Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide; (R01/16); (SL-28170)

Liebert® IntelliSlot™
Modbus RTU, Modbus TCP, BACnet MSTP and BACnet IP
Reference Guide
Table of Content
1.0 Liebert Equipment Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 What’s New in This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Connectivity to Liebert IntelliSlot
Using Modbus RTU, Modbus TCP, BACnet MSTP or BACnet IP . . . . . . . . . . . . . . . . . 1
1.2.1 How to Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2.2 Compatibility with Liebert Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0 Modbus Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Implementation Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Transmission Format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Modbus Packet Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3.1 Device Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.2 Function Code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.3 Data Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.4 Error Check Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.5 RTU Framing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
8
8
8
9
3.0 Modbus RTU and Modbus TCP Protocols. . . . . . . . . . . . . . . . . . . . . . . . 11
3.1 Thermal Management Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Power Distribution and Power Conditioning Products. . . . . . . . . . . . . . . . . . . . . . . . . . . 159
3.3 UPS Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
3.4 Battery Monitoring Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
4.0 BACnet Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
4.1 BACnet Protocol Implementation Conformance Statement . . . . . . . . . . . . . . . . . . . . . . 373
4.1.1 Segmentation Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
4.1.2 Supported Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
4.1.3 Standard Object Types SupportedObject Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . 374
4.2 Thermal Management Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
4.3 UPS Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 511
4.4 Power Distribution and Power Conditioning Products. . . . . . . . . . . . . . . . . . . . . . . . . . . 663
i
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Page intentionally left blank.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
ii
List of Tables
Table 1-1: Liebert Equipment and Compatible Liebert IntelliSlot Cards Modbus RTU & Modbus TCP Protocols . . 2
Table 1-2: Liebert Equipment and Compatible Liebert IntelliSlot Cards BACnet MSTP & BACnet IP Protocols . . . 5
Table 2-1: Modbus Remote Terminal Unit settings for Liebert IntelliSlot 485/IP interface card . . . . . . . . . . . . . . . . 7
Table 2-2: Supported Modbus function codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Table 2-3: Query sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 2-4: Response sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 3-1: Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™,
Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil . . . . . . . . . . 11
Table 3-2: Extra notes key to Table 3-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 3-3: Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™,
Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding . . . . . . . . 27
Table 3-4: Extra notes key to Table 3-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Table 3-5: Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™,
Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary . . . . . . . . . . . . . . . 54
Table 3-6: Liebert CRV™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Table 3-7: Liebert CRV™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Table 3-8: Liebert CRV™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Table 3-9: Liebert HPC™ (Chiller) - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Table 3-10: Liebert HPC™ (Chiller)—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Table 3-11: Extra notes key to Table 3-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Table 3-12: Liebert HPC™ (Chiller)—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Table 3-13: Liebert XDC™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Table 3-14: Liebert XDC™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Table 3-15: Liebert XDP™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Table 3-16: Liebert XDP™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Table 3-17: Liebert XDP™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Table 3-18: Liebert iCOM® DCL™—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Table 3-19: Liebert iCOM® DCL™—Input and Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Table 3-20: Liebert iCOM® DCL™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Table 3-21: Liebert DS™ and Liebert PeX™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Table 3-22: Liebert DS™ and Liebert PeX™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Table 3-23: Liebert XDF™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Table 3-24: Liebert XDF™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Table 3-25: Liebert Challenger 3000™, Liebert Deluxe System/3™,
Liebert Himod™, Liebert ICS™—Input and Holding—LAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Table 3-26: Liebert DataMate™, Liebert Mini-Mate Plus™, Liebert Mini-Mate2™—Input and Holding—L0B. . . 149
Table 3-27: Liebert DataMate™, Liebert Mini-Mate2™—Input and Holding—MM2 . . . . . . . . . . . . . . . . . . . . . . 150
Table 3-28: Liebert Mini-Mate2™ 8 Ton—Input and Holding—L8T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Table 3-29: Liebert Atlas Air™, Liebert Atlas PEC™, Liebert LECS 15™—Input and Holding—C10 2-step. . . . 154
Table 3-30: Liebert Atlas Air™, Liebert Atlas PEC™,
Liebert CEMS 100™—Input and Holding—C100 4-step . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Table 3-31: Liebert FPC™, Liebert PPC™—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
v
Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide
Table 3-32: Liebert Datawave™, Liebert FPC™,
Liebert PPC™—Input and Holding—PMP Option for Liebert FPC and Liebert PPC . . . . . . . . . . . . 161
Table 3-33: Liebert FPC™, Liebert PPC™—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Table 3-34: Liebert FPC™, Liebert PPC™—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Table 3-35: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Table 3-36: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Table 3-37: Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Status and Coil . . . . . . . . . . . . . . 186
Table 3-38: Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Input and Holding . . . . . . . . . . . . 187
Table 3-39: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™,
Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Table 3-40: Liebert STS™, Liebert STS/PDU™—Input and Holding—STS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Table 3-41: Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 . . . . . . . . . . . . . . . . . . . . . . . . . 195
Table 3-42: Liebert APM™, Liebert NXC™, Liebert NXR™—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Table 3-43: Liebert APM™, Liebert NXC™, Liebert NXR™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . 201
Table 3-44: Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Table 3-45: Liebert APS™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Table 3-46: Liebert APS™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Table 3-47: Liebert APS™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Table 3-48: Liebert EPM™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Table 3-49: Liebert EPM™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Table 3-50: Liebert EPM™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Table 3-51: Liebert eXL™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Table 3-52: Liebert eXL™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Table 3-53: Liebert eXL™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Table 3-54: Liebert eXM™—Controller with LCD HMI—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Table 3-55: Liebert eXM™—Controller with LCD HMI—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Table 3-56: Liebert eXM™—Controller with LCD HMI—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Table 3-57: Liebert eXM™—Controller with Touchscreen HMI—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . 251
Table 3-58: Liebert eXM™—Controller with Touchscreen HMI—Input and Holding . . . . . . . . . . . . . . . . . . . . . . 254
Table 3-59: Liebert eXM™—Controller with Touchscreen HMI—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Table 3-60: Liebert GXT2™ and Liebert GXT3™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Table 3-61: Liebert GXT2™ and Liebert GXT3™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
Table 3-62: Liebert GXT2™ and Liebert GXT3™—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
Table 3-63: Liebert GXT3™ and Liebert GXT4™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
Table 3-64: Liebert GXT3™ and Liebert GXT4™—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Table 3-65: Liebert GXT3™ and Liebert GXT4™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278
Table 3-66: Liebert HiNet™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Table 3-67: Liebert HiNet™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Table 3-68: Liebert Nfinity®—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Table 3-69: Liebert Nfinity®—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
Table 3-70: Liebert NX™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
Table 3-71: Liebert NX™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
Table 3-72: Liebert NX™ 225-600kVA UPS—Chloride ManageUPS—Input and Holding 3 . . . . . . . . . . . . . . . . 290
Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide vi
Table 3-73: Liebert NX 225-600kVA UPS—IS-UNITY-DP—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Table 3-74: Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Table 3-75: Liebert NX 225-600kVA UPS—IS-UNITY-DP—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Table 3-76: Liebert NXL™—60Hz, UL version (Model 40)—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
Table 3-77: Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . 306
Table 3-78: Liebert NXL™—60Hz, UL version (Model 40)—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318
Table 3-79: Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil . . . . . . . . . . . . . . . . . . . . 323
Table 3-80: Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding . . . . . . . . . . . . . . . . . . 327
Table 3-81: Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . 338
Table 3-82: Liebert PowerSure™ Interactive (before July 2008)—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . 346
Table 3-83: Liebert PowerSure™ Interactive (before July 2008)—Input and Holding . . . . . . . . . . . . . . . . . . . . . 347
Table 3-84: Liebert PowerSure™ Interactive 2—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
Table 3-85: Liebert PowerSure™ Interactive 2—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350
Table 3-86: Liebert Series 300™ UPS—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352
Table 3-87: Liebert Series 300™ UPS—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
Table 3-88: Liebert Series 600™ UPS—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355
Table 3-89: Liebert Series 600™ UPS—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
Table 3-90: Liebert Series 610™ SCC UPS—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
Table 3-91: Liebert Series 610 SCC UPS—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
Table 3-92: Liebert HiPulse™ and Liebert SICE 7200™—Input and Holding—SMM/SSM. . . . . . . . . . . . . . . . . 359
Table 3-93: Liebert SICE 7200™—Input and Holding—SSC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361
Table 3-94: Liebert Npower™—Input and Holding—IMP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Table 3-95: Alber® BDSU™—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
Table 3-96: Alber® BDSU™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 367
Table 4-1: Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™,
Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data . . . . . . . . . . . . . 378
Table 4-2: Extra Notes key to Table 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394
Table 4-3: Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™,
Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data . . . . . . . . . . . . 394
Table 4-4: Extra Notes key to Table 4-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
Table 4-5: Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™,
Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data. . . . . . . . . . 415
Table 4-6: Extra Notes key to Table 4-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
Table 4-7: Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™,
Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary . . . . . . . . . . . . . . 430
Table 4-8: Liebert CRV™—Binary Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
Table 4-9: Liebert CRV™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 448
Table 4-10: Liebert CRV™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452
Table 4-11: Liebert CRV™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
Table 4-12: Liebert HPC™—Binary Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465
Table 4-13: Liebert HPC™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
Table 4-14: Liebert HPC™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471
vii Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide
Table 4-15: Liebert HPC™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473
Table 4-16: Liebert XDP™, Liebert XDC™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 477
Table 4-17: Liebert XDP™, Liebert XDC™—Analog Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479
Table 4-18: Liebert XDP™, Liebert XDC™—Multistate Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481
Table 4-19: Liebert XDP™, Liebert XDC™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 488
Table 4-20: Liebert iCOM® DCL™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 495
Table 4-21: Liebert iCOM® DCL™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497
Table 4-22: Liebert iCOM® DCL™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Table 4-23: Liebert iCOM® DCL™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 503
Table 4-24: Liebert DataMate™, Liebert Mini-Mate2™—MM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508
Table 4-25: Liebert Mini-Mate2™ 8 Ton—L8T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 509
Table 4-26: Liebert APM™, Liebert NXC™, Liebert NXR™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 511
Table 4-27: Liebert APM™, Liebert NXC™, Liebert NXR™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 513
Table 4-28: Liebert APM™, Liebert NXC™, Liebert NXR™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 515
Table 4-29: Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516
Table 4-30: Liebert APS™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 519
Table 4-31: Liebert APS™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521
Table 4-32: Liebert APS™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523
Table 4-33: Liebert APS™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 526
Table 4-34: Liebert EPM™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530
Table 4-35: Liebert EPM™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 532
Table 4-36: Liebert EPM™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 534
Table 4-37: Liebert EPM™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536
Table 4-38: Liebert eXL™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 540
Table 4-39: Liebert eXL™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 544
Table 4-40: Liebert eXL™—Multistate Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 549
Table 4-41: Liebert eXL™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 556
Table 4-42: Liebert eXM™—Controller with LCD HMI—Binary Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565
Table 4-43: Liebert eXM™—Controller with LCD HMI—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 568
Table 4-44: Liebert eXM™—Controller with LCD HMI—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 570
Table 4-45: Liebert eXM™—Controller with LCD HMI—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 571
Table 4-46: Liebert eXM™—Controller with Touchscreen HMI—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 575
Table 4-47: Liebert eXM™—Controller with Touchscreen HMI—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . 578
Table 4-48: Liebert eXM™—Controller with Touchscreen HMI—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . 581
Table 4-49: Liebert eXM™—Controller with Touchscreen HMI—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 583
Table 4-50: Liebert GXT3™ and Liebert GXT4™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 588
Table 4-51: Liebert GXT3™ and Liebert GXT4™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 589
Table 4-52: Liebert GXT3™ and Liebert GXT4™—Multistate Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 591
Table 4-53: Liebert GXT3™ and Liebert GXT4™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 593
Table 4-54: Liebert NX™ 225-600kVA—Binary Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 596
Table 4-55: Liebert NX™ 225-600kVA—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 598
Table 4-56: Liebert NX™ 225-600kVA—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 601
Table 4-57: Liebert NX™ 225-600kVA—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603
Table 4-58: Liebert NXL™- 60Hz, UL version (Model 40)—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 606
Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide viii
Table 4-59: Liebert NXL™- 60Hz, UL version (Model 40)—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 612
Table 4-60: Liebert NXL™ - 60Hz, UL version (Model 40)—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 618
Table 4-61: Liebert NXL™—60Hz, UL version (Model 40)—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 624
Table 4-62: Liebert NXL™—60Hz, UL version (Model 40)—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 632
Table 4-63: Liebert NXL™—50 Hz, CE version (Models 48 and 49)—Binary Data. . . . . . . . . . . . . . . . . . . . . . . 640
Table 4-64: Liebert NXL™—50 Hz, CE version (Models 48 and 49)—Analog Data . . . . . . . . . . . . . . . . . . . . . . 644
Table 4-65: Liebert NXL™—50 Hz, CE version (Models 48 and 49)—Multistate Data . . . . . . . . . . . . . . . . . . . . 647
Table 4-66: Liebert NXL™—50 Hz, CE version (Models 48 and 49)—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . 655
Table 4-67: Liebert EXC™, Liebert FDC™, Liebert FPC™,
Liebert PPC™, Liebert RDC™ and Liebert RX™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 663
Table 4-68: Liebert EXC™, Liebert FDC™, Liebert FPC™,
Liebert PPC™, Liebert RDC™ and Liebert RX™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 665
Table 4-69: Liebert EXC™, Liebert FDC™, Liebert FPC™,
Liebert PPC™, Liebert RDC™ and Liebert RX™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . 671
Table 4-70: Liebert FDC™, Liebert FPC™, Liebert PPC™ and Liebert RDC™—Binary Data . . . . . . . . . . . . . . 672
Table 4-71: Liebert FDC™, Liebert FPC™, Liebert PPC™ and Liebert RDC™—Analog Data. . . . . . . . . . . . . . 673
Table 4-72: Liebert FDC™, Liebert FPC™, Liebert PPC™and Liebert RDC™—Multistate Data . . . . . . . . . . . . 675
Table 4-73: Liebert FPC™ and Liebert PPC™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 676
Table 4-74: Liebert FPC™ and Liebert PPC™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 683
Table 4-75: Liebert EXC™, Liebert FDC™, Liebert FPC™,
Liebert PPC™, Liebert RDC™ and Liebert RX™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 684
Table 4-76: Alber® BDSU™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 687
Table 4-77: Alber® BDSU™—Analog Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 691
Table 4-78: Alber® BDSU™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 698
Table 4-79: Alber® BDSU™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 699
ix Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide
Page intentionally left blank.
Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide x
Liebert Equipment Compatibility
1.0 Liebert Equipment Compatibility
1.1 What’s New in This Manual
The Liebert® IntelliSlot™ Unity Communications Card has been updated to support the Liebert EMP™ UPS
and Liebert DCL™ thermal-management equipment. Enhancements have also been added to support
modular Liebert eXM UPS equipment and a number of thermal-management products. The supported
Modbus and BACnet mapping tables for this equipment when using the IS-UNITY-DP communications
card have been added to this document.
In addition, Table 1-1 and Table 1-2 are updated to more-easily present the cards available to support the
specific BACnet and Modbus protocols.
1.2 Connectivity to Liebert IntelliSlot Using Modbus RTU,
Modbus TCP, BACnet MSTP or BACnet IP
This document describes the Modbus and BACnet communications protocols available for communication
with Emerson Network Power equipment. Included are the Liebert IntelliSlot Modbus RTU, Modbus TCP,
BACnet MSTP and the BACnet IP communications cards.
• The Modbus information includes implementation basics, supported types, frame format, function code
support and similar subjects.
• The BACnet information includes the BACnet service listing, object types, device objects, analog
objects, binary objects, multistate objects and BACnet engineering units.
NOTE
Some Building Management Systems can be configured to send continuous updates for device
setpoints, usually setting the same value. The BMS should be configured to send, on a sustained
average, no more than two writes per second to the device. This will allow the device to catch up
after a burst of updates when required while allowing other communication with the device to
proceed.
The Liebert NX™ 225-600kVA UPS uses the Chloride ManageUPS Net Adapter +B card for Modbus
support with the UPS’ native processor. If the UPS is upgraded to use the optional MUND control board,
then the IS-UNITY-DP card may be used to provide both Modbus and BACnet support. Both sets of
mapping tables are provided in this document and referenced in Table 1-1 and Table 1-2.
1.2.1
How to Use This Manual
Table 1-1 and Table 1-2 show the type of Liebert IntelliSlot card required for selected Liebert products.
Find the product first and the tables to reference, the columns to the right of that are the cards supported
for the product.
The information is organized by Product Name, Table Number, Controller Protocol and Card Part Number.
Modbus tables are first and BACnet tables second with products in the following sections:
• Thermal Management Products
• Power Distribution and Power Conditioning Products (Modbus Only)
• UPS Systems
• Battery Monitoring Products (Modbus Only)
Products currently shipping are shown first in each section, followed by older equipment.
1
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Liebert Equipment Compatibility
1.2.2
Compatibility with Liebert Equipment
Table 1-1
Liebert Equipment and Compatible Liebert IntelliSlot Cards
Modbus RTU & Modbus TCP Protocols
Product Supported
Compatible Card Part Number
Refer
to
Tables:
Modbus
TCP Card
Modbus
RTU Card
Liebert
iCOM® v4
IS-UNITY-DP
IS-IPBML*
IS-UNITY-DP
IS-485L*
Liebert
iCOM® v4
IS-UNITY-DP
IS-UNITY-DP
Liebert
iCOM v3
—
OC485-LBDS
LAM
—
IS-WEBADPT
OC485-ADPT*
L0B
—
IS-WEBADPT
OC485-ADPT*
MM2
—
IS-WEBADPT
OC485-ADPT*
L8T
—
IS-WEBADPT
OC485-ADPT*
C10
2-step
—
IS-WEBADPT
OC485-ADPT*
C100
4-step
—
IS-WEBADPT
OC485-ADPT*
Controller /
Protocol
Thermal Management Products
Liebert Challenger 3000™
3-1 to 3-5
Liebert Challenger ITR™
3-1 to 3-5
™
3-1 to 3-5
Liebert CRV
™
3-6 to 3-8
Liebert CW
™
3-15 to 3-17
Liebert DCP
™
Liebert Deluxe System/3
™
3-1 to 3-5
3-1 to 3-5
Liebert DS
DSE™
3-1 to 3-5
Liebert HPC™ (Chiller)
3-9 to 3-12
Liebert
™
3-1 to 3-5
Liebert HPM
Liebert
PeX™
3-1 to 3-5
Liebert
PCW/PDX™
3-1 to 3-5
Liebert
XDC™
3-13 to 3-10
Liebert
XDP™
3-15 to 3-17
Liebert DCL™
3-18 to 3-20
Liebert DS
3-21 to 3-22
Liebert PeX
3-21 to 3-22
Liebert XDF™
3-23 to 3-24
Liebert Challenger 3000
3-25
Liebert Deluxe System/3
3-25
Liebert
Himod™
3-25
Liebert ICS™
Liebert
3-25
DataMate™
Liebert Mini-Mate
Plus™
3-26
3-26
Liebert Mini-Mate2™
3-26
Liebert DataMate™
3-27
Liebert Mini-Mate2
3-27
Liebert Mini-Mate2 8 Ton
3-28
Liebert Atlas Air™
3-29
Liebert Atlas PEC™
3-29
Liebert LECS 15™
3-29
Liebert Atlas Air
3-30
Liebert Atlas PEC
3-30
Liebert CEMS 100™
3-30
*Communication cards marked with an asterisk are Discontinued.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
2
Liebert Equipment Compatibility
Table 1-1
Product Supported
Liebert Equipment and Compatible Liebert IntelliSlot Cards
Modbus RTU & Modbus TCP Protocols (continued)
Compatible Card Part Number
Refer
to
Tables:
Controller /
Protocol
Modbus
TCP Card
Modbus
RTU Card
IS-UNITY-DP
IS-UNITY-DP
IS-485S*
PMP2
—
IS-WEBADPT
OC485-ADPT*
PMP
—
IS-WEBADPT
OC485-ADPT*
STS
—
IS-WEBADPT
OC485-ADPT*
—
IS-WEBADPT
OC485-ADPT*
Power Distribution & Power Conditioning Products
Liebert EXC™
3-35,3-36,
3-39
LDMF
Liebert FDC™
3-35 to 3-39
LDMF, CPM
FPC™
3-33 to 3-39
Liebert PPC™
3-33 to 3-39
VPMP, LDMF,
CPM
™
Liebert RDC
3-35 to 3-39
LDMF, CPM
Liebert RX™
3-37 to 3-39
LDMF
Liebert
Liebert FPC
3-31
Liebert PPC
3-31
Liebert Datawave™
3-32
Liebert FPC
3-32
Liebert PPC
3-32
Liebert STS™
3-40
Liebert
STS/PDU™
Liebert STS2™
3-40
3-35 to 3-41
STS2
3-41
Liebert STS2/PDU™
3-35,3-36,
3-39, 3-41
STS2 with LDMF
Liebert APM™
3-42 to 3-44
—
IS-UNITY-DP
IS-IPBML*
IS-UNITY-DP
IS-485L*
Liebert APS™
3-45 to 3-47
—
IS-UNITY-DP
IS-UNITY-DP
™
3-48 to 3-50
—
IS-UNITY-DP
IS-UNITY-DP
3-51 to 3-53
—
IS-UNITY-DP
IS-UNITY-DP
Liebert eXM™
3-54 to 3-56
Controller with
LCD HMI
IS-UNITY-DP
IS-UNITY-DP
Liebert eXM™
3-57 to 3-59
Controller with
Touchscreen HMI
IS-UNITY-DP
IS-UNITY-DP
Liebert GXT2™
3-61 to 3-62
—
—
OC-485
UPS Systems
Liebert EPM
Liebert
eXL™
3-61 to 3-62
—
—
OC-485
3-63 to 3-65
—
IS-UNITY-DP
IS-UNITY-DP
Liebert GXT4™
3-63 to 3-65
—
IS-UNITY-DP
IS-UNITY-DP
™
3-66 to 3-67
—
—
OC-485
3-68 to 3-69
—
—
OC-485
3-70 to 3-71
—
—
OC-485
3-72
Native
Chloride
ManageUPS +B
Chloride
ManageUPS +B
3-73 to 3-74
Mund
IS-UNITY-DP
IS-UNITY-DP
IS-IPBML
IS-UNITY-DP
IS-IPBML
IS-UNITY-DP
Liebert GXT3™
Liebert HiNet
™
Liebert Nfinity
™
Liebert NX
Liebert NX™ 225-600
Liebert NXC™
3-42 to 3-44
—
IS-485L
IS-UNITY-DP
Liebert NXR™
3-42 to 3-44
—
IS-485L
IS-UNITY-DP
*Communication cards marked with an asterisk are Discontinued.
3
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Liebert Equipment Compatibility
Table 1-1
Liebert Equipment and Compatible Liebert IntelliSlot Cards
Modbus RTU & Modbus TCP Protocols (continued)
Compatible Card Part Number
Refer
to
Tables:
Controller /
Protocol
Modbus
TCP Card
Modbus
RTU Card
Liebert NXL™- 60 Hz, UL version (Model
40—SA, SR, SN, MM, CD)
3-76 to 3-78
—
IS-UNITY-DP
IS-IPBMX*
IS-UNITY-DP
IS-485X*
Liebert NXL™- 50 Hz, CE version (Model
48 and 49—SA, SR, SN, MM, CD)
3-79 to 3-81
—
IS-UNITY-DP
IS-UNITY-DP
Liebert PowerSure Interactive™
3-82 to 3-83
—
—
OC-485
3-84 to 3-85
—
—
OC-485
Product Supported
UPS Systems (continued)
™
Liebert PowerSure Interactive 2
Liebert Series 300™ UPS
3-86 to 3-87
—
—
IS-WEBADPT
OC485-ADPT*
Liebert Series 600™ UPS
3-88 to 3-89
—
—
IS-WEBADPT
OC485-ADPT*
Liebert Series 610™ SCC UPS
3-90 to 3-91
—
—
IS-WEBADPT
OC485-ADPT*
Liebert HiPulse™
3-92
SMM/SSM
—
IS-WEBADPT
OC485-ADPT*
™
Liebert SICE 7200
3-92
Liebert SICE 7200™
3-93
SSC
—
IS-WEBADPT
OC485-ADPT*
Liebert Npower™
3-94
IMP
—
IS-WEBADPT
OC485-ADPT*
3-95 to 3-96
—
IS-UNITY-DP
IS-IPBMX*
IS-UNITY-DP
IS-485X*
—
Battery Monitoring Products
Alber BDSU™
*Communication cards marked with an asterisk are Discontinued.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
4
Liebert Equipment Compatibility
Table 1-2
Liebert Equipment and Compatible Liebert IntelliSlot Cards
BACnet MSTP & BACnet IP Protocols
Product Supported
Compatible Card Part Number
Refer
to
Tables:
Controller /
Protocol
BACNet IP
BACnet MSTP
Liebert
iCOM v4
IS-UNITY-DP
IS-IPBML*
IS-UNITY-DP
Liebert
iCOM v4
IS-UNITY-DP
IS-UNITY-DP
Thermal Management Products
Liebert Challenger 3000™
4-1 to 4-7
Liebert Challenger ITR™
4-1 to 4-7
™
4-8 to 4-11
Liebert CRV
™
4-1 to 4-7
Liebert CW
Liebert
DCP™
4-16 to 4-19
Liebert Deluxe System/3
4-1 to 4-7
Liebert DS™
4-1 to 4-7
™
4-1 to 4-7
Liebert DSE
Liebert HPC™
4-12 to 4-15
™
Liebert HPM
4-1 to 4-7
Liebert PDX/PCW™
4-1 to 4-7
™
4-1 to 4-7
Liebert PeX
Liebert
XDC™
4-17 to 4-19
Liebert
XDP™
4-17 to 4-19
Liebert DCL™
4-20 to 4-23
Liebert DataMate™
4-24
Liebert Mini-Mate2
4-24
Liebert Mini-Mate2™ 8 Ton
4-25
MM2
IS-WEBADPT
L8T
—
—
UPS Systems
Liebert APM
4-26 to 4-29
—
IS-UNITY-DP
IS-UNITY-DP
Liebert APS
4-30 to 4-33
—
IS-UNITY-DP
IS-UNITY-DP
Liebert EPM™
4-34 to 4-37
—
IS-UNITY-DP
IS-UNITY-DP
Liebert eXL™
4-38 to 4-41
—
IS-UNITY-DP
IS-UNITY-DP
Liebert eXM™
4-42 to 4-45
Controller with
LCD HMI
IS-UNITY-DP
IS-UNITY-DP
Liebert eXM™
4-46 to 4-49
Controller with
Touchscreen HMI
IS-UNITY-DP
IS-UNITY-DP
Liebert GXT3™
4-50 to 4-53
—
IS-UNITY-DP
IS-UNITY-DP
™
Liebert GXT4
4-50 to 4-53
—
IS-UNITY-DP
IS-UNITY-DP
Liebert NX™ 225-600
4-54 to 4-57
—
IS-UNITY-DP
IS-UNITY-DP
NXC™
4-26 to 4-29
—
IS-UNITY-DP
IS-UNITY-DP
Liebert NXR™
4-26 to 4-29
—
IS-UNITY-DP
IS-UNITY-DP
Liebert NXL- 60Hz, UL version
(Model 40)
4-58 to 4-62
—
IS-UNITY-DP
IS-UNITY-DP
Liebert NXL™ - 50Hz, CE version
(Models 48 and 49)
4-63 to 4-66
—
IS-UNITY-DP
IS-UNITY-DP
Liebert
5
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Liebert Equipment Compatibility
Table 1-2
Product Supported
Liebert Equipment and Compatible Liebert IntelliSlot Cards
BACnet MSTP & BACnet IP Protocols (continued)
Compatible Card Part Number
Refer
to
Tables:
Controller /
Protocol
BACNet IP
BACnet MSTP
IS-UNITY-DP
IS-UNITY-DP
IS-485S*
IS-UNITY-DP
IS-UNITY-DP
Power Distribution and Power Conditioning Products
Liebert EXC™
4-67 to 4-69,
4-75
LDMF
Liebert FDC™
4-67 to 4-71,
4-75
LDMF, CPM
Liebert FPC™
4-67 to 4-75
Liebert PPC™
4-67 to 4-75
Liebert RDC™
4-67 to 4-71,
4-75
LDMF, CPM
Liebert RX™
4-67 to 4-69,
4-75
LDMF
4-76 to 4-79
—
VPMP, LDMF,
CPM
Battery Monitoring Products
Alber BDSU™
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
6
Modbus Communications
2.0 Modbus Communications
2.1 Implementation Basics
Modbus protocol provides control and data acquisition, through query and response, between master and
slave devices. This protocol comprises the rules for communication, controlling the message format
between devices, how master and slave devices initiate communications, as well as unit identification,
message-handling and error-checking.
The Liebert IntelliSlot 485/IP card acts as a slave device on a network. This network can be a multidrop
configuration over EIA-485, where multiple slaves reside on a common wire or loop.
2.2 Transmission Format
The Liebert IntelliSlot 485/IP interface card supports Modbus Remote Terminal Unit (RTU) transmission
modes. See Table 2-1 below.
Table 2-1
Modbus Remote Terminal Unit settings for Liebert IntelliSlot 485/IP interface card
Physical
Port
Transmission
Mode
Baud
Rate
Data
Bits
Parity
Bits
Stop
Bits
Start
Bits
EIA-485/422
2 wire
RTU
9600, 19200
or 38400
8
None
1
1
2.3 Modbus Packet Format
Each Modbus packet consists of these fields:
• Device Address
• Function Code
• Data Field(s)
• Error Check Field
2.3.1
Device Address
The address field immediately follows the beginning of the frame and consists of 8-bits (RTU). This bit
indicates the user-assigned address of the slave device that is to receive the message from the attached
master device.
Each slave must be assigned a unique address. Only the addressed slave will respond to a query that
contains its address.
7
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus Communications
2.3.2
Function Code
The function code field tells the addressed slaves what function to perform. Function codes are designed
to invoke a specific action by the slave device. The function code ranges from 1 to 127.
Liebert IntelliSlot Modbus server supports the following Modbus function codes.
Table 2-2
Code
Supported Modbus function codes
Function
Description
01
Read Coils
Read from 1 to 2000 contiguous status of coils managed by the server. Coils in the
response message are packed as one per bit of a byte, 1=On and 0=Off. If the requested
quantity of coils is not a multiple of 8, zeros are padded in the final byte.
02
Read Discrete Inputs
Read from 1 to 2000 contiguous input status managed by the server. Discrete inputs in the
response message are packed as one per bit of a byte, 1=On and 0=Off. If the requested
number of inputs is not a multiple of 8, zeros are padded in the final byte.
03
Read Holding Registers
Read the contents of contiguous block of 1 to 127 holding registers. Data are packed as
two bytes per register; the first byte contains the high order bits.
04
Read Input Registers
Read the contents of contiguous block of 1 to 127 Input registers. Data are packed as two
bytes per register; the first byte contains the high order bits.
05
Write Single Coil
Write a single output to either On (1) or Off (0) mapped in coil section.
06
Write Single Register
Write a value into a single holding register;
15
Write Multiple Coils
Force each coil in a sequence of coils to either On or Off.
16
Write Multiple Registers
Write values into a block of contiguous registers (1 to 120)
2.3.3
Data Fields
The data field length varies, depending on whether the message is a request or a response to a packet.
This field typically contains information required by the slave device to perform the command specified or
to the response to a data request from the master device.
Because Modbus can return only positive numbers, in registers that contain signed numbers the negative
numbers are encoded in two’s-complement form. For example, in a 16-bit register a -7 becomes FFF9 in
hexidecimal or 65529 in decimal.
2.3.4
Error Check Field
The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the
receiving device to detect a packet that has been corrupted by transmission errors.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
8
Modbus Communications
2.3.5
RTU Framing
The example below shows a typical query and response from a Liebert IntelliSlot interface card. The
master device initiates a query asking Slave Device, with address 2, for holding registers starting at
holding register 40051 (offset 50) and including next two registers (three total).
Table 2-3
Query sample
Starting Register
Number of Registers
CRC16
Slave
Address
Function
Code
Hi Byte
Lo Byte
Hi Byte
Lo Byte
Hi Byte
Lo Byte
02
03
00
32
00
03
E5
FA
Table 2-4
Slave
Address
Function
Code
Count:
Bytes of
Data
02
03
6
Response sample
Register
40051 Data
40052 Data
CRC16
40053 Data
Hi
Lo
Hi
Lo
Hi
Lo
Hi Byte
Lo Byte
1
58
00
FA
00
54
1B
0D
Slave Device, with address 2, responds to Function Code 3 with 6 bytes of hexadecimal data and ends
with CRC16 checksum.
Register values: 40051 = 158 (hex) = 344 (decimal)
40052 =
FA (hex) = 250 (decimal)
40053 =
54 (hex) =
9
84 (decimal)
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus Communications
Page intentionally left blank.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
10
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
3.0 Modbus RTU and Modbus TCP Protocols
3.1 Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Ext Reheat Lockout
10009
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Humidifier Lockout
10010
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Minimum Chilled Water Temp Set Point Enable
10013
13
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Return Air Sensor Event Control
10019
19
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Air Sensor A Event Control
10020
20
1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Compressor Lockout
10021
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
—
25
1
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Fan State
10025
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Cooling State
10026
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Free Cooling State
10027
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Hot Water / Hot Gas State
10028
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
System On/Off Control
11
Notes
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Notes
Extra Notes
(see
Table 3-2)
1
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
10031
—
1
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Main Fan Overload
10034
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Loss of Air Flow
10035
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Loss of Flow
10036
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor High Head Pressure
10037
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Low Suction Pressure
10038
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Thermal Overload
10039
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Pump Down Issue
10040
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor High Head Pressure 2
10041
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Low Suction Pressure 2
10042
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Thermal Overload 2
10043
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Data Label
Status
Coil
Number
of Bits
Electric Reheat State
10029
—
Humidifier State
10030
Dehumidifier State
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
12
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Compressor Pump Down Issue 2
10044
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Dig Scroll Comp Over Temp 1
10045
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Dig Scroll Comp Over Temp 2
10046
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Smoke Detected
10047
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Water Under Floor
10048
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Humidifier Issue
10049
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Standby Glycol Pump On
10050
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Standby Unit On
10051
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Condenser Pump High Water
10052
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Return Air Sensor Issue
10053
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Loss of Air Blower
10055
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Humidifier Low Water
10058
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Humidifier Over Current
10059
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
13
Notes
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Ext Over Temperature
10060
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Shutdown - Loss Of Power
10061
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Supply Chilled Water Over Temp
10065
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Return Air Over Temperature
10067
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Return Air Under Temperature
10068
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
High Return Humidity
10069
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Low Return Humidity
10070
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Air Sensor A Over Temperature
10071
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Air Sensor A Under Temperature
10072
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Air Sensor A High Humidity
10073
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Air Sensor A Low Humidity
10074
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Supply Chilled Water Loss of Flow
10075
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Clogged Air Filter
10076
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
14
Notes
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Supply Air Sensor Issue
10077
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Free Cooling Temp Sensor Issue
10078
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Air Sensor A Issue
10079
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Fan Hours Exceeded
10080
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Hours Exceeded 1
10081
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Hours Exceeded 2
10082
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Free Cooling Valve Hours Exceeded
10083
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Electric Reheater Hours Exceeded 1
10084
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Electric Reheater Hours Exceeded 2
10085
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Electric Reheater Hours Exceeded 3
10086
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Hot Water / Hot Gas Valve Hours Exceeded
10087
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Humidifier Hours Exceeded
10088
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Dehumidifier Hours Exceeded
10089
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
15
Notes
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Unit Communication Lost
10091
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Master Unit Communication Lost
10092
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Unit Code Missing
10094
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Service Required
10098
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Humidifier Control Board Not Detected
10099
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Customer Input 1
10104
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Customer Input 2
10105
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Customer Input 3
10106
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Customer Input 4
10107
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Dig Scroll Comp Discharge Temp Sensor Issue 1
10108
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Dig Scroll Comp Discharge Temp Sensor Issue 2
10109
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Supply Air Over Temperature
10209
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Supply Air Under Temperature
10210
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
16
Notes
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Ambient Air Sensor Issue
10211
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 9, 11, 12, 13,
14
Compressor Short Cycle 1
10212
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Short Cycle 2
10213
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Ext Free Cooling Lockout
10214
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Reheater Over Temperature
10215
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Humidifier Cylinder Worn
10216
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Humidifier Under Current
10217
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Fan Issue
10218
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Condenser TVSS Issue
10219
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Condenser VFD Issue
10220
—
1
Active on Alarm
1, 2, 4, 6, 10
Notes
Condenser Issue 1
10221
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Condenser Issue 2
10222
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
BMS Communications Timeout
10223
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
17
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Digital Output Board Not Detected 1
10224
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Digital Output Board Not Detected 2
10225
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Digital Output Board Not Detected 3
10226
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
RAM Battery Issue
10227
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Water Leakage Detector Sensor Issue
10228
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
External Fire Detected
10229
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Chilled Water Control Valve Failure 1
10230
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 11, 12, 13,
14
Chilled Water Control Valve Failure 2
10231
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 11, 12, 13,
14
Unit Off
10232
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Unit On
10233
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Unit Partial Shutdown
10234
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Unit Shutdown
10235
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
High Power Shutdown
10236
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
18
Notes
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Unit Standby
10237
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Maintenance Due
10238
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Maintenance Completed
10239
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Low Pressure Transducer Issue 1
10240
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Low Pressure Transducer Issue 2
10241
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor High Pressure Transducer Issue 1
10242
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor High Pressure Transducer Issue 2
10243
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Compressor Capacity Reduced
10244
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Dew Point Over Temperature
10345
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Dew Point Under Temperature
10346
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Ext Dew Point Over Temperature
10347
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Ext Dew Point Under Temperature
10348
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Compressor Superheat Over Threshold 1
10349
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Compressor Superheat Over Threshold 2
10350
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Unspecified General Event
10351
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
19
Notes
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Remote Sensor Average Over Temperature
10352
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Average Under Temperature
10353
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor System Average Over Temperature
10354
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor System Average Under Temperature
10355
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 1
10356
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 2
10357
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 3
10358
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 4
10359
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 5
10360
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 6
10361
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 7
10362
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 8
10363
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 9
10364
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Over Temperature 10
10365
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 1
10366
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 2
10367
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 3
10368
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 4
10369
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 5
10370
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
20
Notes
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Remote Sensor Under Temperature 6
10371
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 7
10372
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 8
10373
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 9
10374
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Under Temperature 10
10375
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 1
10376
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 10, 11, 12,
13, 14
Remote Sensor Issue 2
10377
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 3
10378
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 4
10379
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 5
10380
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 6
10381
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 7
10382
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 8
10383
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 9
10384
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Remote Sensor Issue 10
10385
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Air Economizer Emergency Override
10386
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
Air Economizer Reduced Airflow
10387
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 9, 10, 11, 12,
13, 14
Temperature Control Sensor Issue
10388
—
1
Active on Alarm
2, 3, 4, 5, 6, 7,
8, 11, 12, 13, 14
21
Notes
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
EEV Unspecified General Event
10488
—
1
Active on Alarm
4, 6, 7, 8, 11,
13, 14
Static Pressure Sensor Issue
10489
—
1
Active on Alarm
3, 5, 6, 7, 8, 9,
11, 12, 13, 14
High Static Pressure
10490
—
1
Active on Alarm
3, 5, 6, 7, 8, 11,
12, 13, 14
Low Static Pressure
10491
—
1
Active on Alarm
3, 5, 6, 7, 8, 11,
12, 13, 14
Pump Unspecified General Event
10492
—
1
Active on Alarm
4, 6, 7, 8, 11,
13, 14
Condenser Unit Unspecified General Event
10493
—
1
Active on Alarm
3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Condenser Circuit Unspecified General Event
10494
—
1
Active on Alarm
3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Input Undervoltage 1
10500
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Input Undervoltage 2
10501
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Input Undervoltage 3
10502
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Input Undervoltage 4
10503
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Input Undervoltage 5
10504
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Input Undervoltage 6
10505
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Return Humidity Sensor Issue
10600
—
1
Active on Alarm
3, 5, 6, 7, 8, 11,
12, 13, 14
Compressor Low Differential Pressure Lockout 1
10601
—
1
Active on Alarm
6, 7, 8, 11, 12,
13, 14
Compressor Low Differential Pressure Lockout 2
10602
—
1
Active on Alarm
6, 7, 8, 11, 12,
13, 14
Airflow Sensor Issue
10603
—
1
Active on Alarm
3, 5, 6, 7, 8, 11,
12, 13, 14
Ext Air Damper Position Issue
10604
—
1
Active on Alarm
3, 5, 6, 7, 8, 9,
11, 12, 13, 14
Ext Power Source A Failure
10605
—
1
Active on Alarm
3, 5, 6, 7, 8, 11,
12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
22
Notes
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Ext Power Source B Failure
10606
—
1
Active on Alarm
3, 5, 6, 7, 8, 11,
12, 13, 14
Static Pressure Sensor Out of Range
10607
—
1
Active on Alarm
3, 5, 6, 7, 8, 9,
11, 12, 13, 14
Fluid Temperature Sensor Issue 1
10608
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Fluid Temperature Sensor Issue 2
10609
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Fluid Flow Sensor Issue 1
10610
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Fluid Flow Sensor Issue 2
10611
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Mixed Mode Lockout
10620
—
1
Active on Alarm
6, 7, 8, 11, 12,
13, 14
Aux Air Temp Device Communication Lost
10630
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Modbus Power Meter Communication Lost 1
10640
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Modbus Power Meter Communication Lost 2
10641
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Modbus Power Meter Communication Lost 3
10642
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Modbus Power Meter Communication Lost 4
10643
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Modbus Power Meter Communication Lost 5
10644
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
Modbus Power Meter Communication Lost 6
10645
—
1
Active on Alarm
5, 8, 11, 12, 13,
14
External Condenser TVSS Issue
10655
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
External Condenser VFD Issue
10656
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Outside Air Temp Out of Operating Range 1
10677
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Outside Air Temp Out of Operating Range 2
10678
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Control Board Issue 1
10679
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
23
Notes
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Condenser Control Board Issue 2
10680
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Outside Air Temp Sensor Issue 1
10681
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Outside Air Temp Sensor Issue 2
10682
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Communication Lost 1
10683
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Communication Lost 2
10684
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Remote Shutdown 1
10685
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Remote Shutdown 2
10686
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser TVSS Issue 1
10687
—
1
Active on Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11,
12, 13, 14
Condenser TVSS Issue 2
10688
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Refrigerant Pressure Sensor Issue 1
10699
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Refrigerant Pressure Sensor Issue 2
10700
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Refrigerant Pressure Under Threshold 1
10701
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Refrigerant Pressure Under Threshold 2
10702
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Refrigerant Pressure Over Threshold 1
10703
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Refrigerant Pressure Over Threshold 2
10704
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Supply Refrigerant Temp Sensor Issue 1
10705
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Supply Refrigerant Temp Sensor Issue 2
10706
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Supply Refrigerant Under Temp 1
10707
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
24
Notes
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Extra Notes
(see
Table 3-2)
Data Label
Status
Coil
Number
of Bits
Condenser Supply Refrigerant Under Temp 2
10708
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Supply Refrigerant Over Temp 1
10709
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Supply Refrigerant Over Temp 2
10710
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Max Fan Speed Override 1
10711
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Max Fan Speed Override 2
10712
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Fan Issue 1
10723
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Fan Issue 2
10724
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Fan Issue 3
10725
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Fan Issue 4
10726
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Fan Issue 5
10727
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Fan Issue 6
10728
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Fan Issue 7
10729
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Condenser Fan Issue 8
10730
—
1
Active on Alarm
3, 5, 7, 8, 9, 11,
12, 13, 14
Compressor 1B Thermal Overload
10741
—
1
Active on Alarm
9
Compressor 2B Thermal Overload
10742
—
1
Active on Alarm
9
Compressor 1B Hours Exceeded
10743
—
1
Active on Alarm
9
Compressor 2B Hours Exceeded
10744
—
1
Active on Alarm
9
Notes
Team Static Pressure Sensor Failure
10750
—
1
Active on Alarm
9
Heating Lockout
10751
—
1
Active on Alarm
9
Free Cooling Stopped - High Room Temp
10752
—
1
Active on Alarm
9
Cold Aisle Temperature/Humidity Team Sensor Failure
10753
—
1
Active on Alarm
9
Cold Aisle Air Sensor Failure 1
10760
—
1
Active on Alarm
9
Cold Aisle Air Sensor Failure 2
10761
—
1
Active on Alarm
9
25
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued)
Controller Liebert iCOM® v4
Units with Liebert iCOM
Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Units with
Liebert Products Liebert iCOM®:
Liebert HPM
Available Points
Status
Data Label
Coil
Number
of Bits
Notes
Extra Notes
(see
Table 3-2)
Cold Aisle Air Sensor Failure 3
10762
—
1
Active on Alarm
9
Chilled Water Inlet Temperature Control Active
10770
—
1
Active on Alarm
9
Chilled Water Inlet Temperature Sensor Failure 1
10780
—
1
Active on Alarm
Chilled Water Inlet Temperature Sensor Failure 2
10781
—
1
Active on Alarm
Chilled Water Outlet Temperature Sensor Failure 1
10782
—
1
Active on Alarm
Chilled Water Outlet Temperature Sensor Failure 2
10783
—
1
Active on Alarm
Chilled Water Flow Meter Sensor Failure 1
10784
—
1
Active on Alarm
Chilled Water Flow Meter Sensor Failure 2
10785
—
1
Active on Alarm
Table 3-2
Number
Extra notes key to Table 3-1
Description
1
This point is supported on: iCOM controller version 1.04.042.STD
2
This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version 2.00.12R
(for Japan and China – language corrections only)
3
This point is supported on: iCOM controller version 2.01.29.07R
4
This point is supported on: iCOM controller version 2.02.21R
5
This point is supported on: iCOM controller version 2.01.45R
6
This point is supported on: iCOM controller version 2.03.27.06R
7
This point is supported on: iCOM controller version 2.03.33R
8
This point is supported on: iCOM controller version 2.04.32R
9
This point is supported on: iCOM controller version A9HB-1.04.23-R (Similar to Liebert PDX and to be
replaced by separate family branch.)
10
This point is supported on: iCOM controller version 1.04.37O-STD
11
This point is supported on: iCOM controller version 2.05.12T
12
This point is supported on: iCOM controller version 2.01.53R
13
This point is supported on: iCOM controller version 2.04.???R (TBD)
14
This point is supported on: iCOM controller version 2.05.19R
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
26
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding
Input
Holding
# of Regs
Scale
Units / Notes
—
0 = Disabled
1 = Contact
2 = Temperature
3 = Set Point
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
1, 9, 10
Data Label
Free Cooling Internal Control Mode
30017
40017
1
Extra Notes
(see
Table 3-4)
Humidity Control Type
30018
40018
1
—
0 = Relative
1 = Compensated
2 = Predictive
Fan Speed Maximum Set Point
30019
40019
1
—
%
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Supply Air Temperature Set Point
30020
40020
1
—
deg C
Int16
1, 9, 10
Supply Air Temperature Set Point
30733
40733
1
—
deg F
Int16
1, 9, 10
Free Cooling Internal Temperature
Delta
30021
40021
1
10
deg C
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Free Cooling Internal Temperature
Delta
30734
40734
1
10
deg F
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Minimum Chilled Water Temp Set
Point
30022
40022
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Minimum Chilled Water Temp Set
Point
30735
40735
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Air Temperature Set Point
30023
40023
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Air Temperature Set Point
30736
40736
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Air Temperature Proportional Band
30024
40024
1
10
deg C
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Air Temperature Proportional Band
30737
40737
1
10
deg F
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Air Temperature Dead Band
30025
40025
1
10
deg C
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Air Temperature Dead Band
30738
40738
1
10
deg F
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Air Temperature Control Integration
Time
30026
40026
1
10
min
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidity Set Point
30027
40027
1
—
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidity Proportional Band
30028
40028
1
—
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidity Control Integration Time
30029
40029
1
10
min
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidity Dead Band
30030
40030
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Auto Restart Delay
30031
40031
1
—
sec
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
27
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Air Temperature Control Type
30033
40033
1
—
0 = Proportional
1 = Prop+Integral
3 = Intelligent
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
BMS Timeout Period
30045
40045
1
—
min
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
High Return Air Temperature
Threshold
30050
40050
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
High Return Air Temperature
Threshold
30739
40739
1
10
deg F
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Low Return Air Temperature
Threshold
30051
40051
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Low Return Air Temperature
Threshold
30740
40740
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Over Temp
Threshold
30052
40052
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Over Temp
Threshold
30741
40741
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Under Temp
Threshold
30053
40053
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Under Temp
Threshold
30742
40742
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
High Return Humidity Threshold
30054
40054
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Low Return Humidity Threshold
30055
40055
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A High Humidity
Threshold
30056
40056
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Low Humidity
Threshold
30057
40057
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Fan Hours Threshold
30070
40070
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Compressor Hours
Threshold 1
30071
40071
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Compressor Hours
Threshold 2
30072
40072
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Humidifier Hours
Threshold
30073
40073
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Dehumidifier Hours
Threshold
30074
40074
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Free Cooling Valve
Hours Threshold
30075
40075
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Electric Reheater
Hours Threshold 1
30076
40076
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Electric Reheater
Hours Threshold 2
30077
40077
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
28
Extra Notes
(see
Table 3-4)
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
(Deprecated) Electric Reheater
Hours Threshold 3
30078
40078
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Hot Water / Hot Gas
Valve Hours Threshold
30079
40079
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Unit Operating State
30100
-
1
—
0 = off
1 = on
2 = standby
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
1 = Normal Operation
2 = StartUp
1, 2, 3, 4, 5, 6, 7, 8,
8 = Normal with Warning
9, 10, 11, 12, 13, 14
16 = Normal with Alarm
32 = Abnormal Operation
System Status
30102
-
1
—
Fan Speed
30103
—
1
—
%
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Utilization
30104
—
1
—
%
Uint16
1, 9, 10
Free Cooling Valve Open Position
30105
—
1
—
%
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Reheat Utilization
30106
—
1
—
%
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidifier Utilization
30107
—
1
—
%
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dehumidifier Utilization
30108
—
1
—
%
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Free Cooling Status
30109
—
1
—
0 = off
2 = on
3 = No Support
12, 13, 14
Return Air Temperature
30110
—
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Return Air Temperature
30743
—
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Supply Air Temperature
30112
—
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Supply Air Temperature
30744
—
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Supply Air Temperature Set Point
30113
—
1
—
deg C
Int16
1, 9, 10
Supply Air Temperature Set Point
30745
—
1
—
deg F
Int16
1, 9, 10
Free Cooling Fluid Temperature
30115
—
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Free Cooling Fluid Temperature
30746
—
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Temperature
30116
—
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
29
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Ext Air Sensor A Temperature
30747
—
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor B Temperature
30117
—
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor B Temperature
30748
—
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor C Temperature
30118
—
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor C Temperature
30749
—
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dig Scroll Comp Discharge Temp 1
30119
—
1
—
deg C
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dig Scroll Comp Discharge Temp 1
30750
—
1
—
deg F
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dig Scroll Comp Discharge Temp 2
30120
—
1
—
deg C
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dig Scroll Comp Discharge Temp 2
30751
—
1
—
deg F
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Return Humidity
30130
—
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Humidity
30132
—
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor B Humidity
30133
—
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor C Humidity
30134
—
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Today's High Air Temperature
30151
—
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Today's High Air Temperature
30752
—
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Today's Low Air Temperature
30153
—
1
10
deg C
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Today's Low Air Temperature
30753
—
1
10
deg F
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Today's High Humidity
30155
—
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Today's Low Humidity
30157
—
1
10
% RH
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
Server Class
30257
—
1
—
1 = UPS
2 = AIR
3 = PMP
4 = PDU
5 = MONITOR
Today's High Air Temperature Time
30258
—
2
—
Seconds since Midnight
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
30
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
30260
—
2
—
Seconds since Midnight
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 9, 10
Data Label
Today's Low Air Temperature Time
Extra Notes
(see
Table 3-4)
Supply Air Temperature Sensor
Control
30262
40262
1
—
0 = Disabled
1 = Limit
2 = Control
3 = Temp Only
Return Air Temperature Set Point
30263
40263
1
—
deg C
Int16
1, 9, 10
Return Air Temperature Set Point
30754
40754
1
—
deg F
Int16
1, 9, 10
Return Humidity Set Point
30264
40264
1
—
% RH
Uint16
1, 9, 10
Today's High Humidity Time
30265
-
2
—
Seconds since Midnight
—
Today's Low Humidity Time
30267
—
2
—
Seconds since Midnight
—
Compressor State 1
30269
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor State 2
30270
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Capacity Control State
1
30271
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Capacity Control State
2
30272
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Infrared Humidifier Flush Rate
30273
40273
1
—
%
Uint16
—
1, 9, 10
Fan Control Mode
30274
40274
1
—
0 = Auto
1 = Manual
2 = Economy
4 = Delta
Analog Input Reading 1
30275
—
1
100
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Analog Input Reading 2
30276
—
1
100
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Analog Input Reading 3
30277
—
1
100
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Analog Input Reading 4
30278
—
1
100
Int16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Unit Control Mode
30280
—
1
—
0 = Internal (Auto)
1 = External (Manual)
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
—
0 = Reason Unknown
1 = Network Display
2 = Alarm
3 = Schedule
4 = Remote System
5 = External Input
6 = Local Display
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Unit Operating State Reason
30281
—
1
31
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Maintenance Ramp
30282
—
1
—
%
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Calculated Next Maintenance Month
30283
—
1
—
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Calculated Next Maintenance Year
30284
—
1
—
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Hot Water / Hot Gas Valve Open
Position
30285
—
1
—
%
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Maintenance Tracking State
30286
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Customer Input 1 - Event Control
30287
40287
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Customer Input 1 - Event Type
30288
40288
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Customer Input 2 - Event Control
30289
40289
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
Customer Input 2 - Event Type
30290
40290
1
—
0 = Message
1 = Warning
2 = Alarm
Customer Input 3 - Event Control
30291
40291
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Customer Input 3 - Event Type
30292
40292
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Customer Input 4 - Event Control
30293
40293
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Customer Input 4 - Event Type
30294
40294
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Free Cooling Lockout - Event
Control
30295
40295
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Free Cooling Lockout - Event
Type
30296
40296
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Condenser Pump High Water Event Control
30297
40297
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Condenser Pump High Water Event Type
30298
40298
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Standby Glycol Pump On - Event
Control
30299
40299
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Standby Glycol Pump On - Event
Type
30300
40300
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
32
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Ext Standby Unit On - Event Control
30301
40301
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Standby Unit On - Event Type
30302
40302
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Humidifier Lockout - Event
Control
30303
40303
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Humidifier Lockout - Event Type
30304
40304
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Loss of Flow - Event Control
30305
40305
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
Ext Loss of Flow - Event Type
30306
40306
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Over Temperature - Event
Control
30307
40307
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Over Temperature - Event Type
30308
40308
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Reheat Lockout - Event Control
30309
40309
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Reheat Lockout - Event Type
30310
40310
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
High Power Shutdown - Event
Control
30311
40311
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
High Power Shutdown - Event Type
30312
40312
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidifier Issue - Event Control
30313
40313
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidifier Issue - Event Type
30314
40314
1
—
0 = Message
1 = Warning
2 = Alarm
Master Unit Communication Lost Event Control
30315
40315
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Master Unit Communication Lost Event Type
30316
40316
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Service Required - Event Control
30317
40317
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Service Required - Event Type
30318
40318
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
33
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Shutdown - Loss Of Power - Event
Control
30319
40319
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Shutdown - Loss Of Power - Event
Type
30320
40320
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Smoke Detected - Event Control
30321
40321
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Smoke Detected - Event Type
30322
40322
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Water Under Floor - Event Control
30323
40323
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
Water Under Floor - Event Type
30324
40324
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Compressor Lockout - Event
Control
30325
40325
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Compressor Lockout - Event
Type
30326
40326
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Clogged Air Filter - Event Control
30327
40327
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Clogged Air Filter - Event Type
30328
40328
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Loss of Air Blower - Event
Control
30329
40329
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Loss of Air Blower - Event Type
30330
40330
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor High Head Pressure Event Control 1
30331
40331
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor High Head Pressure Event Control 2
30332
40332
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor High Head Pressure Event Type 1
30333
40333
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor High Head Pressure Event Type 2
30334
40334
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Low Suction Pressure Event Control 1
30335
40335
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Low Suction Pressure Event Control 2
30336
40336
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
34
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Compressor Low Suction Pressure Event Type 1
30337
40337
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Low Suction Pressure Event Type 2
30338
40338
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Pump Down Issue Event Control 1
30339
40339
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Pump Down Issue Event Control 2
30340
40340
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Pump Down Issue Event Type 1
30341
40341
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Pump Down Issue Event Type 2
30342
40342
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Short Cycle - Event
Control 1
30343
40343
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Short Cycle - Event
Control 2
30344
40344
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Short Cycle - Event
Type 1
30345
40345
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Short Cycle - Event
Type 2
30346
40346
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Thermal Overload Event Control 1
30347
40347
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Thermal Overload Event Control 2
30348
40348
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Thermal Overload Event Type 1
30349
40349
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Thermal Overload Event Type 2
30350
40350
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dig Scroll Comp Discharge Over
Temp - Event Ctrl 1
30351
40351
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dig Scroll Comp Discharge Over
Temp - Event Ctrl 2
30352
40352
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dig Scroll Comp Discharge Over
Temp - Event Type 1
30353
40353
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
35
Extra Notes
(see
Table 3-4)
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Dig Scroll Comp Discharge Over
Temp - Event Type 2
30354
40354
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A High Humidity Event Control
30355
40355
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A High Humidity Event Type
30356
40356
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Low Humidity Event Control
30357
40357
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Low Humidity Event Type
30358
40358
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Over Temp - Event
Control
30359
40359
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
Extra Notes
(see
Table 3-4)
Ext Air Sensor A Over Temp - Event
Type
30360
40360
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Air Sensor A Under Temp Event Control
30361
40361
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Ext Air Sensor A Under Temp Event Type
30362
40362
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
High Return Humidity - Event Control 30363
40363
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
High Return Humidity - Event Type
30364
40364
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Low Return Humidity - Event Control 30365
40365
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Low Return Humidity - Event Type
30366
40366
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Return Air Over Temp - Event
Control
30367
40367
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Return Air Over Temp - Event Type
30368
40368
1
—
0 = Message
1 = Warning
2 = Alarm
Return Air Under Temp - Event
Control
30369
40369
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Return Air Under Temp - Event Type 30370
40370
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Fan Hours Exceeded - Event Control 30371
40371
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
36
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Fan Hours Exceeded - Event Type
30372
40372
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Fan Issue - Event Control
30373
40373
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Fan Issue - Event Type
30374
40374
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Main Fan Overload - Event Control
30375
40375
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Main Fan Overload - Event Type
30376
40376
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Condenser Issue - Event Control 1
30377
40377
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Condenser Issue - Event Control 2
30378
40378
1
—
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Condenser Issue - Event Type 1
30379
40379
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Condenser Issue - Event Type 2
30380
40380
1
—
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
—
40381
1
—
2 = Reset
4 = Acknowledge
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Air Temperature Control Sensor
30481
40481
1
—
0 = Supply
1 = Remote
2 = Return
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
High Supply Air Temperature
Threshold
30482
40482
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
High Supply Air Temperature
Threshold
30755
40755
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Low Supply Air Temperature
Threshold
30483
40483
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Low Supply Air Temperature
Threshold
30756
40756
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Outside Air Temperature
30484
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Outside Air Temperature
30757
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
—
0 = Relative
1 = Compensated
2 = Predictive
3 = Dew Point
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Data Label
System Event Acknowledge/Reset
Humidity Control Type
30485
40485
1
37
Extra Notes
(see
Table 3-4)
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Ext Air Sensor A Dew Point Temp
30486
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Ext Air Sensor A Dew Point Temp
30758
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Ext Dew Point Over Temp Threshold 30487
40487
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Ext Dew Point Over Temp Threshold 30759
40759
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Ext Dew Point Under Temp
Threshold
30488
40488
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Ext Dew Point Under Temp
Threshold
30760
40760
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Compressor Lockout
30489
40489
1
—
0 = disabled
1 = enabled
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Main Chilled Water Valve
30491
40491
1
—
0 = Valve 1
1 = Valve 2
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Reheater Lockout
30492
40492
1
—
0 = disabled
1 = enabled
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Humidifier Lockout
30493
40493
1
—
0 = disabled
1 = enabled
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Data Label
Fan Control Sensor
30494
40494
1
—
0 = Supply
1 = Remote
2 = Return
3 = Manual
Fan Speed Minimum Set Point
30495
40495
1
—
%
Uint16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Fan Speed Temperature Set Point
30497
40497
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Fan Speed Temperature Set Point
30761
40761
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Standby Units
30498
40498
1
—
Uint16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Adjusted Humidity
30499
—
1
10
% RH
Uint16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Return Dew Point
30500
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Return Dew Point
30762
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Actual Air Temperature Set Point
30501
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Actual Air Temperature Set Point
30763
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Actual Humidity Set Point
30502
—
1
—
% RH
Uint16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
38
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Dew Point Set Point
30764
40764
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Supply Air Over/Under Temperature
- Event Control
30504
40504
1
—
0 = disabled
1 = enabled
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Over Temp
Threshold
30505
40505
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Over Temp
Threshold
30765
40765
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Under Temp
Threshold
30506
40506
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Under Temp
Threshold
30766
40766
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Average
Temperature
30507
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Average
Temperature
30767
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Maximum
Temperature
30508
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Maximum
Temperature
30768
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor System Average
Temperature
30509
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor System Average
Temperature
30769
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor System Maximum
Temperature
30510
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor System Maximum
Temperature
30770
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 1
30551
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 1
30771
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 2
30552
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 2
30772
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 3
30553
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 3
30773
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 4
30554
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 4
30774
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Data Label
39
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Remote Sensor Temperature 5
30555
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 5
30775
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 6
30556
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 6
30776
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 7
30557
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 7
30777
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 8
30558
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 8
30778
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 9
30559
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 9
30779
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 10
30560
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Remote Sensor Temperature 10
30780
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Air Economizer Availability
30561
—
1
—
0 = Not Available
1 = Available
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Air Economizer Control Source
30562
40562
1
—
0 = disabled
1 = internal
2 = external
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Cooling Capacity
30564
—
1
—
%
Uint16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Cooling Control Temperature
30565
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Cooling Control Temperature
30781
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Fan Speed Control Temperature
30566
—
1
10
deg C
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Fan Speed Control Temperature
30782
—
1
10
deg F
Int16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
—
0 = Disabled
1 = Contact
2 = Temperature
3 = Set Point
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Data Label
Free Cooling Internal Control Mode
30567
40567
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
1
40
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Humidity Control Sensor
30667
40667
1
—
0 = Supply
1 = Remote
2 = Return
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Digital Scroll Compressor Loading 1
30668
—
1
—
%
Uint16
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
Digital Scroll Compressor Loading 2
30669
—
1
—
%
Uint16
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
Static Pressure Set Point
30672
40672
1
10
Pa
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Unit Static Pressure
30673
—
1
10
Pa
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
System Static Pressure
30674
—
1
10
Pa
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Low Noise Mode State
30675
—
1
—
0 = Inactive
1 = Active (Interval)
2 = Active (Full Day)
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
Condenser Low Noise Mode
Schedule Control
30676
40676
1
—
0 = disabled
1 = enabled
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
Condenser Low Noise Mode Max
Fan Speed
30677
40677
1
—
%
Uint16
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
Condenser Normal Mode Max Fan
Speed
30678
40678
1
—
%
Uint16
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
—
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
Data Label
Condenser Low Noise Mode Interval Days
30679
40679
1
Extra Notes
(see
Table 3-4)
Condenser Low Noise Mode - Full
Days
30680
40680
1
—
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
Condenser Low Noise Mode Start
Time
30681
40681
2
—
Seconds since Midnight
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
Condenser Low Noise Mode Stop
Time
30683
40683
2
—
Seconds since Midnight
3, 4, 5, 6, 7, 8, 11,
12, 13, 14
Pump Hours 1
30685
40685
2
—
hr
Uint32
6, 7, 8, 11, 13, 14
Pump Hours 2
30687
40687
2
—
hr
Uint32
6, 7, 8, 11, 13, 14
41
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
System Input RMS A-N 1
30800
—
1
10
VAC
Int16
5, 8, 9, 11, 12, 13,
14
System Input RMS A-N 2
30801
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-N 3
30802
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-N 4
30803
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-N 5
30804
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-N 6
30805
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-N 1
30810
—
1
10
VAC
Int16
5, 8, 9, 11, 12, 13,
14
System Input RMS B-N 2
30811
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-N 3
30812
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-N 4
30813
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-N 5
30814
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-N 6
30815
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-N 1
30820
—
1
10
VAC
Int16
5, 8, 9, 11, 12, 13,
14
System Input RMS C-N 2
30821
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-N 3
30822
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-N 4
30823
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-N 5
30824
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-N 6
30825
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase A
1
30830
—
1
10
A AC
Int16
5, 8, 9, 11, 12, 13,
14
System Input RMS Current Phase A
2
30831
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase A
3
30832
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase A
4
30833
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
Data Label
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
42
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
System Input RMS Current Phase A
5
30834
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase A
6
30835
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase B
1
30840
—
1
10
A AC
Int16
5, 8, 9, 11, 12, 13,
14
System Input RMS Current Phase B
2
30841
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase B
3
30842
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase B
4
30843
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase B
5
30844
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase B
6
30845
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase C
1
30850
—
1
10
A AC
Int16
5, 8, 9, 11, 12, 13,
14
System Input RMS Current Phase C
2
30851
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase C
3
30852
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase C
4
30853
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase C
5
30854
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
System Input RMS Current Phase C
6
30855
—
1
10
A AC
Int16
5, 8, 11, 12, 13, 14
Energy Consumption 1
30870
40870
2
—
kWH
Int32
5, 8, 9, 11, 12, 13,
14
Energy Consumption 2
30872
40872
2
—
kWH
Int32
5, 8, 11, 12, 13, 14
Energy Consumption 3
30874
40874
2
—
kWH
Int32
5, 8, 11, 12, 13, 14
Energy Consumption 4
30876
40876
2
—
kWH
Int32
5, 8, 11, 12, 13, 14
Energy Consumption 5
30878
40878
2
—
kWH
Int32
5, 8, 11, 12, 13, 14
Energy Consumption 6
30880
40880
2
—
kWH
Int32
5, 8, 11, 12, 13, 14
Fluid Input Temperature 1
30900
—
1
10
deg C
Int16
5, 8, 11, 12, 13, 14
Fluid Input Temperature 2
30901
—
1
10
deg C
Int16
5, 8, 11, 12, 13, 14
Data Label
43
Extra Notes
(see
Table 3-4)
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Fluid Input Temperature 1
30902
—
1
10
deg F
Int16
5, 8, 11, 12, 13, 14
Fluid Input Temperature 2
30903
—
1
10
deg F
Int16
5, 8, 11, 12, 13, 14
Fluid Output Temperature 1
30904
—
1
10
deg C
Int16
5, 8, 11, 12, 13, 14
Fluid Output Temperature 2
30905
—
1
10
deg C
Int16
5, 8, 11, 12, 13, 14
Fluid Output Temperature 1
30906
—
1
10
deg F
Int16
5, 8, 11, 12, 13, 14
Fluid Output Temperature 2
30907
—
1
10
deg F
Int16
5, 8, 11, 12, 13, 14
Fluid Flow Rate 1
30908
—
2
10
l/min
Int32
5, 8, 11, 12, 13, 14
Fluid Flow Rate 2
30910
—
2
10
l/min
Int32
5, 8, 11, 12, 13, 14
Unit Cooling Load
31001
—
2
10
kW
Int32
5, 8, 11, 12, 13, 14
Circuit Cooling Load 1
31003
—
2
10
kW
Int32
5, 8, 11, 12, 13, 14
Circuit Cooling Load 2
31005
—
2
10
kW
Int32
5, 8, 11, 12, 13, 14
Instantaneous Power 1
31010
—
2
—
W
Int32
5, 8, 9, 11, 12, 13,
14
Instantaneous Power 2
31012
—
2
—
W
Int32
5, 8, 11, 12, 13, 14
Instantaneous Power 3
31014
—
2
—
W
Int32
5, 8, 11, 12, 13, 14
Instantaneous Power 4
31016
—
2
—
W
Int32
5, 8, 11, 12, 13, 14
Instantaneous Power 5
31018
—
2
—
W
Int32
5, 8, 11, 12, 13, 14
Instantaneous Power 6
31020
—
2
—
W
Int32
5, 8, 11, 12, 13, 14
Raw Auxiliary Air Temperature
31050
41050
1
10
deg C
Int16
5, 8, 11, 12, 13, 14
Raw Auxiliary Air Temperature
31051
41051
1
10
deg F
Int16
5, 8, 11, 12, 13, 14
Actual Auxiliary Air Temperature
31052
—
1
10
deg C
Int16
5, 8, 11, 12, 13, 14
Actual Auxiliary Air Temperature
31053
—
1
10
deg F
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-B 1
31060
—
1
10
VAC
Int16
5, 8, 9, 11, 12, 13,
14
Data Label
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
44
Extra Notes
(see
Table 3-4)
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
System Input RMS A-B 2
31061
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-B 3
31062
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-B 4
31063
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-B 5
31064
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS A-B 6
31065
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-C 1
31070
—
1
10
VAC
Int16
5, 8, 9, 11, 12, 13,
14
System Input RMS B-C 2
31071
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-C 3
31072
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-C 4
31073
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-C 5
31074
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS B-C 6
31075
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-A 1
31080
—
1
10
VAC
Int16
5, 8, 9, 11, 12, 13,
14
System Input RMS C-A 2
31081
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-A 3
31082
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-A 4
31083
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-A 5
31084
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
System Input RMS C-A 6
31085
—
1
10
VAC
Int16
5, 8, 11, 12, 13, 14
Pump State 1
31100
—
1
—
0 = off
1 = on
7, 8, 11, 13, 14
Pump State 2
31110
—
1
—
0 = off
1 = on
7, 8, 11, 13, 14
Expected Condenser Unit Count
31130
—
1
—
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Refrigerant Type
31131
—
1
—
0 = R22
1 = R407C
2 = R410A
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Reversal Requested
1
31142
—
1
—
0 = false
1 = true
3, 5, 7, 8, 9, 11, 12,
13, 14
Data Label
45
Extra Notes
(see
Table 3-4)
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Condenser Fan Reversal Requested
2
31143
—
1
—
0 = false
1 = true
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Outside Air Temperature
1
31144
—
1
10
deg C
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Outside Air Temperature
1
31145
—
1
10
deg F
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Outside Air Temperature
2
31146
—
1
10
deg C
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Outside Air Temperature
2
31147
—
1
10
deg F
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Refrigerant Pressure 1
31158
—
1
10
bar
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Refrigerant Pressure 2
31159
—
1
10
bar
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Supply Refrigerant
Temperature 1
31160
—
1
10
deg C
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Supply Refrigerant
Temperature 1
31161
—
1
10
deg F
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Supply Refrigerant
Temperature 2
31162
—
1
10
deg C
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Supply Refrigerant
Temperature 2
31163
—
1
10
deg F
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Condenser Fan Speed 1
31174
—
1
—
%
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Speed 2
31175
—
1
—
%
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Speed 3
31176
—
1
—
%
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Speed 4
31177
—
1
—
%
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Speed 5
31178
—
1
—
%
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Speed 6
31179
—
1
—
%
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Speed 7
31180
—
1
—
%
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Speed 8
31181
—
1
—
%
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Power 1
31182
—
1
—
W
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Power 2
31183
—
1
—
W
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Power 3
31184
—
1
—
W
Int16
3, 5, 7, 8, 11, 12,
13, 14
Data Label
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
46
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
Condenser Fan Power 4
31185
—
1
—
W
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Power 5
31186
—
1
—
W
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Power 6
31187
—
1
—
W
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Power 7
31188
—
1
—
W
Int16
3, 5, 7, 8, 11, 12,
13, 14
Condenser Fan Power 8
31189
—
1
—
W
Int16
3, 5, 7, 8, 11, 12,
13, 14
Cold Aisle Humidity Calculation
Method
31200
—
1
—
0 = Highest
1 = Average
9
Cold Aisle Temperature Calculation
Method
31201
—
1
—
0 = Highest
1 = Average
9
Cold Aisle Control Enable
31202
—
1
—
0 = disabled
1 = enabled
9
Cold Aisle Force Max Fan/Cooling Ext Control
31203
—
1
—
0 = disabled
1 = enabled
9
Actual Cold Aisle Humidity
31204
—
1
10
% RH
Int16
9
Actual Cold Aisle Temperature
31205
—
1
10
deg C
Int16
9
Actual Cold Aisle Temperature
31206
—
1
10
deg F
Int16
9
Cold Aisle Cascade Fan Speed Max
Set Point
31207
—
1
—
%
Int16
9
Cold Aisle Fan Speed Min Set Point
31208
—
1
—
%
Int16
9
Cold Aisle Fan Speed Max Set Point
31209
—
1
—
%
Int16
9
Chilled Water Valve Reset Enable
31211
—
1
—
0 = disabled
1 = enabled
9
Humidification Fan Speed Min Set
Point
31212
—
1
—
%
Int16
9
Heating Fan Speed Min Set Point
31213
—
1
—
%
Int16
9
Dehumidification Fan Speed Min Set
Point
31214
—
1
—
%
Int16
9
Back Draft Control Fan Speed
31215
—
1
—
%
Int16
9
Data Label
47
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for
low limit protection
8, 11, 12, 13, 14
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for
low limit protection
8, 11, 12, 13, 14
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for
low limit protection
8, 11, 12, 13, 14
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for
low limit protection
8, 11, 12, 13, 14
8, 11, 12, 13, 14
Data Label
Local Fan Override
Local Cooling Override
Local Electric Heat Override
Local Humidifier Override
31300
31301
31302
31303
—
—
—
—
1
1
1
1
Extra Notes
(see
Table 3-4)
Local Dehumidifier Override
31304
—
1
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for
low limit protection
Super Saver Call For Cooling
31320
—
1
—
%
Int16
9, 11, 14
Tandem 'B' Compressor State 1
31325
—
1
—
0 = off
1 = on
8, 11, 12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
48
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Tandem 'B' Compressor State 2
31326
—
1
—
0 = off
1 = on
8, 11, 12, 13, 14
Tandem 'B' Compressor Hours 1
31327
41327
2
—
hr
Int32
8, 11, 12, 13, 14
Tandem 'B' Compressor Hours 2
31329
41329
2
—
hr
Int32
8, 11, 12, 13, 14
Condenser Fan Current 1
31331
—
1
10
A AC
Uint16
8, 11, 13, 14
Condenser Fan Current 2
31332
—
1
10
A AC
Uint16
8, 11, 13, 14
Condenser Fan Current 3
31333
—
1
10
A AC
Uint16
8, 11, 13, 14
Condenser Fan Current 4
31334
—
1
10
A AC
Uint16
8, 11, 13, 14
Condenser Fan Current 5
31335
—
1
10
A AC
Uint16
8, 11, 13, 14
Condenser Fan Current 6
31336
—
1
10
A AC
Uint16
8, 11, 13, 14
Condenser Fan Current 7
31337
—
1
10
A AC
Uint16
8, 11, 13, 14
Condenser Fan Current 8
31338
—
1
10
A AC
Uint16
8, 11, 13, 14
Compressor Hours 1
31340
41340
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Hours 2
31342
41342
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Chilled Water Valve Hours
31344
41344
2
—
hr
Int32
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
Free Cooling Valve Hours
31346
41346
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Hot Water / Hot Gas Valve Hours
31348
41348
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Electric Reheater Hours 1
31350
41350
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Electric Reheater Hours 2
31352
41352
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Electric Reheater Hours 3
31354
41354
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidifier Hours
31356
41356
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dehumidifier Hours
31358
41358
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Fan Hours
31360
41360
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Data Label
49
Extra Notes
(see
Table 3-4)
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Extra Notes
(see
Table 3-4)
(Deprecated) Chilled Water Valve
Hours
30563
40563
1
—
hr
Uint16
2, 3, 4, 5, 6, 7, 8,
11, 12, 13, 14
(Deprecated) Fan Hours
30141
40141
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Compressor Hours 1
30142
40142
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Compressor Hours 2
30143
40143
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Humidifier Hours
30144
40144
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Dehumidifier Hours
30145
40145
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Free Cooling Valve
Hours
30146
40146
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Electric Reheater
Hours 1
30147
40147
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Electric Reheater
Hours 2
30148
40148
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Electric Reheater
Hours 3
30149
40149
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
(Deprecated) Hot Water / Hot Gas
Valve Hours
30150
40150
1
—
hr
Uint16
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Static Pressure Set Point
31370
41370
1
1000
inWC
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Unit Static Pressure
31371
—
1
1000
inWC
Int16
3, 5, 7, 8, 11, 12,
13, 14
System Static Pressure
31372
—
1
1000
inWC
Int16
3, 5, 7, 8, 9, 11, 12,
13, 14
Dew Point Proportional Band
31380
41380
1
10
deg C
Int16
Dew Point Proportional Band
31382
41382
1
10
deg F
Int16
Dew Point Dead Band
31384
41384
1
10
deg C
Int16
Dew Point Dead Band
31386
41386
1
10
deg F
Int16
Free Cooling Status
30109
—
1
—
0 = off
1 = start
2 = on
11, 12, 13, 14
Thermal Control Override
31390
41390
1
—
0 = disabled
1 = enabled
11, 14
Thermal Control Override Temperature Control Type
31391
41391
1
—
0 = Cooling
1 = Heating
11, 14
Thermal Control Override Temperature Call
31392
41392
1
—
%
Int16
11, 14
Data Label
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
50
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Thermal Control Override - Humidity
Control Type
31393
41393
1
—
0 = Dehumidification
1 = Humidification
11, 14
Thermal Control Override - Humidity
Call
31394
41394
1
—
%
Int16
11, 14
Underfloor Static Pressure Control
Enable
31400
—
1
—
0 = disabled
1 = enabled
2 = visualization only
9
Return Damper Status
31401
—
1
—
0 = closed
1 = open
Air Filter Differential Pressure
31402
—
1
—
Pa
Int16
9
Air Filter Differential Pressure
31403
—
1
100
inWC
Int16
9
Cold Aisle Sensor Air Temperature 1 31410
—
1
10
deg C
Int16
9
Cold Aisle Sensor Air Temperature 1 31416
—
1
10
deg F
Int16
9
Cold Aisle Sensor Air Temperature 2 31411
—
1
10
deg C
Int16
9
Cold Aisle Sensor Air Temperature 2 31417
—
1
10
deg F
Int16
9
Cold Aisle Sensor Air Temperature 3 31412
—
1
10
deg C
Int16
9
Cold Aisle Sensor Air Temperature 3 31418
—
1
10
deg F
Int16
9
Cold Aisle Sensor Humidity 1
31413
—
1
10
% RH
Int16
9
Cold Aisle Sensor Humidity 2
31414
—
1
10
% RH
Int16
9
Cold Aisle Sensor Humidity 3
31415
—
1
10
% RH
Int16
9
Chilled Water Inlet Temperature 1
31420
—
1
10
deg C
Int16
9
Chilled Water Inlet Temperature 1
31424
—
1
10
deg F
Int16
9
Chilled Water Inlet Temperature 2
31421
—
1
10
deg C
Int16
9
Chilled Water Inlet Temperature 2
31425
—
1
10
deg F
Int16
9
Chilled Water Outlet Temperature 1
31422
—
1
10
deg C
Int16
9
Chilled Water Outlet Temperature 1
31426
—
1
10
deg F
Int16
9
Chilled Water Outlet Temperature 2
31423
—
1
10
deg C
Int16
9
Data Label
51
Extra Notes
(see
Table 3-4)
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Chilled Water Outlet Temperature 2
31427
—
1
10
deg F
Int16
9
Compressor Hours Threshold 1
31430
41430
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Compressor Hours Threshold 2
31432
41432
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Free Cooling Valve Hours Threshold
31434
41434
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Hot Water / Hot Gas Valve Hours
Threshold
31436
41436
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Electric Reheater Hours Threshold 1
31438
41438
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Electric Reheater Hours Threshold 2
31440
41440
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Electric Reheater Hours Threshold 3
31442
41442
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Humidifier Hours Threshold
31444
41444
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Dehumidifier Hours Threshold
31446
41446
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Fan Hours Threshold
31448
41448
2
—
hr
Int32
1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 11, 12, 13, 14
Chilled Water Valve Operating Hours
Threshold
31450
41450
2
—
hr
Int32
12, 13, 14
Pump Speed 1
31452
—
1
—
%
Uint16
13, 14
Pump Speed 2
31453
—
1
—
%
Uint16
13, 14
Pump Inlet Refrigerant Temperature
1
31454
—
1
10
deg C
Int16
13, 14
Pump Inlet Refrigerant Temperature
1
31461
—
1
10
deg F
Int16
13, 14
Pump Inlet Refrigerant Temperature
2
31455
—
1
10
deg C
Int16
13, 14
Pump Inlet Refrigerant Temperature
2
31462
—
1
10
deg F
Int16
13, 14
Pump Outlet Refrigerant
Temperature 1
31456
—
1
10
deg C
Int16
13, 14
Pump Outlet Refrigerant
Temperature 1
31463
—
1
10
deg F
Int16
13, 14
Pump Outlet Refrigerant
Temperature 2
31457
—
1
10
deg C
Int16
13, 14
Pump Outlet Refrigerant
Temperature 2
31464
—
1
10
deg F
Int16
13, 14
Data Label
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
52
Extra Notes
(see
Table 3-4)
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued)
Input
Holding
# of Regs
Scale
Units / Notes
Pump Hours Threshold
31458
41458
2
—
hr
Int32
13, 14
Unit Calculated Airflow
31466
—
2
—
m3/h
Uint32
12, 13, 14
—
0 = Bootup
1 = Idle
2 = Manual
3 = Pump Automatic
4 = Test
13, 14
13, 14
Data Label
PRE Operational Mode 1
31468
—
1
PRE Operational Mode 2
31469
—
1
—
0 = Bootup
1 = Idle
2 = Manual
3 = Pump Automatic
4 = Test
System Date and Time
39998
49998
2
—
Secs since Epoch(UTC)
Table 3-4
Extra Notes
(see
Table 3-4)
Extra notes key to Table 3-3
Number Description
1
This point is supported on: iCOM controller version 1.04.042.STD
2
This point is supported on: iCOM controller version 2.00.11R for US iCOM
controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on: iCOM controller version 2.01.29.07R
4
This point is supported on: iCOM controller version 2.02.21R
5
This point is supported on: iCOM controller version 2.01.45R
6
This point is supported on: iCOM controller version 2.03.27.06R
7
This point is supported on: iCOM controller version 2.03.33R
8
This point is supported on: iCOM controller version 2.04.32R
9
This point is supported on: iCOM controller version A9HB-1.04.xx (Similar to Liebert PDX
and to be replaced by separate family branch.)
10
This point is supported on: iCOM controller version 1.04.37O-STD
11
This point is supported on: iCOM controller version 2.05.18R
12
This point is supported on: iCOM controller version 2.01.53R
13
This point is supported on: iCOM controller version 2.04.???R (TBD)
14
This point is supported on: iCOM controller version 2.05.19R
53
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary
Data Label
Data Description
(Deprecated) Free Cooling Status (Deprecated) Free cooling status.
Actual Air Temperature Set Point
The actual set point being used for air temperature control. This value may differ from [Air
Temperature Set Point] if compensation is applied by the control.
Actual Auxiliary Air Temperature
Actual auxiliary air temperature value being used for control. This value may differ from
the raw value received from the auxiliary device if filtering is applied.
Actual Cold Aisle Humidity
Actual humidity value being used for cold aisle humidity control. The value is calculated
from multiple humidity measurements using [Cold Aisle Humidity Calculation Method].
Actual Cold Aisle Temperature
Actual temperature value being used for cold aisle temperature control. The value is
calculated from multiple temperature measurements using [Cold Aisle Temperature
Calculation Method].
Actual Humidity Set Point
The actual set point being used for humidity control. This value may differ from [Humidity
Set Point] if compensation is applied by the control.
Adjusted Humidity
Humidity value being used for control. This value may differ from the actual measured
[Return Humidity] based on several factors which may include, but are not limited to,
selection of humidity control sensor and humidity control type.
Air Economizer Availability
Indicates if the outside air conditions are appropriate for cooling with the air economizer or
glycol freecooling.
Air Economizer Control Source
Source of control of the air economizer.
Air Economizer Emergency
Override
Indoor room temperature has exceeded its upper threshold and the outdoor air damper
has been opened for emergency cooling.
Air Economizer Reduced Airflow
Air economizer filter is dirty and needs to be cleaned or replaced.
Air Filter Differential Pressure
Differential pressure across the air filter.
Air Temperature Control
Integration Time
Time value used when system is under integral air temperature control.
Air Temperature Control Sensor
Sensor from which air temperature measurements will be used for cooling and heating
control.
Air Temperature Control Type
Type of algorithm used to control the system's output air temperature.
Air Temperature Dead Band
Value that is divided evenly to form a temperature range above and below [Air
Temperature Set Point]. If measured air temperature is within this range, no heating or
cooling will occur.
Air Temperature Proportional
Band
Value that is divided evenly to form proportional temperature control bands above and
below [Air Temperature Set Point].
Air Temperature Set Point
Desired air temperature. This set point is dependent upon which sensor is selected for
control.
Airflow Sensor Issue
Airflow sensor is disconnected or the signal is out of range.
Ambient Air Sensor Issue
Ambient air sensor is disconnected or the signal is out of range.
Analog Input Reading
Generic analog input reading (unitless).
Auto Restart Delay
If power is lost, the control will delay this amount of time after power is restored before
restarting the unit.
Aux Air Temp Device
Communication Lost
Communication with external auxiliary device providing an air temperature value has been
lost.
Back Draft Control Fan Speed
Fan speed when in back draft control mode.
BMS Communications Timeout
Building Management System (or external monitoring system) has not communicated with
the system within the expected timeframe.
BMS Timeout Period
Timeframe within which the Building Management System (or external monitoring system)
must communicate with the system to avoid a timeout.
Calculated Next Maintenance
Month
Calculated month of the next scheduled maintenance. Used in conjunction with
[Calculated Next Maintenance Year].
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
54
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Calculated Next Maintenance
Year
Calculated year of the next scheduled maintenance. Used in conjunction with [Calculated
Next Maintenance Month].
Chilled Water Control Valve
Failure
Chilled water valve out of position. Chilled water control valve position does not match
expected value.
Chilled Water Flow Meter Sensor
Failure
Chilled water flow meter sensor is disconnected or the signal is out of range.
Chilled Water Inlet Temperature
Control Active
Chilled water inlet temperature control is active.
Chilled Water Inlet Temperature
Sensor Failure
Chilled water inlet temperature sensor is disconnected or the signal is out of range.
Chilled Water Inlet Temperature
Temperature of the water entering the hydraulic circuit of the chilled water unit.
Chilled Water Outlet Temperature
Chilled water outlet temperature sensor is disconnected or the signal is out of range.
Sensor Failure
Chilled Water Outlet Temperature Temperature of the water exiting the hydraulic circuit of the chilled water unit.
Chilled Water Valve Hours
Operating hours for chilled water valve since last reset of this value.
Chilled Water Valve Operating
Hours Threshold
Operating hours threshold for the chilled water valve. When the number of operating
hours reaches this threshold, an event is generated.
Chilled Water Valve Reset Enable Enable/disable the ability to reset the chilled water valve.
Circuit Cooling Load
The amount of heat energy currently being removed by a single refrigeration circuit.
Clogged Air Filter - Event Control
Enable/disable the activation of the [Clogged Air Filter] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Clogged Air Filter - Event Type
The event type for the [Clogged Air Filter] event.
Clogged Air Filter
Air filter is dirty and needs to be (cleaned or) replaced.
Cold Aisle Air Sensor Failure
Cold aisle sensor measuring air temperature and humidity is disconnected or the signal is
out of range.
Cold Aisle Cascade Fan Speed
Max Set Point
Cold aisle maximum fan speed when system is in cascade mode and one or more units in
the system are in standby.
Cold Aisle Control Enable
Enable/disable cold aisle control.
Cold Aisle Fan Speed Max Set
Point
Cold aisle maximum fan speed when system is not in cascade mode OR when system is
in cascade mode and no units in the system are in standby.
Cold Aisle Fan Speed Min Set
Point
Cold aisle minimum fan speed.
Cold Aisle Force Max Fan/Cooling The cold aisle fan speed and system cooling can be forced to 100% via an external input
- Ext Control
signal. Use this value to enable/disable that feature.
Cold Aisle Humidity Calculation
Method
Algorithm used to calculate a single cold aisle humidity value from multiple humidity
measurements.
Cold Aisle Sensor Air
Temperature
Air temperature measured by cold aisle sensor.
Cold Aisle Sensor Humidity
Humidity measured by cold aisle sensor.
Cold Aisle Temperature
Calculation Method
Algorithm used to calculate a single cold aisle temperature value from multiple
temperature measurements.
Cold Aisle Temperature/Humidity
Team Sensor Failure
Cold aisle team sensor measuring air temperature and humidity is disconnected or the
signal is out of range.
Compressor 1B Hours Exceeded
Fixed compressor 1B run hours have exceeded the threshold.
Compressor 1B Thermal Overload Fixed compressor 1B is shut down due to thermal overload.
Compressor 2B Hours Exceeded
Fixed compressor 2B run hours have exceeded the threshold.
Compressor 2B Thermal Overload Fixed compressor 2B is shut down due to thermal overload.
55
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Compressor Capacity Control
State
Compressor capacity control state. When 'ON', the cooling capacity of the compressor
has been reduced.
Compressor Capacity Reduced
Compressor capacity has been reduced.
Enable/disable the activation of the [Compressor High Head Pressure] event. If set to
Compressor High Head Pressure 'disabled', the event will not be annunciated. This implies that the event will not be placed
Event Control
in any active event list or in any event history list.
Compressor High Head Pressure The event type for the [Compressor High Head Pressure] event.
Event Type
Compressor High Head Pressure
Compressor is shut down due to high head pressure.
Compressor High Pressure
Transducer Issue
Compressor high pressure transducer is disconnected or the signal is out of range.
Compressor Hours Exceeded
[Compressor Hours] has exceeded [Compressor Hours Threshold].
Compressor Hours Threshold
Threshold value used in the [Compressor Hours Exceeded] event.
Compressor Hours
Operating hours for compressor since last reset of this value.
Compressor Lockout
Enable/disable the use of the compressor.
Compressor Low Differential
Pressure Lockout
Compressor exceeded maximum startup attempts due to low differential pressure.
Compressor is shutdown and has been disabled.
Compressor Low Pressure
Transducer Issue
Compressor low pressure transducer is disconnected or the signal is out of range.
Compressor Low Suction
Pressure - Event Control
Enable/disable the activation of the [Compressor Low Suction Pressure] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Compressor Low Suction
Pressure - Event Type
The event type for the [Compressor Low Suction Pressure] event.
Compressor Low Suction
Pressure
Compressor is shut down due to low suction pressure.
Compressor Pump Down Issue Event Control
Enable/disable the activation of the [Compressor Pump Down Issue] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Compressor Pump Down Issue Event Type
The event type for the [Compressor Pump Down Issue] event.
Compressor Pump Down Issue
Unable to pump down suction-side pressure during compressor shutdown.
Compressor Short Cycle - Event
Control
Enable/disable the activation of the [Compressor Short Cycle] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Compressor Short Cycle - Event
Type
The event type for the [Compressor Short Cycle] event.
Compressor Short Cycle
Compressor short cycle. A short cycle is defined as turning on and off a number of times
over a set time period.
Compressor State
Compressor operational state.
Compressor Superheat Over
Threshold
Compressor discharge refrigerant superheat temperature has exceeded an upper
threshold.
Compressor Thermal Overload Event Control
Enable/disable the activation of the [Compressor Thermal Overload] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Compressor Thermal Overload Event Type
The event type for the [Compressor Thermal Overload] event.
Compressor Thermal Overload
Compressor is shut down due to thermal overload.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
56
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Compressor Utilization
Present compressor utilization expressed as a percentage of the maximum rated
capacity.
Condenser Circuit Unspecified
General Event
One or more unspecified condenser circuit events active. See local unit display for further
details.
Condenser Communication Lost
Communication with condenser unit has been lost.
Condenser Control Board Issue
The condenser control board is reporting an issue.
Condenser Fan Current
Condenser fan's measured input current.
Condenser Fan Issue
Condenser fan is not operating within its operational parameters.
Condenser Fan Power
Condenser fan's measured input power.
Condenser Fan Reversal
Requested
Request the condenser fans to rotate in the reverse direction.
Condenser Fan Speed
Condenser fan speed expressed as a percentage of the maximum rated speed.
Condenser Issue - Event Control
Enable/disable the activation of the [Condenser Issue] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Condenser Issue - Event Type
The event type for the [Condenser Issue] event.
Condenser Issue
Condenser is not operating within its operational parameters.
Condenser Low Noise Mode - Full
Days of the week selected for low noise mode full day scheduling.
Days
Condenser Low Noise Mode Interval Days
Days of the week selected for low noise mode interval scheduling.
Condenser Low Noise Mode Max
Fan Speed
Maximum fan speed when condenser is placed in low noise mode.
Condenser Low Noise Mode
Schedule Control
Enable/disable scheduled control of condenser low noise mode.
Condenser Low Noise Mode Start
The time of day at which the condenser will transition into low noise mode.
Time
Condenser Low Noise Mode State State of condenser low noise mode scheduler control.
Condenser Low Noise Mode Stop
The time of day at which the condenser will transition out of low noise mode.
Time
Condenser Max Fan Speed
Override
Fan speed exceeding the maximum set point in order to alleviate a high temperature or
pressure condition.
Condenser Normal Mode Max Fan
Maximum fan speed when condenser is not in low noise mode.
Speed
Condenser Outside Air Temp Out
of Operating Range
[Condenser Outside Air Temperature] is either above an upper threshold or below a lower
threshold.
Condenser Outside Air Temp
Sensor Issue
Condenser outside air temperature sensor is disconnected or the signal is out of range.
Condenser Outside Air
Temperature
Condenser ambient outside air temperature.
Condenser Refrigerant Pressure
Over Threshold
Condenser refrigerant pressure has exceeded a threshold.
Condenser Refrigerant Pressure
Sensor Issue
Condenser refrigerant pressure sensor is disconnected or the signal is out of range.
Condenser Refrigerant Pressure
Under Threshold
Condenser refrigerant pressure has dropped below a threshold.
Condenser Refrigerant Pressure
Pressure of the refrigerant in a condenser circuit.
Condenser Refrigerant Type
Condenser refrigerant type.
Condenser Remote Shutdown
Condenser is shut down by a remote signal.
57
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Condenser Supply Refrigerant
Over Temp
Condenser supply refrigerant temperature has exceeded a threshold.
Condenser Supply Refrigerant
Temp Sensor Issue
Condenser supply refrigerant temperature sensor is disconnected or the signal is out of
range.
Condenser Supply Refrigerant
Temperature
Temperature of the supply refrigerant in a condenser circuit.
Condenser Supply Refrigerant
Under Temp
Condenser supply refrigerant temperature has dropped below a specified threshold.
Condenser TVSS Issue
The condenser Transient Voltage Surge Suppressor or Surge Protection Device has
failed.
Condenser Unit Unspecified
General Event
One or more unspecified condenser unit events active. See local unit display for further
details.
Condenser VFD Issue
The condenser fan Variable Frequency Drive is offline.
Cooling Capacity
Cooling capacity in use, expressed as a percentage of the maximum rated capacity.
Cooling Control Temperature
Temperature value being used for cooling capacity control. This value is compared
against the temperature set point to determine the amount of cooling to be applied.
Cooling State
Cooling operational state.
Customer Input 1 - Event Control
Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Customer Input 1 - Event Type
The event type for the [Customer Input 1] event.
Customer Input 1
Customer Input 1
Customer Input 2 - Event Control
Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Customer Input 2 - Event Type
The event type for the [Customer Input 2] event.
Customer Input 2
Customer Input 2
Customer Input 3 - Event Control
Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Customer Input 3 - Event Type
The event type for the [Customer Input 3] event.
Customer Input 3
Customer Input 3
Customer Input 4 - Event Control
Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Customer Input 4 - Event Type
The event type for the [Customer Input 4] event.
Customer Input 4
Customer Input 4
Dehumidification Fan Speed Min
Set Point
Minimum fan speed when system dehumidification is active.
Dehumidifier Hours Exceeded
Operating hours for the dehumidifier have exceeded the threshold.
Dehumidifier Hours Threshold
Threshold value used in the [Dehumidifier Hours Exceeded] event.
Dehumidifier Hours
Operating hours for dehumidifier since last reset of this value.
Dehumidifier State
Dehumidifier operational state.
Dehumidifier Utilization
Present dehumidifier utilization expressed as a percentage of the maximum rated
capacity.
Dew Point Dead Band
Value that is divided evenly to form a range above and below [Dew Point Set Point]. If
measured humidity is within this range, no humidification or dehumidification will occur.
This parameter is used when [Humidity Control Type] is set to Dew Point.
Dew Point Over Temperature
Dew point temperature reading has exceeded the upper threshold.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
58
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Dew Point Proportional Band
Value that is divided evenly to form proportional humidity control bands above and below
[Dew Point Set Point]. This parameter is used when [Humidity Control Type] is set to Dew
Point.
Dew Point Set Point
Desired dew point temperature.
Dew Point Under Temperature
Dew point temperature reading has dropped below the lower threshold.
Dig Scroll Comp Discharge Over
Temp - Event Ctrl
Enable/disable the activation of the [Dig Scroll Comp Discharge Over Temp] event.
Dig Scroll Comp Discharge Over
Temp - Event Type
The event type for the [Dig Scroll Comp Discharge Over Temp] event.
Dig Scroll Comp Discharge Temp
Sensor Issue
Digital scroll compressor discharge temperature sensor is disconnected or the signal is
out of range.
Dig Scroll Comp Discharge Temp
Digital scroll compressor discharge temperature.
Dig Scroll Comp Over Temp
Digital scroll compressor is shut down due to head temperature exceeding an upper
threshold.
Digital Output Board Not Detected Digital output board is required to be connected, but no signal is detected.
Digital Scroll Compressor Loading
Present digital scroll compressor utilization expressed as a percentage of the maximum
rated capacity.
EEV Unspecified General Event
One or more unspecified electronic expansion valve events active. See local unit display
for further details.
Electric Reheat State
Electric reheater operational state.
Electric Reheater Hours
Exceeded
[Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold].
Electric Reheater Hours
Threshold
Threshold value used in the [Electric Reheater Hours Exceeded] event.
Electric Reheater Hours
Operating hours for electric reheater since last reset of this value.
Energy Consumption
Energy consumption since the last reset of this value.
Expected Condenser Unit Count
Number of physical condenser units that are expected to be connected to the system.
Ext Air Damper Position Issue
Air damper position does not match expected value, as indicated by an external input
signal.
Ext Air Sensor A Dew Point Temp Dew point temperature as measured by external air sensor A.
Ext Air Sensor A Event Control
Enable/disable the activation of events related to measurements by the external air
sensor A.
Ext Air Sensor A High Humidity Event Control
Enable/disable the activation of the [Ext Air Sensor A High Humidity] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Ext Air Sensor A High Humidity Event Type
The event type for the [Ext Air Sensor A High Humidity] event.
