a maximum
cross-section of 2.5 mm² to the terminals of the detector.
Test / Reset
Test/ Reset
NC magnet valve
Characteristics
- Devices equipped with a control circuit with microprocessor
that performs self-diagnosis tasks to ensure the perfect
efficiency of the sensor over time.
- Sensor equipped with a special selective filter in order to
avoid alarms in response to the presence of gas vapours
that are not meant to be detected, such as steam from
cooking, vapours from cleaning fluids etc.
- Devices equipped with an operating time meter, in order to
signal the necessary replacement of the sensor module after
the firsts 5 years of use.
- Luminous (red LED) and acoustic alarm signal.
- TEST (to verify that the device is operating properly) and
Reset system with a single pushbutton.
- The gas detectors are equipped with an output relay that
can command a valve to shut off the distribution of gas.
Key to signals
Luminous LED
Acoustic BUZZER
off
off
flashing
on, fixed
intermittent
-
Reference standards
LVD CEI 216-8 - EMC EN 50270
Connection
with solenoid valve
normally open
NO magnet valve
(with manual reset)
Technical specifications
Power supply voltage
1 potential-free change-over contact
Capacity of relay contacts (max)
6 (2) A 250 V ~
Protection class
IP40
Type of insulation
Class II
Area of application
Domestic - type A
Semiconductor sensor
Installed inside the probe module
Operating temperature
limits
Operating humidity
- 10 °C ÷ + 40 °C
90% UR (maximum)
Types of gas detected
Natural Gas - with model for natural gas
Alarm tripping
LPG - with model for LPG gas
10% LIE (Lower Explosiveness Limit)
Acoustic alarm
For both models
85 dB at 1 m
Sensor warm-up
time at switch-on
Storage temperature
limits
5/54
2CSC600290D0201 | Mylos, Élos, Chiara
230 V~ +/- 10% 50 Hz
Solenoid valve command relay
1 minute
- 15 °C ÷ + 50 °C
Emergency lighting
Description
LED light for emergency lighting or steplight.
Code
2CSK1303CH
Charge reserve up to 3h and recharge time 12h.
Power supply 230V~ - 50Hz.
Equipped with dedicated frame for installation on type 503 box
Components
Yellow LED
Green LED
Frame
Transparent diffuser
High efficiency LED-lit emergency device for embedded
installation. Dimensions of 3 modules. Suitable for installation
of frames of the Chiara wiring accessories’ range.
Instructions for installation and operation
The light provides 6 distinct operating modes, that can be set
by programming.
Each time the diffuser is pressed, it increases the operating
mode by one unit. After three cycles of displaying the mode,
the device will automatically complete the programming
procedure, store the mode that has been set and the GREEN
and YELLOW LEDs will switch off.
In modes 1-2-3 it is possible to adjust the lighting level
(dimmering) by pressing the transparent diffuser.
Functions
The device is equipped with 2 signalling LEDs:
5
Green LED
Meaning
Flashing
Apparatus connected to the electrical network being
On
quick-charged.
Apparatus connected to the electrical network being
Off
recharged for maintenance
Apparatus in emergency state.
Yellow LED
Meaning
On
The apparatus has faults
Off
(monthly test NOT passed)
No malfunction
Wiring diagram
Mode
Description
Battery life Terminals 1 and 2
1
inhibition
1h
Switch-on / switch-off /
2
not activated
inhibition
2h
adjustment
Switch-on / switch-off /
3
not activated
inhibition
3h
adjustment
Switch-on / switch-off /
4
not activated
Inhibition activated
1h
adjustment
Connection for inhibition
5
Inhibition activated
2h
switch
Connection for inhibition
6
Inhibition activated
3h
switch
Connection for inhibition
Modes 1, 2, 3
L
N
Modes 4, 5, 6
1
2
N
NO push switch
1
2
230 V~
Switch
Technical specifications
Power supply voltage
230V~ ±10%, 50-60 Hz.
