Product PDF

1.6/3.8kW Single-Phase Basic PDU, 100-240V
(12-C13 & 2-C19), C20,
C14/L6-20P/L5-20P/5-20P/5-15P, 1U
Highlights
16A 100-240V Basic Power
Distribution Unit
Configurable for 1U horizontal or
vertical rackmount installation
MODEL NUMBER: PDUNV
(12) C13 and (2) C19 outlets
10 ft. / 3m attached line cord with
C20 input
Set of 5 plug adapters support
C14, L6-20P, L5-20P, 5-20P &
5-15P inputs
Reversible housing, 4.25 in. /
10.8cm depth
Package Includes
1U rackmount PDU
Mounting hardware
Set of 5 plug adapters
User manual with warranty
information
Description
Tripp Lite's PDUNV is a 1.6-3.8kW / 16A / 100-240V single phase Basic Power Distribution Unit (PDU) that distributes 100-240V power to multiple loads in IT,
industrial and similar applications from a UPS system, generator or utility wall outlet. The PDUNV accepts input power over a range of 100-240V, making it
compatible with worldwide applications. A 10-ft. power cord with C20 plug and a set of five plug adapters enable it to be connected to a 5-15R, 5-15/20R,
L5-20R, L6-30R, C13 or C19 outlets. The PDUNV's C13 and C19 outlets can be adapted for specific applications by using an appropriate plug adapter (e.g.,
C14 to 5-15R). A switchless design prevents accidental shutoff and safeguards against downtime due to human error. It is suitable for 1U or 0U (vertical)
rackmount installation as well as wall-mount, workbench, and under-counter installations. All mounting accessories are included.
Features
16A single phase 100-240V Basic Power Distribution Unit / PDU
Attached C20 input plug with 15 ft. / 4.5m line cord(connects to C19 100-240V)
Pack of 5 included C19 adapters with locking retainer clip enables plug conversion to C14(connects to C13 100-240V), L6-20P(connects to L6-20R 20A
208/240V), L5-20P(connects to L5-20R 20A 120V), 5-20P(connects to 5-20R 20A 120V) and 5-15P(connects to 5-15R 15A 120V)
1U horizontal rackmount format installs in one rack space
14 outlets:(4) C13 front-facing;( 2) C19 &(8) C13 rear-facing
Mounting flanges support installation in 2 and 4 post racks, with additional support for wall-mount and under-counter installation formats
Mounting ears are reversible for front or rear facing rackmount installation
Optional PDUSIDEBRKT enables 0U vertical rackmount in compatible racks
Back panel grounding lug
Specifications
OVERVIEW
PDU Type
Basic
1/3
OUTPUT
Output Capacity Details
3.84kW (240V), 3.68kW (230V), 3.52kW (220V), 3.33kW (208V), 3.2kW (200V), 2.03kW (127V), 1.92kW (120V),
1.6kW (100V) / 16A total capacity; 16A max per C19 outlet; 12A (10A CE) max per C13 outlet
Frequency Compatibility
50 / 60 Hz
Output Receptacles
(12) C13; (2) C19
Output Nominal Voltage
100; 120; 127; 200; 208; 220; 230; 240
Overload Protection
16A circuit breaker
INPUT
PDU Input Voltage
100; 120; 127; 200; 208; 220; 230; 240
Recommended Electrical Service
20A 120V; 20A 208/240V; 16A 230V
Maximum Input Amps
16
PDU Plug Type
NEMA 5-15P; NEMA 5-20P; NEMA L5-20P; NEMA L6-20P; IEC-320 C14; IEC-320 C20
Input Cord Length (ft.)
10
Input Cord Length (m)
3
Input Phase
Single-Phase
USER INTERFACE, ALERTS & CONTROLS
Switches
n/a
PHYSICAL
Minimum Required Rack Depth
(inches)
7.8
Minimum Required Rack Depth (cm)
19.7
Shipping Dimensions (hwd / in.)
2.5 x 10 x 20.25
Shipping Dimensions (hwd / cm)
6.35 x 25.4 x 52.1
Shipping Weight (lbs.)
3.8
Shipping Weight (kg)
1.72
Unit Dimensions (hwd / in.)
1.75 x 17.5 x 4.25
Unit Dimensions (hwd / cm)
4.44 x 44.45 x 10.8
Unit Weight (lbs.)
3.2
Unit Weight (kg)
1.45
Material of Construction
Metal
Form Factors Supported
1U rackmount, 0U vertical mount, wallmount and under-counter mounting supported
PDU Form Factor
Horizontal (1U, 2U, etc)
Outlets Measurement (Center to
Center)
Distance between Front (C13) outlets = 28.75mm; Distance between Rear (C19) outlets = 55mm; Distance between
Rear (C13) outelts = 28.75mm
2/3
ENVIRONMENTAL
Storage Temperature Range
5 to 122F (-15 to 50C)
Relative Humidity
5 to 95% non condensing
Operating Elevation (ft.)
0-10,000
Operating Elevation (m)
0-3000
CERTIFICATIONS
Certifications
Tested to UL60950-1 (USA), CSA (Canada), CE (EU)
WARRANTY
Product Warranty Period (Worldwide)
5-year limited warranty
© 2016 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
http://www.tripplite.com/products/product-certification-agencies
3/3