Ext Air Sensor A High Humidity
Threshold
Threshold value used in the [External Air Sensor A High Humidity] event.
Ext Air Sensor A High Humidity
[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold].
Ext Air Sensor A Humidity
Relative humidity as measured by external air sensor A.
Ext Air Sensor A Issue
The external air sensor A is disconnected or the signal is out of range.
Ext Air Sensor A Low Humidity Event Control
Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Ext Air Sensor A Low Humidity Event Type
The event type for the [Ext Air Sensor A Low Humidity] event.
Ext Air Sensor A Low Humidity
Threshold
Threshold value used in the [External Air Sensor A Low Humidity] event.
59
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Ext Air Sensor A Low Humidity
[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity
Threshold].
Ext Air Sensor A Over Temp Event Control
Enable/disable the activation of the [External Air Sensor A Over Temperature] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Ext Air Sensor A Over Temp Event Type
The event type for the [External Air Sensor A Over Temperature] event.
Ext Air Sensor A Over Temp
Threshold
Threshold value used in the [External Air Sensor A Over Temperature] event.
Ext Air Sensor A Over
Temperature
[Ext Air Sensor A Temperature] has exceeded [External Air Sensor A Over Temp
Threshold].
Ext Air Sensor A Temperature
Air temperature as measured by external air sensor A.
Ext Air Sensor A Under Temp Event Control
Enable/disable the activation of the [Ext Air Sensor A Under Temperature] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Ext Air Sensor A Under Temp Event Type
The event type for the [Ext Air Sensor A Under Temperature] event.
Ext Air Sensor A Under Temp
Threshold
Threshold value used in the [External Air Sensor A Under Temperature] event.
Ext Air Sensor A Under
Temperature
[Ext Air Sensor A Temperature] has dropped below [Ext Air Sensor A Under Temp
Threshold].
Ext Air Sensor B Humidity
Relative humidity as measured by external air sensor B.
Ext Air Sensor B Temperature
Air temperature as measured by external air sensor B.
Ext Air Sensor C Humidity
Relative humidity as measured by external air sensor C.
Ext Air Sensor C Temperature
Air temperature as measured by external air sensor C.
Ext Compressor Lockout - Event
Control
Enable/disable the activation of the [Ext Compressor Lockout] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Ext Compressor Lockout - Event
Type
The event type for the [Ext Compressor Lockout] event.
Ext Compressor Lockout
The compressor is shut down and disabled by an external input signal.
Ext Condenser Pump High Water
- Event Control
Enable/disable the activation of the [Ext Condenser Pump High Water] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Ext Condenser Pump High Water
- Event Type
The event type for the [Ext Condenser Pump High Water] event.
Ext Condenser Pump High Water
High water is detected in the condensate pump by the auxiliary float, as indicated by an
external input signal.
Ext Dew Point Over Temp
Threshold
Threshold value used in the [Ext Dew Point Over Temperature] event.
Ext Dew Point Over Temperature
At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air
Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold].
Ext Dew Point Under Temp
Threshold
Threshold value used in the [Ext Dew Point Under Temperature] event.
At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air
Ext Dew Point Under Temperature Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp
Threshold].
Ext Free Cooling Lockout - Event
Control
Enable/disable the activation of the [Ext Free Cooling Lockout] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
60
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Ext Free Cooling Lockout - Event
Type
The event type for the [Ext Free Cooling Lockout] event.
Ext Free Cooling Lockout
Free cooling is disabled by an external input signal.
Ext Humidifier Lockout - Event
Control
Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Ext Humidifier Lockout - Event
Type
The event type for the [Ext Humidifier Lockout] event.
Ext Humidifier Lockout
The humidifier is shut down and disabled by an external input signal.
Ext Loss of Air Blower - Event
Control
Enable/disable the activation of the [Ext Loss of Air Blower] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Ext Loss of Air Blower - Event
Type
The event type for the [Ext Loss of Air Blower] event.
Ext Loss of Air Blower
Loss of air blower is detected, as indicated by an external input signal.
Ext Loss of Flow - Event Control
Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Ext Loss of Flow - Event Type
The event type for the [Ext Loss of Flow] event.
Ext Loss of Flow
Loss of flow is detected, as indicated by an external input signal.
Ext Over Temperature - Event
Control
Enable/disable the activation of the [Ext Over Temperature] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Ext Over Temperature - Event
Type
The event type for the [Ext Over Temperature] event.
Ext Over Temperature
A temperature has exceeded its threshold, as indicated by an external input signal.
Ext Power Source A Failure
Unit main power source A failure, as indicated by an external input signal.
Ext Power Source B Failure
Unit main power source B failure, as indicated by an external input signal.
Ext Reheat Lockout - Event
Control
Enable/disable the activation of the [Ext Reheat Lockout] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Ext Reheat Lockout - Event Type
The event type for the [Ext Reheat Lockout] event.
Ext Reheat Lockout
The reheater is shut down and disabled by an external input signal.
Ext Standby Glycol Pump On Event Control
Enable/disable the activation of the [Ext Standby Glycol Pump On] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Ext Standby Glycol Pump On Event Type
The event type for the [Ext Standby Glycol Pump On] event.
Ext Standby Glycol Pump On
The standby glycol pump is on, as indicated by an external input signal.
Ext Standby Unit On - Event
Control
Enable/disable the activation of the [Ext Standby Unit On] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Ext Standby Unit On - Event Type The event type for the [Ext Standby Unit On] event.
Ext Standby Unit On
Standby unit is on, as indicated by an external input signal.
External Condenser TVSS Issue
The condenser Transient Voltage Surge Suppressor or Surge Protection Device has
failed, as indicated by an external input signal.
External Condenser VFD Issue
The condenser fan Variable Frequency Drive is offline, as indicated by an external input
signal.
External Fire Detected
Fire detected, as indicated by an external input signal.
61
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Fan Control Mode
Fan control mode.
Fan Control Sensor
Sensor to be used for fan speed control.
Fan Hours Exceeded - Event
Control
Enable/disable the activation of the [Fan Hours Exceeded] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Fan Hours Exceeded - Event Type The event type for the [Fan Hours Exceeded] event.
Fan Hours Exceeded
Operating hours for the unit blower fan have exceeded the threshold.
Fan Hours Threshold
Threshold value used in the [Fan Hours Exceeded] event.
Fan Hours
Operating hours for fan since last reset of this value.
Fan Issue - Event Control
Enable/disable the activation of the [Fan Issue] event. If set to 'disabled', the event will not
be annunciated. This implies that the event will not be placed in any active event list or in
any event history list.
Fan Issue - Event Type
The event type for the [Fan Issue] event.
Fan Issue
One or more fans are not operating within their operational parameters.
Fan Speed Control Temperature
Temperature value being used for fan speed control. This value is compared against the
fan speed temperature set point to determine the fan speed.
Fan Speed Maximum Set Point
Maximum fan speed. This value may only be modified if iCOM is enabled to allow fan
speed changes by the BMS.
Fan Speed Minimum Set Point
Minimum fan speed.
If fan is in decoupled mode and not under manual control, the fan speed will vary
Fan Speed Temperature Set Point depending on the delta between the selected fan control sensor temperature and this set
point.
Fan Speed
Fan speed expressed as a percentage of the maximum rated speed.
Fan State
Fan operational state.
Fluid Flow Rate
Flow rate of fluid used for cooling.
Fluid Flow Sensor Issue
The fluid flow sensor is disconnected or the signal is out of range.
Fluid Input Temperature
Temperature of the fluid entering the cooling coil.
Fluid Output Temperature
Temperature of the fluid exiting the cooling coil.
Fluid Temperature Sensor Issue
The fluid temperature sensor is disconnected or the signal is out of range.
Free Cooling Fluid Temperature
Free cooling fluid temperature.
Free Cooling Internal Control
Mode
Free cooling internal control mode
Free Cooling Internal
Temperature Delta
Minimum temperature delta required between supply fluid and internal ambient air
temperatures in order to enable free cooling.
Free Cooling State
Free cooling operational state.
Free Cooling Status
Free cooling status.
Free Cooling Stopped - High
Room Temp
Free cooling is temporarily disabled due to room temperature exceeding a preset delta
above the the set point.
Free Cooling Temp Sensor Issue
The free cooling fluid temperature sensor is disconnected or the signal is out of range.
Free Cooling Valve Hours
Exceeded
[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold].
Free Cooling Valve Hours
Threshold
Threshold value used in the [Free Cooling Valve Hours Exceeded] event.
Free Cooling Valve Hours
Operating hours for free cooling valve since last reset of this value.
Free Cooling Valve Open Position Free cooling valve open position.
Heating Fan Speed Min Set Point
Minimum fan speed when system heating is active.
Heating Lockout
Heating is shut down and disabled.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
62
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
High Power Shutdown - Event
Control
Enable/disable the activation of the [High Power Shutdown] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
High Power Shutdown - Event
Type
The event type for the [High Power Shutdown] event.
High Power Shutdown
Supply to high power components has been shutdown.
High Return Air Temperature
Threshold
Threshold value used in the [Return Air Over Temperature] event.
High Return Humidity - Event
Control
Enable/disable the activation of the [High Return Humidity] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
High Return Humidity - Event
Type
The event type for the [High Return Humidity] event.
High Return Humidity Threshold
Threshold value used in the [High Return Humidity] event.
High Return Humidity
Return air high humidity event.
High Static Pressure
High static pressure event.
High Supply Air Temperature
Threshold
Threshold value used in the [Supply Air Over Temperature] event.
Hot Water / Hot Gas State
Hot water / hot gas operational state.
Hot Water / Hot Gas Valve Hours
Exceeded
[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours
Threshold].
Hot Water / Hot Gas Valve Hours
Threshold
Threshold value used in the [Hot Water / Hot Gas Valve Hours Exceeded] event.
Hot Water / Hot Gas Valve Hours
Operating hours for hot water / hot gas valve since last reset of this value.
Hot Water / Hot Gas Valve Open
Position
Hot water / hot gas valve open position.
Humidification Fan Speed Min Set
Minimum fan speed when system humidification is active.
Point
Humidifier Control Board Not
Detected
Humidifier control board is required to be connected, but no signal is detected.
Humidifier Cylinder Worn
Humidifier cylinder is not operating properly and needs to be replaced.
Humidifier Hours Exceeded
Operating hours for the humidifier have exceeded the threshold.
Humidifier Hours Threshold
Threshold value used in the [Humidifier Hours Exceeded] event.
Humidifier Hours
Operating hours for humidifier since last reset of this value.
Humidifier Issue - Event Control
Enable/disable the activation of the [Humidifier Issue] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Humidifier Issue - Event Type
The event type for the [Humidifier Issue] event.
Humidifier Issue
Humidifier issue detected, causing it to be locked out.
Humidifier Lockout
Enable/disable the use of the humidifier.
Humidifier Low Water
The water level in the humidifier has dropped below its threshold.
Humidifier Over Current
The electrical current to the humidifier has exceeded its upper threshold.
Humidifier State
Humidifier operational state.
Humidifier Under Current
The electrical current to the humidifier has dropped below its lower threshold.
Humidifier Utilization
Present humidifier utilization expressed as a percentage of the maximum rated capacity.
Humidity Control Integration Time
Time value used to add an integral term to humidity control. If set to 0, time will not be a
factor in the control algorithm.
63
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Humidity Control Sensor
Sensor from which humidity measurements will be used for humidification and
dehumidification control.
Humidity Control Type
Type of algorithm to use for control of output humidity.
Humidity Control Type
Type of algorithm to use for control of output humidity.
Humidity Dead Band
Value that is divided evenly to form a range above and below [Humidity Set Point]. If
measured humidity is within this range, no humidification or dehumidification will occur.
Humidity Proportional Band
Value that is divided evenly to form proportional humidity control bands above and below
[Humidity Set Point]. This setting applies to Relative, Predictive and Compensated
[Humidity Control Type] selections.
Humidity Set Point
Desired relative humidity.
Infrared Humidifier Flush Rate
A multiple of an internal time constant that determines the flush duration of the infrared
humidifier water pan.
Input Undervoltage
One or more of the input phase voltages has dropped below the limit.
Instantaneous Power
Total electrical power currently being consumed.
Local Cooling Override
The local unit override status for cooling capacity.
Local Dehumidifier Override
The local unit override status for the dehumidifier.
Local Electric Heat Override
The local unit override status for electric heat.
Local Fan Override
The local unit override status for fan speed.
Local Humidifier Override
The local unit override status for the humidifier.
Loss of Air Flow
No air flow through the unit due to failure of all fans.
Low Return Air Temperature
Threshold
Threshold value used in the [Return Air Under Temperature] event.
Low Return Humidity - Event
Control
Enable/disable the activation of the [Low Return Humidity] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Low Return Humidity - Event Type The event type for the [Low Return Humidity] event.
Low Return Humidity Threshold
Threshold value used in the [Low Return Humidity] event.
Low Return Humidity
Return air low humidity event.
Low Static Pressure
Low static pressure event.
Low Supply Air Temperature
Threshold
Threshold value used in the [Supply Air Under Temperature] event.
Main Chilled Water Valve
The primary valve in a dual valve chilled water system.
Main Fan Overload - Event
Control
Enable/disable the activation of the [Main Fan Overload] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Main Fan Overload - Event Type
The event type for the [Main Fan Overload] event.
Main Fan Overload
Main fan is shut down due to thermal overload.
Maintenance Completed
Maintenance has been completed on the unit.
Maintenance Due
The calculated maintenance date has been reached.
Maintenance Ramp
The ratio of operations performed to the calculated operations available between
maintenance intervals.
Maintenance Tracking State
Maintenance tracking operational state.
Enable/disable the activation of the [Master Unit Communication Lost] event. If set to
Master Unit Communication Lost 'disabled', the event will not be annunciated. This implies that the event will not be placed
Event Control
in any active event list or in any event history list.
Master Unit Communication Lost The event type for the [Master Unit Communication Lost] event.
Event Type
Master Unit Communication Lost
Communication with master unit has been lost.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
64
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Minimum Chilled Water Temp Set
Enable/disable the activation of [Minimum Chilled Water Temp Set Point].
Point Enable
Minimum Chilled Water Temp Set
Minimum desired chilled water temperature.
Point
Mixed Mode Lockout
Mixed mode has been entered too many times over a rolling time period and has been
temporarily disabled. Mixed mode is defined as the use of a compressor on one
refrigeration circuit and the use of a refrigerant pump on the other circuit.
Modbus Power Meter
Communication Lost
Communication with Modbus power meter has been lost.
Outside Air Temperature
Ambient outside air temperature.
PRE Operational Mode
Pumped Refrigerant Economizer operational mode.
Pump Hours Threshold
Threshold value used in the [Pump Hours Exceeded] event.
Pump Hours
Operating hours for pump since last reset of this value.
Pump Inlet Refrigerant
Temperature
Refrigerant temperature at the inlet of the pump.
Pump Outlet Refrigerant
Temperature
Refrigerant temperature at the outlet of the pump.
Pump Speed
Pump speed expressed as a percentage of the maximum rated speed.
Pump State
Pump operational state.
Pump Unspecified General Event
One or more unspecified pump events active. See local unit display for further details.
RAM Battery Issue
RAM or RAM backup battery is not operating correctly.
Raw Auxiliary Air Temperature
Air temperature value sent by an external auxiliary device, with no additional filtering by
the receiving system. This may be an aggregated value from multiple sensors.
Reheat Utilization
Present reheating utilization expressed as a percentage of the maximum rated capacity.
Reheater Lockout
Enable/disable the use of the reheater.
Reheater Over Temperature
The temperature of the reheater has exceeded its threshold.
Remote Sensor Average Over
Temperature
[Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp
Threshold].
Remote Sensor Average
Temperature
Average value of remote sensor temperature measurements.
Remote Sensor Average Under
Temperature
[Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp
Threshold].
Remote Sensor Issue
Remote sensor is disconnected or the signal is out of range.
Remote Sensor Maximum
Temperature
Maximum value of remote sensor temperature measurements.
Remote Sensor Over Temp
Threshold
Threshold value used in the remote air sensor over temperature events.
Remote Sensor Over
Temperature
[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold].
Remote Sensor System Average
Over Temperature
[Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over
Temp Threshold].
Remote Sensor System Average
Temperature
Average value of remote sensor temperature measurements among a group of
interconnected units in a single system.
Remote Sensor System Average
Under Temperature
[Remote Sensor System Average Temperature] has dropped below [Remote Sensor
Under Temp Threshold].
Remote Sensor System Maximum Maximum value of remote sensor temperature measurements among a group of
Temperature
interconnected units in a single system.
Remote Sensor Temperature
Air temperature as measured by remote sensor.
65
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Remote Sensor Under Temp
Threshold
Threshold value used in the remote air sensor under temperature events.
Remote Sensor Under
Temperature
[Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp
Threshold].
Return Air Over Temp - Event
Control
Enable/disable the activation of the [Return Air Over Temperature] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Return Air Over Temp - Event
Type
The event type for the [Return Air Over Temperature] event.
Return Air Over Temperature
Return air high temperature event.
Return Air Sensor Event Control
Enable/disable the activation of events related to measurements by the return air sensor.
Return Air Sensor Issue
The air sensor at the inlet of the unit is disconnected or the signal is out of range.
Return Air Temperature Set Point
Desired air temperature at the inlet of the unit.
Return Air Temperature
The temperature of the inlet air
Return Air Under Temp - Event
Control
Enable/disable the activation of the [Return Air Under Temperature] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Return Air Under Temp - Event
Type
The event type for the [Return Air Under Temperature] event.
Return Air Under Temperature
[Return Air Temperature] has dropped below [Low Return Air Temperature Threshold].
Return Damper Status
Status of the return damper.
Return Dew Point
Dew point temperature measured at the inlet of the unit.
Return Humidity Sensor Issue
The humidity sensor at the inlet of the unit is disconnected or the signal is out of range.
Return Humidity Set Point
Desired relative humidity at the inlet of the unit.
Return Humidity
Relative humidity measured at the inlet of the unit.
Server Class
The general classification for this system
Service Required - Event Control
Enable/disable the activation of the [Service Required] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Service Required - Event Type
The event type for the [Service Required] event.
Service Required
Unit requires servicing.
Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to 'disabled',
Shutdown - Loss Of Power - Event
the event will not be annunciated. This implies that the event will not be placed in any
Control
active event list or in any event history list.
Shutdown - Loss Of Power - Event
The event type for the [Shutdown - Loss Of Power] event.
Type
Shutdown - Loss Of Power
System lost power. This event becomes active when the unit is powered on following an
unexpected loss of power. This event remains active for 90 minutes.
Smoke Detected - Event Control
Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', the event
will not be annunciated. This implies that the event will not be placed in any active event
list or in any event history list.
Smoke Detected - Event Type
The event type for the [Smoke Detected] event.
Smoke Detected
Smoke detected.
Standby Units
The number of standby units.
Static Pressure Sensor Issue
The static pressure sensor is disconnected or the signal is out of range.
Static Pressure Sensor Out of
Range
Static pressure sensor signal is out of its configured range.
Static Pressure Set Point
Desired static pressure.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
66
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Super Saver Call For Cooling
Call for cooling value used for Super Saver functionality. A higher call for cooling value
indicates a need for a lower coolant temperature.
Supply Air Over Temperature
Supply air high temperature event.
Supply Air Over/Under
Temperature - Event Control
Enable/disable the activation of the [Supply Air Over Temperature] and [Supply Air Under
Temperature] events.
Supply Air Sensor Issue
The air sensor at the outlet of the unit is disconnected or the signal is out of range.
Supply Air Temperature Sensor
Control
Control mode to be used with the supply air temperature sensor.
Supply Air Temperature Set Point
Desired supply air temperature.
Supply Air Temperature
Air temperature measured at the outlet of the unit.
Supply Air Under Temperature
Supply air low temperature event.
Supply Chilled Water Loss of Flow Supply chilled water or glycol flow is too low.
Supply Chilled Water Over Temp
Chilled water temperature is too high, as indicated by an external input signal.
System Date and Time
The system date and time
System Event Acknowledge/Reset Reset and/or acknowledge all events.
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase
The system input RMS current for Phase A
A
System Input RMS Current Phase
The system input RMS current for Phase B
B
System Input RMS Current Phase
The system input RMS current for Phase C
C
System On/Off Control
Turn system functionality on or off.
System Static Pressure
Static pressure measurement among a group of interconnected units in a single system.
System Status
The operating status for the system
Tandem 'B' Compressor Hours
Operating hours for the 'B' compressor in a tandem configuration since last reset of this
value.
Tandem 'B' Compressor State
Operational state for the 'B' compressor in a tandem configuration.
Team Static Pressure Sensor
Failure
The team static pressure sensor is disconnected or the signal is out of range.
Temperature Control Sensor
Issue
The air sensor selected for cooling control is disconnected or the signal is out of range.
Thermal Control Override Temperature Call
If [Thermal Control Override] is enabled, this value sets the percent call for cooling or
heating.
Thermal Control Override Humidity Call
If [Thermal Control Override] is enabled, this value sets the percent call for humidification
or dehumidification.
Thermal Control Override Humidity Control Type
If [Thermal Control Override] is enabled, this value selects if the humidity override is
applied to humidification or dehumidification.
Thermal Control Override Temperature Control Type
If [Thermal Control Override] is enabled, this value selects if the temperature override is
applied to cooling or heating.
Thermal Control Override
Override internal programmatic control of thermal conditions. This includes, but may not
be limited to, temperature and humidity. The ability to enable this override may require
additional system configuration.
67
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Today's High Air Temperature
Time
[Today's High Air Temperature] was measured at this time.
Today's High Air Temperature
The highest external air temperature measured since midnight.
Today's High Humidity Time
[Today's High Humidity] was measured at this time
Today's High Humidity
The highest external humidity measured since midnight.
Today's Low Air Temperature
Time
[Today's Low Air Temperature] was measured at this time.
Today's Low Air Temperature
The lowest external air temperature measured since midnight.
Today's Low Humidity Time
[Today's Low Humidity] was measured at this time
Today's Low Humidity
The lowest external humidity measured since midnight.
Underfloor Static Pressure Control
Enable/disable the underfloor static pressure control.
Enable
Unit Calculated Airflow
Total airflow calculated for the unit.
Unit Code Missing
Unit code has not been entered and saved.
Unit Communication Lost
Master has lost communication with one or more networked units.
Unit Control Mode
Unit control mode.
Unit Cooling Load
The total amount of heat energy currently being removed by the unit.
Unit Off
Unit was turned off.
Unit On
Unit was turned on.
Unit Operating State Reason
The reason the unit is in the current operating state.
Unit Operating State
Current operating state of the unit.
Unit Partial Shutdown
An event has occurred requiring some system components to be shutdown and disabled.
Unit Shutdown
An event has occurred requiring the unit to be shutdown and disabled to prevent damage
to the system.
Unit Standby
Unit was placed in standby mode.
Unit Static Pressure
Static pressure measurement for a single unit.
Unspecified General Event
One or more unspecified events active. See local unit display for further details.
Water Leakage Detector Sensor
Issue
The water leakage detector sensor is disconnected or the signal is out of range.
Enable/disable the activation of the [Water Under Floor] event. If set to 'disabled', the
Water Under Floor - Event Control event will not be annunciated. This implies that the event will not be placed in any active
event list or in any event history list.
Water Under Floor - Event Type
The event type for the [Water Under Floor] event.
Water Under Floor
Water under the floor is detected.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
68
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-6
Liebert CRV™—Status and Coil
Data Label
Status
Coil
Number of Bits
Notes
10001
—
1
Active on Alarm
Air Temperature
Supply Air Over Temperature
Supply Air Under Temperature
10002
—
1
Active on Alarm
Return Air Over Temperature
10003
—
1
Active on Alarm
Supply Air Sensor Issue
10004
—
1
Active on Alarm
Return Air Sensor Issue
10077
—
1
Active on Alarm
High Return Humidity
10005
—
1
Active on Alarm
Low Return Humidity
10006
—
1
Active on Alarm
Humidifier Hours Exceeded
10007
—
1
Active on Alarm
Dehumidifier Hours Exceeded
10008
—
1
Active on Alarm
Humidifier Under Current
10009
—
1
Active on Alarm
Humidifier Over Current
10010
—
1
Active on Alarm
Humidifier Low Water
10011
—
1
Active on Alarm
Humidifier Cylinder Worn
10012
—
1
Active on Alarm
Humidifier Issue
10013
—
1
Active on Alarm
Humidity
Ext Humidifier Lockout
10014
—
1
Active on Alarm
Humidifier Control Board Not Detected
10015
—
1
Active on Alarm
Return Humidity Out Of Proportional Band
10016
—
1
Active on Alarm
Loss of Air Flow
10017
—
1
Active on Alarm
Fan Hours Exceeded
10018
—
1
Active on Alarm
Fans
Top Fan Issue
10019
—
1
Active on Alarm
Bottom Fan Issue
10020
—
1
Active on Alarm
Remote Sensor Issue
10021
—
1
Active on Alarm
Remote Sensor Issue
10022
—
1
Active on Alarm
Remote Sensor Issue
10023
—
1
Active on Alarm
Remote Sensor Issue
10024
—
1
Active on Alarm
Remote Sensor Issue
10025
—
1
Active on Alarm
Remote Sensor Issue
10026
—
1
Active on Alarm
Remote Sensor Issue
10027
—
1
Active on Alarm
Remote Sensor Issue
10028
—
1
Active on Alarm
Remote Sensor Issue
10029
—
1
Active on Alarm
Remote Sensor Issue
10030
—
1
Active on Alarm
Remote Sensor Average Under Temperature
10120
—
1
Active on Alarm
Remote Sensor Average Over Temperature
10121
—
1
Active on Alarm
Remote Sensor System Average Under Temperature
10122
—
1
Active on Alarm
Remote Sensor System Average Over Temperature
10123
—
1
Active on Alarm
Remote Sensor Average Low Humidity
10124
—
1
Active on Alarm
Remote Sensor Average High Humidity
10125
—
1
Active on Alarm
Remote Sensor System Average Low Humidity
10126
—
1
Active on Alarm
Remote Sensor System Average High Humidity
10127
—
1
Active on Alarm
Compressor 1 High Head Pressure
10031
—
1
Active on Alarm
Compressor 1 Low Suction Pressure
10032
—
1
Active on Alarm
Remote Sensors
Compressor
69
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-6
Liebert CRV™—Status and Coil (continued)
Data Label
Status
Coil
Number of Bits
Notes
Compressor 1 Hours Exceeded
10033
—
1
Active on Alarm
Dig Scroll Comp 1 Temp Sensor Issue
10034
—
1
Active on Alarm
Dig Scroll Comp 1 Over Temp
10035
—
1
Active on Alarm
Compressor 1 Low Pressure Transducer Issue
10036
—
1
Active on Alarm
Ext Compressor Lockout
10037
—
1
Active on Alarm
Compressor 1 Short Cycle
10038
—
1
Active on Alarm
Compressor 1 High Pressure Transducer Issue
10039
—
1
Active on Alarm
Compressor 1 Pump Down Issue
10040
—
1
Active on Alarm
Compressor Capacity Reduced
10180
—
1
Active on Alarm
Compressor Superheat Over Threshold
10181
—
1
Active on Alarm
Reheater Over Temperature
10041
—
1
Active on Alarm
Electric Reheater Hours Exceeded
10042
—
1
Active on Alarm
Ext Reheat Lockout
10043
—
1
Active on Alarm
Electric Reheater Hours Exceeded
10190
—
1
Active on Alarm
Reheater
Condenser
Condenser 1 Issue
10044
—
1
Active on Alarm
Condenser VFD Issue
10045
—
1
Active on Alarm
Condenser TVSS Issue
10046
—
1
Active on Alarm
External Condenser VFD Issue
10200
—
1
Active on Alarm
External Condenser TVSS Issue
10201
—
1
Active on Alarm
Supply Chilled Water Over Temp
10047
—
1
Active on Alarm
Chilled Water Control Valve Failure
10048
—
1
Active on Alarm
Supply Chilled Water Loss of Flow
10049
—
1
Active on Alarm
Chilled Water
System Events
Supply Fluid Temp Sensor Issue
10050
—
1
Active on Alarm
Customer Input 1
10051
—
1
Active on Alarm
Customer Input 2
10052
—
1
Active on Alarm
Customer Input 3
10053
—
1
Active on Alarm
Customer Input 4
10054
—
1
Active on Alarm
Smoke Detected
10055
—
1
Active on Alarm
Water Under Floor
10056
—
1
Active on Alarm
Service Required
10057
—
1
Active on Alarm
Shutdown - Loss Of Power
10058
—
1
Active on Alarm
Ext Over Temperature
10059
—
1
Active on Alarm
Ext Loss of Flow
10060
—
1
Active on Alarm
Ext Condenser Pump High Water
10061
—
1
Active on Alarm
Ext Standby Glycol Pump On
10062
—
1
Active on Alarm
External Fire Detected
10063
—
1
Active on Alarm
Unit On
10064
—
1
Active on Alarm
Unit Off
10065
—
1
Active on Alarm
Unit Standby
10066
—
1
Active on Alarm
Unit Partial Shutdown
10067
—
1
Active on Alarm
Unit Shutdown
10068
—
1
Active on Alarm
Water Leakage Detector Sensor Issue
10069
—
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
70
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-6
Liebert CRV™—Status and Coil (continued)
Status
Coil
Number of Bits
Notes
BMS Communications Timeout
10070
—
1
Active on Alarm
Maintenance Due
10071
—
1
Active on Alarm
Maintenance Completed
10072
—
1
Active on Alarm
Clogged Air Filter
10073
—
1
Active on Alarm
RAM Battery Issue
10074
—
1
Active on Alarm
Master Unit Communication Lost
10075
—
1
Active on Alarm
Data Label
High Power Shutdown
10076
—
1
Active on Alarm
Unspecified General Event
10100
—
1
Active on Alarm
SEC Unspecified General Event
10210
—
1
Active on Alarm
SEC Communication Lost
10211
—
1
Active on Alarm
Static Pressure Sensor Issue
10212
—
1
Active on Alarm
Static Pressure Sensor Out of Range
10213
—
1
Active on Alarm
Power Source 'A' Issue
10214
—
1
Active on Alarm
Power Source B Failure
10215
—
1
Active on Alarm
Fluid Flow Sensor Issue
10216
—
1
Active on Alarm
Fluid Temperature Sensor Issue
10217
—
1
Active on Alarm
Unit Code Missing
10218
—
1
Active on Alarm
Global Condenser
Condenser Outside Air Temp Sensor Issue
10078
—
1
Active on Alarm
Condenser Outside Air Temp Out of Operating Range
10079
—
1
Active on Alarm
Condenser Control Board Issue
10080
—
1
Active on Alarm
Condenser Refrigerant Pressure Over Threshold
10081
—
1
Active on Alarm
Condenser Refrigerant Pressure Under Threshold
10082
—
1
Active on Alarm
Condenser Refrigerant Pressure Sensor Issue
10083
—
1
Active on Alarm
Condenser Supply Refrigerant Over Temp
10084
—
1
Active on Alarm
Condenser Supply Refrigerant Under Temp
10085
—
1
Active on Alarm
Condenser Supply Refrigerant Temp Sensor Issue
10086
—
1
Active on Alarm
Condenser Max Fan Speed Override
10087
—
1
Active on Alarm
Condenser Unit Unspecified General Event
10101
—
1
Active on Alarm
Condenser Circuit Unspecified General Event
10102
—
1
Active on Alarm
Condenser Fan Issue
10088
—
1
Active on Alarm
Condenser Fan Issue
10089
—
1
Active on Alarm
Condenser Fan Issue
10090
—
1
Active on Alarm
Condenser Fan Issue
10091
—
1
Active on Alarm
10111
—
1
Active on Alarm
Condenser Fan
Auxiliary Air
Aux Air Temp Device Communication Lost
Remote Sensor 1
Remote Sensor Low Humidity
10130
—
1
Active on Alarm
Remote Sensor High Humidity
10140
—
1
Active on Alarm
Remote Sensor Under Temperature
10150
—
1
Active on Alarm
Remote Sensor Over Temperature
10160
—
1
Active on Alarm
71
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-6
Liebert CRV™—Status and Coil (continued)
Status
Coil
Number of Bits
Notes
Remote Sensor Low Humidity
10131
—
1
Active on Alarm
Remote Sensor High Humidity
10141
—
1
Active on Alarm
Remote Sensor Under Temperature
10151
—
1
Active on Alarm
Remote Sensor Over Temperature
10161
—
1
Active on Alarm
Data Label
Remote Sensor 2
Remote Sensor 10
Remote Sensor Low Humidity
10139
—
1
Active on Alarm
Remote Sensor High Humidity
10149
—
1
Active on Alarm
Remote Sensor Under Temperature
10159
—
1
Active on Alarm
Remote Sensor Over Temperature
10169
—
1
Active on Alarm
10230
—
1
Active on Alarm
EEV
EEV Superheat Below Threshold
EEV Discharge Temp Above Threshold
10231
—
1
Active on Alarm
EEV Battery Issue
10232
—
1
Active on Alarm
EEV Power Issue
10233
—
1
Active on Alarm
EEV Unspecified General Event
10234
—
1
Active on Alarm
Condenser Communication Lost
10253
—
1
Active on Alarm
Condenser Remote Shutdown
10254
—
1
Active on Alarm
Liebert Condenser
Power Measurement
Input Undervoltage
10270
—
1
Active on Alarm
Modbus Power Meter Communication Lost
10271
—
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
72
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding
Input
Holding
# of Reg
Scale
Notes/Units
Supply Air Temperature
30385
—
1
10
Units : deg C
Int16
Supply Air Temperature
30386
—
1
10
Units : deg F
Int16
Return Air Temperature
30387
—
1
10
Units : deg C
Int16
Return Air Temperature
30388
—
1
10
Units : deg F
Int16
Return Dew Point
30389
—
1
10
Units : deg C
Int16
Return Dew Point
30390
—
1
10
Units : deg F
Int16
Remote Sensor Minimum Temperature
30391
—
1
10
Units : deg C
Int16
Remote Sensor Minimum Temperature
30392
—
1
10
Units : deg F
Int16
Remote Sensor Maximum Temperature
30393
—
1
10
Units : deg C
Int16
Remote Sensor Maximum Temperature
30394
—
1
10
Units : deg F
Int16
Remote Sensor Average Temperature
30395
—
1
10
Units : deg C
Int16
Remote Sensor Average Temperature
30396
—
1
10
Units : deg F
Int16
Air Temperature Set Point
30397
40397
1
10
Units : deg C
Int16
Air Temperature Set Point
30398
40398
1
10
Units : deg F
Int16
Cooling Proportional Band
30399
40399
1
10
Units : deg C
Uint16
Cooling Proportional Band
30400
40400
1
10
Units : deg F
Uint16
Heating Proportional Band
30401
40401
1
10
Units : deg C
Uint16
Heating Proportional Band
30402
40402
1
10
Units : deg F
Uint16
Air Temperature Dead Band
30403
40403
1
10
Units : deg C
Uint16
Air Temperature Dead Band
30404
40404
1
10
Units : deg F
Uint16
Supply Air Over Temp Threshold
30405
40405
1
10
Units : deg C
Int16
Supply Air Over Temp Threshold
30406
40406
1
10
Units : deg F
Int16
Supply Air Under Temp Threshold
30407
40407
1
10
Units : deg C
Int16
Supply Air Under Temp Threshold
30408
40408
1
10
Units : deg F
Int16
Return Air Over Temp Threshold
30409
40409
1
10
Units : deg C
Int16
Return Air Over Temp Threshold
30410
40410
1
10
Units : deg F
Int16
Data Label
Air Temperature
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
73
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Air Temperature Control Sensor
30460
40460
1
—
0 = Supply
1 = Remote
2 = Return
Remote Sensor Temperature Calculation
30461
40461
1
—
0 = Average
1 = Maximum
Supply Humidity
30411
—
1
10
Units : % RH
Uint16
Return Humidity
30412
—
1
10
Units : % RH
Uint16
Humidity Set Point
30413
40413
1
—
Units : % RH
Uint16
Humidification Proportional Band
30414
40414
1
—
Units : % RH
Uint16
Dehumidification Proportional Band
30415
40415
1
—
Units : % RH
Uint16
Humidity Dead Band
30416
40416
1
10
Units : % RH
Uint16
High Return Humidity Threshold
30417
40417
1
10
Units : % RH
Uint16
Low Return Humidity Threshold
30418
40418
1
10
Units : % RH
Uint16
Fan Speed Proportional Band
30419
40419
1
10
Units : deg C
Uint16
Fan Speed Proportional Band
30420
40420
1
10
Units : deg F
Uint16
Fan Speed Manual Set Point
30421
40421
1
—
Units : %
Uint16
Fan Speed Maximum Set Point
30422
40422
1
—
Units : %
Uint16
Fan Speed Minimum Set Point
30423
40423
1
—
Units : %
Uint16
Fan Control Mode
30462
40462
1
—
0 = Internal (Auto)
1 = External (Manual)
Fan Control Sensor
30463
40463
1
—
0 = Supply
1 = Remote
2 = Return
Remote Sensor Temperature
30424
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30425
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30425
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30426
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30426
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30427
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30427
—
1
10
Units : deg C
Int16
Humidity
Fans
Remote Sensors
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
74
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Remote Sensor Temperature
30428
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30428
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30429
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30429
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30430
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30430
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30431
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30431
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30432
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30432
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30433
—
1
10
Units : deg F
Int16
Remote Sensor Temperature
30433
—
1
10
Units : deg C
Int16
Remote Sensor Temperature
30434
—
1
10
Units : deg F
Int16
Remote Sensor Function
30464
40464
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30465
40465
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30466
40466
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30467
40467
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30468
40468
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30469
40469
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30470
40470
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30471
40471
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30472
40472
1
—
0 = Disable
1 = Reference
2 = Control
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
75
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Remote Sensor Function
30473
40473
1
—
0 = Disable
1 = Reference
2 = Control
Remote Sensor System Average Temperature
30520
—
1
10
Units : deg C
Int16
Remote Sensor System Average Temperature
30521
—
1
10
Units : deg F
Int16
Remote Sensor System Maximum Temperature
30522
—
1
10
Units : deg C
Int16
Remote Sensor System Maximum Temperature
30523
—
1
10
Units : deg F
Int16
Remote Sensor Under Temp Threshold
30524
40524
1
10
Units : deg C
Int16
Remote Sensor Under Temp Threshold
30525
40525
1
10
Units : deg F
Int16
Remote Sensor Over Temp Threshold
30526
40526
1
10
Units : deg C
Int16
Remote Sensor Over Temp Threshold
30527
40527
1
10
Units : deg F
Int16
Supply Chilled Water Temperature
30444
—
1
10
Units : deg C
Int16
Supply Chilled Water Temperature
30445
—
1
10
Units : deg F
Int16
Supply Chilled Water Over Temp Threshold
30446
40446
1
10
Units : deg C
Int16
Supply Chilled Water Over Temp Threshold
30447
40447
1
10
Units : deg F
Int16
BMS Timeout Period
30448
40448
1
—
Units : min
Uint16
Auto Restart Delay
30449
40449
1
—
Units : sec
Uint16
Chilled Water
System Info
System Status
30474
—
1
—
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Operating State
30475
—
1
—
0 = off
1 = on
2 = standby
System Control Mode
30476
—
1
—
0 = Internal (Auto)
1 = External (Manual)
—
0 = Reason Unknown
1 = Network Display
2 = Alarm
3 = Schedule
4 = Remote System
5 = External Input
6 = Local Display
System Operating State Reason
30477
—
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
76
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding (continued)
Input
Holding
# of Reg
Scale
Notes/Units
Operating Efficiency
30450
—
1
—
Units : %
Uint16
Fan Speed
30451
—
1
—
Units : %
Uint16
Cooling Capacity (Primary)
30452
—
1
—
Units : %
Uint16
Dehumidifier Utilization
30453
—
1
—
Units : %
Uint16
Reheat Utilization
30454
—
1
—
Units : %
Uint16
Humidifier Utilization
30455
—
1
—
Units : %
Uint16
Calculated Next Maintenance Month
30456
—
1
—
Uint16
Calculated Next Maintenance Year
30457
—
1
—
Uint16
Data Label
System Operations
Maintenance Ramp
30458
—
1
—
Units : %
Uint16
System On/Off Control
30478
40478
1
—
0 = off
1 = on
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for low
limit protection
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for low
limit protection
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for low
limit protection
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for low
limit protection
Local Fan Override
Local Cooling Override
Local Electric Heat Override
Local Humidifier Override
30540
—
30541
—
30542
—
30543
—
1
1
1
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
77
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding (continued)
Data Label
Local Dehumidifier Override
Input
Holding
30544
—
# of Reg
1
Scale
Notes/Units
—
0 = Normal operation
1 = Increased for internal
protection
2 = Decreased for internal
protection
3 = Disabled for internal
protection
4 = Limited or disabled for low
limit protection
Protocol
30459
—
1
—
1 = UPS
2 = AIR
3 = PMP
4 = PDU
5 = MONITOR
Condenser Refrigerant Type
30479
—
1
—
0 = R22
1 = R407C
2 = R410A
Condenser Outside Air Temperature
30480
—
1
10
Units : deg C
Int16
Condenser Outside Air Temperature
30481
—
1
10
Units : deg F
Int16
Condenser Fan Speed
30482
—
1
—
Units : %
Int16
Condenser Fan Speed
30483
—
1
—
Units : %
Int16
Condenser Fan Speed
30484
—
1
—
Units : %
Int16
Condenser Fan Speed
30485
—
1
—
Units : %
Int16
Condenser Fan Power
30486
—
1
10
Units : kW
Uint16
Condenser Fan Power
30487
—
1
10
Units : kW
Uint16
Condenser Fan Power
30488
—
1
10
Units : kW
Uint16
Condenser Fan Power
30489
—
1
10
Units : kW
Uint16
Condenser Low Noise Mode State
30490
—
1
—
0 = Inactive
1 = Active (Interval)
2 = Active (Full Day)
Condenser Low Noise Mode Schedule Control
30491
40491
1
—
0 = disabled
1 = enabled
Condenser Low Noise Mode Max Fan Speed
30492
40492
1
—
Units : %
Uint16
Condenser Normal Mode Max Fan Speed
30493
40493
1
—
Units : %
Uint16
Server Class
Global Condenser
Condenser Fan
Low Noise Mode
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
78
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding (continued)
Data Label
Condenser Low Noise Mode - Interval Days
Input
30494
Holding
40494
# of Reg
1
Scale
Notes/Units
—
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
Condenser Low Noise Mode - Full Days
30495
40495
1
—
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
Condenser Low Noise Mode Start Time
30496
40496
2
—
Secs since Epoch(UTC)
Condenser Low Noise Mode Stop Time
30498
40498
2
—
Secs since Epoch(UTC)
1
—
Units : %
Int16
Super Saver
Super Saver Call For Cooling
30502
Auxiliary Air
Raw Auxiliary Air Temperature
30510
40510
1
10
Units : deg C
Int16
Raw Auxiliary Air Temperature
30511
40511
1
10
Units : deg F
Int16
Actual Auxiliary Air Temperature
30512
—
1
10
Units : deg C
Int16
Actual Auxiliary Air Temperature
30513
—
1
10
Units : deg F
Int16
30550
—
1
10
Units : %
Uint16
30560
—
1
—
Int16
EEV
EEV Open Position
Liebert Condenser
Expected Condenser Unit Count
Condenser Fan Reversal Requested
30562
—
1
—
0 = false
1 = true
Condenser Refrigerant Pressure
30563
—
1
10
Units : bar
Int16
Condenser Supply Refrigerant Temperature
30564
—
1
10
Units : deg C
Int16
Condenser Supply Refrigerant Temperature
30565
—
1
10
Units : deg F
Int16
System Input RMS A-B
30570
—
1
10
Units : VAC
Int16
System Input RMS A-N
30571
—
1
10
Units : VAC
Int16
System Input RMS Current Phase A
30572
—
1
10
Units : A AC
Int16
System Input RMS B-C
30573
—
1
10
Units : VAC
Int16
System Input RMS B-N
30574
—
1
10
Units : VAC
Int16
Power Measurement
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
79
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Input RMS Current Phase B
30575
—
1
10
Units : A AC
Int16
System Input RMS C-A
30576
—
1
10
Units : VAC
Int16
System Input RMS C-N
30577
—
1
10
Units : VAC
Int16
System Input RMS Current Phase C
30578
—
1
10
Units : A AC
Int16
Energy Consumption
30579
40579
2
—
Units : kWH
Int32
Instantaneous Power
30581
—
2
—
Units : W
Int32
Smoke Detected - Event Control
30592
40592
1
—
0 = disabled
1 = enabled
Smoke Detected - Event Type
30593
40593
1
—
0 = Message
1 = Warning
2 = Alarm
Water Under Floor - Event Control
30594
40594
1
—
0 = disabled
1 = enabled
Water Under Floor - Event Type
30595
40595
1
—
0 = Message
1 = Warning
2 = Alarm
Customer Input 1 - Event Control
30596
40596
1
—
0 = disabled
1 = enabled
Customer Input 1 - Event Type
30597
40597
1
—
0 = Message
1 = Warning
2 = Alarm
Customer Input 2 - Event Control
30598
40598
1
—
0 = disabled
1 = enabled
Customer Input 2 - Event Type
30599
40599
1
—
0 = Message
1 = Warning
2 = Alarm
Customer Input 3 - Event Control
30600
40600
1
—
0 = disabled
1 = enabled
Customer Input 3 - Event Type
30601
40601
1
—
0 = Message
1 = Warning
2 = Alarm
Customer Input 4 - Event Control
30602
40602
1
—
0 = disabled
1 = enabled
Customer Input 4 - Event Type
30603
40603
1
—
0 = Message
1 = Warning
2 = Alarm
Service Required - Event Control
30604
40604
1
—
0 = disabled
1 = enabled
Service Required - Event Type
30605
40605
1
—
0 = Message
1 = Warning
2 = Alarm
Shutdown - Loss Of Power - Event Control
30606
40606
1
—
0 = disabled
1 = enabled
Shutdown - Loss Of Power - Event Type
30607
40607
1
—
0 = Message
1 = Warning
2 = Alarm
Event Configuration
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
80
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-7
Liebert CRV™—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Ext Loss of Flow - Event Control
30608
40608
1
—
0 = disabled
1 = enabled
Ext Loss of Flow - Event Type
30609
40609
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Reheat Lockout - Event Control
30610
40610
1
—
0 = disabled
1 = enabled
Ext Reheat Lockout - Event Type
30611
40611
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Humidifier Lockout - Event Control
30612
40612
1
—
0 = disabled
1 = enabled
Ext Humidifier Lockout - Event Type
30613
40613
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Compressor Lockout - Event Control
30614
40614
1
—
0 = disabled
1 = enabled
Ext Compressor Lockout - Event Type
30615
40615
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Over Temperature - Event Control
30616
40616
1
—
0 = disabled
1 = enabled
Ext Over Temperature - Event Type
30617
40617
1
—
0 = Message
1 = Warning
2 = Alarm
Condenser VFD Issue - Event Control
30618
40618
1
—
0 = disabled
1 = enabled
Condenser VFD Issue - Event Type
30619
40619
1
—
0 = Message
1 = Warning
2 = Alarm
Condenser TVSS Issue - Event Control
30620
40620
1
—
0 = disabled
1 = enabled
Condenser TVSS Issue - Event Type
30621
40621
1
—
0 = Message
1 = Warning
2 = Alarm
Condenser 1 Issue - Event Control
30622
40622
1
—
0 = disabled
1 = enabled
Condenser 1 Issue - Event Type
30623
40623
1
—
0 = Message
1 = Warning
2 = Alarm
39998
49998
2
—
Secs since Epoch(UTC)
Time
System Date and Time
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
81
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-8
Liebert CRV™—Glossary
Data Label
Data Description
Actual Auxiliary Air Temperature
Actual auxiliary air temperature value being used for control. This
value may differ from the raw value received from the auxiliary
device if filtering is applied.
Air Temperature Control Sensor
Sensor from which air temperature measurements will be used for
cooling and heating control.
Air Temperature Dead Band
Value that is divided evenly to form a temperature range above and
below [Air Temperature Set Point]. If measured air temperature is
within this range, no heating or cooling will occur.
Air Temperature Set Point
Desired air temperature. This set point is dependent upon which
sensor is selected for control.
Auto Restart Delay
If power is lost, the control will delay this amount of time after power
is restored before restarting the unit.
Aux Air Temp Device Communication Lost
Communication with external auxiliary device providing an air
temperature value has been lost.
BMS Communications Timeout
Building Management System (or external monitoring system) has
not communicated with the system within the expected timeframe.
BMS Timeout Period
Timeframe within which the Building Management System (or
external monitoring system) must communicate with the system to
avoid a timeout.
Bottom Fan Issue
The bottom fan is not operating within its normal parameters.
Calculated Next Maintenance Month
Calculated month of the next scheduled maintenance. Used in
conjunction with [Calculated Next Maintenance Year].
Calculated Next Maintenance Year
Calculated year of the next scheduled maintenance. Used in
conjunction with [Calculated Next Maintenance Month].
Chilled Water Control Valve Failure
Chilled water valve out of position. Chilled water control valve
position does not match expected value.
Clogged Air Filter
Air filter is dirty and needs to be (cleaned or) replaced.
Compressor 1 High Head Pressure
Compressor 1 high head pressure.
Compressor 1 High Pressure Transducer Issue
Compressor 1 high pressure transducer is disconnected or the signal
is out of range.
Compressor 1 Hours Exceeded
Operating hours for compressor 1 have exceeded the threshold.
Compressor 1 Low Pressure Transducer Issue
Compressor 1 low pressure transducer is disconnected or the signal
is out of range.
Compressor 1 Low Suction Pressure
Compressor 1 low suction pressure.
Compressor 1 Pump Down Issue
Unable to pump down suction-side pressure during compressor 1
shutdown.
Compressor 1 Short Cycle
Compressor 1 short cycle. A short cycle is defined as turning on and
off a number of times over a set time period.
Compressor Capacity Reduced
Compressor capacity has been reduced.
Compressor Superheat Over Threshold
Compressor discharge refrigerant superheat temperature has
exceeded an upper threshold.
Condenser 1 Issue - Event Control
Enable/disable the activation of the [Condenser 1 Issue] event. If set
to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Condenser 1 Issue - Event Type
The event type for the [Condenser 1 Issue] event.
Condenser 1 Issue
Condenser 1 is not operating within its normal parameters.
Condenser Circuit Unspecified General Event
One or more unspecified condenser circuit events active. See local
unit display for further details.
Condenser Communication Lost
Communication with condenser unit has been lost.
Condenser Control Board Issue
The condenser control board is reporting an issue.
Condenser Fan Issue
Condenser fan is not operating within its operational parameters.
Condenser Fan Power
Condenser fan's measured input power.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
82
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-8
Liebert CRV™—Glossary (continued)
Data Label
Data Description
Condenser Fan Reversal Requested
Request the condenser fans to rotate in the reverse direction.
Condenser Fan Speed
Condenser fan speed expressed as a percentage of the maximum
rated speed.
Condenser Low Noise Mode - Full Days
Days of the week selected for low noise mode full day scheduling.
Condenser Low Noise Mode - Interval Days
Days of the week selected for low noise mode interval scheduling.
Condenser Low Noise Mode Max Fan Speed
Maximum fan speed when condenser is placed in low noise mode.
Condenser Low Noise Mode Schedule Control
Enable/disable scheduled control of condenser low noise mode.
Condenser Low Noise Mode Start Time
The time of day at which the condenser will transition into low noise
mode.
Condenser Low Noise Mode State
State of condenser low noise mode scheduler control.
Condenser Low Noise Mode Stop Time
The time of day at which the condenser will transition out of low
noise mode.
Condenser Max Fan Speed Override
Fan speed exceeding the maximum set point in order to alleviate a
high temperature or pressure condition.
Condenser Normal Mode Max Fan Speed
Maximum fan speed when condenser is not in low noise mode.
Condenser Outside Air Temp Out of Operating Range
[Condenser Outside Air Temperature] is either above an upper
threshold or below a lower threshold.
Condenser Outside Air Temp Sensor Issue
Condenser outside air temperature sensor is disconnected or the
signal is out of range.
Condenser Outside Air Temperature
Condenser ambient outside air temperature.
Condenser Refrigerant Pressure Over Threshold
Condenser refrigerant pressure has exceeded a threshold.
Condenser Refrigerant Pressure Sensor Issue
Condenser refrigerant pressure sensor is disconnected or the signal
is out of range.
Condenser Refrigerant Pressure Under Threshold
Condenser refrigerant pressure has dropped below a threshold.
Condenser Refrigerant Pressure
Pressure of the refrigerant in a condenser circuit.
Condenser Refrigerant Type
Condenser refrigerant type.
Condenser Remote Shutdown
Condenser is shut down by a remote signal.
Condenser Supply Refrigerant Over Temp
Condenser supply refrigerant temperature has exceeded a
threshold.
Condenser Supply Refrigerant Temp Sensor Issue
Condenser supply refrigerant temperature sensor is disconnected or
the signal is out of range.
Condenser Supply Refrigerant Temperature
Temperature of the supply refrigerant in a condenser circuit.
Condenser Supply Refrigerant Under Temp
Condenser supply refrigerant temperature has dropped below a
specified threshold.
Condenser TVSS Issue - Event Control
Enable/disable the activation of the [Condenser TVSS or SPD Issue]
event (Transient Voltage Surge Suppressor or Surge Protection
Device). If set to 'disabled', the event will not be annunciated. This
implies that the event will not be placed in any active event list or in
any event history list.
Condenser TVSS Issue - Event Type
The event type for the [Condenser TVSS or SPD Issue] event
(Transient Voltage Surge Suppressor or Surge Protection Device).
Condenser TVSS Issue
The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed.
Condenser Unit Unspecified General Event
One or more unspecified condenser unit events active. See local unit
display for further details.
Condenser VFD Issue - Event Control
Enable/disable the activation of the [Condenser VFD Issue] event. If
set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event
history list.
Condenser VFD Issue - Event Type
The event type for the [Condenser VFD Issue] event.
Condenser VFD Issue
The condenser fan Variable Frequency Drive is offline.
83
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-8
Liebert CRV™—Glossary (continued)
Data Label
Data Description
Cooling Capacity (Primary)
Compressor utilization or chilled water valve position, based on unit
type.
Cooling Proportional Band
Temperature control band above [Air Temperature Set Point]. If
measured air temperature is within this band, cooling operations are
proportionally controlled.
Customer Input 1 - Event Control
Enable/disable the activation of the [Customer Input 1] event. If set
to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Customer Input 1 - Event Type
The event type for the [Customer Input 1] event.
Customer Input 1
Customer Input 1.
Customer Input 2 - Event Control
Enable/disable the activation of the [Customer Input 2] event. If set
to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Customer Input 2 - Event Type
The event type for the [Customer Input 2] event.
Customer Input 2
Customer input 2.
Customer Input 3 - Event Control
Enable/disable the activation of the [Customer Input 3] event. If set
to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Customer Input 3 - Event Type
The event type for the [Customer Input 3] event.
Customer Input 3
Customer input 3.
Customer Input 4 - Event Control
Enable/disable the activation of the [Customer Input 4] event. If set
to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Customer Input 4 - Event Type
The event type for the [Customer Input 4] event.
Customer Input 4
Customer input 4.
Dehumidification Proportional Band
Humidity control band above [Humidity Set Point]. If measured
humidity is within this band, dehumidification operations are
proportionally controlled.
Dehumidifier Hours Exceeded
Operating hours for the dehumidifier have exceeded the threshold.
Dehumidifier Utilization
Present dehumidifier utilization expressed as a percentage of the
maximum rated capacity.
Dig Scroll Comp 1 Over Temp
Digital scroll compressor 1 shut off because its head temperature
has exceeded the upper threshold.
Dig Scroll Comp 1 Temp Sensor Issue
Digital scroll compressor 1 temperature sensor is disconnected or
the signal is out of range.
EEV Battery Issue
Electronic expansion valve battery cannot be recharged and needs
to be replaced.
EEV Discharge Temp Above Threshold
Electronic expansion valve refrigerant high discharge temperature
event.
EEV Open Position
Electronic expansion valve open position.
EEV Power Issue
Electronic expansion valve lost power and is running on battery
backup.
EEV Superheat Below Threshold
Electronic expansion valve refrigerant low superheat event.
EEV Unspecified General Event
One or more unspecified electronic expansion valve events active.
See local unit display for further details.
Electric Reheater 1 Hours Exceeded
Operating hours for electric reheater 1 have exceeded the threshold.
Electric Reheater Hours Exceeded
[Electric Reheater Hours] has exceeded [Electric Reheaters Hours
Threshold].
Energy Consumption
Energy consumption since the last reset of this value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
84
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-8
Liebert CRV™—Glossary (continued)
Data Label
Data Description
Expected Condenser Unit Count
Number of physical condenser units that are expected to be
connected to the system.
Ext Compressor Lockout - Event Control
Enable/disable the activation of the [Ext Compressor Lockout] event.
If set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event
history list.
Ext Compressor Lockout - Event Type
The event type for the [Ext Compressor Lockout] event.
Ext Compressor Lockout
The compressor is shut down and disabled by an external input
signal.
Ext Condenser Pump High Water
High water is detected in the condenser, as indicated by an external
input signal.
Ext Humidifier Lockout - Event Control
Enable/disable the activation of the [Ext Humidifier Lockout] event. If
set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event
history list.
Ext Humidifier Lockout - Event Type
The event type for the [Ext Humidifier Lockout] event.
Ext Humidifier Lockout
The humidifier is shut down and disabled by an external input signal.
Ext Loss of Flow - Event Control
Enable/disable the activation of the [Ext Loss of Flow] event. If set to
'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Ext Loss of Flow - Event Type
The event type for the [Ext Loss of Flow] event.
Ext Loss of Flow
Loss of flow is detected, as indicated by an external input signal.
Ext Over Temperature - Event Control
Enable/disable the activation of the [Ext Over Temperature] event. If
set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event
history list.
Ext Over Temperature - Event Type
The event type for the [Ext Over Temperature] event.
Ext Over Temperature
A temperature has exceeded its threshold, as indicated by an
external input signal.
Ext Reheat Lockout - Event Control
Enable/disable the activation of the [Ext Reheat Lockout] event. If set
to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Ext Reheat Lockout - Event Type
The event type for the [Ext Reheat Lockout] event.
Ext Reheat Lockout
The reheater is shut down and disabled by an external input signal.
Ext Standby Glycol Pump On
The standby glycol pump is on, as indicated by an external input
signal.
External Condenser TVSS Issue
The condenser Transient Voltage Surge Suppressor or Surge
Protection Device has failed, as indicated by an external input signal.
External Condenser VFD Issue
The condenser fan Variable Frequency Drive is offline, as indicated
by an external input signal.
External Fire Detected
Fire detected, as indicated by an external input signal.
Fan Control Mode
Fan control mode. Allowable modes are: (0) Auto - Fan speed is
controlled via the selected fan control sensor, and, (1) Manual - Fan
will operate at a fixed speed.
Fan Control Sensor
Sensor from which air temperature measurements will be used for
fan speed control.
Fan Hours Exceeded
Operating hours for the unit blower fan have exceeded the threshold.
Fan Speed Manual Set Point
Manual fan speed.
Fan Speed Maximum Set Point
Maximum fan speed.
Fan Speed Minimum Set Point
Minimum fan speed.
85
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-8
Liebert CRV™—Glossary (continued)
Data Label
Data Description
Fan Speed Proportional Band
Temperature control band above the temperature set point
calculated for proportional fan speed control. If measured air
temperature is within this band, fan speed operations are
proportionally controlled.
Fan Speed
Fan speed expressed as a percentage of the maximum rated speed.
Fluid Flow Sensor Issue
The fluid flow sensor is disconnected or the signal is out of range.
Fluid Temperature Sensor Issue
The fluid temperature sensor is disconnected or the signal is out of
range.
Heating Proportional Band
Temperature control band below [Air Temperature Set Point]. If
measured air temperature is within this band, heating operations are
proportionally controlled.
High Power Shutdown
Supply to high power components has been shutdown.
High Return Humidity Threshold
Threshold value used in the [High Return Humidity] event.
High Return Humidity
Return air high humidity event.
Humidification Proportional Band
Humidity control band below [Humidity Set Point]. If measured
humidity is within this band, humidification operations are
proportionally controlled.
Humidifier Control Board Not Detected
Humidifier control board is required to be connected, but no signal is
detected.
Humidifier Cylinder Worn
Humidifier cylinder is not operating properly and needs to be
replaced.
Humidifier Hours Exceeded
Operating hours for the humidifier have exceeded the threshold.
Humidifier Issue
Humidifier issue detected, causing it to be locked out.
Humidifier Low Water
The water level in the humidifier has dropped below its threshold.
Humidifier Over Current
The electrical current to the humidifier has exceeded its upper
threshold.
Humidifier Under Current
The electrical current to the humidifier has dropped below its lower
threshold.
Humidifier Utilization
Present humidifier utilization expressed as a percentage of the
maximum rated capacity.
Humidity Dead Band
Value that is divided evenly to form a range above and below
[Humidity Set Point]. If measured humidity is within this range, no
humidification or dehumidification will occur.
Humidity Set Point
Desired relative humidity.
Input Undervoltage
One or more of the input phase voltages has dropped below the limit.
Instantaneous Power
Total electrical power currently being consumed.
Local Cooling Override
The local unit override status for cooling capacity.
Local Dehumidifier Override
The local unit override status for the dehumidifier.
Local Electric Heat Override
The local unit override status for electric heat.
Local Fan Override
The local unit override status for fan speed.
Local Humidifier Override
The local unit override status for the humidifier.
Loss of Air Flow
No air flow through the unit due to failure of all fans.
Low Return Humidity Threshold
Threshold value used in the [Low Return Humidity] event.
Low Return Humidity
Return air low humidity event.
Maintenance Completed
Maintenance has been completed on the unit.
Maintenance Due
The calculated maintenance date has been reached.
Maintenance Ramp
The ratio of operations performed to the calculated operations
available between maintenance intervals.
Master Unit Communication Lost
Communication with master unit has been lost.
Modbus Power Meter Communication Lost
Communication with Modbus power meter has been lost.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
86
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-8
Liebert CRV™—Glossary (continued)
Data Label
Data Description
Operating Efficiency
The ratio of cooling energy provided to the amount of total energy
being used.
Power Source 'A' Issue
No power is detected at power source input 'A'.
Power Source B Failure
No power is detected at power source input B.
RAM Battery Issue
RAM or RAM backup battery is not operating correctly.
Raw Auxiliary Air Temperature
Air temperature value sent by an external auxiliary device, with no
additional filtering by the receiving system. This may be an
aggregated value from multiple sensors.
Reheat Utilization
Present reheating utilization expressed as a percentage of the
maximum rated capacity.
Reheater Over Temperature
The temperature of the reheater has exceeded its threshold.
Remote Sensor Average High Humidity
The average humidity of multiple remote sensors on the cooling unit
has exceeded an upper threshold. The event is deactivated when
the humidity drops below the threshold.
Remote Sensor Average Low Humidity
The average humidity of multiple remote sensors on the cooling unit
has dropped below a lower threshold. The event is deactivated
when the humidity rises above the threshold.
Remote Sensor Average Over Temperature
[Remote Sensor Average Temperature] has exceeded [Remote
Sensor Over Temp Threshold].
Remote Sensor Average Temperature
Average value of remote sensor temperature measurements.
Remote Sensor Average Under Temperature
[Remote Sensor Average Temperature] has dropped below [Remote
Sensor Under Temp Threshold].
Remote Sensor Function
Function assigned to remote sensor. Available values are: (0)
Control - sensor will be used in calculation of remote sensor
temperature that may be used for heating and cooling control, (1)
Reference - sensor will not be used in calculation of remote sensor
temperature, but is enabled, (2) Disable - sensor is disabled
Remote Sensor High Humidity
Remote sensor humidity has exceeded an upper threshold. The
event is deactivated when the humidity drops below the threshold.
Remote Sensor Issue
Remote sensor is disconnected or the signal is out of range.
Remote Sensor Low Humidity
Remote sensor humidity has dropped below a lower threshold. The
event is deactivated when the humidity rises above the threshold.
Remote Sensor Maximum Temperature
Maximum value of remote sensor temperature measurements.
Remote Sensor Minimum Temperature
Minimum value of remote sensor temperature measurements.
Remote Sensor Over Temp Threshold
Threshold value used in the remote air sensor over temperature
events.
Remote Sensor Over Temperature
[Remote Sensor Temperature] has exceeded [Remote Sensor Over
Temp Threshold].
Remote Sensor System Average High Humidity
The average humidity of multiple remote sensors on interconnected
cooling units in a single system has exceeded an upper threshold.
The event is deactivated when the humidity drops below the
threshold.
Remote Sensor System Average Low Humidity
The average humidity of multiple remote sensors on interconnected
cooling units in a single system has dropped below a lower
threshold. The event is deactivated when the humidity rises above
the threshold.
Remote Sensor System Average Over Temperature
[Remote Sensor System Average Temperature] has exceeded
[Remote Sensor Over Temp Threshold].
Remote Sensor System Average Temperature
Average value of remote sensor temperature measurements among
a group of interconnected units in a single system.
Remote Sensor System Average Under Temperature
Remote Sensor System Average Temperature] has dropped below
[Remote Sensor Under Temp Threshold].
Remote Sensor System Maximum Temperature
Maximum value of remote sensor temperature measurements
among a group of interconnected units in a single system.
87
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-8
Liebert CRV™—Glossary (continued)
Data Label
Data Description
Remote Sensor Temperature Calculation
Calculation method applied to temperature readings from the remote
sensors to determine a single temperature measurement value for
cooling and heating control.
Remote Sensor Temperature
Air temperature as measured by remote sensor.
Remote Sensor Under Temp Threshold
Threshold value used in the remote air sensor under temperature
events.
Remote Sensor Under Temperature
[Remote Sensor Temperature] has dropped below [Remote Sensor
Under Temp Threshold].
Return Air Over Temp Threshold
Threshold value used in the [Return Air Over Temperature] event.
Return Air Over Temperature
Return air high temperature event.
Return Air Sensor Issue
The air sensor at the inlet of the unit is disconnected or the signal is
out of range.
Return Air Temperature
The temperature of the inlet air
Return Dew Point
Dew point temperature measured at the inlet of the unit.
Return Humidity Out Of Proportional Band
[Return Humidity] has exceeded the upper limit of [Dehumidification
Proportional Band], or has dropped below the lower limit of
[Humidification Proportional Band] ], for an extended period of time.
Return Humidity
Relative humidity measured at the inlet of the unit.
SEC Communication Lost
Communication with the Superheat and Envelope Controller has
been lost. The event is deactivated when communication is reestablished.
SEC Unspecified General Event
One or more unspecified events active for the Superheat and
Envelope Controller. See local unit display for further details.
Server Class
The general classification for this system
Service Required - Event Control
Enable/disable the activation of the [Service Required] event. If set
to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Service Required - Event Type
The event type for the [Service Required] event.
Service Required
Unit requires servicing.
Shutdown - Loss Of Power - Event Control
Enable/disable the activation of the [Shutdown - Loss Of Power]
event. If set to 'disabled', the event will not be annunciated. This
implies that the event will not be placed in any active event list or in
any event history list.
Shutdown - Loss Of Power - Event Type
The event type for the [Shutdown - Loss Of Power] event.
Shutdown - Loss Of Power
System lost power. This event becomes active when the unit is
powered on following an unexpected loss of power. This event
remains active for 90 minutes.
Smoke Detected - Event Control
Enable/disable the activation of the [Smoke Detected] event. If set to
'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Smoke Detected - Event Type
The event type for the [Smoke Detected] event.
Smoke Detected
Smoke detected.
Static Pressure Sensor Issue
The static pressure sensor is disconnected or the signal is out of
range.
Static Pressure Sensor Out of Range
Static pressure sensor signal is out of its configured range.
Super Saver Call For Cooling
Call for cooling value used for Super Saver functionality. A higher
call for cooling value indicates a need for a lower coolant
temperature.
Supply Air Over Temp Threshold
Threshold value used in the [Supply Air Over Temperature] event.
Supply Air Over Temperature
Supply air high temperature event.
Supply Air Sensor Issue
The air sensor at the outlet of the unit is disconnected or the signal is
out of range.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
88
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-8
Liebert CRV™—Glossary (continued)
Data Label
Data Description
Supply Air Temperature
Air temperature measured at the outlet of the unit.
Supply Air Under Temp Threshold
Threshold value used in the [Supply Air Under Temperature] event.
Supply Air Under Temperature
Supply air low temperature event.
Supply Chilled Water Loss of Flow
Supply chilled water flow is too low.
Supply Chilled Water Over Temp Threshold
Threshold value used in the [Supply Chilled Water Over Temp]
event.
Supply Chilled Water Over Temp
[Supply Chilled Water Temperature] has exceeded [Supply Chilled
Water Over Temp Threshold].
Supply Chilled Water Temperature
Supply chilled water temperature.
Supply Fluid Temp Sensor Issue
The supply fluid temperature sensor is disconnected or the signal is
out of range.
Supply Humidity
Relative humidity at the outlet of the unit.
System Control Mode
System control mode.
System Date and Time
The system date and time
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System On/Off Control
Turn system functionality on or off.
System Operating State Reason
The reason the system is in the current operating state.
System Operating State
Current operating state of the system.
System Status
The operating status for the system
Top Fan Issue
The top fan is not operating within its normal parameters.
Unit Code Missing
Unit code has not been entered and saved.
Unit Off
Unit was turned off.
Unit On
Unit was turned on.
Unit Partial Shutdown
An event has occurred requiring some system components to be
shutdown and disabled.
Unit Shutdown
An event has occurred requiring the unit to be shutdown and
disabled to prevent damage to the system.
Unit Standby
Unit was placed in standby mode.
Unspecified General Event
One or more unspecified events active. See local unit display for
further details.
Water Leakage Detector Sensor Issue
The water leakage detector sensor is disconnected or the signal is
out of range.
Water Under Floor - Event Control
Enable/disable the activation of the [Water Under Floor] event. If set
to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history
list.
Water Under Floor - Event Type
The event type for the [Water Under Floor] event.
Water Under Floor
Water under the floor is detected.
89
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-9
Liebert HPC™ (Chiller) - Status and Coil
Status
Coil
Number of Bits
Notes
Compressor Not Stopping
10001
—
1
Active on Alarm
Compressor Superheat Over Threshold
10002
—
1
Active on Alarm
Data Label
Compressors
Compressor 1
Compressor Hours Exceeded
10012
—
1
Active on Alarm
Compressor High Head Pressure
10013
—
1
Active on Alarm
Compressor Low Suction Pressure
10014
—
1
Active on Alarm
Compressor Thermal Overload
10015
—
1
Active on Alarm
Compressor Low Oil Pressure
10016
—
1
Active on Alarm
Compressor Loss of Differential Pressure
10018
—
1
Active on Alarm
Compressor Capacity Reduced
10019
—
1
Active on Alarm
Compressor Capacity Normal
10020
—
1
Active on Alarm
Compressor Contactor Issue
10021
—
1
Active on Alarm
Compressor 2
Compressor Hours Exceeded
10029
—
1
Active on Alarm
Compressor High Head Pressure
10030
—
1
Active on Alarm
Compressor Low Suction Pressure
10031
—
1
Active on Alarm
Compressor Thermal Overload
10032
—
1
Active on Alarm
Compressor Low Suction Pressure
10033
—
1
Active on Alarm
Compressor Loss of Differential Pressure
10035
—
1
Active on Alarm
Compressor Capacity Reduced
10036
—
1
Active on Alarm
Compressor Capacity Normal
10037
—
1
Active on Alarm
Compressor Contactor Issue
10038
—
1
Active on Alarm
Compressor 4
Compressor Hours Exceeded
10230
—
1
Active on Alarm
Compressor High Head Pressure
10231
—
1
Active on Alarm
Compressor Low Suction Pressure
10232
—
1
Active on Alarm
Compressor Thermal Overload
10233
—
1
Active on Alarm
Compressor Low Suction Pressure
10234
—
1
Active on Alarm
Compressor Loss of Differential Pressure
10236
—
1
Active on Alarm
Compressor Capacity Reduced
10237
—
1
Active on Alarm
Compressor Capacity Normal
10238
—
1
Active on Alarm
Compressor Contactor Issue
10239
—
1
Active on Alarm
Condensers 1
Condenser Fan Issue
10046
—
1
Active on Alarm
Low Condenser Refrigerant Pressure
10047
—
1
Active on Alarm
Condenser Max Fan Speed Override
10048
—
1
Active on Alarm
Condensers 2
Condenser Fan Issue
10058
—
1
Active on Alarm
Low Condenser Refrigerant Pressure
10059
—
1
Active on Alarm
Condenser Max Fan Speed Override
10060
—
1
Active on Alarm
Condensers 4
Condenser Fan Issue
10066
1
Active on Alarm
Low Condenser Refrigerant Pressure
10067
1
Active on Alarm
Condenser Max Fan Speed Override
10068
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
90
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-9
Liebert HPC™ (Chiller) - Status and Coil (continued)
Data Label
Status
Coil
Number of Bits
Notes
10070
1
Active on Alarm
10081
1
Active on Alarm
Fluid
Low Fluid Pressure
Supply (Outlet) Fluid
Supply Fluid Over Temp
Supply Fluid Under Temp
10082
1
Active on Alarm
Supply Fluid Temp Sensor Issue
10083
1
Active on Alarm
10096
1
Active on Alarm
All Pumps Loss of Flow
10107
1
Active on Alarm
Pump 1 Loss of Flow
10108
1
Active on Alarm
Pump 2 Loss of Flow
10109
1
Active on Alarm
10120
1
Active on Alarm
10131
1
Active on Alarm
Free Cooling Valve Hours Exceeded
10142
1
Active on Alarm
Ambient Air Temperature Sensor Issue
10143
1
Active on Alarm
Evaporator Inlet Temp Sensor Issue
10154
1
Active on Alarm
Evaporator Return Fluid Over Temp
10155
1
Active on Alarm
Evaporator Return Fluid Under Temp
10156
1
Active on Alarm
Evaporator Fluid Freeze - Auto Reset
10165
1
Active on Alarm
Evaporator Fluid Freeze - Manual Reset Required
10166
1
Active on Alarm
Supply Refrigerant Temp Sensor Issue
10167
1
Active on Alarm
Evaporator Fluid Freeze - Auto Reset
10178
1
Active on Alarm
Evaporator Fluid Freeze - Manual Reset Required
10179
1
Active on Alarm
Supply Refrigerant Temp Sensor Issue
10180
1
Active on Alarm
Customer Input 1
10191
1
Active on Alarm
Customer Input 2
10192
1
Active on Alarm
Customer Input 3
10251
1
Active on Alarm
Customer Input 4
10252
1
Active on Alarm
Unit On
10193
1
Active on Alarm
Unit Off
10194
1
Active on Alarm
Return (Inlet) Fluid
Return Fluid Temp Sensor Issue
Pumps
Pump 1
Pump Hours Exceeded
Pump 2
Pump Hours Exceeded
Free Cooling
Evaporators
Evaporator 1
Evaporator 2
System Events
Master Unit Communication Lost
10195
1
Active on Alarm
Subgroup Event Occurred During Communication Loss
10196
1
Active on Alarm
Humidifier Control Board Not Detected
10197
1
Active on Alarm
RAM Battery Issue
10198
1
Active on Alarm
Unit Code Missing
10199
1
Active on Alarm
Unspecified General Event
10200
1
Active on Alarm
Unit Shutdown Unspecified General Event
10250
1
Active on Alarm
91
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-9
Liebert HPC™ (Chiller) - Status and Coil (continued)
Data Label
Status
Coil
Number of Bits
Notes
10270
1
Active on Alarm
10280
1
Active on Alarm
10300
1
Active on Alarm
10311
1
Active on Alarm
10322
1
Active on Alarm
EEV 1
EEV Unspecified General Event
EEV 2
EEV Unspecified General Event
EEV 4
EEV Unspecified General Event
Power Measurement 1
Modbus Power Meter Communication Lost
Power Measurement 2
Modbus Power Meter Communication Lost
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
92
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-10 Liebert HPC™ (Chiller)—Input and Holding
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Protocol
Server Class
30385
1
1 = UPS
2 = AIR
3 = PMP
4 = PDU
5 = MONITOR
Compressors
Compressor Shut Down - Ambient Air Low Temp Limit
30389
40389
1
Units : deg C
Int16
Compressor Shut Down - Ambient Air Low Temp Limit
30390
40390
1
Units : deg F
Int16
Compressor 1
Compressor State
30394
1
0 = off
1 = on
Compressor Capacity Control State
30395
1
0 = off
1 = on
Compressor Head Pressure
30396
1
Compressor Hours
30397
40397
1
Units : hr
Uint16
Compressor Hours Threshold
30398
40398
1
Units : hr
Uint16
10
Units : bar
Uint16
Compressor 2
Compressor State
30402
1
0 = off
1 = on
Compressor Capacity Control State
30403
1
0 = off
1 = on
Compressor Head Pressure
30404
1
Compressor Hours
30405
40405
1
Units : hr
Uint16
Compressor Hours Threshold
30406
40406
1
Units : hr
Uint16
10
Units : bar
Uint16
Compressor 4
Compressor State
30550
1
0 = off
1 = on
Compressor Capacity Control State
30551
1
0 = off
1 = on
Compressor Head Pressure
30552
1
Compressor Hours
30553
40553
1
Units : hr
Uint16
Compressor Hours Threshold
30554
40554
1
Units : hr
Uint16
30410
1
Units : %
Uint16
30414
1
Units : %
Uint16
10
Units : bar
Uint16
Condensers 1
Condenser Fan Speed
Condensers 2
Condenser Fan Speed
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
93
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-10 Liebert HPC™ (Chiller)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Condensers 4
Condenser Fan Speed
Units : %
Uint16
30417
1
Fluid Pressure
30418
1
10
Units : bar
Int16
Fluid Cooling Proportional Band
30419
40419
1
10
Units : deg C
Uint16
Fluid Cooling Proportional Band
30420
40420
1
10
Units : deg F
Uint16
Supply Fluid Temp Set Point 1
30424
40424
1
10
Units : deg C
Int16
Supply Fluid Temp Set Point 1
30425
40425
1
10
Units : deg F
Int16
Supply Fluid Temp Set Point 2
30426
40426
1
Units : deg C
Int16
Supply Fluid Temp Set Point 2
30427
40427
1
Units : deg F
Int16
Supply Fluid Over Temp Alarm Threshold
30430
40430
1
Units : deg C
Int16
Supply Fluid Over Temp Alarm Threshold
30431
40431
1
Units : deg F
Int16
Supply Fluid Under Temp Alarm Threshold
30434
40434
1
Units : deg C
Int16
Supply Fluid Under Temp Alarm Threshold
30435
40435
1
Units : deg F
Int16
Pump Hours
30450
40450
1
Units : hr
Uint16
Pump Hours Threshold
30451
40451
1
Units : hr
Uint16
Pump Hours
30455
40455
1
Units : hr
Uint16
Pump Hours Threshold
30456
40456
1
Units : hr
Uint16
Free Cooling External Temperature Delta
30460
40460
1
Units : deg C
Uint16
Free Cooling External Temperature Delta
30461
40461
1
Units : deg F
Uint16
Free Cooling Status
30462
1
0 = off
2 = on
3 = No Support
Free Cooling Valve Open Position
30463
1
Units : %
Uint16
Free Cooling Valve Hours
30464
40464
1
Units : hr
Uint16
Free Cooling Valve Hours Threshold
30465
40465
1
Units : hr
Uint16
Fluid
Supply (Outlet) Fluid
Pump 1
Pump 2
Free Cooling
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
94
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-10 Liebert HPC™ (Chiller)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Evaporators
Evaporator Return Fluid Temperature
30469
1
10
Units : deg C
Int16
Evaporator Return Fluid Temperature
30470
1
10
Units : deg F
Int16
Evaporator Return Fluid Over Temp Alarm Threshold
30615
40615
1
Units : deg C
Int16
Evaporator Return Fluid Over Temp Alarm Threshold
30616
40616
1
Units : deg F
Int16
Evaporator Return Fluid Over Temp Warning Threshold 30617
40617
1
Units : deg C
Int16
Evaporator Return Fluid Over Temp Warning Threshold 30618
40618
1
Units : deg F
Int16
Evaporator Return Fluid Under Temp Warning
Threshold
30619
40619
1
Units : deg C
Int16
Evaporator Return Fluid Under Temp Warning
Threshold
30620
40620
1
Units : deg F
Int16
Evaporator Return Fluid Under Temp Alarm Threshold
30621
40621
1
Units : deg C
Int16
Supply Brine Temp Set Point
30474
40474
1
Units : deg C
Int16
Supply Brine Temp Set Point
30475
40475
1
Units : deg F
Int16
30479
40479
1
Uint16
Brine
Standby Units
Standby Units
System Info
System Status
30483
1
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Operating State
30484
1
0 = off
1 = on
2 = standby
System Control Mode
30485
1
0 = Internal (Auto)
1 = External (Manual)
1
0 = Reason Unknown
1 = Network Display
2 = Alarm
3 = Schedule
4 = Remote System
5 = External Input
6 = Local Display
1
0 = off
1 = on
System Operating State Reason
30486
System On/Off Control
30487
40487
System Operations
Return Fluid Temperature
30491
1
10
Units : deg C
Int16
Return Fluid Temperature
30492
1
10
Units : deg F
Int16
Supply Fluid Temperature
30493
1
10
Units : deg C
Int16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
95
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-10 Liebert HPC™ (Chiller)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Supply Fluid Temperature
30494
—
1
10
Units : deg F
Int16
Actual Supply Fluid Temp Set Point
30495
—
1
10
Units : deg C
Int16
Actual Supply Fluid Temp Set Point
30496
—
1
10
Units : deg F
Int16
Condenser Inlet Water Temperature
30497
—
1
10
Units : deg C
Int16
Condenser Inlet Water Temperature
30498
—
1
10
Units : deg F
Int16
Condenser Outlet Water Temperature
30499
—
1
10
Units : deg C
Int16
Condenser Outlet Water Temperature
30500
—
1
10
Units : deg F
Int16
Supply Heated Water Temp Set Point
30501
40501
1
—
Units : deg C
Int16
Supply Heated Water Temp Set Point
30502
40502
1
—
Units : deg F
Int16
Free Cooling Utilization
30503
—
1
—
Units : %
Uint16
Reheat Utilization
30504
—
1
—
Units : %
Uint16
Compressor Utilization
30505
—
1
—
Units : %
Uint16
Ambient Air Temperature
30506
—
1
10
Units : deg C
Int16
Ambient Air Temperature
30507
—
1
10
Units : deg F
Int16
Compressor Economizer Utilization
30508
—
1
—
Units : %
Uint16
Condenser Adiabatic Cooling Utilization
30509
—
1
—
Units : %
Uint16
Pump 1 State
30510
—
1
—
0 = off
1 = on
Pump 2 State
30511
—
1
—
0 = off
1 = on
40515
1
—
2 = Reset
4 = Acknowledge
System Events
System Event Acknowledge/Reset
Power Measurement 1
System Input RMS A-B
30707
—
1
—
Units : VAC
Int16
System Input RMS A-N
30708
—
1
—
Units : VAC
Int16
System Input RMS Current Phase A
30709
—
1
—
Units : A AC
Int16
System Input RMS B-C
30710
—
1
—
Units : VAC
Int16
System Input RMS B-N
30711
—
1
—
Units : VAC
Int16
System Input RMS Current Phase B
30712
—
1
—
Units : A AC
Int16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
96
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-10 Liebert HPC™ (Chiller)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Input RMS C-A
30713
—
1
—
Units : VAC
Int16
System Input RMS C-N
30714
—
1
—
Units : VAC
Int16
System Input RMS Current Phase C
30715
—
1
—
Units : A AC
Int16
Energy Consumption
30716
—
2
—
Units : kWH
Int32
Instantaneous Power
30718
—
2
—
Units : W
Int32
Output Power Factor
30720
—
1
—
Int16
System Input RMS A-B
30731
—
1
—
Units : VAC
Int16
System Input RMS A-N
30732
—
1
—
Units : VAC
Int16
System Input RMS Current Phase A
30733
—
1
—
Units : A AC
Int16
System Input RMS B-C
30734
—
1
—
Units : VAC
Int16
System Input RMS B-N
30735
—
1
—
Units : VAC
Int16
System Input RMS Current Phase B
30736
—
1
—
Units : A AC
Int16
System Input RMS C-A
30737
—
1
—
Units : VAC
Int16
System Input RMS C-N
30738
—
1
—
Units : VAC
Int16
System Input RMS Current Phase C
30739
—
1
—
Units : A AC
Int16
Energy Consumption
30740
—
2
—
Units : kWH
Int32
Instantaneous Power
30742
—
2
—
Units : W
Int32
Output Power Factor
30744
—
1
—
Int16
39998
49998
2
—
Secs since Epoch(UTC)
Power Measurement 2
Time
System Date and Time
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 3-11 Extra notes key to Table 3-10
Number
Description
1
This point is supported on iCOM Controller Version 2.02.xxx
2
This point is supported on iCOM Controller Version 2.03.xxx
97
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-12 Liebert HPC™ (Chiller)—Glossary
Data Label
Data Description
Actual Supply Fluid Temp Set Point
The actual set point value being used for the desired fluid
temperature at the outlet of the unit.
All Pumps Loss of Flow
System is shut down due to loss of flow in all available pumps.
Ambient Air Temperature Sensor Issue
The ambient air temperature sensor is disconnected or the signal
is out of range.
Ambient Air Temperature
Ambient air temperature.
Compressor Capacity Control State
Compressor capacity control state. When 'ON', the cooling
capacity of the compressor has been reduced.
Compressor Capacity Normal
Compressor has returned to normal load capacity.
Compressor Capacity Reduced
Compressor capacity has been reduced.
Compressor Contactor Issue
Compressor contactor is not closing during compressor startup or
is not opening during compressor shutdown.
Compressor Economizer Utilization
Present compressor economizer utilization expressed as a
percentage of the maximum.
Compressor Head Pressure
Compressor head pressure.
Compressor High Head Pressure
Compressor is shut down due to high head pressure.
Compressor Hours Exceeded
[Compressor Hours] has exceeded [Compressor Hours
Threshold].
Compressor Hours Threshold
Threshold value used in the [Compressor Hours Exceeded] event.
Compressor Hours
Operating hours for compressor since last reset of this value.
Compressor Loss of Differential Pressure
Compressor is shut down due to low differential pressure.
Compressor Low Oil Pressure
Compressor low oil pressure.
Compressor Low Suction Pressure
Compressor is shut down due to low suction pressure.
Compressor Not Stopping
Compressor commanded to stop, but continues to run.
Compressor Shut Down - Ambient Air Low Temp Limit
When the temperature of ambient air falls below this lower
threshold, the compressor will be shut off. Correct condensing
pressure cannot be achieved when temperature is too low.
Compressor State
Compressor operational state.
Compressor Superheat Over Threshold
Compressor discharge refrigerant superheat temperature has
exceeded an upper threshold.
Compressor Thermal Overload
Compressor is shut down due to thermal overload.
Compressor Utilization
Present compressor utilization expressed as a percentage of the
maximum rated capacity.
Condenser Adiabatic Cooling Utilization
Present adiabatic cooling utilization expressed as a percentage of
the maximum.
Condenser Fan Issue
Condenser fan is not operating within its operational parameters.
Condenser Fan Speed
Condenser fan speed expressed as a percentage of the maximum
rated speed.
Condenser Inlet Water Temperature
For water cooled condensers, the temperature of the water
entering the heat exchanger, before cooling the refrigerant.
Condenser Max Fan Speed Override
Fan speed exceeding the maximum set point in order to alleviate
a high temperature or pressure condition.
Condenser Outlet Water Temperature
For water cooled condensers, the temperature of the water exiting
the heat exchanger, after cooling the refrigerant.
Customer Input 1
Customer input 1.
Customer Input 2
Customer input 2.
Customer Input 3
Customer input 3.
Customer Input 4
Customer input 4.
EEV Unspecified General Event
One or more unspecified electronic expansion valve events
active. See local unit display for further details.
Energy Consumption
Energy consumption since the last reset of this value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
98
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-12 Liebert HPC™ (Chiller)—Glossary (continued)
Data Label
Data Description
Evaporator Fluid Freeze - Auto Reset
Evaporator outlet fluid temperature has dropped below the freeze
threshold. Evaporator has been shut down, but will restart when
the temperature rises above the threshold.
Evaporator Fluid Freeze - Manual Reset Required
Evaporator outlet fluid temperature has dropped below the freeze
threshold. Evaporator has been shut down and requires a manual
reset.
Evaporator Inlet Temp Sensor Issue
The evaporator inlet temperature sensor is disconnected or the
signal is out of range.
Evaporator Return Fluid Over Temp Alarm Threshold
Alarm threshold value used in the [Evaporator Return Fluid Over
Temp] event.
Evaporator Return Fluid Over Temp Warning Threshold
Warning threshold value used in the [Evaporator Return Fluid
Over Temp] event.
Evaporator Return Fluid Over Temp
[Evaporator Return Fluid Temperature] has exceeded a threshold.
The event is deactivated when the temperature drops below the
threshold.
Evaporator Return Fluid Temperature
Fluid temperature measured at the inlet of the evaporator.
Evaporator Return Fluid Under Temp Alarm Threshold
Alarm threshold value used in the [Evaporator Return Fluid Under
Temp] event.
Evaporator Return Fluid Under Temp Warning Threshold
Warning threshold value used in the [Evaporator Return Fluid
Under Temp] event.
Evaporator Return Fluid Under Temp
[Evaporator Return Fluid Temperature] has dropped below a
threshold. The event is deactivated when the temperature rises
above the threshold.
Fluid Cooling Proportional Band
Temperature control band above [Actual Supply Fluid Temp Set
Point]. If [Return Fluid Temperature] is within this band, fluid
cooling operations are proportionally controlled.
Fluid Pressure
Fluid pressure. This is the pressure within a closed water/glycol
circuit.
Free Cooling External Temperature Delta
Minimum temperature delta required between return fluid and
external ambient air temperatures in order to enable free cooling.
Free Cooling Status
Free cooling status.
Free Cooling Utilization
Present free cooling utilization expressed as a percentage of the
maximum.
Free Cooling Valve Hours Exceeded
[Free Cooling Valve Hours] has exceeded [Free Cooling Valve
Hours Threshold].
Free Cooling Valve Hours Threshold
Threshold value used in the [Free Cooling Valve Hours Exceeded]
event.
Free Cooling Valve Hours
Operating hours for free cooling valve since last reset of this
value.
Free Cooling Valve Open Position
Free cooling valve open position.
Humidifier Control Board Not Detected
Humidifier control board is required to be connected, but no signal
is detected.
Instantaneous Power
Total electrical power currently being consumed.
Low Condenser Refrigerant Pressure
Refrigerant pressure in condenser coil is too low.
Low Fluid Pressure
[Fluid Pressure] has dropped below a specified threshold.
Master Unit Communication Lost
Communication with master unit has been lost.
Modbus Power Meter Communication Lost
Communication with Modbus power meter has been lost.
Output Power Factor
Total power factor, real power/apparent power for all phases
combined
Pump 1 Loss of Flow
Loss of flow is detected in pump 1. This condition occurs when no
flow is detected through the flow switch.
Pump 1 State
Pump 1 operational state.
Pump 2 Loss of Flow
Loss of flow is detected in pump 2. This condition occurs when no
flow is detected through the flow switch.
99
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-12 Liebert HPC™ (Chiller)—Glossary (continued)
Data Label
Data Description
Pump 2 State
Pump 2 operational state.
Pump Hours Exceeded
[Pump Hours] has exceeded [Pump Hours Threshold].
Pump Hours Threshold
Threshold value used in the [Pump Hours Exceeded] event.
Pump Hours
Operating hours for pump since last reset of this value.
RAM Battery Issue
RAM or RAM backup battery is not operating correctly.
Reheat Utilization
Present reheating utilization expressed as a percentage of the
maximum rated capacity.
Return Fluid Temp Sensor Issue
The return fluid temperature sensor is disconnected or the signal
is out of range.
Return Fluid Temperature
Fluid temperature measured at the inlet of the unit.
Server Class
The general classification for this system
Standby Units
The number of standby units.
Subgroup Event Occurred During Communication Loss
While subgroup unit communication was lost, an event occurred
on the subgroup unit. Please check subgroup unit event log.
Supply Brine Temp Set Point
Desired brine fluid temperature at the outlet of the unit.
Supply Fluid Over Temp Alarm Threshold
Threshold value used to generate a [Supply Fluid Over Temp]
alarm.
Supply Fluid Over Temp
[Supply Fluid Temperature] has exceeded a specified threshold.
Supply Fluid Temp Sensor Issue
The supply fluid temperature sensor is disconnected or the signal
is out of range.
Supply Fluid Temp Set Point 1
Set point 1 of desired fluid temperature at the outlet of the unit.
Supply Fluid Temp Set Point 2
Set point 2 of desired fluid temperature at the outlet of the unit.
Supply Fluid Temperature
Fluid temperature measured at the outlet of the unit.
Supply Fluid Under Temp Alarm Threshold
Threshold value used to generate a [Supply Fluid Under Temp]
alarm.
Supply Fluid Under Temp
[Supply Fluid Temperature] has dropped below a specified
threshold.
Supply Heated Water Temp Set Point
Desired heated water temperature at the outlet of the unit.
Supply Refrigerant Temp Sensor Issue
The supply refrigeramt temperature sensor is disconnected or the
signal is out of range.
System Control Mode
System control mode.
System Date and Time
The system date and time
System Event Acknowledge/Reset
Reset and/or acknowledge all events.
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System On/Off Control
Turn system functionality on or off.
System Operating State Reason
The reason the system is in the current operating state.
System Operating State
Current operating state of the system.
System Status
The operating status for the system
Unit Code Missing
Unit code has not been entered and saved.
Unit Off
Unit was turned off.
Unit On
Unit was turned on.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
100
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-12 Liebert HPC™ (Chiller)—Glossary (continued)
Data Label
Data Description
Unit Shutdown Unspecified General Event
One or more unspecified unit shutdown events active. See local
unit display for further details.
Unspecified General Event
One or more unspecified events active. See local unit display for
further details.
101
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-13 Liebert XDC™—Status and Coil
Controller Liebert iCOM® v4
Status
Coil
Number
of Bits
Scale
Notes / Units
Pump 1 Loss of Flow
10001
—
1
—
Active on Alarm
Pump 2 Loss of Flow
10002
—
1
—
Active on Alarm
Data Description
Fan Issue
10003
—
1
—
Active on Alarm
System Condensation Detected
10004
—
1
—
Active on Alarm
Customer Input 1
10005
—
1
—
Active on Alarm
Supply Refrigerant Over Temp
10006
—
1
—
Active on Alarm
Supply Refrigerant Under Temp
10007
—
1
—
Active on Alarm
Supply Refrigerant Temp Sensor Issue
10008
—
1
—
Active on Alarm
Ext Air Sensor A Over Temperature
10009
—
1
—
Active on Alarm
Ext Air Sensor A Under Temperature
10010
—
1
—
Active on Alarm
Ext Air Sensor A Issue
10011
—
1
—
Active on Alarm
Ext Air Sensor B Over Temperature
10012
—
1
—
Active on Alarm
Ext Air Sensor B Under Temperature
10013
—
1
—
Active on Alarm
Ext Air Sensor B Issue
10014
—
1
—
Active on Alarm
Ext Dew Point Over Temperature
10015
—
1
—
Active on Alarm
Pump Short Cycle
10016
—
1
—
Active on Alarm
Compressor 1A High Head Pressure
10017
—
1
—
Active on Alarm
Compressor 1B High Head Pressure
10018
—
1
—
Active on Alarm
Compressor 2A High Head Pressure
10019
—
1
—
Active on Alarm
Compressor 2B High Head Pressure
10020
—
1
—
Active on Alarm
Compressor 1A Short Cycle
10021
—
1
—
Active on Alarm
Compressor 1B Short Cycle
10022
—
1
—
Active on Alarm
Compressor 2A Short Cycle
10023
—
1
—
Active on Alarm
Compressor 2B Short Cycle
10024
—
1
—
Active on Alarm
Circuit 1 Low Suction Pressure
10025
—
1
—
Active on Alarm
Circuit 2 Low Suction Pressure
10026
—
1
—
Active on Alarm
Shutdown - Loss Of Power
10027
—
1
—
Active on Alarm
Smoke Detected
10028
—
1
—
Active on Alarm
Water Under Floor
10029
—
1
—
Active on Alarm
Service Required
10030
—
1
—
Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
102
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-14 Liebert XDC™—Input and Holding
Controller Liebert iCOM® v4
Input
Register
Holding
Register
# of
Reg.
Scale
Pump 1 State
30385
—
1
—
0 = Off / 1 = On
Pump 2 State
30386
—
1
—
0 = Off / 1 = On
Supply Refrigerant Temperature
30387
—
1
10
deg C
Supply Refrigerant Temperature
30388
—
1
10
deg F
System Operating State
30389
—
1
—
Ext Air Sensor A Temperature
30390
—
1
10
deg C
Ext Air Sensor A Temperature
30391
—
1
10
deg F
Ext Air Sensor A Humidity
30392
—
1
10
% RH
Ext Air Sensor A Dew Point Temp
30393
—
1
10
deg C
Ext Air Sensor A Dew Point Temp
30394
—
1
10
deg F
Ext Air Sensor B Temperature
30395
—
1
10
deg C
Ext Air Sensor B Temperature
30396
—
1
10
deg F
Ext Air Sensor B Humidity
30397
—
1
10
% RH
Ext Air Sensor B Dew Point Temp
30398
—
1
10
deg C
Ext Air Sensor B Dew Point Temp
30399
—
1
10
deg F
Dew Point Temperature
30400
—
1
10
deg C
Dew Point Temperature
30401
—
1
10
deg F
Minimum Room Temperature Set Point
30402
40402
1
—
deg C
Minimum Room Temperature Set Point
30403
40403
1
—
deg F
Ext Air Over Temp Threshold
30404
40404
1
—
deg C
Ext Air Over Temp Threshold
30405
40405
1
—
deg F
Ext Air Under Temp Threshold
30406
40406
1
—
deg C
Ext Air Under Temp Threshold
30407
40407
1
—
deg F
Ext Dew Point Over Temp Threshold
30408
40408
1
—
deg C
Ext Dew Point Over Temp Threshold
30409
40409
1
—
deg F
Supply Refrig Over Temp Threshold
30410
40410
1
—
deg C
Supply Refrig Over Temp Threshold
30411
40411
1
—
deg F
Hot Gas Valve 1 Open Position
30412
—
1
100
%
Hot Gas Valve 2 Open Position
30413
—
1
100
%
Hot Gas Solenoid Valve 1 Position
30414
—
1
—
0 = Closed
1 = Open
Hot Gas Solenoid Valve 2 Position
30415
—
1
—
0 = Closed
1 = Open
Data Description
Notes / Units
0 = Off / 1 = On
2 = Standby
Compressor 1A State
30416
—
1
—
0 = Off / 1 = On
Compressor 1B State
30417
—
1
—
0 = Off / 1 = On
Compressor 2A State
30418
—
1
—
0 = Off / 1 = On
Compressor 2B State
30419
—
1
—
0 = Off / 1 = On
Calculated Next Maintenance Month
30420
—
1
—
—
Calculated Next Maintenance Year
30421
—
1
—
—
System Status
30422
—
1
—
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
103
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-14 Liebert XDC™—Input and Holding (continued)
Controller Liebert iCOM® v4
Data Description
System Control Mode
Input
Register
Holding
Register
# of
Reg.