Emergency light flow
50 lumen with 1h autonomy
35 lumen with 3h autonomy
SE mode (not permanent) 5mA
at 230V~ = 1.6W
SA mode (permanent) 30mA
at 230V~ = 7 W
Ni-Mh batteries, AA 3.6V 1300mAh
High Temperature
12 hours quick charge
Consumption
switch
To access programming mode you need to connect the
batteries using the appropriate connector: the yellow LED
will light up and the green LED will flash a number of times
equal to the mode set (for example, 2 flashes=mode 2). This
sequence will be repeated 3 times.
If you wish to change the operating mode, press the
transparent diffuser: the yellow LED will switch off for a
fraction of a second to indicate that the key has been pressed
and the green LED will indicate the value of the new mode by
the number of flashes.
L
230 V~
Battery recharge time
Battery life
1h, 2h and 3h
Lamp
2 white high efficiency 1W LEDs
Signalling
2 LEDs, GREEN and YELLOW
Ambient Temperature
25°C
Reference standards
EN 60598-2-22
Mylos, Élos, Chiara | 2CSC600290D0201
5/55
Chiara - Technical details
Safety and comfort devices
Description
Removable anti-blackout light, 230V~. Charge reserve 4.5 h and
Code
2CSK1214CH
recharge time 10-20h. To be combined with 230V~ plug sockets;
particularly recommended for codes 2CSK1108CH and 2CSK1109CH.
Components
Green LED
Red LED
Pushbutton for manual activation
5
Battery
Functions
A light source is activated automatically whenever the line
voltage is missing (blackout) thanks to rechargeable backup
batteries.
- Possibility to extract it from the socket and use it as a
normal pocket torch with an on/off button on the front.
- Long autonomy, 4.5 hours of continuous operation.
- Small dimensions - protrusion from the Schuko profile
(only 8 mm).
On the front part there are two LEDs (one red and one green)
that indicate the state of the lamp when it is powered:
- Red LED on, recharging in progress. In the event of a
blackout the lamp will remain off (battery saving condition,
used in the case of prolonged absence).
- Green LED on, recharging in progress. In the event
of a blackout the lamp will light up and will switch off
automatically when the network is restored.
The pushbutton on the front part allows you to switch from
one condition to another.
2P 10A plug, P11 type
ON
The anti-blackout light is an automatic removable,
rechargeable electronic lamp that can be inserted in any
Schuko socket or Italian P11 standard 10A bivalent socket.
Socket outlets particularly recommended for holding the
lamp are the sockets of the Chiara wiring accessories’ range
2CSK1108CH and 2CSK1109CH, that allow the body of the
lamp to be embedded in the socket outlet, thus minimizing
the external dimensions.
The device was designed to light up automatically in the
event of a blackout (no voltage warning), or to be used as a
portable lighting device, useful in order to guarantee visibility
and facilitate maintenance operations and/or searching for
faults in unlit environments.
Technical specifications
Plug
2P 10A
Center distance of the pins
19 mm
Ø of the pins
4 mm
Power supply
230V~50-60 Hz
Recharge time
10-20 hours
Useful battery life
4.5 hours
Reference standards
EN 60598-1, EN 60598-2
5/56
2CSC600290D0201 | Mylos, Élos, Chiara
OFF
Other devices
Description
IR motion detector with twilight sensor for control and adjustment of
Code
2CSK1216CH
the operation time of lighting devices.
Relay output NO 5A (AC1)/2A (AC15) - 250V~.
Instructions for installation
- for installation inside
- flush-mounted installation: 1.1-1.2 m
from the walking surface
Power supply 230V~ - 50/60Hz.
1,2 m
Components
Fresnel lens
Adjustment of the twilight tripping threshold
The apparatus cannot be installed in:
- environments with sudden changes
in temperature.
- environments with high humidity.
- environments with presence of gas, corrosive fluids,
sea air or dust.
5
Schema di collegamento
L
N
Adjustment of timing
2
1
Switch with infrared presence sensor in order to switch lights
on through adjustable twilight sensor threshold and delay
cycle.
It operates the load automatically when persons or animals
pass through the field of action of the sensor.