Scale
30423
—
1
—
Notes / Units
0 = Internal (Auto)
1 = External (Manual)
Maintenance Ramp
30424
—
1
—
%
Auto Restart Delay
30425
40425
1
—
sec
System On/Off Control
30426
40426
1
—
0 = Off / 1 = On
—
40427
1
—
2 = Reset
4 = Acknowledge
System Event Acknowledge/Reset
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
104
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-15 Liebert XDP™—Status and Coil
Controller Liebert iCOM® v4
Status
Coil
Number of Bits
Notes
Pump 1 Loss of Flow
10001
—
1
Active on Alarm
Pump 2 Loss of Flow
10002
—
1
Active on Alarm
Pump Short Cycle
10020
—
1
Active on Alarm
Data Label
Pumps
System Events
Fan Issue
10003
—
1
Active on Alarm
System Condensation Detected
10004
—
1
Active on Alarm
Customer Input 1
10005
—
1
Active on Alarm
Shutdown - Loss Of Power
10019
—
1
Active on Alarm
Water Under Floor
10021
—
1
Active on Alarm
Smoke Detected
10022
—
1
Active on Alarm
Service Required
10023
—
1
Active on Alarm
Unit Communication Lost
10262
—
1
Active on Alarm
RAM Battery Issue
10263
—
1
Active on Alarm
Master Unit Communication Lost
10264
—
1
Active on Alarm
Remote Shutdown
10265
—
1
Active on Alarm
Unit Code Missing
10266
—
1
Active on Alarm
Supply Chilled Water Over Temp
10006
—
1
Active on Alarm
Supply Chilled Water Temp Sensor Issue
10007
—
1
Active on Alarm
Chilled Water Control Valve Position
10018
—
1
Active on Alarm
10008
—
1
Active on Alarm
Chilled Water
Refrigerant
Supply Refrigerant Over Temp
Supply Refrigerant Under Temp
10009
—
1
Active on Alarm
Supply Refrigerant Temp Sensor Issue
10010
—
1
Active on Alarm
Ext Air Sensor A Over Temperature
10011
—
1
Active on Alarm
Ext Air Sensor A Under Temperature
10012
—
1
Active on Alarm
Ext Air Sensor A Issue
10013
—
1
Active on Alarm
Ext Air Sensor B Over Temperature
10014
—
1
Active on Alarm
Ext Air Sensor B Under Temperature
10015
—
1
Active on Alarm
External Air
Ext Air Sensor B Issue
10016
—
1
Active on Alarm
Ext Dew Point Over Temperature
10017
—
1
Active on Alarm
10030
—
1
Active on Alarm
10036
—
1
Active on Alarm
10042
—
1
Active on Alarm
Pump Hours 1
Pump Hours Exceeded
Pump Hours 2
Pump Hours Exceeded
XD System 1
Ext System Condensation Detected
—
Ext Fan Issue
10043
—
1
Active on Alarm
Sensor Issue
10044
—
1
Active on Alarm
Ext Remote Shutdown
10045
—
1
Active on Alarm
Hot Aisle Temp Out of Range
10046
—
1
Active on Alarm
Cold Aisle Temp Out of Range
10047
—
1
Active on Alarm
105
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-15 Liebert XDP™—Status and Coil (continued)
Controller Liebert iCOM® v4
Status
Coil
Number of Bits
Notes
Ext System Condensation Detected
10053
—
1
Active on Alarm
Ext Fan Issue
10054
—
1
Active on Alarm
Data Label
XD System 2
Sensor Issue
10055
—
1
Active on Alarm
Ext Remote Shutdown
10056
—
1
Active on Alarm
Hot Aisle Temp Out of Range
10057
—
1
Active on Alarm
Cold Aisle Temp Out of Range
10058
—
1
Active on Alarm
10251
—
1
Active on Alarm
XD System 20
Ext System Condensation Detected
Ext Fan Issue
10252
—
1
Active on Alarm
Sensor Issue
10253
—
1
Active on Alarm
Ext Remote Shutdown
10254
—
1
Active on Alarm
Hot Aisle Temp Out of Range
10255
—
1
Active on Alarm
Cold Aisle Temp Out of Range
10256
—
1
Active on Alarm
Messages
Unit On
10272
—
1
Active on Alarm
Unit Off
10273
—
1
Active on Alarm
Unit Standby
10274
—
1
Active on Alarm
Unit Partial Shutdown
10275
—
1
Active on Alarm
Unit Shutdown
10276
—
1
Active on Alarm
Maintenance Due
10277
—
1
Active on Alarm
Maintenance Completed
10278
—
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
106
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding
Controller Liebert iCOM® v4
Input
Holding
Pump 1 State
30385
—
1
—
0 = off
1 = on
Pump 2 State
30386
—
1
—
0 = off
1 = on
Supply Refrigerant Temperature
30387
—
1
10
Units : deg C
Supply Refrigerant Temperature
30388
—
1
10
Units : deg F
Supply Refrig Over Temp Threshold
30411
40411
1
10
Units : deg C
Supply Refrig Over Temp Threshold
30412
40412
1
10
Units : deg F
Supply Chilled Water Temperature
30389
—
1
10
Units : deg C
Supply Chilled Water Temperature
30390
—
1
10
Units : deg F
Supply Chilled Water Over Temp Threshold
30413
40413
1
10
Units : deg C
Supply Chilled Water Over Temp Threshold
30414
40414
1
10
Units : deg F
Chilled Water Valve Open Position
31710
—
1
—
—
Data Label
# of Reg Scale
Notes/Units
Pumps
Refrigerant
Chilled Water
System Information
System Status
30391
—
1
—
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Operating State
30392
—
1
—
0 = off
1 = on
2 = standby
Auto Restart Delay
30417
40417
1
—
Units : sec
System Control Mode
30418
—
1
—
0 = Internal (Auto)
1 = External (Manual)
Maintenance Ramp
30419
—
1
—
Units : %
Calculated Next Maintenance Month
30420
—
1
—
Calculated Next Maintenance Year
30421
—
1
—
System On/Off Control
30422
40422
1
—
0 = off
1 = on
31704
—
1
—
0 = Reason Unknown
1 = Network Display
2 = Alarm
3 = Schedule
4 = Remote System
5 = External Input
6 = Local Display
Ext Air Sensor A Temperature
30393
—
1
10
Units : deg C
Ext Air Sensor A Temperature
30394
—
1
10
Units : deg F
Ext Air Sensor A Humidity
30395
—
1
10
Units : % RH
Ext Air Sensor A Dew Point Temp
30396
—
1
10
Units : deg C
System Operating State Reason
External Air
Ext Air Sensor A Dew Point Temp
30397
—
1
10
Units : deg F
Ext Air Sensor B Temperature
30398
—
1
10
Units : deg C
Ext Air Sensor B Temperature
30399
—
1
10
Units : deg F
Ext Air Sensor B Humidity
30400
—
1
10
Units : % RH
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
107
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Data Label
Input
Holding
Ext Air Sensor B Dew Point Temp
30401
—
# of Reg Scale
1
10
Notes/Units
Units : deg C
Ext Air Sensor B Dew Point Temp
30402
—
1
10
Units : deg F
Minimum Room Temperature Set Point
30403
40403
1
10
Units : deg C
Minimum Room Temperature Set Point
30404
40404
1
10
Units : deg F
Ext Air Over Temp Threshold
30405
40405
1
10
Units : deg C
Ext Air Over Temp Threshold
30406
40406
1
10
Units : deg F
Ext Air Under Temp Threshold
30407
40407
1
10
Units : deg C
Ext Air Under Temp Threshold
30408
40408
1
10
Units : deg F
Ext Dew Point Over Temp Threshold
30409
40409
1
10
Units : deg C
Ext Dew Point Over Temp Threshold
30410
40410
1
10
Units : deg F
Dew Point Temperature
30415
—
1
10
Units : deg C
Dew Point Temperature
30416
—
1
10
Units : deg F
39998
49998
2
—
Secs since Epoch (UTC)
Time
System Date and Time
Pump Hours 1
Pump Hours
30430
40430
1
—
Units : hr
Pump Hours Threshold
30431
40431
1
—
Units : hr
Pump Hours
30437
40437
1
—
Units : hr
Pump Hours Threshold
30438
40438
1
—
Units : hr
Communication Status
30444
—
1
—
0 = Connected
1 = Not Connected
Fan On/Off Control
30445
40445
1
—
0 = off
1 = on
Primary Fan Group State
30446
—
1
—
0 = off
1 = on
2 = economy
Fan Button Control
30447
40447
1
—
0 = enabled
1 = disabled
Visual ID Control
30448
40448
1
—
0 = disabled
1 = enabled
Cooling Capacity
30449
—
1
—
Units : %
Cooling Capacity
30450
—
1
—
Units : kW
Pump Hours 2
XD System 1
Ext System Condensation Detected - Event Control
30451
40451
1
—
0 = disabled
1 = enabled
Ext System Condensation Detected - Event Type
30452
40452
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Fan Issue - Event Control
30453
40453
1
—
0 = disabled
1 = enabled
Ext Fan Issue - Event Type
30454
40454
1
—
0 = Message
1 = Warning
2 = Alarm
Sensor Issue - Event Control
30455
40455
1
—
0 = disabled
1 = enabled
Sensor Issue - Event Type
30456
40456
1
—
0 = Message
1 = Warning
2 = Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
108
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Data Label
Input
Holding
# of Reg Scale
Notes/Units
Ext Remote Shutdown - Event Control
30457
40457
1
—
0 = disabled
1 = enabled
Ext Remote Shutdown - Event Type
30458
40458
1
—
0 = Message
1 = Warning
2 = Alarm
Hot Aisle Over Temp Threshold
30459
40459
1
—
Units : deg C
Hot Aisle Over Temp Threshold
30460
40460
1
—
Units : deg F
Hot Aisle Under Temp Threshold
30461
40461
1
—
Units : deg C
Hot Aisle Under Temp Threshold
30462
40462
1
—
Units : deg F
Cold Aisle Over Temp Threshold
30463
40463
1
—
Units : deg C
Cold Aisle Over Temp Threshold
30464
40464
1
—
Units : deg F
Cold Aisle Under Temp Threshold
30465
40465
1
—
Units : deg C
Cold Aisle Under Temp Threshold
30466
40466
1
—
Units : deg F
Communication Status
30472
—
1
—
0 = Connected
1 = Not Connected
Fan On/Off Control
30473
40473
1
—
0 = off
1 = on
Primary Fan Group State
30474
—
1
—
0 = off
1 = on
2 = economy
Fan Button Control
30475
40475
1
—
0 = enabled
1 = disabled
Visual ID Control
30476
40476
1
—
0 = disabled
1 = enabled
XD System 2
Cooling Capacity
30477
—
1
—
Units : %
Cooling Capacity
30478
—
1
—
Units : kW
Ext System Condensation Detected - Event Control
30479
40479
1
—
0 = disabled
1 = enabled
Ext System Condensation Detected - Event Type
30480
40480
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Fan Issue - Event Control
30481
40481
1
—
0 = disabled
1 = enabled
Ext Fan Issue - Event Type
30482
40482
1
—
0 = Message
1 = Warning
2 = Alarm
Sensor Issue - Event Control
30483
40483
1
—
0 = disabled
1 = enabled
Sensor Issue - Event Type
30484
40484
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Remote Shutdown - Event Control
30485
40485
1
—
0 = disabled
1 = enabled
Ext Remote Shutdown - Event Type
30486
40486
1
—
0 = Message
1 = Warning
2 = Alarm
Hot Aisle Over Temp Threshold
30487
40487
1
—
Units : deg C
Hot Aisle Over Temp Threshold
30488
40488
1
—
Units : deg F
Hot Aisle Under Temp Threshold
30489
40489
1
—
Units : deg C
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
109
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Data Label
Input
Holding
# of Reg Scale
Notes/Units
Hot Aisle Under Temp Threshold
30490
40490
1
—
Units : deg F
Cold Aisle Over Temp Threshold
30491
40491
1
—
Units : deg C
Cold Aisle Over Temp Threshold
30492
40492
1
—
Units : deg F
Cold Aisle Under Temp Threshold
30493
40493
1
—
Units : deg C
Cold Aisle Under Temp Threshold
30494
40494
1
—
Units : deg F
Communication Status
30976
—
1
—
0 = Connected
1 = Not Connected
Fan On/Off Control
30977
40977
1
—
0 = off
1 = on
Primary Fan Group State
30978
—
1
—
0 = off
1 = on
2 = economy
Fan Button Control
30979
40979
1
—
0 = enabled
1 = disabled
Visual ID Control
30980
40980
1
—
0 = disabled
1 = enabled
XD System 20
Cooling Capacity
30981
—
1
—
Units : %
Cooling Capacity
30982
—
1
—
Units : kW
Ext System Condensation Detected - Event Control
30983
40983
1
—
0 = disabled
1 = enabled
Ext System Condensation Detected - Event Type
30984
40984
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Fan Issue - Event Control
30985
40985
1
—
0 = disabled
1 = enabled
Ext Fan Issue - Event Type
30986
40986
1
—
0 = Message
1 = Warning
2 = Alarm
Sensor Issue - Event Control
30987
40987
1
—
0 = disabled
1 = enabled
Sensor Issue - Event Type
30988
40988
1
—
0 = Message
1 = Warning
2 = Alarm
Ext Remote Shutdown - Event Control
30989
40989
1
—
0 = disabled
1 = enabled
Ext Remote Shutdown - Event Type
30990
40990
1
—
0 = Message
1 = Warning
2 = Alarm
Hot Aisle Over Temp Threshold
30991
40991
1
—
Units : deg C
Hot Aisle Over Temp Threshold
30992
40992
1
—
Units : deg F
Hot Aisle Under Temp Threshold
30993
40993
1
—
Units : deg C
Hot Aisle Under Temp Threshold
30994
40994
1
—
Units : deg F
Cold Aisle Over Temp Threshold
30995
40995
1
—
Units : deg C
Cold Aisle Over Temp Threshold
30996
40996
1
—
Units : deg F
Cold Aisle Under Temp Threshold
30997
40997
1
—
Units : deg C
Cold Aisle Under Temp Threshold
30998
40998
1
—
Units : deg F
Remote Sensor Temperature
31004
—
1
10
Units : deg C
Remote Sensor Temperature
31005
—
1
10
Units : deg F
XD System 1 Temperature Sensor 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
110
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Input
Holding
Remote Sensor Temperature
31011
—
1
10
Units : deg C
Remote Sensor Temperature
31012
—
1
10
Units : deg F
Remote Sensor Temperature
31025
—
1
10
Units : deg C
Remote Sensor Temperature
31026
—
1
10
Units : deg F
Fan State
31032
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31033
41033
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31039
—
1
10
Units : deg C
Remote Sensor Temperature
31040
—
1
10
Units : deg F
Remote Sensor Temperature
31046
—
1
10
Units : deg C
Remote Sensor Temperature
31047
—
1
10
Units : deg F
Remote Sensor Temperature
31060
—
1
10
Units : deg C
Remote Sensor Temperature
31061
—
1
10
Units : deg F
Fan State
31067
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31068
41068
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31074
—
1
10
Units : deg C
Remote Sensor Temperature
31075
—
1
10
Units : deg F
Remote Sensor Temperature
31081
—
1
10
Units : deg C
Remote Sensor Temperature
31082
—
1
10
Units : deg F
Remote Sensor Temperature
31095
—
1
10
Units : deg C
Remote Sensor Temperature
31096
—
1
10
Units : deg F
Fan State
31102
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31103
41103
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31109
—
1
10
Units : deg C
Remote Sensor Temperature
31110
—
1
10
Units : deg F
Data Label
# of Reg Scale
Notes/Units
XD System 1 Temperature Sensor 2
XD System 1 Temperature Sensor 4
XD System 1 Secondary Fans
XD System 2 Temperature Sensor 1
XD System 2 Temperature Sensor 2
XD System 2 Temperature Sensor 4
XD System 2 Secondary Fans
XD System 3 Temperature Sensor 1
XD System 3 Temperature Sensor 2
XD System 3 Temperature Sensor 4
XD System 3 Secondary Fans
XD System 4 Temperature Sensor 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
111
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Input
Holding
Remote Sensor Temperature
31116
—
1
10
Units : deg C
Remote Sensor Temperature
31117
—
1
10
Units : deg F
Remote Sensor Temperature
31130
—
1
10
Units : deg C
Remote Sensor Temperature
31131
—
1
10
Units : deg F
Fan State
31137
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31138
41138
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31144
—
1
10
Units : deg C
Remote Sensor Temperature
31145
—
1
10
Units : deg F
Data Label
# of Reg Scale
Notes/Units
XD System 4 Temperature Sensor 2
XD System 4 Temperature Sensor 4
XD System 4 Secondary Fans
XD System 5 Temperature Sensor 1
XD System 5 Temperature Sensor 2
Remote Sensor Temperature
31151
—
1
10
Units : deg C
Remote Sensor Temperature
31152
—
1
10
Units : deg F
Remote Sensor Temperature
31165
—
1
10
Units : deg C
Remote Sensor Temperature
31166
—
1
10
Units : deg F
Fan State
31172
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31173
41173
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31179
—
1
10
Units : deg C
Remote Sensor Temperature
31180
—
1
10
Units : deg F
XD System 5 Temperature Sensor 4
XD System 5 Secondary Fans
XD System 6 Temperature Sensor 1
XD System 6 Temperature Sensor 2
Remote Sensor Temperature
31186
—
1
10
Units : deg C
Remote Sensor Temperature
31187
—
1
10
Units : deg F
Remote Sensor Temperature
31200
—
1
10
Units : deg C
Remote Sensor Temperature
31201
—
1
10
Units : deg F
Fan State
31207
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31208
41208
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31214
—
1
10
Units : deg C
Remote Sensor Temperature
31215
—
1
10
Units : deg F
XD System 6 Temperature Sensor 4
XD System 6 Secondary Fans
XD System 7 Temperature Sensor 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
112
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Input
Holding
Remote Sensor Temperature
31221
—
1
10
Units : deg C
Remote Sensor Temperature
31222
—
1
10
Units : deg F
Remote Sensor Temperature
31235
—
1
10
Units : deg C
Remote Sensor Temperature
31236
—
1
10
Units : deg F
Fan State
31242
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31243
41243
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31249
—
1
10
Units : deg C
Remote Sensor Temperature
31250
—
1
10
Units : deg F
Remote Sensor Temperature
31256
—
1
10
Units : deg C
Remote Sensor Temperature
31257
—
1
10
Units : deg F
Remote Sensor Temperature
31270
—
1
10
Units : deg C
Remote Sensor Temperature
31271
—
1
10
Units : deg F
Fan State
31277
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31278
41278
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31284
—
1
10
Units : deg C
Remote Sensor Temperature
31285
—
1
10
Units : deg F
Remote Sensor Temperature
31291
—
1
10
Units : deg C
Remote Sensor Temperature
31292
—
1
10
Units : deg F
Remote Sensor Temperature
31305
—
1
10
Units : deg C
Remote Sensor Temperature
31306
—
1
10
Units : deg F
Fan State
31312
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31313
41313
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31319
—
1
10
Units : deg C
Remote Sensor Temperature
31320
—
1
10
Units : deg F
Data Label
# of Reg Scale
Notes/Units
XD System 7 Temperature Sensor 2
XD System 7 Temperature Sensor 4
XD System 7 Secondary Fans
XD System 8 Temperature Sensor 1
XD System 8 Temperature Sensor 2
XD System 8 Temperature Sensor 4
XD System 8 Secondary Fans
XD System 9 Temperature Sensor 1
XD System 9 Temperature Sensor 2
XD System 9 Temperature Sensor 4
XD System 9 Secondary Fans
XD System 10 Temperature Sensor 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
113
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Input
Holding
Remote Sensor Temperature
31326
—
1
10
Units : deg C
Remote Sensor Temperature
31327
—
1
10
Units : deg F
Remote Sensor Temperature
31340
—
1
10
Units : deg C
Remote Sensor Temperature
31341
—
1
10
Units : deg F
Fan State
31347
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31348
41348
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31354
—
1
10
Units : deg C
Remote Sensor Temperature
31355
—
1
10
Units : deg F
Remote Sensor Temperature
31361
—
1
10
Units : deg C
Remote Sensor Temperature
31362
—
1
10
Units : deg F
Remote Sensor Temperature
31375
—
1
10
Units : deg C
Remote Sensor Temperature
31376
—
1
10
Units : deg F
Fan State
31382
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31383
41383
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31389
—
1
10
Units : deg C
Remote Sensor Temperature
31390
—
1
10
Units : deg F
Remote Sensor Temperature
31396
—
1
10
Units : deg C
Remote Sensor Temperature
31397
—
1
10
Units : deg F
Remote Sensor Temperature
31410
—
1
10
Units : deg C
Remote Sensor Temperature
31411
—
1
10
Units : deg F
Fan State
31417
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31418
41418
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31424
—
1
10
Units : deg C
Remote Sensor Temperature
31425
—
1
10
Units : deg F
Data Label
# of Reg Scale
Notes/Units
XD System 10 Temperature Sensor 2
XD System 10 Temperature Sensor 4
XD System 10 Secondary Fans
XD System 11 Temperature Sensor 1
XD System 11 Temperature Sensor 2
XD System 11 Temperature Sensor 4
XD System 11 Secondary Fans
XD System 12 Temperature Sensor 1
XD System 12 Temperature Sensor 2
XD System 12 Temperature Sensor 4
XD System 12 Secondary Fans
XD System 13 Temperature Sensor 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
114
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Input
Holding
Remote Sensor Temperature
31431
—
1
10
Units : deg C
Remote Sensor Temperature
31432
—
1
10
Units : deg F
Remote Sensor Temperature
31445
—
1
10
Units : deg C
Remote Sensor Temperature
31446
—
1
10
Units : deg F
Fan State
31452
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31453
41453
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31459
—
1
10
Units : deg C
Remote Sensor Temperature
31460
—
1
10
Units : deg F
Remote Sensor Temperature
31466
—
1
10
Units : deg C
Remote Sensor Temperature
31467
—
1
10
Units : deg F
Remote Sensor Temperature
31480
—
1
10
Units : deg C
Remote Sensor Temperature
31481
—
1
10
Units : deg F
Fan State
31487
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31488
41488
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31494
—
1
10
Units : deg C
Remote Sensor Temperature
31495
—
1
10
Units : deg F
Remote Sensor Temperature
31501
—
1
10
Units : deg C
Remote Sensor Temperature
31502
—
1
10
Units : deg F
Remote Sensor Temperature
31515
—
1
10
Units : deg C
Remote Sensor Temperature
31516
—
1
10
Units : deg F
Fan State
31522
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31523
41523
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31529
—
1
10
Units : deg C
Remote Sensor Temperature
31530
—
1
10
Units : deg F
Data Label
# of Reg Scale
Notes/Units
XD System 13 Temperature Sensor 2
XD System 13 Temperature Sensor 4
XD System 13 Secondary Fans
XD System 14 Temperature Sensor 1
XD System 14 Temperature Sensor 2
XD System 14 Temperature Sensor 4
XD System 14 Secondary Fans
XD System 15 Temperature Sensor 1
XD System 15 Temperature Sensor 2
XD System 15 Temperature Sensor 4
XD System 15 Secondary Fans
XD System 16 Temperature Sensor 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
115
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Input
Holding
Remote Sensor Temperature
31536
—
1
10
Units : deg C
Remote Sensor Temperature
31537
—
1
10
Units : deg F
Remote Sensor Temperature
31550
—
—
10
Units : deg C
Remote Sensor Temperature
31551
—
—
10
Units : deg F
Fan State
31557
—
—
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31558
41558
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31564
—
1
10
Units : deg C
Remote Sensor Temperature
31565
—
1
10
Units : deg F
Remote Sensor Temperature
31571
—
1
10
Units : deg C
Remote Sensor Temperature
31572
—
1
10
Units : deg F
Remote Sensor Temperature
31585
—
1
10
Units : deg C
Remote Sensor Temperature
31586
—
1
10
Units : deg F
Fan State
31592
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31593
41593
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31599
—
1
10
Units : deg C
Remote Sensor Temperature
31600
—
1
10
Units : deg F
Data Label
# of Reg Scale
Notes/Units
XD System 16 Temperature Sensor 2
XD System 16 Temperature Sensor 4
XD System 16 Secondary Fans
XD System 17 Temperature Sensor 1
XD System 17 Temperature Sensor 2
XD System 17 Temperature Sensor 4
XD System 17 Secondary Fans
XD System 18 Temperature Sensor 1
XD System 18 Temperature Sensor 2
—
Remote Sensor Temperature
31606
—
1
10
Units : deg C
Remote Sensor Temperature
31607
—
1
10
Units : deg F
Remote Sensor Temperature
31620
—
1
10
Units : deg C
Remote Sensor Temperature
31621
—
1
10
Units : deg F
Fan State
31627
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31628
41628
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31634
—
1
10
Units : deg C
Remote Sensor Temperature
31635
—
1
10
Units : deg F
XD System 18 Temperature Sensor 4
XD System 18 Secondary Fans
XD System 19 Temperature Sensor 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
116
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-16 Liebert XDP™—Input and Holding (continued)
Controller Liebert iCOM® v4
Input
Holding
Remote Sensor Temperature
31641
—
1
10
Units : deg C
Remote Sensor Temperature
31642
—
1
10
Units : deg F
Remote Sensor Temperature
31655
—
1
10
Units : deg C
Remote Sensor Temperature
31656
—
1
10
Units : deg F
Fan State
31662
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31663
41663
1
—
0 = disabled
1 = automatic
2 = manual
Remote Sensor Temperature
31669
—
1
10
Units : deg C
Remote Sensor Temperature
31670
—
1
10
Units : deg F
Remote Sensor Temperature
31676
—
1
10
Units : deg C
Remote Sensor Temperature
31677
—
1
10
Units : deg F
Remote Sensor Temperature
31690
—
1
10
Units : deg C
Remote Sensor Temperature
31691
—
1
10
Units : deg F
Fan State
31697
—
1
—
0 = off
1 = on
2 = economy
Fan Economy Mode
31698
41698
1
—
0 = disabled
1 = automatic
2 = manual
Data Label
# of Reg Scale
Notes/Units
XD System 19 Temperature Sensor 2
XD System 19 Temperature Sensor 4
XD System 19 Secondary Fans
XD System 20 Temperature Sensor 1
XD System 20 Temperature Sensor 2
XD System 20 Temperature Sensor 4
XD System 20 Secondary Fans
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
117
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-17 Liebert XDP™—Glossary
Controller Liebert iCOM® v4
Data Label
Data Description
Auto Restart Delay
If power is lost, the control will delay this amount of time after power is restored before
restarting the unit.
Calculated Next Maintenance Month
Calculated month of the next scheduled maintenance. Used in conjunction with
[Calculated Next Maintenance Year].
Calculated Next Maintenance Year
Calculated year of the next scheduled maintenance. Used in conjunction with
[Calculated Next Maintenance Month].
Chilled Water Control Valve Failure
Chilled water valve out of position. Chilled water control valve position does not match
expected value.
Chilled Water Valve Open Position
Chilled water valve open position.
Cold Aisle Over Temp Threshold
Upper threshold value used in the [Cold Aisle Temp Out of Range] event.
Cold Aisle Temp Out of Range
The air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold]
or below [Cold Aisle Under Temp Threshold].
Cold Aisle Under Temp Threshold
Lower threshold value used in the [Cold Aisle Temp Out of Range] event.
Communication Status
Communication status of remote device.
Cooling Capacity
Cooling capacity in use, expressed as a percentage of the maximum rated capacity.
Cooling Capacity
Cooling capacity in use, expressed in kilowatts.
Customer Input 1
Customer input 1.
Dew Point Temperature
Dew point temperature, using the highest reading from all sensors.
Ext Air Over Temp Threshold
Threshold value used in the ([Ext Air Sensor A Over Temperature], [Ext Air Sensor B
Over Temperature]...) events.
Ext Air Sensor A Dew Point Temp
Dew point temperature as measured by External Air Sensor A.
Ext Air Sensor A Humidity
Relative humidity as measured by External Air Sensor A.
Ext Air Sensor A Issue
The External Air Sensor A is disconnected or the signal is out of range.
Ext Air Sensor A Over Temperature
[Ext Air Sensor A Temperature] has exceeded [Ext Air Over Temp Threshold].
Ext Air Sensor A Temperature
Air temperature as measured by External Air Sensor A.
Ext Air Sensor A Under Temperature
[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold].
Ext Air Sensor B Dew Point Temp
Dew point temperature as measured by External Air Sensor B.
Ext Air Sensor B Humidity
Relative humidity as measured by External Air Sensor B.
Ext Air Sensor B Issue
The External Air Sensor B is disconnected or the signal is out of range.
Ext Air Sensor B Over Temperature
[Ext Air Sensor B Temperature] has exceeded [Ext Air Over Temp Threshold].
Ext Air Sensor B Temperature
Air temperature as measured by External Air Sensor B.
Ext Air Sensor B Under Temperature
[Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold].
Ext Air Under Temp Threshold
Threshold value used in the ([Ext Air Sensor A Under Temperature], [Ext Air Sensor B
Under Temperature]...) events.
Ext Dew Point Over Temp Threshold
Threshold value used in the [Ext Dew Point Over Temperature] event.
Ext Dew Point Over Temperature
At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext
Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp
Threshold].
Ext Fan Issue - Event Control
Enable/disable the activation of the [Ext Fan Issue] event. If set to “disabled,” the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Ext Fan Issue - Event Type
The event type for the [Ext Fan Issue] event.
Ext Fan Issue
One or more fans are not operating within their operational parameters.
Enable/disable the activation of the [Remote Shutdown] event. If set to “disabled,” the
Ext Remote Shutdown - Event Control event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Ext Remote Shutdown - Event Type
The event type for the [Remote Shutdown] event.
Ext Remote Shutdown
Unit is shut down by a remote signal.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
118
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-17 Liebert XDP™—Glossary (continued)
Controller Liebert iCOM® v4
Data Label
Data Description
Ext System Condensation Detected Event Control
Enable/disable the activation of the [Ext System Condensation Detected] event. If set
to “disabled,” the event will not be annunciated. This implies that the event will not be
placed in any active event list or in any event history list.
Ext System Condensation Detected Event Type
The event type for the [Ext System Condensation Detected] event.
Ext System Condensation Detected
External system condensation detected.
Fan Button Control
Enable or disable the buttons from controlling the state of the fans.
Fan Economy Mode
Mode in which system secondary fans are to be controlled.
Fan Issue
One or more fans are not operating within their operational parameters.
Fan On/Off Control
Turn system fans on or off.
Fan State
Current operational state of a group of fans.
Hot Aisle Over Temp Threshold
Upper threshold value used in the [Hot Aisle Temp Out of Range] event.
Hot Aisle Temp Out of Range
The air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold]
or below [Hot Aisle Under Temp Threshold].
Hot Aisle Under Temp Threshold
Lower threshold value used in the [Hot Aisle Temp Out of Range] event.
Maintenance Completed
Maintenance has been completed on the unit.
Maintenance Due
The calculated maintenance date has been reached.
Maintenance Ramp
The ratio of operations performed to the calculated operations available between
maintenance intervals.
Master Unit Communication Lost
Communication with master unit has been lost.
Minimum Room Temperature Set
Point
Minimum desired room air temperature. If the room air temperature falls below this set
point, the unit will reduce the cooling.
Primary Fan Group State
Current operational state of the primary fan group.
Pump 1 Loss of Flow
Loss of flow is detected in pump 1. The loss of flow condition occurs when no
differential pressure is detected across the pump.
Pump 1 State
Pump 1 operational state.
Pump 2 Loss of Flow
Loss of flow is detected in pump 2. The loss of flow condition occurs when no
differential pressure is detected across the pump.
Pump 2 State
Pump 2 operational state.
Pump Hours Exceeded
[Pump Hours] has exceeded [Pump Hours Threshold].
Pump Hours Threshold
Threshold value used in the [Pump Hours Exceeded] event.
Pump Hours
Operating hours for pump since last reset of this value.
Pump Short Cycle
Pumps have short cycled. A short cycle is defined as turning on and off a number of
times over a set time period.
RAM Battery Issue
RAM or RAM backup battery is not operating correctly.
Remote Shutdown
Unit is shut down by a remote signal.
Sensor Issue - Event Control
Enable/disable the activation of the [Sensor Issue] event. If set to “disabled,” the
event will not be annunciated. This implies that the event will not be placed in any
active event list or in any event history list.
Sensor Issue - Event Type
The event type for the [Sensor Issue] event.
Sensor Issue
One or more sensors are disconnected or the signals are out of range.
Sensor Temperature
Temperature as measured by sensor.
Service Required
Unit requires servicing.
Shutdown - Loss Of Power
System lost power. This event becomes active when the unit is powered on following
an unexpected loss of power.
Smoke Detected
Smoke detected.
Supply Chilled Water Over Temp
Threshold
Threshold value used in the [Supply Chilled Water Over Temp] event.
Supply Chilled Water Over Temp
Chilled water temperature is too high, as indicated by an external input signal.
119
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-17 Liebert XDP™—Glossary (continued)
Controller Liebert iCOM® v4
Data Label
Data Description
Supply Chilled Water Temp Sensor
Issue
The supply chilled water temperature sensor is disconnected or the signal is out of
range.
Supply Chilled Water Temperature
Supply chilled water temperature.
Supply Refrig Over Temp Threshold
Threshold value used in the [Supply Refrigerant Over Temp] event.
Supply Refrigerant Over Temp
Event that is activated when [Supply Refrigerant Temperature] exceeds [Supply
Refrig Over Temp Threshold]. The event is deactivated when the temperature drops
below the threshold.
Supply Refrigerant Temp Sensor Issue
The supply refrigeramt temperature sensor is disconnected or the signal is out of
range.
Supply Refrigerant Temperature
Supply refrigerant temperature.
Supply Refrigerant Under Temp
[Supply Refrigerant Temperature] has dropped below a specified threshold.
System Condensation Detected
System condensation detected.
System Control Mode
System control mode.
System Date and Time
The system date and time
System On/Off Control
Turn system functionality on or off.
System Operating State Reason
The reason the system is in the current operating state.
System Operating State
Current operating state of the system.
System Status
The operating status for the system
Unit Code Missing
Unit code has not been entered and saved.
Unit Communication Lost
Master has lost communication with one or more networked units.
Unit Off
Unit was turned off.
Unit On
Unit was turned on.
Unit Partial Shutdown
An event has occurred requiring some system components to be shutdown and
disabled.
Unit Shutdown
An event has occurred requiring the unit to be shutdown and disabled to prevent
damage to the system.
Unit Standby
Unit was placed in standby mode.
Visual ID Control
Visual identification control to display an LED flashing sequence, allowing it to be
visually located.
Water Under Floor
Water under the floor is detected.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
120
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-18 Liebert iCOM® DCL™—Status and Coil
Data Label
Status
Coil
Number of
Bits
Notes
Air Temperature
Supply Air Over Temperature
10001
1
Active on Alarm
Supply Air Under Temperature
10002
1
Active on Alarm
Return Air Over Temperature
10003
1
Active on Alarm
Supply Air Sensor Issue
10004
1
Active on Alarm
Return Air Sensor Issue
10005
1
Active on Alarm
Unit Top Return Air Sensor Failure
10006
1
Active on Alarm
Unit Middle Return Air Sensor Failure
10007
1
Active on Alarm
Unit Bottom Return Air Sensor Failure
10008
1
Active on Alarm
Unit Top Supply Air Sensor Failure
10009
1
Active on Alarm
Unit Middle First Supply Air Sensor Failure
10010
1
Active on Alarm
Unit Middle Second Supply Air Sensor Failure
10011
1
Active on Alarm
Unit Bottom Supply Air Sensor Failure
10012
1
Active on Alarm
Pipe Temperature Sensor Failure
10013
1
Active on Alarm
Humidity
High Return Humidity
10024
1
Active on Alarm
Low Return Humidity
10025
1
Active on Alarm
Dehumidifier Hours Exceeded
10026
1
Active on Alarm
Loss of Air Flow
10037
1
Active on Alarm
Fan Hours Exceeded
10038
1
Active on Alarm
Top Fan Issue
10039
1
Active on Alarm
Bottom Fan Issue
10040
1
Active on Alarm
10051
1
Active on Alarm
10062
1
Active on Alarm
10084
1
Active on Alarm
10095
1
Active on Alarm
Fans
Remote Sensors 1
Remote Sensor Issue
Remote Sensors 2
Remote Sensor Issue
Remote Sensors 4
Remote Sensor Issue
Chilled Water
Chilled Water Control Valve Failure
Supply Chilled Water Loss of Flow
10096
1
Active on Alarm
Chilled Water Control Active
10097
1
Active on Alarm
Modbus 0-10V Module Communication Failure
10098
1
Active on Alarm
Chilled Water Circuit 1
Chilled Water Flow Transducer Failure
10109
1
Active on Alarm
Chilled Water Inlet Temperature Sensor Failure
10110
1
Active on Alarm
Chilled Water High Inlet Temperature
10111
1
Active on Alarm
Chilled Water Circuit 2
Chilled Water Flow Transducer Failure
10122
1
Active on Alarm
Chilled Water Inlet Temperature Sensor Failure
10123
1
Active on Alarm
Chilled Water High Inlet Temperature
10124
1
Active on Alarm
Customer Input 1
10135
1
Active on Alarm
Customer Input 2
10136
1
Active on Alarm
Customer Input 3
10137
1
Active on Alarm
System Events
121
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-18 Liebert iCOM® DCL™—Status and Coil (continued)
Data Label
Status
Coil
Number of
Bits
Notes
Customer Input 4
10138
1
Active on Alarm
Smoke Detected
10139
1
Active on Alarm
Water Under Floor
10140
1
Active on Alarm
Service Required
10141
1
Active on Alarm
Ext Over Temperature
10142
1
Active on Alarm
Ext Loss of Flow
10143
1
Active on Alarm
Ext Condenser Pump High Water
10144
1
Active on Alarm
Ext Standby Glycol Pump On
10145
1
Active on Alarm
External Fire Detected
10146
1
Active on Alarm
Unit On
10147
1
Active on Alarm
Unit Off
10148
1
Active on Alarm
Unit Partial Shutdown
10149
1
Active on Alarm
Unit Shutdown
10150
1
Active on Alarm
Water Leakage Detector Sensor Issue
10151
1
Active on Alarm
BMS Communications Timeout
10152
1
Active on Alarm
Maintenance Due
10153
1
Active on Alarm
Maintenance Completed
10154
1
Active on Alarm
RAM Battery Issue
10155
1
Active on Alarm
High Power Shutdown
10156
1
Active on Alarm
Unspecified General Event
10157
1
Active on Alarm
Rack Doors Open
10158
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
122
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-19 Liebert iCOM® DCL™—Input and Status
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Protocol
Server Class
1 = UPS
2 = AIR
3 = PMP
4 = PDU
5 = MONITOR
30385
1
Supply Air Temperature
30396
1
10
Units : deg C
Int16
Supply Air Temperature
30397
1
10
Units : deg F
Int16
Return Air Temperature
30398
1
10
Units : deg C
Int16
Return Air Temperature
30399
1
10
Units : deg F
Int16
Return Dew Point
30400
1
10
Units : deg C
Int16
Return Dew Point
30401
1
10
Units : deg F
Int16
Remote Sensor Minimum Temperature
30402
1
10
Units : deg C
Int16
Remote Sensor Minimum Temperature
30403
1
10
Units : deg F
Int16
Remote Sensor Maximum Temperature
30404
1
10
Units : deg C
Int16
Remote Sensor Maximum Temperature
30405
1
10
Units : deg F
Int16
Remote Sensor Average Temperature
30406
1
10
Units : deg C
Int16
Remote Sensor Average Temperature
30407
1
10
Units : deg F
Int16
Air Temperature Set Point
30408
40408
1
10
Units : deg C
Int16
Air Temperature Set Point
30409
40409
1
10
Units : deg F
Int16
Cooling Proportional Band
30410
40410
1
10
Units : deg C
Int16
Cooling Proportional Band
30411
40411
1
10
Units : deg F
Int16
Air Temperature Dead Band
30412
40412
1
10
Units : deg C
Int16
Air Temperature Dead Band
30413
40413
1
10
Units : deg F
Int16
Air Temperature Control Sensor
30414
40414
1
0 = Supply
1 = Remote
2 = Return
Remote Sensor Temperature Calculation
30415
40415
1
0 = Average
1 = Maximum
Air Temperature
123
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-19 Liebert iCOM® DCL™—Input and Status (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
High Supply Air Temperature Threshold
30416
40416
1
10
Units : deg C
Int16
High Supply Air Temperature Threshold
30417
40417
1
10
Units : deg F
Int16
Return Temperature/Humidity Sensor Control
Type
30418
40418
1
0 = Average
1 = Maximum
2 = Top Sensor
3 = Middle Sensor 1
4 = Middle Sensor 2
5 = Bottom Sensor
Supply Temperature Sensor Control Type
30419
Unit Top Return Sensor Temperature
30420
1
10
Units : deg C
Int16
Unit Top Return Sensor Temperature
30421
1
10
Units : deg F
Int16
Unit Middle Return Sensor Temperature
30422
1
10
Units : deg C
Int16
Unit Middle Return Sensor Temperature
30423
1
10
Units : deg F
Int16
Unit Bottom Return Sensor Temperature
30424
1
10
Units : deg C
Int16
Unit Bottom Return Sensor Temperature
30425
1
10
Units : deg F
Int16
Unit Top Supply Sensor Temperature
30426
1
10
Units : deg C
Int16
Unit Top Supply Sensor Temperature
30427
1
10
Units : deg F
Int16
Unit Middle First Supply Sensor Temperature
30428
1
10
Units : deg C
Int16
Unit Middle First Supply Sensor Temperature
30429
1
10
Units : deg F
Int16
Unit Middle Second Supply Sensor Temperature
30430
1
10
Units : deg C
Int16
Unit Middle Second Supply Sensor Temperature
30431
1
10
Units : deg F
Int16
Unit Bottom Supply Sensor Temperature
30432
1
10
Units : deg C
Int16
Unit Bottom Supply Sensor Temperature
30433
1
10
Units : deg F
Int16
Low Supply Air Temperature Threshold
30434
40434
1
10
Units : deg C
Int16
Low Supply Air Temperature Threshold
30435
40435
1
10
Units : deg F
Int16
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
40419
1
0 = Average
1 = Maximum
2 = Top Sensor
3 = Middle Sensor
4 = Bottom Sensor
124
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-19 Liebert iCOM® DCL™—Input and Status (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
High Return Air Temperature Threshold
30436
40436
1
10
Units : deg C
Int16
High Return Air Temperature Threshold
30437
40437
1
10
Units : deg F
Int16
Humidity
Supply Humidity
30448
1
10
Units : % RH
Uint16
Return Humidity
30449
1
10
Units : % RH
Uint16
Humidity Set Point
30450
40450
1
High Return Humidity Threshold
30451
40451
1
10
Units : % RH
Uint16
Low Return Humidity Threshold
30452
40452
1
10
Units : % RH
Uint16
Dehumidifier State
30453
40453
1
Unit Top Return Sensor Humidity
30454
1
10
Units : % RH
Int16
Unit Middle Return Sensor Humidity
30455
1
10
Units : % RH
Int16
Unit Bottom Return Sensor Humidity
30456
1
10
Units : % RH
Int16
Units : % RH
Uint16
0 = off
1 = on
Fans
0 = Internal (Auto)
1 = External (Manual)
Fan Control Mode
30467
40467
1
Fan Speed Proportional Band
30468
40468
1
10
Units : deg C
Uint16
Fan Speed Proportional Band
30469
40469
1
10
Units : deg F
Uint16
Fan Speed Manual Set Point
30470
40470
1
Units : %
Uint16
Fan Speed Maximum Set Point
30471
40471
1
Units : %
Uint16
Fan Speed Minimum Set Point
30472
40472
1
Units : %
Uint16
0 = Supply Sensor
1 = Remote Sensor
2 = Return Sensor
3 = Delta Ret-Sup
4 = Delta Remote
5 = Pipe Sensor
Fan Control Sensor
30473
40473
1
Pipe Temperature Set Point
30474
40474
1
10
Units : deg C
Int16
Pipe Temperature Set Point
30475
40475
1
10
Units : deg F
Int16
Pipe Temperature Dead Band
30476
40476
1
10
Units : deg C
Int16
125
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-19 Liebert iCOM® DCL™—Input and Status (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Pipe Temperature Dead Band
30477
40477
1
10
Units : deg F
Int16
Fan Control Mode
30467
40467
1
Fan Speed Proportional Band
30468
40468
1
10
Units : deg C
Uint16
Fan Speed Proportional Band
30469
40469
1
10
Units : deg F
Uint16
Fan Speed Manual Set Point
30470
40470
1
Units : %
Uint16
Fan Speed Maximum Set Point
30471
40471
1
Units : %
Uint16
Fan Speed Minimum Set Point
30472
40472
1
Units : %
Uint16
Remote Sensors 1
0 = Internal (Auto)
1 = External (Manual)
0 = Supply Sensor
1 = Remote Sensor
2 = Return Sensor
3 = Delta Ret-Sup
4 = Delta Remote
5 = Pipe Sensor
Fan Control Sensor
30473
40473
1
Pipe Temperature Set Point
30474
40474
1
10
Units : deg C
Int16
Pipe Temperature Set Point
30475
40475
1
10
Units : deg F
Int16
Pipe Temperature Dead Band
30476
40476
1
10
Units : deg C
Int16
Pipe Temperature Dead Band
30477
40477
1
10
Units : deg F
Int16
Remote Sensor Function
30488
40488
1
Remote Sensor Temperature
30489
1
10
Units : deg C
Int16
Remote Sensor Temperature
30490
1
10
Units : deg F
Int16
0 = Disable
1 = Reference
2 = Control
Remote Sensors 2
40501
0 = Disable
1 = Reference
2 = Control
Remote Sensor Function
30501
1
Remote Sensor Temperature
30502
1
10
Units : deg C
Int16
Remote Sensor Temperature
30503
1
10
Units : deg F
Int16
Remote Sensors 4
Remote Sensor Function
30527
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
40527
126
1
0 = Disable
1 = Reference
2 = Control
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-19 Liebert iCOM® DCL™—Input and Status (continued)
Data Label
Input
Remote Sensor Temperature
Remote Sensor Temperature
Holding
# of Reg
Scale
Notes/Units
30528
1
10
Units : deg C
Int16
30529
1
10
Units : deg F
Int16
Chilled Water
High Supply Fluid Temperature Threshold
30540
40540
1
10
Units : deg C
Int16
High Supply Fluid Temperature Threshold
30541
40541
1
10
Units : deg F
Int16
Int16
Chilled Water Valve Control
30542
40542
1
0 = Single
1 = 2 Parallel
2 = 2 Alternate
3 = 2 Cascade
Chilled Water Main Valve
30543
40543
1
0=1
1=2
Chilled Water Auto Valve Rotation
30544
40544
1
0 = disabled
1 = enabled
Chilled Water Valve Rotation Hour
30545
40545
1
Chilled Water Inlet Temperature Control
30546
40546
1
Chilled Water Inlet High Temperature Threshold
30547
40547
1
10
Units : deg C
Int16
Chilled Water Inlet High Temperature Threshold
30548
40548
1
10
Units : deg F
Int16
30549
40549
1
Chilled Water Inlet Temperature Hysteresis
30550
40550
1
10
Units : deg C
Int16
Chilled Water Inlet Temperature Hysteresis
30551
40551
1
10
Units : deg F
Int16
Units : hr
Int16
0 = disabled
1 = enabled
Int16
Chilled Water Valve Open Position
Units : %
Int16
Int16
Chilled Water Circuit 1
Chilled Water Outlet Temperature
30562
1
10
Units : deg C
Int16
Chilled Water Outlet Temperature
30563
1
10
Units : deg F
Int16
Chilled Water Inlet Temperature
30564
1
10
Units : deg C
Int16
Chilled Water Inlet Temperature
30565
1
10
Units : deg F
Int16
127
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-19 Liebert iCOM® DCL™—Input and Status (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Chilled Water Circuit 2
Chilled Water Outlet Temperature
30576
1
10
Units : deg C
Int16
Chilled Water Outlet Temperature
30577
1
10
Units : deg F
Int16
Chilled Water Inlet Temperature
30578
1
10
Units : deg C
Int16
Chilled Water Inlet Temperature
30579
1
10
Units : deg F
Int16
System Info
System Status
30590
1
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal
Operation
Unit Operating State
30591
1
0 = off
1 = on
2 = standby
Unit Control Mode
30592
1
0 = Internal (Auto)
1 = External (Manual)
1
0 = Reason Unknown
1 = Network Display
2 = Alarm
3 = Schedule
4 = Remote System
5 = External Input
6 = Local Display
Unit Operating State Reason
30593
BMS Timeout Period
30594
40594
1
Units : min
Uint16
Auto Restart Delay
30595
40595
1
Units : sec
Uint16
System Operations
Cooling Capacity
30606
1
Units : %
Uint16
Fan Speed
30607
1
Units : %
Uint16
Dehumidifier Utilization
30608
1
Units : %
Uint16
Calculated Next Maintenance Month
30609
1
Uint16
Calculated Next Maintenance Year
30610
1
Uint16
Maintenance Ramp
30611
1
Units : %
Uint16
System On/Off Control
30612
40612
1
Rack Door Open High Supply Air Temperature
Threshold
30613
40613
1
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
128
0 = off
1 = on
10
Units : deg C
Int16
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-19 Liebert iCOM® DCL™—Input and Status (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Rack Door Open High Supply Air Temperature
Threshold
30614
40614
1
10
Units : deg F
Int16
1
0 = Supply Sensor
1 = Rack Sensor 1
2 = Rack Sensor 2
3 = Rack Sensor 3
4 = Rack Sensor 4
40626
1
0 = disabled
1 = enabled
30627
40627
1
0 = Message
1 = Warning
2 = Alarm
30628
40628
1
0 = disabled
1 = enabled
Rack Door Open Sensor Selection
30615
Smoke Detected - Event Control
30626
Smoke Detected - Event Type
Water Under Floor - Event Control
Water Under Floor - Event Type
30629
40629
1
0 = Message
1 = Warning
2 = Alarm
Customer Input 1 - Event Control
30630
40630
1
0 = disabled
1 = enabled
Customer Input 1 - Event Type
30631
40631
1
0 = Message
1 = Warning
2 = Alarm
Customer Input 2 - Event Control
30632
40632
1
0 = disabled
1 = enabled
Customer Input 2 - Event Type
30633
40633
1
0 = Message
1 = Warning
2 = Alarm
Customer Input 3 - Event Control
30634
40634
1
0 = disabled
1 = enabled
Customer Input 3 - Event Type
30635
40635
1
0 = Message
1 = Warning
2 = Alarm
Customer Input 4 - Event Control
30636
40636
1
0 = disabled
1 = enabled
Customer Input 4 - Event Type
30637
40637
1
0 = Message
1 = Warning
2 = Alarm
Service Required - Event Control
30638
40638
1
0 = disabled
1 = enabled
Service Required - Event Type
30639
40639
1
0 = Message
1 = Warning
2 = Alarm
Ext Loss of Flow - Event Control
30640
40640
1
0 = disabled
1 = enabled
Ext Loss of Flow - Event Type
30641
40641
1
0 = Message
1 = Warning
2 = Alarm
129
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-19 Liebert iCOM® DCL™—Input and Status (continued)
Data Label
Input
Holding
# of Reg
Ext Over Temperature - Event Control
30642
40642
1
0 = disabled
1 = enabled
40643
1
0 = Message
1 = Warning
2 = Alarm
40644
1
2 = Reset
4 = Acknowledge
Ext Over Temperature - Event Type
30643
System Event Acknowledge/Reset
Scale
Notes/Units
Power Measurement
System Input RMS A-B
30655
1
Units : VAC
Int16
System Input RMS A-N
30656
1
Units : VAC
Int16
System Input RMS Current Phase A
30657
1
Units : A AC
Int16
System Input RMS B-C
30658
1
Units : VAC
Int16
System Input RMS B-N
30659
1
Units : VAC
Int16
System Input RMS Current Phase B
30660
1
Units : A AC
Int16
System Input RMS C-A
30661
1
Units : VAC
Int16
System Input RMS C-N
30662
1
Units : VAC
Int16
System Input RMS Current Phase C
30663
1
Units : A AC
Int16
Energy Consumption
30664
2
Units : kWH
Int32
Instantaneous Power
30666
2
Units : W
Int32
2
Units : Secs since
Epoch(UTC)
Time
System Date and Time
39998
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
49998
130
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-20 Liebert iCOM® DCL™—Glossary
Data Label
Data Description
Air Temperature Control Sensor
Sensor from which air temperature measurements will be used for cooling
and heating control.
Air Temperature Dead Band
Value that is divided evenly to form a temperature range above and below [Air
Temperature Set Point]. If measured air temperature is within this range, no
heating or cooling will occur.
Air Temperature Set Point
Desired air temperature. This set point is dependent upon which sensor is
selected for control.
Auto Restart Delay
If power is lost, the control will delay this amount of time after power is
restored before restarting the unit.
BMS Communications Timeout
Building Management System (or external monitoring system) has not
communicated with the system within the expected timeframe.
BMS Timeout Period
Timeframe within which the Building Management System (or external
monitoring system) must communicate with the system to avoid a timeout.
Bottom Fan Issue
The bottom fan is not operating within its normal parameters.
Calculated Next Maintenance Month
Calculated month of the next scheduled maintenance. Used in conjunction
with [Calculated Next Maintenance Year].
Calculated Next Maintenance Year
Calculated year of the next scheduled maintenance. Used in conjunction with
[Calculated Next Maintenance Month].
Chilled Water Auto Valve Rotation
If enabled, the priority of the chilled water valves will change daily.
Chilled Water Control Active
Chilled water inlet temperature control function is enabled due to 'bad' water.
Chilled Water Control Valve Failure
Chilled water valve out of position. Chilled water control valve position does
not match expected value.
Chilled Water Flow Transducer Failure
Chilled water flow transducer is disconnected or the signal is out of range.
Chilled Water High Inlet Temperature
Chilled water inlet temperature has exceeded an upper threshold.
Chilled Water Inlet High Temperature
Threshold
Defines the threshold for considering the inlet water temperature too high.
Chilled Water Inlet Temperature Control
Enable/disable the function to switch off the fan and open the chilled water
valve in case of 'bad' inlet water.
Chilled Water Inlet Temperature Hysteresis
Hysteresis used before returning to standard control mode when [Chilled
Water Inlet Temperature Control] is enabled.
Chilled Water Inlet Temperature Sensor
Failure
Chilled water inlet temperature sensor is disconnected or the signal is out of
range. The sensor is mandatory for the chilled water flow function.
Chilled Water Inlet Temperature
Temperature of the water entering the hydraulic circuit of the chilled water
unit.
Chilled Water Main Valve
Specifies which of the two chilled water valves is the main valve.
Chilled Water Outlet Temperature
Temperature of the water exiting the hydraulic circuit of the chilled water unit.
Chilled Water Valve Control
Method for controlling the chilled water cooling capacity. The options
available are: single, parallel, alternate and cascade.
Chilled Water Valve Open Position
Chilled water valve open position.
Chilled Water Valve Rotation Hour
Hour of the day for switching the priority of the valves.
Cooling Capacity
Cooling capacity in use, expressed as a percentage of the maximum rated
capacity.
Cooling Proportional Band
Temperature control band above [Air Temperature Set Point]. If measured air
temperature is within this band, cooling operations are proportionally
controlled.
Customer Input 1 - Event Control
Enable/disable the activation of the [Customer Input 1] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Customer Input 1 - Event Type
The event type for the [Customer Input 1] event.
Customer Input 1
Customer Input 1.
131
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-20 Liebert iCOM® DCL™—Glossary (continued)
Data Label
Data Description
Customer Input 2 - Event Control
Enable/disable the activation of the [Customer Input 2] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Customer Input 2 - Event Type
The event type for the [Customer Input 2] event.
Customer Input 2
Customer input 2.
Customer Input 3 - Event Control
Enable/disable the activation of the [Customer Input 3] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Customer Input 3 - Event Type
The event type for the [Customer Input 3] event.
Customer Input 3
Customer input 3.
Customer Input 4 - Event Control
Enable/disable the activation of the [Customer Input 4] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Customer Input 4 - Event Type
The event type for the [Customer Input 4] event.
Customer Input 4
Customer input 4.
Dehumidifier Hours Exceeded
Operating hours for the dehumidifier have exceeded the threshold.
Dehumidifier State
Dehumidifier operational state.
Dehumidifier Utilization
Present dehumidifier utilization expressed as a percentage of the maximum
rated capacity.
Energy Consumption
Energy consumption since the last reset of this value.
Ext Condenser Pump High Water
High water is detected in the condensate pump by the auxiliary float, as
indicated by an external input signal.
Ext Loss of Flow - Event Control
Enable/disable the activation of the [Ext Loss of Flow] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Ext Loss of Flow - Event Type
The event type for the [Ext Loss of Flow] event.
Ext Loss of Flow
Loss of flow is detected, as indicated by an external input signal.
Ext Over Temperature - Event Control
Enable/disable the activation of the [Ext Over Temperature] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Ext Over Temperature - Event Type
The event type for the [Ext Over Temperature] event.
Ext Over Temperature
A temperature has exceeded its threshold, as indicated by an external input
signal.
Ext Standby Glycol Pump On
The standby glycol pump is on, as indicated by an external input signal.
External Fire Detected
Fire detected, as indicated by an external input signal.
Fan Control Mode
Fan control mode. Allowable modes are: (0) Auto - Fan speed is controlled
via the selected fan control sensor, and, (1) Manual - Fan will operate at a
fixed speed.
Fan Control Sensor
Sensor from which air temperature measurements will be used for fan speed
control.
Fan Hours Exceeded
Operating hours for the unit blower fan have exceeded the threshold.
Fan Speed Manual Set Point
Manual fan speed.
Fan Speed Maximum Set Point
Maximum fan speed.
Fan Speed Minimum Set Point
Minimum fan speed.
Fan Speed Proportional Band
Temperature control band above the temperature set point calculated for
proportional fan speed control. If measured air temperature is within this
band, fan speed operations are proportionally controlled.
Fan Speed
Fan speed expressed as a percentage of the maximum rated speed.
High Power Shutdown
Supply to high power components has been shutdown.
High Return Air Temperature Threshold
Threshold value used in the [Return Air Over Temperature] event.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
132
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-20 Liebert iCOM® DCL™—Glossary (continued)
Data Label
Data Description
High Return Humidity Threshold
Threshold value used in the [High Return Humidity] event.
High Return Humidity
Return air high humidity event.
High Supply Air Temperature Threshold
Threshold value used in the [Supply Air Over Temperature] event.
High Supply Fluid Temperature Threshold
Threshold value used in the [Supply Chilled Water Over Temp] event.
Humidity Set Point
Desired relative humidity.
Instantaneous Power
Total electrical power currently being consumed.
Loss of Air Flow
No air flow through the unit due to failure of all fans.
Low Return Humidity Threshold
Threshold value used in the [Low Return Humidity] event.
Low Return Humidity
Return air low humidity event.
Low Supply Air Temperature Threshold
Threshold value used in the [Supply Air Under Temperature] event.
Maintenance Completed
Maintenance has been completed on the unit.
Maintenance Due
The calculated maintenance date has been reached.
Maintenance Ramp
The ratio of operations performed to the calculated operations available
between maintenance intervals.
Modbus 0-10V Module Communication
Failure
Modbus 0-10V module for managing the second Chilled Water circuit valve is
disconnected or the signal is out of range.
Pipe Temperature Dead Band
Value that is divided evenly to form a temperature range above and below
[Pipe Temperature Set Point]. If measured air temperature is within this
range, the fan speed will not change.
Pipe Temperature Sensor Failure
Air temperature sensor located in the pipe is not sending a valid value.
Pipe Temperature Set Point
This value will be used as a comparison against pipe air temperature
measurements in order to manage the speed of the fans.
Rack Door Open High Supply Air Temperature If the rack supply air temperature exceeds this threshold, the rack doors are
Threshold
opened.
Rack Door Open Sensor Selection
Specifies the temperature sensor to be used by the control to manage the
automatic rack door opening function.
Rack Doors Open
Rack doors opened due to supply air temperature exceeding the [Rack Door
Open High Supply Air Temperature Threshold].
RAM Battery Issue
RAM or RAM backup battery is not operating correctly.
Remote Sensor Average Temperature
Average value of remote sensor temperature measurements.
Remote Sensor Function
Function assigned to remote sensor. Available values are: (0) Control sensor will be used in calculation of remote sensor temperature that may be
used for heating and cooling control, (1) Reference - sensor will not be used
in calculation of remote sensor temperature, but is enabled, (2) Disable sensor is disabled
Remote Sensor Issue
Remote sensor is disconnected or the signal is out of range.
Remote Sensor Maximum Temperature
Maximum value of remote sensor temperature measurements.
Remote Sensor Minimum Temperature
Minimum value of remote sensor temperature measurements.
Remote Sensor Temperature Calculation
Calculation method applied to temperature readings from the remote sensors
to determine a single temperature measurement value for cooling and heating
control.
Remote Sensor Temperature
Air temperature as measured by remote sensor.
Return Air Over Temperature
Return air high temperature event.
Return Air Sensor Issue
The air sensor at the inlet of the unit is disconnected or the signal is out of
range.
Return Air Temperature
The temperature of the inlet air
Return Dew Point
Dew point temperature measured at the inlet of the unit.
Return Humidity
Relative humidity measured at the inlet of the unit.
Return Temperature/Humidity Sensor Control
Type
Specifies whether the average, maximum, or only one of the return sensor
values is to be used for return humidity and temperature control.
133
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-20 Liebert iCOM® DCL™—Glossary (continued)
Data Label
Data Description
Server Class
The general classification for this system
Service Required - Event Control
Enable/disable the activation of the [Service Required] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Service Required - Event Type
The event type for the [Service Required] event.
Service Required
Unit requires servicing.
Smoke Detected - Event Control
Enable/disable the activation of the [Smoke Detected] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Smoke Detected - Event Type
The event type for the [Smoke Detected] event.
Smoke Detected
Smoke detected.
Supply Air Over Temperature
Supply air high temperature event.
Supply Air Sensor Issue
The air sensor at the outlet of the unit is disconnected or the signal is out of
range.
Supply Air Temperature
Air temperature measured at the outlet of the unit.
Supply Air Under Temperature
Supply air low temperature event.
Supply Chilled Water Loss of Flow
Supply chilled water or glycol flow is too low.
Supply Humidity
Relative humidity at the outlet of the unit.
Supply Temperature Sensor Control Type
Specifies whether the average, maximum, or only one of the supply sensor
values is to be used for supply temperature control.
System Date and Time
The system date and time
System Event Acknowledge/Reset
Reset and/or acknowledge all events.
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System On/Off Control
Turn system functionality on or off.
System Status
The operating status for the system
Top Fan Issue
The top fan is not operating within its normal parameters.
Unit Bottom Return Air Sensor Failure
Return air sensor at the bottom of the unit is disconnected or the signal is out
of range.
Unit Bottom Return Sensor Humidity
Return humidity as measured by the sensor located at the bottom of the unit.
Unit Bottom Return Sensor Temperature
Return air temperature as measured by the sensor located at the bottom of
the unit.
Unit Bottom Supply Air Sensor Failure
Supply air sensor at the bottom of the unit is disconnected or the signal is out
of range.
Unit Bottom Supply Sensor Temperature
Supply air temperature as measured by the sensor located at the bottom of
the unit.
Unit Control Mode
Unit control mode.
Unit Middle First Supply Air Sensor Failure
First supply air sensor in the middle of the unit is disconnected or the signal is
out of range.
Unit Middle First Supply Sensor Temperature
Supply air temperature as measured by the first sensor located in the middle
of the unit.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
134
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-20 Liebert iCOM® DCL™—Glossary (continued)
Data Label
Data Description
Unit Middle Return Air Sensor Failure
Return air sensor in the middle of the unit is disconnected or the signal is out
of range.
Unit Middle Return Sensor Humidity
Return humidity as measured by the sensor located in the middle of the unit.
Unit Middle Return Sensor Temperature
Return air temperature as measured by the sensor located in the middle of
the unit.
Unit Middle Second Supply Air Sensor Failure
Second supply air sensor in the middle of the unit is disconnected or the
signal is out of range.
Unit Middle Second Supply Sensor
Temperature
Supply air temperature as measured by the second sensor located in the
middle of the unit.
Unit Off
Unit was turned off.
Unit On
Unit was turned on.
Unit Operating State Reason
The reason the unit is in the current operating state.
Unit Operating State
Current operating state of the unit.
Unit Partial Shutdown
An event has occurred requiring some system components to be shutdown
and disabled.
Unit Shutdown
An event has occurred requiring the unit to be shutdown and disabled to
prevent damage to the system.
Unit Top Return Air Sensor Failure
Return air sensor at the top of the unit is disconnected or the signal is out of
range.
Unit Top Return Sensor Humidity
Return humidity as measured by the sensor located at the top of the unit.
Unit Top Return Sensor Temperature
Return air temperature as measured by the sensor located at the top of the
unit.
Unit Top Supply Air Sensor Failure
Supply air sensor at the top of the unit is disconnected or the signal is out of
range.
Unit Top Supply Sensor Temperature
Supply air temperature as measured by the sensor located at the top of the
unit.
Unspecified General Event
One or more unspecified events active. See local unit display for further
details.
Water Leakage Detector Sensor Issue
The water leakage detector sensor is disconnected or the signal is out of
range.
Water Under Floor - Event Control
Enable/disable the activation of the [Water Under Floor] event. If set to
'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Water Under Floor - Event Type
The event type for the [Water Under Floor] event.
Water Under Floor
Water under the floor is detected.
135
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-21 Liebert DS™ and Liebert PeX™—Status and Coil
Controller Liebert iCOM™ v3
Coil
Number
of Bits
Data Description
Status
Scale
Notes / Units
Sleep on Monday
10001
1
1
—
—
Sleep on Tuesday
10002
2
1
—
—
Sleep on Wednesday
10003
3
1
—
—
Sleep on Thursday
10004
4
1
—
—
Sleep on Friday
10005
5
1
—
—
Sleep on Saturday
10006
6
1
—
—
Sleep on Sunday
10007
7
1
—
—
Supply Limit Enable
10008
8
1
—
—
Reheat Lockout
10009
9
1
—
—
Humidifier Lockout
10010
10
1
—
—
Temperature
Indication 1
10011
11
1
—
—
10012
12
1
—
—
Minimum Chilled Water Temp Enable
10013
13
1
—
—
Std. Sensor Alarms Enable
10019
19
1
—
—
Sensor A Alarms Enable
10020
20
1
—
—
Compressor Lockout
10021
21
1
—
—
VSD Fan speed
10022
22
1
—
—
—
25
1
—
—
Timer Mode Type
Unit Control
Reset Alarm
—
26
1
—
—
Acknowledge Alarm
—
27
1
—
—
Reset Total Run Hours Fan Motor
—
28
1
—
—
Reset Comp1Run Hour
—
29
1
—
—
Reset Comp2Run Hour
—
30
1
—
—
Reset Humidifier Run Hour
—
31
1
—
—
Reset Dehumidifier Run Hour
—
32
1
—
—
Reset CW/FC Run Hour
—
33
1
—
—
Reset E-Heater1RunHour
—
34
1
—
—
Reset E-heater2RunHour
—
35
1
—
—
Reset E-heater3 Run Hour
—
36
1
—
—
Reset HG/HW Run Hour
—
37
1
—
—
Fan On
10025
—
1
—
—
Cool On
10026
—
1
—
—
Free Cool On
10027
—
1
—
—
Hot Water On
10028
—
1
—
—
Electrical Heater On
10029
—
1
—
—
Humidification On
10030
—
1
—
—
Dehumidification On
10031
—
1
—
—
Audible Alarm On
10032
—
1
—
—
Reserved
10033
—
1
—
—
Main Fan Overload
10034
—
1
—
—
Loss of Airflow
10035
—
1
—
—
Loss of Flow
10036
—
1
—
—
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
136
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-21 Liebert DS™ and Liebert PeX™—Status and Coil (continued)
Controller Liebert iCOM™ v3
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Comp 1 High Pressure
10037
—
1
—
—
Comp 1 Low Pressure
10038
—
1
—
—
Comp 1 Overload
10039
—
1
—
—
Comp 1 Pumpdown Fail
10040
—
1
—
—
Comp 2 High Pressure
10041
—
1
—
—
Comp 2 Low Pressure
10042
—
1
—
—
Comp 2 Overload
10043
—
1
—
—
Comp 2 Pumpdown Fail
10044
—
1
—
—
Digital Scroll Compressor 1 High Temperature
10045
—
1
—
—
Digital Scroll Compressor 2 High Temperature
10046
—
1
—
—
Smoke Detected
10047
—
1
—
—
Water Under Floor
10048
—
1
—
—
Humidifier Problem
10049
—
1
—
—
Stby Glycol Pump On
10050
—
1
—
—
Standby Unit On
10051
—
1
—
—
Cond Pump-high Water
10052
—
1
—
—
Room Sensor Failure
10053
—
1
—
—
Loss Compressor Power
10054
—
1
—
—
Loss of Air Blower 1
10055
—
1
—
—
Humidifier Low Water
10058
—
1
—
—
Humidifier High Amps
10059
—
1
—
—
High Temperature
10060
—
1
—
—
Loss of Power
10061
—
1
—
—
Unspecified Event(s) 1
10064
—
1
—
—
High CW Temp
10065
—
1
—
—
Reserved
10066
—
1
—
—
High Room Temp
10067
—
1
—
—
Low Room Temp
10068
—
1
—
—
High Room Hum
10069
—
1
—
—
Low Room Hum
10070
—
1
—
—
High Temp Sensor A
10071
—
1
—
—
Low Temp Sensor A
10072
—
1
—
—
High Hum Sensor A
10073
—
1
—
—
Low Hum Sensor A
10074
—
1
—
—
Loss of CW Flow
10075
—
1
—
—
Clogged Filters
10076
—
1
—
—
Supply Sensor Failure
10077
—
1
—
—
Freecool Temp Sensor
10078
—
1
—
—
Sensor A Failure
10079
—
1
—
—
Unit Hrs Exceeded
10080
—
1
—
—
Comp 1 Hrs Exceeded
10081
—
1
—
—
Comp 2 Hrs Exceeded
10082
—
1
—
—
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event.
137
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-21 Liebert DS™ and Liebert PeX™—Status and Coil (continued)
Controller Liebert iCOM™ v3
Status
Coil
Number
of Bits
Scale
Notes / Units
FC Hrs Exceeded
10083
—
1
—
—
El Heat1 Hrs Exceeded
10084
—
1
—
—
El Heat2 Hrs Exceeded
10085
—
1
—
—
El Heat3 Hrs Exceeded
10086
—
1
—
—
HW/HG Hrs Exceeded
10087
—
1
—
—
Hum Hrs Exceeded
10088
—
1
—
—
Dehum Hrs Exceeded
10089
—
1
—
—
Network Failure
10091
—
1
—
—
Data Description
No Connection W/Unit
10092
—
1
—
—
Unit(s) Disconnected
10093
—
1
—
—
Unit Code Missing
10094
—
—
—
—
Unit Code Mismatch
10095
—
—
—
—
Call Service
10096
—
—
—
—
Low Memory 1
10097
—
—
—
—
RAM / Battery Failure
10098
—
—
—
—
HCB not connected
10099
—
—
—
—
(Parallel Flash) Memory 1 Fail
10100
—
—
—
—
(Serial Flash) Memory 2 Fail
10101
—
—
—
—
Customer Input 1
10104
—
—
—
—
Customer Input 2
10105
—
—
—
—
Customer Input 3
10106
—
—
—
—
Customer Input 4
10107
—
—
—
—
Digital Scroll Compressor 1 Sensor Fail
10108
—
—
—
—
Digital Scroll Compressor 2 Sensor Fail
10109
—
—
—
—
Low Int Temperature
10110
—
—
—
—
High Ext Dewpoint
10111
—
—
—
—
Cabinet Temp Sensor Fail
10112
—
—
—
—
Cabinet Humidity Sensor Fail
10113
—
—
—
—
Ambient Temp Sensor Fail
10114
—
—
—
—
Comp 1 Short Cycle
10132
—
—
—
—
Comp 2 Short Cycle
10133
—
—
—
—
Reheat Lockout
10140
—
—
—
—
Humidifier Lockout
10141
—
—
—
—
Compressor(s) Lockout
10142
—
—
—
—
Fire Alarm
10148
—
—
—
—
Heaters Overheated
10149
—
—
—
—
Condenser 1 Failure
10150
—
—
—
—
Condenser 2 Failure
10151
—
—
—
—
Humidifier Cylinder Worn
10152
—
—
—
—
Heat Rej VFD
10153
—
—
—
—
Heat Rej TVSS
10154
—
—
—
—
Humidifier Low Amps
10155
—
—
—
—
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
138
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-21 Liebert DS™ and Liebert PeX™—Status and Coil (continued)
Controller Liebert iCOM™ v3
Status
Coil
Number
of Bits
Scale
Notes / Units
FC Lockout
10156
—
—
—
—
Water Leak Sensor Fail
10157
—
—
—
—
Data Description
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event.
139
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-22 Liebert DS™ and Liebert PeX™—Input and Holding
Controller Liebert iCOM® v3
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Vendor ID
30001
40001
1
—
—
Device ID
30002
40002
1
—
—
Version Number
30003
40003
1
—
—
UPS/Env/Pwr
30004
40004
1
—
—
Mode 1
30016
40016
1
—
—
30017
40017
1
—
—
Timer
Type of DT Room-FC 2
Humidity Control
3
30018
40018
1
—
—
VSD Setpoint
30019
40019
1
—
% (HP)
Supply Temperature Limit
30020
40020
1
10
deg C
DT between Room and FC
30021
40021
1
10
deg C
Minimum CW Temperature
30022
40022
1
10
deg C
Temperature Setpoint
30023
40023
1
10
deg C
Temperature Proportional Band
30024
40024
1
10
deg C
Temperature Deadband
30025
40025
1
10
deg C
Temperature Integration Time
30026
40026
1
—
Minutes
Humidity Setpoint
30027
40027
1
—
%
Humidity Proportional Band
30028
40028
1
—
%
Humidity Integration Time
30029
40029
1
—
Minutes
Humidity Deadband
30030
40030
1
—
%
Single Unit Auto-Restart Delay
30031
40031
1
—
Seconds
Infrared Flush Rate
30032
40032
1
—
%
Temp Control Type 4
30033
40033
1
—
—
Sleep Interval 1 Start Time Hour: Minute
30040
40040
1
—
LSB:Min
Sleep Interval 1 End Time Hour: Minute
30041
40041
1
—
LSB:Min
Sleep Interval 2 Start Time Hour: Minute
30042
40042
1
—
LSB:Min
Sleep Interval 2 End Time Hour: Minute
30043
40043
1
—
LSB:Min
Timer Deadband
30044
40044
1
10
deg C
Manual VSD Timer/Counter 5
30045
40045
1
—
—
High Temperature
30050
40050
1
10
deg C
Low Temperature
30051
40051
1
10
deg C
High Temperature Sensor A
30052
40052
1
10
deg C
Low Temperature Sensor A
30053
40053
1
10
deg C
High Humidity
30054
40054
1
—
%
Low Humidity
30055
40055
1
—
%
High Humidity Sensor A
30056
40056
1
—
%
Low Humidity Sensor A
30057
40057
1
—
%
Fan Run Hour Threshold
30070
40070
—
—
Hours
Compressor 1 Run Hour Threshold
30071
40071
—
—
Hours
Compressor 2 Run Hour Threshold
30072
40072
—
—
Hours
Humidifier Run Hours Threshold
30073
40073
—
—
Hours
Dehumidification Run Hours Threshold
30074
40074
—
—
Hours
CW/FC Run Hours Threshold
30075
40075
—
—
Hours
Electrical Heaters #1 Run Hours Threshold
30076
40076
—
—
Hours
Electrical Heaters #2 Run Hours Threshold
30077
40077
—
—
Hours
Electrical Heaters #3 Run Hours Threshold
30078
40078
—
—
Hours
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
140
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-22 Liebert DS™ and Liebert PeX™—Input and Holding (continued)
Controller Liebert iCOM® v3
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Hot Water / Hot Gas Run Hours Threshold
30079
40079
—
—
Hours
Operating State 6
30100
—
—
—
—
Number of Active Events/Alarm
30101
—
—
—
—
Summary Alarm Status 7
30102
—
—
—
—
Data Description
Fan Ramp
30103
—
—
—
%
Cooling Ramp
30104
—
—
—
%
Free Cooling Ramp
30105
—
—
—
%
Heating Ramp
30106
—
—
—
%
Humidification Ramp
30107
—
—
—
%
Dehumidifier Ramp
30108
—
—
—
%
FreeCooling
Status 8
Return Temperature
30109
—
—
—
%
30110
—
—
10
deg C
Actual Temperature SP
30111
—
—
10
deg C
Supply Temperature
30112
—
—
10
deg C
Actual Supply Temperature SP
30113
—
—
10
deg C
FC Temperature
30115
—
—
10
deg C
Sensor A Temperature
30116
—
—
10
deg C
Sensor B Temperature
30117
—
—
10
deg C
Sensor C Temperature
30118
—
—
10
deg C
Digital Scroll Compressor 1 High Temperature
30119
—
—
10
deg C
Digital Scroll Compressor 2 High Temperature
30120
—
—
10
deg C
Return Humidity
30130
—
—
—
%
Actual Humidity SP
30131
—
—
—
%
Sensor A Humidity
30132
—
—
—
%
Sensor B Humidity
30133
—
—
—
%
Sensor C Humidity
30134
—
—
—
%
Fan Run Hour
30141
—
—
—
Hours
Compressor 1 Run Hour
30142
—
—
—
Hours
Compressor 2 Run Hour
30143
—
—
—
Hours
Humidifier Run Hours
30144
—
—
—
Hours
Dehumidification Run Hours
30145
—
—
—
Hours
Free cooling Run Hours
30146
—
—
—
Hours
Electrical Heaters #1 Run Hours
30147
—
—
—
Hours
Electrical Heaters #2 Run Hours
30148
—
—
—
Hours
Electrical Heaters #3 Run Hours
30149
—
—
—
Hours
Hot Water / Hot Gas Run Hours
30150
—
—
—
Hours
Daily High Temperature
30151
—
—
10
deg C
Daily High Temp Time
30152
—
—
—
Hh:mm
Daily Low Temperature
30153
—
—
10
deg C
Daily Low Temp Time
30154
—
—
—
Hh:mm
Daily High Humidity
30155
—
—
—
%RH
Daily High Hum Time
30156
—
—
—
Hh:mm
Daily Low Humidity
30157
—
—
—
%RH
141
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-22 Liebert DS™ and Liebert PeX™—Input and Holding (continued)
Controller Liebert iCOM® v3
Data Description
Daily Low Hum Time
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
30158
—
—
—
Hh:mm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
1. Timer mode: 0 = no, 1 = yes
2. Type of DT Room-Glycol: 0 = no, 1 = contact, 2 = value
3. Predictive Hum Control: 0 = relative, 1 = compensated, 2 = predictive
4. Temp Control Algorithm: 0 = proportional, 1 = PD, 2 = PDI; 3 = intelligent
5. When VFD is set to manual mode (coil 22), the host can control the VFD by the value of register 40019. The Manual VSD
Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically
reset this timer in order to maintain the manual mode. Consult factory for BMS timer information.
6. Operating state:
Bit 0-1: 00 unit off, 01 unit on, 10 unit standby
Bit 2-3: 00 auto, 01 manual
Bit 4-7: 0000 none
0001 local user
0010 alarm
0011 schedule
0100 remote user
0101 external device
0110 local display
7. Alarm state bit map:
Bit 0 =
Reset state
Bit 1 =
Active state
Bit 2 =
Acknowledge state
Bit 3-7 = Alarm Type
00000: Message
00001: Warning
00010: Alarm
8. Free-cool state: 0 = Off, 1 = Start, 2 = On
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
142
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-23 Liebert XDF™—Status and Coil
Controller Liebert iCOM® v3
Temperature Indication
Coil
Number
of Bits
Scale
Notes / Units
10011
11
1
—
—
—
25
1
—
—
Status
Data Description
1
Unit Control
Reset Alarm
—
26
1
—
—
Acknowledge Alarm
—
27
1
—
—
Cabinet Sensor Alarm Enable
10023
23
1
—
—
Fan On
10025
—
1
—
—
Cool On
10026
—
1
—
—
Compressor 1 High Pressure
10037
—
1
—
—
Compressor 1 Low Pressure
10038
—
1
—
—
Cond Pump-High Water
10052
—
1
—
—
Loss Compressor Power
10054
—
1
—
—
Emergency Damper Fail
10056
—
1
—
—
High Internal Temperature
10057
—
1
—
—
Loss of Power
10061
—
1
—
—
Remote Shutdown
10062
—
1
—
—
Unspecified Event(s) 1
10064
—
1
—
—
Unit Hrs Exceeded
10080
—
1
—
—
Comp 1 Hrs Exceeded
10081
—
1
—
—
Network Failure
10091
—
1
—
—
No Connection W/Unit 1
10092
—
1
—
—
Unit(s) Disconnected
10093
—
1
—
—
Unit Code Missing
10094
—
—
—
—
Unit Code Mismatch
10095
—
—
—
—
Low Memory 1
10097
—
—
—
—
Ram / Battery Failure
10098
—
—
—
—
(Parallel Flash) MEMORY 1 FAIL
10100
—
—
—
—
(Serial Flash) MEMORY 2 FAIL
10101
—
—
—
—
Front Door Open
10102
—
—
—
—
Rear Door Open
10103
—
—
—
—
Digital Scroll Compressor 1 Sensor Fail
10108
—
—
—
—
Low Int Temperature
10110
—
—
—
—
High Ext Dewpoint
10111
—
—
—
—
Cabinet Temp Sensor Fail
10112
—
—
—
—
Cabinet Humidity Sensor Fail
10113
—
—
—
—
Ambient Temp Sensor Fail
10114
—
—
—
—
Comp 1 Short Cycle
10132
—
—
—
—
Reheat Lockout
10140
—
—
—
—
Humidifier Lockout
10141
—
—
—
—
Compressor(s) Lockout
10142
—
—
—
—
Backup Ventilation
10143
—
—
—
—
Door Open
10144
—
—
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
1. Any non-recognized alarm code by current firmware received from the XDF control will trigger this event.
143
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-23 Liebert XDF™—Status and Coil (continued)
Controller Liebert iCOM® v3
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Device Load
10146
—
—
—
—
Alarm Status
10147
—
—
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
1. Any non-recognized alarm code by current firmware received from the XDF control will trigger this event.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
144
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-24 Liebert XDF™—Input and Holding
Controller Liebert iCOM® v3
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Vendor ID
30001
40001
1
—
—
Device ID
30002
40002
1
—
—
Version number
30003
40003
1
—
—
UPS/Env/Pwr
30004
40004
1
—
—
Temperature Setpoint
30023
40023
1
10
deg C
Delay after safe Temp has been reached
30034
40034
—
—
Minutes
Allowable deviation between internal temp sensors
30035
40035
—
—
deg C
High Cabinet Temperature Setpoint
30058
40058
—
10
deg C
Low Cabinet Temperature Setpoint
30059
40059
—
10
deg C
Fan Run Hour Threshold
30070
40070
—
—
Hours
Compressor 1 Run Hour Threshold
30071
40071
—
—
Hours
Service Ramp
30099
—
—
—
%
30100
—
—
—
—
30101
—
—
—
—
Operating
State 6
Number of Active Events/Alarm
Summary Alarm
Status 7
30102
—
—
—
—
Fan Ramp
30103
—
—
—
%
Cooling Ramp
30104
—
—
—
%
Digital Scroll Compressor 1 High Temperature
30119
—
—
10
deg C
Sensor 1 Temp
30121
—
—
10
deg C
Sensor 2 Temp
30122
—
—
10
deg C
Sensor 3 Temp
30123
—
—
10
deg C
Sensor 4 Temp
30124
—
—
10
deg C
Ambient Temp
30125
—
—
10
deg C
Ambient Humidity
30126
—
—
—
%
Dew Point Temp
30127
—
—
—
deg C
Adjusted Setpoint Temp
30128
—
—
10
deg C
Cabinet Temperature
30129
—
—
10
deg C
Service Due Year
30135
—
—
—
—
Service Due Month
30136
—
—
—
—
Device kW Load
30137
—
—
—
kW
Fan Run Hour
30141
—
—
—
Hours
145
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-24 Liebert XDF™—Input and Holding (continued)
Controller Liebert iCOM® v3
Data Description
Compressor 1 Run Hour
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
30142
—
—
—
Hours
NOTES
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
1. Timer mode: 0 = no, 1 = yes
2. Type of DT Room-Glycol: 0 = no, 1 = contact, 2 = value
3. Predictive Hum Control: 0 = relative, 1 = compensated, 2 = predictive
4. Temp Control Algorithm: 0 = proportional, 1 = PD, 2 = PDI; 3 = intelligent
5. When VFD is set to manual mode (coil 22), the host can control the VFD by the value of register 40019. The Manual VSD
Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically
reset this timer in order to maintain the manual mode. Consult factory for BMS timer information.
6. Operating state:
Bit 0-1: 00 unit off, 01 unit on, 10 unit standby
Bit 2-3: 00 auto, 01 manual
Bit 4-7: 0000 none
0001 local user
0010 alarm
0011 schedule
0100 remote user
0101 external device
0110 local display
7. Alarm state bit map:
Bit 0 =
Reset state
Bit 1 =
Active state
Bit 2 =
Acknowledge state
Bit 3-7 = Alarm Type
00000: Message
00001: Warning
00010: Alarm
8. Free-cool state: 0 = Off, 1 = Start, 2 = On
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
146
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-25 Liebert Challenger 3000™, Liebert Deluxe System/3™, Liebert Himod™, Liebert ICS™—
Input and Holding—LAM
Controller Advanced Microprocessor - LAM
Liebert Challenger 3000
Liebert Deluxe System/3
Liebert Products
Liebert Himod (LNA version - Using Liebert SiteScan®)
Liebert ICS
Available Points
Input
Register
Holding
Register
Temperature
—
40001
1
—
—
Humidity
—
40002
1
—
—
Data Description
# of
Reg.
Scale
Notes / Units
Status Points (View)
Cooling
—
40003
1
—
1=On / 0=Off
Heating
—
40004
1
—
1=On / 0=Off
Humidification
—
40005
1
—
1=On / 0=Off
De-humidification
—
40006
1
—
1=On / 0=Off
Econ-O-Cycle
—
40007
1
—
1=On / 0=Off
Stages
—
40008
1
—
—
% Capacity
—
40009
1
—
—
Unit Status (On / Off)
—
40018
1
—
1=On / 0=Off (Read Only)
Discrete alarm objects available;
use autodiscover for this unit
Alarm Points
Communications
—
40289
1
—
Bit 0
Local Off
—
40289
1
—
Bit 1
Remote Off
—
40289
1
—
Bit 2
High Head Pressure 1
—
40289
1
—
Bit 3
High Head Pressure 2
—
40289
1
—
Bit 4
Loss of Airflow
—
40289
1
—
Bit 5
Standby Glycol Unit On
—
40289
1
—
Bit 6
Liquid Detected
—
40289
1
—
Bit 7
Change Filters
—
40289
1
—
Bit 8
High Temperature
—
40289
1
—
Bit 9
Low Temperature
—
40289
1
—
Bit 10
High Humidity
—
40290
1
—
Bit 0
Low Humidity
—
40290
1
—
Bit 1
Humidifier Problem
—
40290
1
—
Bit 2
No Water in Humidifier Pan
—
40290
1
—
Bit 3
Compressor 1 Overload
—
40290
1
—
Bit 4
Compressor 2 Overload
—
40290
1
—
Bit 5
Main Fan Overload
—
40290
1
—
Bit 6
Manual Override
—
40290
1
—
Bit 7
Smoke Detected
—
40290
1
—
Bit 8
Loss of Water
—
40290
1
—
Bit 9
Standby Unit On
—
40290
1
—
Bit 10
Low Suction
—
40291
1
—
Bit 0
Short Cycle
—
40291
1
—
Bit 1
Loss of Power
—
40291
1
—
Bit 2
Inverter on Bypass
—
40291
1
—
Bit 3
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
147
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-25 Liebert Challenger 3000™, Liebert Deluxe System/3™, Liebert Himod™, Liebert ICS™—
Input and Holding—LAM (continued)
Controller Advanced Microprocessor - LAM
Liebert Challenger 3000
Liebert Deluxe System/3
Liebert Products
Liebert Himod (LNA version - Using Liebert SiteScan®)
Liebert ICS
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Standby Fan On
—
40291
1
—
Bit 4
Loss of Emergency Power
—
40291
1
—
Bit 5
Local Alarm 1
—
40291
1
—
Bit 6
Data Description
Local Alarm 2
—
40291
1
—
Bit 7
Off by Remote Shutdown
—
40291
1
—
Bit 8
Local Alarm 3
—
40291
1
—
Bit 9
Local Alarm 4
—
40291
1
—
Bit 10
Compressor 1 Run Hours
—
40019
1
—
—
Compressor 2 Run Hours
—
40020
1
—
—
Fan Motor Run Hours
—
40021
1
—
—
Humidifier Run Hours
—
40022
1
—
—
Temperature Setpoint
—
40010
1
—
(R/W)
Temperature Tolerance
—
40011
1
—
(R/W)
Humidity Setpoint
—
40012
1
—
(R/W)
Setpoints (View)
Humidity Tolerance
—
40013
1
—
(R/W)
High Temp Alarm Setpoint
—
40014
1
—
(R/W)
Low Temp Alarm Setpoint
—
40015
1
—
(R/W)
High Humd Alarm Setpoint
—
40016
1
—
(R/W)
Low Humidity Alarm Setpoint
—
40017
1
—
(R/W)
Winter Start Delay
—
40028
1
—
Minutes (R/W)
Auto Flush Rate
—
40029
1
—
% (R/W)
Chill Water Flush Rate
—
40030
1
—
Hours (R/W)
Auto Restart Delay
—
40031
1
—
0.1 minute (R/W)
Control Points (Set)
Unit On / Off
—
40349
1
—
Temperature Setpoint
—
40350
1
—
Bit 0 On=unit Off; Bit 1 On=unit On
—
Temperature Tolerance
—
40350
1
1000
—
Humidity Setpoint
—
40351
1
—
—
Humidity Tolerance
—
40351
1
1000
Reheat Lockout
—
40349
1
—
Bit 2 On=RH Off; Bit 3 On=RH On
Humidifier Lockout
—
40349
1
—
Bit 4 On=HL Off; Bit 5 On=HL On
—
Trendable Points (Set)
Temperature
—
—
1
—
—
Humidity
—
—
1
—
—
Reports
—
—
—
—
Trend
—
—
1
—
—
Status
—
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
148
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-26 Liebert DataMate™, Liebert Mini-Mate Plus™, Liebert Mini-Mate2™—Input and Holding—L0B
Controller Small Systems - L0B
Liebert DataMate
Liebert Products Liebert Mini-Mate Plus
Liebert Mini-Mate2
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Temperature
—
40001
1
—
—
Humidity
—
40002
1
—
—
Cooling
—
40003
1
—
1=On / 0=Off
Data Description
Status Points (View)
Heating
—
40004
1
—
1=On / 0=Off
Humidification
—
40005
1
—
1=On / 0=Off
Dehumidification
—
40006
1
—
1=On / 0=Off
Econ-o-Cycle
—
40007
1
—
1=On / 0=Off
Stages
—
40008
1
—
—
% Capacity
—
40009
1
—
—
Communications
—
40289
1
—
Bit 0
Local Off
—
40289
1
—
Bit 1
Remote Off
—
40289
1
—
Bit 2
High Temperature
—
40289
1
—
Bit 3
Low Temperature
—
40289
1
—
Bit 4
High Humidity
—
40289
1
—
Bit 5
Low Humidity
—
40289
1
—
Bit 6
—
—
1
—
—
Unit On/Off
—
40011
1
—
1=On / 0=Off (R/W)
Remote On/Off
—
40349
1
—
Temperature
—
—
1
—
—
Humidity
—
—
1
—
—
Reports
—
—
—
—
Trend
—
—
1
—
—
Status
—
—
1
—
—
Alarm Points
Setpoints (View)
None
Control Points (Set)
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Trendable Points (Set)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
149
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-27 Liebert DataMate™, Liebert Mini-Mate2™—Input and Holding—MM2
Controller MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Temperature
—
40001
1
—
—
Humidity
—
40002
1
—
—
Data Description
Status Points (View)
Cooling
—
40003
1
—
1=On / 0=Off
Heating
—
40004
1
—
1=On / 0=Off
Humidification
—
40005
1
—
1=On / 0=Off
Dehumidification
—
40006
1
—
1=On / 0=Off
Econ-o-Cycle
—
40007
1
—
1=On / 0=Off
Stages
—
40008
1
—
—
% Capacity
—
40009
1
—
—
Communications
—
40289
1
—
Bit 0
Local Off
—
40289
1
—
Bit 1
Alarm Points
Remote Off
—
40289
1
—
Bit 2
High Head Pressure 1
—
40289
1
—
Bit 3
Loss of Airflow
—
40289
1
—
Bit 5
Standby Glycol Unit On
—
40289
1
—
Bit 6
Change Filters
—
40289
1
—
Bit 8
High Temperature
—
40289
1
—
Bit 9
Low Temperature
—
40289
1
—
Bit 10
High Humidity
—
40290
1
—
Bit 0
Low Humidity
—
40290
1
—
Bit 1
Humidifier Problem
—
40290
1
—
Bit 2
Smoke Detected
—
40290
1
—
Bit 8
Loss of Water Flow
—
40290
1
—
Bit 9
Standby Unit On
—
40290
1
—
Bit 10
Short Cycle
—
40291
1
—
Bit 1
Loss of Power
—
40291
1
—
Bit 2
Local Alarm 1
—
40291
1
—
Bit 6
Local Alarm 2
—
40291
1
—
Bit 7
Local Alarm 3
—
40291
1
—
Bit 9
Local Alarm 4
—
40291
1
—
Bit 10
Compressor 1
—
40019
1
—
—
Fan Motor
—
40020
1
—
—
Humidifier
—
40021
1
—
—
Run Hours (View)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
150
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-27 Liebert DataMate™, Liebert Mini-Mate2™—Input and Holding—MM2 (continued)
Controller MM2
Liebert Products
Liebert DataMate
Liebert Mini-Mate2
Available Points
Input
Register
Holding
Register
Temperature
—
40010
1
—
—
Temp Tolerance
—
40011
1
—
—
Data Description
# of
Reg.
Scale
Notes / Units
Setpoints (View)
Humidity
—
40012
1
—
—
Humidity Tolerance
—
40013
1
—
—
High Temperature Alarm
—
40014
1
—
—
Low Temperature Alarm
—
40015
1
—
—
High Humidity Alarm
—
40016
1
—
—
Low Humidity Alarm
—
40017
1
—
—
Chill Water Flush Rate
—
40025
1
—
Hours (R/W)
Auto Restart Delay
—
40026
1
—
0.1 minute (R/W)
Unit On/Off
—
40018
1
—
1=On / 0=Off (Read Only)
Remote On/Off
—
40349
1
—
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Temperature Setpoint
—
40350
1
—
Control Points (Set)
(W)
Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Temperature Tolerance
—
40350
1
1000
Humidity Setpoint
—
40351
1
-
Humidity Tolerance
—
40351
1
1000
Temperature
—
—
1
—
—
Humidity
—
—
1
—
—
Trend
—
—
1
—
—
Status
—
—
1
—
—
(W)
Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Trendable Points (Set)
Reports
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
151
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-28 Liebert Mini-Mate2™ 8 Ton—Input and Holding—L8T
Controller L8T
Liebert Products Liebert Mini-Mate2 8 Ton
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Temperature
—
40001
1
—
—
Humidity
—
40002
1
—
—
Cooling
—
40003
1
—
1=On / 0=Off
Data Description
Status Points (View)
Heating
—
40004
1
—
1=On / 0=Off
Humidification
—
40005
1
—
1=On / 0=Off
De-humidification
—
40006
1
—
1=On / 0=Off
Econ-O-Cycle
—
40007
1
—
1=On / 0=Off
Stages
—
40008
1
—
—
% Capacity
—
40009
1
—
—
Analog input 1
—
40023
1
—
A/D raw value w/ slope =1
and offset = 0
Analog input 2
—
40024
1
—
A/D raw value w/ slope =1
and offset = 0
Analog input 3
—
40025
1
—
A/D raw value w/ slope =1
and offset = 0
Analog input 4
—
40026
1
—
A/D raw value w/ slope =1
and offset = 0
Communications
—
40289
1
—
Bit 0
Local Off
—
40289
1
—
Bit 1
Remote Off
—
40289
1
—
Bit 2
High Head Pressure 1
—
40289
1
—
Bit 3
High Head Pressure 2
—
40289
1
—
Bit 4
Loss of Airflow
—
40289
1
—
Bit 5
Standby Glycol Unit On
—
40289
1
—
Bit 6
Alarm Points
Not Used
—
40289
1
—
Bit 7
Change Filters
—
40289
1
—
Bit 8
High Temperature
—
40289
1
—
Bit 9
Low Temperature
—
40289
1
—
Bit 10
High Humidity
—
40290
1
—
Bit 0
Low Humidity
—
40290
1
—
Bit 1
Humidifier Problem
—
40290
1
—
Bit 2
Smoke Detected
—
40290
1
—
Bit 8
Loss of Water
—
40290
1
—
Bit 9
Standby Unit On
—
40290
1
—
Bit 10
Not Used
—
40291
1
—
Bit 0
Short Cycle
—
40291
1
—
Bit 1
Loss of Power
—
40291
1
—
Bit 2
Local Alarm 1
—
40291
1
—
Bit 6
Local Alarm 2
—
40291
1
—
Bit 7
EPO Shutdown
—
40291
1
—
Bit 8
Local Alarm 3
—
43291
1
—
Bit 9
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
152
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-28 Liebert Mini-Mate2™ 8 Ton—Input and Holding—L8T (continued)
Controller L8T
Liebert Products Liebert Mini-Mate2 8 Ton
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
—
40291
1
—
Bit 10
Compressor 1 Run Hours
—
40019
1
—
—
Compressor 2 Run Hours
—
40020
1
—
—
Data Description
Local Alarm 4
Run Times (View)
Glycol Run Hours
—
—
1
—
—
Fan Motor Run Hours
—
40021
1
—
—
Humidifier Run Hours
—
40022
1
—
—
Reheat 1 Run Hours
—
—
1
—
—
Reheat 2 Run Hours
—
—
1
—
—
Reheat 3 Run Hours
—
—
1
—
—
Chilled H2O Valve Run Hours
—
—
1
—
—
Temperature Setpoint
—
40010
1
—
(R/W)
Temperature Tolerance
—
40011
1
—
(R/W)
Setpoints (View)
Humidity Setpoint
—
40012
1
—
(R/W)
Humidity Tolerance
—
40013
1
—
(R/W)
High Temperature Alarm Setpoint
—
40014
1
—
(R/W)
Low Temp Alarm Setpoint
—
40015
1
—
(R/W)
High Humidity Alarm Setpoint
—
40016
1
—
(R/W)
Low Humidity Alarm Setpoint
—
40017
1
—
(R/W)
Winter Start Delay
—
40028
1
—
Minutes (R/W)
Auto Flush Rate
—
40029
1
—
% (R/W)
Chill Water Flush Rate
—
40030
1
—
Hours (R/W)
Auto Restart Delay
—
40031
1
—
0.1 minute (R/W)
Unit Status (On / Off)
—
40018
1
—
1=On / 0=Off (Read Only)
Unit On / Off
—
40349
1
—
Temperature Setpoint
—
40350
1
—
(W)
Temperature Tolerance
—
40350
1
1000
(W)
Control Points (Set)
Bit 0 On=unit Off
Bit 1 On=unit On (W)
Humidity Setpoint
—
40351
1
-
(W)
Humidity Tolerance
—
40351
1
1000
(W)
Reheat Lockout
—
40349
1
—
Bit 2 On=RH Off
Bit 3 On=RH On
Humidifier Lockout
—
40349
1
—
Bit 4 On=HL Off
Bit 5 On=HL On
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
153
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-29 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert LECS 15™—Input and Holding—C10 2-step
Controller C10
Liebert Atlas Air
Liebert Products Liebert Atlas PEC
Liebert LECS 15
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Unit Number
—
40001
1
—
1-99
Average Return Air Temp.
—
40002
1
10
deg C
Average Return Air Humidity
—
40003
1
10
%
Data Description
Status Points (View)
Average Supply Air Temp.
—
40004
1
10
deg C
Average Supply Air Humidity
—
40005
1
10
%
Fan Status
—
40007
1
—
1=On / 0=Off
Cool 1 Status
—
40008
1
—
1=On / 0=Off
Cool 2 Status
—
40009
1
—
1=On / 0=Off
Heat 1 Status
—
40010
1
—
1=On / 0=Off
Heat 2 Status
—
40011
1
—
1=On / 0=Off
Humidifier Status
—
40012
1
—
—
De-humidifier Status
—
40013
1
—
—
Cooling Capacity
—
40014
1
—
%
Heating Capacity
—
40015
1
—
%
Temperature Control Status
—
40019
1
—
0=Return / 1=Supply
Battery Voltage Level
—
40020
1
10
V
Remote Shutdown Status
—
40021
1
—
1=Enabled / 0=Disabled
Temperature Control Select
—
40024
1
—
0=Return / 1=Supply
2=Remote / 3=Auto
Communications
—
40289
1
—
Bit 0
Faulty Sensor
—
40289
1
—
Bit 1
High Temperature
—
40289
1
—
Bit 2
Low Temperature
—
40289
1
—
Bit 3
High Humidity
—
40289
1
—
Bit 4
Alarm Points
Low Humidity
—
40289
1
—
Bit 5
Loss of Airflow
—
40289
1
—
Bit 6
Water Under Floor
—
40289
1
—
Bit 7
Cool 1 Low Pressure Alarm
—
40289
1
—
Bit 8
Cool 2 Low Pressure Alarm
—
40289
1
—
Bit 9
Cool 1 High Pressure Alarm
—
40289
1
—
Bit 10
Cool 2 High Pressure Alarm
—
40290
1
—
Bit 0
Cool Service
—
40290
1
—
Bit 1
Humidifier Service
—
40290
1
—
Bit 2
Filter Service
—
40290
1
—
Bit 3
Humidity Low Level
—
40290
1
—
Bit 4
Battery Level Low
—
40290
1
—
Bit 5
Loss of Power
—
40290
1
—
Bit 6
Local Alarm 1
—
40290
1
—
Bit 7
Local Alarm 2
—
40290
1
—
Bit 8
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
154
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-29 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert LECS 15™—Input and Holding—C10 2-step
Controller C10
Liebert Atlas Air
Liebert Products Liebert Atlas PEC
Liebert LECS 15
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
—
40016
1
10
deg C (R/W)
Setpoints (View)
Return Air Temperature
Return Air Humidity
—
40017
1
10
deg C (R/W)
Supply Air Temperature
—
40018
1
10
deg C (R/W)
High Temp Alarm
—
40025
1
10
deg C (R/W)
Low Temp Alarm
—
40026
1
10
deg C (R/W)
High Hum Alarm
—
40027
1
10
% (R/W)
Low Hum Alarm
—
40028
1
10
% (R/W)
Restart Delay
—
40029
1
—
Seconds (R/W)
Activation Mode
—
40006
1
—
1=On / 0=Off (R/W)
General Alarm Status
—
40022
1
—
1=On / 0=Off; write 0 to reset alarm
Control Points (Set)
Audible Alarm Status
—
40023
1
—
1=On / 0=Off; write 0 to ack alarm
Return Air Temperature
—
40349
1
10
deg C (R/W)
Return Air Humidity
—
40350
1
10
deg C (R/W)
Supply Air Temperature
—
40351
1
10
deg C (R/W)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
155
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-30 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert CEMS 100™—Input and Holding—
C100 4-step
Controller CEMS 100
Liebert Atlas Air
Liebert Products Liebert Atlas PEC
Liebert CEMS 100
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Unit Number
—
40001
1
—
1-99
Average Return Air Temp.
—
40002
1
10
deg C
Average Return Air Humidity
—
40003
1
10
%
Data Description
Status Points (View)
Average Supply Air Temp.
—
40004
1
10
deg C
Average Supply Air Humidity
—
40005
1
10
%
Fan Status
—
40007
1
—
1=On / 0=Off
Cool 1 Status
—
40008:0
1
—
1=On / 0=Off
Cool 2 Status
—
40009:0
1
—
1=On / 0=Off
Cool 3 Status
—
40008:4
1
—
1=On / 0=Off
Cool 4 Status
—
40009:4
1
—
1=On / 0=Off
Heat 1 Status
—
40010
1
—
1=On / 0=Off
Heat 2 Status
—
40011
1
—
1=On / 0=Off
Humidifier Status
—
40012
1
—
—
De-humidifier Status
—
40013
1
—
—
Cooling Capacity
—
40014
1
—
%
Heating Capacity
—
40015
1
—
%
Temperature Control Status
—
40019
1
—
0=Return / 1=Supply
Battery Voltage Level
—
40020
1
100
V
Remote Shutdown Status
—
40021
1
—
1=Enabled / 0=Disabled
Temperature Control Select
—
40024
1
—
0=Return / 1=Supply
2=Remote / 3=Auto
Communications
—
40289
1
—
Bit 0
Faulty Sensor
—
40289
1
—
Bit 1
High Temperature
—
40289
1
—
Bit 2
Low Temperature
—
40289
1
—
Bit 3
High Humidity
—
40289
1
—
Bit 4
Alarm Points
Low Humidity
—
40289
1
—
Bit 5
Loss of Airflow
—
40289
1
—
Bit 6
Water Under Floor
—
40289
1
—
Bit 7
Cool 1 Low Pressure Alarm
—
40289
1
—
Bit 8
Cool 2 Low Pressure Alarm
—
40289
1
—
Bit 9
Cool 1 High Pressure Alarm
—
40289
1
—
Bit 10
Cool 2 High Pressure Alarm
—
40290
1
—
Bit 0
Cool Service
—
40290
1
—
Bit 1
Humidifier Service
—
40290
1
—
Bit 2
Filter Service
—
40290
1
—
Bit 3
Humidity Low Level
—
40290
1
—
Bit 4
Battery Level Low
—
40290
1
—
Bit 5
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
156
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Table 3-30 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert CEMS 100™—Input and Holding—
C100 4-step (continued)
Controller CEMS 100
Liebert Atlas Air
Liebert Products Liebert Atlas PEC
Liebert CEMS 100
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Loss of Power
—
40290
1
—
Bit 6
Local Alarm 1
—
40290
1
—
Bit 7
Local Alarm 2
—
40290
1
—
Bit 8
Cool 3 Low Pressure
—
40290
1
—
Bit 9
Cool 4 Low Pressure
—
40290
1
—
Bit 10
Cool 3 High Pressure
—
40290
1
—
Bit 11
Cool 4 High Pressure
—
40290
1
—
Bit 12
Air Flow 2 Loss
—
40290
1
—
Bit 13
—
40016
1
10
deg C (R/W)
Data Description
Setpoints (View)
Return Air Temperature
Return Air Humidity
—
40017
1
10
deg C (R/W)
Supply Air Temperature
—
40018
1
10
deg C (R/W)
High Temp Alarm
—
40025
1
10
deg C (R/W)
Low Temp Alarm
—
40026
1
10
deg C (R/W)
High Hum Alarm
—
40027
1
10
% (R/W)
Low Hum Alarm
—
40028
1
10
% (R/W)
Restart Delay
—
40029
1
—
Seconds (R/W)
Activation Mode
—
40006
1
—
1=On / 0=Off (R/W)
General Alarm Status
—
40022
1
—
1=On / 0=Off; write 0 to reset alarm
Control Points (Set)
Audible Alarm Status
—
40023
1
—
1=On / 0=Off; write 0 to ack alarm
Return Air Temperature
—
40349
1
10
deg C (R/W)
Return Air Humidity
—
40350
1
10
deg C (R/W)
Supply Air Temperature
—
40351
1
10
deg C (R/W)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
157
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Thermal Management Products
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
158
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
3.2 Power Distribution and Power Conditioning Products
Table 3-31 Liebert FPC™, Liebert PPC™—Input and Holding
Controller Power Monitoring Panel - PMP2
Liebert Products
Liebert FPC
Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Voltage In X-Y
—
40001
1
—
V
Voltage In Y-Z
—
40002
1
—
V
Voltage In Z-X
—
40003
1
—
V
Data Description
Status Points (View)
Voltage Out A-B
—
40004
1
—
V
Voltage Out B-C
—
40005
1
—
V
Voltage Out C-A
—
40006
1
—
V
Voltage Out A-N
—
40007
1
—
V
Voltage Out B-N
—
40008
1
—
V
Voltage Out C-N
—
40009
1
—
V
Current Out A
—
40010
1
—
A
Current Out B
—
40011
1
—
A
Current Out C
—
40012
1
—
A
Ground Current
—
40013
1
10
A
Neutral Current
—
40014
1
—
A
kVA
—
40015
1
—
kVA
kW
—
40016
1
—
kW
Frequency
—
40017
1
10
Hz
% Capacity A
—
40018
1
—
%
% Capacity B
—
40019
1
—
%
% Capacity C
—
40020
1
—
%
Power Factor
—
40021
1
100
—
Kilowatt Hours
—
—
1
—
—
THD Voltage X
—
—
1
—
—
THD Voltage Y
—
—
1
—
—
THD Voltage Z
—
—
1
—
—
THD Current X
—
—
1
—
—
THD Current Y
—
—
1
—
—
THD Current Z
—
—
1
—
—
K Factor Current X
—
—
1
—
—
K Factor Current Y
—
—
1
—
—
K Factor Current Z
—
—
1
—
—
CREST Factor Current X
—
—
1
—
—
CREST Factor Current Y
—
—
1
—
—
CREST Factor Current Z
—
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value
159
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-31 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller Power Monitoring Panel - PMP2
Liebert Products
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Alarm Points
Communications
Notes / Units
Discrete alarm objects available; use
auto-discover for this unit
—
40289
1
—
Bit 0
Output Undervoltage
—
40289
1
—
Bit 1
Output Overvoltage
—
40289
1
—
Bit 2
Output Overcurrent
—
40289
1
—
Bit 3
Frequency Deviation
—
40289
1
—
Bit 4
Ground Overcurrent
—
40289
1
—
Bit 5
Transformer Overtemp
—
40289
1
—
Bit 6
Ground Fault
—
40289
1
—
Bit 7
Ground Failure
—
40289
1
—
Bit 8
Liquid Detected
—
40289
1
—
Bit 9
Security Alarm
—
40289
1
—
Bit 10
Phase Rotation/Loss
—
40290
1
—
Bit 0
Datawave Overtemperature
—
40290
1
—
Bit 1
Emergency Shutdown
—
40290
1
—
Bit 2
Load On Bypass
—
40290
1
—
Bit 3
Local Alarm #1
—
40290
1
—
Bit 4
Local Alarm #2
—
40290
1
—
Bit 5
Output Voltage THD
—
40290
1
—
Bit 6
Custom Alarm #1
—
40290
1
—
Bit 7
Custom Alarm #2
—
40290
1
—
Bit 8
—
—
1
—
—
—
—
1
—
—
Setpoints (View)
None
Control Points (Set)
None
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
160
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-32 Liebert Datawave™, Liebert FPC™, Liebert PPC™—Input and Holding—
PMP Option for Liebert FPC and Liebert PPC
Controller
Power Monitoring Panel - PMP
Option for Liebert FPC and Liebert PPC
Liebert Datawave
Liebert Products Liebert FPC
Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Voltage In X-Y
—
40001
1
—
V
Voltage In Y-Z
—
40002
1
—
V
Voltage In Z-X
—
40003
1
—
V
Data Description
Status Points (View)
Voltage Out A-B
—
40004
1
—
V
Voltage Out B-C
—
40005
1
—
V
Voltage Out C-A
—
40006
1
—
V
Voltage Out A-N
—
40007
1
—
V
Voltage Out B-N
—
40008
1
—
V
Voltage Out C-N
—
40009
1
—
V
Current Out A
—
40010
1
—
A
Current Out B
—
40011
1
—
A
Current Out C
—
40012
1
—
A
Ground Current
—
40013
1
10
A
Neutral Current
—
40014
1
—
A
kVA
—
40015
1
—
kVA
kW
—
40016
1
—
kW
Frequency
—
40017
1
10
Hz
% Capacity A
—
40018
1
—
%
% Capacity B
—
40019
1
—
%
% Capacity C
—
40020
1
—
Alarm Points
Communications
%
Discrete alarm objects available; use
auto-discover for this unit
—
40289
1
—
Bit 0
Output Undervoltage
—
40289
1
—
Bit 1
Output Overvoltage
—
40289
1
—
Bit 2
Output Overcurrent
—
40289
1
—
Bit 3
Frequency Deviation
—
40289
1
—
Bit 4
Ground Overcurrent
—
40289
1
—
Bit 5
Transformer Overtemp
—
40289
1
—
Bit 6
Ground Fault
—
40289
1
—
Bit 7
Ground Failure
—
40289
1
—
Bit 8
Liquid Detected
—
40289
1
—
Bit 9
Security Alarm
—
40289
1
—
Bit 10
Phase Rotation/Loss
—
40290
1
—
Bit 0
Datawave Overtemperature
—
40290
1
—
Bit 1
Emergency Shutdown
—
40290
1
—
Bit 2
Load On Bypass
—
40290
1
—
Bit 3
Local Alarm
—
40290
1
—
Bit 4
Custom Alarm #1
—
40290
1
—
Bit 5
161
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-32 Liebert Datawave™, Liebert FPC™, Liebert PPC™—Input and Holding—
PMP Option for Liebert FPC and Liebert PPC (continued)
Controller
Power Monitoring Panel - PMP
Option for Liebert FPC and Liebert PPC
Liebert Datawave
Liebert Products Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Custom Alarm #2
—
40290
1
—
Bit 6
1
—
—
1
—
—
Setpoints (View)
None
—
Control Points (Set)
None
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
162
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-33 Liebert FPC™, Liebert PPC™—Status and Coil
Controller Liebert iCOM® v4
Liebert Products Liebert FPC, Liebert PPC
Available Points
Status
Coil
Number
of Bits
Scale
Notes / Units
Phase Loss
10001
—
1
—
Active on Alarm
Phase Rotation Error
10002
—
1
—
Active on Alarm
Phase Loss
10013
—
1
—
Active on Alarm
Phase Rotation Error
10014
—
1
—
Active on Alarm
10025
—
1
—
Active on Alarm
Data Label
Input Power 1
Input Power 2 (used only with 2nd VPMP controller)
Output Power 1
Output Overvoltage
Output Undervoltage
10026
—
1
—
Active on Alarm
Output Overcurrent
10027
—
1
—
Active on Alarm
Neutral Overcurrent
10028
—
1
—
Active on Alarm
Ground Overcurrent
10029
—
1
—
Active on Alarm
Output Voltage THD
10030
—
1
—
Active on Alarm
Frequency Deviation
10031
—
1
—
Active on Alarm
Transformer Overtemperature Power Off
10032
—
1
—
Active on Alarm
Transformer Overtemperature
10033
—
1
—
Active on Alarm
Transformer Temperature Sensor Fail
10034
—
1
—
Active on Alarm
Output Power 2 (used only with 2nd VPMP controller for Dual-output Transformer)
Output Overvoltage
10045
—
1
—
Active on Alarm
Output Undervoltage
10046
—
1
—
Active on Alarm
Output Overcurrent
10047
—
1
—
Active on Alarm
Neutral Overcurrent
10048
—
1
—
Active on Alarm
Ground Overcurrent
10049
—
1
—
Active on Alarm
Output Voltage THD
10050
—
1
—
Active on Alarm
Frequency Deviation
10051
—
1
—
Active on Alarm
Transformer Overtemperature Power Off
10052
—
1
—
Active on Alarm
Transformer Overtemperature
10053
—
1
—
Active on Alarm
Transformer Temperature Sensor Fail
10054
—
1
—
Active on Alarm
Panel Summary Alarm
10065
—
1
—
Active on Alarm
Panel Overvoltage
10066
—
1
—
Active on Alarm
Panel Undervoltage
10067
—
1
—
Active on Alarm
Panel 1
Panel Phase Overcurrent
10068
—
1
—
Active on Alarm
Panel Phase Overcurrent
10069
—
1
—
Active on Warning
Panel Neutral Overcurrent
10070
—
1
—
Active on Alarm
Panel Ground Overcurrent
10071
—
1
—
Active on Alarm
Panel Summary Alarm
10082
—
1
—
Active on Alarm
Panel Overvoltage
10083
—
1
—
Active on Alarm
Panel Undervoltage
10084
—
1
—
Active on Alarm
Panel 2
Panel Phase Overcurrent
10085
—
1
—
Active on Alarm
Panel Phase Overcurrent
10086
—
1
—
Active on Warning
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
163
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-33 Liebert FPC™, Liebert PPC™—Status and Coil (continued)
Controller Liebert iCOM® v4
Liebert Products Liebert FPC, Liebert PPC
Available Points
Data Label
Status
Coil
Number
of Bits
Scale
Notes / Units
Panel Neutral Overcurrent
10087
—
1
—
Active on Alarm
Panel Ground Overcurrent
10088
—
1
—
Active on Alarm
Panel Summary Alarm
10116
—
1
—
Active on Alarm
Panel Overvoltage
10117
—
1
—
Active on Alarm
Panel Undervoltage
10118
—
1
—
Active on Alarm
Panel 4
Panel Phase Overcurrent
10119
—
1
—
Active on Alarm
Panel Phase Overcurrent
10120
—
1
—
Active on Warning
Panel Neutral Overcurrent
10121
—
1
—
Active on Alarm
Panel Ground Overcurrent
10122
—
1
—
Active on Alarm
10133
—
1
—
Active on Alarm
Branch Overcurrent
10134
—
1
—
Active on Warning
Branch Undercurrent Warning
10135
—
1
—
Active on Alarm
10146
—
1
—
Active on Alarm
Branch Overcurrent
10147
—
1
—
Active on Warning
Branch Undercurrent Warning
10148
—
1
—
Active on Alarm
11212
—
1
—
Active on Alarm
Panel 1 Position 1
Branch Overcurrent
Panel 1 Position 2
Branch Overcurrent
Panel 1 Position 84
Branch Overcurrent
Branch Overcurrent
11213
—
1
—
Active on Warning
Branch Undercurrent Warning
11214
—
1
—
Active on Alarm
11225
—
1
—
Active on Alarm
Panel 2 Position 1
Branch Overcurrent
Branch Overcurrent
11226
—
1
—
Active on Warning
Branch Undercurrent Warning
11227
—
1
—
Active on Alarm
11238
—
1
—
Active on Alarm
Panel 2 Position 2
Branch Overcurrent
Branch Overcurrent
11239
—
1
—
Active on Warning
Branch Undercurrent Warning
11240
—
1
—
Active on Alarm
12304
—
1
—
Active on Alarm
Branch Overcurrent
12305
—
1
—
Active on Warning
Branch Undercurrent Warning
12306
—
1
—
Active on Alarm
12317
—
1
—
Active on Alarm
Branch Overcurrent
12318
—
1
—
Active on Warning
Branch Undercurrent Warning
12319
—
1
—
Active on Alarm
12330
—
1
—
Active on Alarm
Branch Overcurrent
12331
—
1
—
Active on Warning
Branch Undercurrent Warning
12332
—
1
—
Active on Alarm
Panel 2 Position 84
Branch Overcurrent
Panel 3 Position 1
Branch Overcurrent
Panel 3 Position 2
Branch Overcurrent
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
164
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-33 Liebert FPC™, Liebert PPC™—Status and Coil (continued)
Controller Liebert iCOM® v4
Liebert Products Liebert FPC, Liebert PPC
Available Points
Status
Coil
Number
of Bits
Scale
Notes / Units
13396
—
1
—
Active on Alarm
Branch Overcurrent
13397
—
1
—
Active on Warning
Branch Undercurrent Warning
13398
—
1
—
Active on Alarm
Branch Overcurrent
13409
—
1
—
Active on Alarm
Branch Overcurrent
13410
—
1
—
Active on Warning
Branch Undercurrent Warning
13411
—
1
—
Active on Alarm
13422
—
1
—
Active on Alarm
Branch Overcurrent
13423
—
1
—
Active on Warning
Branch Undercurrent Warning
13424
—
1
—
Active on Alarm
14488
—
1
—
Active on Alarm
Branch Overcurrent
14489
—
1
—
Active on Warning
Branch Undercurrent Warning
14490
—
1
—
Active on Alarm
Subfeed Phase Overcurrent
14501
—
1
—
Active on Alarm
Subfeed Phase Overcurrent
14502
—
1
—
Active on Warning
Subfeed Neutral Overcurrent
14503
—
1
—
Active on Alarm
Subfeed Ground Overcurrent
14504
—
1
—
Active on Alarm
Data Label
Panel 3 Position 84
Branch Overcurrent
Panel 4 Position 1
Panel 4 Position 2
Branch Overcurrent
Panel 4 Position 84
Branch Overcurrent
Subfeed 1
Subfeed 2
Subfeed Phase Overcurrent
14515
—
1
—
Active on Alarm
Subfeed Phase Overcurrent
14516
—
1
—
Active on Warning
Subfeed Neutral Overcurrent
14517
—
1
—
Active on Alarm
Subfeed Ground Overcurrent
14518
—
1
—
Active on Alarm
Subfeed Phase Overcurrent
15383
—
1
—
Active on Alarm
Subfeed Phase Overcurrent
15384
—
1
—
Active on Warning
Subfeed Neutral Overcurrent
15385
—
1
—
Active on Alarm
Subfeed Ground Overcurrent
15386
—
1
—
Active on Alarm
Subfeed 64
Customer Events 1 (Alarms 1 - 5 for 1 VPMP, Alarms 6 - 10 only if 2nd VPMP is used)
Event State
15397
—
1
—
Active on Alarm
15408
—
1
—
Active on Alarm
15496
—
1
—
Active on Alarm
Customer Events 2
Event State
Customer Events 10
Event State
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
165
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-33 Liebert FPC™, Liebert PPC™—Status and Coil (continued)
Controller Liebert iCOM® v4
Liebert Products Liebert FPC, Liebert PPC
Available Points
Data Label
Status
Coil
Number
of Bits
Scale
Notes / Units
15507
—
1
—
Active on Alarm
System
System Shutdown - EPO
System Shutdown - REPO
15508
—
1
—
Active on Alarm
Transformer Overtemperature Shutdown
15509
—
1
—
Active on Alarm
Transformer Overtemperature
15510
—
1
—
Active on Alarm
Equipment Temperature Sensor Fail
15511
—
1
—
Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
166
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Input Voltage A-B
30385
—
1
—
VAC
Input Voltage B-C
30386
—
1
—
VAC
Input Voltage C-A
30387
—
1
—
VAC
Data Label
Input Power 1
Input Power 2 (used only with 2nd VPMP controller)
Input Voltage A-B
30391
—
1
—
VAC
Input Voltage B-C
30392
—
1
—
VAC
Input Voltage C-A
30393
—
1
—
VAC
Output Voltage X-Y
30397
—
1
—
VAC
Output Voltage Y-Z
30398
—
1
—
VAC
Output Voltage Z-X
30399
—
1
—
VAC
Output Voltage Vx
30400
—
1
—
VAC
Output Voltage Vy
30401
—
1
—
VAC
Output Voltage Vz
30402
—
1
—
VAC
Output Current Ix
30403
—
1
—
A AC
Output Current Iy
30404
—
1
—
A AC
Output Current Iz
30405
—
1
—
A AC
Output Power 1
—
—
Output Neutral Current
30406
—
1
—
A AC
Ground Current
30407
—
1
10
A AC
Output Frequency
30408
—
1
—
Hz
Output Power (kVA)
30409
—
1
—
kVA
Output Power (kW)
30410
—
1
—
kW
Output kW-Hrs
30411
40411
2
—
kWH
Output Power Factor
30413
—
1
100
—
Output Percent Load
30414
—
1
—
%
Output Voltage Vx THD
30415
—
1
10
% THD
Output Voltage Vy THD
30416
—
1
10
% THD
Output Voltage Vz THD
30417
—
1
10
% THD
Output Current Ix THD
30418
—
1
10
% THD
Output Current Iy THD
30419
—
1
10
% THD
Output Current Iz THD
30420
—
1
10
% THD
Output Current Ix K-Factor
30421
—
1
10
—
Output Current Iy K-Factor
30422
—
1
10
—
Output Current Iz K-Factor
30423
—
1
10
—
Output Current Ix Crest Factor
30424
—
1
10
—
Output Current Iy Crest Factor
30425
—
1
10
—
Output Current Iz Crest Factor
30426
—
1
10
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
167
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Output Power 2 (used only with 2nd VPMP controller)
Output Voltage X-Y
30430
—
1
—
VAC
Output Voltage Y-Z
30431
—
1
—
VAC
Output Voltage Z-X
30432
—
1
—
VAC
Output Voltage Vx
30433
—
1
—
VAC
Output Voltage Vy
30434
—
1
—
VAC
Output Voltage Vz
30435
—
1
—
VAC
Output Current Ix
30436
—
1
—
A AC
Output Current Iy
30437
—
1
—
A AC
Output Current Iz
30438
—
1
—
A AC
Output Neutral Current
30439
—
1
—
A AC
Ground Current
30440
—
1
10
A AC
Output Frequency
30441
—
1
—
Hz
Output Power (kVA)
30442
—
1
—
kVA
Output Power (kW)
30443
—
1
—
kW
Output kW-Hrs
30444
40444
2
—
kWH
Output Power Factor
30446
—
1
100
—
Output Percent Load
30447
—
1
-
%
Output Voltage Vx THD
30448
—
1
10
% THD
Output Voltage Vy THD
30449
—
1
10
% THD
Output Voltage Vz THD
30450
—
1
10
% THD
Output Current Ix THD
30451
—
1
10
% THD
Output Current Iy THD
30452
—
1
10
% THD
Output Current Iz THD
30453
—
1
10
% THD
Output Current Ix K-Factor
30454
—
1
10
—
Output Current Iy K-Factor
30455
—
1
10
—
Output Current Iz K-Factor
30456
—
1
10
—
Output Current Ix Crest Factor
30457
—
1
10
—
Output Current Iy Crest Factor
30458
—
1
10
—
Output Current Iz Crest Factor
30459
—
1
10
—
30463
—
1
—
—
Panel 1
Columns of Breakers
Number of Breakers
30464
—
1
—
—
Panel Main Voltage X-Y
30465
—
1
—
VAC
Panel Main Voltage Y-Z
30466
—
1
—
VAC
Panel Main Voltage Z-X
30467
—
1
—
VAC
Panel Main Voltage X-N
30468
—
1
—
VAC
Panel Main Voltage Y-N
30469
—
1
—
VAC
Panel Main Voltage Z-N
30470
—
1
—
VAC
Panel Main Current Ix
30471
—
1
—
A AC
Panel Main Current Iy
30472
—
1
—
A AC
Panel Main Current Iz
30473
—
1
—
A AC
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
168
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Panel Main Neutral Current
30474
—
1
—
A AC
Panel Main Ground Current
30475
—
1
10
A AC
Panel Main Output Power (kVA)
30476
—
1
—
kVA
Panel Main Output Power (kW)
30477
—
1
—
kW
Panel Main Output kW-Hrs
30478
40478
2
10
kWH
Panel Main Output Power Factor
30480
—
1
100
—
Panel Main Output Percent Load
30481
—
1
—
%
Panel Main Voltage Vx THD
30482
—
1
10
% THD
Panel Main Voltage Vy THD
30483
—
1
10
% THD
Panel Main Voltage Vz THD
30484
—
1
10
% THD
Panel Main Current Ix THD
30485
—
1
10
% THD
Panel Main Current Iy THD
30486
—
1
10
% THD
Panel Main Current Iz THD
30487
—
1
10
% THD
Panel Main Current Ix Crest Factor
30488
—
1
10
—
Panel Main Current Iy Crest Factor
30489
—
1
10
—
Panel Main Current Iz Crest Factor
30490
—
1
10
—
30494
—
1
—
—
Panel 2
Columns of Breakers
Number of Breakers
30495
—
1
—
—
Panel Main Voltage X-Y
30496
—
1
—
VAC
Panel Main Voltage Y-Z
30497
—
1
—
VAC
Panel Main Voltage Z-X
30498
—
1
—
VAC
Panel Main Voltage X-N
30499
—
1
—
VAC
Panel Main Voltage Y-N
30500
—
1
—
VAC
Panel Main Voltage Z-N
30501
—
1
—
VAC
Panel Main Current Ix
30502
—
1
—
A AC
Panel Main Current Iy
30503
—
1
—
A AC
Panel Main Current Iz
30504
—
1
—
A AC
Panel Main Neutral Current
30505
—
1
—
A AC
Panel Main Ground Current
30506
—
1
10
A AC
Panel Main Output Power (kVA)
30507
—
1
—
kVA
Panel Main Output Power (kW)
30508
—
1
—
kW
Panel Main Output kW-Hrs
30509
40509
2
10
kWH
Panel Main Output Power Factor
30511
—
1
100
—
Panel Main Output Percent Load
30512
—
1
—
%
Panel Main Voltage Vx THD
30513
—
1
10
% THD
Panel Main Voltage Vy THD
30514
—
1
10
% THD
Panel Main Voltage Vz THD
30515
—
1
10
% THD
Panel Main Current Ix THD
30516
—
1
10
% THD
Panel Main Current Iy THD
30517
—
1
10
% THD
Panel Main Current Iz THD
30518
—
1
10
% THD
Panel Main Current Ix Crest Factor
30519
—
1
10
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
169
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Panel Main Current Iy Crest Factor
30520
—
1
10
—
Panel Main Current Iz Crest Factor
30521
—
1
10
—
30556
—
1
—
—
Data Label
Panel 4
Columns of Breakers
Number of Breakers
30557
—
1
—
—
Panel Main Voltage X-Y
30558
—
1
—
VAC
Panel Main Voltage Y-Z
30559
—
1
—
VAC
Panel Main Voltage Z-X
30560
—
1
—
VAC
Panel Main Voltage X-N
30561
—
1
—
VAC
Panel Main Voltage Y-N
30562
—
1
—
VAC
Panel Main Voltage Z-N
30563
—
1
—
VAC
Panel Main Current Ix
30564
—
1
—
A AC
Panel Main Current Iy
30565
—
1
—
A AC
Panel Main Current Iz
30566
—
1
—
A AC
Panel Main Neutral Current
30567
—
1
—
A AC
Panel Main Ground Current
30568
—
1
10
A AC
Panel Main Output Power (kVA)
30569
—
1
—
kVA
Panel Main Output Power (kW)
30570
—
1
—
kW
Panel Main Output kW-Hrs
30571
40571
2
10
kWH
Panel Main Output Power Factor
30573
—
1
100
—
Panel Main Output Percent Load
30574
—
1
-
%
Panel Main Voltage Vx THD
30575
—
1
10
% THD
Panel Main Voltage Vy THD
30576
—
1
10
% THD
Panel Main Voltage Vz THD
30577
—
1
10
% THD
Panel Main Current Ix THD
30578
—
1
10
% THD
Panel Main Current Iy THD
30579
—
1
10
% THD
Panel Main Current Iz THD
30580
—
1
10
% THD
Panel Main Current Ix Crest Factor
30581
—
1
10
—
Panel Main Current Iy Crest Factor
30582
—
1
10
—
Panel Main Current Iz Crest Factor
30583
—
1
10
—
Breaker position
30587
—
1
—
—
Branch Current Phase 1
30588
—
1
10
A AC
Branch Current Phase 2
30589
—
1
10
A AC
Panel 1 Position 1
Branch Current Phase 3
30590
—
1
10
A AC
Branch Output Power (kW)
30591
—
1
1000
kW
Output kW-Hrs
30592
—
2
1000
kWH
Branch Output Power Factor
30594
—
1
100
-
Branch Output Percent Load
30595
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
170
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Breaker position
30599
—
1
—
—
Branch Current Phase 1
30600
—
1
10
A AC
Branch Current Phase 2
30601
—
1
10
A AC
Data Label
Panel 1 Position 2
Branch Current Phase 3
30602
—
1
10
A AC
Branch Output Power (kW)
30603
—
1
1000
kW
Output kW-Hrs
30604
—
2
1000
kWH
Branch Output Power Factor
30606
—
1
100
—
Branch Output Percent Load
30607
—
1
—
%
Panel 1 Position 84
Breaker position
31583
—
1
—
—
Branch Current Phase 1
31584
—
1
10
A AC
Branch Current Phase 2
31585
—
1
10
A AC
Branch Current Phase 3
31586
—
1
10
A AC
Branch Output Power (kW)
31587
—
1
1000
kW
Output kW-Hrs
31588
—
2
1000
kWH
Branch Output Power Factor
31590
—
1
100
—
Branch Output Percent Load
31591
—
1
—
%
Breaker position
31595
—
1
-
—
Branch Current Phase 1
31596
—
1
10
A AC
Branch Current Phase 2
31597
—
1
10
A AC
Panel 2 Position 1
Branch Current Phase 3
31598
—
1
10
A AC
Branch Output Power (kW)
31599
—
1
1000
kW
Output kW-Hrs
31600
—
2
1000
kWH
Branch Output Power Factor
31602
—
1
100
—
Branch Output Percent Load
31603
—
1
—
%
Panel 2 Position 2
Breaker position
31607
—
1
—
—
Branch Current Phase 1
31608
—
1
10
A AC
Branch Current Phase 2
31609
—
1
10
A AC
Branch Current Phase 3
31610
—
1
10
A AC
Branch Output Power (kW)
31611
—
1
1000
kW
Output kW-Hrs
31612
—
2
1000
kWH
Branch Output Power Factor
31614
—
1
100
—
Branch Output Percent Load
31615
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
171
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Breaker position
32591
—
1
—
—
Branch Current Phase 1
32592
—
1
10
A AC
Branch Current Phase 2
32593
—
1
10
A AC
Data Label
Panel 2 Position 84
Branch Current Phase 3
32594
—
1
10
A AC
Branch Output Power (kW)
32595
—
1
1000
kW
Output kW-Hrs
32596
—
2
1000
kWH
Branch Output Power Factor
32598
—
1
100
—
Branch Output Percent Load
32599
—
1
—
%
Panel 3 Position 1
Breaker position
32603
—
1
—
—
Branch Current Phase 1
32604
—
1
10
A AC
Branch Current Phase 2
32605
—
1
10
A AC
Branch Current Phase 3
32606
—
1
10
A AC
Branch Output Power (kW)
32607
—
1
1000
kW
Output kW-Hrs
32608
—
2
1000
kWH
Branch Output Power Factor
32610
—
1
100
—
Branch Output Percent Load
32611
—
1
—
%
Breaker position
32615
—
1
—
—
Branch Current Phase 1
32616
—
1
10
A AC
Branch Current Phase 2
32617
—
1
10
A AC
Panel 3 Position 2
Branch Current Phase 3
32618
—
1
10
A AC
Branch Output Power (kW)
32619
—
1
1000
kW
Output kW-Hrs
32620
—
2
1000
kWH
Branch Output Power Factor
32622
—
1
100
—
Branch Output Percent Load
32623
—
1
—
%
Panel 3 Position 84
Breaker position
33599
—
1
—
—
Branch Current Phase 1
33600
—
1
10
A AC
Branch Current Phase 2
33601
—
1
10
A AC
Branch Current Phase 3
33602
—
1
10
A AC
Branch Output Power (kW)
33603
—
1
1000
kW
Output kW-Hrs
33604
—
2
1000
kWH
Branch Output Power Factor
33606
—
1
100
—
Branch Output Percent Load
33607
—
1
—
%
Panel 4 Position 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
172
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Breaker position
33611
—
1
—
—
Branch Current Phase 1
33612
—
1
10
A AC
Branch Current Phase 2
33613
—
1
10
A AC
Branch Current Phase 3
33614
—
1
10
A AC
Branch Output Power (kW)
33615
—
1
1000
kW
Output kW-Hrs
33616
—
2
1000
kWH
Branch Output Power Factor
33618
—
1
100
—
Branch Output Percent Load
33619
—
1
—
%
Breaker position
33623
—
1
—
—
Branch Current Phase 1
33624
—
1
10
A AC
Branch Current Phase 2
33625
—
1
10
A AC
Data Label
Scale
Notes / Units
Panel 4 Position 2
Branch Current Phase 3
33626
—
1
10
A AC
Branch Output Power (kW)
33627
—
1
1000
kW
Output kW-Hrs
33628
—
2
1000
kWH
Branch Output Power Factor
33630
—
1
100
—
Branch Output Percent Load
33631
—
1
-
%
Panel 4 Position 84
Breaker position
34607
—
1
—
—
Branch Current Phase 1
34608
—
1
10
A AC
Branch Current Phase 2
34609
—
1
10
A AC
Branch Current Phase 3
34610
—
1
10
A AC
Branch Output Power (kW)
34611
—
1
1000
kW
Output kW-Hrs
34612
—
2
1000
kWH
Branch Output Power Factor
34614
—
1
100
—
Branch Output Percent Load
34615
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
173
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Subfeed Current Ix
34619
—
1
—
A AC
Subfeed Current Iy
34620
—
1
—
A AC
Subfeed Current Iz
34621
—
1
—
A AC
Data Label
Subfeed 1
Subfeed Neutral Current
34622
—
1
—
A AC
Subfeed Ground Current
34623
—
1
10
A AC
Subfeed Output Power (kVA)
34624
—
1
—
kVA
Subfeed Output Power (kW)
34625
—
1
—
kW
Subfeed Output kW-Hrs
34626
44626
2
10
kWH
Subfeed Power Factor
34628
—
1
100
—
Subfeed Output Percent Load
34629
—
1
-
%
Subfeed Current Ix THD
34630
—
1
10
%
Subfeed Current Iy THD
34631
—
1
10
%
Subfeed Current Iz THD
34632
—
1
10
%
Subfeed Current Ix Crest Factor
34633
—
1
10
—
Subfeed Current Iy Crest Factor
34634
—
1
10
—
Subfeed Current Iz Crest Factor
34635
—
1
10
—
Subfeed Current Ix
34639
—
1
—
A AC
Subfeed Current Iy
34640
—
1
—
A AC
Subfeed Current Iz
34641
—
1
—
A AC
Subfeed Neutral Current
34642
—
1
—
A AC
Subfeed Ground Current
34643
—
1
10
A AC
Subfeed Output Power (kVA)
34644
—
1
—
kVA
Subfeed 2
Subfeed Output Power (kW)
34645
—
1
—
kW
Subfeed Output kW-Hrs
34646
44646
2
10
kWH
Subfeed Power Factor
34648
—
1
100
—
Subfeed Output Percent Load
34649
—
1
-
%
Subfeed Current Ix THD
34650
—
1
10
%
Subfeed Current Iy THD
34651
—
1
10
%
Subfeed Current Iz THD
34652
—
1
10
%
Subfeed Current Ix Crest Factor
34653
—
1
10
—
Subfeed Current Iy Crest Factor
34654
—
1
10
—
Subfeed Current Iz Crest Factor
34655
—
1
10
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
174
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued)
Controller VPMP
Liebert Products Liebert FPC, Liebert PPC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Subfeed Current Ix
35879
—
1
—
A AC
Subfeed Current Iy
35880
—
1
—
A AC
Subfeed Current Iz
35881
—
1
—
A AC
Data Label
Subfeed 64
Subfeed Neutral Current
35882
—
1
—
A AC
Subfeed Ground Current
35883
—
1
10
A AC
Subfeed Output Power (kVA)
35884
—
1
—
kVA
Subfeed Output Power (kW)
35885
—
1
—
kW
Subfeed Output kW-Hrs
35886
45886
2
10
kWH
Subfeed Power Factor
35888
—
1
100
—
Subfeed Output Percent Load
35889
—
1
-
%
Subfeed Current Ix THD
35890
—
1
10
%
Subfeed Current Iy THD
35891
—
1
10
%
Subfeed Current Iz THD
35892
—
1
10
%
Subfeed Current Ix Crest Factor
35893
—
1
10
—
Subfeed Current Iy Crest Factor
35894
—
1
10
—
Subfeed Current Iz Crest Factor
35895
—
1
10
—
System
System Status
System Event Acknowledge/Reset
System Date and Time
35899
—
1
—
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
—
45900
1
—
2 = Reset
4 = Acknowledge
39998
49998
2
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
175
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-35 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Status and Coil
Controller Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC,
Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Status
Coil
Number
of Bits
Scale
Notes / Units
Panel 1 – Panelboard Main 1 (if panelboards are installed)
Panel Summary Alarm
10065
—
1
—
Active on Alarm
Panel Overvoltage
10066
—
1
—
Active on Alarm
Panel Undervoltage
10067
—
1
—
Active on Alarm
Panel Phase Overcurrent
10068
—
1
—
Active on Alarm
Panel Phase Overcurrent
10069
—
1
—
Active on Warning
Panel Neutral Overcurrent
10070
—
1
—
Active on Alarm
Panel Ground Overcurrent
10071
—
1
—
Active on Alarm
Panel 2 – Panelboard Main 2 (if panelboards are installed)
Panel Summary Alarm
10082
—
1
—
Active on Alarm
Panel Overvoltage
10083
—
1
—
Active on Alarm
Panel Undervoltage
10084
—
1
—
Active on Alarm
Panel Phase Overcurrent
10085
—
1
—
Active on Alarm
Panel Phase Overcurrent
10086
—
1
—
Active on Warning
Panel Neutral Overcurrent
10087
—
1
—
Active on Alarm
Panel Ground Overcurrent
10088
—
1
—
Active on Alarm
Panel 4 – Panelboard Main 4 (if panelboards are installed)
Panel Summary Alarm
10116
—
1
—
Active on Alarm
Panel Overvoltage
10117
—
1
—
Active on Alarm
Panel Undervoltage
10118
—
1
—
Active on Alarm
Panel Phase Overcurrent
10119
—
1
—
Active on Alarm
Panel Phase Overcurrent
10120
—
1
—
Active on Warning
Panel Neutral Overcurrent
10121
—
1
—
Active on Alarm
Panel Ground Overcurrent
10122
—
1
—
Active on Alarm
Branch Overcurrent
10133
—
1
—
Active on Alarm
Branch Overcurrent
10134
—
1
—
Active on Warning
Branch Undercurrent Warning
10135
—
1
—
Active on Alarm
Branch Overcurrent
10146
—
1
—
Active on Alarm
Branch Overcurrent
10147
—
1
—
Active on Warning
Branch Undercurrent Warning
10148
—
1
—
Active on Alarm
Branch Overcurrent
11212
—
1
—
Active on Alarm
Branch Overcurrent
11213
—
1
—
Active on Warning
Branch Undercurrent Warning
11214
—
1
—
Active on Alarm
Branch Overcurrent
11225
—
1
—
Active on Alarm
Branch Overcurrent
11226
—
1
—
Active on Warning
Branch Undercurrent Warning
11227
—
1
—
Active on Alarm
Panel 1 Position 1
Panel 1 Position 2
Panel 1 Position 84
Panel 2 Position 1
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
176
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-35 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Status and Coil (continued)
Controller Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC,
Liebert RX, Liebert STS2/PDU
Available Points
Status
Coil
Number
of Bits
Scale
Notes / Units
Branch Overcurrent
11238
—
1
—
Active on Alarm
Branch Overcurrent
11239
—
1
—
Active on Warning
Branch Undercurrent Warning
11240
—
1
—
Active on Alarm
Branch Overcurrent
12304
—
1
—
Active on Alarm
Branch Overcurrent
12305
—
1
—
Active on Warning
Branch Undercurrent Warning
12306
—
1
—
Active on Alarm
Branch Overcurrent
12317
—
1
—
Active on Alarm
Branch Overcurrent
12318
—
1
—
Active on Warning
Branch Undercurrent Warning
12319
—
1
—
Active on Alarm
Branch Overcurrent
12330
—
1
—
Active on Alarm
Branch Overcurrent
12331
—
1
—
Active on Warning
Branch Undercurrent Warning
12332
—
1
—
Active on Alarm
Branch Overcurrent
13396
—
1
—
Active on Alarm
Branch Overcurrent
13397
—
1
—
Active on Warning
Branch Undercurrent Warning
13398
—
1
—
Active on Alarm
Branch Overcurrent
13409
—
1
—
Active on Alarm
Branch Overcurrent
13410
—
1
—
Active on Warning
Branch Undercurrent Warning
13411
—
1
—
Active on Alarm
Panel 4 Position 2
Branch Overcurrent
13422
—
1
—
Active on Alarm
Branch Overcurrent
13423
—
1
—
Active on Warning
Branch Undercurrent Warning
13424
—
1
—
Active on Alarm
Branch Overcurrent
14488
—
1
—
Active on Alarm
Branch Overcurrent
14489
—
1
—
Active on Warning
Branch Undercurrent Warning
14490
—
1
—
Active on Alarm
14501
—
1
—
Active on Alarm
Data Label
Panel 2 Position 2
Panel 2 Position 84
Panel 3 Position 1
Panel 3 Position 2
Panel 3 Position 84
Panel 4 Position 1
Panel 4 Position 84
Subfeed 1
Subfeed Phase Overcurrent
Subfeed Phase Overcurrent
14502
—
1
—
Active on Warning
Subfeed Neutral Overcurrent
14503
—
1
—
Active on Alarm
Subfeed Ground Overcurrent
14504
—
1
—
Active on Alarm
177
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-35 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Status and Coil (continued)
Controller Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC,
Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Status
Coil
Number
of Bits
Scale
Notes / Units
14515
—
1
—
Active on Alarm
Subfeed 2
Subfeed Phase Overcurrent
Subfeed Phase Overcurrent
14516
—
1
—
Active on Warning
Subfeed Neutral Overcurrent
14517
—
1
—
Active on Alarm
Subfeed Ground Overcurrent
14518
—
1
—
Active on Alarm
Subfeed 64
Subfeed Phase Overcurrent
15383
—
1
—
Active on Alarm
Subfeed Phase Overcurrent
15384
—
1
—
Active on Warning
Subfeed Neutral Overcurrent
15385
—
1
—
Active on Alarm
Subfeed Ground Overcurrent
15386
—
1
—
Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
178
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Input and Holding
Controller
Liebert Products
Liebert LDMF
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Panel 1
Columns of Breakers
30463
—
1
—
—
Number of Breakers
30464
—
1
—
—
Panel Main Voltage X-Y
30465
—
1
—
VAC
Panel Main Voltage Y-Z
30466
—
1
—
VAC
Panel Main Voltage Z-X
30467
—
1
—
VAC
Panel Main Voltage X-N
30468
—
1
—
VAC
Panel Main Voltage Y-N
30469
—
1
—
VAC
Panel Main Voltage Z-N
30470
—
1
—
VAC
Panel Main Current Ix
30471
—
1
—
A AC
Panel Main Current Iy
30472
—
1
—
A AC
Panel Main Current Iz
30473
—
1
—
A AC
Panel Main Neutral Current
30474
—
1
—
A AC
Panel Main Ground Current
30475
—
1
10
A AC
Panel Main Output Power (kVA)
30476
—
1
—
kVA
Panel Main Output Power (kW)
30477
—
1
—
kW
Panel Main Output kW-Hrs
30478
40478
2
10
kWH
Panel Main Output Power Factor
30480
—
1
100
—
Panel Main Output Percent Load
30481
—
1
—
%
Panel Main Voltage Vx THD
30482
—
1
10
% THD
Panel Main Voltage Vy THD
30483
—
1
10
% THD
Panel Main Voltage Vz THD
30484
—
1
10
% THD
Panel Main Current Ix THD
30485
—
1
10
% THD
Panel Main Current Iy THD
30486
—
1
10
% THD
Panel Main Current Iz THD
30487
—
1
10
% THD
Panel Main Current Ix Crest Factor
30488
—
1
10
—
Panel Main Current Iy Crest Factor
30489
—
1
10
—
Panel Main Current Iz Crest Factor
30490
—
1
10
—
Panel 2
Columns of Breakers
30494
—
1
—
—
Number of Breakers
30495
—
1
—
—
Panel Main Voltage X-Y
30496
—
1
—
VAC
Panel Main Voltage Y-Z
30497
—
1
—
VAC
Panel Main Voltage Z-X
30498
—
1
—
VAC
Panel Main Voltage X-N
30499
—
1
—
VAC
Panel Main Voltage Y-N
30500
—
1
—
VAC
Panel Main Voltage Z-N
30501
—
1
—
VAC
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
179
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued)
Controller
Liebert Products
Liebert LDMF
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Panel Main Current Ix
30502
—
1
—
A AC
Panel Main Current Iy
30503
—
1
—
A AC
Panel Main Current Iz
30504
—
1
—
A AC
Panel Main Neutral Current
30505
—
1
—
A AC
Panel Main Ground Current
30506
—
1
10
A AC
Data Label
Panel Main Output Power (kVA)
30507
—
1
—
kVA
Panel Main Output Power (kW)
30508
—
1
—
kW
Panel Main Output kW-Hrs
30509
40509
2
10
kWH
Panel Main Output Power Factor
30511
—
1
100
—
Panel Main Output Percent Load
30512
—
1
—
%
Panel Main Voltage Vx THD
30513
—
1
10
% THD
Panel Main Voltage Vy THD
30514
—
1
10
% THD
Panel Main Voltage Vz THD
30515
—
1
10
% THD
Panel Main Current Ix THD
30516
—
1
10
% THD
Panel Main Current Iy THD
30517
—
1
10
% THD
Panel Main Current Iz THD
30518
—
1
10
% THD
Panel Main Current Ix Crest Factor
30519
—
1
10
—
Panel Main Current Iy Crest Factor
30520
—
1
10
—
Panel Main Current Iz Crest Factor
30521
—
1
10
—
30556
—
1
—
—
Number of Breakers
30557
—
1
—
—
Panel Main Voltage X-Y
30558
—
1
—
VAC
Panel Main Voltage Y-Z
30559
—
1
—
VAC
Panel Main Voltage Z-X
30560
—
1
—
VAC
Panel Main Voltage X-N
30561
—
1
—
VAC
Panel Main Voltage Y-N
30562
—
1
—
VAC
Panel Main Voltage Z-N
30563
—
1
—
VAC
Panel Main Current Ix
30564
—
1
—
A AC
Panel Main Current Iy
30565
—
1
—
A AC
Panel Main Current Iz
30566
—
1
—
A AC
Panel Main Neutral Current
30567
—
1
—
A AC
Panel Main Ground Current
30568
—
1
10
A AC
Panel 4
Columns of Breakers
Panel Main Output Power (kVA)
30569
—
1
—
kVA
Panel Main Output Power (kW)
30570
—
1
—
kW
Panel Main Output kW-Hrs
30571
40571
2
10
kWH
Panel Main Output Power Factor
30573
—
1
100
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
180
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued)
Controller
Liebert Products
Liebert LDMF
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Panel Main Output Percent Load
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
30574
—
1
-
%
Panel Main Voltage Vx THD
30575
—
1
10
% THD
Panel Main Voltage Vy THD
30576
—
1
10
% THD
Panel Main Voltage Vz THD
30577
—
1
10
% THD
Panel Main Current Ix THD
30578
—
1
10
% THD
Panel Main Current Iy THD
30579
—
1
10
% THD
Panel Main Current Iz THD
30580
—
1
10
% THD
Panel Main Current Ix Crest Factor
30581
—
1
10
—
Panel Main Current Iy Crest Factor
30582
—
1
10
—
Panel Main Current Iz Crest Factor
30583
—
1
10
—
Breaker position
30587
—
1
—
—
Branch Current Phase 1
30588
—
1
10
A AC
Branch Current Phase 2
30589
—
1
10
A AC
Branch Current Phase 3
30590
—
1
10
A AC
Branch Output Power (kW)
30591
—
1
1000
kW
Output kW-Hrs
30592
—
2
1000
kWH
Branch Output Power Factor
30594
—
1
100
-
Branch Output Percent Load
30595
—
1
—
%
Breaker position
30599
—
1
—
—
Branch Current Phase 1
30600
—
1
10
A AC
Branch Current Phase 2
30601
—
1
10
A AC
Branch Current Phase 3
30602
—
1
10
A AC
Branch Output Power (kW)
30603
—
1
1000
kW
Output kW-Hrs
30604
—
2
1000
kWH
Branch Output Power Factor
30606
—
1
100
—
Branch Output Percent Load
30607
—
1
—
%
Breaker position
31583
—
1
—
—
Branch Current Phase 1
31584
—
1
10
A AC
Branch Current Phase 2
31585
—
1
10
A AC
Branch Current Phase 3
31586
—
1
10
A AC
Branch Output Power (kW)
31587
—
1
1000
kW
Panel 1 Position 1
Panel 1 Position 2
Panel 1 Position 84
Output kW-Hrs
31588
—
2
1000
kWH
Branch Output Power Factor
31590
—
1
100
—
Branch Output Percent Load
31591
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
181
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued)
Controller
Liebert Products
Liebert LDMF
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Input
Register
Holding
Register
# of
Reg.
Breaker position
31595
—
1
—
—
Branch Current Phase 1
31596
—
1
10
A AC
Branch Current Phase 2
31597
—
1
10
A AC
Branch Current Phase 3
31598
—
1
10
A AC
Branch Output Power (kW)
31599
—
1
1000
kW
Output kW-Hrs
31600
—
2
1000
kWH
Branch Output Power Factor
31602
—
1
100
—
Branch Output Percent Load
31603
—
1
—
%
Breaker position
31607
—
1
—
—
Branch Current Phase 1
31608
—
1
10
A AC
Branch Current Phase 2
31609
—
1
10
A AC
Branch Current Phase 3
31610
—
1
10
A AC
Branch Output Power (kW)
31611
—
1
1000
kW
Output kW-Hrs
31612
—
2
1000
kWH
Branch Output Power Factor
31614
—
1
100
—
Branch Output Percent Load
31615
—
1
—
%
Breaker position
32591
—
1
—
—
Branch Current Phase 1
32592
—
1
10
A AC
Branch Current Phase 2
32593
—
1
10
A AC
Branch Current Phase 3
32594
—
1
10
A AC
Branch Output Power (kW)
32595
—
1
1000
kW
Output kW-Hrs
32596
—
2
1000
kWH
Branch Output Power Factor
32598
—
1
100
—
Branch Output Percent Load
32599
—
1
—
%
Breaker position
32603
—
1
—
—
Branch Current Phase 1
32604
—
1
10
A AC
Branch Current Phase 2
32605
—
1
10
A AC
Branch Current Phase 3
32606
—
1
10
A AC
Branch Output Power (kW)
32607
—
1
1000
kW
Data Label
Scale
Notes / Units
Panel 2 Position 1
Panel 2 Position 2
Panel 2 Position 84
Panel 3 Position 1
Output kW-Hrs
32608
—
2
1000
kWH
Branch Output Power Factor
32610
—
1
100
—
Branch Output Percent Load
32611
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
182
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued)
Controller
Liebert Products
Liebert LDMF
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Input
Register
Holding
Register
# of
Reg.
Breaker position
32615
—
1
—
—
Branch Current Phase 1
32616
—
1
10
A AC
Branch Current Phase 2
32617
—
1
10
A AC
Branch Current Phase 3
32618
—
1
10
A AC
Branch Output Power (kW)
32619
—
1
1000
kW
Output kW-Hrs
32620
—
2
1000
kWH
Branch Output Power Factor
32622
—
1
100
—
Branch Output Percent Load
32623
—
1
—
%
Breaker position
33599
—
1
—
—
Branch Current Phase 1
33600
—
1
10
A AC
Branch Current Phase 2
33601
—
1
10
A AC
Data Label
Scale
Notes / Units
Panel 3 Position 2
Panel 3 Position 84
Branch Current Phase 3
33602
—
1
10
A AC
Branch Output Power (kW)
33603
—
1
1000
kW
Output kW-Hrs
33604
—
2
1000
kWH
Branch Output Power Factor
33606
—
1
100
—
Branch Output Percent Load
33607
—
1
—
%
Breaker position
33611
—
1
—
—
Branch Current Phase 1
33612
—
1
10
A AC
Branch Current Phase 2
33613
—
1
10
A AC
Branch Current Phase 3
33614
—
1
10
A AC
Branch Output Power (kW)
33615
—
1
1000
kW
Output kW-Hrs
33616
—
2
1000
kWH
Branch Output Power Factor
33618
—
1
100
—
Branch Output Percent Load
33619
—
1
—
%
Breaker position
33623
—
1
—
—
Branch Current Phase 1
33624
—
1
10
A AC
Branch Current Phase 2
33625
—
1
10
A AC
Branch Current Phase 3
33626
—
1
10
A AC
Branch Output Power (kW)
33627
—
1
1000
kW
Panel 4 Position 1
Panel 4 Position 2
Output kW-Hrs
33628
—
2
1000
kWH
Branch Output Power Factor
33630
—
1
100
—
Branch Output Percent Load
33631
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
183
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued)
Controller
Liebert Products
Liebert LDMF
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Input
Register
Holding
Register
# of
Reg.
Breaker position
34607
—
1
—
—
Branch Current Phase 1
34608
—
1
10
A AC
Branch Current Phase 2
34609
—
1
10
A AC
Branch Current Phase 3
34610
—
1
10
A AC
Branch Output Power (kW)
34611
—
1
1000
kW
Output kW-Hrs
34612
—
2
1000
kWH
Branch Output Power Factor
34614
—
1
100
—
Branch Output Percent Load
34615
—
1
—
%
Subfeed Current Ix
34619
—
1
—
A AC
Subfeed Current Iy
34620
—
1
—
A AC
Subfeed Current Iz
34621
—
1
—
A AC
Subfeed Neutral Current
34622
—
1
—
A AC
Subfeed Ground Current
34623
—
1
10
A AC
Subfeed Output Power (kVA)
34624
—
1
—
kVA
Subfeed Output Power (kW)
34625
—
1
—
kW
Subfeed Output kW-Hrs
34626
44626
2
10
kWH
Subfeed Power Factor
34628
—
1
100
—
Subfeed Output Percent Load
34629
—
1
—
%
Subfeed Current Ix THD
34630
—
1
10
%
Subfeed Current Iy THD
34631
—
1
10
%
Subfeed Current Iz THD
34632
—
1
10
%
Subfeed Current Ix Crest Factor
34633
—
1
10
—
Subfeed Current Iy Crest Factor
34634
—
1
10
—
Subfeed Current Iz Crest Factor
34635
—
1
10
—
Subfeed Current Ix
34639
—
1
—
A AC
Subfeed Current Iy
34640
—
1
—
A AC
Subfeed Current Iz
34641
—
1
—
A AC
Subfeed Neutral Current
34642
—
1
—
A AC
Subfeed Ground Current
34643
—
1
10
A AC
Subfeed Output Power (kVA)
34644
—
1
—
kVA
Data Label
Scale
Notes / Units
Panel 4 Position 84
Subfeed 1
Subfeed 2
Subfeed Output Power (kW)
34645
—
1
—
kW
Subfeed Output kW-Hrs
34646
44646
2
10
kWH
Subfeed Power Factor
34648
—
1
100
—
Subfeed Output Percent Load
34649
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
184
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™,
Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued)
Controller
Liebert Products
Liebert LDMF
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Subfeed Current Ix THD
34650
—
1
10
%
Subfeed Current Iy THD
34651
—
1
10
%
Subfeed Current Iz THD
34652
—
1
10
%
Subfeed Current Ix Crest Factor
34653
—
1
10
—
Subfeed Current Iy Crest Factor
34654
—
1
10
—
Subfeed Current Iz Crest Factor
34655
—
1
10
—
Subfeed Current Ix
35879
—
1
—
A AC
Subfeed Current Iy
35880
—
1
—
A AC
Subfeed Current Iz
35881
—
1
—
A AC
Subfeed Neutral Current
35882
—
1
—
A AC
Subfeed Ground Current
35883
—
1
10
A AC
Subfeed Output Power (kVA)
35884
—
1
—
kVA
Data Label
Subfeed 64
Subfeed Output Power (kW)
35885
—
1
—
kW
Subfeed Output kW-Hrs
35886
45886
2
10
kWH
Subfeed Power Factor
35888
—
1
100
—
Subfeed Output Percent Load
35889
—
1
-
%
Subfeed Current Ix THD
35890
—
1
10
%
Subfeed Current Iy THD
35891
—
1
10
%
Subfeed Current Iz THD
35892
—
1
10
%
Subfeed Current Ix Crest Factor
35893
—
1
10
—
Subfeed Current Iy Crest Factor
35894
—
1
10
—
Subfeed Current Iz Crest Factor
35895
—
1
10
—
System
System Status
System Event Acknowledge/Reset
System Date and Time
35899
—
1
—
1 = Normal
Operation
2 = Startup
8 = Normal with
Warning
16 = Normal
with Alarm
32 = Abnormal
Operation
—
45900
1
—
2 = Reset
4=
Acknowledge
39998
49998
2
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
185
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-37 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Status and Coil
Controller Liebert CPM
Liebert Products Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC
Available Points
Data Label
Status
Coil
Number
of Bits
Scale
Notes / Units
Panel 1 – Panelboard Main 1 (if panelboards are installed)
Panel Summary Alarm
10065
—
1
—
Active on Alarm
Panel Overvoltage
10066
—
1
—
Active on Alarm
Panel Undervoltage
10067
—
1
—
Active on Alarm
Panel Phase Overcurrent
10068
—
1
—
Active on Alarm
Panel Phase Overcurrent
10069
—
1
—
Active on Warning
Panel Neutral Overcurrent
10070
—
1
—
Active on Alarm
Panel Ground Overcurrent
10071
—
1
—
Active on Alarm
Panel 2 – Panelboard Main 2 (if panelboards are installed)
Panel Summary Alarm
10082
—
1
—
Active on Alarm
Panel Overvoltage
10083
—
1
—
Active on Alarm
Panel Undervoltage
10084
—
1
—
Active on Alarm
Panel Phase Overcurrent
10085
—
1
—
Active on Alarm
Panel Phase Overcurrent
10086
—
1
—
Active on Warning
Panel Neutral Overcurrent
10087
—
1
—
Active on Alarm
Panel Ground Overcurrent
10088
—
1
—
Active on Alarm
Panel 4 – Panelboard Main 4 (if panelboards are installed)
Panel Summary Alarm
10116
—
1
—
Active on Alarm
Panel Overvoltage
10117
—
1
—
Active on Alarm
Panel Undervoltage
10118
—
1
—
Active on Alarm
Panel Phase Overcurrent
10119
—
1
—
Active on Alarm
Panel Phase Overcurrent
10120
—
1
—
Active on Warning
Panel Neutral Overcurrent
10121
—
1
—
Active on Alarm
Panel Ground Overcurrent
10122
—
1
—
Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
186
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-38 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Input and Holding
Controller
Liebert Products
Liebert CPM
Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Columns of Breakers
30463
—
1
—
—
Number of Breakers
30464
—
1
—
—
Panel Main Voltage X-Y
30465
—
1
—
VAC
Panel Main Voltage Y-Z
30466
—
1
—
VAC
Panel Main Voltage Z-X
30467
—
1
—
VAC
Panel Main Voltage X-N
30468
—
1
—
VAC
Panel Main Voltage Y-N
30469
—
1
—
VAC
Data Label
Panel 1
Panel Main Voltage Z-N
30470
—
1
—
VAC
Panel Main Current Ix
30471
—
1
—
A AC
Panel Main Current Iy
30472
—
1
—
A AC
Panel Main Current Iz
30473
—
1
—
A AC
Panel Main Neutral Current
30474
—
1
—
A AC
Panel Main Ground Current
30475
—
1
10
A AC
Panel Main Output Power (kVA)
30476
—
1
—
kVA
Panel Main Output Power (kW)
30477
—
1
—
kW
Panel Main Output kW-Hrs
30478
40478
2
10
kWH
Panel Main Output Power Factor
30480
—
1
100
—
Panel Main Output Percent Load
30481
—
1
—
%
Panel Main Voltage Vx THD
30482
—
1
10
% THD
Panel Main Voltage Vy THD
30483
—
1
10
% THD
Panel Main Voltage Vz THD
30484
—
1
10
% THD
Panel Main Current Ix THD
30485
—
1
10
% THD
Panel Main Current Iy THD
30486
—
1
10
% THD
Panel Main Current Iz THD
30487
—
1
10
% THD
Panel Main Current Ix Crest Factor
30488
—
1
10
—
Panel Main Current Iy Crest Factor
30489
—
1
10
—
Panel Main Current Iz Crest Factor
30490
—
1
10
—
Columns of Breakers
30494
—
1
—
—
Number of Breakers
30495
—
1
—
—
Panel Main Voltage X-Y
30496
—
1
—
VAC
Panel Main Voltage Y-Z
30497
—
1
—
VAC
Panel Main Voltage Z-X
30498
—
1
—
VAC
Panel Main Voltage X-N
30499
—
1
—
VAC
Panel Main Voltage Y-N
30500
—
1
—
VAC
Panel 2
Panel Main Voltage Z-N
30501
—
1
—
VAC
Panel Main Current Ix
30502
—
1
—
A AC
Panel Main Current Iy
30503
—
1
—
A AC
Panel Main Current Iz
30504
—
1
—
A AC
Panel Main Neutral Current
30505
—
1
—
A AC
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
187
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-38 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Input and Holding (continued)
Controller
Liebert Products
Liebert CPM
Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Panel Main Ground Current
30506
—
1
10
A AC
Panel Main Output Power (kVA)
30507
—
1
—
kVA
Data Label
Panel Main Output Power (kW)
30508
—
1
—
kW
Panel Main Output kW-Hrs
30509
40509
2
10
kWH
Panel Main Output Power Factor
30511
—
1
100
—
Panel Main Output Percent Load
30512
—
1
—
%
Panel Main Voltage Vx THD
30513
—
1
10
% THD
Panel Main Voltage Vy THD
30514
—
1
10
% THD
Panel Main Voltage Vz THD
30515
—
1
10
% THD
Panel Main Current Ix THD
30516
—
1
10
% THD
Panel Main Current Iy THD
30517
—
1
10
% THD
Panel Main Current Iz THD
30518
—
1
10
% THD
Panel Main Current Ix Crest Factor
30519
—
1
10
—
Panel Main Current Iy Crest Factor
30520
—
1
10
—
Panel Main Current Iz Crest Factor
30521
—
1
10
—
Panel 4
Columns of Breakers
30556
—
1
—
—
Number of Breakers
30557
—
1
—
—
Panel Main Voltage X-Y
30558
—
1
—
VAC
Panel Main Voltage Y-Z
30559
—
1
—
VAC
Panel Main Voltage Z-X
30560
—
1
—
VAC
Panel Main Voltage X-N
30561
—
1
—
VAC
Panel Main Voltage Y-N
30562
—
1
—
VAC
Panel Main Voltage Z-N
30563
—
1
—
VAC
Panel Main Current Ix
30564
—
1
—
A AC
Panel Main Current Iy
30565
—
1
—
A AC
Panel Main Current Iz
30566
—
1
—
A AC
Panel Main Neutral Current
30567
—
1
—
A AC
Panel Main Ground Current
30568
—
1
10
A AC
Panel Main Output Power (kVA)
30569
—
1
—
kVA
Panel Main Output Power (kW)
30570
—
1
—
kW
Panel Main Output kW-Hrs
30571
40571
2
10
kWH
Panel Main Output Power Factor
30573
—
1
100
—
Panel Main Output Percent Load
30574
—
1
-
%
Panel Main Voltage Vx THD
30575
—
1
10
% THD
Panel Main Voltage Vy THD
30576
—
1
10
% THD
Panel Main Voltage Vz THD
30577
—
1
10
% THD
Panel Main Current Ix THD
30578
—
1
10
% THD
Panel Main Current Iy THD
30579
—
1
10
% THD
Panel Main Current Iz THD
30580
—
1
10
% THD
Panel Main Current Ix Crest Factor
30581
—
1
10
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
188
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-38 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Input and Holding (continued)
Controller
Liebert Products
Liebert CPM
Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Panel Main Current Iy Crest Factor
30582
—
1
10
—
Panel Main Current Iz Crest Factor
30583
—
1
10
—
Data Label
System
System Status
System Event Acknowledge/Reset
System Date and Time
35899
—
1
—
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
—
45900
1
—
2 = Reset
4 = Acknowledge
39998
49998
2
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
189
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-39 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™,
Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Glossary
Data Label
Data Description
Branch Current Phase 1
Branch breaker Phase 1 RMS current
Branch Current Phase 2
Branch Breaker Phase 2 RMS current
Branch Current Phase 3
Branch breaker Phase 3 RMS current
Branch Output Percent Load
Branch breaker percent load of rated current
Branch Output Power (W)
Branch breaker W
Branch Output Power Factor
Branch breaker Power Factor (real power/apparent power)
Branch Overcurrent
Branch breaker current has exceeded the limit.
Branch Undercurrent Warning
Branch breaker current is less than the limit.
Breaker position
Panelboard pole position of the branch breaker. First position if 2 or 3 pole breaker
Columns of Breakers
The breakers in this panel are physically arranged in this many columns.
Equipment Temperature Sensor Fail
Transformer temperature sensor has failed
Event State
Alarm present
Frequency Deviation
The output frequency is outside a specified range.
Ground Current
Unit Ground RMS current.
Ground Overcurrent
Unit ground current has exceeded the limit.
Input Voltage A-B
Unit Input RMS Voltage between Phase A and Phase B
Input Voltage B-C
Unit Input RMS Voltage between Phase B and Phase C
Input Voltage C-A
Unit Input RMS Voltage between Phase C and Phase A
Neutral Overcurrent
Unit neutral current has exceeded the limit.
Number of Breakers
Number of Breakers in this panelboard.
Output Current Ix Crest Factor
Unit phase X Current Crest Factor (peak/RMS).
Output Current Ix K-Factor
Unit output Current Harmonic K-Factor for phase X.
Output Current Ix THD
Unit Current Total Harmonic Distortion for phase X.
Output Current Ix
Unit Phase X output RMS current.
Output Current Iy Crest Factor
Unit phase Y Current Crest Factor (peak/RMS).
Output Current Iy K-Factor
Unit output Current Harmonic K-Factor for phase Y.
Output Current Iy THD
Unit Current Total Harmonic Distortion for phase Y.
Output Current Iy
Unit Phase Y output RMS current.
Output Current Iz Crest Factor
Unit phase Z Current Crest Factor (peak/RMS).
Output Current Iz K-Factor
Unit output Current Harmonic K-Factor for phase Z.
Output Current Iz THD
Unit Current Total Harmonic Distortion for phase Z.
Output Current Iz
Unit Phase Z output RMS current.
Output Frequency
The system output frequency.
Output kW-Hrs
Branch Breaker accumulated KW-Hours since last KW-Hours reset.
Output kW-Hrs
Unit accumulated KW-Hours since last KW-Hours reset.
Output Neutral Current
Unit output Neutral RMS current.
Output Overcurrent
Unit phase current has exceeded the limit.
Output Overvoltage
Unit voltage has exceeded the limit.
Output Percent Load
Unit percent load of rated current
Output Power (kVA)
Unit output kVA
Output Power (kW)
Unit output KW
Output Power Factor
Unit output Power Factor (real power/apparent power)
Output Undervoltage
Unit voltage is less than the limit.
Output Voltage THD
Unit output Voltage Total Harmonic Distortion has exceeded the limit.
Output Voltage Vx THD
Unit Voltage Total Harmonic Distortion for phase X.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
190
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-39 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™,
Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Glossary (continued)
Data Label
Data Description
Output Voltage Vx
Unit output RMS voltage between phase X and Neutral
Output Voltage Vy THD
Unit Voltage Total Harmonic Distortion for phase Y.
Output Voltage Vy
Unit output RMS voltage between phase Y and Neutral
Output Voltage Vz THD
Unit Voltage Total Harmonic Distortion for phase Z.
Output Voltage Vz
Unit output RMS voltage between phase Z and Neutral
Output Voltage X-Y
Unit output RMS voltage between phases X and Y
Output Voltage Y-Z
Unit output RMS voltage between phases Y and Z.
Output Voltage Z-X
Unit output RMS voltage between phases Z and X.
Panel Ground Overcurrent
Panelboard Ground current has exceeded the limit.
Panel Main Current Ix Crest Factor
Panelboard phase X Current Crest Factor (peak/RMS).
Panel Main Current Ix THD
Current Total Harmonic Distortion for Panelboard phase X.
Panel Main Current Ix
Panelboard RMS current for phase X.
Panel Main Current Iy Crest Factor
Panelboard phase Y Current Crest Factor (peak/RMS).
Panel Main Current Iy THD
Current Total Harmonic Distortion for Panelboard phase Y.
Panel Main Current Iy
Panelboard RMS current for phase Y.
Panel Main Current Iz Crest Factor
Panelboard phase Z Current Crest Factor (peak/RMS).
Panel Main Current Iz THD
Current Total Harmonic Distortion for Panelboard phase Z.
Panel Main Current Iz
Panelboard RMS current for phase Z.
Panel Main Ground Current
Panelboard Ground RMS current.
Panel Main Neutral Current
Panelboard Neutral RMS current.
Panel Main Output kW-Hrs
Panelboard accumulated KW-Hours since last KW-Hours reset.
Panel Main Output Percent Load
Panelboard percent load of rated current
Panel Main Output Power (kVA)
Panelboard output kVA.
Panel Main Output Power (kW)
Panelboard output KW
Panel Main Output Power Factor
Panelboard Output Power Factor (real power/apparent power)
Panel Main Voltage Vx THD
Voltage Total Harmonic Distortion for Panelboard phase X.
Panel Main Voltage Vy THD
Voltage Total Harmonic Distortion for Panelboard phase Y.
Panel Main Voltage Vz THD
Voltage Total Harmonic Distortion for Panelboard phase Z.
Panel Main Voltage X-N
Panelboard RMS voltage between Phase X and Neutral.
Panel Main Voltage X-Y
Panelboard RMS voltage between phases X and Y.
Panel Main Voltage Y-N
Panelboard RMS voltage between Phase Y and Neutral.
Panel Main Voltage Y-Z
Panelboard RMS voltage between phases Y and Z.
Panel Main Voltage Z-N
Panelboard RMS voltage between Phase Z and Neutral.
Panel Main Voltage Z-X
Panelboard RMS voltage between phases Z and X.
Panel Neutral Overcurrent
Panelboard Neutral current has exceeded the limit.
Panel Overvoltage
Panelboard voltage has exceeded the limit.
Panel Phase Overcurrent
Panelboard phase current has exceeded the limit.
Panel Summary Alarm
Panelboard Summary Alarm. Annunciates upon occurrence of any branch or
panelboard main breaker alarm.
Panel Undervoltage
Panelboard voltage is less than the limit.
Phase Loss
Voltage and/or Frequency on one or more of the phases is outside the limit.
Phase Rotation Error
Unit input phase sequence is not A, B, C. The phase sequence should be verified
and corrected.
Subfeed Current Ix Crest Factor
Subfeed breaker phase X Current Crest Factor (peak/RMS).
Subfeed Current Ix THD
Current Total Harmonic Distortion for Subfeed breaker phase X.
Subfeed Current Ix
Subfeed breaker RMS current for phase X.
191
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-39 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™,
Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Glossary (continued)
Data Label
Data Description
Subfeed Current Iy Crest Factor
Subfeed breaker phase Y Current Crest Factor (peak/RMS).
Subfeed Current Iy THD
Current Total Harmonic Distortion for Subfeed breaker phase Y.
Subfeed Current Iy
Subfeed breaker RMS current for phase Y.
Subfeed Current Iz Crest Factor
Subfeed breaker phase Z Current Crest Factor (peak/RMS).
Subfeed Current Iz THD
Current Total Harmonic Distortion for Subfeed breaker phase Z.
Subfeed Current Iz
Subfeed breaker RMS current for phase Z.
Subfeed Ground Current
Subfeed breaker Ground RMS current.
Subfeed Ground Overcurrent
Subfeed breaker Ground current has exceeded the limit.
Subfeed Neutral Current
Subfeed breaker Neutral RMS current.
Subfeed Neutral Overcurrent
Subfeed breaker Neutral current has exceeded the limit.
Subfeed Output kW-Hrs
Subfeed breaker accumulated KW-Hours since last KW-Hours reset.
Subfeed Output Percent Load
Subfeed breaker percent load of rated current
Subfeed Output Power (kVA)
Subfeed breaker output kVA.
Subfeed Output Power (kW)
Subfeed breaker output KW
Subfeed Phase Overcurrent
Subfeed breaker phase current has exceeded the limit.
Subfeed Power Factor
Subfeed breaker Power Factor (real power/apparent power)
System Date and Time
Unit date and time
System Event Acknowledge/Reset
Alarm Present/Reset
System Shutdown - EPO
Unit shutdown by Emergency Power Off (EPO) switch
System Shutdown - REPO
Unit shutdown by Remote Emergency Power Off (REPO) switch
System Status
The operating status for the system
Transformer Overtemperature Power
Off
Output power shutdown due to high transformer temperature
Transformer Overtemperature
Shutdown
Unit shutdown due to transformer over temperature
Transformer Overtemperature
Transformer temperature has exceeded the limit
Transformer Overtemperature
Transformer temperature has exceeded the limit
Transformer Temperature Sensor Fail
Transformer temperature sensor has failed
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
192
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-40 Liebert STS™, Liebert STS/PDU™—Input and Holding—STS
Controller STS
Liebert Products
Liebert STS
Liebert STS/PDU
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Transfer Count
—
40001
1
—
—
Preferred Source
—
40002
1
—
1=Source 1 / 2=Source 2
Data Description
Notes / Units
Status Points (View)
Load On Source
—
40003
1
—
1=Source 1 / 2=Source 2
Source 1 Voltage A-B
—
40004
1
—
V
Source 1 Voltage B-C
—
40005
1
—
V
Source 1 Voltage C-A
—
40006
1
—
V
Source 1 Current A
—
40007
1
—
A
Source 1 Current B
—
40008
1
—
A
Source 1 Current C
—
40009
1
—
A
Source 1 Frequency
—
40010
1
10
Hz
Source 2 Voltage A-B
—
40011
1
—
V
Source 2 Voltage B-C
—
40012
1
—
V
Source 2 Voltage C-A
—
40013
1
—
V
Source 2 Current A
—
40014
1
—
A
Source 2 Current B
—
40015
1
—
A
Source 2 Current C
—
40016
1
—
A
Source 2 Frequency
—
40017
1
10
Hz
kW
—
40018
1
—
kW
kVA
—
40019
1
—
kVA
Auto Transfer Timer
—
40020
1
—
Seconds
Nominal Voltage Deviation
—
40021
1
—
V
Phase Differential Limit
—
40022
1
—
Degree
Frequency Deviation
—
40023
1
10
Hz
Alarm Points
Communications
—
40289
1
—
Bit 0
Logic Failure
—
40289
1
—
Bit 1
Equipment Overtemp
—
40289
1
—
Bit 2
Power Supply 1 Fault
—
40289
1
—
Bit 3
Source 1 Overvoltage
—
40289
1
—
Bit 4
Source 1 Undervoltage
—
40289
1
—
Bit 5
Source 2 Overvoltage
—
40289
1
—
Bit 6
Source 2 Undervoltage
—
40289
1
—
Bit 7
Source 1 Overload
—
40289
1
—
Bit 8
Shorted SCR1
—
40289
1
—
Bit 9
Shorted SCR2
—
40289
1
—
Bit 10
Open SCR1
—
40290
1
—
Bit 0
Open SCR2
—
40290
1
—
Bit 1
Fan Failure
—
40290
1
—
Bit 2
Source 2 Overload
—
40290
1
—
Bit 3
Power Supply 2 Fault
—
40290
1
—
Bit 4
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
193
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-40 Liebert STS™, Liebert STS/PDU™—Input and Holding—STS (continued)
Controller STS
Liebert Products
Liebert STS
Liebert STS/PDU
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Frequency Deviation
—
40290
1
—
Bit 5
Transfer Inhibit
—
40290
1
—
Bit 6
Auto Retransfer Primed
—
40290
1
—
Bit 7
Out of Synchronization
—
40290
1
—
Bit 8
Source 1 Failure
—
40290
1
—
Bit 9
Data Description
Source 2 Failure
—
40290
1
—
Bit 10
Auto Retransfer Failed
—
40291
1
—
Bit 0
Overload
—
40291
1
—
Bit 1
Control Fuse 1 Blown
—
40291
1
—
Bit 2
Control Fuse 2 Blown
—
40291
1
—
Bit 3
Source 1 CB1 Open
—
40291
1
—
Bit 4
Source 2 CB2 Open
—
40291
1
—
Bit 5
Output CB3 Open
—
40291
1
—
Bit 6
Custom Alarm 1
—
40291
1
—
Bit 7
Custom Alarm 2
—
40291
1
—
Bit 8
Bypass CB4 Closed
—
40291
1
—
Bit 9
Bypass CB5 Closed
—
40291
1
—
Bit 10
Custom Alarm 3
—
40292
1
—
Bit 0
Custom Alarm 4
—
40292
1
—
Bit 1
Custom Alarm 5
—
40292
1
—
Bit 2
Custom Alarm 6
—
40292
1
—
Bit 3
Custom Alarm 7
—
40292
1
—
Bit 4
Custom Alarm 8
—
40292
1
—
Bit 5
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
194
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-41 Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Status Points (View)
Total Transfer Count
—
40001
1
—
—
Preferred Source
—
40002
1
—
1=Source 1, 2=Source 2
Active Source
—
40003
1
—
1=Source 1, 2=Source 2
Source 1 Volts A-B
—
40004
1
—
V
Source 1 Volts B-C
—
40005
1
—
V
Source 1 Volts C-A
—
40006
1
—
V
Source 1 Current A
—
40007
1
—
A
Source 1 Current B
—
40008
1
—
A
Source 1 Current C
—
40009
1
—
A
Source 1 Frequency
—
40010
1
10
Hz
Source 2 Volts A-B
—
40011
1
—
V
Source 2 Volts B-C
—
40012
1
—
V
Source 2 Volts C-A
—
40013
1
—
V
Source 2 Current A
—
40014
1
—
A
Source 2 Current B
—
40015
1
—
A
Source 2 Current C
—
40016
1
—
A
Source 2 Frequency
—
40017
1
10
Hz
Output kW
—
40018
1
—
kW
Output kVA
—
40019
1
—
kVA
CB 1 Status
—
40024
1
—
Bit 0
CB 2 Status
—
40024
1
—
Bit 1
CB 3 Status
—
40024
1
—
Bit 2
CB 3A Status
—
40024
1
—
Bit 3
CB 4 Status
—
40024
1
—
Bit 4
CB 5 Status
—
40024
1
—
Bit 5
CB Spare 1 Status
—
40024
1
—
Bit 6
CB Spare 2 Status
—
40024
1
—
Bit 7
CB 7 Status
—
40024
1
—
Bit 8
CB 8 Status
—
40024
1
—
Bit 9
Auto Xfer Enabled
—
40025
1
—
Bit 0
Has Dual Out Breakers
—
40025
1
—
Bit 1
Has PDU Equipped
—
40025
1
—
Bit 2
Has 4 pole Switch
—
40025
1
—
Bit 3
Has Shunt Trip
—
40025
1
—
Bit 4
Has Wye Out Xfmr
—
40025
1
—
Bit 5
Has Rmt Sorce Sel
—
40025
1
—
Bit 6
Manual I peak Reset
—
40025
1
—
Bit 7
Auto Restart Enabled
—
40025
1
—
Bit 8
LoadKVA %
—
40026
1
—
%
Source 1 Volts A-N
—
40027
1
—
V (4 Pole only)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
195
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-41 Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 (continued)
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Source 1 Volts B-N
—
40028
1
—
V (4 Pole only)
Source 1 Volts C-N
—
40029
1
—
V (4 Pole only)
Source 2 Volts A-N
—
40030
1
—
V (4 Pole only)
Source 2 Volts B-N
—
40031
1
—
V (4 Pole only)
Source 2 Volts C-N
—
40032
1
—
V (4 Pole only)
Source 1 Neutral Current
—
40033
1
—
A (4 Pole only)
Source 2 Neutral Current
—
40034
1
—
A (4 Pole only)
—
40020
1
—
Seconds
Setpoints (View)
Retransfer Delay
STS2 Voltage Rating
—
40021
1
—
V
Max Xfer Phase Angle
—
40022
1
—
Degree
Freq. Deviation Trip Point
—
40023
1
10
Hz
Source 1 Neutral Current Limit
—
40035
1
—
A (4 Pole only)
Source 2 Neutral Current Limit
—
40036
1
—
A (4 Pole only)
Discrete alarm objects available;
use auto-discover for this unit
Alarm Points
Communications Lost
—
40289
1
—
Bit 0
S1 SCR Short
—
40289
1
—
Bit 1
S2 SCR Short
—
40289
1
—
Bit 2
S1 SCR Open
—
40289
1
—
Bit 3
S2 SCR Open
—
40289
1
—
Bit 4
Primary Fan Fail
—
40289
1
—
Bit 5
Control Module Fail
—
40289
1
—
Bit 6
PWR Supply DC A Fail
—
40289
1
—
Bit 7
PWR Supply DC B Fail
—
40289
1
—
Bit 8
PWR Supply SRC 1 AC Fail
—
40289
1
—
Bit 9
PWR Supply SRC 2 AC Fail
—
40289
1
—
Bit 10
PWR Supply Logic Fail
—
40289
1
—
Bit 11
Output Voltage Sense Fail
—
40289
1
—
Bit 12
S1 Voltage Sense Fail
—
40289
1
—
Bit 13
S2 Voltage Sense Fail
—
40289
1
—
Bit 14
S1 SCR Sense Fail
—
40289
1
—
Bit 15
S2 SCR Sense Fail
—
40290
1
—
Bit 0
S1 Current Sense Fail
—
40290
1
—
Bit 1
S2 Current Sense Fail
—
40290
1
—
Bit 2
S1 Gate Drive Fail
—
40290
1
—
Bit 3
S2 Gate Drive Fail
—
40290
1
—
Bit 4
Internal Comm Fail
—
40290
1
—
Bit 5
External Comm Fail
—
40290
1
—
Bit 6
CB1 Shunt Trip Fail
—
40290
1
—
Bit 7
CB2 Shunt Trip Fail
—
40290
1
—
Bit 8
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
196
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-41 Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 (continued)
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
CB6 Neutral Open
—
40290
1
—
Bit 9 (N/A to 4P)
Contactor Neutral Fail
—
40290
1
—
Bit 10 (N/A to 4P)
Heatsink Overtemp
—
40290
1
—
Bit 11
Equipment Overtemp
—
40290
1
—
Bit 12 (N/A to 4P)
Ambient Overtemp
—
40290
1
—
Bit 13 (N/A to 4P)
S1 Undervolts
—
40290
1
—
Bit 14
S1 Undervolts (RMS)
—
40290
1
—
Bit 15
S1 Overvolts
—
40291
1
—
Bit 0
S1 Over/Under Freq
—
40291
1
—
Bit 1
S1 Fail
—
40291
1
—
Bit 2
S2 Undervolts
—
40291
1
—
Bit 3
S2 Undervolts (RMS)
—
40291
1
—
Bit 4
S2 Overvolts
—
40291
1
—
Bit 5
S2 Over/Under Frequency
—
40291
1
—
Bit 6
S2 Fail
—
40291
1
—
Bit 7
S1 Overcurrent
—
40291
1
—
Bit 8
S2 Overcurrent
—
40291
1
—
Bit 9
S1 I-Peak
—
40291
1
—
Bit 10
S2 I-Peak
—
40291
1
—
Bit 11
Sources Out of Sync
—
40291
1
—
Bit 12
Load On Alternate Source
—
40291
1
—
Bit 13
Auto Retransfer Inhibit
—
40291
1
—
Bit 14
CB1 (S1) Open
—
40292
1
—
Bit 0
CB2 (S2) Open
—
40292
1
—
Bit 1
CB4 (S1 BYP) Closed
—
40292
1
—
Bit 2
CB5 (S2 BYP) Closed
—
40292
1
—
Bit 3
CB3 Output Bkr Open
—
40292
1
—
Bit 4
CB3A Output Bkr Open
—
40292
1
—
Bit 5
S1 Phase Rotation Error
—
40292
1
—
Bit 6
S2 Phase Rotation Error
—
40292
1
—
Bit 7
Transfer Inhibited
—
40292
1
—
Bit 8
Output Undervoltage
—
40292
1
—
Bit 9
History Logs Full
—
40292
1
—
Bit 10
Equipment Fan Fail
—
40292
1
—
Bit 11
Load Volt THD High
—
40292
1
—
Bit 12
Load Over-current
—
40292
1
—
Bit 13
Ground Over-current
—
40292
1
—
Bit 14
Neutral Over-current
—
40292
1
—
Bit 15
Customer Alarm #1
—
40293
1
—
Bit 0
Customer Alarm #2
—
40293
1
—
Bit 1
Customer Alarm #3
—
40293
1
—
Bit 2
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
197
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products
Table 3-41 Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 (continued)
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Customer Alarm #4
—
40293
1
—
Bit 3
Customer Alarm #5
—
40293
1
—
Bit 4
Customer Alarm #6
—
40293
1
—
Bit 5
Customer Alarm #7
—
40293
1
—
Bit 6
Customer Alarm #8
—
40293
1
—
Bit 7
Neutral Current 1 Over Limit
—
40294
1
—
Bit 13 (4P Only)
Neutral Current 2 Over Limit
—
40294
1
—
Bit 14 (4P Only)
Data Description
Neutral Snubber Fail
—
40294
1
—
Bit 15 (4P Only)
Neutral 1 SCR Short
—
40295
1
—
Bit 0 (4P Only)
Neutral 2 SCR Short
—
40295
1
—
Bit 1 (4P Only)
Neutral 1 SCR Open
—
40295
1
—
Bit 2 (4P Only)
Neutral 2 SCR Open
—
40295
1
—
Bit 3 (4P Only)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
198
Modbus RTU and Modbus TCP Protocols—UPS Systems
3.3 UPS Systems
Table 3-42 Liebert APM™, Liebert NXC™, Liebert NXR™—Status and Coil
Status
Coil
Number
of Bits
Scale
Notes / Units
Battery Auto Test In Progress
10001
—
1
—
Active on Alarm
Battery Equalize
10002
—
1
—
Active on Alarm
Battery Charging Inhibited
10003
—
1
—
Active on Alarm
On Generator
10004
—
1
—
Active on Alarm
Data Label
System Status
System Events
System Input Power Problem
10015
—
1
—
Active on Alarm
Rectifier Failure
10016
—
1
—
Active on Alarm
Inverter Failure
10017
—
1
—
Active on Alarm
Bypass Not Available
10018
—
1
—
Active on Alarm
Battery Low
10019
—
1
—
Active on Alarm
LBS Inhibited
10020
—
1
—
Active on Alarm
System Fan Failure
10021
—
1
—
Active on Alarm
Equipment Over Temperature
10022
—
1
—
Active on Alarm
System Shutdown - EPO
10023
—
1
—
Active on Alarm
Bypass Static Switch Unavailable
10024
—
1
—
Active on Alarm
Bypass - Excess Auto Retransfers
10025
—
1
—
Active on Alarm
Parallel Comm Warning
10026
—
1
—
Active on Alarm
Power Supply Failure
10027
—
1
—
Active on Alarm
Battery Over Temperature
10028
—
1
—
Active on Alarm
System Input Phs Rotation Error
10029
—
1
—
Active on Alarm
Fuse Failure
10030
—
1
—
Active on Alarm
Inverter Overload Phase A
10031
—
1
—
Active on Alarm
Inverter Overload Phase B
10032
—
1
—
Active on Alarm
Inverter Overload Phase C
10033
—
1
—
Active on Alarm
MMS Overload
10034
—
1
—
Active on Alarm
Inverter Shutdown - Overload
10035
—
1
—
Active on Alarm
System Output Fault
10036
—
1
—
Active on Alarm
Internal Communications Failure
10037
—
1
—
Active on Alarm
Battery Charging Error
10038
—
1
—
Active on Alarm
System Input Current Imbalance
10039
—
1
—
Active on Alarm
Main Battery Disconnect Open
10040
—
1
—
Active on Alarm
Inverter Static Switch SCR Short
10041
—
1
—
Active on Alarm
Battery Not Qualified
10042
—
1
—
Active on Alarm
Battery Terminals Reversed
10043
—
1
—
Active on Alarm
Battery Converter Failure
10044
—
1
—
Active on Alarm
Inverter SCR Open
10045
—
1
—
Active on Alarm
Load Sharing Fault
10046
—
1
—
Active on Alarm
DC Bus Abnormal
10047
—
1
—
Active on Alarm
Mains Input Neutral Lost
10048
—
1
—
Active on Alarm
Load Impact Transfer
10049
—
1
—
Active on Alarm
User Operation Invalid
10050
—
1
—
Active on Alarm
Power Sub Module Fault
10051
—
1
—
Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
199
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-42 Liebert APM™, Liebert NXC™, Liebert NXR™—Status and Coil (continued)
Data Label
Status
Coil
Number
of Bits
Scale
Notes / Units
Battery Discharging
10052
—
1
—
Active on Alarm
UPS Output on Bypass
10053
—
1
—
Active on Alarm
Output Load on Maint. Bypass
10054
—
1
—
Active on Alarm
Battery Capacity Low
10055
—
1
—
Active on Alarm
MMS On Battery
10056
—
1
—
Active on Alarm
Loss of Redundancy
10057
—
1
—
Active on Alarm
Top Outlet Fan Fault
10058
—
1
—
Active on Alarm
MMS Over Capacity
10059
—
1
—
Active on Alarm
Battery Charge Equalization Timeout
10060
—
1
—
Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
200
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-43 Liebert APM™, Liebert NXC™, Liebert NXR™—Input and Holding
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Input
System Input RMS A-B
30385
—
1
—
VAC
System Input RMS B-C
30386
—
1
—
VAC
System Input RMS C-A
30387
—
1
—
VAC
System Input RMS Current Phase A
30388
—
1
—
A AC
System Input RMS Current Phase B
30389
—
1
—
A AC
System Input RMS Current Phase C
30390
—
1
—
A AC
System Input Frequency
30391
—
1
10
Hz
System Input RMS A-N
30392
—
1
—
VAC
System Input RMS B-N
30393
—
1
—
VAC
System Input RMS C-N
30394
—
1
—
VAC
System Input Power Factor Phs A
30395
—
1
100
—
System Input Power Factor Phs B
30396
—
1
100
—
System Input Power Factor Phs C
30397
—
1
100
—
Bypass Input Voltage RMS A-N
30401
—
1
—
VAC
Bypass Input Voltage RMS B-N
30402
—
1
—
VAC
Bypass
Bypass Input Voltage RMS C-N
30403
—
1
—
VAC
Bypass Input Frequency
30404
—
1
10
Hz
30408
—
1
—
min
Battery
Battery Time Remaining
Battery Volts for Cabinet
30409
—
1
—
VDC
Battery Temperature for Cabinet
30410
—
1
—
deg C
Battery Temperature for Cabinet
30411
—
1
—
deg F
Inlet Air Temperature
30412
—
1
—
deg C
Inlet Air Temperature
30413
—
1
—
deg F
DC Bus Current
30414
—
1
—
A DC
UPS battery1 status
30415
—
1
—
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
System Output Voltage RMS A-N
30419
—
1
—
VAC
System Output Voltage RMS B-N
30420
—
1
—
VAC
System Output Voltage RMS C-N
30421
—
1
—
VAC
System Output RMS Current Phs A
30422
—
1
—
A AC
System Output RMS Current Phs B
30423
—
1
—
A AC
System Output RMS Current Phs C
30424
—
1
—
A AC
System Output Frequency
30425
—
1
10
Hz
Output
System Output Voltage RMS A-B
30426
—
1
—
VAC
System Output Voltage RMS B-C
30427
—
1
—
VAC
System Output Voltage RMS C-A
30428
—
1
—
VAC
System Output Power Factor Phs A
30429
—
1
100
—
System Output Power Factor Phs B
30430
—
1
100
—
System Output Power Factor Phs C
30431
—
1
100
—
System Output Pct Power Phase A
30432
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
201
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-43 Liebert APM™, Liebert NXC™, Liebert NXR™—Input and Holding (continued)
Data Label
System Output Pct Power Phase B
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
30433
—
1
—
%
System Output Pct Power Phase C
30434
—
1
—
%
MMS Output Apparent Power
30435
—
1
—
kVA
MMS Output Power
30436
—
1
—
kW
System Output Apparent Power
30437
—
1
—
kVA
System Output Power
30438
—
1
—
kW
Output Current Crest Factor Phs A
30439
—
1
10
—
Output Current Crest Factor Phs B
30440
—
1
10
—
Output Current Crest Factor Phs C
30441
—
1
10
—
Inverter On/Off State
30445
—
1
—
0 = Off / 1 = On
Maintenance Bypass Breaker (MBB)
30446
—
1
—
0 = Open / 1 = Closed
2 = Not Installed
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Status
UPS Output Source
30447
—
1
System Status
30448
—
1
—
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
ECO Mode Operation State
30449
—
1
—
0 = disabled
1 = enabled
39998
49998
2
—
Secs since Epoch(UTC)
System Configuration
System Date and Time
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
202
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-44 Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary
Data Label
Data Description
Battery Auto Test In Progress
Automatic battery test is in progress
Battery Capacity Low
Battery capacity is low
Battery Charging Error
The battery is not charging properly
Battery Charging Inhibited
Battery charging is inhibited due to an external inhibit signal
Battery Converter Failure
Battery converter failure. This is a summary event caused by one or more power submodules in a UPS module.
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage level.
Battery Low
The calculated battery time remaining has reached the low battery threshold
Battery Not Qualified
The UPS battery voltage is not qualified. This event will be detected even in the
absence of battery disconnect or when it is open.
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Terminals Reversed
The measured battery voltage is a negative value due to reverse battery terminal
connections.
Battery Time Remaining
The calculated available time on battery
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a battery cabinet
Bypass - Excess Auto Retransfers
The number of auto retransfers, from bypass to inverter, has exceeded the maximum
for a specified time interval
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage RMS A-N
The bypass input RMS voltage between phase A and Neutral
Bypass Input Voltage RMS B-N
The bypass input RMS voltage between phase B and Neutral
Bypass Input Voltage RMS C-N
The bypass input RMS voltage between phase C and Neutral
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Static Switch Unavailable
The static bypass switch is off, and unable to operate
DC Bus Abnormal
The system has detected an abnormal DC Bus Voltage.
DC Bus Current
The current at the battery input terminals. In charging mode, the current will be a
positive value. In discharging mode, the current will be a negative value
Equipment Over Temperature
Equipment over temperature summary event
Fuse Failure
A summary event indicating one or more fuse failures
Inlet Air Temperature
The temperature of the inlet air
Internal Communications Failure
The control has detected a communication failure of a component on the internal
communication bus
Inverter Failure
Inverter failure - inverter output is off
Inverter On/Off State
inverter on/off state
Inverter Overload Phase A
Inverter is operating with an overload on phase A
Inverter Overload Phase B
Inverter is operating with an overload on phase B
Inverter Overload Phase C
Inverter is operating with an overload on phase C
Inverter SCR Open
The system has detected an open across one or more inverter static switch Silicon
Controlled Rectifiers.