N
L
Sensor volumetric cover
A
B
B
Examples of application
A
B
A
A
B
B
A
A
Technical specifications
m
8
6
4
2
0
2
4
Power supply
6
Pyroelectric reading sensor and Fresnel lens with volumetric cover.
230V AC (L-N terminals)
Power relay output (terminals 1-2)
Max load
- resistive loads
10A / 250V AC
- inductive loads
2A / 250V AC
Tripping threshold
0-300 Lux
A
1,2
Adjustable by means of a front
m
0
B
C
2
8
Time delay
trimmer
From approximately 5 s to
approximately 5 min
Front twilight sensor.
Operating temperature
Adjustable by means of a front trimmer
-5 a +35 °C.
Reference standards
LV Directive; EMC Directive; EN 60730
Mylos, Élos, Chiara | 2CSC600290D0201
5/57
Chiara - Technical details
Safety and comfort devices
Description
Universal badge switch with location light Relay output
Code
2CSK1426CH
with NO contact 10A (AC1). Power supply 230V~ 50/60Hz
Vertical badge electronic switch, relay output 16 A 250 V~,
power supply 230 V~ 50-60 Hz, modules.
Supplied without ISO card (badge). The device is equipped
with a courtesy LED for night-time location.
Components
Wiring diagram
Badge slot
Courtesy LED (on the front, under the slot)
5
230 V ~
NA
Operation
Load OFF
1
Load ON
2
L
N
Technical specifications
Power supply
230 V~ ±10% 50-60 Hz
Output
relay with clean contact 10 A
250 V~ cos ø 1
230 V~ 50-60 Hz: 30 mA, with relay
active
-5 °C +45 °C
Typical absorption
Operating temperature
Reference standards
LV Directive; EMC Directive; Standard EN 60669-2-1
5/58
2CSC600290D0201 | Mylos, Élos, Chiara
Chiara - Technical details
Wall-mounted enclosures
IP40 and IP55 wall-mounted enclosures
Dedicated rectangular cable grommets
Dedicated rectangular cable grommets
IP55 watertight door
IP40 enclosure
5
IP55 enclosure
Area of application
The IP40 wall-mounted enclosures, pursuant to Standard CEI 64-8, extend the area of application of the devices of the Chiara
series to environments such as boiler rooms, warehouses, mechanical workshop, basements etc., where protection class IP40
is prescribed, defined by Standard EN 60529 (CEI 70-1).
This is guaranteed through devices installed in the enclosures, if the installation is carried out according to the supported
procedures, through the use of connections, cable grommets and pipe ducts.
For devices with an open front (e.g. socket outlets) the protection class is less than IP40 but never less than IP20.
IP55 watertight wall-mounted enclosures, on the other hand, allow the application of the equipment of the Chiara series in
environments such as building sites, sports installations, marinas, industrial and agricultural establishments, gardens, camp
sites etc. The protection class IP55, defined by the Standard EN 60529 (CEI 70-1), is guaranteed by devices installed in the
enclosures, if the installation is carried out according to the supported procedures, through the use of the suitable accessories
and with the cover closed.
Dimensions of IP40 and IP55 enclosures
H
A
P
L
H
A
L
P
IP40 enclosure
no. modules
H
A
L
P
2CSK2140CH
1
38
80
65
55
2CSK2240CH
2
38
80
65
55
2CSK2340CH
3
38
80
104
55
2CSK2440CH
4
38
80
130
55
IP55 enclosure
no. modules
H
A
L
P
2CSK2155CH
1
40,5
80
65
63
2CSK2255CH
2
40,5
80
65
63
2CSK2355CH
3
40,5
80
104
63
2CSK2455CH
4
40,5
80
130
63
Mylos, Élos, Chiara | 2CSC600290D0201
5/59
Chiara - Technical details
Wall-mounted enclosures
Because of the maximum depth dimension H, the IP40 and IP55 wall-mounted enclosures of the Chiara series cannot house
the following contact blocks:
Code
2CSK1204CH
Description
Electronic dimmer with rotary control and two-way switch
Code
2CSK1307CH
Description
Automatic RCD 1P+N, C6 – 10 mA
for resistive loads 100-500W
2CSK1308CH
Automatic RCD 1P+N, C10 – 10 mA
Electronic dimmer with rotary control for resistive loads
2CSK1309CH
Automatic RCD 1P+N, C16 – 10 mA
100-500W
2CSK1328CH
Automatic RCD 1P+N, C6 – 30 mA
2CSK1207CH
Electronic dimmer with pushbutton control for resistive
2CSK1329CH
Automatic RCD 1P+N, C10 – 30 mA
and inductive loads
2CSK1330CH
Automatic RCD 1P+N, C16 – 30 mA
2CSK1317CH
Electro-mechanical bell, 12V, 5VA, sound intensity 80 dB
2CSK1324CH
Interlocked socket with MCB (2P+E 16A 230V P17/11)
2CSK1318CH
Electro-mechanical bell, 230V, 8VA, sound intensity 80 dB
2CSK1325CH
Interlocked socket with MCB (2P+E 16A 230V)
2CSK1321CH
Electro-mechanical buzzer, 12V, 5VA, sound intensity 70 dB
2CSK1326CH
Interlocked socket with automatic RCD 10mA
2CSK1205CH
5
(2P+E 16A 230V P17/11)
2CSK1322CH
Electro-mechanical buzzer, 230V, 8VA, sound intensity 70 dB
2CSK1304CH
Automatic MCB 1P+N, C6
2CSK1012CH
Single pole latching relay, 230V, 1 10A output contact
2CSK1305CH
Automatic MCB 1P+N, C10
2CSK1014CH
4 sequence switch relay, 230V, 2 10A output contacts
2CSK1306CH
Automatic MCB 1P+N, C16
The installation of similar devices in the form of a DIN rail in the distribution board is recommended where possible.
5/60
2CSC600290D0201 | Mylos, Élos, Chiara
Chiara - Technical details
Other installation solutions
Support for DIN bar 1-2-3 modules
Description
Support for DIN bar for 1-2-3 modules, customisable
Code
2CSK1608CH
Components
Instruction for installation
3 modules: snap assemble the two halves.
1 or 2 modules: using a cutter, cut along lines 1 or 2
respectively and assemble the two halves.
DIN rail couplings
Customisable adapter
DIN rail couplings
5
Reference dimensions:
1 module version: 1,9 DIN modules
2 modules version: 3,4 DIN modules
3 modules version: 4,4 DIN modules
Mylos, Élos, Chiara | 2CSC600290D0201
5/61
Chiara - Technical details
Frames
The frames of the Chiara series are made from technopolymer
with natural/pastel colour shades or surface galvanic painting,
and are characterised by their minimal protrusion from the
wall, since they are not fitted with an under-plate.
Reference standards
CEI 23-9 (EN 60669-1).
5
Frame that adheres
to all surfaces
2 ÷ 8 mm
Customization
Frames customized with a logo/text string can be supplied on
request. They are produced by means of monochromatic pad
printing on the areas highlighted below.
1
5
5/62
2
3
4
Position 2
Logo inside a rectangle
10 mm in height and 45mm in length
Positions 1-3-4-5
Logo in square with 13 mm sides.
2CSC600290D0201 | Mylos, Élos, Chiara
Customization is possible with standard colours (black,
Pantone cool gray 3C, Pantone 5425 C) or with a colour
specified by the customer.
Minimum order batch: 36 pieces including various
modularities.
For quotes and delivery times contact an ABB sales
executive.
Chiara - Coding
Order information
Coding criteria of the devices
2
C
S
K
1
C
Product
family
Fixed part of the code
Product progressive
number
0
Control devices
1
Socket outlets
2
Comfort devices
3
Protection devices and signalling devices
6
Components for installation, accessories and spare parts
H
Fixed part of the code
5
Example: single-pole switch
2
C
S
K
1
K
0
0
0
1
C
H
C
H
Coding criteria of the frames
2
C
S
Number of
modules
Fixed part of the code
2
2-module frame
3
3-module frame
4
4-module frame
7
7-module frame
Colour code
01
02
03
04
11
12
13
14
15
16
17
Fixed part of the code
18
white
sand
stone
volcano
pastel yellow
pastel orange
pastel green
pastel blue
glossy chromium
satin chromium
glossy metal
satin metal black
51
52
53
54
glossy bronze
satin bronze
glossy gold
satin gold
Example: technopolymer frame, 3 modules, sand colour
2
C
S
K
0
3
0
2
C
H
Packaging
To enable automatic warehouse management using optical readers, the devices and frames of the Chiara wiring accessories’
range are packaged in boxes that bear the EAN bar code and that protect the contents adequately against dust and shocks.