Inverter Shutdown - Overload
The inverter has shutdown due to a sustained overload
Inverter Static Switch SCR Short
The system has detected a short across one or more inverter static switch Silicon
Controlled Rectifiers (SCR)
LBS Inhibited
The system has detected that conditions to perform Load Bus Sync are not satisfied
Load Impact Transfer
On bypass as result of load impact.
Load Sharing Fault
Difference between any phase inverter current of unit and the relevant average output
current of parallel system is more than a specific percent of nominal current.
Main Battery Disconnect Open
Main battery disconnect is open
Mains Input Neutral Lost
Loss of neutral in the input source is detected.
203
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-44 Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary (continued)
Data Label
Data Description
Maintenance Bypass Breaker (MBB)
Maintenance bypass breaker (MBB)
MMS On Battery
The multi-module system is on battery
MMS Output Apparent Power
The sum total apparent power of all system output modules
MMS Output Power
The sum total power of all system output modules
MMS Overload
Multi-module system overload
On Generator
A generator is supplying the power to the system
Output Current Crest Factor Phs A
Output current crest factor of Phase A.
Output Current Crest Factor Phs B
Output current crest factor of Phase B.
Output Current Crest Factor Phs C
Output current crest factor of Phase C.
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Parallel Comm Warning
Parallel communication bus warning
Power Sub Module Fault
One or more failures detected in power module, inverter or rectifier.
Power Supply Failure
Power supply failure
Rectifier Failure
Rectifier failure - rectifier is off
System Date and Time
The system date and time
System Fan Failure
System fan failure - one or more fans have failed
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Frequency
The system input frequency
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the sequence
preferred for the rectifier (A-B-C)
System Input Power Factor Phs A
The system input power factor for Phase A
System Input Power Factor Phs B
The system input power factor for Phase B
System Input Power Factor Phs C
The system input power factor for Phase C
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Pct Power Phase A
The system output power on phase A as a percentage of the rated capacity
System Output Pct Power Phase B
The system output power on phase B as a percentage of the rated capacity
System Output Pct Power Phase C
The system output power on phase C as a percentage of the rated capacity
System Output Power Factor Phs A
The system output power factor of phase A
System Output Power Factor Phs B
The system output power factor of phase B
System Output Power Factor Phs C
The system output power factor of phase C
System Output Power
The sum total power of all system output phases
System Output RMS Current Phs A
The system output RMS current for Phase A
System Output RMS Current Phs B
The system output RMS current for Phase B
System Output RMS Current Phs C
The system output RMS current for Phase C
System Output Voltage RMS A-B
The system output RMS voltage between phases A and B
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
204
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-44 Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary (continued)
Data Label
Data Description
System Output Voltage RMS A-N
The system output RMS voltage between phases A and Neutral
System Output Voltage RMS B-C
The system output RMS voltage between phases B and C
System Output Voltage RMS B-N
The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A
The system output RMS voltage between phases C and A
System Output Voltage RMS C-N
The system output RMS voltage between phases C and Neutral
System Shutdown - EPO
System shutdown due to Emergency Power Off (EPO)
System Status
The operating status for the system
UPS battery1 status
UPS battery status
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
User Operation Invalid
User attempted an invalid operation.
205
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-45 Liebert APS™—Status and Coil
Status
Coil
Number
of Bits
Notes
Rectifier Failure
10001
—
1
Active on Alarm
System Input Power Problem
10002
—
1
Active on Alarm
System Input Current Imbalance
10003
—
1
Active on Alarm
UPS Output on Bypass
10014
—
1
Active on Alarm
Output Load on Maint. Bypass
10015
—
1
Active on Alarm
Data Label
Input
Bypass
Bypass Not Available
10016
—
1
Active on Alarm
Bypass Overload
10017
—
1
Active on Alarm
Bypass Frequency Error
10018
—
1
Active on Alarm
Bypass Auto Retransfer Failed
10019
—
1
Active on Alarm
Battery Discharging
10030
—
1
Active on Alarm
Battery Manual Test In Progress
10031
—
1
Active on Alarm
Battery Auto Test In Progress
10032
—
1
Active on Alarm
Battery
Battery Test Passed
10033
—
1
Active on Alarm
Battery Test Failed
10034
—
1
Active on Alarm
Low Battery - Shutdown Imminent
10035
—
1
Active on Alarm
Battery Module Fault
10036
—
1
Active on Alarm
Battery Module Warning
10037
—
1
Active on Alarm
Battery Over Temperature
10038
—
1
Active on Alarm
Battery Temperature Imbalance
10039
—
1
Active on Alarm
Output Overload
10050
—
1
Active on Alarm
Output Off Pending
10051
—
1
Active on Alarm
System Output Off
10052
—
1
Active on Alarm
System Shutdown - Transformer Over Temperature
10053
—
1
Active on Alarm
Output
Inverter Shutdown - Overload
10054
—
1
Active on Alarm
System Shutdown - Output Short
10055
—
1
Active on Alarm
System Shutdown - Low Battery
10056
—
1
Active on Alarm
System Shutdown - Remote Shutdown
10057
—
1
Active on Alarm
System Shutdown - Hardware Fault
10058
—
1
Active on Alarm
Maximum Load Alarm
10059
—
—
Active on Alarm
Loss of Redundancy
10070
—
1
Active on Alarm
Power Module Failure
10071
—
1
Active on Alarm
Power Module Warning
10072
—
1
Active on Alarm
Unspecified General Event
10083
—
1
Active on Alarm
Check Air Filter
10084
—
1
Active on Alarm
Frame Fan Fault
10085
—
1
Active on Alarm
Inverter
System Status
Transformer Fan Fault
10086
—
1
Active on Alarm
Transformer Overtemperature
10087
—
1
Active on Alarm
No Load Warning
10088
—
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
206
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-45 Liebert APS™—Status and Coil (continued)
Status
Data Label
Coil
Number
of Bits
Notes
PowerModule 1
Power Module Fan Fault
10099
—
1
Active on Alarm
Power Module Over Temperature
10100
—
1
Active on Alarm
Power Module Shutdown - Over Temperature
10101
—
1
Active on Alarm
PowerModule 2
Power Module Fan Fault
10112
—
1
Active on Alarm
Power Module Over Temperature
10113
—
1
Active on Alarm
Power Module Shutdown - Over Temperature
10114
—
1
Active on Alarm
PowerModule 10
Power Module Fan Fault
10216
—
1
Active on Alarm
Power Module Over Temperature
10217
—
1
Active on Alarm
Power Module Shutdown - Over Temperature
10218
—
1
Active on Alarm
Battery Module Temperature Sensor Fault
10229
—
1
Active on Alarm
Battery Module Over Temperature
10230
—
1
Active on Alarm
Replace Battery Module
10231
—
1
Active on Alarm
Battery Module Temperature Sensor Fault
10242
—
1
Active on Alarm
Battery Module Over Temperature
10243
—
1
Active on Alarm
Replace Battery Module
10244
—
1
Active on Alarm
Battery Module Temperature Sensor Fault
11256
—
1
Active on Alarm
Battery Module Over Temperature
11257
—
1
Active on Alarm
Replace Battery Module
11258
—
1
Active on Alar
11269
—
1
Active on Alarm
BatteryModule 1
BatteryModule 2
BatteryModule 80
ChargerModule
Charger Module Fan Fault
207
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-46 Liebert APS™—Input and Holding
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
30385
—
—
—
1 = UPS
2 = AIR
3 = PMP
4 = PDU
System Input RMS L1-N
30396
—
1
10
Units : VAC
Uint 16
System Input RMS L2-N
30397
—
1
10
Units : VAC
Uint 16
System Input RMS L3-N
30398
—
1
10
Units : VAC
Uint 16
System Input RMS L1-L2
30399
—
1
10
Units : VAC
Uint 16
System Input RMS L2-L3
30400
—
1
10
Units : VAC
Uint 16
System Input RMS L3-L1
30401
—
1
10
Units : VAC
Uint 16
System Input RMS Current L1
30402
—
1
10
Units : A AC
Uint 16
System Input RMS Current L2
30403
—
1
10
Units : A AC
Uint 16
System Input RMS Current L3
30404
—
1
10
Units : A AC
Uint 16
System Input Frequency
30405
—
1
100
Units : Hz
Uint 16
System Input Power Factor L1
30406
—
1
100
Uint 16
System Input Power Factor L2
30407
—
1
100
Uint 16
System Input Power Factor L3
30408
—
1
100
Uint 16
System Input Brown Out Count
30409
—
1
—
Uint 16
System Input Black Out Count
30410
—
1
—
Uint 16
Bypass Input Voltage RMS L1-N
30421
—
1
10
Units : VAC
Uint 16
Bypass Input Voltage RMS L2-N
30422
—
1
10
Units : VAC
Uint 16
Bypass Input Voltage RMS L1-L2
30423
—
1
10
Units : VAC
Uint 16
Bypass Input Frequency
30424
—
1
100
Units : Hz
Uint 16
Number Of Transfers To Bypass
30425
—
1
—
Uint 16
Bypass Qualification Status
30426
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Data Label
Protocol
Server Class
Input
Bypass
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
208
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-46 Liebert APS™—Input and Holding (continued)
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Battery Time Remaining
30437
—
1
—
Units : min
Uint 16
Battery Volts for Cabinet
30438
—
1
10
Units : VDC
Uint 16
DC Bus Current
30439
—
1
100
Units : A DC
Uint 16
Battery Percentage Charge
30440
—
1
—
Units : %
Uint16
UPS Battery Status
30441
—
1
—
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
Data Label
Battery
Battery is
30442
—
1
—
0 = fully charged
1 = charging
2 = discharging
3 = not charging
(charger off)
Battery Temperature
30443
—
1
10
Units : deg C
Int16
Battery Temperature
30444
—
10
Units : degF
Int16
Number of Discharge Cycles
30445
—
1
—
Uint 16
Accumulated Discharge Time
30446
—
1
10
Units : hr
Uint 16
Time Until Next Auto Battery Test
30447
—
2
—
Units : min
Uint32
Number of EBC Installed
30449
—
1
—
Uint 16
Low Battery Warning Time
30450
40450
1
—
Units : min
Uint 16
Automatic Battery Test
30451
40451
1
—
0 = disabled
1 = enabled
30452
40452
1
—
0 = 8 weeks
1 = 12 weeks
2 = 16 weeks
3 = 20 weeks
4 = 26 weeks
—
40453
1
—
1 = Start Test
System Output Voltage RMS L1-N
30464
—
1
10
Units : VAC
Uint 16
System Output Voltage RMS L2-N
30465
—
1
10
Units : VAC
Uint 16
System Output Voltage RMS L1-L2
30466
—
1
10
Units : VAC
Uint 16
System Output RMS Current L1
30467
—
1
10
Units : A AC
Uint 16
System Output RMS Current L2
30468
—
1
10
Units : A AC
Uint16
System Output Frequency
30469
—
1
100
Units : Hz
Uint 16
System Output Power Factor L1
30470
—
1
100
Uint 16
System Output Power Factor L2
30471
—
1
100
Uint 16
Auto Battery Test Interval
Manual Battery Test
Output
209
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-46 Liebert APS™—Input and Holding (continued)
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
System Output Apparent Power
30472
—
1
100
Units : kVA
Uint 16
System Output Apparent Power L1
30473
—
1
100
Units : kVA
Uint 16
System Output Apparent Power L2
30474
—
1
100
Units : kVA
Uint 16
System Output Power
30475
—
1
100
Units : kW
Uint 16
System Output Power L1
30476
—
1
100
Units : kW
Uint 16
System Output Power L2
30477
—
1
100
Units : kW
Uint 16
System Output Pct Power L1
30478
—
1
10
Units : %
Uint 16
System Output Pct Power L2
30479
—
1
10
Units : %
Uint 16
Data Label
Output Qualification Status
30480
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Maximum Load Alarm Limit
30481
40481
1
10
Units : kVA
Uint16
Shutdown After Delay
30482
40482
1
—
Units : sec
Uint 16
Reboot After Delay
30483
40483
1
—
Units : sec
Uint 16
Output On Delay
30484
40484
1
—
Units : sec
Uint 16
Inverter On/Off State
30495
—
1
—
0 = off
1 = on
System Set To Operate With
30496
40496
1
—
0 = No Redundancy
1 = Redundancy
System Capacity
30507
—
1
—
Units : VA
Uint 16
Frame Capacity
30508
—
1
—
Units : VA
Uint 16
Inverter
Number of Installed Power Modules
30509
—
1
—
Uint 16
Number Of Active Power Modules
30510
—
1
—
Uint 16
Number Of Power Modules With Warnings
30511
—
1
—
Uint 16
Number Of Failed Power Modules
30512
—
1
—
Uint 16
Number of Installed Battery Strings
30513
—
1
—
Uint 16
Number of Active Battery Strings
30514
—
1
—
Uint 16
Number of Battery Strings With Warnings
30515
—
1
—
Uint 16
Number of Failed Battery Strings
30516
—
1
—
Uint 16
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
UPS Output Source
30517
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
—
210
1
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-46 Liebert APS™—Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
System Status
30518
—
1
—
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
Auto Restart
30519
—
40519
1
0 = disabled
1 = enabled
Auto Restart Delay
30520
—
40520
1
Units : sec
Uint 16
Auto Restart Minimum Battery Setting
30521
—
40521
1
0 = 0%
1 = 10%
2 = 20%
3 = 30%
4 = 40%
5 = 50%
6 = 60%
7 = 70%
8 = 80%
9 = 90%
No Load Warning Current Threshold
30522
40522
1
—
Units : A AC
Int16
No Load Warning Delay
30523
40523
1
—
Units : min
Uint 16
PowerModule 1
Module Operating Status
30534
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status
30535
—
1
—
0 = Inverter Inactive
1 = Inverter Active
Module Operating Status
30546
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status
30547
—
1
—
0 = Inverter Inactive
1 = Inverter Active
PowerModule 2
PowerModule 10
Module Operating Status
30642
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status
30643
—
1
—
0 = Inverter Inactive
1 = Inverter Active
Module Operating Status
30654
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Battery String Voltage
30655
—
1
10
Units : VDC
Uint16
Battery Module Temperature
30656
—
1
10
Units : deg C
Int16
Battery Module Temperature
30657
—
1
10
Units : degF
Int16
Number of Discharge Cycles
30658
—
1
—
Uint 16
BatteryModule 1
211
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-46 Liebert APS™—Input and Holding (continued)
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
30659
—
1
10
Units : hr
Uint 16
Module Operating Status
30670
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Battery String Voltage
30671
—
1
10
Units : VDC
Uint16
Battery Module Temperature
30672
—
1
10
Units : deg C
Int16
Battery Module Temperature
30673
—
1
10
Units : degF
Int16
Number of Discharge Cycles
30674
—
1
—
Uint 16
Data Label
Accumulated Discharge Time
BatteryModule 2
30675
—
1
10
Units : hr
Uint 16
Module Operating Status
31918
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Battery String Voltage
31919
—
1
10
Units : VDC
Uint16
Battery Module Temperature
31920
—
1
10
Units : deg C
Int16
Battery Module Temperature
31921
—
1
10
Units : degF
Int16
Number of Discharge Cycles
31922
—
1
—
Uint 16
Accumulated Discharge Time
BatteryModule 80
Accumulated Discharge Time
31923
—
1
10
Units : hr
Uint 16
31934
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
ChargerModule
Module Operating Status
Charger Mode
31935
—
1
—
0 = Not Charging
1 = Float Charging
2 = Current Limit
Charging
3 = Equalize Charging
31946
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
31957
41957
2
—
Secs since Epoch(UTC)
39998
49998
2
—
Secs since Epoch(UTC)
BypassControlModule
Module Operating Status
System Configuration
System Date and Time
SystemConfiguration
System Date and Time
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
212
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-47 Liebert APS™—Glossary
Data Label
Data Description
Accumulated Discharge Time
The highest accumulated battery discharge time among installed
battery modules.
Accumulated Discharge Time
Total accumulated discharge time for the Battery Module since it was
made.
Auto Battery Test Interval
The time between automatic battery tests.
Auto Restart Delay
If 'Auto Restart' is set to 'enabled' the UPS will not restart the load after
a battery discharge until this amount of time has elapsed since the
restoration of utility power.
Auto Restart Minimum Battery Setting
The percent state of charge that the batteries must have before the unit
is allowed to auto restart.
Auto Restart
When 'enabled', the UPS will automatically restart the load when utility
power is restored after a battery discharge.
Automatic Battery Test
Enable/disable the automatic battery test schedule.
Battery Auto Test In Progress
Automatic battery test is in progress
Battery Discharging
The battery is discharging
Battery is
Battery charge status.
Battery Manual Test In Progress
Manual battery test is in progress
Battery Module Fault
One or more battery modules are reporting a fault condition.
Battery Module Over Temperature
The Battery Module has detected an over temperature condition.
Battery Module Temperature Sensor Fault
A Battery Module temperature sensor fault has been detected.
Battery Module Temperature
The battery temperature measured by the Battery Module.
Battery Module Warning
One or more battery modules are reporting a warning condition.
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Percentage Charge
The percentage of battery charge
Battery String Voltage
The voltage between the positive and negative battery terminals of a
battery string.
Battery Temperature Imbalance
Excessive temperature differences between battery sensors detected
Battery Temperature
The highest battery temperature among all installed Battery Modules.
Battery Test Failed
Battery test failed
Battery Test Passed
Battery test passed
Battery Time Remaining
The calculated available time on battery
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a
battery cabinet
Bypass Auto Retransfer Failed
After performing a recoverable transfer to bypass, an attempt to auto
retransfer from bypass to inverter failed
Bypass Frequency Error
The bypass frequency is outside the inverter synchronization limits
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage RMS L1-L2
The bypass input RMS voltage between Lines 1 and 2
Bypass Input Voltage RMS L1-N
The bypass input RMS voltage between Line 1 and Neutral
Bypass Input Voltage RMS L2-N
The bypass input RMS voltage between Line 2 and Neutral
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Overload
Bypass overloaded, reduce load immediately.
Bypass Qualification Status
bypass qualification status
Charger Mode
The Charger Module is operating in the stated charging mode.
Charger Module Fan Fault
The Charger Module has detected a fan fault.
Check Air Filter
Please check air filter, it may need to be cleaned or replaced.
DC Bus Current
The current at the battery input terminals. In charging mode, the current
will be a positive value. In discharging mode, the current will be a
negative value
213
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-47 Liebert APS™—Glossary (continued)
Data Label
Data Description
Frame Capacity
Total system capacity supported when the maximum number of power
modules are installed.
Frame Fan Fault
The frame top outlet fan has failed.
Inverter On/Off State
inverter on/off state
Inverter Shutdown - Overload
The inverter has shutdown due to a sustained overload
Inverter Status
Status of the inverter output. Active means the inverter is online with
regulated output voltage and ready to power the load. Inactive means
the inverter is offline and not ready to power the load.
Loss of Redundancy
The system has an insufficient number of power modules to provide
redundancy.
Low Battery - Shutdown Imminent
If active and guaranteed shutdown is enabled, a low battery reserve
condition exists that will shutdown the UPS.
Low Battery Warning Time
When battery time remaining falls to, or below, this value the low
battery alarm is activated.
Manual Battery Test
Command to initiate a manual battery test.
Maximum Load Alarm Limit
Maximum load [VA] supportable without a 'Maximum Load Alarm'
condition.
Maximum Load Alarm
Maximum load alarm indicating load setting has been exceeded.
Module Operating Status
The operating status for this Battery Module.
Module Operating Status
The operating status for this Bypass Control Module.
Module Operating Status
The operating status for this Charger Module.
Module Operating Status
The operating status for this Power Module.
No Load Warning Current Threshold
If the output current is below this number of amps for a period of [No
Load Warning Delay] time, the [No Load Warning] will become active.
No Load Warning Delay
If the output current is below the [No Load Warning Current Threshold]
number of amps for this period of time, the [No Load Warning] will
become active.
No Load Warning
Indicates the UPS has output voltage but the output current is below a
set threshold [No Load Warning Current Threshold] for a set period of
time [No Load Warning Delay].
Number of Active Battery Strings
The total number of active battery strings.
Number Of Active Power Modules
The total number of active power modules.
Number of Battery Strings With Warnings
The total number of battery strings with warnings.
Number of Discharge Cycles
The highest number of battery discharge cycles among all installed
Battery Modules.
Number of Discharge Cycles
The total number of battery discharge cycles for the Battery Module
since it was made.
Number of EBC Installed
The total number of Extended Battery Cabinets installed.
Number of Failed Battery Strings
The total number of failed battery strings.
Number Of Failed Power Modules
The total number of failed power modules.
Number of Installed Battery Strings
The total number of battery strings installed.
Number of Installed Power Modules
The total number of Power Modules installed.
Number Of Power Modules With Warnings
The total number of power modules with warnings.
Number Of Transfers To Bypass
The total number of transfers to bypass from inverter since system
startup.
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Output Off Pending
Output off pending - shutdown imminent.
Output On Delay
When a value is written to this point the output will be turned on after
the specified time has elapsed.
Output Overload
An overload exists on the output.
Output Qualification Status
output qualification status
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
214
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-47 Liebert APS™—Glossary (continued)
Data Label
Data Description
Power Module Failure
One or more conditions indicate a power module failure, service is
required.
Power Module Fan Fault
The Power Module has detected a fan fault.
Power Module Over Temperature
The Power Module has detected an over temperature condition.
Power Module Shutdown - Over Temperature
Power Module has shutdown due to over temperature.
Power Module Warning
One or more power modules is reporting a warning condition.
Reboot After Delay
When a value is written to this point the output will be turned off after
the specified time has elapsed and then turned back on 10-30 seconds
later.
Rectifier Failure
Rectifier failure - rectifier is off
Replace Battery Module
The Battery Module needs to be replaced.
Server Class
The general classification for this system
Shutdown After Delay
When a value is written to this point the system will shutdown after the
specified time has elapsed and output will remain off.
System Capacity
System capacity supported by the installed power modules.
System Date and Time
The system date and time
System Input Black Out Count
The number of occurrences, since the last reset, where the input was
not qualified to provide power to the system
System Input Brown Out Count
The number of occurrences, since the last reset, where the system
input voltage has fallen below a pre-determined threshold for a
specified amount of time
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Frequency
The system input frequency
System Input Power Factor L1
The system input power factor for Line 1
System Input Power Factor L2
The system input power factor for Line 2
System Input Power Factor L3
The system input power factor for Line 3
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS Current L1
The system input RMS current for Line 1
System Input RMS Current L2
The system input RMS current for Line 2
System Input RMS Current L3
The system input RMS current for Line 3
System Input RMS L1-L2
The System Input RMS Voltage between Line 1 and Line 2
System Input RMS L1-N
The System Input RMS Voltage between Line 1 and Neutral
System Input RMS L2-L3
The System Input RMS Voltage between Line 2 and Line 3
System Input RMS L2-N
The System Input RMS Voltage between Line 2 and Neutral
System Input RMS L3-L1
The System Input RMS Voltage between Line 3 and Line 1
System Input RMS L3-N
The System Input RMS Voltage between Line 3 and Neutral
System Output Apparent Power L1
System output apparent power on Line 1
System Output Apparent Power L2
System output apparent power on Line 2
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Frequency
The system output frequency
System Output Off
The system output is off
System Output Pct Power L1
The system output power on Line 1 as a percentage of the rated
capacity
System Output Pct Power L2
The system output power on Line 2 as a percentage of the rated
capacity
System Output Power Factor L1
The system output power factor of Line 1
System Output Power Factor L2
The system output power factor of Line 2
System Output Power L1
The system output power on Line 1.
System Output Power L2
The system output power on Line 2.
215
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-47 Liebert APS™—Glossary (continued)
Data Label
Data Description
System Output Power
The sum total power of all system output phases
System Output RMS Current L1
The system output RMS current for Line 1
System Output RMS Current L2
The system output RMS current for Line 2
System Output Voltage RMS L1-L2
The system output RMS voltage between Lines 1 and 2
System Output Voltage RMS L1-N
The system output RMS voltage between Line 1 and Neutral
System Output Voltage RMS L2-N
The system output RMS voltage between Line 2 and Neutral
System Set To Operate With
If this point reports 'Redundancy' then the system is configured for
redundancy and the 'Loss of Redundancy' alarm is enabled.
System Shutdown - Hardware Fault
Shutdown was due to an externally applied hardware control signal.
System Shutdown - Low Battery
Shutdown was due to a low battery condition.
System Shutdown - Output Short
Shutdown was due to a short on the output.
System Shutdown - Remote Shutdown
Shutdown was due to a remote communications shutdown command.
System Shutdown - Transformer Over Temperature
System shutdown due to transformer over temperature.
System Status
The operating status for the system
Time Until Next Auto Battery Test
The time until the next automatic battery test is started.
Transformer Fan Fault
The transformer fan has failed.
Transformer Overtemperature
Transformer temperature has exceeded the limit
Unspecified General Event
One or more unspecified events active. See local unit display for further
details.
UPS Battery Status
UPS battery status
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
216
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-48 Liebert EPM™—Status and Coil
Data Label
Status
Coil
Number of
Bits
Notes
System Status
Battery Equalize
10001
1
Active on Alarm
Battery Charging Inhibited
10002
1
Active on Alarm
On Generator
10003
1
Active on Alarm
Battery Self Test
10004
1
Active on Alarm
Battery Circuit Breaker 1 Open
10005
1
Active on Alarm
Battery Circuit Breaker 2 Open
10006
1
Active on Alarm
Battery Circuit Breaker 3 Open
10007
1
Active on Alarm
Battery Circuit Breaker 4 Open
10008
1
Active on Alarm
Main Battery Disconnect Open
10009
1
Active on Alarm
System Events
System Input Power Problem
10020
1
Active on Alarm
Rectifier Failure
10021
1
Active on Alarm
Inverter Failure
10022
1
Active on Alarm
Bypass Not Available
10023
1
Active on Alarm
Battery Low
10024
1
Active on Alarm
LBS Inhibited
10025
1
Active on Alarm
System Fan Failure
10026
1
Active on Alarm
Equipment Over Temperature
10027
1
Active on Alarm
System Shutdown - EPO
10028
1
Active on Alarm
Bypass Static Switch Unavailable
10029
1
Active on Alarm
Bypass - Excess Auto Retransfers
10030
1
Active on Alarm
Parallel Comm Warning
10031
1
Active on Alarm
Power Supply Failure
10032
1
Active on Alarm
Battery Over Temperature
10033
1
Active on Alarm
System Input Phs Rotation Error
10034
1
Active on Alarm
Fuse Failure
10035
1
Active on Alarm
Inverter Overload
10036
1
Active on Alarm
MMS Overload
10037
1
Active on Alarm
Inverter Shutdown - Overload
10038
1
Active on Alarm
System Output Fault
10039
1
Active on Alarm
Internal Communications Failure
10040
1
Active on Alarm
Battery Charging Error
10041
1
Active on Alarm
System Input Current Imbalance
10042
1
Active on Alarm
Battery Not Qualified
10043
1
Active on Alarm
Battery Terminals Reversed
10044
1
Active on Alarm
Battery Converter Failure
10045
1
Active on Alarm
Load Sharing Fault
10046
1
Active on Alarm
DC Bus Abnormal
10047
1
Active on Alarm
Mains Input Neutral Lost
10048
1
Active on Alarm
Load Impact Transfer
10049
1
Active on Alarm
User Operation Invalid
10050
1
Active on Alarm
Battery Discharging
10051
1
Active on Alarm
UPS Output on Bypass
10052
1
Active on Alarm
Output Load on Maint. Bypass
10053
1
Active on Alarm
Battery Capacity Low
10054
1
Active on Alarm
217
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-48 Liebert EPM™—Status and Coil (continued)
Data Label
Status
Coil
Number of
Bits
Notes
MMS On Battery
10055
1
Active on Alarm
Loss of Redundancy
10056
1
Active on Alarm
Top Outlet Fan Fault
10057
1
Active on Alarm
MMS Over Capacity
10058
1
Active on Alarm
Bypass Input Voltage Fault
10059
1
Active on Alarm
Power Module Over Temperature
10060
1
Active on Alarm
Excess ECO Suspends
10061
1
Active on Alarm
Battery Ground Fault
10062
1
Active on Alarm
System Input Current Limit
10063
1
Active on Alarm
Inverter Relay Fault
10064
1
Active on Alarm
Transfer to Bypass - System Overload
10065
1
Active on Alarm
Input Source Backfeed
10066
1
Active on Alarm
Loss of Synchronization
10067
1
Active on Alarm
Battery Converter Current Limit
10068
1
Active on Alarm
LBS Cable Failure
10069
1
Active on Alarm
Battery Charge Equalization Timeout
10070
1
Active on Alarm
Parallel Cable Failure
10071
1
Active on Alarm
Battery Fault
10072
1
Active on Alarm
Battery Room Alarm
10073
1
Active on Alarm
Battery Breaker 1 Open Failure
10074
1
Active on Alarm
Battery Breaker 2 Open Failure
10075
1
Active on Alarm
Battery Breaker 3 Open Failure
10076
1
Active on Alarm
Battery Breaker 4 Open Failure
10077
1
Active on Alarm
Bypass Backfeed Detected
10078
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
218
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-49 Liebert EPM™—Input and Holding
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Input
System Input RMS A-B
30385
1
Units : VAC
Uint16
System Input RMS B-C
30386
1
Units : VAC
Uint16
System Input RMS C-A
30387
1
Units : VAC
Uint16
System Input RMS Current Phase A
30388
1
Units : A AC
Uint16
System Input RMS Current Phase B
30389
1
Units : A AC
Uint16
System Input RMS Current Phase C
30390
1
Units : A A
Uint16
System Input Frequency
30391
1
System Input RMS A-N
30392
1
Units : VAC
Uint16
System Input RMS B-N
30393
1
Units : VAC
Uint16
System Input RMS C-N
30394
1
Units : VAC
Uint16
System Input Power Factor Phs A
30395
1
100
Uint16
System Input Power Factor Phs B
30396
1
100
Uint16
System Input Power Factor Phs C
30397
1
100
Uint16
Bypass Input Voltage RMS A-N
30408
1
Units : VAC
Uint16
Bypass Input Voltage RMS B-N
30409
1
Units : VAC
Uint16
Bypass Input Voltage RMS C-N
30410
1
Units : VAC
Uint16
Bypass Input Frequency
30411
1
Bypass Input Voltage RMS A-B
30412
1
Units : VAC
Uint16
Bypass Input Voltage RMS B-C
30413
1
Units : VAC
Uint16
Bypass Input Voltage RMS C-A
30414
1
Units : VAC
Uint16
Battery Time Remaining
30425
1
Units : min
Uint16
Battery Volts for Cabinet
30426
1
Units : VDC
Int16
Battery Temperature for Cabinet
30427
1
Units : deg C
Int16
Battery Temperature for Cabinet
30428
1
Units : deg F
Int16
DC Bus Current
30429
1
Units : A DC
Int16
10
Units : Hz
Uint16
Bypass
10
Units : Hz Uint16
Battery
219
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-49 Liebert EPM™—Input and Holding (continued)
Data Label
UPS battery1 status
Input
Holding
# of Reg
Scale
Notes/Units
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
30430
1
System Output Voltage RMS A-N
30441
1
Units : VAC
Uint16
System Output Voltage RMS B-N
30442
1
Units : VAC
Uint16
System Output Voltage RMS C-N
30443
1
Units : VAC
Uint16
System Output RMS Current Phs A
30444
1
Units : A AC
Uint16
System Output RMS Current Phs B
30445
1
Units : A AC
Uint16
System Output RMS Current Phs C
30446
1
Units : A AC
Uint16
System Output Frequency
30447
1
System Output Voltage RMS A-B
30448
1
Units : VAC
Uint16
System Output Voltage RMS B-C
30449
1
Units : VAC
Uint16
System Output Voltage RMS C-A
30450
1
Units : VAC
Uint16
System Output Power Factor Phs A
30451
1
100
Uint16
System Output Power Factor Phs B
30452
1
100
Uint16
System Output Power Factor Phs C
30453
1
100
Output
10
Units : Hz
Uint16
Uint16
System Output Pct Power Phase A
30454
1
Units : %
Uint16
System Output Pct Power Phase B
30455
1
Units : %
Uint16
System Output Pct Power Phase C
30456
1
Units : %
Uint16
MMS Output Apparent Power
30457
1
Units : kVA
Uint16
MMS Output Power
30458
1
Units : kW
Uint16
Output Current Crest Factor Phs A
30459
1
10
Uint16
Output Current Crest Factor Phs B
30460
1
10
Uint16
Output Current Crest Factor Phs C
30461
1
10
Uint16
System Output Power Phase A
30462
1
Units : kW
Uint16
System Output Power Phase B
30463
1
Units : kW
Uint16
System Output Power Phase C
30464
1
Units : kW
Uint16
System Output Apparent Power Phs A
30465
1
Units : kVA
Uint16
System Output Apparent Power Phs B
30466
1
Units : kVA
Uint16
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
220
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-49 Liebert EPM™—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Output Apparent Power Phs C
30467
1
Units : kVA
Uint16
System Output Power
30468
1
Units : kW
Uint16
System Output Apparent Power
30469
1
Units : kVA
Uint16
Inverter On/Off State
30480
1
0 = off
1 = on
Maintenance Bypass Breaker
30481
1
0 = Open
1 = Close
2 = Not Installed
1
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Status
UPS Output Source
30482
System Status
30483
1
1 = Normal Operation
2 = StartUp
8 = Normal with
Warning
16 = Normal with Alarm
32 = Abnormal
Operation
ECO Mode Operation State
30484
1
0 = disabled
1 = enabled
1
0 = Open
1 = Close
2 = Not Installed
1
0 = Open
1 = Close
2 = Not Installed
Input Breaker
Internal Bypass Breaker
30485
30486
Output Breaker
30487
1
0 = Open
1 = Close
2 = Not Installed
UPS Application Mode
30488
1
0 = UPS Mode
1 = Frequency
converter mode
MMS UPS Output Source
30489
1
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Intelligent Parallel Operation State
30490
1
0 = disabled
1 = enabled
221
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-49 Liebert EPM™—Input and Holding (continued)
Data Label
Advanced Efficiency Mode
Input
Holding
# of Reg
Scale
Notes/Units
0 = unknown
1 = ECO mode
2 = Intelligent ECO
mode
3 = Active Inverter
ECO mode
30491
1
System Input Nominal Voltage
30502
1
System Input Nominal Frequency
30503
1
System Input Nominal Current
30504
1
Units : A AC
Uint16
Bypass Nominal Voltage
30505
1
Units : VAC
Uint16
System Output Nominal Voltage
30506
1
Units : VAC
Uint16
System Output Nominal Frequency
30507
1
Total System Operating Time
30518
2
Average system efficiency
30520
1
Inlet Air Temperature
30521
1
Units : deg C
Uint16
Inlet Air Temperature
30522
1
Units : deg F
Uint16
2
Secs since
Epoch(UTC)
System Configuration
Units : VAC
Uint16
10
10
Units : Hz
Uint16
Units : Hz
Uint16
System Analog
Units : hr
Uint32
10
Units : %
Uint16
System Configuration
System Date and Time
39998
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
222
49998
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-50 Liebert EPM™—Glossary
Data Label
Advanced Efficiency Mode
Data Description
Advanced efficiency modes where the UPS supports the critical load
using the static bypass.
Average system efficiency
Average system efficiency
Battery Breaker 1 Open Failure
Battery circuit breaker 1 failed to open
Battery Breaker 2 Open Failure
Battery circuit breaker 2 failed to open
Battery Breaker 3 Open Failure
Battery circuit breaker 3 failed to open
Battery Breaker 4 Open Failure
Battery circuit breaker 4 failed to open
Battery Capacity Low
Battery capacity is low
Battery Charge Equalization Timeout
The battery equalizing is time out.
Battery Charging Error
The battery is not charging properly
Battery Charging Inhibited
Battery charging is inhibited due to an external inhibit signal
Battery Circuit Breaker 1 Open
Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open
Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open
Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open
Battery circuit breaker 4 is open
Battery Converter Current Limit
The battery converter has reached is maximum current limit.
Battery Converter Failure
Battery converter failure. This is a summary event caused by one or
more power sub-modules in a UPS module.
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage
level.
Battery Fault
A short circuit exists in the battery system.
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Low
The calculated battery time remaining has reached the low battery
threshold
Battery Not Qualified
The UPS battery voltage is not qualified. This event will be detected
even in the absence of battery disconnect or when it is open.
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Room Alarm
The ambient temperature of the battery room is abnormal.
Battery Self Test
Battery self test is in progress
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Terminals Reversed
The measured battery voltage is a negative value due to reverse
battery terminal connections.
Battery Time Remaining
The calculated available time on battery
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a
battery cabinet
Bypass - Excess Auto Retransfers
The number of auto retransfers, from bypass to inverter, has exceeded
the maximum for a specified time interval
Bypass Backfeed Detected
The system detected a voltage on the bypass when none was
expected
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage Fault
The system has detected the bypass voltage is unqualified.
Bypass Input Voltage RMS A-B
The bypass input RMS voltage between phases A and B
Bypass Input Voltage RMS A-N
The bypass input RMS voltage between phase A and Neutral
Bypass Input Voltage RMS B-C
The bypass input RMS voltage between phases B and C
Bypass Input Voltage RMS B-N
The bypass input RMS voltage between phase B and Neutral
Bypass Input Voltage RMS C-A
The bypass input RMS voltage between phases C and A
Bypass Input Voltage RMS C-N
The bypass input RMS voltage between phase C and Neutral
223
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-50 Liebert EPM™—Glossary (continued)
Data Label
Data Description
Bypass Nominal Voltage
Bypass nominal (or rated) voltage
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Static Switch Unavailable
The static bypass is unavailable to support the critical load.
DC Bus Abnormal
The system has detected an abnormal DC Bus Voltage.
DC Bus Current
The current at the battery input terminals. In charging mode, the
current will be a positive value. In discharging mode, the current will be
a negative value
ECO Mode Operation State
This setting is used to enable or disable ECO Mode.
Equipment Over Temperature
Equipment over temperature summary event
Excess ECO Suspends
Number of automatic suspensions has exceeded the ECO Mode Maximum Auto Suspensions setting.
Fuse Failure
A summary event indicating one or more fuse failures
Inlet Air Temperature
The temperature of the inlet air
Input Breaker
Input breaker
Input Source Backfeed
The battery is backfeeding the input source.
Intelligent Parallel Operation State
This setting is used to enable or disable Intelligent Paralleling.
Internal Bypass Breaker
Internal bypass breaker
Internal Communications Failure
The control has detected a communication failure of a component on
the internal communication bus
Inverter Failure
Inverter failure - inverter output is off
Inverter On/Off State
inverter on/off state
Inverter Overload
Inverter in overload fault
Inverter Relay Fault
The inverter relay has malfunctioned.
Inverter Shutdown - Overload
The inverter has shutdown due to a sustained overload
LBS Cable Failure
Load Bus Sync communications is abnormal. A problem with the LBS
cable may exist.
LBS Inhibited
The system has detected that conditions to perform Load Bus Sync
are not satisfied
Load Impact Transfer
On bypass as result of load impact.
Load Sharing Fault
Difference between any phase inverter current of unit and the relevant
average output current of parallel system is more than a specific
percent of nominal current.
Loss of Redundancy
The multi-module collection doesn't have enough modules to satisfy
the redundancy configuration.
Loss of Synchronization
The inverter and bypass are no longer synchronized.
Main Battery Disconnect Open
Main battery disconnect is open
Mains Input Neutral Lost
Loss of neutral in the input source is detected.
Maintenance Bypass Breaker
Maintenance bypass breaker
MMS On Battery
The multi-module system is on battery
MMS Output Apparent Power
The sum total apparent power of all system output modules
MMS Output Power
The sum total power of all system output modules
MMS Over Capacity
The multi-module system load is larger than the apparent power limit
setting.
MMS Overload
Multi-module system overload
MMS UPS Output Source
Multi-module UPS output source
On Generator
A generator is supplying the power to the system
Output Breaker
Output breaker
Output Current Crest Factor Phs A
Output current crest factor of Phase A.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
224
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-50 Liebert EPM™—Glossary (continued)
Data Label
Data Description
Output Current Crest Factor Phs B
Output current crest factor of Phase B.
Output Current Crest Factor Phs C
Output current crest factor of Phase C.
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Parallel Cable Failure
The UPS parallel system communications is abnormal. A problem with
the parallel cable may exist.
Parallel Comm Warning
Parallel communication bus warning
Power Module Over Temperature
The Power Module has detected an over temperature condition.
Power Supply Failure
Power supply failure
Rectifier Failure
Rectifier failure - rectifier is off
System Date and Time
The system date and time
System Fan Failure
System fan failure - one or more fans have failed
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Current Limit
The RMS input current has reached the input current limit threshold
System Input Frequency
The system input frequency
System Input Nominal Current
The nominal (or rated) system input current
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the
sequence preferred for the rectifier (A-B-C)
System Input Power Factor Phs A
The system input power factor for Phase A
System Input Power Factor Phs B
The system input power factor for Phase B
System Input Power Factor Phs C
The system input power factor for Phase C
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Output Apparent Power Phs A
System output apparent power on phase A
System Output Apparent Power Phs B
System output apparent power on phase B
System Output Apparent Power Phs C
System output apparent power on phase C
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Nominal Frequency
The nominal (or rated) system output frequency
System Output Nominal Voltage
The nominal (or rated) system output voltage
System Output Pct Power Phase A
The system output power on phase A as a percentage of the rated
capacity
System Output Pct Power Phase B
The system output power on phase B as a percentage of the rated
capacity
System Output Pct Power Phase C
The system output power on phase C as a percentage of the rated
capacity
System Output Power Factor Phs A
The system output power factor of phase A
225
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-50 Liebert EPM™—Glossary (continued)
Data Label
Data Description
System Output Power Factor Phs B
The system output power factor of phase B
System Output Power Factor Phs C
The system output power factor of phase C
System Output Power Phase A
The system output power on phase A.
System Output Power Phase B
The system output power on phase B.
System Output Power Phase C
The system output power on phase C.
System Output Power
The sum total power of all system output phases
System Output RMS Current Phs A
The system output RMS current for Phase A
System Output RMS Current Phs B
The system output RMS current for Phase B
System Output RMS Current Phs C
The system output RMS current for Phase C
System Output Voltage RMS A-B
The system output RMS voltage between phases A and B
System Output Voltage RMS A-N
The system output RMS voltage between phases A and Neutral
System Output Voltage RMS B-C
The system output RMS voltage between phases B and C
System Output Voltage RMS B-N
The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A
The system output RMS voltage between phases C and A
System Output Voltage RMS C-N
The system output RMS voltage between phases C and Neutral
System Shutdown - EPO
System shutdown due to Emergency Power Off (EPO)
System Status
The operating status for the system
Top Outlet Fan Fault
Top outlet fan fault - one or more top outlet fans have failed.
Total System Operating Time
The cumulative operation time of the unit
Transfer to Bypass - System Overload
The UPS System has transferred to bypass because the active power
modules cannot support the critical load.
UPS Application Mode
UPS application mode.
UPS battery1 status
UPS battery status
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
User Operation Invalid
User attempted an invalid operation.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
226
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-51 Liebert eXL™—Status and Coil
Data Label
Status
Coil
Number
of Bits
Notes
Input
Mains Input Neutral Lost
10001
1
Active on Alarm
System Input Phs Rotation Error
10002
1
Active on Alarm
System Input Power Problem
10003
1
Active on Alarm
Input Source Backfeed
10004
1
Active on Alarm
10015
1
Active on Alarm
Bypass
Bypass Not Available
Bypass Static Switch Unavailable
10016
1
Active on Alarm
Bypass - Excess Auto Retransfers
10017
1
Active on Alarm
UPS Output on Bypass
10018
1
Active on Alarm
Output Load on Maint. Bypass
10019
1
Active on Alarm
Bypass Overload
10020
1
Active on Alarm
Bypass Frequency Error
10021
1
Active on Alarm
Bypass Input Voltage Fault
10022
1
Active on Alarm
Bypass Backfeed Detected
10023
1
Active on Alarm
Main Battery Disconnect Open
10034
1
Active on Alarm
Battery Circuit Breaker 4 Open
10035
1
Active on Alarm
Battery Circuit Breaker 3 Open
10036
1
Active on Alarm
Battery Circuit Breaker 2 Open
10037
1
Active on Alarm
Battery Circuit Breaker 1 Open
10038
1
Active on Alarm
Battery
Battery Self Test
10039
1
Active on Alarm
Battery Charging Inhibited
10040
1
Active on Alarm
Battery Discharging
10041
1
Active on Alarm
Battery Manual Test In Progress
10042
1
Active on Alarm
Battery Auto Test In Progress
10043
1
Active on Alarm
Battery Test Passed
10044
1
Active on Alarm
Battery Test Failed
10045
1
Active on Alarm
Battery Over Temperature
10046
1
Active on Alarm
Battery Low
10047
1
Active on Alarm
Battery Ground Fault
10048
1
Active on Alarm
Battery Not Qualified
10049
1
Active on Alarm
Battery Terminals Reversed
10050
1
Active on Alarm
Battery Capacity Low
10051
1
Active on Alarm
Battery Converter Current Limit
10052
1
Active on Alarm
Battery Charge Equalization Timeout
10053
1
Active on Alarm
Battery Fault
10054
1
Active on Alarm
Battery Room Alarm
10055
1
Active on Alarm
Battery Breaker 1 Open Failure
10056
1
Active on Alarm
Battery Breaker 2 Open Failure
10057
1
Active on Alarm
Battery Breaker 3 Open Failure
10058
1
Active on Alarm
Battery Breaker 4 Open Failure
10059
1
Active on Alarm
Battery Equalize
10060
1
Active on Alarm
10071
1
Active on Alarm
Inverter
Loss of Synchronization
227
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-51 Liebert eXL™—Status and Coil (continued)
Data Label
Status
Coil
Number
of Bits
Notes
Output
Output Overload
10082
1
Active on Alarm
System Output Fault
10083
1
Active on Alarm
Power Module Input Current Abnormal
10094
1
Active on Alarm
Rectifier Failure
10095
1
Active on Alarm
Inverter Failure
10096
1
Active on Alarm
DC Bus Abnormal
10097
1
Active on Alarm
Load Sharing Fault
10098
1
Active on Alarm
Power Modules 1
Inverter Relay Fault
10099
1
Active on Alarm
Battery Charging Error
10100
1
Active on Alarm
Battery Converter Failure
10101
1
Active on Alarm
Power Module Balancer of DC Bus Failure
10102
1
Active on Alarm
Inverter Shutdown - Overload
10103
1
Active on Alarm
Power Module Fuse Failure
10104
1
Active on Alarm
Power Module Power Supply Failure
10105
1
Active on Alarm
Power Module Fan Fault
10106
1
Active on Alarm
Power Module Over Temperature
10107
1
Active on Alarm
Inverter Overload
10108
1
Active on Alarm
Power Module Input Current Abnormal
10119
1
Active on Alarm
Rectifier Failure
10120
1
Active on Alarm
Inverter Failure
10121
1
Active on Alarm
DC Bus Abnormal
10122
1
Active on Alarm
Load Sharing Fault
10123
1
Active on Alarm
Power Modules 2
Inverter Relay Fault
10124
1
Active on Alarm
Battery Charging Error
10125
1
Active on Alarm
Battery Converter Failure
10126
1
Active on Alarm
Power Module Balancer of DC Bus Failure
10127
1
Active on Alarm
Inverter Shutdown - Overload
10128
1
Active on Alarm
Power Module Fuse Failure
10129
1
Active on Alarm
Power Module Power Supply Failure
10130
1
Active on Alarm
Power Module Fan Fault
10131
1
Active on Alarm
Power Module Over Temperature
10132
1
Active on Alarm
Inverter Overload
10133
1
Active on Alarm
Power Module Input Current Abnormal
10569
1
Active on Alarm
Rectifier Failure
10570
1
Active on Alarm
Inverter Failure
10571
1
Active on Alarm
DC Bus Abnormal
10572
1
Active on Alarm
Load Sharing Fault
10573
1
Active on Alarm
Power Modlues 20
Inverter Relay Fault
10574
1
Active on Alarm
Battery Charging Error
10575
1
Active on Alarm
Battery Converter Failure
10576
1
Active on Alarm
Power Module Balancer of DC Bus Failure
10577
1
Active on Alarm
Inverter Shutdown - Overload
10578
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
228
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-51 Liebert eXL™—Status and Coil (continued)
Number
of Bits
Notes
10579
1
Active on Alarm
Power Module Power Supply Failure
10580
1
Active on Alarm
Power Module Fan Fault
10581
1
Active on Alarm
Data Label
Status
Power Module Fuse Failure
Coil
Power Module Over Temperature
10582
1
Active on Alarm
Inverter Overload
10583
1
Active on Alarm
10594
1
Active on Alarm
System Status
Loss of Redundancy
Parallel Cable Failure
10595
1
Active on Alarm
LBS Cable Failure
10596
1
Active on Alarm
Transfer to Bypass - System Overload
10597
1
Active on Alarm
Excess ECO Suspends
10598
1
Active on Alarm
Transformer Overtemperature
10599
1
Active on Alarm
MMS Over Capacity
10600
1
Active on Alarm
Loss of Redundancy
10601
1
Active on Alarm
User Operation Invalid
10602
1
Active on Alarm
Load Impact Transfer
10603
1
Active on Alarm
Internal Communications Failure
10604
1
Active on Alarm
MMS Overload
10605
1
Active on Alarm
Parallel Comm Warning
10606
1
Active on Alarm
Equipment Over Temperature
10607
1
Active on Alarm
LBS Inhibited
10608
1
Active on Alarm
On Generator
10609
1
Active on Alarm
LBS Active
10610
1
Active on Alarm
System Shutdown - EPO
10611
1
Active on Alarm
Top Outlet Fan Fault
10612
1
Active on Alarm
229
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-52 Liebert eXL™—Input and Holding
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Input
System Input RMS A-B
30385
1
Units : VAC
Uint16
System Input RMS B-C
30386
1
Units : VAC
Uint16
System Input RMS C-A
30387
1
Units : VAC
Uint16
System Input RMS Current Phase A
30388
1
Units : A AC
Uint16
System Input RMS Current Phase B
30389
1
Units : A AC
Uint16
System Input RMS Current Phase C
30390
1
Units : A AC
Uint16
System Input Frequency
30391
1
System Input RMS A-N
30392
1
Units : VAC
Uint16
System Input RMS B-N
30393
1
Units : VAC
Uint16
System Input RMS C-N
30394
1
Units : VAC
Uint16
System Input Power Factor Phs A
30395
1
10
100
Units : Hz
Uint16
Uint16
System Input Power Factor Phs B
30396
1
100
Uint16
System Input Power Factor Phs C
30397
1
100
Uint16
System Input Nominal Voltage
30398
1
System Input Nominal Frequency
30399
1
System Input Nominal Current
30400
1
Units : A AC
Uint16
System Input Brown Out Count
30401
1
Uint16
System Input Black Out Count
30402
1
Uint16
Input Breaker
30403
1
0 = Open
1 = Close
2 = Not Installed
Bypass Input Voltage RMS A-N
30414
1
Units : VAC
Uint16
Bypass Input Voltage RMS B-N
30415
1
Units : VAC
Uint16
Bypass Input Voltage RMS C-N
30416
1
Units : VAC
Uint16
Bypass Input Frequency
30417
1
Bypass Input Voltage RMS A-B
30418
1
Units : VAC
Uint16
10
Units : Hz
Uint16
Bypass
10
Units : Hz
Uint16
Units : VAC
Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
230
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-52 Liebert eXL™—Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Bypass Input Voltage RMS B-C
30419
1
Units : VAC
Uint16
Bypass Input Voltage RMS C-A
30420
1
Units : VAC
Uint16
Bypass Nominal Voltage
30421
1
Units : VAC
Uint16
30422
1
0 = Open
1 = Close
2 = Not Installed
Battery Time Remaining
30433
1
Units : min
Uint16
DC Bus Current
30434
1
Units : A DC
Int16
Time Until Next Auto Battery Test
30435
2
Units : min
Uint32
Battery Percentage Charge
30437
1
Units : %
Uint16
Number of Discharge Cycles
30438
1
Uint16
Internal Bypass Breaker
Battery
Accumulated Discharge Time
30439
1
Units : hr
Uint16
Low Battery Warning Time
30440
1
Units : min
Uint16
1
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
UPS Battery Status
30441
Battery charge status.
30442
1
0 = fully charged
1 = charging
2 = discharging
3 = not charging (charger off)
Manual Battery Test
30443
1
1 = Start Test
Automatic Battery Test
30444
1
0 = disabled
1 = enabled
0 = 8 weeks
1 = 12 weeks
2 = 16 weeks
3 = 20 weeks
4 = 26 weeks
Auto Battery Test Interval
30445
1
DC Bus Voltage
30446
1
Battery Temperature
30447
1
Units : deg
C Int16
Battery Temperature
30448
1
Units : deg
F Int16
10
Units : VDC
Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
231
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-52 Liebert eXL™—Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Battery Cabinets 1
Battery Temperature for Cabinet
30459
1
Units : deg C
Int16
Battery Temperature for Cabinet
30460
1
Units : deg F
Int16
Battery Volts for Cabinet
30461
1
Units : VDC
Uint16
Battery Temperature for Cabinet
30472
1
Units : deg C
Int16
Battery Temperature for Cabinet
30473
1
Units : deg F
Int16
Battery Volts for Cabinet
30474
1
Units : VDC
Uint16
Battery Temperature for Cabinet
30550
1
Units : deg C
Int16
Battery Temperature for Cabinet
30551
1
Units : deg F
Int16
Battery Volts for Cabinet
30552
1
Units : VDC
Uint16
Output Breaker
30563
1
0 = Open
1 = Close
2 = Not Installed
Inverter On/Off State
30564
1
0 = off
1 = on
System Output Voltage RMS A-N
30575
1
Units : VAC
Uint16
System Output Voltage RMS B-N
30576
1
Units : VAC
Uint16
System Output Voltage RMS C-N
30577
1
Units : VAC
Uint16
System Output RMS Current Phs A
30578
1
Units : A AC
Uint16
System Output RMS Current Phs B
30579
1
Units : A AC
Uint16
System Output RMS Current Phs C
30580
1
Units : A AC
Uint16
System Output Frequency
30581
1
System Output Voltage RMS A-B
30582
1
Units : VAC
Uint16
System Output Voltage RMS B-C
30583
1
Units : VAC
Uint16
Battery Cabinets 2
Battery Cabinets 8
Inverter
Output
10
Units : Hz Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
232
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-52 Liebert eXL™—Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Units : VAC
Uint16
System Output Voltage RMS C-A
30584
1
System Output Power Factor Phs A
30585
1
100
Uint16
System Output Power Factor Phs B
30586
1
100
Uint16
System Output Power Factor Phs C
30587
1
100
Uint16
System Output Pct Power Phase A
30588
1
Units : %
Uint16
System Output Pct Power Phase B
30589
1
Units : %
Uint16
System Output Pct Power Phase C
30590
1
Units : %
Uint16
MMS Output Apparent Power
30591
1
Units : kVA
Uint16
MMS Output Power
30592
1
Units : kW
Uint16
Output Current Crest Factor Phs A
30593
1
10
Uint16
Output Current Crest Factor Phs B
30594
1
10
Uint16
Output Current Crest Factor Phs C
30595
1
10
Uint16
System Output Power Phase A
30596
1
Units : kW
Uint16
System Output Power Phase B
30597
1
Units : kW
Uint16
System Output Power Phase C
30598
1
Units : kW
Uint16
System Output Apparent Power Phs A
30599
1
Units : kVA
Uint16
System Output Apparent Power Phs B
30600
1
Units : kVA
Uint16
System Output Apparent Power Phs C
30601
1
Units : kVA
Uint16
System Output Power
30602
1
Units : kW
Uint16
System Output Apparent Power
30603
1
Units : kVA Uint16
System Output Pct Pwr (VA) Phs A
30604
1
Units : %
Uint16
System Output Pct Pwr (VA) Phs B
30605
1
Units : %
Uint16
System Output Pct Pwr (VA) Phs C
30606
1
Units : %
Uint16
System Output Nominal Voltage
30607
1
Units : VAC
Uint16
System Output Nominal Frequency
30608
1
10
Units : Hz
Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
233
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-52 Liebert eXL™—Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Power Modules 1
Power Module Sleep Status
30619
1
0 = Sleeping
1 = Not Sleeping
Module Operating Status
30620
1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status
30621
1
0 = Inverter Inactive
1 = Inverter Active
30632
1
0 = Sleeping
1 = Not Sleeping
Power Modules 2
Power Module Sleep Status
Module Operating Status
30633
1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status
30634
1
0 = Inverter Inactive
1 = Inverter Active
30866
1
0 = Sleeping
1 = Not Sleeping
Power Modules 20
Power Module Sleep Status
Module Operating Status
30867
1
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status
30868
1
0 = Inverter Inactive
1 = Inverter Active
Power Module Bypass Input Frequency
30879
1
Power Module Bypass Input Voltage RMS A-N
30880
1
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS B-N
30881
1
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS C-N
30882
1
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS A-B
30883
1
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS B-C
30884
1
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS C-A
30885
1
Units : VAC
Uint16
System Set To Operate With
30896
1
0 = No Redundancy
1 = Redundancy
Number Of Active Power Modules
30897
1
Uint16
Bypass Control Module
10
Units : Hz
Uint16
System Status
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
234
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-52 Liebert eXL™—Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Installed Power Modules
30898
1
Uint16
Inlet Air Temperature
30899
1
Units : deg C
Uint16
Inlet Air Temperature
30900
1
Units : deg F
Uint16
Average system efficiency
30901
1
Maintenance Bypass Breaker
30902
1
0 = Open
1 = Close
2 = Not Installed
ECO Mode Operation State
30903
1
0 = disabled
1 = enabled
UPS Application Mode
30904
1
0 = UPS Mode
1 = Frequency converter
mode
10
Units : %
Uint16
MMS UPS Output Source
30905
1
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Intelligent Parallel Operation State
30906
1
0 = disabled
1 = enabled
Bypass Isolation Breaker
30907
1
0 = Open
1 = Close
2 = Not Installed
Total System Operating Time
30918
2
Units : hr
Uint32
System Capacity
30920
1
Units : kVA
Uint16
1
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
1
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
2
Units : Secs since
Epoch(UTC)
System Configuration
UPS Output Source
30921
System Status
30922
System Date and Time
39998
49998
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
235
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-53 Liebert eXL™—Glossary
Data Label
Data Description
Accumulated Discharge Time
Total accumulated discharge time for the Battery Module since it was made.
Auto Battery Test Interval
The time between automatic battery tests.
Automatic Battery Test
Enable/disable the automatic battery test schedule.
Average system efficiency
Average system efficiency
Battery Auto Test In Progress
Automatic battery test is in progress
Battery Breaker 1 Open Failure
Battery circuit breaker 1 failed to open
Battery Breaker 2 Open Failure
Battery circuit breaker 2 failed to open
Battery Breaker 3 Open Failure
Battery circuit breaker 3 failed to open
Battery Breaker 4 Open Failure
Battery circuit breaker 4 failed to open
Battery Capacity Low
Battery capacity is low
Battery Charge Equalization Timeout
The battery equalizing is time out.
Battery charge status.
Battery charge status.
Battery Charging Error
The battery is not charging properly
Battery Charging Inhibited
Battery charging is inhibited due to an external inhibit signal
Battery Circuit Breaker 1 Open
Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open
Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open
Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open
Battery circuit breaker 4 is open
Battery Converter Current Limit
The battery converter has reached is maximum current limit.
Battery Converter Failure
Battery converter failure. This is a summary event caused by one or more power
sub-modules in a UPS module.
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage level.
Battery Fault
A short circuit exists in the battery system.
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Low
The calculated battery time remaining has reached the low battery threshold
Battery Manual Test In Progress
Manual battery test is in progress
Battery Not Qualified
The UPS battery voltage is not qualified. This event will be detected even in the
absence of battery disconnect or when it is open.
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Percentage Charge
The percentage of battery charge
Battery Room Alarm
The ambient temperature of the battery room is abnormal.
Battery Self Test
Battery self test is in progress
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Temperature
The highest battery temperature among all Battery Cabinets
Battery Terminals Reversed
The measured battery voltage is a negative value due to reverse battery terminal
connections.
Battery Test Failed
Battery test failed
Battery Test Passed
Battery test passed
Battery Time Remaining
The calculated available time on battery
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a battery
cabinet
Bypass - Excess Auto Retransfers
The number of auto retransfers, from bypass to inverter, has exceeded the
maximum for a specified time interval
Bypass Backfeed Detected
The system detected a voltage on the bypass when none was expected
Bypass Frequency Error
The bypass frequency is outside the inverter synchronization limits
Bypass Input Frequency
The bypass input frequency
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
236
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-53 Liebert eXL™—Glossary (continued)
Data Label
Data Description
Bypass Input Voltage Fault
The system has detected the bypass voltage is unqualified.
Bypass Input Voltage RMS A-B
The bypass input RMS voltage between phases A and B
Bypass Input Voltage RMS A-N
The bypass input RMS voltage between phase A and Neutral
Bypass Input Voltage RMS B-C
The bypass input RMS voltage between phases B and C
Bypass Input Voltage RMS B-N
The bypass input RMS voltage between phase B and Neutral
Bypass Input Voltage RMS C-A
The bypass input RMS voltage between phases C and A
Bypass Input Voltage RMS C-N
The bypass input RMS voltage between phase C and Neutral
Bypass Isolation Breaker
Bypass isolation breaker
Bypass Nominal Voltage
Bypass nominal (or rated) voltage
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Overload
Bypass overloaded, reduce load immediately.
Bypass Static Switch Unavailable
The static bypass is unavailable to support the critical load.
DC Bus Abnormal
The system has detected an abnormal DC Bus Voltage.
DC Bus Current
The current at the battery input terminals. In charging mode, the current will be a
positive value. In discharging mode, the current will be a negative value
DC Bus Voltage
The voltage between the positive and negative terminals of the DC bus at the
battery input
ECO Mode Operation State
This setting is used to enable or disable ECO Mode.
Equipment Over Temperature
Equipment over temperature summary event
Excess ECO Suspends
Number of automatic suspensions has exceeded the ECO Mode - Maximum
Auto Suspensions setting.
Inlet Air Temperature
The temperature of the inlet air
Input Breaker
Input breaker
Input Source Backfeed
The battery is backfeeding the input source.
Intelligent Parallel Operation State
This setting is used to enable or disable Intelligent Paralleling.
Internal Bypass Breaker
Internal bypass breaker
Internal Communications Failure
The control has detected a communication failure of a component on the internal
communication bus
Inverter Failure
Inverter failure - inverter output is off
Inverter On/Off State
inverter on/off state
Inverter Overload
Inverter in overload fault
Inverter Relay Fault
The inverter relay has malfunctioned.
Inverter Shutdown - Overload
The inverter has shutdown due to a sustained overload
Inverter Status
Status of the inverter output. Active means the inverter is online with regulated
output voltage and ready to power the load. Inactive means the inverter is offline
and not ready to power the load.
LBS Active
The Load Bus Sync option is active
LBS Cable Failure
Load Bus Sync communications is abnormal. A problem with the LBS cable may
exist.
LBS Inhibited
The system has detected that conditions to perform Load Bus Sync are not
satisfied
Load Impact Transfer
On bypass as result of load impact.
Load Sharing Fault
Difference between any phase inverter current of unit and the relevant average
output current of parallel system is more than a specific percent of nominal
current.
Loss of Redundancy
The multi-module collection doesn't have enough modules to satisfy the
redundancy configuration.
Loss of Redundancy
The system has an insufficient number of power modules to provide
redundancy.
237
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-53 Liebert eXL™—Glossary (continued)
Data Label
Data Description
Loss of Synchronization
The inverter and bypass are no longer synchronized.
Low Battery Warning Time
When battery time remaining falls to, or below, this value the low battery alarm is
activated.
Main Battery Disconnect Open
Main battery disconnect is open
Mains Input Neutral Lost
Loss of neutral in the input source is detected.
Maintenance Bypass Breaker
Maintenance bypass breaker
Manual Battery Test
Command to initiate a manual battery test.
MMS Output Apparent Power
The sum total apparent power of all system output modules
MMS Output Power
The sum total power of all system output modules
MMS Over Capacity
The multi-module system load is larger than the apparent power limit setting.
MMS Overload
Multi-module system overload
MMS UPS Output Source
Multi-module UPS output source
Module Operating Status
The operating status for this Power Module.
Number Of Active Power Modules
The total number of active power modules.
Number of Discharge Cycles
The total number of battery discharge cycles for the Battery Module since it was
made.
Number of Installed Power Modules
The total number of Power Modules installed.
On Generator
A generator is supplying the power to the system
Output Breaker
Output breaker
Output Current Crest Factor Phs A
Output current crest factor of Phase A.
Output Current Crest Factor Phs B
Output current crest factor of Phase B.
Output Current Crest Factor Phs C
Output current crest factor of Phase C.
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Output Overload
An overload exists on the output.
Parallel Cable Failure
The UPS parallel system communications is abnormal. A problem with the
parallel cable may exist.
Parallel Comm Warning
Parallel communication bus warning
Power Module Balancer of DC Bus Failure
Balancer of DC Bus in the power module has failed
Power Module Bypass Input Frequency
The bypass input frequency detected by power module
Power Module Bypass Input Voltage RMS
A-B
The bypass input RMS voltage between phases A and B detected by power
module
Power Module Bypass Input Voltage RMS
A-N
The bypass input RMS voltage between phase A and Neutral detected by power
module
Power Module Bypass Input Voltage RMS
B-C
The bypass input RMS voltage between phases B and C detected by power
module
Power Module Bypass Input Voltage RMS
B-N
The bypass input RMS voltage between phase B and Neutral detected by power
module
Power Module Bypass Input Voltage RMS
C-A
The bypass input RMS voltage between phases C and A detected by power
module
Power Module Bypass Input Voltage RMS
C-N
The bypass input RMS voltage between phase C and Neutral detected by power
module
Power Module Fan Fault
The Power Module has detected a fan fault.
Power Module Fuse Failure
A summary event indicating one or more fuse failures in the power module
Power Module Input Current Abnormal
Input current of the power module is abnormal
Power Module Over Temperature
The Power Module has detected an over temperature condition.
Power Module Power Supply Failure
Power module power supply failure
Power Module Sleep Status
Sleep status of the Power module
Rectifier Failure
Rectifier failure - rectifier is off
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
238
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-53 Liebert eXL™—Glossary (continued)
Data Label
Data Description
System Capacity
System capacity supported by the installed power modules.
System Date and Time
The system date and time
System Input Black Out Count
The number of occurrences, since the last reset, where the input was not
qualified to provide power to the system
System Input Brown Out Count
The number of occurrences, since the last reset, where the system input voltage
has fallen below a pre-determined threshold for a specified amount of time
System Input Frequency
The system input frequency
System Input Nominal Current
The nominal (or rated) system input current
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the sequence
preferred for the rectifier (A-B-C)
System Input Power Factor Phs A
The system input power factor for Phase A
System Input Power Factor Phs B
The system input power factor for Phase B
System Input Power Factor Phs C
The system input power factor for Phase C
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Output Apparent Power Phs A
System output apparent power on phase A
System Output Apparent Power Phs B
System output apparent power on phase B
System Output Apparent Power Phs C
System output apparent power on phase C
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Nominal Frequency
The nominal (or rated) system output frequency
System Output Nominal Voltage
The nominal (or rated) system output voltage
System Output Pct Power Phase A
The system output power on phase A as a percentage of the rated capacity
System Output Pct Power Phase B
The system output power on phase B as a percentage of the rated capacity
System Output Pct Power Phase C
The system output power on phase C as a percentage of the rated capacity
System Output Pct Pwr (VA) Phs A
The system output apparent power on phase A as a percentage of the rated
capacity
System Output Pct Pwr (VA) Phs B
The system output apparent power on phase B as a percentage of the rated
capacity
System Output Pct Pwr (VA) Phs C
The system output apparent power on phase C as a percentage of the rated
capacity
System Output Power Factor Phs A
The system output power factor of phase A
System Output Power Factor Phs B
The system output power factor of phase B
System Output Power Factor Phs C
The system output power factor of phase C
System Output Power Phase A
The system output power on phase A.
System Output Power Phase B
The system output power on phase B.
System Output Power Phase C
The system output power on phase C.
239
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-53 Liebert eXL™—Glossary (continued)
Data Label
Data Description
System Output Power
The sum total power of all system output phases
System Output RMS Current Phs A
The system output RMS current for Phase A
System Output RMS Current Phs B
The system output RMS current for Phase B
System Output RMS Current Phs C
The system output RMS current for Phase C
System Output Voltage RMS A-B
The system output RMS voltage between phases A and B
System Output Voltage RMS A-N
The system output RMS voltage between phases A and Neutral
System Output Voltage RMS B-C
The system output RMS voltage between phases B and C
System Output Voltage RMS B-N
The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A
The system output RMS voltage between phases C and A
System Output Voltage RMS C-N
The system output RMS voltage between phases C and Neutral
System Set To Operate With
If this point reports 'Redundancy' then the system is configured for redundancy
and the 'Loss of Redundancy' alarm is enabled.
System Shutdown - EPO
System shutdown due to Emergency Power Off (EPO)
System Status
The operating status for the system
Time Until Next Auto Battery Test
The time until the next automatic battery test is started.
Top Outlet Fan Fault
Top outlet fan fault - one or more top outlet fans have failed.
Total System Operating Time
The cumulative operation time of the unit
Transfer to Bypass - System Overload
The UPS System has transferred to bypass because the active power modules
cannot support the critical load.
Transformer Overtemperature
Transformer temperature has exceeded the limit
UPS Application Mode
UPS application mode.
UPS Battery Status
UPS battery status
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
User Operation Invalid
User attempted an invalid operation.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
240
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-54 Liebert eXM™—Controller with LCD HMI—Status and Coil
Data Label
Status
Coil
Number
of Bits
Notes
System Status
Battery Equalize
10001
—
1
Active on Alarm
Battery Charging Inhibited
10002
—
1
Active on Alarm
On Generator
10003
—
1
Active on Alarm
Battery Self Test
10004
—
1
Active on Alarm
Battery Circuit Breaker 1 Open
10005
—
1
Active on Alarm
Battery Circuit Breaker 2 Open
10006
—
1
Active on Alarm
Battery Circuit Breaker 3 Open
10007
—
1
Active on Alarm
Battery Circuit Breaker 4 Open
10008
—
1
Active on Alarm
Main Battery Disconnect Open
10009
—
1
Active on Alarm
System Events
System Input Power Problem
10020
—
1
Active on Alarm
Rectifier Failure
10021
—
1
Active on Alarm
Inverter Failure
10022
—
1
Active on Alarm
Bypass Not Available
10023
—
1
Active on Alarm
Battery Low
10024
—
1
Active on Alarm
LBS Inhibited
10025
—
1
Active on Alarm
System Fan Failure
10026
—
1
Active on Alarm
Equipment Over Temperature
10027
—
1
Active on Alarm
System Shutdown - EPO
10028
—
1
Active on Alarm
Bypass Static Switch Unavailable
10029
—
1
Active on Alarm
Bypass - Excess Auto Retransfers
10030
—
1
Active on Alarm
Parallel Comm Warning
10031
—
1
Active on Alarm
Power Supply Failure
10032
—
1
Active on Alarm
Battery Over Temperature
10033
—
1
Active on Alarm
System Input Phs Rotation Error
10034
—
1
Active on Alarm
Fuse Failure
10035
—
1
Active on Alarm
Inverter Overload
10036
—
1
Active on Alarm
MMS Overload
10037
—
1
Active on Alarm
Inverter Shutdown - Overload
10038
—
1
Active on Alarm
System Output Fault
10039
—
1
Active on Alarm
Internal Communications Failure
10040
—
1
Active on Alarm
Battery Charging Error
10041
—
1
Active on Alarm
System Input Current Imbalance
10042
—
1
Active on Alarm
Battery Not Qualified
10043
—
1
Active on Alarm
Battery Terminals Reversed
10044
—
1
Active on Alarm
Battery Converter Failure
10045
—
1
Active on Alarm
Load Sharing Fault
10046
—
1
Active on Alarm
DC Bus Abnormal
10047
—
1
Active on Alarm
Mains Input Neutral Lost
10048
—
1
Active on Alarm
Load Impact Transfer
10049
—
1
Active on Alarm
User Operation Invalid
10050
—
1
Active on Alarm
Battery Discharging
10051
—
1
Active on Alarm
UPS Output on Bypass
10052
—
1
Active on Alarm
Output Load on Maint. Bypass
10053
—
1
Active on Alarm
Battery Capacity Low
10054
—
1
Active on Alarm
241
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-54 Liebert eXM™—Controller with LCD HMI—Status and Coil (continued)
Data Label
Status
Coil
Number
of Bits
Notes
MMS On Battery
10055
—
1
Active on Alarm
Loss of Redundancy
10056
—
1
Active on Alarm
Top Outlet Fan Fault
10057
—
1
Active on Alarm
MMS Over Capacity
10058
—
1
Active on Alarm
Bypass Input Voltage Fault
10059
—
1
Active on Alarm
Power Module Over Temperature
10060
—
1
Active on Alarm
Excess ECO Suspends
10061
—
1
Active on Alarm
Battery Ground Fault
10062
—
1
Active on Alarm
System Input Current Limit
10063
—
1
Active on Alarm
Inverter Relay Fault
10064
—
1
Active on Alarm
Transfer to Bypass - System Overload
10065
—
1
Active on Alarm
Input Source Backfeed
10066
—
1
Active on Alarm
Loss of Synchronization
10067
—
1
Active on Alarm
Battery Converter Current Limit
10068
—
1
Active on Alarm
LBS Cable Failure
10069
—
1
Active on Alarm
Battery Charge Equalization Timeout
10070
—
1
Active on Alarm
Parallel Cable Failure
10071
—
1
Active on Alarm
Battery Fault
10072
—
1
Active on Alarm
Battery Room Alarm
10073
—
1
Active on Alarm
Battery Breaker 1 Open Failure
10074
—
1
Active on Alarm
Battery Breaker 2 Open Failure
10075
—
1
Active on Alarm
Battery Breaker 3 Open Failure
10076
—
1
Active on Alarm
Battery Breaker 4 Open Failure
10077
—
1
Active on Alarm
Bypass Backfeed Detected
10078
—
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
242
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-55 Liebert eXM™—Controller with LCD HMI—Input and Holding
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Input RMS A-B
30385
—
1
—
Units : VAC
Uint16
System Input RMS B-C
30386
—
1
—
Units : VAC
Uint16
System Input RMS C-A
30387
—
1
—
Units : VAC
Uint16
System Input RMS Current Phase A
30388
—
1
—
Units : A AC
Uint16
System Input RMS Current Phase B
30389
—
1
—
Units : A AC
Uint16
System Input RMS Current Phase C
30390
—
1
—
Units : A AC
Uint16
System Input Frequency
30391
—
1
10
Units : Hz
Uint16
System Input RMS A-N
30392
—
1
—
Units : VAC
Uint16
System Input RMS B-N
30393
—
1
—
Units : VAC
Uint16
System Input RMS C-N
30394
—
1
—
Units : VAC
Uint16
System Input Power Factor Phs A
30395
—
1
100
Uint16
Input
System Input Power Factor Phs B
30396
—
1
100
Uint16
System Input Power Factor Phs C
30397
—
1
100
Uint16
Bypass Input Voltage RMS A-N
30408
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS B-N
30409
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS C-N
30410
—
1
—
Units : VAC
Uint16
Bypass Input Frequency
30411
—
1
10
Units : Hz
Uint16
Bypass Input Voltage RMS A-B
30412
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS B-C
30413
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS C-A
30414
—
1
—
Units : VAC
Uint16
Battery Time Remaining
30425
—
1
—
Units : min
Uint16
Battery Volts for Cabinet
30426
—
1
—
Units : VDC
Int16
Battery Temperature for Cabinet
30427
—
1
—
Units : deg C
Int16
Battery Temperature for Cabinet
30428
—
1
—
Units : deg F
Int16
DC Bus Current
30429
—
1
—
Units : A DC
Int16
Bypass
Battery
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
243
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-55 Liebert eXM™—Controller with LCD HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
30430
—
1
—
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
System Output Voltage RMS A-N
30441
—
1
—
Units : VAC
Uint16
System Output Voltage RMS B-N
30442
—
1
—
Units : VAC
Uint16
System Output Voltage RMS C-N
30443
—
1
—
Units : VAC
Uint16
System Output RMS Current Phs A
30444
—
1
—
Units : A AC
Uint16
System Output RMS Current Phs B
30445
—
1
—
Units : A AC
Uint16
System Output RMS Current Phs C
30446
—
1
—
Units : A AC
Uint16
System Output Frequency
30447
—
1
10
Units : Hz
Uint16
System Output Voltage RMS A-B
30448
—
1
—
Units : VAC
Uint16
System Output Voltage RMS B-C
30449
—
1
—
Units : VAC
Uint16
System Output Voltage RMS C-A
30450
—
1
—
Units : VAC
Uint16
System Output Power Factor Phs A
30451
—
1
100
Uint16
UPS Battery1 Status
Output
System Output Power Factor Phs B
30452
—
1
100
Uint16
System Output Power Factor Phs C
30453
—
1
100
Uint16
System Output Pct Power Phase A
30454
—
1
—
Units : %
Uint16
System Output Pct Power Phase B
30455
—
1
—
Units : %
Uint16
System Output Pct Power Phase C
30456
—
1
—
Units : %
Uint16
MMS Output Apparent Power
30457
—
1
—
Units : kVA
Uint16
MMS Output Power
30458
—
1
—
Units : kW
Uint16
Output Current Crest Factor Phs A
30459
—
1
10
Uint16
Output Current Crest Factor Phs B
30460
—
1
10
Uint16
Output Current Crest Factor Phs C
30461
—
1
10
Uint16
System Output Power Phase A
30462
—
1
—
Units : kW
Uint16
System Output Power Phase B
30463
—
1
—
Units : kW
Uint16
System Output Power Phase C
30464
—
1
—
Units : kW
Uint16
System Output Apparent Power Phs A
30465
—
1
—
Units : kVA
Uint16
System Output Apparent Power Phs B
30466
—
1
—
Units : kVA
Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
244
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-55 Liebert eXM™—Controller with LCD HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Output Apparent Power Phs C
30467
—
1
—
Units : kVA
Uint16
System Output Power
30468
—
1
—
Units : kW
Uint16
System Output Apparent Power
30469
—
1
—
Units : kVA
Uint16
Inverter On/Off State
30480
—
1
—
0 = off
1 = on
Maintenance Bypass Breaker
30481
—
1
—
0 = Open
1 = Close
2 = Not Installed
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Status
UPS Output Source
30482
—
1
System Status
30483
—
1
—
1 = Normal
Operation
2 = StartUp
8 = Normal with
Warning
16 = Normal with
Alarm
32 = Abnormal
Operation
ECO Mode Operation State
30484
—
1
—
0 = disabled
1 = enabled
Input Breaker
30485
—
1
—
0 = Open
1 = Close
2 = Not Installed
Internal Bypass Breaker
30486
—
1
—
0 = Open
1 = Close
2 = Not Installed
Output Breaker
30487
—
1
—
0 = Open
1 = Close
2 = Not Installed
UPS Application Mode
30488
—
1
—
0 = UPS Mode
1 = Frequency
converter mode
MMS UPS Output Source
30489
—
1
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Intelligent Parallel Operation State
30490
—
1
—
0 = disabled
1 = enabled
—
0 = unknown
1 = ECO mode
2 = Intelligent ECO
mode
3 = Active Inverter
ECO mode
Advanced Efficiency Mode
30491
—
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
245
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-55 Liebert eXM™—Controller with LCD HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Input Nominal Voltage
30502
—
1
—
Units : VAC
Uint16
System Input Nominal Frequency
30503
—
1
10
Units : Hz
Uint16
System Input Nominal Current
30504
—
1
—
Units : A AC
Uint16
Bypass Nominal Voltage
30505
—
1
—
Units : VAC
Uint16
System Output Nominal Voltage
30506
—
1
—
Units : VAC
Uint16
System Output Nominal Frequency
30507
—
1
10
Units : Hz
Uint16
Total System Operating Time
30518
—
2
—
Units : hr
Uint32
Average system efficiency
30520
—
1
10
Units : %
Uint16
Inlet Air Temperature
30521
—
1
—
Units : deg C
Uint16
Inlet Air Temperature
30522
—
1
—
Units : deg F
Uint16
39998
49998
2
—
Secs since
Epoch(UTC)
System Configuration
System Analog
SystemAnalog
System Date and Time
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
246
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-56 Liebert eXM™—Controller with LCD HMI—Glossary
Data Label
Data Description
Advanced Efficiency Mode
Advanced efficiency modes where the UPS supports the critical load using the static
bypass.
Average system efficiency
Average system efficiency
Battery Breaker 1 Open Failure
Battery circuit breaker 1 failed to open
Battery Breaker 2 Open Failure
Battery circuit breaker 2 failed to open
Battery Breaker 3 Open Failure
Battery circuit breaker 3 failed to open
Battery Breaker 4 Open Failure
Battery circuit breaker 4 failed to open
Battery Capacity Low
Battery capacity is low
Battery Charge Equalization Timeout
The battery equalizing is time out.
Battery Charging Error
The battery is not charging properly
Battery Charging Inhibited
Battery charging is inhibited due to an external inhibit signal
Battery Circuit Breaker 1 Open
Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open
Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open
Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open
Battery circuit breaker 4 is open
Battery Converter Current Limit
The battery converter has reached is maximum current limit.
Battery Converter Failure
Battery converter failure. This is a summary event caused by one or more power
sub-modules in a UPS module.
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage level.
Battery Fault
A short circuit exists in the battery system.
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Low
The calculated battery time remaining has reached the low battery threshold
Battery Not Qualified
The UPS battery voltage is not qualified. This event will be detected even in the
absence of battery disconnect or when it is open.
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Room Alarm
The ambient temperature of the battery room is abnormal.
Battery Self Test
Battery self test is in progress
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Terminals Reversed
The measured battery voltage is a negative value due to reverse battery terminal
connections.
Battery Time Remaining
The calculated available time on battery
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a battery cabinet
Bypass - Excess Auto Retransfers
The number of auto retransfers, from bypass to inverter, has exceeded the
maximum for a specified time interval
Bypass Backfeed Detected
The system detected a voltage on the bypass when none was expected
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage Fault
The system has detected the bypass voltage is unqualified.
Bypass Input Voltage RMS A-B
The bypass input RMS voltage between phases A and B
Bypass Input Voltage RMS A-N
The bypass input RMS voltage between phase A and Neutral
Bypass Input Voltage RMS B-C
The bypass input RMS voltage between phases B and C
Bypass Input Voltage RMS B-N
The bypass input RMS voltage between phase B and Neutral
Bypass Input Voltage RMS C-A
The bypass input RMS voltage between phases C and A
Bypass Input Voltage RMS C-N
The bypass input RMS voltage between phase C and Neutral
Bypass Nominal Voltage
Bypass nominal (or rated) voltage
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Static Switch Unavailable
The static bypass is unavailable to support the critical load.
DC Bus Abnormal
The system has detected an abnormal DC Bus Voltage.
247
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-56 Liebert eXM™—Controller with LCD HMI—Glossary (continued)
Data Label
Data Description
DC Bus Current
The current at the battery input terminals. In charging mode, the current will be a
positive value. In discharging mode, the current will be a negative value
ECO Mode Operation State
This setting is used to enable or disable ECO Mode.
Equipment Over Temperature
Equipment over temperature summary event
Excess ECO Suspends
Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto
Suspensions setting.
Fuse Failure
A summary event indicating one or more fuse failures
Inlet Air Temperature
The temperature of the inlet air
Input Breaker
Input breaker
Input Source Backfeed
The battery is backfeeding the input source.
Intelligent Parallel Operation State
This setting is used to enable or disable Intelligent Paralleling.
Internal Bypass Breaker
Internal bypass breaker
Internal Communications Failure
The control has detected a communication failure of a component on the internal
communication bus
Inverter Failure
Inverter failure - inverter output is off
Inverter On/Off State
inverter on/off state
Inverter Overload
Inverter in overload fault
Inverter Relay Fault
The inverter relay has malfunctioned.
Inverter Shutdown - Overload
The inverter has shutdown due to a sustained overload
LBS Cable Failure
Load Bus Sync communications is abnormal. A problem with the LBS cable may
exist.
LBS Inhibited
The system has detected that conditions to perform Load Bus Sync are not satisfied
Load Impact Transfer
On bypass as result of load impact.
Load Sharing Fault
Difference between any phase inverter current of unit and the relevant average
output current of parallel system is more than a specific percent of nominal current.
Loss of Redundancy
The multi-module collection doesn't have enough modules to satisfy the redundancy
configuration.
Loss of Synchronization
The inverter and bypass are no longer synchronized.
Main Battery Disconnect Open
Main battery disconnect is open
Mains Input Neutral Lost
Loss of neutral in the input source is detected.
Maintenance Bypass Breaker
Maintenance bypass breaker
MMS On Battery
The multi-module system is on battery
MMS Output Apparent Power
The sum total apparent power of all system output modules
MMS Output Power
The sum total power of all system output modules
MMS Over Capacity
The multi-module system load is larger than the apparent power limit setting.
MMS Overload
Multi-module system overload
MMS UPS Output Source
Multi-module UPS output source
On Generator
A generator is supplying the power to the system
Output Breaker
Output breaker
Output Current Crest Factor Phs A
Output current crest factor of Phase A.
Output Current Crest Factor Phs B
Output current crest factor of Phase B.
Output Current Crest Factor Phs C
Output current crest factor of Phase C.
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Parallel Cable Failure
The UPS parallel system communications is abnormal. A problem with the parallel
cable may exist.
Parallel Comm Warning
Parallel communication bus warning
Power Module Over Temperature
The Power Module has detected an over temperature condition.
Power Supply Failure
Power supply failure
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
248
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-56 Liebert eXM™—Controller with LCD HMI—Glossary (continued)
Data Label
Data Description
Rectifier Failure
Rectifier failure - rectifier is off
System Date and Time
The system date and time
System Fan Failure
System fan failure - one or more fans have failed
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Current Limit
The RMS input current has reached the input current limit threshold
System Input Frequency
The system input frequency
System Input Nominal Current
The nominal (or rated) system input current
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the sequence
preferred for the rectifier (A-B-C)
System Input Power Factor Phs A
The system input power factor for Phase A
System Input Power Factor Phs B
The system input power factor for Phase B
System Input Power Factor Phs C
The system input power factor for Phase C
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Output Apparent Power Phs A
System output apparent power on phase A
System Output Apparent Power Phs B
System output apparent power on phase B
System Output Apparent Power Phs C
System output apparent power on phase C
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Nominal Frequency
The nominal (or rated) system output frequency
System Output Nominal Voltage
The nominal (or rated) system output voltage
System Output Pct Power Phase A
The system output power on phase A as a percentage of the rated capacity
System Output Pct Power Phase B
The system output power on phase B as a percentage of the rated capacity
System Output Pct Power Phase C
The system output power on phase C as a percentage of the rated capacity
System Output Power Factor Phs A
The system output power factor of phase A
System Output Power Factor Phs B
The system output power factor of phase B
System Output Power Factor Phs C
The system output power factor of phase C
System Output Power Phase A
The system output power on phase A.
System Output Power Phase B
The system output power on phase B.
System Output Power Phase C
The system output power on phase C.
System Output Power
The sum total power of all system output phases
System Output RMS Current Phs A
The system output RMS current for Phase A
System Output RMS Current Phs B
The system output RMS current for Phase B
System Output RMS Current Phs C
The system output RMS current for Phase C
System Output Voltage RMS A-B
The system output RMS voltage between phases A and B
System Output Voltage RMS A-N
The system output RMS voltage between phases A and Neutral
249
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-56 Liebert eXM™—Controller with LCD HMI—Glossary (continued)
Data Label
Data Description
System Output Voltage RMS B-C
The system output RMS voltage between phases B and C
System Output Voltage RMS B-N
The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A
The system output RMS voltage between phases C and A
System Output Voltage RMS C-N
The system output RMS voltage between phases C and Neutral
System Shutdown - EPO
System shutdown due to Emergency Power Off (EPO)
System Status
The operating status for the system
Top Outlet Fan Fault
Top outlet fan fault - one or more top outlet fans have failed.
Total System Operating Time
The cumulative operation time of the unit
Transfer to Bypass - System Overload
The UPS System has transferred to bypass because the active power modules
cannot support the critical load.
UPS Application Mode
UPS application mode.
UPS battery1 status
UPS battery status
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
User Operation Invalid
User attempted an invalid operation.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
250
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-57 Liebert eXM™—Controller with Touchscreen HMI—Status and Coil
Status
Coil
Number
of Bits
Notes
Mains Input Neutral Lost
10001
—
1
Active on Alarm
System Input Phs Rotation Error
10002
—
1
Active on Alarm
System Input Power Problem
10003
—
1
Active on Alarm
Input Source Backfeed
10004
—
1
Active on Alarm
Bypass Not Available
10015
—
1
Active on Alarm
Bypass Static Switch Unavailable
10016
—
1
Active on Alarm
Bypass - Excess Auto Retransfers
10017
—
1
Active on Alarm
UPS Output on Bypass
10018
—
1
Active on Alarm
Output Load on Maint. Bypass
10019
—
1
Active on Alarm
Data Label
Input
Bypass
Bypass Input Voltage Fault
10020
—
1
Active on Alarm
Bypass Backfeed Detected
10021
—
1
Active on Alarm
Main Battery Disconnect Open
10032
—
1
Active on Alarm
Battery Circuit Breaker 4 Open
10033
—
1
Active on Alarm
Battery Circuit Breaker 3 Open
10034
—
1
Active on Alarm
Battery Circuit Breaker 2 Open
10035
—
1
Active on Alarm
Battery Circuit Breaker 1 Open
10036
—
1
Active on Alarm
Bypass
Battery Self Test
10037
—
1
Active on Alarm
Battery Charging Inhibited
10038
—
1
Active on Alarm
Battery Discharging
10039
—
1
Active on Alarm
Battery Manual Test In Progress
10040
—
1
Active on Alarm
Battery Auto Test In Progress
10041
—
1
Active on Alarm
Battery Test Passed
10042
—
1
Active on Alarm
Battery Test Failed
10043
—
1
Active on Alarm
Battery Over Temperature
10044
—
1
Active on Alarm
Battery Low
10045
—
1
Active on Alarm
Battery Ground Fault
10046
—
1
Active on Alarm
Battery Not Qualified
10047
—
1
Active on Alarm
Battery Terminals Reversed
10048
—
1
Active on Alarm
Battery Capacity Low
10049
—
1
Active on Alarm
Battery Converter Current Limit
10050
—
1
Active on Alarm
Battery Charge Equalization Timeout
10051
—
1
Active on Alarm
Battery Room Alarm
10052
—
1
Active on Alarm
Battery Breaker 1 Open Failure
10053
—
1
Active on Alarm
Battery Breaker 2 Open Failure
10054
—
1
Active on Alarm
Battery Breaker 3 Open Failure
10055
—
1
Active on Alarm
Battery Breaker 4 Open Failure
10056
—
1
Active on Alarm
Battery Equalize
10057
—
1
Active on Alarm
10068
—
1
Active on Alarm
Output Overload
10079
—
1
Active on Alarm
System Output Fault
10080
—
1
Active on Alarm
Inverter
Loss of Synchronization
Output
251
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-57 Liebert eXM™—Controller with Touchscreen HMI—Status and Coil (continued)
Data Label
Status
Coil
Number
of Bits
Notes
Power Modules 1
Power Module Input Current Abnormal
10091
—
1
Active on Alarm
Rectifier Failure
10092
—
1
Active on Alarm
Inverter Failure
10093
—
1
Active on Alarm
DC Bus Abnormal
10094
—
1
Active on Alarm
Load Sharing Fault
10095
—
1
Active on Alarm
Inverter Relay Fault
10096
—
1
Active on Alarm
Battery Charging Error
10097
—
1
Active on Alarm
Battery Converter Failure
10098
—
1
Active on Alarm
Power Module Balancer of DC Bus Failure
10099
—
1
Active on Alarm
Inverter Shutdown - Overload
10100
—
1
Active on Alarm
Power Module Fuse Failure
10101
—
1
Active on Alarm
Power Module Power Supply Failure
10102
—
1
Active on Alarm
Power Module Fan Fault
10103
—
1
Active on Alarm
Power Module Over Temperature
10104
—
1
Active on Alarm
Power Module Input Current Abnormal
10115
—
1
Active on Alarm
Rectifier Failure
10116
—
1
Active on Alarm
Inverter Failure
10117
—
1
Active on Alarm
DC Bus Abnormal
10118
—
1
Active on Alarm
Load Sharing Fault
10119
—
1
Active on Alarm
Power Modules 2
Inverter Relay Fault
10120
—
1
Active on Alarm
Battery Charging Error
10121
—
1
Active on Alarm
Battery Converter Failure
10122
—
1
Active on Alarm
Power Module Balancer of DC Bus Failure
10123
—
1
Active on Alarm
Inverter Shutdown - Overload
10124
—
1
Active on Alarm
Power Module Fuse Failure
10125
—
1
Active on Alarm
Power Module Power Supply Failure
10126
—
1
Active on Alarm
Power Module Fan Fault
10127
—
1
Active on Alarm
Power Module Over Temperature
10128
—
1
Active on Alarm
Power Modules 20
Power Module Input Current Abnormal
10547
—
1
Active on Alarm
Rectifier Failure
10548
—
1
Active on Alarm
Inverter Failure
10549
—
1
Active on Alarm
DC Bus Abnormal
10550
—
1
Active on Alarm
Load Sharing Fault
10551
—
1
Active on Alarm
Inverter Relay Fault
10552
—
1
Active on Alarm
Battery Charging Error
10553
—
1
Active on Alarm
Battery Converter Failure
10554
—
1
Active on Alarm
Power Module Balancer of DC Bus Failure
10555
—
1
Active on Alarm
Inverter Shutdown - Overload
10556
—
1
Active on Alarm
Power Module Fuse Failure
10557
—
1
Active on Alarm
Power Module Power Supply Failure
10558
—
1
Active on Alarm
Power Module Fan Fault
10559
—
1
Active on Alarm
Power Module Over Temperature
10560
—
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
252
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-57 Liebert eXM™—Controller with Touchscreen HMI—Status and Coil (continued)
Status
Coil
Number
of Bits
Notes
Loss of Redundancy
10571
—
1
Active on Alarm
Parallel Cable Failure
10572
—
1
Active on Alarm
Data Label
System Status
LBS Cable Failure
10573
—
1
Active on Alarm
Transfer to Bypass - System Overload
10574
—
1
Active on Alarm
Excess ECO Suspends
10575
—
1
Active on Alarm
User Operation Invalid
10576
—
1
Active on Alarm
Load Impact Transfer
10577
—
1
Active on Alarm
Internal Communications Failure
10578
—
1
Active on Alarm
MMS Overload
10579
—
1
Active on Alarm
Parallel Comm Warning
10580
—
1
Active on Alarm
Equipment Over Temperature
10581
—
1
Active on Alarm
LBS Inhibited
10582
—
1
Active on Alarm
On Generator
10583
—
1
Active on Alarm
LBS Active
10584
—
1
Active on Alarm
System Shutdown - EPO
10585
—
1
Active on Alarm
Top Outlet Fan Fault
10586
—
1
Active on Alarm
253
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Input RMS A-B
30385
—
1
System Input RMS B-C
30386
—
1
—
Units : VAC
Uint16
System Input RMS C-A
30387
—
1
—
Units : VAC
Uint16
System Input RMS Current Phase A
30388
—
1
—
Units : A AC
Uint16
System Input RMS Current Phase B
30389
—
1
—
Units : A AC
Uint16
System Input RMS Current Phase C
30390
—
1
—
Units : A AC
Uint16
System Input Frequency
30391
—
1
10
Units : Hz
Uint16
System Input RMS A-N
30392
—
1
—
Units : VAC
Uint16
System Input RMS B-N
30393
—
1
—
Units : VAC
Uint16
System Input RMS C-N
30394
—
1
—
Units : VAC
Uint16
System Input Power Factor Phs A
30395
—
1
100
Uint16
System Input Power Factor Phs B
30396
—
1
100
Uint16
System Input Power Factor Phs C
30397
—
1
100
Uint16
Input
Units : VAC
Uint16
System Input Nominal Voltage
30398
—
1
—
Units : VAC
Uint16
System Input Nominal Frequency
30399
—
1
10
Units : Hz
Uint16
System Input Nominal Current
30400
—
1
—
Units : A AC
Uint16
System Input Brown Out Count
30401
—
1
—
Uint16
System Input Black Out Count
30402
—
1
—
Uint16
30403
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Input Voltage RMS A-N
30414
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS B-N
30415
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS C-N
30416
—
1
—
Units : VAC
Uint16
Bypass Input Frequency
30417
—
1
10
Units : Hz
Uint16
Bypass Input Voltage RMS A-B
30418
—
1
—
Units : VAC
Uint16
Input Breaker
Bypass
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
254
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Bypass Input Voltage RMS B-C
30419
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS C-A
30420
—
1
—
Units : VAC
Uint16
Bypass Nominal Voltage
30421
—
1
—
Units : VAC
Uint16
External Bypass Breaker
30422
—
1
—
0 = Open
1 = Close
2 = Not Installed
Battery Time Remaining
30433
—
1
—
Units : min
Uint16
DC Bus Current
30434
—
1
—
Units : A DC
Int16
Time Until Next Auto Battery Test
30435
—
2
—
Units : min
Uint32
Battery Percentage Charge
30437
—
1
—
Units : %
Uint16
Number of Discharge Cycles
30438
—
1
—
Uint16
Accumulated Discharge Time
30439
—
1
—
Units : hr
Uint16
Low Battery Warning Time
30440
—
1
—
Units : min
Uint16
—
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
Battery
UPS Battery Status
30441
—
1
Battery charge status.