For a better explanations of the installation methods, a specific instruction sheet is supplied. Individual packages are available
for only for the codes with the lowest turnover.
Mylos, Élos, Chiara | 2CSC600290D0201
5/63
Chiara
Overall dimensions
5
Chiara code
Description
No. Modules
Depth mm
2CSK1001CH
Single-pole switch, 16A - 250V~
1
30
2CSK1002CH
Double-pole switch, 16A - 250V~
1
30
2CSK1003CH
Single-pole two-way switch, 16A - 250V~
1
30
2CSK1004CH
Single-pole switch, 16A - 250V~, 2 modules
2
30
2CSK1005CH
Single-pole push switch NO, 16A
1
30
2CSK1006CH
Double-pole switch, 16A - 250V~, with key control
1
25
2CSK1006CHU
Double-pole switch, 16A - 250V~, with universal key control 1
25
2CSK1007CH
Single-pole two-way switch, 16A - 250V~, 2 modules
2
30
2CSK1008CH
Intermediate switch, 16A - 250V~, 2 modules
2
30
2CSK1009CH
Double-pole push switch, NO, 16A - 250V~, with key control 1
25
2CSK1009CHU
Double-pole push switch, NO, 16A - 250V~,
1
25
1 module
45
22
2 modules
with universal key control
45
2CSK1010CH
Intermediate switch, 16A - 250V~
1
30
2CSK1011CH
Change-over switch, 10A - 250V~, 3 positions
1
31
2CSK1012CH
Single pole latching relay, 230V
1
31
2CSK1014CH
4 sequence switch relay, 230V, 2 10A output contacts
1
31
2CSK1016CH
Single-pole push switch NC, 16A
1
30
2CSK1017CH
Double single-pole push switch, NO+NO, 16A - 250V~
1
30
Double single-pole push switch, NO+NO, 16A - 250V~,
1
30
2CSK1018CH
44
3 modules
with interlock
2CSK1022CH
Single-pole push switch 1 NO and 1 NC, 16A, with ON
1
30
2CSK1023CH
Single-pole push switch 1 NO and 1 NC, 16A,
1
30
45
with OFF symbol
2CSK1020CH
Single-pole push switch NC with cord pull, 16A
1
30
2CSK1021CH
Single-pole push switch NC with cord pull, 16A
1
30
2CSK1028CH
Single-pole push switch NO, 16A, with BELL
1
30
2CSK1029CH
Single-pole push switch NO, 16A, with KEY
1
30
2CSK1030CH
Single-pole push switch NO, 16A, with STAIR LIGHT
1
30
2CSK1024CH
Single-pole push switch NO, 16A, with red diffuser
1
30
2CSK1025CH
Single-pole push switch NO, 16A, with green diffuser
1
30
2CSK1026CH
Single-pole push switch NO, 16A, with orange diffuser
1
30
2CSK1027CH
Single-pole push switch NO, 16A, with white diffuser
1
30
2CSK1031CH
Single-pole pushbutton NO, 16A, with backlit label
2
30
3
30
holder plate push switch
2CSK1032CH
Single-pole push switch NO, 16A, with backlit label
holder plate, 3 modules
2CSK1101CH
2P+E socket outlet, 10A - 250V~, P11 type
1
22
2CSK1102CH
2P+E socket outlet, 16A - 250V~, P17 type
1
22
2CSK1103CH
2P+E socket outlet, 10/16A - 250V~, P17/P11 type
1
22
2CSK1104CH
2P+E socket outlets, 10/16A, red
1
22
2CSK1105CH
2P+E socket outlets, 10/16A, green
1
22
2CSK1106CH
2P+E socket outlets, 10/16A, orange
1
22
2CSK1108CH
2P+E socket outlet, 16A - 250V~, P30 type
2
31
2CSK1114CH