30442
—
1
—
0 = fully charged
1 = charging
2 = discharging
3 = not charging
(charger off)
Automatic Battery Test
30443
—
1
—
0 = disabled
1 = enabled
Battery Self Test Cycle Time
30444
—
1
—
Units : day
Uint16
DC Bus Voltage
30445
—
1
—
Units : VDC
Uint16
Battery Temperature
30446
—
1
—
Units : deg C
Int16
Battery Temperature
30447
—
1
—
Units : deg F
Int16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
255
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Battery Temperature for Cabinet
30458
—
1
—
Units : deg
C Int16
Battery Temperature for Cabinet
30459
—
1
—
Units : deg
F Int16
Battery Volts for Cabinet
30460
—
1
—
Units : VDC
Uint16
Battery Temperature for Cabinet
30471
—
1
—
Units : deg C
Int16
Battery Temperature for Cabinet
30472
—
1
—
Units : deg F
Int16
Battery Volts for Cabinet
30473
—
1
—
Units : VDC
Uint16
Battery Temperature for Cabinet
30549
—
1
—
Units : deg C
Int16
Battery Temperature for Cabinet
30550
—
1
—
Units : deg F
Int16
Battery Volts for Cabinet
30551
—
1
—
Units : VDC
Uint16
Battery Cabinets 1
Battery Cabinets 2
Battery Cabinets 8
Inverter
Output Breaker
30562
—
1
—
0 = Open
1 = Close
2 = Not Installed
Inverter On/Off State
30563
—
1
—
0 = off
1 = on
System Output Voltage RMS A-N
30574
—
1
—
Units : VAC
Uint16
System Output Voltage RMS B-N
30575
—
1
—
Units : VAC
Uint16
System Output Voltage RMS C-N
30576
—
1
—
Units : VAC
Uint16
System Output RMS Current Phs A
30577
—
1
—
Units : A AC
Uint16
System Output RMS Current Phs B
30578
—
1
—
Units : A AC
Uint16
System Output RMS Current Phs C
30579
—
1
—
Units : A AC
Uint16
System Output Frequency
30580
—
1
10
Units : Hz
Uint16
System Output Voltage RMS A-B
30581
—
1
—
Units : VAC
Uint16
System Output Voltage RMS B-C
30582
—
1
—
Units : VAC
Uint16
Output
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
256
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Output Voltage RMS C-A
30583
—
1
—
Units : VAC
Uint16
System Output Power Factor Phs A
30584
—
1
100
Uint16
System Output Power Factor Phs B
30585
—
1
100
Uint16
System Output Power Factor Phs C
30586
—
1
100
Uint16
System Output Pct Power Phase A
30587
—
1
—
Units : %
Uint16
System Output Pct Power Phase B
30588
—
1
—
Units : %
Uint16
System Output Pct Power Phase C
30589
—
1
—
Units : %
Uint16
MMS Output Apparent Power
30590
—
1
—
Units : kVA
Uint16
MMS Output Power
30591
—
1
—
Units : kW
Uint16
Output Current Crest Factor Phs A
30592
—
1
10
Uint16
Output Current Crest Factor Phs B
30593
—
1
10
Uint16
Output Current Crest Factor Phs C
30594
—
1
10
Uint16
System Output Power Phase A
30595
—
1
—
Units : kW
Uint16
System Output Power Phase B
30596
—
1
—
Units : kW
Uint16
System Output Power Phase C
30597
—
1
—
Units : kW
Uint16
System Output Apparent Power Phs A
30598
—
1
—
Units : kVA
Uint16
System Output Apparent Power Phs B
30599
—
1
—
Units : kVA
Uint16
System Output Apparent Power Phs C
30600
—
1
—
Units : kVA
Uint16
System Output Power
30601
—
1
—
Units : kW
Uint16
System Output Apparent Power
30602
—
1
—
Units : kVA
Uint16
System Output Pct Pwr (VA) Phs A
30603
—
1
—
Units : %
Uint16
System Output Pct Pwr (VA) Phs B
30604
—
1
—
Units : %
Uint16
System Output Pct Pwr (VA) Phs C
30605
—
1
—
Units : %
Uint16
System Output Nominal Voltage
30606
—
1
—
Units : VAC
Uint16
System Output Nominal Frequency
30607
—
1
10
Units : Hz
Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
257
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
30618
—
1
—
0 = Sleeping
1 = Not Sleeping
Power Modules 1
Power Module Sleep Status
Module Operating Status
30619
—
1
—
0 = Normal
1 = Warning
2 = Alarm 4 =
Fault
Inverter Status
30620
—
1
—
0 = Inverter
Inactive
1 = Inverter Active
30631
—
1
—
0 = Sleeping
1 = Not Sleeping
Power Modules 2
Power Module Sleep Status
Module Operating Status
30632
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status
30633
—
1
—
0 = Inverter
Inactive
1 = Inverter Active
30865
—
1
—
0 = Sleeping
1 = Not Sleeping
Power Modules 20
Power Module Sleep Status
Module Operating Status
30866
—
1
—
0 = Normal
1 = Warning
2 = Alarm
4 = Fault
Inverter Status
30867
—
1
—
0 = Inverter
Inactive
1 = Inverter Active
Power Module Bypass Input Frequency
30878
—
1
10
Units : Hz
Uint16
Power Module Bypass Input Voltage RMS A-N
30879
—
1
—
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS B-N
30880
—
1
—
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS C-N
30881
—
1
—
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS A-B
30882
—
1
—
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS B-C
30883
—
1
—
Units : VAC
Uint16
Power Module Bypass Input Voltage RMS C-A
30884
—
1
—
Units : VAC
Uint16
Bypass Control Module
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
258
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Set To Operate With
30895
—
1
—
0 = No
Redundancy
1 = Redundancy
Number Of Active Power Modules
30896
—
1
—
Uint16
Number of Installed Power Modules
30897
—
1
—
Uint16
Inlet Air Temperature
30898
—
1
—
Units : deg C
Uint16
Inlet Air Temperature
30899
—
1
—
Units : deg F
Uint16
Average system efficiency
30900
—
1
10
Units : %
Uint16
Maintenance Bypass Breaker
30901
—
1
—
0 = Open
1 = Close
2 = Not Installed
ECO Mode Operation State
30902
—
1
—
0 = disabled
1 = enabled
UPS Application Mode
30903
—
1
—
0 = UPS Mode
1 = Frequency
converter mode
System Status
MMS UPS Output Source
30904
—
1
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Intelligent Parallel Operation State
30905
—
1
—
0 = disabled
1 = enabled
Total System Operating Time
30916
—
2
—
Units : hr
Uint32
System Capacity
30918
—
1
—
Units : kVA
Uint16
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Configuration
UPS Output Source
30919
—
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
259
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
System Status
30920
—
1
System Date and Time
39998
49998
2
Scale
Notes/Units
—
1 = Normal
Operation
2 = StartUp
8 = Normal with
Warning
16 = Normal with
Alarm
32 = Abnormal
Operation
Units : Secs since
Epoch(UTC)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
260
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary
Data Label
Data Description
Accumulated Discharge Time
Total accumulated discharge time for the Battery Module since it was made.
Automatic Battery Test
Enable/disable the automatic battery test schedule.
Average system efficiency
Average system efficiency
Battery Auto Test In Progress
Automatic battery test is in progress
Battery Breaker 1 Open Failure
Battery circuit breaker 1 failed to open
Battery Breaker 2 Open Failure
Battery circuit breaker 2 failed to open
Battery Breaker 3 Open Failure
Battery circuit breaker 3 failed to open
Battery Breaker 4 Open Failure
Battery circuit breaker 4 failed to open
Battery Capacity Low
Battery capacity is low
Battery Charge Equalization Timeout
The battery equalizing is time out.
Battery charge status.
Battery charge status.
Battery Charging Error
The battery is not charging properly
Battery Charging Inhibited
Battery charging is inhibited due to an external inhibit signal
Battery Circuit Breaker 1 Open
Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open
Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open
Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open
Battery circuit breaker 4 is open
Battery Converter Current Limit
The battery converter has reached is maximum current limit.
Battery Converter Failure
Battery converter failure. This is a summary event caused by one or more power
sub-modules in a UPS module.
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage level.
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Low
The calculated battery time remaining has reached the low battery threshold
Battery Manual Test In Progress
Manual battery test is in progress
Battery Not Qualified
The UPS battery voltage is not qualified. This event will be detected even in the
absence of battery disconnect or when it is open.
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Percentage Charge
The percentage of battery charge
Battery Room Alarm
The ambient temperature of the battery room is abnormal.
Battery Self Test Cycle Time
The time between automatic battery self test cycles.
Battery Self Test
Battery self test is in progress
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Temperature
The highest battery temperature among all Battery Cabinets
Battery Terminals Reversed
The measured battery voltage is a negative value due to reverse battery terminal
connections.
Battery Test Failed
Battery test failed
Battery Test Passed
Battery test passed
Battery Time Remaining
The calculated available time on battery
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a battery cabinet
Bypass - Excess Auto Retransfers
The number of auto retransfers, from bypass to inverter, has exceeded the
maximum for a specified time interval
Bypass Backfeed Detected
The system detected a voltage on the bypass when none was expected
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage Fault
The system has detected the bypass voltage is unqualified.
Bypass Input Voltage RMS A-B
The bypass input RMS voltage between phases A and B
Bypass Input Voltage RMS A-N
The bypass input RMS voltage between phase A and Neutral
261
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary (continued)
Data Label
Bypass Input Voltage RMS B-C
Data Description
The bypass input RMS voltage between phases B and C
Bypass Input Voltage RMS B-N
The bypass input RMS voltage between phase B and Neutral
Bypass Input Voltage RMS C-A
The bypass input RMS voltage between phases C and A
Bypass Input Voltage RMS C-N
The bypass input RMS voltage between phase C and Neutral
Bypass Nominal Voltage
Bypass nominal (or rated) voltage
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Static Switch Unavailable
The static bypass is unavailable to support the critical load.
DC Bus Abnormal
The system has detected an abnormal DC Bus Voltage.
DC Bus Current
The current at the battery input terminals. In charging mode, the current will be a
positive value. In discharging mode, the current will be a negative value
DC Bus Voltage
The voltage between the positive and negative terminals of the DC bus at the
battery input
ECO Mode Operation State
This setting is used to enable or disable ECO Mode.
Equipment Over Temperature
Equipment over temperature summary event
Excess ECO Suspends
Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto
Suspensions setting.
External Bypass Breaker
The status of the external bypass breaker.
Inlet Air Temperature
The temperature of the inlet air
Input Breaker
Input breaker
Input Source Backfeed
The battery is backfeeding the input source.
Intelligent Parallel Operation State
This setting is used to enable or disable Intelligent Paralleling.
Internal Communications Failure
The control has detected a communication failure of a component on the internal
communication bus
Inverter Failure
Inverter failure - inverter output is off
Inverter On/Off State
inverter on/off state
Inverter Relay Fault
The inverter relay has malfunctioned.
Inverter Shutdown - Overload
The inverter has shutdown due to a sustained overload
Inverter Status
Status of the inverter output. Active means the inverter is online with regulated
output voltage and ready to power the load. Inactive means the inverter is offline
and not ready to power the load.
LBS Active
The Load Bus Sync option is active
LBS Cable Failure
Load Bus Sync communications is abnormal. A problem with the LBS cable may
exist.
LBS Inhibited
The system has detected that conditions to perform Load Bus Sync are not satisfied
Load Impact Transfer
On bypass as result of load impact.
Load Sharing Fault
Difference between any phase inverter current of unit and the relevant average
output current of parallel system is more than a specific percent of nominal current.
Loss of Redundancy
The system has an insufficient number of power modules to provide redundancy.
Loss of Synchronization
The inverter and bypass are no longer synchronized.
Low Battery Warning Time
When battery time remaining falls to, or below, this value the low battery alarm is
activated.
Main Battery Disconnect Open
Main battery disconnect is open
Mains Input Neutral Lost
Loss of neutral in the input source is detected.
Maintenance Bypass Breaker
Maintenance bypass breaker
MMS Output Apparent Power
The sum total apparent power of all system output modules
MMS Output Power
The sum total power of all system output modules
MMS Overload
Multi-module system overload
MMS UPS Output Source
Multi-module UPS output source
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
262
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary (continued)
Data Label
Module Operating Status
Data Description
The operating status for this Power Module.
Number Of Active Power Modules
The total number of active power modules.
Number of Discharge Cycles
The total number of battery discharge cycles for the Battery Module since it was
made.
Number of Installed Power Modules
The total number of Power Modules installed.
On Generator
A generator is supplying the power to the system
Output Breaker
Output breaker
Output Current Crest Factor Phs A
Output current crest factor of Phase A.
Output Current Crest Factor Phs B
Output current crest factor of Phase B.
Output Current Crest Factor Phs C
Output current crest factor of Phase C.
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Output Overload
An overload exists on the output.
Parallel Cable Failure
The UPS parallel system communications is abnormal. A problem with the parallel
cable may exist.
Parallel Comm Warning
Parallel communication bus warning
Power Module Balancer of DC Bus
Failure
Balancer of DC Bus in the power module has failed
Power Module Bypass Input Frequency
The bypass input frequency detected by power module
Power Module Bypass Input Voltage
RMS A-B
The bypass input RMS voltage between phases A and B detected by power module
Power Module Bypass Input Voltage
RMS A-N
The bypass input RMS voltage between phase A and Neutral detected by power
module
Power Module Bypass Input Voltage
RMS B-C
The bypass input RMS voltage between phases B and C detected by power module
Power Module Bypass Input Voltage
RMS B-N
The bypass input RMS voltage between phase B and Neutral detected by power
module
Power Module Bypass Input Voltage
RMS C-A
The bypass input RMS voltage between phases C and A detected by power module
Power Module Bypass Input Voltage
RMS C-N
The bypass input RMS voltage between phase C and Neutral detected by power
module
Power Module Fan Fault
The Power Module has detected a fan fault.
Power Module Fuse Failure
A summary event indicating one or more fuse failures in the power module
Power Module Input Current Abnormal
Input current of the power module is abnormal
Power Module Over Temperature
The Power Module has detected an over temperature condition.
Power Module Power Supply Failure
Power module power supply failure
Power Module Sleep Status
Sleep status of the Power module
Rectifier Failure
Rectifier failure - rectifier is off
System Capacity
System capacity supported by the installed power modules.
System Date and Time
The system date and time
System Input Black Out Count
The number of occurrences, since the last reset, where the input was not qualified
to provide power to the system
System Input Brown Out Count
The number of occurrences, since the last reset, where the system input voltage
has fallen below a pre-determined threshold for a specified amount of time
System Input Frequency
The system input frequency
System Input Nominal Current
The nominal (or rated) system input current
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the sequence
preferred for the rectifier (A-B-C)
263
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary (continued)
Data Label
System Input Power Factor Phs A
Data Description
The system input power factor for Phase A
System Input Power Factor Phs B
The system input power factor for Phase B
System Input Power Factor Phs C
The system input power factor for Phase C
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Output Apparent Power Phs A
System output apparent power on phase A
System Output Apparent Power Phs B
System output apparent power on phase B
System Output Apparent Power Phs C
System output apparent power on phase C
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Nominal Frequency
The nominal (or rated) system output frequency
System Output Nominal Voltage
The nominal (or rated) system output voltage
System Output Pct Power Phase A
The system output power on phase A as a percentage of the rated capacity
System Output Pct Power Phase B
The system output power on phase B as a percentage of the rated capacity
System Output Pct Power Phase C
The system output power on phase C as a percentage of the rated capacity
System Output Pct Pwr (VA) Phs A
The system output apparent power on phase A as a percentage of the rated
capacity
System Output Pct Pwr (VA) Phs B
The system output apparent power on phase B as a percentage of the rated
capacity
System Output Pct Pwr (VA) Phs C
The system output apparent power on phase C as a percentage of the rated
capacity
System Output Power Factor Phs A
The system output power factor of phase A
System Output Power Factor Phs B
The system output power factor of phase B
System Output Power Factor Phs C
The system output power factor of phase C
System Output Power Phase A
The system output power on phase A.
System Output Power Phase B
The system output power on phase B.
System Output Power Phase C
The system output power on phase C.
System Output Power
The sum total power of all system output phases
System Output RMS Current Phs A
The system output RMS current for Phase A
System Output RMS Current Phs B
The system output RMS current for Phase B
System Output RMS Current Phs C
The system output RMS current for Phase C
System Output Voltage RMS A-B
The system output RMS voltage between phases A and B
System Output Voltage RMS A-N
The system output RMS voltage between phases A and Neutral
System Output Voltage RMS B-C
The system output RMS voltage between phases B and C
System Output Voltage RMS B-N
The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A
The system output RMS voltage between phases C and A
System Output Voltage RMS C-N
The system output RMS voltage between phases C and Neutral
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
264
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary (continued)
Data Label
Data Description
System Set To Operate With
If this point reports 'Redundancy' then the system is configured for redundancy and
the 'Loss of Redundancy' alarm is enabled.
System Shutdown - EPO
System shutdown due to Emergency Power Off (EPO)
System Status
The operating status for the system
Time Until Next Auto Battery Test
The time until the next automatic battery test is started.
Top Outlet Fan Fault
Top outlet fan fault - one or more top outlet fans have failed.
Total System Operating Time
The cumulative operation time of the unit
Transfer to Bypass - System Overload
The UPS System has transferred to bypass because the active power modules
cannot support the critical load.
UPS Application Mode
UPS application mode.
UPS Battery Status
UPS battery status
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
User Operation Invalid
User attempted an invalid operation.
265
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-60 Liebert GXT2™ and Liebert GXT3™—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Audible Alarm Enabled
10002
2
1
—
—
Automatic Battery Test Enabled
10003
3
1
—
—
DC-to-DC Converter On
10042
—
1
—
—
Battery Charge Compensation
10046
—
1
—
—
Inverter Ready
10047
—
1
—
—
Power Factor Correction State
10050
—
1
—
—
Load Circuit 1 State
10057
—
1
—
—
Load Circuit 2 State
10058
—
1
—
—
Load Circuit 3 State
10059
—
1
—
—
Load Circuit 4 State
10060
—
1
—
—
Load Circuit 5 State
10061
—
1
—
—
Load Circuit 6 State
10062
—
1
—
—
Load Circuit 7 State
10063
—
1
—
—
Load Circuit 8 State
10064
—
1
—
—
Load Circuit 9 State
10065
—
1
—
—
Load Circuit 10 State
10066
—
1
—
—
Load Circuit 11 State
10067
—
1
—
—
Load Circuit 12 State
10068
—
1
—
—
Load Circuit 13 State
10069
—
1
—
—
Load Circuit 14 State
10070
—
1
—
—
Load Circuit 15 State
10071
—
1
—
—
Load Circuit 16 State
10072
—
1
—
—
Load On Inverter
10073
—
1
—
—
Bypass Active
10074
—
1
—
—
Replace Battery
10081
—
1
—
—
Battery Under Test
10082
—
1
—
—
Shutdown Reason - Over Temperature
10086
—
1
—
—
Shutdown Reason - Overload
10087
—
1
—
—
Shutdown Reason - Link Over Voltage
10088
—
1
—
—
Shutdown Reason - Output Short
10089
—
1
—
—
Shutdown Reason - Line Neutral Swap
10090
—
1
—
—
Shutdown Reason - Low Battery
10092
—
1
—
—
Shutdown Reason - Remote Shutdown
10093
—
1
—
—
Shutdown Reason - Input Under Voltage
10094
—
1
—
—
Shutdown Reason - PFC Startup
10095
—
1
—
—
Shutdown Reason - Hardware
10096
—
1
—
—
Load on Battery
10128
—
1
—
—
Output Off Pending
10151
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
Over Temperature Warning
10171
—
1
—
—
Battery Over Temperature CB Trip
10172
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Input Over Voltage
10187
—
1
—
—
Input Under Voltage
10188
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
266
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-60 Liebert GXT2™ and Liebert GXT3™—Status and Coil (continued)
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Bad Input Frequency
10190
—
1
—
—
Bypass Input Voltage/Frequency Fault
10202
—
1
—
—
Output Under Voltage
10218
—
1
—
—
Output Over Voltage
10219
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
267
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-61 Liebert GXT2™ and Liebert GXT3™—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Audible Alarm Enabled
10002
2
1
—
—
Automatic Battery Test Enabled
10003
3
1
—
—
DC-to-DC Converter On
10042
—
1
—
—
Battery Charge Compensation
10046
—
1
—
—
Inverter Ready
10047
—
1
—
—
Power Factor Correction State
10050
—
1
—
—
Load Circuit 1 State
10057
—
1
—
—
Load Circuit 2 State
10058
—
1
—
—
Load Circuit 3 State
10059
—
1
—
—
Load Circuit 4 State
10060
—
1
—
—
Load Circuit 5 State
10061
—
1
—
—
Load Circuit 6 State
10062
—
1
—
—
Load Circuit 7 State
10063
—
1
—
—
Load Circuit 8 State
10064
—
1
—
—
Load Circuit 9 State
10065
—
1
—
—
Load Circuit 10 State
10066
—
1
—
—
Load Circuit 11 State
10067
—
1
—
—
Load Circuit 12 State
10068
—
1
—
—
Load Circuit 13 State
10069
—
1
—
—
Load Circuit 14 State
10070
—
1
—
—
Load Circuit 15 State
10071
—
1
—
—
Load Circuit 16 State
10072
—
1
—
—
Load On Inverter
10073
—
1
—
—
Bypass Active
10074
—
1
—
—
Replace Battery
10081
—
1
—
—
Battery Under Test
10082
—
1
—
—
Shutdown Reason - Over Temperature
10086
—
1
—
—
Shutdown Reason - Overload
10087
—
1
—
—
Shutdown Reason - Link Over Voltage
10088
—
1
—
—
Shutdown Reason - Output Short
10089
—
1
—
—
Shutdown Reason - Line Neutral Swap
10090
—
1
—
—
Shutdown Reason - Low Battery
10092
—
1
—
—
Shutdown Reason - Remote Shutdown
10093
—
1
—
—
Shutdown Reason - Input Under Voltage
10094
—
1
—
—
Shutdown Reason - PFC Startup
10095
—
1
—
—
Shutdown Reason - Hardware
10096
—
1
—
—
Load on Battery
10128
—
1
—
—
Output Off Pending
10151
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
Over Temperature Warning
10171
—
1
—
—
Battery Over Temperature CB Trip
10172
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Input Over Voltage
10187
—
1
—
—
Input Under Voltage
10188
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
268
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-61 Liebert GXT2™ and Liebert GXT3™—Status and Coil (continued)
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Bad Input Frequency
10190
—
1
—
—
Bypass Input Voltage/Frequency Fault
10202
—
1
—
—
Output Under Voltage
10218
—
1
—
—
Output Over Voltage
10219
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
269
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-62 Liebert GXT2™ and Liebert GXT3™—Input and Holding
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Number of SubModules
30009
40009
1
—
—
—
There are 16 possible Load Circuits.
Each bit represents 1 Load Circuit.
Load Circuit 1 is bit 0, Load Circuit 2
is bit 1 and so on. If the bit is 1, then
the Load Circuit is supported.
Data Description
Load Circuit Present
30013
40013
1
Battery Cabinet Type
30018
40018
2
—
—
Battery Cabinet Number
30019
40019
1
—
—
Battery AmpHour
30020
40020
1
—
AH
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch Voltage
30029
40029
1
—
V
Nominal Input Current
30030
40030
1
—
A
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
Nominal Battery Voltage
30034
40034
1
—
V
Auto Restart Delay
30051
40051
1
—
Seconds
Device Low Battery Time
30053
40053
1
—
Minutes
Load (Apparent Power)
30102
—
2
—
VA
Load (Real Power)
30104
—
2
—
W
Load / Capacity
30106
—
1
—
%
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Hz
—
1
—
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Charge Status
30112
Battery Voltage
30113
—
1
—
V
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Ambient Temperature
30119
—
1
—
deg C
Battery Test Result
30130
—
1
—
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1
30153
—
1
—
V
Bypass Voltage L1
30159
—
1
—
V
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
270
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-62 Liebert GXT2™ and Liebert GXT3™—Input and Holding (continued)
Data Description
Input Maximum Voltage L1
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
30180
—
1
—
V
Input Minimum Voltage L1
30181
—
1
—
V
Output Maximum Voltage L1
30182
—
1
—
V
Output Minimum Voltage L1
30183
—
1
—
V
Black Out Count
30301
—
1
—
—
Brown Out Count
30302
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
271
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-63 Liebert GXT3™ and Liebert GXT4™—Status and Coil
Data Label
Status
Coil
Number of Bits
Notes
Input
Input Undervoltage
10001
1
Active on Alarm
Input Overvoltage
10002
1
Active on Alarm
10013
1
Active on Alarm
Bypass
Bypass Not Available
Battery
Battery Self Test
10024
1
Active on Alarm
Battery Low
10025
1
Active on Alarm
Battery Under Voltage
10026
1
Active on Alarm
Battery Over Voltage
10027
1
Active on Alarm
Battery Test Failed
10028
1
Active on Alarm
Replace Battery
10029
1
Active on Alarm
10040
1
Active on Alarm
Output
Output Overload
Output Undervoltage
10041
1
Active on Alarm
Output Overvoltage
10042
1
Active on Alarm
System Output Off
10043
1
Active on Alarm
UPS Output on Bypass
10054
1
Active on Alarm
Battery Discharging
10055
1
Active on Alarm
System
System Input Power Problem
10056
1
Active on Alarm
Equipment Over Temperature
10057
1
Active on Alarm
Input Frequency Deviation
10058
1
Active on Alarm
Shutdown Pending
10059
1
Active on Alarm
Unspecified General Event
10060
1
Active on Alarm
Parallel Comm Warning
10061
1
Active on Alarm
Loss of Redundancy
10062
1
Active on Alarm
Charger Failure
10063
1
Active on Alarm
Rectifier Failure
10064
1
Active on Alarm
Inverter Failure
10065
1
Active on Alarm
Maintenance Bypass Breaker Closed
10066
1
Active on Alarm
System Fan Failure
10067
1
Active on Alarm
Emergency Power Off - Latched
10068
1
Active on Alarm
Input Wiring Fault
10069
1
Active on Alarm
DC to DC Converter Fault
10070
1
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
272
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Protocol
Server Class
1 = UPS
2 = AIR
3 = PMP
4 = PDU
5 = MONITOR
30385
1
System Input RMS L1-N
30396
1
10
Units : VAC
Uint16
System Input RMS L2-N
30397
1
10
Units : VAC
Uint16
System Input RMS L1-L2
30398
1
10
Units : VAC
Uint16
System Input RMS Current L1
30399
1
10
Units : A AC
Uint16
System Input RMS Current L2
30400
1
10
Units : A AC
Uint16
System Input Frequency
30401
1
10
Units : Hz
Uint16
System Input Max Voltage L1-N
30402
1
10
Units : VAC
Uint16
System Input Min Voltage L1-N
30403
1
10
Units : VAC
Uint16
System Input Max Voltage L2-N
30404
1
10
Units : VAC
Uint16
System Input Min Voltage L2-N
30405
1
10
Units : VAC
Uint16
System Input Nominal Voltage
30406
1
Units : VAC
Uint16
System Input Nominal Current
30407
1
Units : A AC
Uint16
System Input Nominal Frequency
30408
1
Units : Hz
Uint16
Bypass Input Voltage RMS L1-N
30419
1
10
Units : VAC
Uint16
Bypass Input Voltage RMS L1-L2
30420
1
10
Units : VAC
Uint16
Bypass Input Voltage RMS L2-N
30421
1
10
Units : VAC
Uint16
Bypass Input RMS Current
30422
1
10
Units : A AC
Uint16
Bypass Input RMS Current Line 2
30423
1
10
Units : A AC
Uint16
Bypass Input Frequency
30424
1
10
Units : Hz
Uint16
Input
Bypass
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
273
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding (continued)
Data Label
Bypass Nominal Voltage
Input
Holding
30425
# of Reg
Scale
Notes/Units
1
Units : VAC
Uint16
Battery
UPS Battery Status
30436
1
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
Battery Time Remaining
30437
1
Units : min
Uint16
Battery Percentage Charge
30438
1
Units : %
Uint16
Battery Charge Status
30439
1
0 = fully charged
1 = charging
2 = discharging
3 = not charging (charger off)
DC Bus Voltage
30440
1
Units : VDC
Uint16
DC Bus Nominal Voltage
30441
1
Units : VDC
Uint16
Battery Cabinet Type
30442
1
0 = Internal
1 = External
2 = LRT
Battery Rating
30443
1
Units : AH
Uint16
Low Battery Warning Time
30444
1
Units : min
Uint16
Number of EBC Installed
30445
40444
1
Uint16
Battery Charge Compensating
30446
1
0 = false
1 = true
Battery Charger State
30447
1
0 = off
1 = on
Nominal Battery Capacity
30448
1
Units : min
Uint16
Battery Discharge Time
30449
1
Units : min
Uint16
Battery Float Voltage
30450
1
Units : VDC
Uint16
Battery Test Result
30451
1
0 = Unknown
1 = Passed
2 = Failed
3 = In Progress
4 = System Failure
5 = Inhibited
Automatic Battery Test
30452
1
0 = disabled
1 = enabled
1
1 = Start Test
Manual Battery Test
40453
Output
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
274
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
System Output Voltage RMS L1-N
30464
1
10
Units : VAC
Uint16
System Output Voltage RMS L1-L2
30465
1
10
Units : VAC
Uint16
System Output RMS Current L1
30466
1
10
Units : A AC
Uint16
System Output Voltage RMS L2-N
30467
1
10
Units : VAC
Uint16
System Output RMS Current L2
30468
1
10
Units : A AC
Uint16
System Output Frequency
30469
1
10
Units : Hz
Uint16
System Output Max Voltage L1-N
30470
1
10
Units : VAC
Uint16
System Output Min Voltage L1-N
30471
1
10
Units : VAC
Uint16
System Output Max Voltage L2-N
30472
1
10
Units : VAC
Uint16
System Output Min Voltage L2-N
30473
1
10
Units : VAC
Uint16
System Output Power
30474
1
Units : W
Uint16
System Output Power L1
30475
1
Units : W
Uint16
System Output Power L2
30476
1
Units : W
Uint16
System Output Pct Power
30477
1
Units : %
Uint16
System Output Pct Power L1
30478
1
Units : %
Uint16
System Output Pct Power L2
30479
1
Units : %
Uint16
System Output Apparent Power
30480
1
Units : VA
Uint16
System Output Apparent Power L1
30481
1
Units : VA
Uint16
System Output Apparent Power L2
30482
1
Units : VA
Uint16
System Output Nominal Voltage
30483
1
Units : VAC Uint16
Output Apparent Power Rating
30484
1
Units : VA
Uint16
System Output Nominal Frequency
30485
1
Units : Hz
Uint16
Output On Delay
30486
40486
1
Units : sec
Uint16
Reboot With Delay
30487
40487
1
Units : sec
Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
275
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding (continued)
Data Label
Shutdown After Delay
Input
Holding
# of Reg
Scale
Notes/Units
30488
40488
1
Units : sec
Uint16
UPS Output Source
30489
1
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Power Factor Correction
30490
1
0 = off
1 = on
Nominal Power Factor
30491
1
Outlet Group Identifier
30502
1
Uint16
Outlet Group Power Control
30503
1
0 = Off
1 = On
2 = Cycle Power
1
Uint16
1
0 = Off
1 = On
2 = Cycle Power
1
0 = off
1 = on
1
0 = disabled
1 = enabled
1
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
100
Int16
Outlet Group 1
40503
Outlet Group 2
Outlet Group Identifier
30514
Outlet Group Power Control
30515
40515
ECO Mode
ECO Mode Status
30526
ECO Mode Operation State
30527
40527
System
System Status
30538
System Input Black Out Count
30539
1
Uint16
System Input Brown Out Count
30540
1
Uint16
Auto Restart
30541
40541
1
0 = disabled
1 = enabled
Auto Restart Delay
30542
40542
1
Units : sec
Uint16
Inverter On/Off State
30543
1
0 = off
1 = on
Inlet Air Temperature
30544
1
Units : deg C
Int16
Inlet Air Temperature
30545
1
Units : deg F
Int16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
276
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Shutdown Reason
30546
1
0 = None
1 = Over Temperature
2 = Overload
3 = DC Bus Overload
4 = Output Short
5 = Line Swap
6 = Low Battery
7 = Remote Command
8 = Input Under Voltage
9 = Power Factor Correction Fail
10 = External Signal Command
DC Converter Status
30547
1
0 = off
1 = on
UPS Topology
30548
1
0 = unknown
1 = Offline
2 = Line Interactive
3 = Online
Bypass/Inverter Input Config
30549
1
1 = Single/Combined Source
2 = Dual/Separate Sources
Audible Alarm Control
30550
40550
1
0 = off
1 = on
40551
1
1 = Issue Command
Abort Command
Reset Power Statistics
40552
1
1 = Reset
Silence Audible Alarm
40553
1
1 = Silence Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
277
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-65 Liebert GXT3™ and Liebert GXT4™—Glossary
Data Label
Data Description
Abort Command
Attempt to abort a previously issued command to the device that is still
pending
Audible Alarm Control
Audible Alarm Control
Auto Restart Delay
If power is lost, the control will delay this amount of time after power is
restored before restarting the unit.
Auto Restart
When 'enabled', the UPS will automatically restart the load when utility
power is restored after a battery discharge.
Automatic Battery Test
Enable/disable the automatic battery test schedule.
Battery Cabinet Type
Type of extended battery cabinets.
Battery Charge Compensating
Battery charge algorithm changed due to battery temperature
Battery Charge Status
Battery charge status.
Battery Charger State
Current state of the battery charger
Battery Discharge Time
The time on battery operation for this discharge
Battery Discharging
The battery is discharging
Battery Float Voltage
The cell voltage of the battery at float recharging.
Battery Low
The calculated battery time remaining has reached the low battery
threshold
Battery Over Voltage
The system has detected that the battery voltage has exceeded a
predetermined limit.
Battery Percentage Charge
The percentage of battery charge
Battery Rating
Total rating of all parallel strings in the battery.
Battery Self Test
Battery self test is in progress
Battery Test Failed
Battery test failed
Battery Test Result
The outcome of the previous battery test.
Battery Time Remaining
The calculated available time on battery
Battery Under Voltage
Battery voltage is too low.
Bypass Input Frequency
The bypass input frequency
Bypass Input RMS Current Line 2
The bypass input RMS current for Line 2
Bypass Input RMS Current
The bypass input RMS current.
Bypass Input Voltage RMS L1-L2
The bypass input RMS voltage between Lines 1 and 2
Bypass Input Voltage RMS L1-N
The bypass input RMS voltage between Line 1 and Neutral
Bypass Input Voltage RMS L2-N
The bypass input RMS voltage between Line 2 and Neutral
Bypass Nominal Voltage
Bypass nominal (or rated) voltage
Bypass Not Available
A problem associated with the bypass has been detected
Bypass/Inverter Input Config
Input source configuration for the bypass and inverter.
Charger Failure
Charger Failure - Charger is off
DC Bus Nominal Voltage
The nominal (or rated) voltage between the positive and negative
terminals of the DC bus at the battery input
DC Bus Voltage
The voltage between the positive and negative terminals of the DC bus at
the battery input
DC Converter Status
The operating state of the dc converter.
DC to DC Converter Fault
A failure has occurred in the battery discharge circuit.
ECO Mode Operation State
This setting is used to enable or disable ECO Mode.
ECO Mode Status
Current ECO Mode Status
Emergency Power Off - Latched
System output is off - 'Emergency Power Off (EPO) - latched' requires
manual reset
Equipment Over Temperature
Equipment over temperature summary event
Inlet Air Temperature
The temperature of the inlet air
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
278
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-65 Liebert GXT3™ and Liebert GXT4™—Glossary
Data Label
Data Description
Input Frequency Deviation
The input frequency is outside of the normal range.
Input Overvoltage
One or more of the input phase voltages has exceeded the limit.
Input Undervoltage
One or more of the input phase voltages has dropped below the limit.
Input Wiring Fault
The neutral/ground conductors on the input wiring are not properly
bonded, or the line/neutral conductors have been swapped.
Inverter Failure
Inverter failure - inverter output is off
Inverter On/Off State
inverter on/off state
Loss of Redundancy
The multi-module collection doesn't have enough modules to satisfy the
redundancy configuration.
Low Battery Warning Time
When battery time remaining falls to, or below, this value the low battery
alarm is activated.
Maintenance Bypass Breaker
Closed
The maintenance bypass breaker is closed.
Manual Battery Test
Command to initiate a manual battery test.
Nominal Battery Capacity
The nominal (or rated) battery capacity time at full load
Nominal Power Factor
The nominal (or rated) system power factor.
Number of EBC Installed
The total number of Extended Battery Cabinets installed.
Outlet Group Identifier
A runtime assigned outlet group identification number
Outlet Group Power Control
Outlet Group Power Control (OFF, ON, Cycle, etc)
Output Apparent Power Rating
Output apparent power rating
Output On Delay
When a value is written to this point the output will be turned on after the
specified time has elapsed.
Output Overload
An overload exists on the output.
Output Overvoltage
One or more of the output phase voltages has exceeded the limit.
Output Undervoltage
One or more of the output phase voltages has dropped below the limit.
Parallel Comm Warning
Parallel communication bus warning
Power Factor Correction
The state of the power factor correction circuitry of the system
Reboot With Delay
When a value is written to this point the output will be turned off
immediately and then turned back on after the specified time has elapsed.
Rectifier Failure
Rectifier failure - rectifier is off
Replace Battery
The battery is due for replacement.
Reset Power Statistics
Reset Power Statistics
Server Class
The general classification for this system
Shutdown After Delay
When a value is written to this point the system will shutdown after the
specified time has elapsed and output will remain off.
Shutdown Pending
Shutdown is pending.
Shutdown Reason
The reason for the most recent shutdown
Silence Audible Alarm
Silence Audible Alarm
System Fan Failure
System fan failure - one or more fans have failed
System Input Black Out Count
The number of occurrences, since the last reset, where the input was not
qualified to provide power to the system
System Input Brown Out Count
The number of occurrences, since the last reset, where the system input
voltage has fallen below a pre-determined threshold for a specified amount
of time
System Input Frequency
The system input frequency
System Input Max Voltage L1-N
The maximum system input voltage measurement for Line 1-N since the
last reset
System Input Max Voltage L2-N
The maximum system input voltage measurement for Line 2-N since the
last reset
279
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-65 Liebert GXT3™ and Liebert GXT4™—Glossary
Data Label
Data Description
System Input Min Voltage L1-N
The minimum system input voltage measurement for Line 1-N since the
last reset
System Input Min Voltage L2-N
The minimum system input voltage measurement for Line 2-N since the
last reset
System Input Nominal Current
The nominal (or rated) system input current
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS Current L1
The system input RMS current for Line 1
System Input RMS Current L2
The system input RMS current for Line 2
System Input RMS L1-L2
The System Input RMS Voltage between Line 1 and Line 2
System Input RMS L1-N
The System Input RMS Voltage between Line 1 and Neutral
System Input RMS L2-N
The System Input RMS Voltage between Line 2 and Neutral
System Output Apparent Power L1
System output apparent power on Line 1
System Output Apparent Power L2
System output apparent power on Line 2
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Frequency
The system output frequency
System Output Max Voltage L1-N
The maximum system output voltage measurement for Line 1-N since the
last reset.
System Output Max Voltage L2-N
The maximum system output voltage measurement for Line 2-N since the
last reset.
System Output Min Voltage L1-N
The minimum system output voltage measurement for Line 1-N since the
last reset.
System Output Min Voltage L2-N
The minimum system output voltage measurement for Line 2-N since the
last reset.
System Output Nominal Frequency
The nominal (or rated) system output frequency
System Output Nominal Voltage
The nominal (or rated) system output voltage
System Output Off
The system output is off
System Output Pct Power L1
The system output power on Line 1 as a percentage of the rated capacity
System Output Pct Power L2
The system output power on Line 2 as a percentage of the rated capacity
System Output Pct Power
The system output power as a percentage of the rated capacity.
System Output Power L1
The system output power on Line 1.
System Output Power L2
The system output power on Line 2.
System Output Power
The sum total power of all system output phases
System Output RMS Current L1
The system output RMS current for Line 1
System Output RMS Current L2
The system output RMS current for Line 2
System Output Voltage RMS L1-L2 The system output RMS voltage between Lines 1 and 2
System Output Voltage RMS L1-N
The system output RMS voltage between Line 1 and Neutral
System Output Voltage RMS L2-N
The system output RMS voltage between Line 2 and Neutral
System Status
The operating status for the system
Unspecified General Event
One or more unspecified events active. See local unit display for further
details.
UPS Battery Status
UPS battery status
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
UPS Topology
UPS Topology
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
280
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-66 Liebert HiNet™—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
DC-To-DC Converter On
10042
—
1
—
—
Load On Inverter
10073
—
1
—
—
Bypass Active
10074
—
1
—
—
Load On Battery
10128
—
1
—
—
Permanently On Bypass
10133
—
1
—
—
Bypass SCR Open Circuit
10149
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
Inverter Unsynchronized
10160
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Bypass Input Voltage/Frequency Fault
10202
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
281
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-67 Liebert HiNet™—Input and Holding
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Number of SubModules
30009
40009
1
—
-
Number of Battery Cells
30012
40012
1
—
-
Load (Apparent Power)
30102
—
2
—
VA
Load (Real Power)
30104
—
2
—
W
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
Battery Voltage
30113
—
1
—
V
Battery Current (Charge/Discharge)
30114
—
1
—
A
Battery Charge Percentage
30116
—
1
—
%
Ambient Temperature
30119
—
1
—
deg C
Input Voltage L1
30153
—
1
—
V
Input Current L1
30154
—
1
—
A
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Data Description
Input Voltage L2
30203
—
1
—
V
Input Current L2
30204
—
1
—
A
Input Voltage L3
30253
—
1
—
V
Input Current L3
30254
—
1
—
A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
282
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-68 Liebert Nfinity®—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Automatic Battery Test Enabled
10003
3
1
—
—
Battery Charger On
10044
—
1
—
—
Inverter Ready
10047
—
1
—
—
Power Factor Correction State
10050
—
1
—
—
Load on Inverter
10073
—
1
—
—
Bypass Active
10074
—
1
—
—
Replace Battery
10081
—
1
—
—
Battery Under Test
10082
—
1
—
—
Load on Battery
10128
—
1
—
—
Load on Bypass
10129
—
1
—
—
Load on Manual Bypass
10132
—
1
—
—
Load Transferred to Bypass Due to UPS Fault
10134
—
1
—
—
Transfer Inhibit
10146
—
1
—
—
Output Off Pending
10151
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
UPS Overload
10155
—
1
—
—
Output Off
10158
—
1
—
—
Check Air Filter - Replace
10170
—
1
—
—
Transformer Over Temperature
10178
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Internal Device Communication Failure
10284
—
1
—
—
Device Active Alarm
10290
—
1
—
—
Main Control Warning
10291
—
1
—
—
Redundant Control Warning
10292
—
1
—
—
Control Module Failure
10293
—
1
—
—
Redundant Control Module Failed
10294
—
1
—
—
User Interface Module Failed
10295
—
1
—
—
UPS Power Not Redundant
10296
—
1
—
—
Power Module Failure
10298
—
1
—
—
Battery Module Failure
10299
—
1
—
—
Power Module Warning
10300
—
1
—
—
Battery Module Warning
10301
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
283
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-69 Liebert Nfinity®—Input and Holding
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Number of Power Mod.
30010
40010
1
—
—
Number of Battery Modules Installed
30011
40011
1
—
—
Data Description
Device Maximum Frame Capacity
30023
40023
2
—
—
Device System Capacity
30025
40025
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch Voltage
30029
40029
1
—
V
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
Nominal Battery Voltage
30034
40034
1
—
V
Auto Restart Delay
30051
40051
1
—
Seconds
Device Auto Restart Percent Setpt
30052
40052
1
—
%
Device Low Battery Time
30053
40053
1
—
Minutes
Next Battery Auto Test Time
30057
40057
1
—
Minutes
Overload Alarm Limit
30067
40067
2
—
VA
Minimum Redundant Power Modules
30074
40074
1
—
—
Load (Apparent Power)
30102
—
2
—
VA
Load (Real Power)
30104
—
2
—
W
Load / Capacity
30106
—
1
—
%
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Hz
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Charge Status
30112
—
1
—
Battery Voltage
30113
—
1
—
V
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Battery Temperature
30117
—
1
—
deg C
Transformer Temperature
30121
—
1
—
deg C
Redundant Power Modules
30124
—
1
—
—
Active Power Module Count
30126
—
1
—
—
Battery Module Active Count
30127
—
1
—
—
Battery Test Result
30130
—
1
—
-
Input Voltage L1
30153
—
1
—
V
Input Current L1
30154
—
1
—
A
Bypass Voltage L1
30159
—
1
—
V
Bypass Current L1
30160
—
1
—
A
Output Voltage L1
30163
—
1
—
V
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
284
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-69 Liebert Nfinity®—Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Output Current L1
30164
—
1
—
A
Power Module Failure Count
30304
—
1
—
—
Battery Module Failure Count
30305
—
1
—
—
Power Module Warning Count
30306
—
1
—
—
Battery Module Warning Count
30307
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
285
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-70 Liebert NX™—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Economode
10005
5
—
—
—
DC-To-DC Converter On
10042
—
—
—
—
Battery Charge Compensation
10046
—
—
—
—
Inverter Ready
10047
—
—
—
—
Power Factor Correction State
10050
—
—
—
—
Battery Charge Mode
10051
—
—
—
—
Load On Inverter
10073
—
—
—
—
Bypass Active
10074
—
—
—
—
Battery Under Test
10082
—
—
—
—
Load On Battery
10128
—
—
—
—
Overload Transfer To Bypass
10131
—
—
—
—
Input Switch Open
10137
—
—
—
—
Generator Disconnected
10141
—
—
—
—
Bypass Transfer Count Block
10147
—
—
—
—
Static Bypass Switch Disabled
10148
—
—
—
—
Low Battery - Shutdown Imminent
10152
—
—
—
—
Output Overload
10154
—
—
—
—
UPS Load Joint Mode
10156
—
—
—
—
Output Off
10158
—
—
—
—
Inverter Unsynchronized
10160
—
—
—
—
Main Neutral Lost
10161
—
—
—
—
Fan Failure
10169
—
—
—
—
Ambient Over Temperature
10173
—
—
—
—
Rectifier Over Temperature
10174
—
—
—
—
Rectifier Inductor Over Temperature
10175
—
—
—
—
Inverter Over Temperature
10176
—
—
—
—
Inverter Inductor Over Temperature
10177
—
—
—
—
Battery Converter Over Temperature
10179
—
—
—
—
DC Bus Balancer Over Temperature
10180
—
—
—
—
Input Power Supply Fail
10186
—
—
—
—
Input BrownOut
10189
—
—
—
—
Bad Input Frequency
10190
—
—
—
—
Bypass Phase Rotation Error
10191
—
—
—
—
Bypass Phase Loss
10201
—
—
—
—
Bypass Input Voltage/Frequency Fault
10202
—
—
—
—
Output Fuse Blown
10217
—
—
—
—
Output Over Voltage
10219
—
—
—
—
Charger Failed
10234
—
—
—
—
Battery Fault
10235
—
—
—
—
Battery Contact Fail
10236
—
—
—
—
Battery Converter Over Current
10237
—
—
—
—
Battery Converter Fail
10238
—
—
—
—
DC Bus Balancer Over Current
10239
—
—
—
—
DC Bus Balancer Fault
10240
—
—
—
—
DC Bus 1 Power Supply Fail
10251
—
—
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
286
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-70 Liebert NX™—Status and Coil (continued)
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Rectifier Fuse Fail
10257
—
—
—
—
Rectifier Startup Failure
10258
—
—
—
—
Rectifier Fault
10259
—
—
—
—
Rectifier Current Limit
10260
—
—
—
—
Inverter DC Voltage Low Shutdown
10262
—
—
—
—
Inverter Fault
10263
—
—
—
—
Inverter DC Offset Overload
10264
—
—
—
—
Inverter Contactor Fail
10265
—
—
—
—
Inverter Current Limit
10266
—
—
—
—
Parallel Low Battery Warning
10267
—
—
—
—
Load Share Fault
10268
—
—
—
—
Parallel System Fault
10269
—
—
—
—
Parallel Connection Error
10270
—
—
—
—
Parallel System Overload
10271
—
—
—
—
Parallel Transfer To Static Bypass Switch
10272
—
—
—
—
Inverter Communication Fail
10281
—
—
—
—
Rectifier Communication Failure
10282
—
—
—
—
Parallel Communication Fault
10283
—
—
—
—
Operation Fault
10289
—
—
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
287
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-71 Liebert NX™—Input and Holding
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Data Description
Number of SubModules
30009
40009
1
—
—
Module Number
30014
40014
1
—
—
Device Module Count
30015
40015
1
—
—
Device Redundant Count
30016
40016
1
—
—
Device Module Mode
30017
40017
1
—
—
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch Voltage
30029
40029
1
—
V
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
Nominal DC Bus #1 Voltage
30035
40035
1
—
V
Nominal DC Bus #2 Voltage
30036
40036
1
—
—
Nominal Battery Float Voltage
30038
40038
1
—
V
Load Bus Sync Mode
30040
40040
1
—
—
Auto Restart Delay
30051
40051
1
—
Seconds
Device Low Battery Time
30053
40053
1
—
Minutes
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Battery Charge Status
30112
—
1
—
Battery Voltage
30113
—
1
—
Hz
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
V
Battery Current (Charge/Discharge)
30114
—
1
—
A
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Battery Temperature
30117
—
1
—
C
Ambient Temperature
30119
—
1
—
C
Parallel Load Source
30128
—
1
—
—
Rotary Breaker
30129
—
1
—
—
Battery Test Result
30130
—
1
—
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1-L2
30151
—
1
—
V
Input Voltage L1
30153
—
1
—
V
Input Current L1
30154
—
1
—
A
Input Power Factor L1
30155
—
1
100
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
288
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-71 Liebert NX™—Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Bypass Voltage L1
30159
—
1
—
V
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Output Load L1
30165
—
1
—
—
Output Power Factor L1
30166
—
1
100
%
Apparent Output Power L1
30168
—
2
—
VA
Reactive Output Power L1
30170
—
2
—
VAR
Output Power L1
30172
—
2
—
W
Output Current Crest Factor L1
30186
—
1
—
%
Input Voltage L2-L3
30201
—
1
—
V
Input Voltage L2
30203
—
1
—
V
Input Current L2
30204
—
1
—
A
Input Power Factor L2
30205
—
1
100
—
Bypass Voltage L2
30209
—
1
—
V
Output Voltage L2
30213
—
1
—
V
Output Current L2
30214
—
1
—
A
Output Load L2
30215
—
1
—
%
Output Power Factor L2
30216
—
1
100
—
Apparent Output Power L2
30218
—
2
—
VA
Reactive Output Power L2
30220
—
2
—
VAR
Output Power L2
30222
—
2
—
W
Output Current Crest Factor L2
30236
—
1
—
%
Input Voltage L3-L1
30251
—
1
—
V
Input Voltage L3
30253
—
1
—
V
Input Current L3
30254
—
1
—
A
Input Power Factor L3
30255
—
1
100
—
Bypass Voltage L3
30259
—
1
—
V
Output Voltage L3
30263
—
1
—
V
Output Current L3
30264
—
1
—
A
Output Load L3
30265
—
1
—
%
Output Power Factor L3
30266
—
1
100
—
Apparent Output Power L3
30268
—
2
—
VA
Reactive Output Power L3
30270
—
2
—
VAR
Output Power L3
30272
—
2
—
W
Output Current Crest Factor L3
30286
—
1
—
%
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
289
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-72 Liebert NX™ 225-600kVA UPS—Chloride ManageUPS—Input and Holding 3
Input
Holding
Register
# of
Reg
Scale
Modbus Protocol Version
—
40002
1
—
XX.YY
Manufacturer
—
40003
1
—
0 = Chloride
Data Description
Notes/Units
Identification
Model
—
40004
1
—
8 = 80Net
UPS Software 1 Version
—
40005
1
—
HH Major – LL Minor
UPS Software 1 Date Year
—
40006
1
—
—
UPS Software 1 Date Month
—
40007
1
—
—
UPS Software 1 Date Day
—
40008
1
—
—
UPS Software 1 Code
—
40009
1
—
10HXXXXX code
UPS Software 2 Version
—
40010
1
—
HH Major – LL Minor
UPS Software 2 Date Year
—
40011
1
—
—
UPS Software 2 Date Month
—
40012
1
—
—
UPS Software 2 Date Day
—
40013
1
—
—
UPS Software 2 Code
—
40014
1
—
10HXXXXX code
Battery Status
—
40020
1
—
1 = Unknown
2 = Battery Normal
3 = Battery Low
4 = Battery Depleted
Seconds On Battery
—
40021
1
—
Units: Seconds
Estimated Seconds Remaining
—
40022
1
—
Units: Seconds
Battery
Estimated Charge Remaining
—
40023
1
—
Units: %
Battery Voltage
—
40024
1
10
Units: V
Battery Current
—
40025
1
10
Units: A
Battery Temperature
—
40026
1
—
Units: Deg C
Line Bads
—
40032
1
—
—
Frequency
—
40033
1
10
Units: Hz
Number Lines
—
40034
1
—
Voltage L1
—
40035
1
—
Units: V
Voltage L2
—
40036
1
—
Units: V
Voltage L3
—
40037
1
—
Units: V
Current L1
—
40038
1
10
Units: Amps
Current L2
—
40039
1
10
Units: A
Current L3
—
40040
1
10
Units: A
Real Power L1
—
40041
1
10
Units: kW
Real Power L2
—
40042
1
10
Units: kW
Input
Real Power L3
—
40043
1
10
Units: kW
DC Voltage
—
40044
1
—
Units: V
1. If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
2. The Modbus mapping in this table assumes the default Modbus offset is 1. This value is configurable via the Web interface. If the Modbus
offset is changed you will need to adjust the above Holding registers accordingly.
3. This mapping table defines Liebert NX 225-600kVA UPS support using the Chloride ManageUPS Net Adapter +B communication card.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
290
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-72 Liebert NX™ 225-600kVA UPS—Chloride ManageUPS—Input and Holding 3 (continued)
Data Description
Input
Holding
Register
# of
Reg
Scale
Notes/Units
Output
Source
—
40050
1
—
1 = Other
2 = None
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Frequency
—
40051
1
10
Units: Hz
Number Lines
—
40052
1
—
—
Voltage L1
—
40053
1
—
Units: V
Voltage L2
—
40054
1
—
Units: V
Voltage L3
—
40055
1
—
Units: V
Current L1
—
40056
1
10
Units: A
Current L2
—
40057
1
10
Units: A
Current L3
—
40058
1
10
Units: A
Real Power L1
—
40059
1
10
Units: kW
Real Power L2
—
40060
1
10
Units: kW
Real Power L3
—
40061
1
10
Units: kW
Percent Load L1
—
40062
1
—
Units: %
Percent Load L2
—
40063
1
—
Units: %
Percent Load L3
—
40064
1
—
Units: %
Bypass
Line Bads
—
40070
1
—
—
Frequency
—
40071
1
10
Units: Hz
Number Lines
—
40072
1
—
—
Voltage L1
—
40073
1
—
Units: V
Voltage L2
—
40074
1
—
Units: V
Voltage L3
—
40075
1
—
Units: V
Current L1
—
40076
1
10
Units: A
Current L2
—
40077
1
10
Units: A
Current L3
—
40078
1
10
Units: A
Alarms Present
—
40087
1
—
Bit 0
On Battery
—
40087
1
—
Bit 2
Low Battery
—
40087
1
—
Bit 3
Depleted Battery
—
40087
1
—
Bit 4
Temperature Bad
—
40087
1
—
Bit 5
Input Bad
—
40087
1
—
Bit 6
Alarms
Output Overload
—
40088
1
—
Bit 0
On Bypass
—
40088
1
—
Bit 1
Bypass Bad
—
40088
1
—
Bit 2
Charger Failed
—
40088
1
—
Bit 5
Fan Failure
—
40089
1
—
Bit 0
1. If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
2. The Modbus mapping in this table assumes the default Modbus offset is 1. This value is configurable via the Web interface. If the Modbus
offset is changed you will need to adjust the above Holding registers accordingly.
3. This mapping table defines Liebert NX 225-600kVA UPS support using the Chloride ManageUPS Net Adapter +B communication card.
291
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-72 Liebert NX™ 225-600kVA UPS—Chloride ManageUPS—Input and Holding 3 (continued)
Input
Holding
Register
# of
Reg
Scale
Notes/Units
General Fault
—
40089
1
—
Bit 2
Diagnostic Test Failed
—
40089
1
—
Bit 3
Communications Lost
—
40089
1
—
Bit 4
Data Description
Shutdown Pending
—
40089
1
—
Bit 6
Test In Progress
—
40090
1
—
Bit 0
General Warning
—
40090
1
—
Bit 2
—
0 = Bypass not present
1 = Bypass on
2 = Bypass off
3 = Bypass fault
4 = Bypass not prepared
Condition
Bypass
—
40091
1
Inverter
—
40092
1
—
0 = Inverter off
1 = Inverter turning on
2 = Inverter on
3 = Inverter fault
4 = Inverter turning off
Rectifier
—
40093
1
—
0 = Rectifier Off
1 = Rectifier Turning On
2 = Rectifier On
3 = Rectifier Fault
Battery Connected
—
40094
1
—
—
NonSynchronism
—
40095
1
—
—
In Parallel Set
—
40101
1
—
0 = UPS is Single
1 = UPS is part of parallel set
Customer-Dedicated Information
—
—
—
Customer Info 1
—
40108
1
—
—
Customer Info 2
—
40109
1
—
—
Customer Info 3
—
40110
1
—
—
Customer Info 4
—
40111
1
—
—
Customer Info 5
—
40112
1
—
—
Parallel Condition
1. If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
2. The Modbus mapping in this table assumes the default Modbus offset is 1. This value is configurable via the Web interface. If the Modbus
offset is changed you will need to adjust the above Holding registers accordingly.
3. This mapping table defines Liebert NX 225-600kVA UPS support using the Chloride ManageUPS Net Adapter +B communication card.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
292
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-73 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Status and Coil
Status
Coil
Number of Bits
Notes
Rectifier Failure
10001
—
1
Active on Alarm
System Input Phs Rotation Error
10002
—
1
Active on Alarm
System Input Current Limit
10003
—
1
Active on Alarm
System Input Power Problem
10004
—
1
Active on Alarm
10015
—
1
Active on Alarm
Bypass Input Voltage Fault
10016
—
1
Active on Alarm
Bypass Not Available
10017
—
1
Active on Alarm
Bypass Overload
10018
—
1
Active on Alarm
Data Label
Input
Bypass
Bypass Static Switch Unavailable
Battery
Battery Test Failed
10029
—
1
Active on Alarm
Battery Test Passed
10030
—
1
Active on Alarm
Battery Terminals Reversed
10031
—
1
Active on Alarm
Battery Over Voltage
10032
—
1
Active on Alarm
Battery Temperature Out of Range
10033
—
1
Active on Alarm
Battery Low
10034
—
1
Active on Alarm
Battery Over Temperature
10035
—
1
Active on Alarm
Battery Discharging
10036
—
1
Active on Alarm
Battery Auto Test In Progress
10037
—
1
Active on Alarm
Battery Manual Test In Progress
10038
—
1
Active on Alarm
Battery Ground Fault
10039
—
1
Active on Alarm
DC Bus Abnormal
10040
—
1
Active on Alarm
10051
—
1
Active on Alarm
Output
System Output Off
Output Load on Maint. Bypass
10052
—
1
Active on Alarm
UPS Output on Bypass
10053
—
1
Active on Alarm
Inverter
Inverter Failure
10065
—
1
Active on Alarm
Inverter Overload
10066
—
1
Active on Alarm
System Output Fault
10067
—
1
Active on Alarm
Output Of/Uf
10068
—
1
Active on Alarm
System Shutdown - Output Short
10069
—
1
Active on Alarm
Inverter Desaturation
10070
—
1
Active on Alarm
Booster-Charger
Booster Failure
10081
—
1
Active on Alarm
Charger Failure
10082
—
1
Active on Alarm
System Shutdown - EPO
10093
—
1
Active on Alarm
Generic DIC Fault
10094
—
1
Active on Alarm
Inlet Air Over Temperature
10095
—
1
Active on Alarm
Generic Test Event
10096
—
1
Active on Alarm
System Status
Fan Hours Exceeded
10097
—
1
Active on Alarm
Unit Shutdown
10098
—
1
Active on Alarm
Main Controller Fault
10099
—
1
Active on Alarm
Equipment Over Temperature
10100
—
1
Active on Alarm
293
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-73 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Status and Coil (continued)
Data Label
Status
Coil
Number of Bits
Notes
Maximum Load Alarm
10101
—
1
Active on Alarm
Ground Fault
10102
—
1
Active on Alarm
Backfeed Breaker Open
10113
—
1
Active on Alarm
Input Breaker Open
10114
—
1
Active on Alarm
Output Breaker Open
10115
—
1
Active on Alarm
Maintenance Bypass Breaker Closed
10116
—
1
Active on Alarm
Battery Breaker Open
10117
—
1
Active on Alarm
Switch Gear
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
294
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding
Input
Holding
# of Reg
Scale
Notes/Units
System Input RMS A-B
30385
—
1
10
Units : VAC
Uint16
System Input RMS B-C
30386
—
1
10
Units : VAC
Uint16
System Input RMS C-A
30387
—
1
10
Units : VAC
Uint16
System Input RMS Current Phase A
30388
—
1
10
Units : A AC
Uint16
System Input RMS Current Phase B
30389
—
1
10
Units : A AC
Uint16
System Input RMS Current Phase C
30390
—
1
10
Units : A AC
Uint16
System Input Frequency
30391
—
1
10
Units : Hz
Uint16
Rectifier Status
30392
—
1
—
0 = off
1 = on
Rectifier Phase A Temperature sensor
30403
—
1
—
Units : deg C
Int16
Rectifier Phase A Temperature sensor
30404
—
1
—
Units : deg F
Int16
Rectifier Phase B Temperature sensor
30405
—
1
—
Units : deg C
Int16
Rectifier Phase B Temperature sensor
30406
—
1
—
Units : deg F
Int16
Rectifier Phase C Temperature sensor
30407
—
1
—
Units : deg C
Int16
Rectifier Phase C Temperature sensor
30408
—
1
—
Units : deg F
Int16
Data Label
Input
Rectifier Module Temperatures 1
Rectifier Module Temperatures 2
—
—
Rectifier Phase A Temperature sensor
30419
—
1
—
Units : deg C
Int16
Rectifier Phase A Temperature sensor
30420
—
1
—
Units : deg F
Int16
Rectifier Phase B Temperature sensor
30421
—
1
—
Units : deg C
Int16
Rectifier Phase B Temperature sensor
30422
—
1
—
Units : deg F
Int16
Rectifier Phase C Temperature sensor
30423
—
1
—
Units : deg C
Int16
Rectifier Phase C Temperature sensor
30424
—
1
—
Units : deg F
Int16
295
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding (continued)
Input
Holding
# of Reg
Scale
Notes/Units
Rectifier Phase A Temperature sensor
30451
—
1
—
Units : deg C
Int16
Rectifier Phase A Temperature sensor
30452
—
1
—
Units : deg F
Int16
Rectifier Phase B Temperature sensor
30453
—
1
—
Units : deg C
Int16
Rectifier Phase B Temperature sensor
30454
—
1
—
Units : deg F
Int16
Rectifier Phase C Temperature sensor
30455
—
1
—
Units : deg C
Int16
Rectifier Phase C Temperature sensor
30456
—
1
—
Units : deg F
Int16
Bypass Input Voltage RMS A-B
30467
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS B-C
30468
—
1
—
Units : VAC
Uint16
Bypass Input Voltage RMS C-A
30469
—
1
—
Units : VAC
Uint16
Bypass Input Frequency
30470
—
1
—
Units : Hz
Uint16
Static Bypass Switch
30471
—
1
—
0 = off
1 = on
Data Label
Rectifier Module Temperatures 4
Bypass
30472
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
DC Bus Voltage
30483
—
1
—
Units : VDC
Uint16
Battery Volts for Cabinet
30484
—
1
—
Units : VDC
Int16
DC Bus Current
30485
—
1
—
Units : A DC
Int16
Battery Time Remaining
30486
—
1
—
Units : min
Uint16
Battery Percentage Charge
30487
—
1
—
Units : %
Uint16
Battery Temperature for Cabinet
30488
—
1
—
Units : deg C
Int16
Battery Temperature for Cabinet
30489
—
1
—
Units : deg F
Int16
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
—
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
Bypass Qualification Status
Battery
DC Bus Qualification Status
UPS battery1 status
30490
30491
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
—
1
—
1
296
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding (continued)
Input
Holding
# of Reg
Scale
Notes/Units
System Output Voltage RMS A-B
30502
—
1
10
Units : VAC
Uint16
System Output Voltage RMS B-C
30503
—
1
10
Units : VAC
Uint16
System Output Voltage RMS C-A
30504
—
1
10
Units : VAC
Uint16
System Output RMS Current Phs A
30505
—
1
10
Units : A AC
Uint16
System Output RMS Current Phs B
30506
—
1
10
Units : A AC
Uint16
System Output RMS Current Phs C
30507
—
1
10
Units : A AC
Uint16
System Output Frequency
30508
—
1
10
Units : Hz
Uint16
System Output Apparent Power
30509
—
1
—
Units : kVA
Uint16
System Output Power
30510
—
1
—
Units : kW
Uint16
System Output Apparent Power Phs A
30511
—
1
—
Units : kVA
Uint16
System Output Apparent Power Phs B
30512
—
1
—
Units : kVA
Uint16
System Output Apparent Power Phs C
30513
—
1
—
Units : kVA
Uint16
System Output Power Phase A
30514
—
1
—
Units : kW
Uint16
System Output Power Phase B
30515
—
1
—
Units : kW
Uint16
System Output Power Phase C
30516
—
1
—
Units : kW
Uint16
System Output Pct Power Phase A
30517
—
1
—
Units : %
Uint16
System Output Pct Power Phase B
30518
—
1
—
Units : %
Uint16
System Output Pct Power Phase C
30519
—
1
—
Units : %
Uint16
Output Percent Load
30520
—
1
—
Units : %
Uint16
Temperature
30521
—
1
—
Units : deg C
Int16
Temperature
30522
—
1
—
Units : deg F
Int16
Data Label
Output
UPS Output Source
30523
—
1
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
Load Power Source
30524
—
1
—
0 = Load Off
1 = UPS
2 = Maintenance Bypass
297
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding (continued)
Input
Holding
# of Reg
Scale
Notes/Units
Inverter Overload Time Remaining
30535
—
1
—
Units : sec
Uint16
Inverter On/Off State
30536
—
1
—
0 = off
1 = on
Data Label
Inverter
30537
—
1
—
0 = External
1 = Self clock (internal)
2 = Output
3 = Bypass
Inverter Phase A Temperature sensor
30548
—
1
—
Units : deg C
Int16
Inverter Phase A Temperature sensor
30549
—
1
—
Units : deg F
Int16
Inverter Phase B Temperature sensor
30550
—
1
—
Units : deg C
Int16
Inverter Phase B Temperature sensor
30551
—
1
—
Units : deg F
Int16
Inverter Phase C temperature sensor
30552
—
1
—
Units : deg C
Int16
Inverter Phase C temperature sensor
30553
—
1
—
Units : deg F
Int16
Inverter Phase A Temperature sensor
30564
—
1
—
Units : deg C
Int16
Inverter Phase A Temperature sensor
30565
—
1
—
Units : deg F
Int16
Inverter Phase B Temperature sensor
30566
—
1
—
Units : deg C
Int16
Inverter Phase B Temperature sensor
30567
—
1
—
Units : deg F
Int16
Inverter Phase C temperature sensor
30568
—
1
—
Units : deg C
Int16
Inverter Phase C temperature sensor
30569
—
1
—
Units : deg F
Int16
Inverter Phase A Temperature sensor
30596
—
1
—
Units : deg C
Int16
Inverter Phase A Temperature sensor
30597
—
1
—
Units : deg F
Int16
Inverter Phase B Temperature sensor
30598
—
1
—
Units : deg C
Int16
Inverter Phase B Temperature sensor
30599
—
1
—
Units : deg F
Int16
Inverter Phase C temperature sensor
30600
—
1
—
Units : deg C
Int16
Inverter Phase C temperature sensor
30601
—
1
—
Units : deg F
Int16
30612
—
1
100
Units : VDC
Uint16
Inverter Synchronization Source
Inverter Module Temperatures 1
Inverter Module Temperatures 2
Inverter Module Temperatures 4
Booster-Charger
Battery Recharge Voltage
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
298
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Max Charge Current
30613
—
1
—
Units : A DC
Int16
Booster On/Off State
30614
—
1
—
0 = off
1 = on
Charger On/Off State
30615
—
1
—
0 = off
1 = on
Booster-Charger Temperature
30626
—
1
—
Units : deg C
Int16
Booster-Charger Temperature
30627
—
1
—
Units : deg F
Int16
Booster Charger Module Temperatures 1
Booster Charger Module Temperatures 2
—
—
Booster-Charger Temperature
30638
—
1
—
Units : deg C
Int16
Booster-Charger Temperature
30639
—
1
—
Units : deg F
Int16
Booster Charger Module Temperatures 4
—
—
Booster-Charger Temperature
30662
—
1
—
Units : deg C
Int16
Booster-Charger Temperature
30663
—
1
—
Units : deg F
Int16
—
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Status
System Status
30674
—
1
UPS Operating Mode
30675
—
1
—
0 = Idle
1 = Double Conversion Mode (VFI)
2 = Interactive Mode (VI)
3 = Stand-By Mode (VFD)
4 = CR Mode (CR)
5 = ECO Mode (DIM)
ECO Mode Operation State
30676
—
1
—
0 = disabled
1 = enabled
Output Apparent Power Rating
30687
—
1
—
Units : kVA
Uint16
System Input Nominal Voltage
30688
—
1
—
Units : VAC
Uint16
System Input Nominal Frequency
30689
—
1
—
Units : Hz
Uint16
Ratings
299
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-75 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Glossary
Data Label
Data Description
Backfeed Breaker Open
The backfeed breaker is in the open position
Battery Auto Test In Progress
Automatic battery test is in progress
Battery Breaker Open
The battery circuit is open.
Battery Discharging
The battery is discharging
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Low
The calculated battery time remaining has reached the low battery threshold
Battery Manual Test In Progress
Manual battery test is in progress
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Over Voltage
The system has detected that the battery voltage has exceeded a predetermined
limit.
Battery Percentage Charge
The percentage of battery charge
Battery Recharge Voltage
The recharge cell voltage for the battery.
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Temperature Out of Range
Battery temperature is outside of acceptable range.
Battery Terminals Reversed
The measured battery voltage is a negative value due to reverse battery terminal
connections.
Battery Test Failed
Battery test failed
Battery Test Passed
Battery test passed
Battery Time Remaining
The calculated available time on battery
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a battery cabinet
Booster Failure
Booster failure - boost is off
Booster On/Off State
Booster on/off state
Booster-Charger Temperature
Temperature measured at the charger stage
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage Fault
The system has detected the bypass voltage is unqualified.
Bypass Input Voltage RMS A-B
The bypass input RMS voltage between phases A and B
Bypass Input Voltage RMS B-C
The bypass input RMS voltage between phases B and C
Bypass Input Voltage RMS C-A
The bypass input RMS voltage between phases C and A
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Overload
Bypass overloaded, reduce load immediately.
Bypass Qualification Status
bypass qualification status
Bypass Static Switch Unavailable
The static bypass is unavailable to support the critical load.
Charger Failure
Charger Failure - Charger is off
Charger On/Off State
Charger on/off state
DC Bus Abnormal
The system has detected an abnormal DC Bus Voltage.
DC Bus Current
The current at the battery input terminals. In charging mode, the current will be a
positive value. In discharging mode, the current will be a negative value
DC Bus Qualification Status
dc bus qualification status
DC Bus Voltage
The voltage between the postivie and negative terminals of the internal DC Bus.
ECO Mode Operation State
This setting is used to enable or disable ECO Mode.
Equipment Over Temperature
Equipment over temperature summary event
Fan Hours Exceeded
Operating hours for the unit blower fan have exceeded the threshold.
Generic DIC Fault
The control board reports a fault - Service required.
Generic Test Event
A generic test event designed to evaluate system handling of events
Ground Fault
An AC phase to ground fault or three phase fault to ground exists on the output of
the UPS.
Inlet Air Over Temperature
The inlet air exceeds the maximum temperature threshold
Input Breaker Open
The main input breaker is open.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
300
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-75 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Glossary (continued)
Data Label
Data Description
Inverter Desaturation
Inverter Desaturation
Inverter Failure
Inverter failure - inverter output is off
Inverter On/Off State
inverter on/off state
Inverter Overload Time Remaining
The calculated time remaining before inverter shutdown
Inverter Overload
Inverter in overload fault
Inverter Phase A Temperature sensor
Inverter temperature sensor reading for Phase A.
Inverter Phase B Temperature sensor
Inverter temperature sensor reading for Phase B.
Inverter Phase C temperature sensor
Inverter temperature sensor reading for Phase C.
Inverter Synchronization Source
The reference source for inverter synchronization
Load Power Source
Load power source
Main Controller Fault
A Main Controller fault has been detected.
Maintenance Bypass Breaker Closed
The maintenance bypass breaker is closed.
Max Charge Current
The maximum allowed current to be used for charging the batteries.
Maximum Load Alarm
Maximum load alarm indicating load setting has been exceeded.
Output Apparent Power Rating
Output apparent power rating
Output Breaker Open
The output breaker is open.
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Output Of/Uf
The output frequency has exceeded a specified range for a specified period of time.
Output Percent Load
The percentage of the system's total rated output current that is flowing from the
system.
Rectifier Failure
Rectifier failure - rectifier is off
Rectifier Phase A Temperature sensor
Rectifier temperature sensor reading for Phase A.
Rectifier Phase B Temperature sensor
Rectifier temperature sensor reading for Phase B.
Rectifier Phase C Temperature sensor
Rectifier temperature sensor reading for Phase C.
Rectifier Status
rectifier status
Static Bypass Switch
Static Bypass Switch state - On/Off
System Input Current Limit
The RMS input current has reached the input current limit threshold
System Input Frequency
The system input frequency
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the sequence
preferred for the rectifier (A-B-C)
System Input Power Problem
The input is not qualified to provide power to the system
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Output Apparent Power Phs A
System output apparent power on phase A
System Output Apparent Power Phs B
System output apparent power on phase B
System Output Apparent Power Phs C
System output apparent power on phase C
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Off
The system output is off
System Output Pct Power Phase A
The system output power on phase A as a percentage of the rated capacity
301
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-75 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Glossary (continued)
Data Label
Data Description
System Output Pct Power Phase B
The system output power on phase B as a percentage of the rated capacity
System Output Pct Power Phase C
The system output power on phase C as a percentage of the rated capacity
System Output Power Phase A
The system output power on phase A.
System Output Power Phase B
The system output power on phase B.
System Output Power Phase C
The system output power on phase C.
System Output Power
The sum total power of all system output phases
System Output RMS Current Phs A
The system output RMS current for Phase A
System Output RMS Current Phs B
The system output RMS current for Phase B
System Output RMS Current Phs C
The system output RMS current for Phase C
System Output Voltage RMS A-B
The system output RMS voltage between phases A and B
System Output Voltage RMS B-C
The system output RMS voltage between phases B and C
System Output Voltage RMS C-A
The system output RMS voltage between phases C and A
System Shutdown - EPO
System shutdown due to Emergency Power Off (EPO)
System Shutdown - Output Short
Shutdown was due to a short on the output.
System Status
The operating status for the system
Temperature
Temperature measured at the temperature sensor
Unit Shutdown
An event has occurred requiring the unit to be shutdown and disabled to prevent
damage to the system.
UPS battery1 status
UPS battery status
UPS Operating Mode
UPS Operating Mode
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
302
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-76 Liebert NXL™—60Hz, UL version (Model 40)—Status and Coil
Data Label
Status
Coil
# of Bits
Notes
NXL Type
Battery Self Test
10082
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Low Shutdown
10092
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Shutdown - REPO
10093
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
UPS Output on Bypass
10129
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Output Load on Maint. Bypass
10132
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Main Battery Disconnect Open
10136
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Bypass - Excess Auto Retransfers
10147
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Battery Low
10152
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Shutdown - EPO
10157
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Output Off
10158
—
1
Active on Alarm
Deprecated
Battery Over Temperature
10172
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inlet Air Over Temperature
10173
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Current Imbalance
10185
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Phs Rotation Error
10191
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Rectifier Failure
10259
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Failure
10263
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Main Controller Fault
10293
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Bypass Not Available
10321
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase A
10322
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase B
10323
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Overload Phase C
10324
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Auto Retransfer Failed
10325
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Unavailable
10326
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Overload
10327
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Excessive Pulse Parallel
10328
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Auto Transfer Failed
10329
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Frequency Error
10330
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass - Manual Rexfr Inhibited
10331
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass - Manual Xfr Inhibited
10332
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Bypass Static Switch Off Extrnl
10333
—
1
Active on Alarm
CE only
Battery Charging Reduced-Extrnl
10334
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Capacity Low
10335
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Discharging
10336
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Temperature Imbalance
10337
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Temperature Sensor Fault
10338
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Charging Inhibited
10339
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 1 Open
10340
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 2 Open
10341
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 3 Open
10342
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 4 Open
10343
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 5 Open
10344
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 6 Open
10345
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 7 Open
10346
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Circuit Breaker 8 Open
10347
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery - External Monitor 1
10348
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery - External Monitor 2
10349
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
303
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-76 Liebert NXL™—60Hz, UL version (Model 40)—Status and Coil (continued)
Data Label
Status
Coil
# of Bits
Notes
NXL Type
Battery Over Temperature
10350
—
1
Active on Warning
N+1, 1+N, 1+1, SMS
DC Bus Ground Fault - Positive
10351
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
DC Bus Ground Fault - Negative
10352
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Output Low Power Factor
10353
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Leading Power Factor
10354
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Output Amp Over User Limit-Phs A
10355
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Output Amp Over User Limit-Phs B
10356
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Output Amp Over User Limit-Phs C
10357
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Output Fault
10358
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Overload Phase A
10359
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Overload Phase B
10360
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Overload Phase C
10361
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Inhibit - External
10362
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Shutdown - Overload
10363
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Inverter Off - External
10364
—
1
Active on Alarm
CE only
Inverter Static Switch SCR Short
10365
—
1
Active on Alarm
CE only
Equipment Over Temperature
10366
—
1
Active on Warning
SCC, N+1, 1+N, 1+1, SMS
Equipment Over Temperature
10367
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Equipment Temperature Sensor Fail
10368
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 01
10369
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 02
10370
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 03
10371
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 04
10372
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 05
10373
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 06
10374
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 07
10375
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 08
10376
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 09
10377
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 10
10378
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 11
10379
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 12
10380
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 13
10381
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 14
10382
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 15
10383
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Contact 16
10384
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Rectifier Operation Inhibit-Ext
10385
—
1
Active on Alarm
Deprecated
System Fan Failure - Redundant
10386
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Multiple Fan Failure
10387
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Auto Restart In Progress
10388
—
1
Active on Alarm
SCC, SMS
Automatic Restart Failed
10389
—
1
Active on Alarm
SCC, SMS
Fuse Failure
10390
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
System Breaker(s) Open Failure
10391
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
System Breaker(s) Close Failure
10392
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Input Filter Cycle Lock
10393
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Service Code Active
10394
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
LBS Inhibited
10396
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
304
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-76 Liebert NXL™—60Hz, UL version (Model 40)—Status and Coil (continued)
Status
Coil
# of Bits
Notes
NXL Type
Controls Reset Required
10397
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Battery Test Failed
10398
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Auto Restart Inhibited - Ext
10399
—
1
Active on Alarm
SCC, SMS
Battery Test Inhibited
10400
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Data Label
Battery Equalize
10401
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Backfeed Breaker Open
10402
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
On Generator
10403
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Power Supply Failure
10404
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Battery Ground Fault
10405
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Battery Charging Error
10406
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Power Problem
10407
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
System Input Current Limit
10408
—
1
Active on Alarm
N+1, 1+N, 1+1, SMS
Internal Communications Failure
10409
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
System Controller Error
10410
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
10510
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Parallel Comm Warning
10521
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1
System Comm Fail
10522
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1
Loss of Redundancy
10523
—
1
Active on Alarm
SCC, 1+N, 1+1
Output
Output Of/Uf
MultiModule
BPSS Startup Inhibit
10524
—
1
Active on Alarm
Deprecated
MMS Transfer Inhibit
10525
—
1
Active on Alarm
SCC, 1+N, 1+1
MMS Retransfer Inhibit
10526
—
1
Active on Alarm
SCC, 1+N, 1+1
MMS Loss of Sync Pulse
10527
—
1
Active on Alarm
Deprecated
MMS Overload
10528
—
1
Active on Alarm
SCC
MMS On Battery
10529
—
1
Active on Alarm
SCC, 1+N, 1+1
MMS Low Battery Warning
10530
—
1
Active on Alarm
SCC, 1+N, 1+1
MMS Module Alarm Active
10531
—
1
Active on Alarm
SCC
MMS Sharing Calib Active
10532
—
1
Active on Alarm
SCC
10543
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1
ECO Mode Active
10554
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
ECO Mode Suspended
10555
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
Excess ECO Suspends
10556
—
1
Active on Alarm
SCC, N+1, 1+N, 1+1, SMS
LBS Active - Master
10567
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
LBS Active - Slave
10568
—
1
Active on Alarm
SCC, 1+N, 1+1, SMS
Intelligent Paralleling
Module In Standby - Intelligent Paralleling
ECO Mode
System
EMO Shutdown
10575
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
Cont Tie Active
10576
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
User kWh Reset
10577
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
Peak kW Reset
10578
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
10580
—
1
Active on Alarm
SCC, SMS, 1+N, N+1
10590
—
1
Active on Alarm
SMS, 1+N, N+1, SCC
Environment
Outlet Air Overtemperature Limit
Service Reminder
Service Required
305
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
System Date and Time
30005
—
2
—
Masks:
Year 0xFFFF 0000
Mon 0x0000 FF00
Day 0x0000 00FF
SCC, N+1,
1+N, 1+1,
SMS
System Date and Time
30007
—
2
—
Masks:
Hour 0xFF00 0000
Min 0x00FF 0000
Sec 0x0000 FF00
SCC, N+1,
1+N, 1+1,
SMS
Output Apparent Power Rating
30021
—
2
—
kVA
SCC, N+1,
1+N, 1+1,
SMS
System Input Nominal Voltage
30027
—
1
—
VAC
SCC, N+1,
1+N, 1+1,
SMS
System Output Nominal Voltage
30028
—
1
—
VAC
SCC, N+1,
1+N, 1+1,
SMS
Bypass Nominal Voltage
30029
—
1
—
VAC
SCC, 1+N,
1+1, SMS
System Input Nominal Frequency
30031
—
1
10
Hz
SCC, N+1,
1+N, 1+1,
SMS
System Output Nominal Frequency
30032
—
1
10
Hz
SCC, N+1,
1+N, 1+1,
SMS
System Output Apparent Power
30102
—
2
—
kVA
N+1, 1+N,
1+1, SMS
System Output Power
30104
—
2
—
kW
N+1, 1+N,
1+1, SMS
System Input Frequency
30107
—
1
10
Hz
N+1, 1+N,
1+1, SMS
System Output Frequency
30108
—
1
10
Hz
N+1, 1+N,
1+1, SMS
Bypass Input Frequency
30109
—
1
10
Hz
SCC, 1+N,
1+1, SMS
Battery Volts at Main Disconnect
30113
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Time Remaining
30115
—
1
—
min
N+1, 1+N,
1+1, SMS
Battery Percentage Charge
30116
—
1
—
—
N+1, 1+N,
1+1, SMS
Inlet Air Temperature
30119
—
1
—
deg C
SCC, N+1,
1+N,
1+1, SMS
System Input RMS A-B
30151
—
1
—
VAC
N+1, 1+N,
1+1, SMS
System Input RMS Current Phase A
30154
—
1
—
A AC
N+1, 1+N,
1+1, SMS
Bypass Input Voltage RMS A-B
30157
—
1
—
VAC
SCC, 1+N,
1+1, SMS
System Output Voltage RMS A-B
30161
—
1
—
VAC
N+1, 1+N,
1+1, SMS
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
306
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
System Output Voltage RMS A-N
30162
—
1
—
VAC
N+1, 1+N,
1+1, SMS
System Output RMS Current Phs A
30164
—
1
—
A AC
N+1, 1+N,
1+1, SMS
System Output Pct Power Phase A
30165
—
1
—
%
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs A
30166
—
1
100
—
N+1, 1+N,
1+1, SMS
System Input RMS B-C
30201
—
1
—
VAC
N+1, 1+N,
1+1, SMS
System Input RMS Current Phase B
30204
—
1
—
A AC
N+1, 1+N,
1+1, SMS
Bypass Input Voltage RMS B-C
30207
—
1
—
VAC
SCC, 1+N,
1+1, SMS
System Output Voltage RMS B-C
30211
—
1
—
VAC
N+1, 1+N,
1+1, SMS
System Output Voltage RMS B-N
30212
—
1
—
VAC
N+1, 1+N,
1+1, SMS
System Output RMS Current Phs B
30214
—
1
—
A AC
N+1, 1+N,
1+1, SMS
System Output Pct Power Phase B
30215
—
1
—
%
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs B
30216
—
1
100
—
N+1, 1+N,
1+1, SMS
System Input RMS C-A
30251
—
1
—
VAC
N+1, 1+N,
1+1, SMS
System Input RMS Current Phase C
30254
—
1
—
A AC
N+1, 1+N,
1+1, SMS
Bypass Input Voltage RMS C-A
30257
—
1
—
VAC
SCC, 1+N,
1+1, SMS
System Output Voltage RMS C-A
30261
—
1
—
VAC
N+1, 1+N,
1+1, SMS
System Output Voltage RMS C-N
30262
—
1
—
VAC
N+1, 1+N,
1+1, SMS
System Output RMS Current Phs C
30264
—
1
—
A AC
N+1, 1+N,
1+1, SMS
System Output Pct Power Phase C
30265
—
1
—
%
N+1, 1+N,
1+1, SMS
System Output Power Factor Phs C
30266
—
1
100
—
N+1, 1+N,
1+1, SMS
Battery Discharge Time
30309
—
1
—
sec
N+1, 1+N,
1+1, SMS
Battery Amp-Hours Consumed This
Discharge
30310
—
1
—
AH
N+1, 1+N,
1+1, SMS
Input Qualification Status
30312
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
N+1, 1+N,
1+1, SMS
Bypass Sync Phase Difference
30313
—
1
—
deg
SCC, 1+N,
1+1, SMS
Bypass SS Overload Time Remain
30314
—
1
—
sec
SCC, 1+N,
1+1, SMS
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
307
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
Bypass Qualification Status
30315
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
SCC, 1+N,
1+1, SMS
Battery Total Discharge Time
30316
—
1
—
hr
N+1, 1+N,
1+1, SMS
Battery Discharge Power
30317
—
1
—
W
N+1, 1+N,
1+1, SMS
Battery Last Discharge Date
30318
—
2
—
Masks:
Year 0xFFFF 0000
Mon 0x0000 FF00
Day 0x0000 00FF
N+1, 1+N,
1+1, SMS
Battery Last Discharge Date
30320
—
2
—
Masks:
Hour 0xFF00 0000
Min 0x00FF 0000
Sec 0x0000 FF00
N+1, 1+N,
1+1, SMS
Battery Commission Date
30322
—
2
—
Masks: Year
0xFFFF 0000
Mon 0x0000 FF00
Day 0x0000 00FF
N+1, 1+N,
1+1, SMS
Battery Commission Date
30324
—
2
—
Masks:
Hour 0xFF00 0000
Min 0x00FF 0000
Sec 0x0000 FF00
N+1, 1+N,
1+1, SMS
DC Bus Voltage
30326
—
1
—
VDC
N+1, 1+N,
1+1, SMS
DC Bus Current
30327
—
1
—
A DC
N+1, 1+N,
1+1, SMS
DC Bus Qualification Status
30328
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
N+1, 1+N,
1+1, SMS
System Output Pct Pwr (VA) Phs A
30329
—
1
—
%
N+1, 1+N,
1+1, SMS
System Output Pct Pwr (VA) Phs B
30330
—
1
—
%
N+1, 1+N,
1+1, SMS
System Output Pct Pwr (VA) Phs C
30331
—
1
—
%
N+1, 1+N,
1+1, SMS
Output Qualification Status
30332
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
N+1, 1+N,
1+1, SMS
Inverter Overload Time Remaining
30333
—
1
—
sec
N+1, 1+N,
1+1, SMS
Inverter Output Qualification Status
30334
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
N+1, 1+N,
1+1, SMS
Total System Operating Time
30335
—
2
—
hr
SCC, N+1,
1+N, 1+1,
SMS
—
0 = 6 Pulse
1 = 12 Pulse
2 = 18 Pulse
3 = 24 Pulse
N+1, 1+N,
1+1, SMS
Rectifier Pulse Count
30337
—
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
308
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
Rectifier Input Passive Filter
30338
—
1
—
0 = Not Installed
1 = Installed
N+1, 1+N,
1+1, SMS
Rectifier Passive Filter Switch
30339
—
1
—
0 = Not Installed
1 = Installed
N+1, 1+N,
1+1, SMS
Rectifier Active Filter
30340
—
1
—
0 = Not Installed
1 = Installed
N+1, 1+N,
1+1, SMS
Rectifier Status
30341
—
1
—
0 = off
1 = on
N+1, 1+N,
1+1, SMS
—
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
SCC, N+1,
1+N, 1+1,
SMS
—
0 = Single Module System
1 = Module (1 + 1)
2 = Module (1 + N)
3 = Module (N + 1)
4 = System Control Cabinet
5 = Main Static Switch
SCC, N+1,
1+N, 1+1,
SMS
SCC, 1+N,
1+1, SMS
System Status
UPS Module Type
30342
30343
—
—
1
1
Static Switch Type
30344
—
1
—
0 = Not Applicable
1 = Continuous
Duty
2 = Momentary
Duty
System Input Power Source
30345
—
1
—
0 = None
1 = Utility (mains)
2 = Generator
SCC, N+1,
1+N, 1+1,
SMS
Output Real Power Rating
30346
—
2
—
kW
SCC, N+1,
1+N, 1+1,
SMS
Input Isolation Transformer
30348
—
1
—
0 = Not Installed
1 = Installed
SCC, N+1,
1+N, 1+1,
SMS
System Output Maximum Amp
Rating
30350
—
1
—
A AC
SCC, 1+N,
1+1
SCC, N+1,
1+N, 1+1,
SMS
Output Wire Configuration
30353
—
1
—
0 = Two Wire (single phase
+ return)
1 = Two Wire
(2 phase, no neutral)
2 = Three Wire
(2 phase + neutral)
3 = Three Wire (3-phase,
no neutral)
4 = Four Wire
(3 phases + neutral)
Battery Cell Count - Lead Acid
30354
—
1
—
—
SCC, N+1,
1+N, 1+1,
SMS
Battery Cell Count-Nickel Cadmium
30355
—
1
—
—
SCC, N+1,
1+N, 1+1,
SMS
SCC, 1+N,
1+1, SMS
SCC, 1+N,
1+1, SMS
UPS System Output Source
30356
—
1
—
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
Static Bypass Switch
30357
—
1
—
0 = off 1 = on
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
309
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
Battery Volts for Cabinet 1
30358
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 2
30359
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 3
30360
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 4
30361
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 5
30362
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 6
30363
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 7
30364
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 8
30365
—
1
—
VDC
N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 1
30366
—
1
—
deg C
N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 2
30367
—
1
—
deg C
N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 3
30368
—
1
—
deg C
N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 4
30369
—
1
—
deg C
N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 5
30370
—
1
—
deg C
N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 6
30371
—
1
—
deg C
N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 7
30372
—
1
—
deg C
N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 8
30373
—
1
—
deg C
N+1, 1+N,
1+1, SMS
Backfeed Breaker
30374
—
1
—
0 = Open
1 = Close
2 = Not Installed
N+1, 1+N,
1+1, SMS
SBS Load Disconnect
30375
—
1
—
0 = Open
1 = Close
2 = Not Installed
Deprecated
Input Breaker (CB1/RIB)
30376
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, N+1,
1+N, 1+1,
SMS
Trap Filter Disconnect
30377
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, N+1,
1+N, 1+1,
SMS
Output Breaker (CB2/IOB)
30378
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, N+1,
1+N, 1+1,
SMS
Internal Bypass Breaker (CB3)
30379
—
1
—
0 = Open
1 = Close
2 = Not Installed
Deprecated
Bypass Isolation Breaker (BIB)
30380
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, 1+N,
1+1, SMS
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
310
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
Rectifier Feed Breaker (RFB)
30381
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS
Maintenance Bypass Breaker
(MBB)
30382
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, 1+N,
1+1, SMS
Maintenance Isolation Breaker
(MIB)
30383
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, 1+N,
1+1, SMS
Output Series Static Switch
30384
—
1
—
0 = Open
1 = Close
2 = Not Installed
LEU/LAP
only
Module Output Breaker (MOB)
30385
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, 1+N,
1+1
Battery Amp-Hours Consumed
30386
—
2
—
AH
N+1, 1+N,
1+1, SMS
Auto Retransfer Time Remaining
30388
—
1
—
sec
SCC, 1+N,
1+1, SMS
Inverter On/Off State
30389
—
1
—
0 = off
1 = on
SCC, N+1,
1+N, 1+1,
SMS
UPS Battery Status
30390
—
1
—
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
N+1, 1+N,
1+1, SMS
SCC, 1+N,
1+1, SMS
UPS Output Source
30391
—
1
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Date and Time
39998
49998
2
—
—
SCC, N+1,
1+N, 1+1,
SMS
Total kW Hours Saved
30491
—
2
—
Units : kWH
SCC, N+1,
1+N, 1+1,
SMS
System Date and Time
39998
49998
2
—
Secs since
Epoch(UTC)
SCC, N+1,
1+N, 1+1,
SMS
Environment
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
311
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
NXL
Types
Scale
Units / Notes
—
0 = Two Wire
(single phase
+ return)
1 = Two Wire
(2 phase,
no neutral)
2 = Three Wire
(2 phase
+ neutral)
3 = Three Wire
(3 phase,
no neutral)
4 = Four Wire
(3 phases
+ neutral)
SCC, 1+N,
1+1, SMS
SCC, N+1,
1+N,
1+1, SMS
System
Bypass Input Wire Configuration
30496
—
1
Configuration Description
30497
—
1
—
0 = Single Module System 33
1 = Single Module System 34
2 = Single Module System 44
3 = 1+1 33
4 = 1+1 34
5 = 1+1 44
6 = 1+N 33 7 = 1+N 34
8 = 1+N 44
9 = N+1 33
10 = N+1 34
11 = N+1 44
12 = SCC w/Continuous Duty SS 33
13 = SCC w/
Continuous Duty
SS 44
14 = SCC w/
Momentary
Duty SS
15 = Main Static
Switch
System Accumulated Energy
30810
40810
2
10
Units: kWH
SCC, 1+N,
N+1
Module Accumulated Energy
30812
40812
10
Units: kWH
SMS, 1+N,
N+1, SCC
Output kWh Reset Timestamp
30814
—
—
Secs since Epoch(UTC)
SMS, 1+N,
N+1, SCC
Output Peak kW Demand
30816
—
—
Units: kWH
SMS, 1+N,
N+1, SCC
Output Peak kW Demand Hist
30817
—
—
Units: kW
SMS, 1+N,
N+1, SCC
SMS, 1+N,
N+1, SCC
2
1
Peak kW Demand Period
30818
—
1
—
1 = Hourly
2 = Daily
3 = Weekly
4 = Monthly
5 = Yearly
Peak kW Demand Timestamp
30819
—
2
—
Secs since Epoch(UTC)
SMS, 1+N,
N+1, SCC
30501
—
1
—
—
SCC, 1+N,
1+1, SMS
Ratings
System UPS Module Count
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
312
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
MultiModule
Multi-module System Output
Voltage RMS A-B
30505
—
1
—
Units : VAC
1+N, SCC
Multi-module System Output
Voltage RMS B-C
30506
—
1
—
Units : VAC
1+N, SCC
Multi-module System Output
Voltage RMS C-A
30507
—
1
—
Units : VAC
1+N, SCC
Multi-module System Output
Voltage RMS A-N
30508
—
1
—
Units : VAC
1+N, SCC
Multi-module System Output
Voltage RMS B-N
30509
—
1
—
Units : VAC
1+N, SCC
Multi-module System Output
Voltage RMS C-N
30510
—
1
—
Units : VAC
1+N, SCC
Sum of MMS Output RMS Currents
for Phase A
30511
—
1
—
Units : A AC
1+N, SCC
Sum of MMS Output RMS Currents
for Phase B
30512
—
1
—
Units : A AC
1+N, SCC
Sum of MMS Output RMS Currents
for Phase C
30513
—
1
—
Units : A AC
1+N, SCC
MMS Output Frequency
30514
—
1
10
Units : Hz
1+N, SCC
MMS Output Power
30515
—
1
—
Units : kW
1+N, SCC
MMS Output Apparent Power
30516
—
1
—
Units : kVA
1+N, SCC
MMS Output Power Factor
Phase A
30517
—
1
100
—
1+N, SCC
MMS Output Power Factor
Phase B
30518
—
1
100
—
1+N, SCC
MMS Output Power Factor
Phase C
30519
—
1
100
—
1+N, SCC
MMS Output Pct Power Phase A
30520
—
1
—
Units : %
1+N, SCC
MMS Output Pct Power Phase B
30521
—
1
—
Units : %
1+N, SCC
MMS Output Pct Power Phase C
30522
—
1
—
Units : %
1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase A
30523
—
1
—
Units : %
1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase B
30524
—
1
—
Units : %
1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase C
30525
—
1
—
Units : %
1+N, SCC
Number of Redundant Modules
30526
—
1
—
—
1+N, SCC
MMS Module Number
30527
—
1
—
—
1+N, SCC
Number of Modules in an MMS
30528
—
1
—
—
1+N, SCC
Module Output Breaker for
Module 1 (MOB1)
30529
—
1
—
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 2 (MOB2)
30530
—
1
—
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 3 (MOB3)
30531
—
1
—
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
313
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
Module Output Breaker for
Module 4 (MOB4)
30532
—
1
—
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 5 (MOB5)
30533
—
1
—
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 6 (MOB6)
30534
—
1
—
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 7 (MOB7)
30535
—
1
—
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 8 (MOB8)
30536
—
1
—
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Bypass Isolation Breaker for
Module 1 (BIB1)
30537
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS,
1+N
Bypass Isolation Breaker for
Module 2 (BIB2)
30538
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS,
1+N
Bypass Isolation Breaker for
Module 3 (BIB3)
30539
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS,
1+N
Bypass Isolation Breaker for
Module 4 (BIB4)
30540
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS,
1+N
Bypass Isolation Breaker for
Module 5 (BIB5)
30541
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS,
1+N
Bypass Isolation Breaker for
Module 6 (BIB6)
30542
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS,
1+N
Bypass Isolation Breaker for
Module 7 (BIB7)
30543
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS,
1+N
Bypass Isolation Breaker for
Module 8 (BIB8)
30544
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC, SMS,
1+N
System Output Breaker (UOB)
30545
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC
System Load Bank Breaker (LBB)
30546
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC
System Isolation Output Breaker
(IOB)
30547
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC
SCC Event Summary
30548
—
1
—
0 = None
1 = Alarm
2 = Fault
SCC
—
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
SCC, N+1,
1+N,
MMS UPS Battery Status
30549
—
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
314
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
NXL
Types
Scale
Units / Notes
SCC, 1+N,
30550
—
1
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
MMS Inter-Module Comm
Status
30554
—
1
—
0 = Failed
1 = Normal
1+N, SCC
MMS Event Summary
30555
—
1
—
0 = None
1 = Alarm
2 = Fault
1+N, SCC
MMS Module Inverter Status
30556
—
1
—
0 = off
1 = on
SCC, 1+N
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
1+N, SCC
1+N, SCC
MMS UPS Output Source
ModuleList 1
MMS Module Output Voltage
Status
30557
—
1
MMS Module Output Source
30558
—
1
—
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
MMS Module Total kW Output
30559
—
1
—
Units : kW
SCC
MMS Module Total kVA Output
30560
—
1
—
Units : kVA
SCC
MMS Module DC Bus Voltage
30561
—
1
—
Units : VDC
SCC
MMS Module Battery Current
30562
—
1
—
Units : A DC
SCC
MMS Module Battery Time
Remaining
30563
—
1
—
Units : min
SCC
MMS Inter-Module Comm
Status
30567
—
1
—
0 = Failed
1 = Normal
1+N, SCC
MMS Event Summary
30568
—
1
—
0 = None
1 = Alarm
2 = Fault
1+N, SCC
MMS Module Inverter Status
30569
—
1
—
0 = off 1 = on
1+N, SCC
MMS Module Output Voltage Status
30570
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
1+N, SCC
MMS Module Output Source
30571
—
1
—
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
1+N, SCC
MMS Module Total kW Output
30572
—
1
—
Units : kW
SCC
MMS Module Total kVA Output
30573
—
1
—
Units : kVA
SCC
MMS Module DC Bus Voltage
30574
—
1
—
Units : VDC
SCC
MMS Module Battery Current
30575
—
1
—
Units : A DC
SCC
MMS Module Battery Time
Remaining
30576
—
1
—
Units : min
SCC
ModuleList 2
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
315
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
ModuleList 8
MMS Inter-Module Comm
Status
30645
—
1
—
0 = Failed
1 = Normal
1+N, SCC
MMS Event Summary
30646
—
1
—
0 = None
1 = Alarm
2 = Fault
1+N, SCC
MMS Module Inverter Status
30647
—
1
—
0 = off 1 = on
1+N, SCC
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
1+N, SCC
1+N, SCC
MMS Module Output Voltage
Status
30648
—
1
MMS Module Output Source
30649
—
1
—
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
MMS Module Total kW Output
30650
—
1
—
Units : kW
SCC
MMS Module Total kVA Output
30651
—
1
—
Units : kVA
SCC
MMS Module DC Bus Voltage
30652
—
1
—
Units : VDC
SCC
MMS Module Battery Current
30653
—
1
—
Units : A DC
SCC
MMS Module Battery Time
Remaining
30654
—
1
—
Units : min
SCC
Intelligent Parallel Operation
State
30658
—
1
—
0 = disabled
1 = enabled
N+1, 1+N,
SCC
Intelligent Parallel Mode
30659
—
1
—
1 = Disconnect
(More Efficient)
N+1,
1+N,
SCC
Intelligent Paralleling Shutdown
Delay
30660
—
1
—
Units : min
N+1, 1+N,
SCC
Intelligent Parallel Minimum
Redundancy
30661
—
1
—
—
N+1, 1+N,
SCC
Intelligent Parallel Maximum
Time in Standby
30662
—
1
—
Units : day
N+1, 1+N,
SCC
ECO Mode Operation State
30666
40666
1
—
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Continuous Operation - ECO Mode
30667
—
1
—
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Maximum Auto Suspensions - ECO
Mode
30668
—
1
—
—
SMS, 1+N,
SCC
Restart Delay - ECO Mode
30669
—
1
—
Units : min
SMS, 1+N,
SCC
Time Remaining - ECO Mode
30670
—
1
—
Units : min
SMS, 1+N,
SCC
Intelligent Paralleling
ECO Mode
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
316
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued)
Data Label
Input
Holding # of
Register Register Regs
Scale
Units / Notes
NXL
Types
EcoModeSchedule 1
Schedule Operation State - ECO
Mode
30674
—
1
—
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode
30675
—
1
—
0 = stop
1 = start
SMS, 1+N,
SCC
SMS, 1+N,
SCC
Schedule Day of Week - ECO
Mode
30676
—
1
—
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode
30677
—
1
—
Units : hr
SMS, 1+N,
SCC
Schedule Minute - ECO Mode
30678
—
1
—
Units : min
SMS, 1+N,
SCC
Schedule Operation State - ECO
Mode
30682
—
1
—
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode
30683
—
1
—
0 = stop
1 = start
SMS, 1+N,
SCC
SMS, 1+N,
SCC
EcoModeSchedule 2
Schedule Day of Week - ECO
Mode
30684
—
1
—
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode
30685
—
1
—
Units : hr
SMS, 1+N,
SCC
Schedule Minute - ECO Mode
30686
—
1
—
Units : min
SMS, 1+N,
SCC
Schedule Operation State - ECO
Mode
30794
—
1
—
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode
30795
—
1
—
0 = stop
1 = start
SMS, 1+N,
SCC
SMS, 1+N,
SCC
EcoModeSchedule 16
Schedule Day of Week - ECO
Mode
30796
—
1
—
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode
30797
—
1
—
Units : hr
SMS, 1+N,
SCC
Schedule Minute - ECO Mode
30798
—
1
—
Units : min
SMS, 1+N,
SCC
30821
—
1
—
—
SMS, 1+N,
N+1
Battery
Total Number of Battery Discharges
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
317
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary
Data Label
Data Description
Auto Restart In Progress
Auto restart is in progress
Auto Restart Inhibited - Ext
Auto restart inhibited due to an external signal
Auto Retransfer Time Remaining
Time remaining before an inverter overload or inverter fault can be cleared
and auto retransfer from the bypass to the inverter can take place
Automatic Restart Failed
Automatic restart failed
Backfeed Breaker Open
The backfeed breaker is in the open position
Backfeed Breaker
Backfeed breaker
Battery - External Monitor 1
External battery monitor 1 - battery maintenance required
Battery - External Monitor 2
External battery monitor 2 - battery maintenance required
Battery Amp-Hours Consumed This Discharge
Battery amp-hours withdrawn this discharge.