2P+E socket outlets, 16A - 250V~, P30 type, red
2
31
2CSK1115CH
2P+E socket outlets, 16A - 250V~, P30 type, green
2
31
2CSK1116CH
2P+E socket outlets, 16A - 250V~, P30 type, orange
2
31
2CSK1109CH
2P+E socket outlet, 16A - 250V~, P30/17 type
2
35
2CSK1110CH
2P+E socket outlets, 16A - 250V~, P30/17 type, red
2
35
2CSK1111CH
2P+E socket outlets, 16A - 250V~, P30/17 type, green
2
35
2CSK1112CH
2P+E socket outlets, 16A - 250V~, P30/17 type, orange
2
35
2CSK1113CH
2P shaver socket with insulating transformer
3
37,5
5/64
2CSC600290D0201 | Mylos, Élos, Chiara
66
Chiara code
Description
No. Modules
Depth mm
2CSK1324CH
2P+E socket outlet, 16A - 250V~, interlocked with MCB,
2
37,5
2CSK1325CH
P17/11
2P+E socket outlet, 16A - 250V~, interlocked with MCB,
3
37,5
2CSK1326CH
P30
2P+E socket outlet, 16A - 250V~, with RCD 10mA,
3
37,5
P17/11
2CSK1117CH
TV coaxial socket, direct, male IEC connector ø 9.5 mm, 1
21
2CSK1118CH
insulated type
TV/SAT coaxial socket, direct, male IEC connector
1
21
2CSK1132CH
ø 9.5 mm, with feedthrough of direct current
TV/SAT coaxial socket, feedthrough, male IEC connector
1
21
2CSK1136CH
ø 9.5 mm, attenuation 7dB
TV/SAT coaxial socket, feedthrough, male IEC connector
1
21
2CSK1137CH
ø 9.5 mm, attenuation 10dB
TV/SAT coaxial socket, feedthrough, male IEC connector
1
21
2CSK1138CH
ø 9.5 mm, attenuation 14dB
TV/SAT coaxial socket, feedthrough, male IEC connector
1
21
2CSK1119CH
ø 9.5 mm, attenuation 18dB
TV/SAT coaxial socket, direct, female F connector,
1
21
2CSK1133CH
with feedthrough of direct current
Double demixed TV/SAT coaxial socket, direct, male IEC 1
21
2CSK1120CH
connector ø 9.5 mm and female F connector
Double demixed TV/SAT coaxial socket, feedthrough,
1
21
1
21
1
21
1
21
attenuation 18dB
RJ11 telephone connector
1
21
2CSK1122CH
RJ12 telephone connector
1
21
2CSK1124CH
RJ45 connector, Cat. 5e, UTP (unshielded)
1
21
2CSK1125CH
RJ45 connector, Cat. 5e, FTP (shielded)
1
21
2CSK1127CH
RJ45 connector, Cat. 6, UTP (unshielded)
1
21
2CSK1128CH
RJ45 connector, Cat. 6, FTP (shielded)
1
21
2CSK1160CH
Flush-mounted USB charger 500-650mA
1
35
2CSK1210CH
Electronic natural gas detector
3
39
2CSK1211CH
Electronic LPG gas detector with acoustic and
3
39
5
male IEC connector ø 9.5 mm and female F connector,
2CSK1130CH
attenuation 7dB
Double demixed TV/SAT coaxial socket, feedthrough,
male IEC connector ø 9.5 mm and female F connector,
2CSK1131CH
attenuation 10dB
Double demixed TV/SAT coaxial socket, feedthrough,
male IEC connector ø 9.5 mm and female F connector,
2CSK1139CH
attenuation 14dB
Double demixed TV/SAT coaxial socket, feedthrough,
male IEC connector ø 9.5 mm and female F connector,
2CSK1121CH
indicator signal
2CSK1301CH
Fuse holder, for fuses Ø5x20 / Ø6.3x32 mm, max. 16A
1
26
2CSK1303CH