Battery Amp-Hours Consumed
Cumulative battery amp-hours withdrawn over the life of the battery
Battery Capacity Low
Battery capacity is low
Battery Cell Count - Lead Acid
Battery cell count - lead acid
Battery Cell Count-Nickel Cadmium
Battery cell count - nickel cadmium
Battery Charging Inhibited
Battery charging is inhibited due to an external inhibit signal
Battery Charging Reduced-Extrnl
Using a reduced battery charging algorithm due to an external signal
Battery Circuit Breaker 1 Open
Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open
Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open
Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open
Battery circuit breaker 4 is open
Battery Circuit Breaker 5 Open
Battery circuit breaker 5 is open
Battery Circuit Breaker 6 Open
Battery circuit breaker 6 is open
Battery Circuit Breaker 7 Open
Battery circuit breaker 7 is open
Battery Circuit Breaker 8 Open
Battery circuit breaker 8 is open
Battery Commission Date
Date and time when battery placed into service
Battery Discharge Power
Instantaneous battery power while discharging
Battery Discharge Time
The time on battery operation for this discharge
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage
level.
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Last Discharge Date
The date and time of the last battery discharge
Battery Low Shutdown
Battery disconnect due to end-of-discharge.
Battery Low
The calculated battery time remaining has reached the low battery
threshold
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Percentage Charge
The percentage of battery charge
Battery Self Test
Battery self test is in progress
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Temperature Imbalance
Excessive temperature differences between battery sensors detected
Battery Temperature Sensor Fault
A battery temperature sensor fault has been detected
Battery Test Failed
Battery test failed
Battery Test Inhibited
Automatic (scheduled) battery tests are inhibited
Battery Time Remaining
The calculated available time on battery
Battery Total Discharge Time
The cumulative battery discharge time
Battery Volts at Main Disconnect
The voltage between the positive and the negative battery terminals of the
common battery disconnect
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
318
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary (continued)
Data Label
Data Description
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a
battery cabinet
Bypass - Excess Auto Retransfers
The number of auto retransfers, from bypass to inverter, has exceeded the
maximum for a specified time interval
Bypass - Manual Rexfr Inhibited
Manual transfer from bypass to inverter is inhibited.
Bypass - Manual Xfr Inhibited
Manual transfer from inverter to bypass is inhibited.
Bypass Auto Retransfer Failed
After performing a recoverable transfer to bypass, an attempt to auto
retransfer from bypass to inverter failed
Bypass Auto Transfer Failed
An automatic transfer to static bypass failed
Bypass Excessive Pulse Parallel
The system has performed too many pulse parallel operations within a
specified time interval
Bypass Frequency Error
The bypass frequency is outside the inverter synchronization limits
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage RMS A-B
The bypass input RMS voltage between phases A and B
Bypass Input Voltage RMS B-C
The bypass input RMS voltage between phases B and C
Bypass Input Voltage RMS C-A
The bypass input RMS voltage between phases C and A
Bypass Isolation Breaker (BIB)
Bypass isolation breaker (BIB)
Bypass Nominal Voltage
Bypass nominal (or rated) voltage
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Overload Phase A
An overload exists on output phase A while operating on the bypass
Bypass Overload Phase B
An overload exists on output phase B while operating on the bypass
Bypass Overload Phase C
An overload exists on output phase C while operating on the bypass
Bypass Qualification Status
bypass qualification status
Bypass SS Overload Time Remain
The calculated time remaining before bypass static switch shutdown due to
the present overload condition
Bypass Static Switch Off Extrnl
Bypass static switch is off due to the state of an external signal
Bypass Static Switch Overload
Bypass off due to static switch overload
Bypass Static Switch Unavailable
The static bypass switch is off, and unable to operate
Bypass Sync Phase Difference
The phase angle difference between the inverter output and bypass source
Controls Reset Required
A controls reset is required due to one or more critical settings changing
DC Bus Current
The current at the battery input terminals. In charging mode, the current will
be a positive value. In discharging mode, the current will be a negative
value
DC Bus Ground Fault - Negative
A ground fault has been detected on the negative DC Bus link
DC Bus Ground Fault - Positive
A ground fault has been detected on the positive DC Bus link
DC Bus Qualification Status
DC bus qualification status
DC Bus Voltage
The voltage between the positive and negative terminals of the DC bus at
the battery input
Equipment Over Temperature
Equipment over temperature summary event
Equipment Temperature Sensor Fail
One or more temperature sensors report a temperature outside of the
range of expected operation.
Fuse Failure
A summary event indicating one or more fuse failures
Inlet Air Over Temperature
The inlet air exceeds the maximum temperature threshold
Inlet Air Temperature
The temperature of the inlet air
Input Breaker (CB1/RIB)
Input breaker (CB1/RIB)
Input Contact 01
The external input contact 1
Input Contact 02
The external input contact 2
Input Contact 03
The external input contact 3
Input Contact 04
The external input contact 4
319
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary (continued)
Data Label
Data Description
Input Contact 05
The external input contact 5
Input Contact 06
The external input contact 6
Input Contact 07
The external input contact 7
Input Contact 08
The external input contact 8
Input Contact 09
The external input contact 9
Input Contact 10
The external input contact 10
Input Contact 11
The external input contact 11
Input Contact 12
The external input contact 12
Input Contact 13
The external input contact 13
Input Contact 14
The external input contact 14
Input Contact 15
The external input contact 15
Input Contact 16
The external input contact 16
Input Filter Cycle Lock
The input filter disconnect is open due to exceeding the maximum number
of cycles.
Input Isolation Transformer
Input isolation transformer
Input Qualification Status
input qualification status
Internal Bypass Breaker (CB3)
Internal bypass breaker (CB3)
Internal Communications Failure
The control has detected a communication failure of a component on the
internal communication bus
Inverter Failure
Inverter failure - inverter output is off
Inverter Inhibit - External
Restart of the inverter is inhibited by an external signal
Inverter Off - External
Inverter is off (operation is inhibited) due to external signal state
Inverter On/Off State
inverter on/off state
Inverter Output Qualification Status
inverter output qualification status
Inverter Overload Phase A
Inverter is operating with an overload on phase A
Inverter Overload Phase B
Inverter is operating with an overload on phase B
Inverter Overload Phase C
Inverter is operating with an overload on phase C
Inverter Overload Time Remaining
The calculated time remaining before inverter shutdown
Inverter Shutdown - Overload
The inverter has shutdown due to a sustained overload
Inverter Static Switch SCR Short
The system has detected a short across one or more inverter static switch
Silicon Controlled Rectifiers (SCR)
LBS Inhibited
The system has detected that conditions to perform Load Bus Sync are not
satisfied
Leading Power Factor
The leading output Power Factor has fallen below a specified value
Main Battery Disconnect Open
Main battery disconnect is open
Main Controller Fault
A Main Controller fault has been detected.
Maintenance Bypass Breaker (MBB)
Maintenance bypass breaker (MBB)
Maintenance Isolation Breaker (MIB)
Maintenance isolation breaker (MIB)
Module Output Breaker (MOB)
Module output breaker (MOB)
Multiple Fan Failure
Multiple fan failure
On Generator
A generator is supplying the power to the system
Output Amp Over User Limit-Phs A
The phase A output has exceeded the user amperage threshold
Output Amp Over User Limit-Phs B
The phase B output has exceeded the user amperage threshold
Output Amp Over User Limit-Phs C
The phase C output has exceeded the user amperage threshold
Output Apparent Power Rating
Output apparent power rating
Output Breaker (CB2/IOB)
Output breaker (CB2/IOB)
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Output Qualification Status
output qualification status
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
320
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary (continued)
Data Label
Data Description
Output Real Power Rating
Output real power rating
Output Series Static Switch
output series static switch
Output Wire Configuration
Output wire configuration
Power Supply Failure
Power supply failure
Rectifier Active Filter
Rectifier input active filter configuration
Rectifier Failure
Rectifier failure - rectifier is off
Rectifier Feed Breaker (RFB)
Rectifier feed breaker (RFB)
Rectifier Input Passive Filter
Rectifier input passive filter configuration
Rectifier Operation Inhibit-Ext
The operation of the rectifier is inhibited by an external signal
Rectifier Passive Filter Switch
Rectifier input passive filter switch configuration
Rectifier Pulse Count
Rectifier pulse count per cycle configuration
Rectifier Status
rectifier status
SBS Load Disconnect
SBS load disconnect
Service Code Active
Service code is running
Static Bypass Switch
Static Bypass Switch state - On/Off
Static Switch Type
Static switch type configuration
System Breaker(s) Close Failure
One or more breakers in the system failed to close
System Breaker(s) Open Failure
One or more breakers in the system failed to open
System Controller Error
System controller internal error
System Date and Time
The system date and time
System Fan Failure - Redundant
Redundant system fan failure
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Current Limit
The RMS input current has reached the input current limit threshold
System Input Frequency
The system input frequency
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the
sequence preferred for the rectifier (A-B-C)
System Input Power Problem
The input is not qualified to provide power to the system
System Input Power Source
System input power source
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Low Power Factor
The system output power factor is low, resulting in reduced output capacity
System Output Maximum Amp Rating
System output maximum amperage rating
System Output Nominal Frequency
The nominal (or rated) system output frequency
System Output Nominal Voltage
The nominal (or rated) system output voltage
System Output Off
The system output is off
System Output Pct Power Phase A
The system output power on phase A as a percentage of the rated capacity
System Output Pct Power Phase B
The system output power on phase B as a percentage of the rated capacity
System Output Pct Power Phase C
The system output power on phase C as a percentage of the rated capacity
321
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary (continued)
Data Label
Data Description
System Output Pct Pwr (VA) Phs A
The system output apparent power on phase A as a percentage of the
rated capacity
System Output Pct Pwr (VA) Phs B
The system output apparent power on phase B as a percentage of the
rated capacity
System Output Pct Pwr (VA) Phs C
The system output apparent power on phase C as a percentage of the
rated capacity
System Output Power Factor Phs A
The system output power factor of phase A
System Output Power Factor Phs B
The system output power factor of phase B
System Output Power Factor Phs C
The system output power factor of phase C
System Output Power
The sum total power of all system output phases
System Output RMS Current Phs A
The system output RMS current for Phase A
System Output RMS Current Phs B
The system output RMS current for Phase B
System Output RMS Current Phs C
The system output RMS current for Phase C
System Output Voltage RMS A-B
The system output RMS voltage between phases A and B
System Output Voltage RMS A-N
The system output RMS voltage between phases A and Neutral
System Output Voltage RMS B-C
The system output RMS voltage between phases B and C
System Output Voltage RMS B-N
The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A
The system output RMS voltage between phases C and A
System Output Voltage RMS C-N
The system output RMS voltage between phases C and Neutral
System Shutdown - EPO
System shutdown due to Emergency Power Off (EPO)
System Shutdown - REPO
System shutdown due to Remote Emergency Power Off (REPO)
System Status
The operating status for the system
Total System Operating Time
The cumulative operation time of the unit
Trap Filter Disconnect
Trap filter disconnect
UPS Battery Status
UPS battery status
UPS Module Type
UPS module type
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
UPS System Output Source
The UPS system's output power source
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
322
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-79 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil
Status
Data Description
Coil
Number
of Bits
Notes / Units
Input
System Input Power Problem
10001
—
1
Active on Alarm
System Input Phs Rotation Error
10002
—
1
Active on Alarm
System Input Current Limit
10003
—
1
Active on Alarm
System Input Current Imbalance
10004
—
1
Active on Alarm
Bypass Not Available
10015
—
1
Active on Alarm
Bypass Overload Phase A
10016
—
1
Active on Alarm
Bypass Overload Phase B
10017
—
1
Active on Alarm
Bypass Overload Phase C
10018
—
1
Active on Alarm
Bypass Auto Retransfer Failed
10019
—
1
Active on Alarm
Bypass Static Switch Overload
10020
—
1
Active on Alarm
Bypass Static Switch Unavailable
10021
—
1
Active on Alarm
Bypass Auto Transfer Failed
10022
—
1
Active on Alarm
Bypass Frequency Error
10023
—
1
Active on Alarm
Bypass
Bypass - Manual Rexfr Inhibited
10024
—
1
Active on Alarm
Bypass - Manual Xfr Inhibited
10025
—
1
Active on Alarm
Battery Automatic Test Inhibited
10036
—
1
Active on Alarm
Battery Capacity Low
10037
—
1
Active on Alarm
Battery Discharging
10038
—
1
Active on Alarm
Battery
Battery Temperature Imbalance
10039
—
1
Active on Alarm
Battery Equalize
10040
—
1
Active on Alarm
Battery Auto Test In Progress
10041
—
1
Active on Alarm
Main Battery Disconnect Open
10042
—
1
Active on Alarm
Battery Low
10043
—
1
Active on Alarm
Battery Temperature Sensor Fault
10044
—
1
Active on Alarm
Battery Circuit Breaker 1 Open
10045
—
1
Active on Alarm
Battery Circuit Breaker 2 Open
10046
—
1
Active on Alarm
Battery Circuit Breaker 3 Open
10047
—
1
Active on Alarm
Battery Circuit Breaker 4 Open
10048
—
1
Active on Alarm
Battery Circuit Breaker 5 Open
10049
—
1
Active on Alarm
Battery Circuit Breaker 6 Open
10050
—
1
Active on Alarm
Battery - External Monitor 1
10051
—
1
Active on Alarm
Battery - External Monitor 2
10052
—
1
Active on Alarm
Battery Ground Fault
10053
—
1
Active on Alarm
Battery Over Temperature Limit
10054
—
1
Active on Alarm
Battery Low Shutdown
10055
—
1
Active on Alarm
Battery Over Temperature
10056
—
1
Active on Alarm
Battery Test Failed
10057
—
1
Active on Alarm
Unexpected Main Battery Disconnect Closure
10058
—
1
Active on Alarm
Battery Over Voltage
10059
—
1
Active on Alarm
Battery Fuse Fault
10060
—
1
Active on Alarm
Main Battery Disconnect Forced To Unlock
10061
—
1
Active on Alarm
Battery Test Manually Stopped
10062
—
1
Active on Alarm
Battery Test Passed
10063
—
1
Active on Alarm
323
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-79 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil (continued)
Status
Coil
Number
of Bits
Notes / Units
10074
—
1
Active on Alarm
System Shutdown - EPO
10085
—
1
Active on Alarm
System Shutdown - REPO
10086
—
1
Active on Alarm
System Output Low Power Factor
10088
—
1
Active on Alarm
Output Amp Over User Limit-Phs A
10089
—
1
Active on Alarm
Data Description
DC Bus
DC Bus Low Fault
Output
Output Amp Over User Limit-Phs B
10090
—
1
Active on Alarm
Output Amp Over User Limit-Phs C
10091
—
1
Active on Alarm
System Output Fault
10092
—
1
Active on Alarm
Output Of/Uf
10093
—
1
Active on Alarm
Inverter Failure
10104
—
1
Active on Alarm
Inverter Overload Phase A
10105
—
1
Active on Alarm
Inverter Overload Phase B
10106
—
1
Active on Alarm
Inverter
Inverter Overload Phase C
10107
—
1
Active on Alarm
Inverter Inhibit - External
10108
—
1
Active on Alarm
Inverter Shutdown - Overload
10109
—
1
Active on Alarm
Inverter Static Switch SCR Short
10110
—
1
Active on Alarm
10121
—
1
Active on Alarm
Environment
Inlet Air Over Temperature
Outlet Air Overtemperature Limit
10122
—
1
Active on Alarm
Equipment Temperature Sensor Fail
10123
—
1
Active on Alarm
Input Contact 01
10134
—
1
Active on Alarm
Input Contact 02
10135
—
1
Active on Alarm
Input Contact 03
10136
—
1
Active on Alarm
Input Contact 04
10137
—
1
Active on Alarm
Input Contact 05
10138
—
1
Active on Alarm
Input Contact 06
10139
—
1
Active on Alarm
Input Contact 07
10140
—
1
Active on Alarm
Input Contact 08
10141
—
1
Active on Alarm
Input Contact 09
10142
—
1
Active on Alarm
Input Contact 10
10143
—
1
Active on Alarm
Input Contact 11
10144
—
1
Active on Alarm
Input Contact 12
10145
—
1
Active on Alarm
Input Contact 13
10146
—
1
Active on Alarm
Input Contact 14
10147
—
1
Active on Alarm
Input Contact 15
10148
—
1
Active on Alarm
Input Contact 16
10149
—
1
Active on Alarm
Rectifier Failure
10160
—
1
Active on Alarm
Vdc Backfeed
10162
—
1
Active on Alarm
Rectifier Configuration Change Request
10163
—
1
Active on Alarm
External Input Signals
Rectifier
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
324
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-79 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil (continued)
Status
Data Description
Coil
Number
of Bits
Notes / Units
System
System Fan Failure - Redundant
10174
—
1
Active on Alarm
Multiple Fan Failure
10175
—
1
Active on Alarm
Internal Communications Failure
10176
—
1
Active on Alarm
UPS Output on Bypass
10177
—
1
Active on Alarm
Output Load on Maint. Bypass
10178
—
1
Active on Alarm
Backfeed Breaker Open
10179
—
1
Active on Alarm
Auto Restart In Progress
10180
—
1
Active on Alarm
Power Supply Failure
10181
—
1
Active on Alarm
Auto Restart Inhibited - Ext
10183
—
1
Active on Alarm
Automatic Restart Failed
10184
—
1
Active on Alarm
Main Controller Fault
10185
—
1
Active on Alarm
Fuse Failure
10186
—
1
Active on Alarm
System Controller Error
10187
—
1
Active on Alarm
System Breaker(s) Open Failure
10188
—
1
Active on Alarm
System Breaker(s) Close Failure
10189
—
1
Active on Alarm
Input Filter Cycle Lock
10190
—
1
Active on Alarm
EMO Shutdown
10191
—
1
Active on Alarm
Service Code Active
10192
—
1
Active on Alarm
LBS Active
10193
—
1
Active on Alarm
LBS Inhibited
10194
—
1
Active on Alarm
Regeneration Active
10195
—
1
Active on Alarm
Regeneration Operation Terminated
10196
—
1
Active on Alarm
Regeneration Operation Failure
10197
—
1
Active on Alarm
Leading Power Factor
10198
—
1
Active on Alarm
Controls Reset Required
10199
—
1
Active on Alarm
Loss of Redundancy
10212
—
1
Active on Alarm
MMS Overload
10215
—
1
Active on Alarm
MMS On Battery
10216
—
1
Active on Alarm
MMS Module Alarm Active
10218
—
1
Active on Alarm
Program Input Contact 01
10229
—
1
Active on Alarm
Program Input Contact 02
10230
—
1
Active on Alarm
Program Input Contact 03
10231
—
1
Active on Alarm
Program Input Contact 04
10232
—
1
Active on Alarm
Program Input Contact 05
10233
—
1
Active on Alarm
Program Input Contact 06
10234
—
1
Active on Alarm
Program Input Contact 07
10235
—
1
Active on Alarm
Program Input Contact 08
10236
—
1
Active on Alarm
Program Input Contact 09
10237
—
1
Active on Alarm
Program Input Contact 10
10238
—
1
Active on Alarm
Program Input Contact 11
10239
—
1
Active on Alarm
Program Input Contact 12
10240
—
1
Active on Alarm
MultiModule
Program Input Signals
325
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-79 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil (continued)
Status
Coil
Number
of Bits
Notes / Units
10251
—
1
Active on Alarm
ECO Mode Active
10262
—
1
Active on Alarm
ECO Mode Suspended
10263
—
1
Active on Alarm
Excess ECO Suspends
10264
—
1
Active on Alarm
Data Description
Intelligent Paralleling
IP Inhibit
ECO Mode
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
326
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding
Input
Holding
# of Reg
Scale
Notes/Units
System Input RMS A-B
30385
—
1
10
Units : VAC
Uint16
System Input RMS B-C
30386
—
1
10
Units : VAC
Uint16
System Input RMS C-A
30387
—
1
10
Units : VAC
Uint16
System Input RMS Current Phase A
30388
—
1
—
Units : A AC
Uint16
System Input RMS Current Phase B
30389
—
1
—
Units : A AC
Uint16
System Input RMS Current Phase C
30390
—
1
—
Units : A AC
Uint16
System Input Frequency
30391
—
1
100
Units : Hz
Uint16
Data Label
Input
30392
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Bypass Input Voltage RMS A-B
30403
—
1
10
Units : VAC
Uint16
Bypass Input Voltage RMS B-C
30404
—
1
10
Units : VAC
Uint16
Bypass Input Voltage RMS C-A
30405
—
1
10
Units : VAC
Uint16
Bypass Input Frequency
30406
—
1
100
Units : Hz
Uint16
Bypass Sync Phase Difference
30407
—
1
—
Units : deg
Int16
Bypass SS Overload Time Remain
30408
—
1
—
Units : sec
Uint16
Static Bypass Switch
30409
—
1
—
0 = off
1 = on
Bypass Qualification Status
30410
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Auto Retransfer Time Remaining
30411
—
1
—
Units : sec
Uint16
Battery Total Discharge Time
30422
—
1
—
Units : hr
Uint16
Battery Percentage Charge
30423
—
1
—
Uint16
Battery Volts at Main Disconnect
30424
—
1
—
Units : VDC
Uint16
Battery Volts for Cabinet 1
30425
—
1
—
Units : VDC
Uint16
Battery Volts for Cabinet 2
30426
—
1
—
Units : VDC
Uint16
Battery Volts for Cabinet 3
30427
—
1
—
Units : VDC
Uint16
Input Qualification Status
Bypass
Battery
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
327
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Battery Volts for Cabinet 4
30428
—
1
—
Units : VDC
Uint16
Battery Volts for Cabinet 5
30429
—
1
—
Units : VDC
Uint16
Battery Volts for Cabinet 6
30430
—
1
—
Units : VDC
Uint16
Battery Temperature for Cabinet
30431
—
1
10
Units : deg C
Int16
Battery Temperature for Cabinet 1
30432
—
1
10
Units : deg F
Int16
Battery Temperature for Cabinet 2
30433
—
1
10
Units : deg C
Int16
Battery Temperature for Cabinet 2
30434
—
1
10
Units : deg F
Int16
Battery Temperature for Cabinet 3
30435
—
1
10
Units : deg C
Int16
Battery Temperature for Cabinet 3
30436
—
1
10
Units : deg F
Int16
Battery Temperature for Cabinet 4
30437
—
1
10
Units : deg C
Int16
Battery Temperature for Cabinet 4
30438
—
1
10
Units : deg F
Int16
Battery Temperature for Cabinet 5
30439
—
1
10
Units : deg C
Int16
Battery Temperature for Cabinet 5
30440
—
1
10
Units : deg F
Int16
Battery Temperature for Cabinet 6
30441
—
1
10
Units : deg C
Int16
Battery Temperature for Cabinet 6
30442
—
1
10
Units : deg F
Int16
Battery Amp-Hours Consumed This Discharge
30443
—
1
—
Units : AH
Uint16
Battery Time Remaining
30444
—
1
—
Units : min
Uint16
Battery Discharge Time
30445
—
1
—
Units : sec
Uint16
Battery Discharge Power
30446
—
1
—
Units : W
Uint16
Battery Last Discharge Date
30447
—
2
—
Secs since Epoch(UTC)
Battery Amp-Hours Consumed
30449
—
2
—
Units : AH
Uint32
UPS Battery Status
30451
—
1
—
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
The main battery disconnect status.
30452
—
1
—
0 = Open
1 = Closed
2 = Disabled
Battery SCR Status
30453
—
1
—
0 = OK
1 = Fault
2 = unknown
Main Battery Disconnect Switch Lock Status
30454
—
1
—
0 = Locked
1 = Unlocked
2 = unknown
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
328
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Input
Holding
# of Reg
Scale
Notes/Units
DC Bus Voltage
30465
—
1
—
Units : VDC
Uint16
DC Bus Current
30466
—
1
—
Units : A DC
Int16
Data Label
DC Bus
30467
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
System Output Voltage RMS A-B
30478
—
1
10
Units : VAC
Uint16
System Output Voltage RMS B-C
30479
—
1
10
Units : VAC
Uint16
System Output Voltage RMS C-A
30480
—
1
10
Units : VAC
Uint16
System Output Voltage RMS A-N
30481
—
1
10
Units : VAC
Uint16
System Output Voltage RMS B-N
30482
—
1
10
Units : VAC
Uint16
System Output Voltage RMS C-N
30483
—
1
10
Units : VAC
Uint16
System Output RMS Current Phs A
30484
—
1
—
Units : A AC
Uint16
System Output RMS Current Phs B
30485
—
1
—
Units : A AC
Uint16
System Output RMS Current Phs C
30486
—
1
—
Units : A AC
Uint16
System Output Frequency
30487
—
1
100
Units : Hz
Uint16
System Output Power
30488
—
1
—
Units : kW
Uint16
System Output Apparent Power
30489
—
1
—
Units : kVA
Uint16
DC Bus Qualification Status
Output
System Output Power Factor Phs A
30490
—
1
100
Uint16
System Output Power Factor Phs B
30491
—
1
100
Uint16
System Output Power Factor Phs C
30492
—
1
100
Uint16
System Output Pct Power Phase A
30493
—
1
—
Units : %
Uint16
System Output Pct Power Phase B
30494
—
1
—
Units : %
Uint16
System Output Pct Power Phase C
30495
—
1
—
Units : %
Uint16
System Output Pct Pwr (VA) Phs A
30496
—
1
—
Units : %
Uint16
System Output Pct Pwr (VA) Phs B
30497
—
1
—
Units : %
Uint16
System Output Pct Pwr (VA) Phs C
30498
—
1
—
Units : %
Uint16
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Output Qualification Status
30499
—
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
329
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
30510
—
1
—
Units : sec
Uint16
Inverter
Inverter Overload Time Remaining
Inverter Output Qualification Status
30511
—
1
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
Inverter On/Off State
30512
—
1
—
0 = off
1 = on
Inlet Air Temperature
30523
—
1
—
Units : deg C
Int16
Inlet Air Temperature
30524
—
1
—
Units : deg F
Int16
Total System Operating Time
30525
—
2
—
Units : hr
Uint32
System Date and Time
30527
40527
2
—
Secs since Epoch(UTC)
System Date and Time
39998
49998
2
—
Secs since Epoch(UTC)
Environment
Rectifier
Rectifier Pulse Count
30539
—
1
—
0 = 6 Pulse
1 = 12 Pulse
2 = 18 Pulse
3 = 24 Pulse
Rectifier Input Passive Filter
30540
—
1
—
0 = Not Installed
1 = Installed
Rectifier Passive Filter Switch
30541
—
1
—
0 = Not Installed
1 = Installed
Rectifier Active Filter
30542
—
1
—
0 = Not Installed
1 = Installed
Rectifier Status
30543
—
1
—
0 = off
1 = on
—
0 = Single Module System
1 = Module (1 + 1)
2 = Module (1 + N)
3 = Module (N + 1)
4 = System Control Cabinet
5 = Main Static Switch
—
0 = Two Wire (single phase +
return)
1 = Two Wire (2 phase, no
neutral)
2 = Three Wire (2 phase +
neutral)
3 = Three Wire (3 phase, no
neutral)
4 = Four Wire (3 phases +
neutral)
System
UPS Module Type
Bypass Input Wire Configuration
30554
30555
—
—
1
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
330
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Output Wire Configuration
30556
—
1
—
0 = Two Wire (single phase +
return)
1 = Two Wire (2 phase, no
neutral)
2 = Three Wire (2 phase +
neutral)
3 = Three Wire (3 phase, no
neutral)
4 = Four Wire (3 phases +
neutral)
Static Switch Type
30557
—
1
—
0 = Not Applicable
1 = Continuous Duty
2 = Momentary Duty
Configuration Description
30558
—
1
—
0 = Single Module System 33
1 = Single Module System 34
2 = Single Module System 44
3 = 1+1 33
4 = 1+1 34
5 = 1+1 44
6 = 1+N 33
7 = 1+N 34
8 = 1+N 44
9 = N+1 33
10 = N+1 34
11 = N+1 44
12 = SCC w/Continuous Duty
SS 33
13 = SCC w/Continuous Duty
SS 44
14 = SCC w/Momentary Duty
SS
15 = Main Static Switch
UPS System Output Source
30559
—
1
—
0 = None
1 = Inverter
2 = Bypass
System Input Power Source
30560
—
1
—
0 = None
1 = Utility (mains)
2 = Generator
—
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Status
30561
—
1
UPS Output Source
30562
—
1
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Fan Status
30563
—
1
—
0 = Unknown
1 = Normal
2 = Failure
System Fan Redundant Status
30564
—
1
—
0 = Unknown
1 = Redundancy Available
2 = Loss of Redundancy
System Fan Capacity Status
30565
—
1
—
0 = Unknown
1 = Normal
2 = Failure
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
331
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Input
Holding
# of Reg
Scale
Notes/Units
Bypass Nominal Voltage
30576
—
1
—
Units : VAC
Uint16
System Input Nominal Voltage
30577
—
1
—
Units : VAC
Uint16
System Input Nominal Frequency
30578
—
1
10
Units : Hz
Uint16
System Output Nominal Voltage
30579
—
1
—
Units : VAC
Uint16
System Output Nominal Frequency
30580
—
1
10
Units : Hz
Uint16
Battery Cell Count - Lead Acid
30581
—
1
—
Uint16
Battery Cell Count-Nickel Cadmium
30582
—
1
—
Uint16
Data Label
Ratings
Output Apparent Power Rating
30583
—
1
—
Units : kVA
Uint16
Output Real Power Rating
30584
—
1
—
Units : kW
Uint16
Input Isolation Transformer
30585
—
1
—
0 = Not Installed
1 = Installed
System UPS Module Count
30586
—
1
—
Uint16
System Output Maximum Amp Rating
30587
—
1
—
Units : A AC
Uint16
System Redundant UPS Modules
30588
—
1
—
Uint16
Backfeed Breaker
30599
—
1
—
0 = Open
1 = Close
2 = Not Installed
SBS Load Disconnect
30600
—
1
—
0 = Open
1 = Close
2 = Not Installed
Input Breaker
30601
—
1
—
0 = Open
1 = Close
2 = Not Installed
Trap Filter Disconnect
30602
—
1
—
0 = Open
1 = Close
2 = Not Installed
Output Breaker
30603
—
1
—
0 = Open
1 = Close
2 = Not Installed
Internal Bypass Breaker
30604
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker
30605
—
1
—
0 = Open
1 = Close
2 = Not Installed
Maintenance Bypass Breaker
30606
—
1
—
0 = Open
1 = Close
2 = Not Installed
Maintenance Isolation Breaker
30607
—
1
—
0 = Open
1 = Close
2 = Not Installed
Output Series Static Switch
30608
—
1
—
0 = Off
1 = On
2 = Not Installed
Device Status
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
332
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Module Output Breaker
30609
—
1
—
0 = Open
1 = Close
2 = Not Installed
Multi-module System Output Voltage RMS A-B
30620
—
1
10
Units : VAC
Uint16
Multi-module System Output Voltage RMS B-C
30621
—
1
10
Units : VAC
Uint16
Multi-module System Output Voltage RMS C-A
30622
—
1
10
Units : VAC
Uint16
Multi-module System Output Voltage RMS A-N
30623
—
1
10
Units : VAC
Uint16
Multi-module System Output Voltage RMS B-N
30624
—
1
10
Units : VAC
Uint16
Multi-module System Output Voltage RMS C-N
30625
—
1
10
Units : VAC
Uint16
Sum of MMS Output RMS Currents for Phase A
30626
—
1
—
Units : A AC
Uint16
Sum of MMS Output RMS Currents for Phase B
30627
—
1
—
Units : A AC
Uint16
Sum of MMS Output RMS Currents for Phase C
30628
—
1
—
Units : A AC
Uint16
MMS Output Frequency
30629
—
1
10
Units : Hz
Uint16
MMS Output Power
30630
—
1
—
Units : kW
Uint16
MMS Output Apparent Power
30631
—
1
—
Units : kVA
Uint16
MMS Output Power Factor Phase A
30632
—
1
100
Int16
MMS Output Power Factor Phase B
30633
—
1
100
Int16
MMS Output Power Factor Phase C
30634
—
1
100
Int16
MultiModule
MMS Output Pct Power Phase A
30635
—
1
—
Units : %
Int16
MMS Output Pct Power Phase B
30636
—
1
—
Units : %
Int16
MMS Output Pct Power Phase C
30637
—
1
—
Units : %
Int16
MMS Output Pct Apparent Pwr (kVA) Phase A
30638
—
1
—
Units : %
Uint16
MMS Output Pct Apparent Pwr (kVA) Phase B
30639
—
1
—
Units : %
Uint16
MMS Output Pct Apparent Pwr (kVA) Phase C
30640
—
1
—
Units : %
Uint16
Number of Redundant Modules
30641
—
1
—
Uint16
MMS Module Number
30642
—
1
—
Int16
Number of Modules in a MMS
30643
—
1
—
Uint16
Module Output Breaker for Module 1
30644
—
1
—
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 2
30645
—
1
—
0 = Open
1 = Close
2 = Not Installed
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
333
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
Module Output Breaker for Module 3
30646
—
1
—
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 4
30647
—
1
—
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 5
30648
—
1
—
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 6
30649
—
1
—
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 7
30650
—
1
—
0 = Open
1 = Close
2 = Not Installed
Module Output Breaker for Module 8
30651
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 1
30652
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 2
30653
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 3
30654
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 4
30655
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 5
30656
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 6
30657
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 7
30658
—
1
—
0 = Open
1 = Close
2 = Not Installed
Bypass Isolation Breaker for Module 8
30659
—
1
—
0 = Open
1 = Close
2 = Not Installed
System Output Breaker
30660
—
1
—
0 = Open
1 = Close
2 = Not Installed
System Load Bank Breaker
30661
—
1
—
0 = Open
1 = Close
2 = Not Installed
System Isolation Output Breaker
30662
—
1
—
0 = Open
1 = Close
2 = Not Installed
SCC Event Summary
30663
—
1
—
0 = None
1 = Alarm
2 = Fault
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
334
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Data Label
Input
Holding
# of Reg
Scale
Notes/Units
30665
—
1
—
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
MMS Inter-Module Comm Status
30676
—
1
—
0 = Failed
1 = Normal
MMS Event Summary
30677
—
1
—
0 = None
1 = Alarm
2 = Fault
MMS Module Inverter Status
30678
—
1
—
0 = off
1 = on
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
MMS UPS Output Source
ModuleList 1
MMS Module Output Voltage Status
30679
—
1
30680
—
1
—
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
MMS Inter-Module Comm Status
30691
—
1
—
0 = Failed
1 = Normal
MMS Event Summary
30692
—
1
—
0 = None
1 = Alarm
2 = Fault
MMS Module Inverter Status
30693
—
1
—
0 = off
1 = on
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
MMS Module Output Source
ModuleList 2
MMS Module Output Voltage Status
30694
—
1
30695
—
1
—
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
MMS Inter-Module Comm Status
30781
—
1
—
0 = Failed
1 = Normal
MMS Event Summary
30782
—
1
—
0 = None
1 = Alarm
2 = Fault
MMS Module Inverter Status
30783
—
1
—
0 = off
1 = on
—
0 = Fail
1 = Marginal Low
2 = Normal
3 = Marginal High
—
0 = Off
1 = Normal
2 = Bypass
3 = Maintenance Bypass
MMS Module Output Source
ModuleList 8
MMS Module Output Voltage Status
MMS Module Output Source
30784
30785
—
—
1
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
335
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Input
Holding
# of Reg
Scale
Notes/Units
Intelligent Parallel Operation State
30796
—
1
—
0 = disabled
1 = enabled
Intelligent Parallel Minimum Redundancy
30797
—
1
—
Uint16
Intelligent Parallel Maximum Time in Standby
30798
—
1
—
Units : day
Uint16
ECO Mode Operation State
30809
40809
1
—
0 = disabled
1 = enabled
Continuous Operation - ECO Mode
30810
—
1
—
0 = disabled
1 = enabled
Maximum Auto Suspensions - ECO Mode
30811
—
1
—
Uint16
Restart Delay - ECO Mode
30812
—
1
—
Units : min
Uint16
Time Remaining - ECO Mode
30813
—
1
—
Units : min
Uint16
Schedule Operation State - ECO Mode
30824
—
1
—
0 = disabled
1 = enabled
Schedule Action - ECO Mode
30825
—
1
—
0 = stop
1 = start
Data Label
Intelligent Paralleling
ECO Mode
EcoModeSchedule 1
Schedule Day of Week - ECO Mode
30826
—
1
—
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode
30827
—
1
—
Units : hr
Uint16
Schedule Minute - ECO Mode
30828
—
1
—
Units : min
Uint16
Schedule Operation State - ECO Mode
30839
—
1
—
0 = disabled
1 = enabled
Schedule Action - ECO Mode
30840
—
1
—
0 = stop
1 = start
EcoModeSchedule 2
Schedule Day of Week - ECO Mode
30841
—
1
—
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode
30842
—
1
—
Units : hr
Uint16
Schedule Minute - ECO Mode
30843
—
1
—
Units : min
Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
336
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued)
Input
Holding
# of Reg
Scale
Notes/Units
Schedule Operation State - ECO Mode
31019
—
1
—
0 = disabled
1 = enabled
Schedule Action - ECO Mode
31020
—
1
—
0 = stop
1 = start
Data Label
EcoModeSchedule 14
Schedule Day of Week - ECO Mode
31021
—
1
—
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
Schedule Hour - ECO Mode
31022
—
1
—
Units : hr
Uint16
Schedule Minute - ECO Mode
31023
—
1
—
Units : min
Uint16
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
337
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary
Data Label
Data Description
Auto Restart In Progress
Auto restart is in progress
Auto Restart Inhibited - Ext
Auto restart inhibited due to an external signal
Auto Retransfer Time Remaining
Time remaining before an inverter overload or inverter fault can be cleared and auto
retransfer from the bypass to the inverter can take place
Automatic Restart Failed
Automatic restart failed
Backfeed Breaker Open
The backfeed breaker is in the open position
Backfeed Breaker
Backfeed breaker
Battery - External Monitor 1
External battery monitor 1 - battery maintenance required
Battery - External Monitor 2
External battery monitor 2 - battery maintenance required
Battery Amp-Hours Consumed This
Discharge
Battery amp-hours withdrawn this discharge.
Battery Amp-Hours Consumed
Cumulative battery amp-hours withdrawn over the life of the battery
Battery Auto Test In Progress
Automatic battery test is in progress
Battery Automatic Test Inhibited
Automatic (scheduled) battery tests are inhibited
Battery Capacity Low
Battery capacity is low
Battery Cell Count - Lead Acid
Battery cell count - lead acid
Battery Cell Count-Nickel Cadmium
Battery cell count - nickel cadmium
Battery Circuit Breaker 1 Open
Battery circuit breaker 1 is open
Battery Circuit Breaker 2 Open
Battery circuit breaker 2 is open
Battery Circuit Breaker 3 Open
Battery circuit breaker 3 is open
Battery Circuit Breaker 4 Open
Battery circuit breaker 4 is open
Battery Circuit Breaker 5 Open
Battery circuit breaker 5 is open
Battery Circuit Breaker 6 Open
Battery circuit breaker 6 is open
Battery Discharge Power
Instantaneous battery power while discharging
Battery Discharge Time
The time on battery operation for this discharge
Battery Discharging
The battery is discharging
Battery Equalize
The rectifier output voltage is increased to equalize the battery voltage level.
Battery Fuse Fault
One or more battery fuse faults has occurred.
Battery Ground Fault
Battery system ground fault amperage exceeds the threshold
Battery Last Discharge Date
The date and time of the last battery discharge
Battery Low Shutdown
The battery voltage has dropped to the End of Discharge value.
Battery Low
The calculated battery time remaining has reached the low battery threshold
Battery Over Temperature Limit
A battery temperature sensor is reporting a value above a predetermined limit.
Battery Over Temperature
A battery temperature sensor is reporting a value above a threshold
Battery Over Voltage
The system has detected that the battery voltage has exceeded a predetermined
limit.
Battery Percentage Charge
The percentage of battery charge
Battery SCR Status
The status of the battery SCR.
Battery Temperature for Cabinet
The battery temperature for a cabinet
Battery Temperature Imbalance
Excessive temperature differences between battery sensors detected
Battery Temperature Sensor Fault
A battery temperature sensor fault has been detected
Battery Test Failed
Battery test failed
Battery Test Manually Stopped
The battery test was manually stopped prior to completion
Battery Test Passed
Battery test passed
Battery Time Remaining
The calculated available time on battery
Battery Total Discharge Time
The cumulative battery discharge time
Battery Volts at Main Disconnect
The voltage between the positive and the negative battery terminals of the common
battery disconnect
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
338
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued)
Data Label
Data Description
Battery Volts for Cabinet
The voltage between the positive and negative battery terminals of a battery cabinet
Bypass - Manual Rexfr Inhibited
Manual transfer from bypass to inverter is inhibited.
Bypass - Manual Xfr Inhibited
Manual transfer from inverter to bypass is inhibited.
Bypass Auto Retransfer Failed
After performing a recoverable transfer to bypass, an attempt to auto retransfer from
bypass to inverter failed
Bypass Auto Transfer Failed
An automatic transfer to static bypass failed
Bypass Frequency Error
The bypass frequency is outside the inverter synchronization limits
Bypass Input Frequency
The bypass input frequency
Bypass Input Voltage RMS A-B
The bypass input RMS voltage between phases A and B
Bypass Input Voltage RMS B-C
The bypass input RMS voltage between phases B and C
Bypass Input Voltage RMS C-A
The bypass input RMS voltage between phases C and A
Bypass Input Wire Configuration
Bypass input wire configuration
Bypass Isolation Breaker for Module 1 Bypass isolation breaker for module 1
Bypass Isolation Breaker for Module 2 Bypass isolation breaker for module 2
Bypass Isolation Breaker for Module 3 Bypass isolation breaker for module 3
Bypass Isolation Breaker for Module 4 Bypass isolation breaker for module 4
Bypass Isolation Breaker for Module 5 Bypass isolation breaker for module 5
Bypass Isolation Breaker for Module 6 Bypass isolation breaker for module 6
Bypass Isolation Breaker for Module 7 Bypass isolation breaker for module 7
Bypass Isolation Breaker for Module 8 Bypass isolation breaker for module 8
Bypass Isolation Breaker
Bypass isolation breaker
Bypass Nominal Voltage
Bypass nominal (or rated) voltage
Bypass Not Available
A problem associated with the bypass has been detected
Bypass Overload Phase A
An overload exists on output phase A while operating on the bypass
Bypass Overload Phase B
An overload exists on output phase B while operating on the bypass
Bypass Overload Phase C
An overload exists on output phase C while operating on the bypass
Bypass Qualification Status
bypass qualification status
Bypass SS Overload Time Remain
The calculated time remaining before bypass static switch shutdown due to the
present overload condition
Bypass Static Switch Overload
Bypass off due to static switch overload
Bypass Static Switch Unavailable
The static bypass switch is off, and unable to operate
Bypass Sync Phase Difference
The phase angle difference between the inverter output and bypass source
Configuration Description
Configuration description
Continuous Operation - ECO Mode
This setting gives the user the ability to Enable/Disable ECO Mode continuous
operation.
Controls Reset Required
A controls reset is required due to one or more critical settings changing
DC Bus Current
The current at the battery input terminals. In charging mode, the current will be a
positive value. In discharging mode, the current will be a negative value
DC Bus Low Fault
The DC Bus voltage has reached a critical low level.
DC Bus Qualification Status
dc bus qualification status
DC Bus Voltage
The voltage between the positive and negative terminals of the DC bus at the battery
input
ECO Mode Active
Conditions for Activation or Automatic Reactivation have been satisfied.
ECO Mode Operation State
This setting is used to enable or disable ECO Mode.
ECO Mode Suspended
ECO Mode session is suspended.
EMO Shutdown
An Emergency Module Off command has been detected.
Equipment Temperature Sensor Fail
One or more temperature sensors report a temperature outside of the range of
expected operation.
339
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued)
Data Label
Data Description
Excess ECO Suspends
Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto
Suspensions setting.
Fuse Failure
A summary event indicating one or more fuse failures
Inlet Air Over Temperature
The inlet air exceeds the maximum temperature threshold
Inlet Air Temperature
The temperature of the inlet air
Input Breaker
Input breaker
Input Contact 01
The external input contact 1
Input Contact 02
The external input contact 2
Input Contact 03
The external input contact 3
Input Contact 04
The external input contact 4
Input Contact 05
The external input contact 5
Input Contact 06
The external input contact 6
Input Contact 07
The external input contact 7
Input Contact 08
The external input contact 8
Input Contact 09
The external input contact 9
Input Contact 10
The external input contact 10
Input Contact 11
The external input contact 11
Input Contact 12
The external input contact 12
Input Contact 13
The external input contact 13
Input Contact 14
The external input contact 14
Input Contact 15
The external input contact 15
Input Contact 16
The external input contact 16
Input Filter Cycle Lock
The input filter disconnect is open due to exceeding the maximum number of cycles.
Input Isolation Transformer
Input isolation transformer
Input Qualification Status
input qualification status
Intelligent Parallel Maximum Time in
Standby
The maximum time a module can be in standby mode due to Intelligent Paralleling.
Intelligent Parallel Minimum
Redundancy
This is the minimum Number of Redundant Modules that the system will allow before
bringing one or more modules back to normal operation and terminating Intelligent
Paralleling.
Intelligent Parallel Operation State
This setting is used to enable or disable Intelligent Paralleling.
Internal Communications Failure
The control has detected a communication failure of a component on the internal
communication bus
Inverter Failure
Inverter failure - inverter output is off
Inverter Inhibit - External
Restart of the inverter is inhibited by an external signal
Inverter On/Off State
inverter on/off state
Inverter Output Qualification Status
inverter output qualification status
Inverter Overload Phase A
Inverter is operating with an overload on phase A
Inverter Overload Phase B
Inverter is operating with an overload on phase B
Inverter Overload Phase C
Inverter is operating with an overload on phase C
Inverter Overload Time Remaining
The calculated time remaining before inverter shutdown
Inverter Shutdown - Overload
The inverter has shutdown due to a sustained overload
Inverter Static Switch SCR Short
The system has detected a short across one or more inverter static switch Silicon
Controlled Rectifiers (SCR)
IP Inhibit
The intelligent paralleling operation is inhibited.
LBS Inhibited
The system has detected that conditions to perform Load Bus Sync are not satisfied
Leading Power Factor
The leading output Power Factor has fallen below a specified value
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
340
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued)
Data Label
Data Description
Loss of Redundancy
The multi-module collection doesn't have enough modules to redundantly support the
load.
Main Battery Disconnect Forced To
Unlock
The main battery disconnect is forced to the unlocked state.
Main Battery Disconnect Open
Main battery disconnect is open
Main Battery Disconnect Switch Lock
Status
The main battery disconnect switch lock status.
Main Controller Fault
A Main Controller fault has been detected.
Maintenance Bypass Breaker
Maintenance bypass breaker
Maintenance Isolation Breaker
Maintenance isolation breaker
Maximum Auto Suspensions - ECO
Mode
This setting sets the maximum number of automatic ECO Mode suspensions in a
session.
MMS Event Summary
Summary of any active user alarm or fault of this module in a multi-module system
MMS Inter-Module Comm Status
Inter-module communication status of this module in a multi-module system
MMS Module Alarm Active
Active alarm or fault of any module in a multi-module system
MMS Module Inverter Status
Multi-module inverter status of this module (on/off)
MMS Module Number
MMS module number
MMS Module Output Source
Module output source in a multi-module system (normal/bypass/maintenance
bypass/off)
MMS Module Output Voltage Status
Output voltage status of this module in multi-module system
MMS On Battery
The multi-module system is on battery
MMS Output Apparent Power
The sum total apparent power of all system output modules
MMS Output Frequency
The multi-module system output frequency
MMS Output Pct Apparent Pwr (kVA)
Phase A
The multi-module system output apparent power on phase A as a percentage of the
rated capacity
MMS Output Pct Apparent Pwr (kVA)
Phase B
The multi-module system output apparent power on phase B as a percentage of the
rated capacity
MMS Output Pct Apparent Pwr (kVA)
Phase C
The multi-module system output apparent power on phase C as a percentage of the
rated capacity
MMS Output Pct Power Phase A
The multi-module system output power on phase A as a percentage of the rated
capacity
MMS Output Pct Power Phase B
The multi-module system output power on phase B as a percentage of the rated
capacity
MMS Output Pct Power Phase C
The multi-module system output power on phase C as a percentage of the rated
capacity
MMS Output Power Factor Phase A
The multi-module system output power factor for phase A
MMS Output Power Factor Phase B
The multi-module system output power factor for phase B
MMS Output Power Factor Phase C
The multi-module system output power factor for phase C
MMS Output Power
The sum total power of all system output modules
MMS Overload
Multi-module system overload
MMS UPS Output Source
Multi-module UPS output source
Module Output Breaker for Module 1
Module output breaker for module 1
Module Output Breaker for Module 2
Module output breaker for module 2
Module Output Breaker for Module 3
Module output breaker for module 3
Module Output Breaker for Module 4
Module output breaker for module 4
Module Output Breaker for Module 5
Module output breaker for module 5
Module Output Breaker for Module 6
Module output breaker for module 6
Module Output Breaker for Module 7
Module output breaker for module 7
Module Output Breaker for Module 8
Module output breaker for module 8
Module Output Breaker
Module output breaker
341
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued)
Data Label
Data Description
Multi-module System Output Voltage
RMS A-B
Multi-module system output RMS voltage between phases A and B
Multi-module System Output Voltage
RMS A-N
Multi-module system output RMS voltage between phase A and Neutral
Multi-module System Output Voltage
RMS B-C
Multi-module system output RMS voltage between phases B and C
Multi-module System Output Voltage
RMS B-N
Multi-module system output RMS voltage between phase B and Neutral
Multi-module System Output Voltage
RMS C-A
Multi-module system output RMS voltage between phases C and A
Multi-module System Output Voltage
RMS C-N
Multi-module system output RMS voltage between phase C and Neutral
Multiple Fan Failure
Multiple fan failure
Number of Modules in a MMS
The number of modules in a multi-module system
Number of Redundant Modules
The number of redundant modules in a multi-module collective.
Outlet Air Overtemperature Limit
The difference between the outlet air temperature and inlet air temperature exceeds a
specified maximum temperature.
Output Amp Over User Limit-Phs A
The phase A output has exceeded the user amperage threshold
Output Amp Over User Limit-Phs B
The phase B output has exceeded the user amperage threshold
Output Amp Over User Limit-Phs C
The phase C output has exceeded the user amperage threshold
Output Apparent Power Rating
Output apparent power rating
Output Breaker
Output breaker
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Output Of/Uf
The output frequency has exceeded a specified range for a specified period of time.
Output Qualification Status
output qualification status
Output Real Power Rating
Output real power rating
Output Series Static Switch
output series static switch
Output Wire Configuration
Output wire configuration
Power Supply Failure
Power supply failure
Program Input Contact 01
When the signal from [Program Input Contact 01] is active the function assigned to
this contact is executed.
Program Input Contact 02
When the signal from [Program Input Contact 02] is active the function assigned to
this contact is executed.
Program Input Contact 03
When the signal from [Program Input Contact 03] is active the function assigned to
this contact is executed.
Program Input Contact 04
When the signal from [Program Input Contact 04] is active the function assigned to
this contact is executed.
Program Input Contact 05
When the signal from [Program Input Contact 05] is active the function assigned to
this contact is executed.
Program Input Contact 06
When the signal from [Program Input Contact 06] is active the function assigned to
this contact is executed.
Program Input Contact 07
When the signal from [Program Input Contact 07] is active the function assigned to
this contact is executed.
Program Input Contact 08
When the signal from [Program Input Contact 08] is active the function assigned to
this contact is executed.
Program Input Contact 09
When the signal from [Program Input Contact 09] is active the function assigned to
this contact is executed.
Program Input Contact 10
When the signal from [Program Input Contact 10] is active the function assigned to
this contact is executed.
Program Input Contact 11
When the signal from [Program Input Contact 11] is active the function assigned to
this contact is executed.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
342
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued)
Data Label
Data Description
Program Input Contact 12
When the signal from [Program Input Contact 12] is active the function assigned to
this contact is executed.
Rectifier Active Filter
Rectifier input active filter configuration
Rectifier Configuration Change
Request
This event indicates that the battery is not configured and PFC is not enabled.
Rectifier Failure
Rectifier failure - rectifier is off
Rectifier Input Passive Filter
Rectifier input passive filter configuration
Rectifier Passive Filter Switch
Rectifier input passive filter switch configuration
Rectifier Pulse Count
Rectifier pulse count per cycle configuration
Rectifier Status
rectifier status
Regeneration Active
Regeneration operation is active.
Regeneration Operation Failure
Regeneration operation has been terminated due to bypass source instability or unit
misoperation.
Regeneration Operation Terminated
Regeneration operation is not active.
Restart Delay - ECO Mode
The time delay that the conditions to activate ECO Mode must be satisfied before
ECO Mode can be reactivated during an active session.
SCC Event Summary
Summary of any active user alarms or faults on the SCC
Schedule Action - ECO Mode
This setting gives the user the ability to choose the action of a schedule entry to be
either stop or start.
Schedule Day of Week - ECO Mode
This setting represents the day of the week when an associated ECO Mode schedule
entry action will take effect.
Schedule Hour - ECO Mode
This setting represents the hour of the day when an associated schedule entry action
will take effect.
Schedule Minute - ECO Mode
This setting represents the minute of the hour when an associated schedule entry
action will take effect.
Schedule Operation State - ECO Mode
This setting gives the user the ability to either enable or disable a schedule entry if the
action is Start.
Service Code Active
Service code is running
Static Bypass Switch
Static Bypass Switch state - On/Off
Static Switch Type
Static switch type configuration
Sum of MMS Output RMS Currents for
The sum of the multi-module system output RMS currents for phase A
Phase A
Sum of MMS Output RMS Currents for
The sum of the multi-module system output RMS currents for phase B
Phase B
Sum of MMS Output RMS Currents for
The sum of the multi-module system output RMS currents for phase C
Phase C
System Breaker(s) Close Failure
One or more breakers in the system failed to close
System Breaker(s) Open Failure
One or more breakers in the system failed to open
System Controller Error
System controller internal error
System Date and Time
The system date and time
System Fan Capacity Status
System fan capacity status
System Fan Failure - Redundant
Redundant system fan failure
System Fan Redundant Status
System fan redundant status
System Fan Status
System fan status
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Current Limit
The RMS input current has reached the input current limit threshold
System Input Frequency
The system input frequency
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
343
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued)
Data Label
Data Description
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the sequence
preferred for the rectifier (A-B-C)
System Input Power Problem
The input is not qualified to provide power to the system
System Input Power Source
System input power source
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Isolation Output Breaker
System isolation output breaker
System Load Bank Breaker
System load bank breaker
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Breaker
System output breaker
System Output Fault
A fault has been detected in the system output
System Output Frequency
The system output frequency
System Output Low Power Factor
The system output power factor is low, resulting in reduced output capacity
System Output Maximum Amp Rating
System output maximum amperage rating
System Output Nominal Frequency
The nominal (or rated) system output frequency
System Output Nominal Voltage
The nominal (or rated) system output voltage
System Output Pct Power Phase A
The system output power on phase A as a percentage of the rated capacity
System Output Pct Power Phase B
The system output power on phase B as a percentage of the rated capacity
System Output Pct Power Phase C
The system output power on phase C as a percentage of the rated capacity
System Output Pct Pwr (VA) Phs A
The system output apparent power on phase A as a percentage of the rated capacity
System Output Pct Pwr (VA) Phs B
The system output apparent power on phase B as a percentage of the rated capacity
System Output Pct Pwr (VA) Phs C
The system output apparent power on phase C as a percentage of the rated capacity
System Output Power Factor Phs A
The system output power factor of phase A
System Output Power Factor Phs B
The system output power factor of phase B
System Output Power Factor Phs C
The system output power factor of phase C
System Output Power
The sum total power of all system output phases
System Output RMS Current Phs A
The system output RMS current for Phase A
System Output RMS Current Phs B
The system output RMS current for Phase B
System Output RMS Current Phs C
The system output RMS current for Phase C
System Output Voltage RMS A-B
The system output RMS voltage between phases A and B
System Output Voltage RMS A-N
The system output RMS voltage between phases A and Neutral
System Output Voltage RMS B-C
The system output RMS voltage between phases B and C
System Output Voltage RMS B-N
The system output RMS voltage between phases B and Neutral
System Output Voltage RMS C-A
The system output RMS voltage between phases C and A
System Output Voltage RMS C-N
The system output RMS voltage between phases C and Neutral
System Redundant UPS Modules
Number of redundant UPS modules in the system
System Shutdown - EPO
System shutdown due to Emergency Power Off (EPO)
System Shutdown - REPO
System shutdown due to Remote Emergency Power Off (REPO)
System Status
The operating status for the system
System UPS Module Count
Number of UPS modules in the system
The main battery disconnect status.
Main Battery Disconnect Status
Time Remaining - ECO Mode
Time remaining before current active ECO Mode session stops.
Total System Operating Time
The cumulative operation time of the unit
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
344
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued)
Data Label
Data Description
Trap Filter Disconnect
Trap filter disconnect
Unexpected Main Battery Disconnect
Closure
The main battery disconnect has closed unexpectedly.
UPS Battery Status
UPS battery status
UPS Module Type
UPS module type
UPS Output on Bypass
The output power is supplied by the bypass
UPS Output Source
UPS output source
UPS System Output Source
The UPS system's output power source
VDC Backfeed
The voltage between battery and DC bus measurements is out of tolerance.
345
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-82 Liebert PowerSure™ Interactive (before July 2008)—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Audible Alarm Enabled
10002
2
1
—
—
Automatic Battery Test Enabled
10003
3
1
—
—
Battery Charge Compensation
10046
—
1
—
—
Inverter Ready
10047
—
1
—
—
Load Circuit 1 State
10057
—
1
—
—
Load Circuit 2 State
10058
—
1
—
—
Load Circuit 3 State
10059
—
1
—
—
Load Circuit 4 State
10060
—
1
—
—
Load Circuit 5 State
10061
—
1
—
—
Load Circuit 6 State
10062
—
1
—
—
Load Circuit 7 State
10063
—
1
—
—
Load Circuit 8 State
10064
—
1
—
—
Load Circuit 9 State
10065
—
1
—
—
Load Circuit 10 State
10066
—
1
—
—
Load Circuit 11 State
10067
—
1
—
—
Load Circuit 12 State
10068
—
1
—
—
Load Circuit 13 State
10069
—
1
—
—
Load Circuit 14 State
10070
—
1
—
—
Load Circuit 15 State
10071
—
1
—
—
Load Circuit 16 State
10072
—
1
—
—
Load On Inverter
10073
—
1
—
—
Boost Mode On
10075
—
1
—
—
Buck Mode On
10076
—
1
—
—
Battery Under Test
10082
—
1
—
—
Shutdown Reason - Over Temperature
10086
—
1
—
—
Shutdown Reason - Overload
10087
—
1
—
—
Shutdown - Output Short
10089
—
1
—
—
Shutdown Reason - Remote Shutdown
10093
—
1
—
—
Load On Battery
10128
—
1
—
—
Output Off Pending
10151
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
Over Temperature Warning
10171
—
1
—
—
Battery Over Temperature CB Trip
10172
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Input Over Voltage
10187
—
1
—
—
Input Under Voltage
10188
—
1
—
—
Bad Input Frequency
10190
—
1
—
—
Output Under Voltage
10218
—
1
—
—
Output Over Voltage
10219
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
346
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-83 Liebert PowerSure™ Interactive (before July 2008)—Input and Holding
Data Description
Number of Input Lines
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Number of SubModules
30009
40009
1
—
-
Load Circuit Present
30013
40013
1
—
There are 16 possible Load Circuits. Each bit
represents 1 load circuit. Load Circuit 1 is bit
0, Load Circuit 2 is bit 1 and so on. If the bit is
1, then the Load Circuit is supported.
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Input Current
30030
40030
1
—
A
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
Nominal Battery Voltage
30034
40034
1
—
V
Auto Restart Delay
30051
40051
1
—
Seconds
Device Low Battery Time
30053
40053
1
—
Minutes
Load (Apparent Power)
30102
—
2
—
VA
Load / Capacity
30106
—
1
—
%
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Charge Status
30112
—
1
—
Battery Voltage
30113
—
1
—
V
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Battery Test Result
30130
—
1
—
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
7 - Inhibited
Input Voltage L1
30153
—
1
—
V
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Input Maximum Voltage L1
30180
—
1
—
V
Input Minimum Voltage L1
30181
—
1
—
V
Output Maximum Voltage L1
30182
—
1
—
V
Output Minimum Voltage L1
30183
—
1
—
V
Black Out Count
30301
—
1
—
—
Brown Out Count
30302
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
347
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-84 Liebert PowerSure™ Interactive 2—Status and Coil
Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153)
Status
Coil
Number
of Bits
Scale
Notes / Units
Audible Alarm Enabled
10002
2
1
—
—
Automatic Battery Test Enabled
10003
3
1
—
—
DC-To-DC Converter On
10042
—
1
—
—
Battery Charger On
10044
—
1
—
—
Load Circuit 1 State
10057
—
1
—
—
Load Circuit 2 State
10058
—
1
—
—
Load Circuit 3 State
10059
—
1
—
—
Load Circuit 4 State
10060
—
1
—
—
Load Circuit 5 State
10061
—
1
—
—
Load Circuit 6 State
10062
—
1
—
—
Load Circuit 7 State
10063
—
1
—
—
Load Circuit 9 State
10065
—
1
—
—
Load Circuit 10 State
10066
—
1
—
—
Load Circuit 11 State
10067
—
1
—
—
Load Circuit 12 State
10068
—
1
—
—
Load Circuit 13 State
10069
—
1
—
—
Load Circuit 14 State
10070
—
1
—
—
Load Circuit 15 State
10071
—
1
—
—
Data Description
Load Circuit 16 State
10072
—
1
—
—
Load On Inverter
10073
—
1
—
—
Boost Mode On
10075
—
1
—
—
Buck Mode On
10076
—
1
—
—
Replace Battery
10081
—
1
—
—
Battery Under Test
10082
—
1
—
—
Shutdown Reason - Over Temperature
10086
—
1
—
—
Shutdown Reason - Overload
10087
—
1
—
—
Shutdown Reason - Output Short
10089
—
1
—
—
Shutdown Reason - Line Neutral Swap
10090
—
1
—
—
Shutdown Reason - Low Battery
10092
—
1
—
—
Shutdown Reason - Remote Shutdown
10093
—
1
—
—
Shutdown Reason - Input Under Voltage
10094
—
1
—
—
Shutdown Reason - Hardware
10096
—
1
—
—
Load On Battery
10128
—
1
—
—
Output Off Pending
10151
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
Over Temperature Warning
10171
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Input Over Voltage
10187
—
1
—
—
Input Under Voltage
10188
—
1
—
—
Input BrownOut
10189
—
1
—
—
Bad Input Frequency
10190
—
1
—
—
Output Under Voltage
10218
—
1
—
—
Output Over Voltage
10219
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
348
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-84 Liebert PowerSure™ Interactive 2—Status and Coil (continued)
Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153)
Coil
Number
of Bits
Data Description
Status
Scale
Notes / Units
Charger Failed
10234
—
1
—
—
Battery Under Voltage
10241
—
1
—
—
Battery Over Voltage
10242
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
349
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-85 Liebert PowerSure™ Interactive 2—Input and Holding
Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153)
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Number of SubModules
30009
40009
1
—
—
—
There are 16 possible Load Circuits.
Each bit represents 1 load circuit.
Load Circuit 1 is bit 0, Load Circuit 2 is
bit 1 and so on. If the bit is 1, then the
Load Circuit is supported.
Data Description
Load Circuit Present
30013
40013
1
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Input Current
30030
40030
1
—
A
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
Nominal Battery Voltage
30034
40034
1
—
V
Nominal Battery Capacity
30037
40037
1
—
Minutes
Nominal Battery Float Voltage
30038
40038
1
—
V
Auto Restart Delay
30051
40051
1
—
Seconds
Device Low Battery Time
30053
40053
1
—
Minutes
Ambient Temperature Warning Point
30069
40069
1
—
deg C
Over Temperature Limit Point
30072
40072
1
—
deg C
Load (Apparent Power)
30102
—
2
—
VA
Load (Real Power)
30104
—
2
—
W
Load / Capacity
30106
—
1
—
%
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Charge Status
30112
—
1
—
Battery Voltage
30113
—
1
—
V
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Ambient Temperature
30119
—
1
—
deg C
Battery Test Result
30130
—
1
—
—
Input Voltage L1
30153
—
1
—
V
Input Current L1
30154
—
1
—
A
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Input Maximum Voltage L1
30180
—
1
—
V
Input Minimum Voltage L1
30181
—
1
—
V
Output Maximum Voltage L1
30182
—
1
—
V
Output Minimum Voltage L1
30183
—
1
—
V
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
350
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-85 Liebert PowerSure™ Interactive 2—Input and Holding (continued)
Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153)
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Black Out Count
30301
—
1
—
—
Brown Out Count
30302
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
351
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-86 Liebert Series 300™ UPS—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Automatic Restart Enabled
10001
1
1
—
—
Battery Charge Compensation
10046
—
1
—
—
Inverter Ready
10047
—
1
—
—
Load Circuit 1 State
10057
—
1
—
—
Load Circuit 2 State
10058
—
1
—
—
Load Circuit 3 State
10059
—
1
—
—
Load Circuit 4 State
10060
—
1
—
—
Load Circuit 5 State
10061
—
1
—
—
Load Circuit 6 State
10062
—
1
—
—
Load Circuit 7 State
10063
—
1
—
—
Load Circuit 8 State
10064
—
1
—
—
Load Circuit 9 State
10065
—
1
—
—
Load Circuit 10 State
10066
—
1
—
—
Load Circuit 11 State
10067
—
1
—
—
Load Circuit 12 State
10068
—
1
—
—
Load Circuit 13 State
10069
—
1
—
—
Load Circuit 14 State
10070
—
1
—
—
Load Circuit 15 State
10071
—
1
—
—
Load Circuit 16 State
10072
—
1
—
—
Load On Inverter
10073
—
1
—
—
Bypass Active
10074
—
1
—
—
Buck On
10076
—
1
—
—
Replace Battery
10081
—
1
—
—
Battery Under Test
10082
—
1
—
—
Load On Battery
10128
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
Over Temperature Warning
10171
—
1
—
—
Battery Over Temperature CB Trip
10172
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Input Over Voltage
10187
—
1
—
—
Input Under Voltage
10188
—
1
—
—
Bad Input Frequency
10190
—
1
—
—
Bypass Input Voltage/Frequency Fault
10202
—
1
—
—
Output Under Voltage
10218
—
1
—
—
Output Over Voltage
10219
—
1
—
—
Battery Charger Fail
10234
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
352
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-87 Liebert Series 300™ UPS—Input and Holding
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Number of SubModules
30009
40009
1
—
—
Data Description
Load Circuit Present
30013
40013
1
—
There are 16 possible Load Circuits. Each bit
represents 1 Load Circuit. Load Circuit 1 is bit
0, Load Circuit 2 is bit 1 and so on. If the bit is
1, then the Load Circuit is supported.
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch
Voltage
30029
40029
1
—
V
Nominal Input Current
30030
40030
1
—
A
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
Nominal Battery Voltage
30034
40034
1
—
V
Device Low Battery Time
30053
40053
1
—
Minutes
Load (Apparent Power)
30102
—
2
—
VA
Load (Real Power)
30104
—
2
—
W
Load / Capacity
30106
—
1
—
%
Input Frequency
30107
—
1
10
Hz
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Hz
Battery Charge Status
30112
—
1
—
Battery Voltage
30113
—
1
—
V
Battery Current
30114
—
1
—
A
1 - 100% Charged
2 - Less than 100% Charged
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Battery Test Result
30130
—
1
—
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1
30153
—
1
—
V
Input Current
30154
—
1
—
A
Bypass Voltage L1
30159
—
1
—
V
Bypass Current L1
30160
—
1
—
A
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Input Voltage L2
30203
—
1
—
V
Input Current L2
30204
—
1
—
A
Bypass Voltage L2
30209
—
1
—
V
Bypass Current L2
30210
—
1
—
A
Output Voltage L2
30213
—
1
—
V
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
353
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-87 Liebert Series 300™ UPS—Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Output Current L2
30214
—
1
—
A
Input Voltage L3
30253
—
1
—
V
Input Current L3
30254
—
1
—
A
Bypass Voltage L3
30259
—
1
—
V
Bypass Current L3
30260
—
1
—
A
Output Voltage L3
30263
—
1
—
V
Output Current L3
30264
—
1
—
A
Black Out Count
30301
—
1
—
—
Brown Out Count
30302
—
1
—
—
Transient Count
30301
—
1
—
—
40101
—
—
Silent Audible Alarm
—
Any value
Battery Start
—
40102
1
—
1=Start, 0=Abort
Open UPS Output Switch
—
40104
—
—
Delay time in Seconds, last digit will be ignored
Reboot UPS Output Switch
—
40105
1
—
Delay time in Seconds, last digit will be ignored
Close UPS Output Switch
—
40106
—
—
Delay time in Seconds, last digit will be ignored
Transfer Load to Bypass
—
40107
1
—
Any value
Transfer Load to Inverter
—
40108
—
—
Any value
Reset UPS Statistic data
—
40111
1
—
Any value
Turn UPS Outlets On
—
40112
1
—
Bitmap mask for Outlet 1-16. All bits set to 1
will be turned On
Turn UPS Outlets Off
—
40113
1
—
Bitmap mask for Outlet 1-16. All bits set to 1
will be turned Off
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
354
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-88 Liebert Series 600™ UPS—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Auto Retransfer Primed
10049
—
1
—
—
Load On Inverter
10073
—
1
—
—
Load On Bypass
10074
—
1
—
—
Battery data Buffer Full
10084
—
1
—
—
Shutdown Reason - Hardware
10096
—
1
—
—
Load On Battery
10128
—
1
—
—
Load On Bypass
10129
—
1
—
—
Manual Reset Transfer
10130
—
1
—
—
Emergency Transfer
10134
—
1
—
—
Battery Switch Open
10136
—
1
—
—
Input Switch Open
10137
—
1
—
—
Output Switch open
10138
—
1
—
—
SBS Unable
10148
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Frequency Off
10153
—
1
—
—
Output Overload
10154
—
1
—
—
System Emergency Off
10157
—
1
—
—
Reverse Power
10159
—
1
—
—
Fan Fail
10169
—
1
—
—
Over Temperature Warning
10171
—
1
—
—
Ambient Over Temperature
10173
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Input Phase Rotation Error
10191
—
1
—
—
Bypass Input Voltage Fail
10202
—
1
—
—
Output Under Voltage
10218
—
1
—
—
Output Over Voltage
10219
—
1
—
—
DC Ground Fault
10233
—
1
—
—
DC Cap Fuse Blown
10252
—
1
—
—
Rectifier Fuse Blown
10257
—
1
—
—
Inverter Fuse Blown
10261
—
1
—
—
Customer Alarm 1
10313
—
1
—
—
Customer Alarm 2
10314
—
1
—
—
Customer Alarm 3
10315
—
1
—
—
Customer Alarm 4
10316
—
1
—
—
Customer Alarm 5
10317
—
1
—
—
Customer Alarm 6
10318
—
1
—
—
Customer Alarm 7
10319
—
1
—
—
Customer Alarm 8
10320
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
355
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-89 Liebert Series 600™ UPS—Input and Holding
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Data Description
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch Voltage
30029
40029
1
—
V
Nominal Input Current
30030
40030
1
—
A
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
Nominal Battery Voltage
30034
40034
1
—
V
—
40101
1
—
—
30102
—
2
—
VA
Silence Alarm
Load (Apparent Power)
Load (Real Power)
30104
—
2
—
W
Load / Capacity
30106
—
1
—
%
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Hz
Battery Charge Status
30112
—
1
—
Battery Voltage
30113
—
1
—
V
Battery Current
30114
—
1
—
A
1 - 100% Charged
2 - Less than 100% Charged
Battery Time Remaining
30115
—
1
—
Minutes
Battery Charge Percentage
30116
—
1
—
%
Input Voltage L1
30153
—
1
—
V
Input Current L1
30154
—
1
—
A
Bypass Voltage L1
30159
—
1
—
V
Bypass Current L1
30160
—
1
—
A
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Input Voltage L2
30203
—
1
—
V
Input Current L2
30204
—
1
—
A
Bypass Voltage L2
30209
—
1
—
V
Bypass Current L2
30210
—
1
—
A
Output Voltage L2
30213
—
1
—
V
Output Current L2
30214
—
1
—
A
Input Voltage L3
30253
—
1
—
V
Input Current L3
30254
—
1
—
A
Bypass Voltage L3
30259
—
1
—
V
Bypass Current L3
30260
—
1
—
A
Output Voltage L3
30263
—
1
—
V
Output Current L3
30264
—
1
—
A
Battery Discharge Count
30308
—
1
—
—
Battery Discharge duration
30309
—
1
—
Seconds
Battery Amp-Hour
30310
—
1
—
AH
Battery Watt-Hour
30311
—
2
—
WH
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
356
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-90 Liebert Series 610™ SCC UPS—Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Auto Retransfer Primed
10049
—
1
—
—
Load On Inverter
10073
—
1
—
—
Load On Bypass
10074
—
1
—
—
Load On Bypass
10129
—
1
—
—
Manual Reset Transfer
10130
—
1
—
—
Emergency Transfer
10134
—
1
—
—
Output Switch open
10138
—
1
—
—
SBS Unable
10148
—
1
—
—
Output Frequency Off
10153
—
1
—
—
Output Overload
10154
—
1
—
—
System Emergency Off
10157
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Input Phase Rotation Error
10191
—
1
—
—
Bypass Input Voltage Fail
10202
—
1
—
—
Output Under Voltage
10218
—
1
—
—
Output Over Voltage
10219
—
1
—
—
Module Alarm Active
10304
—
1
—
—
Customer Alarm 1
10313
—
1
—
—
Customer Alarm 2
10314
—
1
—
—
Customer Alarm 3
10315
—
1
—
—
Customer Alarm 4
10316
—
1
—
—
Customer Alarm 5
10317
—
1
—
—
Customer Alarm 6
10318
—
1
—
—
Customer Alarm 7
10319
—
1
—
—
Customer Alarm 8
10320
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
357
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-91 Liebert Series 610 SCC UPS—Input and Holding
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
—
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
—
Bits 4 - 7
Data Description
Number of Output Lines
30004
40004
1
—
Bits 8 - 11
Nominal Power Rating
30021
40021
2
—
VA
Nominal Input Voltage
30027
40027
1
—
V
Nominal Output Voltage
30028
40028
1
—
V
Nominal Static Bypass Switch Voltage
30029
40029
1
—
V
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
—
—
40101
1
—
—
30102
—
2
—
VA
W
Silence Alarm
Load (Apparent Power)
Load (Real Power)
30104
—
2
—
Load / Capacity
30106
—
1
—
%
Output Frequency
30108
—
1
10
Hz
Bypass Frequency
30109
—
1
10
Hz
Input Voltage L1
30153
—
1
—
V
Bypass Voltage L1
30159
—
1
—
V
Bypass Current L1
30160
—
1
—
A
Output Voltage L1
30163
—
1
—
V
Output Current L1
30164
—
1
—
A
Input Voltage L2
30203
—
1
—
V
Bypass Voltage L2
30209
—
1
—
V
Bypass Current L2
30210
—
1
—
A
Output Voltage L2
30213
—
1
—
V
Output Current L2
30214
—
1
—
A
Input Voltage L3
30253
—
1
—
V
Bypass Voltage L3
30259
—
1
—
V
Bypass Current L3
30260
—
1
—
A
Output Voltage L3
30263
—
1
—
V
Output Current L3
30264
—
1
—
A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
358
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-92 Liebert HiPulse™ and Liebert SICE 7200™—Input and Holding—SMM/SSM
Controller Multi Module Series - SMM
Liebert HiPulse
Liebert Products
Liebert SICE 7200
Available Points
Data Description
Status Points (View)
Output Voltage L1-L2
Output Voltage L2-L3
Output Voltage L3-L1
Output Amps L1
Output Amps L2
Output Amps L3
Power L1
Power L2
Power L3
Bypass Frequency
Inverter Frequency
Battery Voltage
Battery Amperage
Apparent Power L1
Apparent Power L2
Apparent Power L3
% Load L1
% Load L2
% Load L3
% Battery Charge
Battery Temperature
Battery Time Remaining
Alarm Points
Communications
Bypass Switch Open
Output Switch Open
Rectifier Switch Open
Battery CB Open
Manual Bypass Closed
Bypass Absent
Bypass Overvoltage
Bypass Undervoltage
Bypass Frequency Error
Byp Phase Rotation Error
Bypass SCR Failure
Bypass Off
Bypass Off
Load On Bypass
Bypass Overtemperature
Rectifier Under Voltage
Rectifier Block
Rectifier Block
Rectifier Current Limit
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
—
—
—
—
—
—
—
—
—
10
10
—
—
—
—
—
—
—
—
—
—
—
V
V
V
A
A
A
kW
kW
kW
Hz
Hz
V
A
kVA
kVA
kVA
%
%
%
—
deg C
Minutes
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
40289
40289
40289
40289
40289
40289
40289
40289
40289
40289
40289
40290
40290
40290
40290
40290
40290
40290
40290
40290
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
359
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-92 Liebert HiPulse™ and Liebert SICE 7200™—Input and Holding—SMM/SSM (continued)
Controller Multi Module Series - SMM
Liebert HiPulse
Liebert Products
Liebert SICE 7200
Available Points
Data Description
Rectifier Overtemperature
Rectifier Fuse Failure
Inverter Voltage Fault
Inverter Disable
Inverter Disable
Inverter Current Limit
Inverter Overtemperature
Inverter Non Sync
Inverter Overvoltage
Inverter Undervoltage
Inverter Fuse Failure
Output Overvoltage
Output Undervoltage
Output Undervoltage
Output Waveform Error
Inverter Frequency Error
Inverter Parallel Error
Contactor Failure
Battery Test
Battery Test Failed
Battery On Load
Battery End of Discharge
Boost Time Expired
DC Overvoltage
DC Undervoltage
Battery Fuse Failure
DC Overvoltage
Transfer Count Block
Overload Shutdown
Overtemperature SD
Emergency Stop
Overload Present
Overload Shutdown TO
Display Error
Display Error
Inverter Over Capacity
Bypass ECO Mode
Fan Failure
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
40290
40290
40291
40291
40291
40291
40291
40291
40291
40291
40291
40291
40291
40292
40292
40292
40292
40292
40292
40292
40292
40292
40292
40292
40293
40293
40293
40293
40293
40293
40293
40293
40293
40293
40293
40293
40293
40293
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Bit 9
Bit 10
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
360
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-93 Liebert SICE 7200™—Input and Holding—SSC
Controller System Control Cabinet - SSC
Liebert Products Liebert SICE 7200
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Output Voltage L1-L2
—
40001
1
—
V
Output Voltage L2-L3
—
40002
1
—
V
Data Description
Output Voltage L3-L1
—
40003
1
—
V
Output Amps L1
—
40004
1
—
A
Output Amps L2
—
40005
1
—
A
Output Amps L3
—
40006
1
—
A
Power L1
—
40007
1
—
kW
Power L2
—
40008
1
—
kW
Power L3
—
40009
1
—
kW
Bypass Frequency
—
40010
1
10
Hz
Battery Voltage
—
40012
1
—
V
Battery Amperage
—
40013
1
—
A
Apparent Power L1
—
40014
1
—
kVA
Apparent Power L2
—
40015
1
—
kVA
Apparent Power L3
—
40016
1
—
kVA
% Load L1
—
40017
1
—
%
% Load L2
—
40018
1
—
%
% Load L3
—
40019
1
—
%
% Battery Charge
—
40020
1
—
%
Battery Temperature
—
40021
1
—
deg C
Battery Time Remaining
—
40022
1
—
Minutes
Communications
—
40289
1
—
Bit 0
Bypass Switch Open
—
40289
1
—
Bit 1
Output Switch Open
—
40289
1
—
Bit 2
Battery CB Open
—
40289
1
—
Bit 3
Manual Bypass Closed
—
40289
1
—
Bit 4
Bypass Absent
—
40289
1
—
Bit 5
Bypass Overvoltage
—
40289
1
—
Bit 6
Bypass Undervoltage
—
40289
1
—
Bit 7
Bypass Frequency Error
—
40289
1
—
Bit 8
Bypass Ph Rotation Error
—
40289
1
—
Bit 9
Bypass SCR Failure
—
40289
1
—
Bit 10
Bypass Off
—
40290
1
—
Bit 0
Bypass Off
—
40290
1
—
Bit 1
Load On Bypass
—
40290
1
—
Bit 2
Bypass Overtemperature
—
40290
1
—
Bit 3
Inverter Non Sync
—
40290
1
—
Bit 4
Output Overvoltage
—
40290
1
—
Bit 5
Output Undervoltage
—
40290
1
—
Bit 6
Output Undervoltage
—
40290
1
—
Bit 7
Output Waveform Error
—
40290
1
—
Bit 8
Transfer Count Block
—
40290
1
—
Bit 9
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
361
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-93 Liebert SICE 7200™—Input and Holding—SSC (continued)
Controller System Control Cabinet - SSC
Liebert Products Liebert SICE 7200
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Overload Shutdown
—
40290
1
—
Bit 10
Overtemperature Shutdown
—
40291
1
—
Bit 0
Emergency Stop
—
40291
1
—
Bit 1
Overload Present
—
40291
1
—
Bit 2
Overload Shutdown TO
—
40291
1
—
Bit 3
Display Error
—
40291
1
—
Bit 4
Display Error
—
40291
1
—
Bit 5
Invewrter Over Capacity
—
40291
1
—
Bit 6
Parallel Bus Open
—
40291
1
—
Bit 7
Battery Ground Fault
—
40291
1
—
Bit 8
Bypass Backfeed
—
40291
1
—
Bit 9
Bypass Sync Inhibited
—
40291
1
—
Bit 10
Bypass ECO Mode
—
40291
1
—
Bit 11
Fan Failure
—
40291
1
—
Bit 12
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
362
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-94 Liebert Npower™—Input and Holding—IMP
Controller Single Module Series - SMS
Liebert Products Liebert Npower - SMS
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Input Voltage A-B
—
40001
1
—
V
Input Voltage B-C
—
40002
1
—
V
Input Voltage C-A
—
40003
1
—
V
Data Description
Status Points (View)
Bypass Voltage A-B
—
40004
1
—
V
Bypass Voltage B-C
—
40005
1
—
V
Bypass Voltage C-A
—
40006
1
—
V
Battery Voltage
—
40007
1
—
V
Battery Current
—
40008
1
10
A
Battery Temperature
—
40009
1
—
deg C
Output Voltage A-B
—
40010
1
—
V
Output Voltage B-C
—
40011
1
—
V
Output Voltage C-A
—
40012
1
—
V
Output Current A
—
40013
1
10
A
Output Current B
—
40014
1
10
A
Output Current C
—
40015
1
10
A
Output kVA A
—
40016
1
—
kVA
Output kVA B
—
40017
1
—
kVA
Output kVA C
—
40018
1
—
kVA
Output kW A
—
40019
1
—
kW
Output kW B
—
40020
1
—
kW
Output kW C
—
40021
1
—
kW
Output Frequency
—
40022
1
10
Hz
Rated kVA Percentage
—
40023
1
—
%
Rated kW Percentage
—
40024
1
—
%
Communications Loss
—
40289
1
—
Bit 0
Battery Fuse Fail
—
40289
1
—
Bit 1
Battery Low Transfer
—
40289
1
—
Bit 2
DC Over Voltage Transient
—
40289
1
—
Bit 3
Input Phase Rotation Error
—
40289
1
—
Bit 4
Rectifier/Trap Fuse Fail
—
40289
1
—
Bit 5
Any of Rectifier / Trap Fuse
Bypass Frequency Error
—
40289
1
—
Bit 6
Alarm Points
Bypass Overload Shutdown
—
40289
1
—
Bit 7
Bypass Phase Rotation Error
—
40289
1
—
Bit 8
Inverter Over Voltage Transfer
—
40289
1
—
Bit 9
Inverter Fuse Fail
—
40289
1
—
Bit 10
Output Over Voltage Transfer
—
40289
1
—
Bit 11
Output Under Voltage Transfer
—
40289
1
—
Bit 12
SBS SCR Open
—
40289
1
—
Bit 13
SBS SCR Short
—
40289
1
—
Bit 14
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
363
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—UPS Systems
Table 3-94 Liebert Npower™—Input and Holding—IMP (continued)
Controller Single Module Series - SMS
Liebert Products Liebert Npower - SMS
Available Points
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Inverter Over Current Transfer
—
40289
1
—
Bit 15
Equipment Over Temperature
—
40290
1
—
Bit 0
Any of Battery / Heatsink / Ambient / Timeout
Shutdown
Battery Ground Fault CB Trip
—
40290
1
—
Bit 1
—
Bit 2
Any of Input / Bypass / Output / F1 / SWGR /
MM / Option / AuEPO / LBS Power Fail
Data Description
Power Supply Fail
—
40290
1
EPO Shutdown
—
40290
1
—
Bit 3
Rectifier Fail
—
40290
1
—
Bit 4
Inverter Fail
—
40290
1
—
Bit 5
Hardware Shutdown
—
40290
1
—
Bit 6
Battery Discharge
—
40290
1
—
Bit 7
Input Current Imbalance
—
40290
1
—
Bit 8
Input Line fail
—
40290
1
—
Bit 9
Input Under Voltage
—
40290
1
—
Bit 10
Input Over Voltage
—
40290
1
—
Bit 11
Input Over Current
—
40290
1
—
Bit 12
Battery CB Open
—
40290
1
—
Bit 13
Bypass Sync Error
—
40290
1
—
Bit 14
Bypass Voltage Out of Tolerance
—
40290
1
—
Bit 15
Bypass Line Fail
—
40291
1
—
Bit 0
Inverter Over Current
—
40291
1
—
Bit 1
Output OF/UF
—
40291
1
—
Bit 2
Inverter Overload
—
40291
1
—
Bit 3
Any of Inverter Phase A / B / C Overload
Excessive Auto Retransfer
—
40291
1
—
Bit 4
Equipment Over Temperature
Warning
—
40291
1
—
Bit 5
Any of AuBattery / Ambient / Heatsink / Inlet
Over Temp Warning
Fan Fail
—
40291
1
—
Bit 6
Any of Power Pole Fan 1 / 2 / 3, Primary Fan 1 /
2 / 3 and System Fan Fail
SBS Unable
—
40291
1
—
Bit 7
Inverter Off By User
—
40291
1
—
Bit 8
Battery low Warning
—
40291
1
—
Bit 9
Battery Test Fail
—
40291
1
—
Bit 10
User Shutdown
—
40291
1
—
Bit 11
Load On Bypass
—
40291
1
—
Bit 12
Input Contact Alarms
—
40291
1
—
Bit 13
Any of Input Contact 1-8 Alarms
Generic Alarms
—
40291
1
—
Bit 14
Any other alarm conditions that are not mapped
Bypass Overload
—
40291
1
—
Bit 15
Any of Bypass A / B / C Overload
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
364
Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products
3.4 Battery Monitoring Products
Table 3-95 Alber® BDSU™—Status and Coil
Status
Coil
Number
of Bits
Notes / Units
10001-10032
—
1
Active on Alarm
High Ambient Temperature
String 1 - 32
10033-10064
—
1
Active on Alarm
Low Ambient Temperature
String 1 - 32
10065-10096
—
1
Active on Alarm
Low Ambient Temperature Probe Two
String 1 - 32
10097-10128
—
1
Active on Alarm
High Ambient Temperature Probe Two
String 1 - 32
10129-10160
—
1
Active on Alarm
Low Overall Voltage
String 1 - 32
10161-10192
—
1
Active on Alarm
High Overall Voltage
String 1 - 32
10193-10224
—
1
Active on Alarm
High Battery String Current
String 1 - 32
10225-10256
—
1
Active on Alarm
Low Battery String Float Current
String 1 - 32
10257-10288
—
1
Active on Alarm
High Battery String Float Current
String 1 - 32
10289-10320
—
1
Active on Alarm
High Battery String Ripple Current
String 1 - 32
10321-10352
—
1
Active on Alarm
Battery String Discharge Detected
String 1 - 32
10353-10384
—
1
Active on Alarm
Maximum Discharge Time Exceeded
String 1 - 32
10385-10416
—
1
Active on Alarm
Discharge Low Overall Voltage
String 1 - 32
10417-10448
—
1
Active on Alarm
Discharge Low Cell Voltage
String 1 - 32
10449-10480
—
1
Active on Alarm
Discharge High Battery String Current
String 1 - 32
10481-10512
—
1
Active on Alarm
Excessive Cell to Cell Temperature Deviation
String 1 - 32
10513-10544
—
1
Active on Alarm
Excessive Cell to Ambient Temperature Deviation
String 1 - 32
10545-10576
—
1
Active on Alarm
Thermal Runaway Detected
String 1 - 32
10577-10608
—
1
Active on Alarm
Battery String Equalize
String 1 - 32
10609-10640
—
1
Active on Alarm
Battery String Offline
String 1 - 32
10641-10672
—
1
Active on Alarm
Thermal Runaway Cell to Ambient Temperature Event
String 1 - 32
13233-13264
—
1
Active on Alarm
Thermal Runaway Cell to Cell Temperature Event
String 1 - 32
13265-13296
—
1
Active on Alarm
Thermal Runaway Charger Current Level One Event
String 1 - 32
13297-13328
—
1
Active on Alarm
Data Description
Battery Entity
Battery Discharging
Battery 1 - 32
String Entity
365
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products
Table 3-95 Alber® BDSU™—Status and Coil (continued)
Status
Coil
Number
of Bits
Notes / Units
Thermal Runaway Charger Current Level Two Event
String 1 - 32
13329-13360
—
1
Active on Alarm
Ground Fault Detected
String 1 - 32
14041-14072
—
1
Active on Alarm
Low Cell Voltage
Cell 1 - 320
10673-10992
—
1
Active on Alarm
High Cell Voltage
Cell 1 - 320
10993-11312
—
1
Active on Alarm
Low Cell Temperature
Cell 1 - 320
11313-11632
—
1
Active on Alarm
High Cell Temperature
Cell 1 - 320
11633-11952
—
1
Active on Alarm
Low Internal Resistance
Cell 1 - 320
11953-12272
—
1
Active on Alarm
High Internal Resistance
Cell 1 - 320
12273-12592
—
1
Active on Alarm
High Intercell Resistance
Cell 1 - 320
12593-12912
—
1
Active on Alarm
Discharge Low Cell Voltage
Cell 1 - 320
12913-13232
—
1
Active on Alarm
Intertier Resistance High
Cell 1 - 320
13361-13680
—
1
Active on Alarm
Low Cell Voltage
Cell 321 - 360
13681-13720
—
1
Active on Alarm
High Cell Voltage
Cell 321 – 360
13721-13760
—
1
Active on Alarm
Low Cell Temperature
Cell 321 – 360
13761-13800
—
1
Active on Alarm
High Cell Temperature
Cell 321 – 360
13801-13840
—
1
Active on Alarm
Low Internal Resistance
Cell 321 – 360
13841-13780
—
1
Active on Alarm
High Internal Resistance
Cell 321 – 360
13881-13920
—
1
Active on Alarm
High Intercell Resistance
Cell 321 – 360
13921-12860
—
1
Active on Alarm
Discharge Low Cell Voltage
Cell 321 – 360
13961-14000
—
1
Active on Alarm
Intertier Resistance High
Cell 321 - 360
14001-14040
—
1
Active on Alarm
Data Description
Cell Entity (Cells 1 – 320)
Cell Entity (Cells 321 – 360)
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
366
Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products
Table 3-96 Alber® BDSU™—Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Battery Measurement and Control
30385
—
1
—
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
Battery Name
Battery 1 - 32
30386-31057
—
21
—
Each 16-bit register is a single
Unicode character of a null
terminated string
Battery Rating
Battery 1 - 32
31186-31217
—
1
—
Units : AH
Battery Time Remaining
Battery 1 - 32
31058-31121
—
2
—
Units : sec
Battery Discharge Time
Battery 1 - 32
31122-31185
—
2
—
Units : sec
Ordinal Position of Battery
Battery 1 - 32
31218-31249
—
1
—
—
Battery String Name
String 1 - 32
31250-31921
—
21
—
Each 16-bit register is a single
Unicode character of a null
terminated string
Installation Date
String 1 - 32
33170-33233
—
2
—
Secs since Epoch(UTC)
Cell/Monobloc Rating
String 1 - 32
33234-33265
—
1
—
Units : AH
String Ambient Temperature 1
String 1 - 32
31922-31953
—
1
Scale :
x / 10
Units : deg C
String Ambient Temperature 2
String 1 - 32
31954-31985
—
1
Scale :
x / 10
Units : deg C
String Ambient Temperature 1
String 1 - 32
31986-32017
—
1
Scale :
x / 10
Units : deg F
String Ambient Temperature 2
String 1 - 32
32018-32049
—
1
Scale :
x / 10
Units : deg F
String Overall Voltage
String 1 - 32
32050-32081
—
1
Scale :
x / 10
Units : VDC
String Current
String 1 - 32
32082-32113
—
1
—
Units : A DC
Float Current
String 1 - 32
32114-32145
—
1
—
Units : mA DC
Ripple Current
String 1 - 32
32146-32177
—
1
—
Units : A AC
Total Active Alarms on a Battery String
String 1 - 32
32178-32209
—
1
—
Units : 0
Discharge State
String 1 - 32
32210-32241
—
1
—
0 = Not In Progress
1 = In Progress
Battery String Discharge Time
String 1 - 32
32338-32401
—
2
—
Units : sec
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
33042-33073
—
1
—
Units : deg C
System Status
Battery Entity
String Entity
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
367
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products
Table 3-96 Alber® BDSU™—Input and Holding (continued)
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
33074-33105
—
1
—
Units : deg F
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
33106-33137
—
1
—
Units : deg C
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
33138-33169
—
1
—
Units : deg F
—
43490-43521
1
—
2 = Reset
4 = Acknowledge
Battery String Time-To-Go
String 1 - 32
32242-32305
—
2
—
Units : min
Amp-Hours Remaining in Battery String
String 1 - 32
32306-32337
—
1
—
Units : AH
Low Ambient Temperature Global
Threshold
String 1 - 32
32402-32433
—
1
Scale :
x / 10
Units : deg C
Low Ambient Temperature Global
Threshold
String 1 - 32
32434-32465
—
1
Scale :
x / 10
Units : deg F
High Ambient Temperature Global
Threshold
String 1 - 32
32466-32497
—
1
Scale :
x / 10
Units : deg C
High Ambient Temperature Global
Threshold
String 1 - 32
32498-32529
—
1
Scale :
x / 10
Units : deg F
Battery String Overall Voltage Low
Threshold
String 1 - 32
32530-32561
—
1
Scale :
x / 10
Units : VDC
Battery String Overall Voltage High
Threshold
String 1 - 32
32562-32593
—
1
Scale :
x / 10
Units : VDC
Battery String Current High Threshold
String 1 - 32
32594-32625
—
1
—
Units : A DC
Battery String Float Current Low Threshold
String 1 - 32
32626-32657
—
1
—
Units : mA DC
Battery String Float Current High Threshold
String 1 - 32
32658-32689
—
1
—
Units : mA DC
Battery String Ripple Current High
Threshold
String 1 - 32
32690-32721
—
1
—
Units : A AC
Cell Voltage Low Global Threshold
String 1 - 32
32722-32753
—
1
Scale :
x/
1000
Units : VDC
Cell Voltage High Global Threshold
String 1 - 32
32754-32785
—
1
Scale :
x/
1000
Units : VDC
Cell Temperature Low Global Threshold
String 1 - 32
32786-32817
—
1
Scale :
x / 10
Units : deg C
Cell Temperature Low Global Threshold
String 1 - 32
32818-32849
—
1
Scale :
x / 10
Units : deg F
Cell Temperature High Global Threshold
String 1 - 32
32850-32881
—
1
Scale :
x / 10
Units : deg C
Data Description
Battery String Alarm Reset or Acknowledge
String 1 - 32
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
368
Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products
Table 3-96 Alber® BDSU™—Input and Holding (continued)
Input
Register
Holding
Register
# of
Reg.