LED light for emergency lighting or steplight
3
50
2CSK1304CH
Automatic MCB, 1P+N, C6, breaking capacity 1.5kA
1
36
2CSK1305CH
Automatic MCB, 1P+N, C10, breaking capacity 3kA
1
36
2CSK1306CH
Automatic MCB, 1P+N, C16, breaking capacity 3kA
1
36
2CSK1307CH
Automatic RCD, 1P+N, C6 - 10 mA,
2
36
2
36
breaking capacity 1.5kA
2CSK1308CH
Automatic RCD, 1P+N, C10 - 10 mA,
breaking capacity 3kA
Mylos, Élos, Chiara | 2CSC600290D0201
5/65
Chiara
Overall dimensions
Chiara code
Description
No. Modules
Depth mm
2CSK1309CH
Automatic RCD, 1P+N, C16 - 10 mA,
2
36
breaking capacity 3kA
2CSK1315CH
Overvoltage limiter, 75J, 230V~
1
26
2CSK1328CH
Automatic RCD, 1P+N, C6 - 30 mA,
2
36
2CSK1329CH
Automatic RCD, 1P+N, C10 - 30 mA,
2
36
2
36
breaking capacity 1.5kA
breaking capacity 3kA
2CSK1330CH
Automatic RCD, 1P+N, C16 - 30 mA,
breaking capacity 3kA
5
2CSK1310CH
Warning light, ORANGE colour
1
20
2CSK1311CH
Warning light, WHITE colour
1
20
2CSK1312CH
Warning light, RED colour
1
20
2CSK1313CH
Warning light, GREEN colour
1
20
2CSK1317CH
Electro-mechanical bell, 12V
1
37
2CSK1318CH
Electro-mechanical bell, 230V,
1
37
2CSK1321CH
Electro-mechanical buzzer, 12V
1
37
2CSK1322CH
Electro-mechanical buzzer, 230V
1
37
2CSK1201CH
Summer/winter electronic time-programmed thermostat
3
38
2CSK1202CH
Summer/winter electronic thermostat
2
29,5
2CSK1205CH
Electronic dimmer with rotary control for resistive loads
1
39
1
39
1
39
100-500W
2CSK1204CH
Electronic dimmer with rotary control and two-way
switch for resistive loads 100-500W
2CSK1207CH
Electronic dimmer with pushbutton control for resistive
and inductive loads 60-500W
2CSK1214CH
Removable anti-blackout light, 230V
see drawing
2CSK1216CH
IR motion detector with twilight sensor for control and
1
32
2
32
adjustment of the operation time of lighting devices
2CSK1426CH
5/66
Universal badge switch with location light
2CSC600290D0201 | Mylos, Élos, Chiara
Frames
2 modules
3 modules
4 modules
92
92
97
92
119
141
7 modules
5
92
209
Self-supporting frames
2 modules
3 modules
4 modules
79
79
79
97
119
Screw distance: 60 mm
141
Screw distance: 83.5 mm
Screwr distance: 108 mm
3 modules
4 modules
Supports
2 modules
79
79
93,5
115
Screw distance of the box: 60 mm
Screw distance of the box: 83.5 mm
79
137,5
Screw distance of the box: 108 mm
7 moduli
79
205
Screw distance of the box: 100 mm
All measurements are in millimetres.
Mylos, Élos, Chiara | 2CSC600290D0201
5/67
Chiara
Overall dimensions
Safety and comfort devices
Anti-blackout light
43
26
44
5
IP40 wall-mounted enclosures
2 modules
3 modules
4 modules
80
80
80
65
55
130
104
IP55 wall-mounted enclosures
2 modules
3 modules
4 modules
80
65
80
80
130
104
63
IP55 flush-mounted escutcheon plate
91
96
All measurements are in millimetres.
5/68
2CSC600290D0201 | Mylos, Élos, Chiara