Cell Temperature High Global Threshold
String 1 - 32
32882-32913
—
Internal Resistance Low Global Threshold
String 1 - 32
32914-32945
Internal Resistance High Global Threshold
String 1 - 32
Scale
Notes / Units
1
Scale :
x / 10
Units : deg F
—
1
—
Units : microOhm
32946-32977
—
1
—
Units : microOhm
Intercell Resistance High Global Threshold
String 1 - 32
32978-33009
—
1
—
Units : microOhm
Intertier Resistance High Global Threshold
String 1 - 32
33010-33041
—
1
—
Units : microOhm
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
39027-39058
—
1
Scale :
x / 10
Units : deg C
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
39059-39090
—
1
Scale :
x / 10
Units : deg F
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39091-39122
—
1
Scale :
x / 10
Units : deg C
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39123-39154
—
1
Scale :
x / 10
Units : deg F
Discharge Low Cell Voltage Threshold
String 1 - 32
33266-33297
—
1
Scale :
x/
1000
Units : VDC
Discharge Low Overall Voltage Threshold
String 1 - 32
33298-33329
—
1
Scale :
x / 10
Units : VDC
Discharge Battery String Current High
Threshold
String 1 - 32
33330-33361
—
1
—
Units : A DC
Discharge Maximum Time
String 1 - 32
33362-33393
—
1
—
Units : min
Startup Date
String 1 - 32
33394-33457
—
2
—
Secs since Epoch(UTC)
Battery String Commissioned Status
String 1 - 32
33458-33489
—
1
—
0 = Not Commissioned
1 = Commissioned
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
39027-39058
—
1
Scale :
x / 10
Units : deg C
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
39059-39090
—
1
Scale :
x / 10
Units : deg F
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39091-39122
—
1
Scale :
x / 10
Units : deg C
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39123-39152
—
1
Scale :
x / 10
Units : deg F
Ordinal Position of String
String 1 - 32
33522-33553
—
1
—
—
Index of Parent Battery
String 1 - 32
33554-33585
—
1
—
—
Data Description
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
369
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products
Table 3-96 Alber® BDSU™—Input and Holding (continued)
Input
Register
Holding
Register
# of
Reg.
Cell Voltage
Cell 1 - 320
33586-33905
—
Cell Temperature
Cell 1 - 320
33906-34225
Cell Temperature
Cell 1 - 320
Scale
Notes / Units
1
Scale :
x/
1000
Units : VDC
—
1
Scale :
x / 10
Units : deg C
34226-34545
—
1
Scale :
x / 10
Units : deg F
Internal Resistance Value
Cell 1 - 320
34546-34865
—
1
—
Units : microOhm
Intercell Resistance Value
Cell 1 - 320
34866-35185
—
1
—
Units : microOhm
Cell Voltage Low Threshold
Cell 1 - 320
35186-35505
—
1
Scale :
x/
1000
Units : VDC
Cell Voltage High Threshold
Cell 1 - 320
35506-35825
—
1
Scale :
x/
1000
Units : VDC
Cell Temperature Low Threshold
Cell 1 - 320
35826-36145
—
1
Scale :
x / 10
Units : deg C
Cell Temperature Low Threshold
Cell 1 - 320
36146-36465
—
1
Scale :
x / 10
Units : deg F
Cell Temperature High Threshold
Cell 1 - 320
36466-36785
—
1
Scale :
x / 10
Units : deg C
Cell Temperature High Threshold
Cell 1 - 320
36786-37105
—
1
Scale :
x / 10
Units : deg F
Internal Resistance Low Threshold
Cell 1 - 320
37106-37425
—
1
—
Units : microOhm
Internal Resistance High Threshold
Cell 1 - 320
37426-37745
—
1
—
Units : microOhm
Intercell Resistance High Threshold
Cell 1 - 320
37746-38065
—
1
—
Units : microOhm
Ordinal Position of Cell
Cell 1 - 320
38066-38385
—
1
—
—
Index of Parent String
Cell 1 - 320
38386-38705
—
1
—
Index of Parent Battery
Cell 1 - 320
38706-39025
—
1
—
Cell Voltage
Cell 321 - 360
39155-39194
—
1
Scale :
x/
1000
Units : VDC
Cell Temperature
Cell 321 – 360
39195-39234
—
1
Scale :
x / 10
Units : deg C
Cell Temperature
Cell 321 – 360
39235-39274
—
1
Scale :
x / 10
Units : deg F
Internal Resistance Value
Cell 321 – 360
39275-39314
—
1
—
Units : microOhm
Intercell Resistance Value
Cell 321 – 360
39315-39354
—
1
—
Units : microOhm
Cell Voltage Low Threshold
Cell 321 – 360
39355-39394
—
1
Scale :
x/
1000
Units : VDC
Data Description
Cell Entity (Cells 1 – 320)
Cell Entity (Cells 321 – 360)
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
370
Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products
Table 3-96 Alber® BDSU™—Input and Holding (continued)
Input
Register
Holding
Register
# of
Reg.
Cell Voltage High Threshold
Cell 321 – 360
39395-39434
—
Cell Temperature Low Threshold
Cell 321 – 360
39435-39474
Cell Temperature Low Threshold
Cell 321 – 360
Scale
Notes / Units
1
Scale :
x/
1000
Units : VDC
—
1
Scale :
x / 10
Units : deg C
39475-39514
—
1
Scale :
x / 10
Units : deg F
Cell Temperature High Threshold
Cell 321 - 360
39515-39554
—
1
Scale :
x / 10
Units : deg C
Cell Temperature High Threshold
Cell 321 – 360
39555-39594
—
1
Scale :
x / 10
Units : deg F
Internal Resistance Low Threshold
Cell 321 – 360
39595-39634
—
1
—
Units : microOhm
Internal Resistance High Threshold
Cell 321 – 360
39635-39674
—
1
—
Units : microOhm
Intercell Resistance High Threshold
Cell 321 – 360
39675-39714
—
1
—
Units : microOhm
Ordinal Position of Cell
Cell 321 – 360
39715-39754
—
1
—
—
Index of Parent String
Cell 321 – 360
39755-39794
—
1
—
—
Index of Parent Battery
Cell 321 - 360
39795-39834
—
1
—
—
Data Description
Device Status and Control
Group Status
39026
—
1
—
1 = Normal Operation
2 = StartUp
4 = Unknown - No System
Support for System Status
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
64 = Unknown Communication Failure
39998
49998
2
—
Secs since Epoch(UTC)
UXCM Device
System Date and Time
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
371
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products
Page intentionally left blank.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
372
BACnet Communications—BACnet Protocol Implementation Conformance Statement
4.0 BACnet Communications
4.1 BACnet Protocol Implementation Conformance Statement
The Liebert IntelliSlot IS-UNITY-DP™, IS-WEBADPT, and IS-IPBML cards provide BACnet IP to Emerson
Network Power® devices via the BACnet protocol. The IS-UNITY-DP card supports the BACnet MSTP
protocol as well. Data points of the managed device are mapped to BACnet objects that are automatically
created in the card when the device is discovered.
The BACnet implementation does not include a BACnet Broadcast Management Device (BBMD).
The IS-UNITY-DP and IS-IPBML cards support Foreign Device Registration. They allow you to register as
a Foreign Device, add the IP address of the BBMD, and set the Foreign Device Time-to-Live.
The BACnet protocol support in the IS-UNITY-DP card has been tested by the BACnet Testing
Laboratories (BTL) and certified to be compliant with the BACnet protocol standards. The BACnet
Protocol Implementation Conformance Statement for the IS-UNITY-DP card is available to download from
our public product website found here.
The following sections contain the BACnet implementation listings of Services and Objects supported in
the IS-WEBADPT and IS-IPBML cards.
4.1.1
Segmentation Capability
Not supported.
4.1.2
Supported Services
Service
Alarm and Event Services
• AcknowledgeAlarm
• ConfirmedCOVNotification
• UnconfirmedCOVNotification
• ConfirmedEventNotification
• UnconfirmedEventNotification
• GetAlarmSummary
• GetEnrollmentSummary
• GetEventInformation
• LifeSafetyOperation
• SubscribeCOV
• SubscribeCOVProperty
File Access Services
• AtomicReadFile
• AtomicWriteFile
Object Access Services
• AddListElement
• RemoveListElement
• CreateObject
• DeleteObject
• ReadProperty
• ReadPropertyConditional
• ReadPropertyMultiple
• WriteProperty
• WritePropertyMultiple
• ReadRange
Initiate
Execute
—
x
x
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
x
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
x
—
x
x
x
—
373
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—BACnet Protocol Implementation Conformance Statement
Service
Initiate
Execute
—
—
—
—
—
—
—
—
—
x
—
x
—
—
—
—
—
—
x (IS-IPBML, IS-UNITY-DP only)
x (IS-IPBML, IS-UNITY-DP only)
x
—
x
—
—
—
—
—
—
—
Remote Device Management Services
• DeviceCommunicationControl
• ConfirmedPrivateTransfer
• UnconfirmedPrivateTransfer
• ReinitializeDevice
• ConfirmedTextMessage
• UnconfirmedTextMessage
• TimeSynchronization
• UTCTimeSynchronization
• Who-Has
• I-Have
• Who-Is
• I-Am
Virtual Terminal Services
• VT-Open
• VT-Close
• VT-Data
4.1.3
Standard Object Types SupportedObject Properties
Object Type
X = Supported
Accumulator
Analog Input
Analog Output
Analog Value
Averaging
Binary Input
Binary Output
Binary Value
Calendar
Command
Device
Event Enrollment
File
Group
Life Safety Point
Life Safety Zone
Loop
Multistate Input
Multistate Output
Multistate Value
Notification Class
Program
Pulse Converter
Schedule
Trend Log
Access Door
Event Log
Load Control
Structured View
Trend Log Multiple
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
—
X
X
X
—
X
X
X
—
—
X
—
—
—
—
—
—
X
X
X
—
—
—
—
—
—
—
—
—
—
374
BACnet Communications—BACnet Protocol Implementation Conformance Statement
The following object properties are supported.
NOTE
All properties are read-only unless otherwise noted
Device Object
The Device object represents the agent (the card) rather than the managed device.
Device Object Property
Comments
Object_Identifier
The card must be configured with a unique Device Instance Number to avoid
interference with other cards on the same BACnet network.
Object_Name
Writable. If the Device Object Name is changed from the default, the configured name
must be unique to avoid interference with other cards on the same BACnet network.
Object_Type
—
System_Status
—
Vendor_Name
—
Vendor_Identifier
—
Model_Name
—
Firmware_Revision
—
Application_Software_Version
—
Location
—
Description
—
Protocol_Version
—
Protocol_Revision
—
Protocol_Services_Supported
—
Protocol_Object_Types_Supported
—
Object_List
—
Max_APDU_Length_Accepted
—
Segmentation_Supported
—
Local_Time
—
Local_Date
—
UTC_Offset
—
Daylight_Savings_Status
—
APDU_Timeout
Writable. Range: 1-65,535 ms. Default 3000 ms.
Number_Of_APDU_Retries
Writable. Range: 0-8. Default 3.
Device_Address_Binding
—
Database_Revision
—
Active_COV_Subscriptions
—
375
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—BACnet Protocol Implementation Conformance Statement
Analog Object
Analog Object
Property
Analog Analog Analog
Input Output Value
Comments
Object_Identifier
x
x
x
—
Object_Name
x
x
x
—
Object_Type
x
x
x
—
Writable if any of these conditions apply:
• Object is Analog Output
• Object is Analog Value and associated device Data Description is
writable
• Out_Of_Service is True
Present_Value
x
x
x
Description
x
x
x
—
Status_Flags
x
x
x
—
Event_State
x
x
x
—
Reliability
x
x
x
—
Out_Of_Service
x
x
x
Units
x
Priority_Array
Writable. Values: True/False. Default: False.
x
x
x
(x)
Support for this property on Analog Value objects is device-dependent.
Support for this property on Analog Value objects is device-dependent. The
value is equal to the Present_Value so that if all entries in the Priority_Array
are relinquished, the Present_Value does not change.
Relinquish_Default
—
x
(x)
COV_Increment
x
x
x
See Units below this table.
Writable. Default: 0.5.
Units
Possible values of the Units property include the BACnet Engineering Units defined in the BACnet
standard, plus these additional proprietary units values:
Value
256
Units
Ampere-Hours
257
MilliHertz (.001 Hertz)
258
GigaHertz (1,000,000,000 Hertz)
259
PSI - Absolute
260
Total Harmonic Distortion (%)
261
Microhms (.000001 Ohms)
262
Bytes
263
Kilobytes
264
Megabytes
265
Gigabytes
266
Terabytes
267
Volt-Ampere-Hours
268
Kilovolt-Ampere-Hours
269
Volt-Ampere-Reactive-Hours
270
Kilovolt-Ampere-Reactive-Hours
271
Grams of Water per Cubic Meter of Air
272
Torrs
273
MilliTorrs
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
376
BACnet Communications—BACnet Protocol Implementation Conformance Statement
Binary Object Properties
Binary Object
Property
Binary Binary Binary
Input Output Value
Comments
Object_Identifier
x
x
x
—
Object_Name
x
x
x
—
Object_Type
x
x
x
—
Writable if any of these conditions apply:
• Object is Binary Output
• Object is Binary Value and associated device Data Description is writable
• Out_Of_Service is True
Present_Value
x
x
x
Description
x
x
x
—
Status_Flags
x
x
x
—
Event_State
x
x
x
—
Reliability
x
x
x
—
Out_Of_Service
x
x
x
Polarity
x
x
—
—
Inactive_Text
x
x
x
—
Writable. Values: True/False. Default: False.
Active_text
x
x
x
Priority_Array
—
x
(x)
Support for this property on Binary Value objects is device-dependent.
—
Relinquish_Default
—
x
(x)
Support for this property on Binary Value objects is device-dependent. The
value is equal to the Present_Value so that if all entries in the Priority_Array
are relinquished, the Present_Value does not change.
Multistate Object Properties
Multistate Object
Property
Multistate Multistate Multistate
Input
Output
Value
Comments
Object_Identifier
x
x
x
—
Object_Name
x
x
x
—
Object_Type
x
x
x
—
Writable if any of these conditions apply:
• Object is Multistate Output
• Object is Multistate Value and associated device Data
Description is writable
• Out_Of_Service is True
Present_Value
x
x
x
Description
x
x
x
—
Status_Flags
x
x
x
—
Event_State
x
x
x
—
Reliability
x
x
x
—
Out_Of_Service
x
x
x
Number_Of_States
x
x
x
State_Text
x
x
x
Priority_Array
Relinquish_Default
—
—
x
x
Writable. Values: True/False. Default: False.
—
—
(x)
Support for this property on Multistate Value objects is devicedependent.
(x)
Support for this property on Multistate Value objects is devicedependent. The value is equal to the Present_Value so that if all
entries in the Priority_Array are relinquished, the Present_Value
does not change.
377
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
4.2 Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data
Controller Liebert iCOM® v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes
(See
Table 4-2)
Air: Supply Air
Supply Air Over Temperature
Supply Air Under Temperature
Supply Air Sensor Issue
Binary_Value
Binary_Value
Binary_Value
1
5015_1_1
2
5019_1_1
3
5026_1_1
RD
RD
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Air: Return Air
Return Air Over Temperature
Return Air Under Temperature
Return Air Sensor Issue
Binary_Value
Binary_Value
Binary_Value
14
15
16
5023_1_1
5335_1_1
5147_1_1
RD
RD
RD
Air: External Sensors
Ext Air Sensor A Over Temperature
Binary_Value
Ext Air Sensor A Under Temperature Binary_Value
27
28
4601_1_1
4608_1_1
RD
RD
Ext Air Sensor A Issue
Binary_Value
29
4618_1_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Ambient Air Sensor Issue
Binary_Value
30
5573_1_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 9, 11,
12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
378
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes
(See
Table 4-2)
Humidity
High Return Humidity
Binary_Value
41
5034_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Low Return Humidity
Binary_Value
42
5036_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Dew Point Over Temperature
Binary_Value
43
5578_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Dew Point Under Temperature
Binary_Value
44
5579_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Return Humidity Sensor Issue
Binary_Value
45
5902_1
RD
Active on Alarm
3, 5, 6, 7, 8,
11, 12, 13,
14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Humidity: External Sensors
Ext Air Sensor A High Humidity
Binary_Value
53
5349_1_1
RD
Ext Air Sensor A Low Humidity
Binary_Value
54
5351_1_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Ext Dew Point Over Temperature
Binary_Value
55
4615_1_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Ext Dew Point Under Temperature
Binary_Value
56
5577_1_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressors
Ext Compressor Lockout
Compressor Capacity Reduced
Binary_Value
Binary_Value
65
66
379
5067_1
5513_1
RD
RD
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes
(See
Table 4-2)
Compressor 1
Compressor Hours Exceeded
Compressor High Head Pressure
Compressor Low Suction Pressure
Compressor Short Cycle
Compressor Pump Down Issue
Compressor Thermal Overload
Dig Scroll Comp Discharge Temp
Sensor Issue
Dig Scroll Comp Over Temp
Compressor Low Pressure
Transducer Issue
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
77
78
79
80
81
82
83
84
85
5269_1_1
5270_1_1
5271_1_1
5352_1_1
5146_1_1
5272_1_1
5354_1_1
5355_1_1
5514_1_1
RD
RD
RD
RD
RD
RD
RD
RD
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressor High Pressure
Transducer Issue
Binary_Value
86
5148_1_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressor Superheat Over
Threshold
Binary_Value
87
5604_1_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Compressor Low Differential
Pressure Lockout
Binary_Value
88
5903_1_1
RD
Active on Alarm
6, 7, 8, 11,
12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
380
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes
(See
Table 4-2)
Compressor 2
Compressor Hours Exceeded
Compressor High Head Pressure
Compressor Low Suction Pressure
Compressor Short Cycle
Compressor Pump Down Issue
Compressor Thermal Overload
Dig Scroll Comp Discharge Temp
Sensor Issue
Dig Scroll Comp Over Temp
Compressor Low Pressure
Transducer Issue
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
97
98
99
100
101
102
103
104
105
5269_1_2
5270_1_2
5271_1_2
5352_1_2
5146_1_2
5272_1_2
5354_1_2
5355_1_2
5514_1_2
RD
RD
RD
RD
RD
RD
RD
RD
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressor High Pressure
Transducer Issue
Binary_Value
106
5148_1_2
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressor Superheat Over
Threshold
Binary_Value
107
5604_1_2
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Compressor Low Differential
Pressure Lockout
Binary_Value
108
5903_1_2
RD
Active on Alarm
6, 7, 8, 11,
12, 13, 14
381
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes
(See
Table 4-2)
Free Cooling/Chilled Water
Free Cooling Valve Hours Exceeded
Ext Free Cooling Lockout
Free Cooling Temp Sensor Issue
Binary_Value
Binary_Value
Binary_Value
117
118
119
5306_1
5361_1
5362_1
RD
RD
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Reheat
Hot Water / Hot Gas Valve Hours
Exceeded
Reheater Over Temperature
Ext Reheat Lockout
Binary_Value
Binary_Value
Binary_Value
130
131
132
5365_1
5068_1
5070_1
RD
RD
RD
Electric Reheater 1
Electric Reheater Hours Exceeded
Binary_Value
143
5368_1_1
RD
Electric Reheater 2
Electric Reheater Hours Exceeded
Binary_Value
154
5368_1_2
RD
Electric Reheater 3
Electric Reheater Hours Exceeded
Binary_Value
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
165
382
5368_1_3
RD
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes
(See
Table 4-2)
Humidifier
Humidifier Hours Exceeded
Ext Humidifier Lockout
Humidifier Control Board Not
Detected
Humidifier Cylinder Worn
Humidifier Issue
Humidifier Low Water
Humidifier Over Current
Humidifier Under Current
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
176
177
178
179
180
181
182
183
5037_1
5044_1
5045_1
5042_1
5043_1
5041_1
5040_1
5039_1
RD
RD
RD
RD
RD
RD
RD
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Dehumidifier
Dehumidifier Hours Exceeded
Binary_Value
194
383
5038_1
RD
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Instance
Object
Name
Access
Notes
Extra
Notes
(See
Table 4-2)
Fan
Fan Hours Exceeded
Main Fan Overload
Fan Issue
Binary_Value
205
Binary_Value
206
5054_1
5376_1
RD
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Binary_Value
207
4729_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Binary_Value
219
5072_1
RD
Active on Alarm
1, 2, 4, 6, 10
Condensers
Condenser VFD Issue
Ext Condenser Pump High Water
Binary_Value
220
5106_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
External Condenser TVSS Issue
Binary_Value
1060
6105_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
External Condenser VFD Issue
Binary_Value
1061
6106_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Condenser 1
Condenser Issue
Binary_Value
231
5377_1_1
RD
Condenser 2
Condenser Issue
Binary_Value
242
5377_1_2
RD
Unit Events
Customer Input 1
Customer Input 2
Binary_Value
Binary_Value
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
253
254
384
4270_1
4271_1
RD
RD
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Customer Input 3
Customer Input 4
Ext Loss of Air Blower
Ext Loss of Flow
Ext Standby Glycol Pump On
BMS Communications Timeout
Ext Standby Unit On
Clogged Air Filter
Loss of Air Flow
Service Required
Master Unit Communication Lost
RAM Battery Issue
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Instance
255
256
257
258
259
260
261
262
263
264
265
266
385
Object
Name
4272_1
4273_1
5415_1
5105_1
5107_1
5115_1
5416_1
5118_1
5053_1
4726_1
5120_1
5119_1
Access
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
Notes
Extra
Notes
(See
Table 4-2)
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Shutdown - Loss Of Power
High Power Shutdown
Smoke Detected
Supply Chilled Water Loss of Flow
Supply Chilled Water Over Temp
Unit Code Missing
Unit Communication Lost
Water Leakage Detector Sensor
Issue
Water Under Floor
Ext Over Temperature
Instance
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
267
268
269
270
271
272
273
274
275
276
Object
Name
4714_1
5121_1
4720_1
4980_1
4626_1
5418_1
5419_1
5114_1
4723_1
5104_1
Access
RD
RD
RD
RD
RD
RD
RD
RD
RD
RD
Notes
Extra
Notes
(See
Table 4-2)
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
External Fire Detected
Binary_Value
277
5108_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Unspecified General Event
Binary_Value
278
5588_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
386
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Extra
Notes
(See
Table 4-2)
Object Type
Instance
Object
Name
Access
Notes
Temperature Control Sensor Issue
Binary_Value
279
5617_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Airflow Sensor Issue
Binary_Value
280
5906_1
RD
Active on Alarm
3, 5, 6, 7, 8,
11, 12, 13,
14
Ext Air Damper Position Issue
Binary_Value
281
5907_1
RD
Active on Alarm
3, 5, 6, 7, 8,
9, 11, 12,
13, 14
Ext Power Source A Failure
Binary_Value
282
5908_1
RD
Active on Alarm
3, 5, 6, 7, 8,
11, 12, 13,
14
Ext Power Source B Failure
Binary_Value
283
5909_1
RD
Active on Alarm
3, 5, 6, 7, 8,
11, 12, 13,
14
Mixed Mode Lockout
Binary_Value
284
5924_1
RD
Active on Alarm
6, 7, 8, 11,
12, 13, 14
Binary_Value
288
4703_1_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 11,
12, 13, 14
Binary_Value
299
4703_1_2
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 11,
12, 13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Unit Events: Chilled Water Valve 1
Chilled Water Control Valve Failure
Unit Events: Chilled Water Valve 2
Chilled Water Control Valve Failure
Unit Events: Messages
Unit Off
Unit On
Unit Partial Shutdown
Unit Shutdown
Unit Standby
Binary_Value
Binary_Value
Binary_Value
Binary_Value
Binary_Value
310
311
312
313
314
387
5110_1_1
5109_1_1
5112_1_1
5113_1_1
5111_1_1
RD
RD
RD
RD
RD
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Object Type
Maintenance Due
Maintenance Completed
Instance
Binary_Value
Binary_Value
315
316
Object
Name
5116_1_1
5117_1_1
Access
RD
RD
Notes
Extra
Notes
(See
Table 4-2)
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Unit Events: iCOM DO Board 1
Digital Output Board Not Detected
Binary_Value
327
5417_1_1
RD
Unit Events: iCOM DO Board 2
Digital Output Board Not Detected
Binary_Value
338
5417_1_2
RD
Unit Events: iCOM DO Board 3
Binary_Value
349
5417_1_3
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Remote Sensor Average Over
Temperature
Binary_Value
361
5593_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Average Under
Temperature
Binary_Value
362
5594_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor System Average
Over Temperature
Binary_Value
363
5595_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor System Average
Under Temperature
Binary_Value
364
5596_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Over Temperature
Binary_Value
376
5597_1_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Under Temperature
Binary_Value
377
5598_1_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 10,
11, 12, 13,
14
Digital Output Board Not Detected
Remote Sensors
Remote Sensor 1
Remote Sensor Issue
Binary_Value
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
378
388
5060_1_1
RD
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Extra
Notes
(See
Table 4-2)
Object Type
Instance
Object
Name
Access
Notes
Remote Sensor Over Temperature
Binary_Value
390
5597_1_2
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Under Temperature
Binary_Value
391
5598_1_2
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Issue
Binary_Value
392
5060_1_2
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Over Temperature
Binary_Value
502
5597_1_10
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Under Temperature
Binary_Value
503
5598_1_10
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Issue
Binary_Value
504
5060_1_10
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Air Economizer Emergency Override Binary_Value
516
5600_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor 2
Remote Sensor 10
Air Economizer
Binary_Value
517
5601_1
RD
Active on Alarm
2, 3, 4, 5, 6,
7, 8, 9, 10,
11, 12, 13,
14
Binary_Value
540
5625_1
RD
Active on Alarm
4, 6, 7, 8,
11, 13, 14
Static Pressure Sensor Issue
Binary_Value
563
5629_1
RD
Active on Alarm
3, 5, 6, 7, 8,
9, 11, 12,
13, 14
High Static Pressure
Binary_Value
564
5630_1
RD
Active on Alarm
3, 5, 6, 7, 8,
11, 12, 13,
14
Low Static Pressure
Binary_Value
565
5631_1
RD
Active on Alarm
3, 5, 6, 7, 8,
11, 12, 13,
14
Static Pressure Sensor Out of
Range
Binary_Value
566
5910_1
RD
Active on Alarm
3, 5, 6, 7, 8,
9, 11, 12,
13, 14
Binary_Value
623
5636_1
RD
Active on Alarm
4, 6, 7, 8,
11, 13, 14
Air Economizer Reduced Airflow
Electronic Expansion Valves
EEV Unspecified General Event
Static Pressure
EconoPhase
Pump Unspecified General Event
389
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Extra
Notes
(See
Table 4-2)
Object Type
Instance
Object
Name
Access
Notes
Input Undervoltage
Binary_Value
1001
5568_1
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Modbus Power Meter
Communication Lost
Binary_Value
1040
5967_1
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Input Undervoltage
Binary_Value
1002
5568_2
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Modbus Power Meter
Communication Lost
Binary_Value
1041
5967_2
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Input Undervoltage
Binary_Value
1006
5568_6
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Modbus Power Meter
Communication Lost
Binary_Value
1045
5967_6
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Fluid Temperature Sensor Issue
Binary_Value
1021
5911_1
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Fluid Flow Sensor Issue
Binary_Value
1022
5912_1
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Fluid Temperature Sensor Issue
Binary_Value
1031
5911_2
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Fluid Flow Sensor Issue
Binary_Value
1032
5912_2
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Binary_Value
1050
5966_1_1
RD
Active on Alarm
5, 8, 11, 12,
13, 14
Binary_Value
643
5637_1
RD
Active on Alarm
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
Condenser Outside Air Temp Out of
Operating Range
Binary_Value
1082
5536_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Control Board Issue
Binary_Value
1084
5537_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Outside Air Temp
Sensor Issue
Binary_Value
1086
5535_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Communication Lost
Binary_Value
1088
5531_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Power Measurement 1
Power Measurement 2
Power Measurement 6
Fluid 1
Fluid 2
Air: Auxiliary Air
Aux Air Temp Device
Communication Lost
Liebert Condensers
Condenser Unit Unspecified General
Event
Liebert Condenser 1
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
390
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Condenser Remote Shutdown
Extra
Notes
(See
Table 4-2)
Object Type
Instance
Object
Name
Access
Notes
Binary_Value
1090
6100_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Binary_Value
218
5073_1_1
RD
Active on Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Condenser Outside Air Temp Out of
Operating Range
Binary_Value
1083
5536_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Control Board Issue
Binary_Value
1085
5537_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Outside Air Temp
Sensor Issue
Binary_Value
1087
5535_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Communication Lost
Binary_Value
1089
5531_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Remote Shutdown
Binary_Value
1091
6100_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser TVSS Issue
Binary_Value
1092
5073_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Circuit Unspecified
General Event
Binary_Value
644
5638_1_1
RD
Active on Alarm
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
Condenser Refrigerant Pressure
Sensor Issue
Binary_Value
1104
5541_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Refrigerant Pressure
Under Threshold
Binary_Value
1106
5540_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Refrigerant Pressure
Over Threshold
Binary_Value
1108
5539_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant Temp
Sensor Issue
Binary_Value
1110
5544_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant
Under Temp
Binary_Value
1112
5543_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser TVSS Issue
Liebert Condenser 2
Liebert Condenser Circuit 1
391
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Extra
Notes
(See
Table 4-2)
Object Type
Instance
Object
Name
Access
Notes
Binary_Value
1114
5542_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Max Fan Speed Override Binary_Value
1116
5545_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant Over
Temp
Liebert Condenser Circuit 2
Condenser Circuit Unspecified
General Event
Binary_Value
896
5638_1_2
RD
Active on Alarm
Condenser Refrigerant Pressure
Sensor Issue
Binary_Value
1105
5541_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Refrigerant Pressure
Under Threshold
Binary_Value
1107
5540_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Refrigerant Pressure
Over Threshold
Binary_Value
1109
5539_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant Temp
Sensor Issue
Binary_Value
1111
5544_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant
Under Temp
Binary_Value
1113
5543_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant Over
Temp
Binary_Value
1115
5542_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Max Fan Speed Override Binary_Value
1117
5545_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Binary_Value
1128
5277_1_1_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Binary_Value
1129
5277_1_1_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Binary_Value
1131
5277_1_1_4
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Binary_Value
1132
5277_1_2_1
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Liebert Condenser 1: Fan 1
Condenser Fan Issue
Liebert Condenser 1: Fan 2
Condenser Fan Issue
Liebert Condenser1: Fan 4
Condenser Fan Issue
Liebert Condenser 2: Fan 1
Condenser Fan Issue
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
392
BACnet Communications—Thermal Management Products
Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™,
Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued)
Controller Liebert iCOM® v4
Data Description
Extra
Notes
(See
Table 4-2)
Object Type
Instance
Object
Name
Access
Notes
Binary_Value
1133
5277_1_2_2
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Binary_Value
1135
5277_1_2_4
RD
Active on Alarm
3, 5, 7, 8, 9,
11, 12, 13,
14
Compressor 1B Thermal Overload
Binary_Value
1146
6092_1
RD
Active on Alarm
9
Compressor 2B Thermal Overload
Binary_Value
1147
6093_1
RD
Active on Alarm
9
Compressor 1B Hours Exceeded
Binary_Value
1148
6094_1
RD
Active on Alarm
9
Compressor 2B Hours Exceeded
Binary_Value
1149
6095_1
RD
Active on Alarm
9
Team Static Pressure Sensor
Failure
Binary_Value
1150
6303_1
RD
Active on Alarm
9
Heating Lockout
Binary_Value
1151
6304_1
RD
Active on Alarm
9
Free Cooling Stopped - High Room
Temp
Binary_Value
1152
6305_1
RD
Active on Alarm
9
Binary_Value
1163
6306_1_1
RD
Active on Alarm
9
Binary_Value
1174
6309_1_1
RD
Active on Alarm
9
Binary_Value
1185
6309_1_2
RD
Active on Alarm
9
Binary_Value
1196
6309_1_3
RD
Active on Alarm
9
Binary_Value
1207
6310_1
RD
Active on Alarm
9
Liebert Condenser 2: Fan 2
Condenser Fan Issue
Liebert Condenser 2: Fan 4
Condenser Fan Issue
PCW-PDX
PCW-PDX - Cold Aisle
Cold Aisle Temperature/Humidity
Team Sensor Failure
PCW-PDX - Cold Aisle Sensor 1
Cold Aisle Air Sensor Failure
PCW-PDX Cold Aisle Sensor 2
Cold Aisle Air Sensor Failure
PCW-PDX Cold Aisle Sensor 3
Cold Aisle Air Sensor Failure
Chilled Water
Chilled Water Inlet Temperature
Control Active
Chilled Water - Chilled Water Circuit 1
Chilled Water Inlet Temperature
Sensor Failure
Binary_Value
1218
6313_1_1
RD
Active on Alarm
Chilled Water Outlet Temperature
Sensor Failure
Binary_Value
1219
6314_1_1
RD
Active on Alarm
Chilled Water Flow Meter Sensor
Failure
Binary_Value
1220
6315_1_1
RD
Active on Alarm
Chilled Water - Chilled Water Circuit 2
Chilled Water Inlet Temperature
Sensor Failure
Binary_Value
1231
6313_1_2
RD
Active on Alarm
Chilled Water Outlet Temperature
Sensor Failure
Binary_Value
1232
6314_1_2
RD
Active on Alarm
Chilled Water Flow Meter Sensor
Failure
Binary_Value
1233
6315_1_2
RD
Active on Alarm
393
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-2
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Extra Notes key to Table 4-1
Description
This point is supported on: iCOM controller version 1.04.042.STD
This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version
2.00.12R (for Japan and China – language corrections only)
This point is supported on: iCOM controller version 2.01.29.07R
This point is supported on: iCOM controller version 2.02.21R
This point is supported on: iCOM controller version 2.01.45R
This point is supported on: iCOM controller version 2.03.27.06R
This point is supported on: iCOM controller version 2.03.33R
This point is supported on: iCOM controller version 2.04.32R
This point is supported on: iCOM controller version A9HB-1.04.23-R (Similar to Liebert PDX
and to be replaced by separate family branch.)
This point is supported on: iCOM controller version 1.04.37O-STD
This point is supported on: iCOM controller version 2.05.12T
This point is supported on: iCOM controller version 2.01.53R
This point is supported on: iCOM controller version 2.04.???R (TBD)
This point is supported on: iCOM controller version 2.05.19R
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra
Notes
(see
Table 4-4)
Air
Air Temperature Set Point
Air Temperature Set Point
Analog_Value
Analog_Value
Air Temperature Proportional Band Analog_Value
Air Temperature Proportional Band Analog_Value
Air Temperature Dead Band
Air Temperature Dead Band
Analog_Value
Analog_Value
1
5008_1
10001
2
5325_1
10002
3
5325_1_deg_F
5011_1
10003
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
5008_1_deg_F
394
5011_1_deg_F
RW
RW
RW
RW
RW
RW
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Air Temperature Control
Integration Time
Today's High Air Temperature
Today's High Air Temperature
Today's High Air Temperature
Time
Today's Low Air Temperature
Today's Low Air Temperature
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Today's Low Air Temperature Time Analog_Value
Instance
4
Object Name
5326_1
5
5327_1
10005
6
5327_1_deg_F
5328_1
7
5329_1
10007
8
5329_1_deg_F
5330_1
Access
Notes
Extra
Notes
(see
Table 4-4)
Units: min
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
Units: Seconds
since Midnight
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
Units: Seconds
since Midnight
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
RD
RD
Air: Supply Air
Supply Air Temperature
Analog_Value
19
5002_1_1
RD
Supply Air Temperature
Analog_Value
10019
5002_1_1_deg_F
RD
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Supply Air Temperature Set Point
Analog_Value
20
5331_1_1
RW
Units: deg C
1, 9, 10
Supply Air Temperature Set Point
Analog_Value
10020
5331_1_1_deg_F
RW
Units: deg F
1, 9, 10
High Supply Air Temperature
Threshold
Analog_Value
21
5014_1_1
RW
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
High Supply Air Temperature
Threshold
Analog_Value
10021
5014_1_1_deg_F
RW
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Low Supply Air Temperature
Threshold
Analog_Value
22
5018_1_1
RW
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
395
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Low Supply Air Temperature
Threshold
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
Analog_Value
10022
5018_1_1_deg_F
RW
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Air: Return Air
High Return Air Temperature
Threshold
High Return Air Temperature
Threshold
Low Return Air Temperature
Threshold
Low Return Air Temperature
Threshold
Analog_Value
Analog_Value
Analog_Value
Analog_Value
33
5022_1_1
10033
34
5022_1_1_deg_F
5334_1_1
10034
5334_1_1_deg_F
RW
RW
RW
RW
Air: External Sensors
Ext Air Sensor A Temperature
Ext Air Sensor A Temperature
Ext Air Sensor B Temperature
Ext Air Sensor B Temperature
Ext Air Sensor C Temperature
Ext Air Sensor C Temperature
Ext Air Sensor A Over Temp
Threshold
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
45
4594_1_1
10045
46
4597_1_1
10046
47
4597_1_1_deg_F
5336_1_1
10047
48
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
4594_1_1_deg_F
5336_1_1_deg_F
5337_1_1
396
RD
RD
RD
RD
RD
RD
RW
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Ext Air Sensor A Over Temp
Threshold
Ext Air Sensor A Under Temp
Threshold
Analog_Value
Analog_Value
Instance
10048
49
Object Name
5337_1_1_deg_F
5338_1_1
Access
RW
RW
Notes
Extra
Notes
(see
Table 4-4)
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Ext Air Sensor A Under Temp
Threshold
Analog_Value
10049
5338_1_1_deg_F
RW
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Outside Air Temperature
Analog_Value
50
5574_1_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Outside Air Temperature
Analog_Value
10050
5574_1_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Humidity
Return Humidity
Analog_Value
60
5028_1
RD
Humidity Set Point
Analog_Value
61
5029_1
RW
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Return Humidity Set Point
Analog_Value
62
5339_1
RW
Units: % RH
1, 9, 10
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: min
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Humidity Proportional Band
Humidity Dead Band
Humidity Control Integration Time
High Return Humidity Threshold
Low Return Humidity Threshold
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
63
5341_1
64
5032_1
65
5342_1
66
5033_1
67
5035_1
397
RW
RW
RW
RW
RW
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Today's High Humidity
Today's High Humidity Time
Today's Low Humidity
Analog_Value
Analog_Value
Analog_Value
Instance
68
Object Name
5343_1
69
5344_1
70
5345_1
Access
Notes
Extra
Notes
(see
Table 4-4)
RD
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
Units: Seconds
since Midnight
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Today's Low Humidity Time
Analog_Value
71
5346_1
RD
Units: Seconds
since Midnight
Dew Point Proportional Band
Analog_Value
72
6258_1
RW
Units: deg C
11, 14
Dew Point Proportional Band
Analog_Value
10072
6258_1_deg_F
RW
Units: deg F
11, 14
Dew Point Dead Band
Analog_Value
73
6259_1
RW
Units: deg C
11, 14
Dew Point Dead Band
Analog_Value
10073
6259_1_deg_F
RW
Units: deg F
11, 14
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Humidity: External Sensors
Ext Air Sensor A Humidity
Ext Air Sensor B Humidity
Ext Air Sensor C Humidity
Ext Air Sensor A High Humidity
Threshold
Analog_Value
Analog_Value
Analog_Value
Analog_Value
82
4595_1_1
83
4598_1_1
84
5347_1_1
85
5348_1_1
RD
RD
RD
RW
Ext Air Sensor A Low Humidity
Threshold
Analog_Value
86
5350_1_1
RW
Units: % RH
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Ext Air Sensor A Dew Point Temp
Analog_Value
87
4596_1_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Ext Air Sensor A Dew Point Temp
Analog_Value
10087
4596_1_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
398
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
Ext Dew Point Over Temp
Threshold
Analog_Value
88
4614_1_1
RW
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Ext Dew Point Over Temp
Threshold
Analog_Value
10088
4614_1_1_deg_F
RW
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Ext Dew Point Under Temp
Threshold
Analog_Value
89
5576_1_1
RW
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Ext Dew Point Under Temp
Threshold
Analog_Value
10089
5576_1_1_deg_F
RW
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressor 1
Compressor Hours
Compressor Hours Threshold
Dig Scroll Comp Discharge Temp
Analog_Value
Analog_Value
Analog_Value
97
5267_1_1
98
5268_1_1
99
5353_1_1
RW
RW
RD
Dig Scroll Comp Discharge Temp
Analog_Value
10099
5353_1_1_deg_F
RD
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Digital Scroll Compressor Loading
Analog_Value
100
5619_1_1
RD
Units: %
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
Tandem 'B' Compressor Hours
Analog_Value
101
6241_1_1
RW
Units: hr
8, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressor 2
Compressor Hours
Compressor Hours Threshold
Dig Scroll Comp Discharge Temp
Analog_Value
Analog_Value
Analog_Value
110
5267_1_2
111
5268_1_2
112
5353_1_2
399
RW
RW
RD
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra
Notes
(see
Table 4-4)
Dig Scroll Comp Discharge Temp
Analog_Value
10112
5353_1_2_deg_F
RD
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Digital Scroll Compressor Loading
Analog_Value
113
5619_1_2
RD
Units: %
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
Tandem 'B' Compressor Hours
Analog_Value
114
6241_1_2
RW
Units: hr
8, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Free Cooling/Chilled Water
Free Cooling Internal Temperature
Delta
Free Cooling Internal Temperature
Delta
Free Cooling Fluid Temperature
Free Cooling Fluid Temperature
Minimum Chilled Water Temp Set
Point
Minimum Chilled Water Temp Set
Point
Free Cooling Valve Hours
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
Analog_Value
123
5356_1
10123
124
5356_1_deg_F
5358_1
10124
125
5358_1_deg_F
5360_1
10125
126
5360_1_deg_F
5304_1
RW
RW
RD
RD
RW
RW
RW
Free Cooling Valve Hours
Threshold
Analog_Value
127
5305_1
RW
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Chilled Water Valve Hours
Analog_Value
128
5614_1
RW
Units: hr
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Chilled Water Valve Operating
Hours Threshold
Analog_Value
129
6452_1
RW
Units: hr
12, 13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
400
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra
Notes
(see
Table 4-4)
Reheat
Hot Water / Hot Gas Valve Hours
Hot Water / Hot Gas Valve Hours
Threshold
Analog_Value
Analog_Value
138
5363_1
139
5364_1
RW
RW
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Electric Reheater 1
Electric Reheater Hours
Electric Reheater Hours Threshold
Analog_Value
Analog_Value
150
5366_1_1
151
5367_1_1
RW
RW
Electric Reheater 2
Electric Reheater Hours
Electric Reheater Hours Threshold
Analog_Value
Analog_Value
162
5366_1_2
163
5367_1_2
RW
RW
Electric Reheater 3
Electric Reheater Hours
Electric Reheater Hours Threshold
Analog_Value
Analog_Value
174
5366_1_3
175
5367_1_3
RW
RW
Humidifier
Humidifier Hours
Humidifier Hours Threshold
Analog_Value
Analog_Value
186
5369_1
187
5370_1
401
RW
RW
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Infrared Humidifier Flush Rate
Analog_Value
Instance
188
Object Name
5445_1
Access
RW
Notes
Extra
Notes
(see
Table 4-4)
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Dehumidifier
Dehumidifier Hours
Dehumidifier Hours Threshold
Analog_Value
Analog_Value
199
5371_1
200
5372_1
RW
RW
Fan
Fan Speed Maximum Set Point
Fan Hours
Analog_Value
Analog_Value
211
5050_1
212
5374_1
RW
RW
Fan Hours Threshold
Analog_Value
213
5375_1
RW
Units: hr
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Fan Speed Minimum Set Point
Analog_Value
214
5051_1
RW
Units: %
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Fan Speed Temperature Set Point
Analog_Value
215
5585_1
RW
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Fan Speed Temperature Set Point
Analog_Value
10215
5585_1_deg_F
RW
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Analog Inputs 1
Analog Input Reading
Analog_Value
224
5378_1
RD
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Analog Inputs 2
Analog Input Reading
Analog_Value
235
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
5378_2
402
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra
Notes
(see
Table 4-4)
Analog Inputs 4
Analog Input Reading
Analog_Value
257
5378_4
RD
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
Units: min
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: sec
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Unit Information
BMS Timeout Period
Analog_Value
268
5075_1
Auto Restart Delay
Analog_Value
269
4710_1
RW
Standby Units
Analog_Value
270
5314_1
RW
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Unit Operations
Return Air Temperature Set Point
Analog_Value
32
5333_1
RW
Units: deg C
1, 9, 10
Return Air Temperature Set Point
Analog_Value
10032
5333_1_deg_F
RW
Units: deg F
1, 9, 10
Units: deg C
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: deg F
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Return Air Temperature
Return Air Temperature
Analog_Value
Analog_Value
31
4291_1
10031
4291_1_deg_F
RD
RD
Fan Speed
Analog_Value
280
5077_1
RD
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressor Utilization
Analog_Value
281
5078_1
RD
Units: %
1, 9, 10
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Free Cooling Valve Open Position
Maintenance Ramp
Calculated Next Maintenance
Month
Analog_Value
Analog_Value
Analog_Value
282
5379_1
283
4870_1
284
4868_1
403
RD
RD
RD
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Calculated Next Maintenance Year Analog_Value
Hot Water / Hot Gas Valve Open
Position
Reheat Utilization
Humidifier Utilization
Analog_Value
Analog_Value
Analog_Value
Instance
285
Object Name
4869_1
286
5380_1
287
5080_1
288
5081_1
Access
Notes
Extra
Notes
(see
Table 4-4)
RD
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
RD
Dehumidifier Utilization
Analog_Value
289
5079_1
RD
Units: %
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Cooling Capacity
Analog_Value
290
5490_1
RD
Units: %
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Adjusted Humidity
Analog_Value
291
5606_1
RD
Units: % RH
2, 3, 4, 5, 6,
7, 8, 9, 10,
11, 12, 13,
14
Return Dew Point
Analog_Value
292
5004_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Return Dew Point
Analog_Value
10292
5004_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Actual Air Temperature Set Point
Analog_Value
293
5607_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Actual Air Temperature Set Point
Analog_Value
10293
5607_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Actual Humidity Set Point
Analog_Value
294
5608_1
RD
Units: % RH
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Dew Point Set Point
Analog_Value
295
5575_1
RW
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Dew Point Set Point
Analog_Value
10295
5575_1_deg_F
RW
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
404
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
Cooling Control Temperature
Analog_Value
296
5615_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Cooling Control Temperature
Analog_Value
10296
5615_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Fan Speed Control Temperature
Analog_Value
297
5616_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Fan Speed Control Temperature
Analog_Value
10297
5616_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Unit Cooling Load
Analog_Value
298
5904_1
RD
Units: kW
5, 8, 11, 12,
13, 14
Unit Calculated Airflow
Analog_Value
299
6134_1
RD
Units: m3/h
12, 13, 14
Time
System Date and Time
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Analog_Value
300
4293_1
RW
Remote Sensor Over Temp
Threshold
Analog_Value
312
5589_1
RW
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Over Temp
Threshold
Analog_Value
10312
5589_1_deg_F
RW
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Under Temp
Threshold
Analog_Value
313
5590_1
RW
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Under Temp
Threshold
Analog_Value
10313
5590_1_deg_F
RW
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Average
Temperature
Analog_Value
314
5007_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Average
Temperature
Analog_Value
10314
5007_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Maximum
Temperature
Analog_Value
315
5006_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Maximum
Temperature
Analog_Value
10315
5006_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor System Average
Temperature
Analog_Value
316
5591_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensors
405
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
Remote Sensor System Average
Temperature
Analog_Value
10316
5591_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor System Maximum
Temperature
Analog_Value
317
5592_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor System Maximum
Temperature
Analog_Value
10317
5592_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Temperature
Analog_Value
329
5059_1_1
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Temperature
Analog_Value
10329
5059_1_1_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Temperature
Analog_Value
341
5059_1_2
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Temperature
Analog_Value
10341
5059_1_2_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Temperature
Analog_Value
437
5059_1_10
RD
Units: deg C
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Remote Sensor Temperature
Analog_Value
10437
5059_1_10_deg_F
RD
Units: deg F
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Static Pressure Set Point
Analog_Value
461
5626_1
RW
Units: Pa
3, 5, 7, 8, 9,
11, 12, 13,
14
Unit Static Pressure
Analog_Value
462
5627_1
RD
Units: Pa
3, 5, 7, 8,
11, 12, 13,
14
System Static Pressure
Analog_Value
463
5628_1
RD
Units: Pa
3, 5, 7, 8, 9,
11, 12, 13,
14
Static Pressure Set Point
Analog_Value
2121
5626_1
RW
Units: Pa
3, 5, 7, 8, 9,
11, 12, 13,
14
Unit Static Pressure
Analog_Value
2122
5627_1
RD
Units: Pa
3, 5, 7, 8,
11, 12, 13,
14
Remote Sensor 1
Remote Sensor 2
Remote Sensor 10
Static Pressure
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
406
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
Analog_Value
2123
5628_1
RD
Units: Pa
3, 5, 7, 8, 9,
11, 12, 13,
14
Pump Hours
Analog_Value
523
5298_1_1
RW
Units: hr
6, 7, 8, 11,
13, 14
Pump Speed
Analog_Value
522
5634_1_1
RD
Units: %
13, 14
Pump Inlet Refrigerant
Temperature
Analog_Value
535
5635_1_1
RD
Units: deg C
13, 14
Pump Inlet Refrigerant
Temperature
Analog_Value
10535
5635_1_1_deg_F
RD
Units: deg F
13, 14
Pump Outlet Refrigerant
Temperature
Analog_Value
537
5639_1_1
RD
Units: deg C
13, 14
Pump Outlet Refrigerant
Temperature
Analog_Value
10537
5639_1_1_deg_F
RD
Units: deg F
13, 14
Pump Hours
Analog_Value
526
5298_1_2
RW
Units: hr
6, 7, 8, 11,
13, 14
Pump Speed
Analog_Value
525
5634_1_2
RD
Units: %
13, 14
Pump Inlet Refrigerant
Temperature
Analog_Value
538
5635_1_2
RD
Units: deg C
13, 14
Pump Inlet Refrigerant
Temperature
Analog_Value
10538
5635_1_2_deg_F
RD
Units: deg F
13, 14
Pump Outlet Refrigerant
Temperature
Analog_Value
540
5639_1_2
RD
Units: deg C
13, 14
Pump Outlet Refrigerant
Temperature
Analog_Value
10540
5639_1_2_deg_F
RD
Units: deg F
13, 14
System Input RMS A-N
Analog_Value
810
4096_1
RD
Units: VAC
5, 8, 9, 11,
12, 13, 14
System Input RMS B-N
Analog_Value
811
4098_1
RD
Units: VAC
5, 8, 9, 11,
12, 13, 14
System Input RMS C-N
Analog_Value
812
4100_1
RD
Units: VAC
5, 8, 9, 11,
12, 13, 14
System Input RMS Current Phase
A
Analog_Value
813
4113_1
RD
Units: A AC
5, 8, 9, 11,
12, 13, 14
System Input RMS Current Phase
B
Analog_Value
814
4114_1
RD
Units: A AC
5, 8, 9, 11,
12, 13, 14
System Input RMS Current Phase
C
Analog_Value
815
4115_1
RD
Units: A AC
5, 8, 9, 11,
12, 13, 14
Instantaneous Power
Analog_Value
816
5901_1
RD
Units: W
5, 8, 9, 11,
12, 13, 14
Energy Consumption
Analog_Value
817
5900_1
RW
Units: kWH
5, 8, 9, 11,
12, 13, 14
System Input RMS A-B
Analog_Value
1900
4097_1
RD
Units: VAC
5, 8, 9, 11,
12, 13, 14
System Static Pressure
EconoPhase: Pump 1
EconoPhase: Pump 2
Power Measurement 1
407
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
System Input RMS B-C
Analog_Value
1901
4099_1
RD
Units: VAC
5, 8, 9, 11,
12, 13, 14
System Input RMS C-A
Analog_Value
1902
4101_1
RD
Units: VAC
5, 8, 9, 11,
12, 13, 14
System Input RMS A-N
Analog_Value
820
4096_2
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS B-N
Analog_Value
821
4098_2
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS C-N
Analog_Value
822
4100_2
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS Current Phase
A
Analog_Value
823
4113_2
RD
Units: A AC
5, 8, 11, 12,
13, 14
System Input RMS Current Phase
B
Analog_Value
824
4114_2
RD
Units: A AC
5, 8, 11, 12,
13, 14
System Input RMS Current Phase
C
Analog_Value
825
4115_2
RD
Units: A AC
5, 8, 11, 12,
13, 14
Instantaneous Power
Analog_Value
826
5901_2
RD
Units: W
5, 8, 11, 12,
13, 14
Energy Consumption
Analog_Value
827
5900_2
RW
Units: kWH
5, 8, 11, 12,
13, 14
System Input RMS A-B
Analog_Value
1910
4097_2
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS B-C
Analog_Value
1911
4099_2
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS C-A
Analog_Value
1912
4101_2
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS A-N
Analog_Value
860
4096_6
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS B-N
Analog_Value
861
4098_6
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS C-N
Analog_Value
862
4100_6
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS Current Phase
A
Analog_Value
863
4113_6
RD
Units: A AC
5, 8, 11, 12,
13, 14
System Input RMS Current Phase
B
Analog_Value
864
4114_6
RD
Units: A AC
5, 8, 11, 12,
13, 14
System Input RMS Current Phase
C
Analog_Value
865
4115_6
RD
Units: A AC
5, 8, 11, 12,
13, 14
Instantaneous Power
Analog_Value
866
5901_6
RD
Units: W
5, 8, 11, 12,
13, 14
Energy Consumption
Analog_Value
867
5900_6
RW
Units: kWH
5, 8, 11, 12,
13, 14
System Input RMS A-B
Analog_Value
1950
4097_6
RD
Units: VAC
5, 8, 11, 12,
13, 14
Power Measurement 2
Power Measurement 10
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
408
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
System Input RMS B-C
Analog_Value
1951
4099_6
RD
Units: VAC
5, 8, 11, 12,
13, 14
System Input RMS C-A
Analog_Value
1952
4101_6
RD
Units: VAC
5, 8, 11, 12,
13, 14
Fluid Input Temperature
Analog_Value
871
5897_1
RD
Units: deg C
5, 8, 11, 12,
13, 14
Fluid Input Temperature
Analog_Value
10871
5897_1_deg_F
RD
Units: deg F
5, 8, 11, 12,
13, 14
Fluid Output Temperature
Analog_Value
872
5898_1
RD
Units: deg C
5, 8, 11, 12,
13, 14
Fluid Output Temperature
Analog_Value
10872
5898_1_deg_F
RD
Units: deg F
5, 8, 11, 12,
13, 14
Fluid Input Temperature
Analog_Value
1871
5897_2
RD
Units: deg C
5, 8, 11, 12,
13, 14
Fluid Input Temperature
Analog_Value
11871
5897_2_deg_F
RD
Units: deg F
5, 8, 11, 12,
13, 14
Fluid Output Temperature
Analog_Value
1872
5898_2
RD
Units: deg C
5, 8, 11, 12,
13, 14
Fluid Output Temperature
Analog_Value
11872
5898_2_deg_F
RD
Units: deg F
5, 8, 11, 12,
13, 14
Analog_Value
881
5899_1
RD
Units: l/min
5, 8, 11, 12,
13, 14
Analog_Value
891
5899_2
RD
Units: l/min
5, 8, 11, 12,
13, 14
Analog_Value
901
5905_1_1
RD
Units: kW
5, 8, 11, 12,
13, 14
Analog_Value
911
5905_1_2
RD
Units: kW
5, 8, 11, 12,
13, 14
Raw Auxiliary Air Temperature
Analog_Value
1960
5964_1_1
RW
Units: deg C
5, 8, 11, 12,
13, 14
Raw Auxiliary Air Temperature
Analog_Value
11960
5964_1_1_deg_F
RW
Units: deg F
5, 8, 11, 12,
13, 14
Actual Auxiliary Air Temperature
Analog_Value
1961
5965_1_1
RD
Units: deg C
5, 8, 11, 12,
13, 14
Actual Auxiliary Air Temperature
Analog_Value
11961
5965_1_1_deg_F
RD
Units: deg F
5, 8, 11, 12,
13, 14
Fluid 1
Fluid 2
Circuit
Fluid Flow Rate
Circuit 2
Fluid Flow Rate
Unit Operations: Cooling Load 1
Circuit Cooling Load
Unit Operations: Cooling Load 2
Circuit Cooling Load
Air: Auxiliary Air
409
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object Name
Access
Analog_Value
1981
6101_1
RD
Notes
Extra
Notes
(see
Table 4-4)
Liebert Condensers
Expected Condenser Unit Count
3, 5, 7, 8, 9,
11, 12, 13,
14
Liebert Condensers: Low Noise Mode
Condenser Low Noise Mode Max
Fan Speed
Analog_Value
529
5548_1_1
RW
Units: %
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
Condenser Normal Mode Max Fan
Speed
Analog_Value
530
5549_1_1
RW
Units: %
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
Condenser Low Noise Mode Start
Time
Analog_Value
531
5552_1_1
RW
Units: Seconds
since Midnight
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
Condenser Low Noise Mode Stop
Time
Analog_Value
532
5553_1_1
RW
Units: Seconds
since Midnight
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
RW
1 = Monday 2 =
Tuesday 4 =
Wednesday 8 = 3, 4, 5, 6, 7,
Thursday 16 =
8, 11, 12,
13, 14
Friday 32 =
Saturday 64 =
Sunday
1 = Monday 2 =
Tuesday 4 =
Wednesday 8 = 3, 4, 5, 6, 7,
Thursday 16 =
8, 11, 12,
Friday 32 =
13, 14
Saturday 64 =
Sunday
Condenser Low Noise Mode Interval Days
Condenser Low Noise Mode - Full
Days
Analog_Value
533
5550_1_1
Analog_Value
534
5551_1_1
RW
Condenser Outside Air
Temperature
Analog_Value
1992
5534_1_1
RD
Units: deg C
3, 5, 7, 8,
11, 12, 13,
14
Condenser Outside Air
Temperature
Analog_Value
11992
5534_1_1_deg_F
RD
Units: deg F
3, 5, 7, 8,
11, 12, 13,
14
Condenser Outside Air
Temperature
Analog_Value
1993
5534_1_2
RD
Units: deg C
3, 5, 7, 8,
11, 12, 13,
14
Condenser Outside Air
Temperature
Analog_Value
11993
5534_1_2_deg_F
RD
Units: deg F
3, 5, 7, 8,
11, 12, 13,
14
Liebert Condenser 1
Liebert Condenser 2
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
410
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
Condenser Refrigerant Pressure
Analog_Value
2004
6103_1_1
RD
Units: bar
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant
Temperature
Analog_Value
2006
6102_1_1
RD
Units: deg C
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant
Temperature
Analog_Value
12006
6102_1_1_deg_F
RD
Units: deg F
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Refrigerant Pressure
Analog_Value
2005
6103_1_2
RD
Units: bar
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant
Temperature
Analog_Value
2007
6102_1_2
RD
Units: deg C
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Supply Refrigerant
Temperature
Analog_Value
12007
6102_1_2_deg_F
RD
Units: deg F
3, 5, 7, 8, 9,
11, 12, 13,
14
Condenser Fan Speed
Analog_Value
2018
5276_1_1_1
RD
Units: %
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Power
Analog_Value
2026
5538_1_1_1
RD
Units: W
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Current
Analog_Value
2034
6244_1_1_1
RD
Units: A AC
8, 11, 13,
14
Condenser Fan Speed
Analog_Value
2019
5276_1_1_2
RD
Units: %
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Power
Analog_Value
2027
5538_1_1_2
RD
Units: W
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Current
Analog_Value
2035
6244_1_1_2
RD
Units: A AC
8, 11, 13,
14
Condenser Fan Speed
Analog_Value
2021
5276_1_1_4
RD
Units: %
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Power
Analog_Value
2029
5538_1_1_4
RD
Units: W
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Current
Analog_Value
2037
6244_1_1_4
RD
Units: A AC
8, 11, 13,
14
Liebert Condenser Circuit 1
Liebert Condenser Circuit 2
Liebert Condenser 1 Fan 1
Liebert Condenser 1 Fan 2
Liebert Condenser 1 Fan 4
411
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Extra
Notes
(see
Table 4-4)
Object Type
Instance
Object Name
Access
Notes
Condenser Fan Speed
Analog_Value
2022
5276_1_2_1
RD
Units: %
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Power
Analog_Value
2030
5538_1_2_1
RD
Units: W
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Current
Analog_Value
2038
6244_1_2_1
RD
Units: A AC
8, 11, 13,
14
Condenser Fan Speed
Analog_Value
2023
5276_1_2_2
RD
Units: %
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Power
Analog_Value
2031
5538_1_2_2
RD
Units: W
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Current
Analog_Value
2039
6244_1_2_2
RD
Units: A AC
8, 11, 13,
14
Condenser Fan Speed
Analog_Value
2025
5276_1_2_4
RD
Units: %
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Power
Analog_Value
2033
5538_1_2_4
RD
Units: W
3, 5, 7, 8,
11, 12, 13,
14
Condenser Fan Current
Analog_Value
2041
6244_1_2_4
RD
Units: A AC
8, 11, 13,
14
Liebert Condenser 2 Fan 1
Liebert Condenser 2 Fan 2
Liebert Condenser 2 Fan 4
PCW-PDX
Actual Cold Aisle Humidity
Analog_Value
2044
6085_1
RD
Units: % RH
9
Actual Cold Aisle Temperature
Analog_Value
2045
6086_1
RD
Units: deg C
9
Actual Cold Aisle Temperature
Analog_Value
12045
6086_1_deg_F
RD
Units: deg F
9
Cold Aisle Cascade Fan Speed
Max Set Point
Analog_Value
2046
6087_1
RD
Units: %
9
Cold Aisle Fan Speed Min Set
Point
Analog_Value
2047
6088_1
RD
Units: %
9
Cold Aisle Fan Speed Max Set
Point
Analog_Value
2048
6089_1
RD
Units: %
9
Humidification Fan Speed Min Set
Point
Analog_Value
2049
6096_1
RD
Units: %
9
Heating Fan Speed Min Set Point
Analog_Value
2050
6097_1
RD
Units: %
9
Dehumidification Fan Speed Min
Set Point
Analog_Value
2051
6098_1
RD
Units: %
9
Back Draft Control Fan Speed
Analog_Value
2052
6099_1
RD
Units: %
9
Air Filter Differential Pressure
Analog_Value
2053
6302_1
RD
Units: Pa
9
Air Filter Differential Pressure
Analog_Value
2213
6302_1
RD
Units: Pa
9
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
412
BACnet Communications—Thermal Management Products
Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object Name
Access
Notes
Extra
Notes
(see
Table 4-4)
Analog_Value
2100
6234_1
RD
Units: %
9, 11, 14
Thermal Control Override Temperature Call
Analog_Value
2135
6263_1
RW
Units: %
11, 14
Thermal Control Override Humidity Call
Analog_Value
2136
6265_1
RW
Units: %
11, 14
Super Saver
Super Saver Call For Cooling
Thermal Control Override
PCW-PDX - Cold Aisle Sensor 1
Cold Aisle Sensor Air Temperature Analog_Value
2147
6307_1_1
RD
Units: deg C
9
Cold Aisle Sensor Air Temperature Analog_Value
12147
6307_1_1_deg_F
RD
Units: deg F
9
Cold Aisle Sensor Humidity
2148
6308_1_1
RD
Units: % RH
9
Analog_Value
PCW-PDX - Cold Aisle Sensor 2
Cold Aisle Sensor Air Temperature Analog_Value
2159
6307_1_2
RD
Units: deg C
9
Cold Aisle Sensor Air Temperature Analog_Value
12159
6307_1_2_deg_F
RD
Units: deg F
9
Cold Aisle Sensor Humidity
2160
6308_1_2
RD
Units: % RH
9
Analog_Value
PCW-PDX - Cold Aisle Sensor 3
Cold Aisle Sensor Air Temperature Analog_Value
2171
6307_1_3
RD
Units: deg C
9
Cold Aisle Sensor Air Temperature Analog_Value
12171
6307_1_3_deg_F
RD
Units: deg F
9
Cold Aisle Sensor Humidity
2172
6308_1_3
RD
Units: % RH
9
Analog_Value
Chilled Water - Chilled Water Circuit 1
Chilled Water Inlet Temperature
Analog_Value
2189
6311_1_1
RD
Units: deg C
9
Chilled Water Inlet Temperature
Analog_Value
12189
6311_1_1_deg_F
RD
Units: deg F
9
Chilled Water Outlet Temperature
Analog_Value
2190
6312_1_1
RD
Units: deg C
9
Chilled Water Outlet Temperature
Analog_Value
12190
6312_1_1_deg_F
RD
Units: deg F
9
Units: deg C
9
Chilled Water - Chilled Water Circuit 2
Chilled Water Inlet Temperature
Analog_Value
2201
6311_1_2
RD
Chilled Water Inlet Temperature
Analog_Value
12201
6311_1_2_deg_F
RD
Units: deg F
9
Chilled Water Outlet Temperature
Analog_Value
2202
6312_1_2
RD
Units: deg C
9
Chilled Water Outlet Temperature
Analog_Value
12202
6312_1_2_deg_F
RD
Units: deg F
9
Analog_Value
505
5299_1
RW
Units: hr
13, 14
EconoPhase
Pump Hours Threshold
413
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-4
Number
Extra Notes key to Table 4-3
Description
1
This point is supported on: iCOM controller version 1.04.042.STD
2
This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version
2.00.12R (for Japan and China – language corrections only)
3
This point is supported on: iCOM controller version 2.01.29.07R
4
This point is supported on: iCOM controller version 2.02.21R
5
This point is supported on: iCOM controller version 2.01.45R
6
This point is supported on: iCOM controller version 2.03.27.06R
7
This point is supported on: iCOM controller version 2.03.33R
8
This point is supported on: iCOM controller version 2.04.32R
9
This point is supported on: iCOM controller version A9HB-1.04.23-R (Similar to Liebert PDX
and to be replaced by separate family branch.)
10
This point is supported on: iCOM controller version 1.04.37O-STD
11
This point is supported on: iCOM controller version 2.05.12T
12
This point is supported on: iCOM controller version 2.01.53R
13
This point is supported on: iCOM controller version 2.04.???R (TBD)
14
This point is supported on: iCOM controller version 2.05.19R
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
414
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data
Controller Liebert iCOM® v4
Data Label
Object Type
Instance Object Name Access
Notes
Extra
Notes (see
Table 4-6)
Protocol
Server Class
MultiState_Value
1
4553_1
RD
1 = UPS
2 = AIR
3 = PMP
4 = PDU
5 = MONITOR
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Air
Air Temperature Control Type
MultiState_Value
12
5324_1
RW
1 = Proportional
2 = Prop+Integral
3 = Intelligent
Air Temperature Control Sensor
MultiState_Value
13
5012_1
RW
1 = Supply
2 = Remote
3 = Return
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
1, 9, 10
Air - Supply Air
Supply Air Temperature Sensor
Control
MultiState_Value
23
5332_1_1
RW
1 = Disabled
2 = Limit
3 = Control
4 = Temp Only
MultiState_Value
34
5340_1
RW
1 = Relative
2 = Compensated
3 = Predictive
1, 9, 10
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Humidity
Humidity Control Type
Humidity Control Type
MultiState_Value
35
5603_1
RW
1 = Relative
2 = Compensated
3 = Predictive
4 = Dew Point
Humidity Control Sensor
MultiState_Value
36
5618_1
RW
1 = Supply
2 = Remote
3 = Return
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
8, 11, 12,
13, 14
Compressors - Compressor 1
Compressor State
MultiState_Value
45
5264_1_1
Compressor Capacity Control
State
MultiState_Value
46
5265_1_1
RD
1 = off
2 = on
Tandem 'B' Compressor State
MultiState_Value
47
6243_1_1
RD
1 = off
2 = on
415
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance Object Name Access
Notes
Extra
Notes (see
Table 4-6)
Compressors - Compressor 2
Compressor State
MultiState_Value
57
5264_1_2
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Compressor Capacity Control
State
MultiState_Value
58
5265_1_2
RD
1 = off
2 = on
Tandem 'B' Compressor State
MultiState_Value
59
6243_1_2
RD
1 = off
2 = on
8, 11, 12,
13, 14
MultiState_Value
69
5302_1
RD
1 = off
2 = on
3 = No Support
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11
RW
1 = Disabled
2 = Contact
3 = Temperature
4 = Set Point
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Free Cooling/Chilled Water
Free Cooling Status
Free Cooling Internal Control
Mode
MultiState_Value
70
5581_1
Minimum Chilled Water Temp
Set Point Enable
MultiState_Value
71
5359_1
RW
1 = disabled
2 = enabled
Main Chilled Water Valve
MultiState_Value
72
5605_1
RW
1 = Valve 1
2 = Valve 2
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Free Cooling Status
MultiState_Value
69
6260_1
RD
1 = off
2 = start
3 = on
11, 12, 13,
14
Free Cooling Internal Control
Mode
MultiState_Value
70
5357_1
RW
1 = Disabled
2 = Contact
3 = Value
1, 9, 10
RW
1 = Auto
2 = Manual
3 = Economy
4 = Delta
1, 9, 10
RW
1 = Supply
2 = Remote
3 = Return
4 = Manual
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Fan
Fan Control Mode
Fan Control Sensor
MultiState_Value
MultiState_Value
82
5373_1
83
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
5586_1
416
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance Object Name Access
Notes
Extra
Notes (see
Table 4-6)
Unit Information
System Status
Unit Operating State
Unit Control Mode
Unit Operating State Reason
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
93
4123_1
94
4706_1
95
4707_1
96
5074_1
RD
1 = Normal
Operation
2 = StartUp
3 = Normal with
Warning
4 = Normal with
Alarm
5 = Abnormal
Operation
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = off
2 = on
= standby
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = Internal (Auto)
2 = External
(Manual)
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = Reason
Unknown
2 = Network Display 1, 2, 3, 4, 5,
3 = Alarm
6, 7, 8, 9,
4 = Schedule
10, 11, 12,
13, 14
5 = Remote System
6 = External Input
7 = Local Display
Unit Operations
Fan State
Cooling State
Free Cooling State
Maintenance Tracking State
Hot Water / Hot Gas State
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
107
5381_1
108
5382_1
109
5383_1
110
5384_1
111
5385_1
417
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Electric Reheat State
Dehumidifier State
Humidifier State
System On/Off Control
Local Fan Override
Local Cooling Override
Local Electric Heat Override
Object Type
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
Instance Object Name Access
112
5386_1
113
5387_1
114
5388_1
115
5143_1
500
6175_1
501
6176_1
502
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
6177_1
418
Notes
Extra
Notes (see
Table 4-6)
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = off
2 = on
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RD
1 = Normal operation
2 = Increased for
internal protection
3 = Decreased for
internal protection
4 = Disabled for
internal protection
5 = Limited or
disabled for low limit
protection
8, 11, 12,
13, 14
RD
1 = Normal operation
2 = Increased for
internal protection
3 = Decreased for
internal protection
4 = Disabled for
internal protection
5 = Limited or
disabled for low limit
protection
8, 11, 12,
13, 14
RD
1 = Normal operation
2 = Increased for
internal protection
3 = Decreased for
internal protection
4 = Disabled for
internal protection
5 = Limited or
disabled for low limit
protection
8, 11, 12,
13, 14
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Local Humidifier Override
Local Dehumidifier Override
Object Type
MultiState_Value
MultiState_Value
Instance Object Name Access
503
6178_1
504
6179_1
Notes
Extra
Notes (see
Table 4-6)
RD
1 = Normal operation
2 = Increased for
internal protection
3 = Decreased for
internal protection
4 = Disabled for
internal protection
5 = Limited or
disabled for low limit
protection
8, 11, 12,
13, 14
RD
1 = Normal operation
2 = Increased for
internal protection
3 = Decreased for
internal protection
4 = Disabled for
internal protection
5 = Limited or
disabled for low limit
protection
8, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
System Event Configuration
Customer Input 1 - Event Control MultiState_Value
Customer Input 1 - Event Type
MultiState_Value
Customer Input 2 - Event Control MultiState_Value
Customer Input 2 - Event Type
MultiState_Value
Customer Input 3 - Event Control MultiState_Value
Customer Input 3 - Event Type
MultiState_Value
Customer Input 4 - Event Control MultiState_Value
126
4718_1
127
4719_1
128
5098_1
129
5099_1
130
5100_1
131
5101_1
132
5102_1
419
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Customer Input 4 - Event Type
Ext Free Cooling Lockout Event Control
Ext Free Cooling Lockout Event Type
Ext Condenser Pump High
Water - Event Control
Ext Condenser Pump High
Water - Event Type
Ext Standby Glycol Pump On Event Control
Ext Standby Glycol Pump On Event Type
Ext Standby Unit On - Event
Control
Ext Standby Unit On - Event
Type
Ext Humidifier Lockout - Event
Control
Ext Humidifier Lockout - Event
Type
Object Type
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
Ext Loss of Flow - Event Control MultiState_Value
Notes
Extra
Notes (see
Table 4-6)
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Instance Object Name Access
133
5103_1
134
5389_1
135
5390_1
136
5122_1
137
5123_1
138
5129_1
139
5130_1
140
5391_1
141
5392_1
142
5086_1
143
5087_1
144
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
5082_1
420
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Ext Loss of Flow - Event Type
Ext Over Temperature - Event
Control
Ext Over Temperature - Event
Type
Ext Reheat Lockout - Event
Control
Ext Reheat Lockout - Event
Type
High Power Shutdown - Event
Control
High Power Shutdown - Event
Type
Humidifier Issue - Event Control
Humidifier Issue - Event Type
Object Type
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
Master Unit Communication Lost
MultiState_Value
- Event Control
Master Unit Communication Lost
MultiState_Value
- Event Type
Service Required - Event Control MultiState_Value
Notes
Extra
Notes (see
Table 4-6)
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Instance Object Name Access
145
5083_1
146
5090_1
147
5091_1
148
5084_1
149
5085_1
150
5141_1
151
5142_1
152
5131_1
153
5132_1
154
5133_1
155
5134_1
156
4727_1
421
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Service Required - Event Type
Shutdown - Loss Of Power Event Control
Shutdown - Loss Of Power Event Type
Object Type
MultiState_Value
MultiState_Value
MultiState_Value
Smoke Detected - Event Control MultiState_Value
Smoke Detected - Event Type
Water Under Floor - Event
Control
Water Under Floor - Event Type
MultiState_Value
MultiState_Value
MultiState_Value
Ext Compressor Lockout - Event
MultiState_Value
Control
Ext Compressor Lockout - Event
MultiState_Value
Type
Clogged Air Filter - Event
Control
Clogged Air Filter - Event Type
Ext Loss of Air Blower - Event
Control
MultiState_Value
MultiState_Value
MultiState_Value
Notes
Extra
Notes (see
Table 4-6)
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Instance Object Name Access
157
4728_1
158
4715_1
159
4716_1
160
4721_1
161
4722_1
162
4724_1
163
4725_1
164
5088_1
165
5089_1
166
5135_1
167
5136_1
168
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
5393_1
422
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Ext Loss of Air Blower - Event
Type
Object Type
MultiState_Value
Notes
Extra
Notes (see
Table 4-6)
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Instance Object Name Access
169
5394_1
System Event Configuration - Compressor 1
Compressor High Head
Pressure - Event Control
Compressor High Head
Pressure - Event Type
Compressor Low Suction
Pressure - Event Control
Compressor Low Suction
Pressure - Event Type
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
Compressor Pump Down Issue MultiState_Value
Event Control
Compressor Pump Down Issue MultiState_Value
Event Type
Compressor Short Cycle - Event
MultiState_Value
Control
Compressor Short Cycle - Event
MultiState_Value
Type
Compressor Thermal Overload MultiState_Value
Event Control
Compressor Thermal Overload MultiState_Value
Event Type
Dig Scroll Comp Discharge Over
MultiState_Value
Temp - Event Ctrl
180
5316_1_1
181
5317_1_1
182
5318_1_1
183
5319_1_1
184
5395_1_1
185
5396_1_1
186
5397_1_1
187
5398_1_1
188
5320_1_1
189
5321_1_1
190
5399_1_1
423
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Dig Scroll Comp Discharge Over
MultiState_Value
Temp - Event Type
Notes
Extra
Notes (see
Table 4-6)
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Instance Object Name Access
191
5400_1_1
System Event Configuration Compressor 2
Compressor High Head
Pressure - Event Control
Compressor High Head
Pressure - Event Type
Compressor Low Suction
Pressure - Event Control
Compressor Low Suction
Pressure - Event Type
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
Compressor Pump Down Issue MultiState_Value
Event Control
Compressor Pump Down Issue MultiState_Value
Event Type
Compressor Short Cycle - Event
MultiState_Value
Control
Compressor Short Cycle - Event
MultiState_Value
Type
Compressor Thermal Overload MultiState_Value
Event Control
Compressor Thermal Overload MultiState_Value
Event Type
Dig Scroll Comp Discharge Over
MultiState_Value
Temp - Event Ctrl
202
5316_1_2
203
5317_1_2
204
5318_1_2
205
5319_1_2
206
5395_1_2
207
5396_1_2
208
5397_1_2
209
5398_1_2
210
5320_1_2
211
5321_1_2
212
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
5399_1_2
424
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Dig Scroll Comp Discharge Over
MultiState_Value
Temp - Event Type
Notes
Extra
Notes (see
Table 4-6)
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Instance Object Name Access
213
5400_1_2
System Event Configuration - Air
Ext Air Sensor A Event Control
MultiState_Value
Return Air Sensor Event Control MultiState_Value
Ext Air Sensor A High Humidity MultiState_Value
Event Control
Ext Air Sensor A High Humidity MultiState_Value
Event Type
Ext Air Sensor A Low Humidity Event Control
Ext Air Sensor A Low Humidity Event Type
Ext Air Sensor A Over Temp Event Control
Ext Air Sensor A Over Temp Event Type
Ext Air Sensor A Under Temp Event Control
Ext Air Sensor A Under Temp Event Type
High Return Humidity - Event
Control
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
224
5401_1_1
225
5402_1_1
226
5403_1_1
227
5404_1_1
228
5405_1_1
229
5406_1_1
230
4602_1_1
231
4603_1_1
232
4609_1_1
233
4610_1_1
234
5137_1_1
425
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
High Return Humidity - Event
Type
Low Return Humidity - Event
Control
Low Return Humidity - Event
Type
Return Air Over Temp - Event
Control
Return Air Over Temp - Event
Type
Return Air Under Temp - Event
Control
Object Type
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
MultiState_Value
Notes
Extra
Notes (see
Table 4-6)
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Instance Object Name Access
235
5138_1_1
236
5139_1_1
237
5140_1_1
238
5024_1_1
239
5025_1_1
240
5407_1_1
Return Air Under Temp - Event
Type
MultiState_Value
241
5408_1_1
RW
1 = Message
2 = Warning
3 = Alarm
Supply Air Over/Under
Temperature - Event Control
MultiState_Value
242
5587_1_1
RW
1 = disabled
2 = enabled
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
System Event Configuration - Fan
Fan Hours Exceeded - Event
Control
MultiState_Value
252
5409_1_1
Fan Hours Exceeded - Event
Type
MultiState_Value
253
5410_1_1
RW
1 = Message
2 = Warning
3 = Alarm
Fan Issue - Event Control
MultiState_Value
254
4730_1_1
RW
1 = disabled
2 = enabled
1, 9, 10
RW
1 = Message
2 = Warning
3 = Alarm
1, 9, 10
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Fan Issue - Event Type
Main Fan Overload - Event
Control
MultiState_Value
MultiState_Value
255
4731_1_1
256
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
5411_1_1
426
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Main Fan Overload - Event Type MultiState_Value
Notes
Extra
Notes (see
Table 4-6)
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = disabled
2 = enabled
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
1, 2, 3, 4, 5,
6, 7, 8, 9,
10, 11, 12,
13, 14
Instance Object Name Access
257
5412_1_1
System Event Configuration - Condenser
Condenser Issue - Event Control MultiState_Value
Condenser Issue - Event Type
MultiState_Value
Condenser Issue - Event Control MultiState_Value
Condenser Issue - Event Type
MultiState_Value
268
5413_1_1
269
5414_1_1
280
5413_1_2
281
5414_1_2
Unit Events
MultiState_Value
292
4717_1
WO
1 = Reset
2 = Acknowledge
MultiState_Value
304
5580_1
RW
1 = disabled
2 = enabled
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
MultiState_Value
316
5582_1
RW
1 = disabled
2 = enabled
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
MultiState_Value
328
5583_1
RW
1 = disabled
2 = enabled
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Air Economizer Availability
MultiState_Value
340
5599_1
RD
1 = Not Available
2 = Available
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
Air Economizer Control Source
MultiState_Value
341
5602_1
RW
1 = disabled
2 = internal
3 = external
2, 3, 4, 5, 6,
7, 8, 11, 12,
13, 14
System Event
Acknowledge/Reset
Compressors
Compressor Lockout
Reheat
Reheater Lockout
Humidifier
Humidifier Lockout
Air Economizer
427
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Notes
Extra
Notes (see
Table 4-6)
RD
1 = off
2 = on
7, 8, 11, 13,
14
13, 14
Instance Object Name Access
EconoPhase - Pump 1
Pump State
PRE Operational Mode
MultiState_Value
364
5633_1_1
MultiState_Value
363
5632_1_1
RD
1 = Bootup
2 = Idle
3 = Manual
4 = Pump Automatic
5 = Test
MultiState_Value
369
5633_1_2
RD
1 = off
2 = on
7, 8, 11, 13,
14
RD
1 = Bootup
2 = Idle
3 = Manual
4 = Pump Automatic
5 = Test
13, 14
1 = R22
2 = R407C
3 = R410A
3, 5, 7, 8,
11, 12, 13,
14
EconoPhase - Pump 2
Pump State
PRE Operational Mode
MultiState_Value
368
5632_1_2
Liebert Condensers
Condenser Refrigerant Type
MultiState_Value
395
5533_1
RD
Liebert Condensers - Low Noise Mode
1 = Inactive
3, 4, 5, 6, 7,
2 = Active (Interval)
8, 11, 12,
13, 14
3 = Active (Full Day)
Condenser Low Noise Mode
State
MultiState_Value
374
5546_1_1
RD
Condenser Low Noise Mode
Schedule Control
MultiState_Value
375
5547_1_1
RW
1 = disabled
2 = enabled
3, 4, 5, 6, 7,
8, 11, 12,
13, 14
406
6104_1_1
RD
1 = false
2 = true
3, 5, 7, 8, 9,
11, 12, 13,
14
MultiState_Value
407
6104_1_2
RD
1 = false
2 = true
3, 5, 7, 8, 9,
11, 12, 13,
14
Cold Aisle Humidity Calculation
Method
MultiState_Value
438
6081_1
RD
1 = Highest
2 = Average
9
Cold Aisle Temperature
Calculation Method
MultiState_Value
439
6082_1
RD
1 = Highest
2 = Average
9
Cold Aisle Control Enable
MultiState_Value
440
6083_1
RD
1 = disabled
2 = enabled
9
Cold Aisle Force Max
Fan/Cooling - Ext Control
MultiState_Value
441
6084_1
RD
1 = disabled
2 = enabled
9
Liebert Condensers - Condenser 1
Condenser Fan Reversal
Requested
MultiState_Value
Liebert Condensers - Condenser 2
Condenser Fan Reversal
Requested
PCW-PDX
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
428
BACnet Communications—Thermal Management Products
Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance Object Name Access
Notes
Extra
Notes (see
Table 4-6)
Static Pressure Control Enable
MultiState_Value
442
6090_1
RD
1 = disabled
2 = enabled
Chilled Water Valve Reset
Enable
MultiState_Value
443
6091_1
RD
1 = disabled
2 = enabled
9
Underfloor Static Pressure
Control Enable
MultiState_Value
529
6300_1
RD
1 = disabled
2 = enabled
3 = visualization only
9
Return Damper Status
MultiState_Value
531
6301_1
RD
1 = closed
2 = open
9
Thermal Control Override
MultiState_Value
516
6261_1
RW
1 = disabled 2 =
enabled
11, 14
Thermal Control Override Temperature Control Type
MultiState_Value
517
6262_1
RW
1 = Cooling 2 =
Heating
11, 14
Thermal Control Override Humidity Control Type
MultiState_Value
518
6264_1
RW
1 = Dehumidification
2 = Humidification
11, 14
Thermal Control Override
Table 4-6
Number
Extra Notes key to Table 4-5
Description
1
This point is supported on: iCOM controller version 1.04.042.STD
2
This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version
2.00.12R (for Japan and China – language corrections only)
3
This point is supported on: iCOM controller version 2.01.29.07R
4
This point is supported on: iCOM controller version 2.02.21R
5
This point is supported on: iCOM controller version 2.01.45R
6
This point is supported on: iCOM controller version 2.03.27.06R
7
This point is supported on: iCOM controller version 2.03.33R
8
This point is supported on: iCOM controller version 2.04.32R
9
This point is supported on: iCOM controller version A9HB-1.04.23-R (Similar to Liebert PDX
and to be replaced by separate family branch.)
10
This point is supported on: iCOM controller version 1.04.37O-STD
11
This point is supported on: iCOM controller version 2.05.12T
12
This point is supported on: iCOM controller version 2.01.53R
13
This point is supported on: iCOM controller version 2.04.???R (TBD)
14
This point is supported on: iCOM controller version 2.05.19R
429
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary
Data Label
Data Description
Actual Air Temperature Set Point
The actual set point being used for air temperature control. This value may
differ from [Air Temperature Set Point] if compensation is applied by the control.
Actual Auxiliary Air Temperature
Actual auxiliary air temperature value being used for control. This value may
differ from the raw value received from the auxiliary device if filtering is applied.
Actual Cold Aisle Humidity
Actual humidity value being used for cold aisle humidity control. The value is
calculated from multiple humidity measurements using [Cold Aisle Humidity
Calculation Method].
Actual Cold Aisle Temperature
Actual temperature value being used for cold aisle temperature control. The
value is calculated from multiple temperature measurements using [Cold Aisle
Temperature Calculation Method].
Actual Humidity Set Point
The actual set point being used for humidity control. This value may differ from
[Humidity Set Point] if compensation is applied by the control.
Adjusted Humidity
Humidity value being used for control. This value may differ from the actual
measured [Return Humidity] based on several factors which may include, but
are not limited to, selection of humidity control sensor and humidity control type.
Air Economizer Availability
Indicates if the outside air conditions are appropriate for cooling with the air
economizer or glycol freecooling.
Air Economizer Control Source
Source of control of the air economizer.
Air Economizer Emergency Override
Indoor room temperature has exceeded its upper threshold and the outdoor air
damper has been opened for emergency cooling.
Air Economizer Reduced Airflow
Air economizer filter is dirty and needs to be cleaned or replaced.
Air Filter Differential Pressure
Differential pressure across the air filter.
Air Temperature Control Integration Time
Time value used when system is under integral air temperature control.
Air Temperature Control Sensor
Sensor from which air temperature measurements will be used for cooling and
heating control.
Air Temperature Control Type
Type of algorithm used to control the system's output air temperature.
Air Temperature Dead Band
Value that is divided evenly to form a temperature range above and below [Air
Temperature Set Point]. If measured air temperature is within this range, no
heating or cooling will occur.
Air Temperature Proportional Band
Value that is divided evenly to form proportional temperature control bands
above and below [Air Temperature Set Point].
Air Temperature Set Point
Desired air temperature. This set point is dependent upon which sensor is
selected for control.
Airflow Sensor Issue
Airflow sensor is disconnected or the signal is out of range.
Ambient Air Sensor Issue
Ambient air sensor is disconnected or the signal is out of range.
Analog Input Reading
Generic analog input reading (unitless).
Auto Restart Delay
If power is lost, the control will delay this amount of time after power is restored
before restarting the unit.
Aux Air Temp Device Communication Lost
Communication with external auxiliary device providing an air temperature
value has been lost.
Back Draft Control Fan Speed
Fan speed when in back draft control mode.
BMS Communications Timeout
Building Management System (or external monitoring system) has not
communicated with the system within the expected timeframe.
BMS Timeout Period
Timeframe within which the Building Management System (or external
monitoring system) must communicate with the system to avoid a timeout.
Calculated Next Maintenance Month
Calculated month of the next scheduled maintenance. Used in conjunction with
[Calculated Next Maintenance Year].
Calculated Next Maintenance Year
Calculated year of the next scheduled maintenance. Used in conjunction with
[Calculated Next Maintenance Month].
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
430
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Chilled Water Control Valve Failure
Chilled water valve out of position. Chilled water control valve position does not
match expected value.
Chilled Water Flow Meter Sensor Failure
Chilled water flow meter sensor is disconnected or the signal is out of range.
Chilled Water Inlet Temperature Control
Active
Chilled water inlet temperature control is active.
Chilled Water Inlet Temperature Sensor
Failure
Chilled water inlet temperature sensor is disconnected or the signal is out of
range.
Chilled Water Inlet Temperature
Temperature of the water entering the hydraulic circuit of the chilled water unit.
Chilled Water Outlet Temperature Sensor
Failure
Chilled water outlet temperature sensor is disconnected or the signal is out of
range.
Chilled Water Outlet Temperature
Temperature of the water exiting the hydraulic circuit of the chilled water unit.
Chilled Water Valve Hours
Operating hours for chilled water valve since last reset of this value.
Chilled Water Valve Operating Hours
Threshold
Operating hours threshold for the chilled water valve. When the number of
operating hours reaches this threshold, an event is generated.
Chilled Water Valve Reset Enable
Enable/disable the ability to reset the chilled water valve.
Circuit Cooling Load
The amount of heat energy currently being removed by a single refrigeration
circuit.
Clogged Air Filter - Event Control
Enable/disable the activation of the [Clogged Air Filter] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Clogged Air Filter - Event Type
The event type for the [Clogged Air Filter] event.
Clogged Air Filter
Air filter is dirty and needs to be (cleaned or) replaced.
Cold Aisle Air Sensor Failure
Cold aisle sensor measuring air temperature and humidity is disconnected or
the signal is out of range.
Cold Aisle Cascade Fan Speed Max Set
Point
Cold aisle maximum fan speed when system is in cascade mode and one or
more units in the system are in standby.
Cold Aisle Control Enable
Enable/disable cold aisle control.
Cold Aisle Fan Speed Max Set Point
Cold aisle maximum fan speed when system is not in cascade mode OR when
system is in cascade mode and no units in the system are in standby.
Cold Aisle Fan Speed Min Set Point
Cold aisle minimum fan speed.
Cold Aisle Force Max Fan/Cooling - Ext
Control
The cold aisle fan speed and system cooling can be forced to 100% via an
external input signal. Use this value to enable/disable that feature.
Cold Aisle Humidity Calculation Method
Algorithm used to calculate a single cold aisle humidity value from multiple
humidity measurements.
Cold Aisle Sensor Air Temperature
Air temperature measured by cold aisle sensor.
Cold Aisle Sensor Humidity
Humidity measured by cold aisle sensor.
Cold Aisle Temperature Calculation Method
Algorithm used to calculate a single cold aisle temperature value from multiple
temperature measurements.
Cold Aisle Temperature/Humidity Team
Sensor Failure
Cold aisle team sensor measuring air temperature and humidity is disconnected
or the signal is out of range.
Compressor 1B Hours Exceeded
Fixed compressor 1B run hours have exceeded the threshold.
Compressor 1B Thermal Overload
Fixed compressor 1B is shut down due to thermal overload.
Compressor 2B Hours Exceeded
Fixed compressor 2B run hours have exceeded the threshold.
Compressor 2B Thermal Overload
Fixed compressor 2B is shut down due to thermal overload.
Compressor Capacity Control State
Compressor capacity control state. When 'ON', the cooling capacity of the
compressor has been reduced.
Compressor Capacity Reduced
Compressor capacity has been reduced.
431
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Compressor High Head Pressure - Event
Control
Enable/disable the activation of the [Compressor High Head Pressure] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Compressor High Head Pressure - Event
Type
The event type for the [Compressor High Head Pressure] event.
Compressor High Head Pressure
Compressor is shut down due to high head pressure.
Compressor High Pressure Transducer
Issue
Compressor high pressure transducer is disconnected or the signal is out of
range.
Compressor Hours Exceeded
[Compressor Hours] has exceeded [Compressor Hours Threshold].
Compressor Hours Threshold
Threshold value used in the [Compressor Hours Exceeded] event.
Compressor Hours
Operating hours for compressor since last reset of this value.
Compressor Lockout
Enable/disable the use of the compressor.
Compressor Low Differential Pressure
Lockout
Compressor exceeded maximum startup attempts due to low differential
pressure. Compressor is shutdown and has been disabled.
Compressor Low Pressure Transducer
Issue
Compressor low pressure transducer is disconnected or the signal is out of
range.
Compressor Low Suction Pressure - Event
Control
Enable/disable the activation of the [Compressor Low Suction Pressure] event.
If set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Compressor Low Suction Pressure - Event
Type
The event type for the [Compressor Low Suction Pressure] event.
Compressor Low Suction Pressure
Compressor is shut down due to low suction pressure.
Compressor Pump Down Issue - Event
Control
Enable/disable the activation of the [Compressor Pump Down Issue] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Compressor Pump Down Issue - Event Type The event type for the [Compressor Pump Down Issue] event.
Compressor Pump Down Issue
Unable to pump down suction-side pressure during compressor shutdown.
Compressor Short Cycle - Event Control
Enable/disable the activation of the [Compressor Short Cycle] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Compressor Short Cycle - Event Type
The event type for the [Compressor Short Cycle] event.
Compressor Short Cycle
Compressor short cycle. A short cycle is defined as turning on and off a number
of times over a set time period.
Compressor State
Compressor operational state.
Compressor Superheat Over Threshold
Compressor discharge refrigerant superheat temperature has exceeded an
upper threshold.
Compressor Thermal Overload - Event
Control
Enable/disable the activation of the [Compressor Thermal Overload] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Compressor Thermal Overload - Event Type The event type for the [Compressor Thermal Overload] event.
Compressor Thermal Overload
Compressor is shut down due to thermal overload.
Compressor Utilization
Present compressor utilization expressed as a percentage of the maximum
rated capacity.
Condenser Circuit Unspecified General
Event
One or more unspecified condenser circuit events active. See local unit display
for further details.
Condenser Communication Lost
Communication with condenser unit has been lost.
Condenser Control Board Issue
The condenser control board is reporting an issue.
Condenser Fan Current
Condenser fan's measured input current.
Condenser Fan Issue
Condenser fan is not operating within its operational parameters.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
432
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Condenser Fan Power
Condenser fan's measured input power.
Condenser Fan Reversal Requested
Request the condenser fans to rotate in the reverse direction.
Condenser Fan Speed
Condenser fan speed expressed as a percentage of the maximum rated speed.
Condenser Issue - Event Control
Enable/disable the activation of the [Condenser Issue] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Condenser Issue - Event Type
The event type for the [Condenser Issue] event.
Condenser Issue
Condenser is not operating within its operational parameters.
Condenser Low Noise Mode - Full Days
Days of the week selected for low noise mode full day scheduling.
Condenser Low Noise Mode - Interval Days
Days of the week selected for low noise mode interval scheduling.
Condenser Low Noise Mode Max Fan
Speed
Maximum fan speed when condenser is placed in low noise mode.
Condenser Low Noise Mode Schedule
Control
Enable/disable scheduled control of condenser low noise mode.
Condenser Low Noise Mode Start Time
The time of day at which the condenser will transition into low noise mode.
Condenser Low Noise Mode State
State of condenser low noise mode scheduler control.
Condenser Low Noise Mode Stop Time
The time of day at which the condenser will transition out of low noise mode.
Condenser Max Fan Speed Override
Fan speed exceeding the maximum set point in order to alleviate a high
temperature or pressure condition.
Condenser Normal Mode Max Fan Speed
Maximum fan speed when condenser is not in low noise mode.
Condenser Outside Air Temp Out of
Operating Range
[Condenser Outside Air Temperature] is either above an upper threshold or
below a lower threshold.
Condenser Outside Air Temp Sensor Issue
Condenser outside air temperature sensor is disconnected or the signal is out
of range.
Condenser Outside Air Temperature
Condenser ambient outside air temperature.
Condenser Refrigerant Pressure Over
Threshold
Condenser refrigerant pressure has exceeded a threshold.
Condenser Refrigerant Pressure Sensor
Issue
Condenser refrigerant pressure sensor is disconnected or the signal is out of
range.
Condenser Refrigerant Pressure Under
Threshold
Condenser refrigerant pressure has dropped below a threshold.
Condenser Refrigerant Pressure
Pressure of the refrigerant in a condenser circuit.
Condenser Refrigerant Type
Condenser refrigerant type.
Condenser Remote Shutdown
Condenser is shut down by a remote signal.
Condenser Supply Refrigerant Over Temp
Condenser supply refrigerant temperature has exceeded a threshold.
Condenser Supply Refrigerant Temp Sensor Condenser supply refrigerant temperature sensor is disconnected or the signal
Issue
is out of range.
Condenser Supply Refrigerant Temperature Temperature of the supply refrigerant in a condenser circuit.
Condenser Supply Refrigerant Under Temp
Condenser supply refrigerant temperature has dropped below a specified
threshold.
Condenser TVSS Issue
The condenser Transient Voltage Surge Suppressor or Surge Protection
Device has failed.
Condenser Unit Unspecified General Event
One or more unspecified condenser unit events active. See local unit display for
further details.
Condenser VFD Issue
The condenser fan Variable Frequency Drive is offline.
Cooling Capacity
Cooling capacity in use, expressed as a percentage of the maximum rated
capacity.
433
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Cooling Control Temperature
Temperature value being used for cooling capacity control. This value is
compared against the temperature set point to determine the amount of cooling
to be applied.
Cooling State
Cooling operational state.
Customer Input 1 - Event Control
Enable/disable the activation of the [Customer Input 1] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Customer Input 1 - Event Type
The event type for the [Customer Input 1] event.
Customer Input 1
Customer Input 1
Customer Input 2 - Event Control
Enable/disable the activation of the [Customer Input 2] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Customer Input 2 - Event Type
The event type for the [Customer Input 2] event.
Customer Input 2
Customer Input 2
Customer Input 3 - Event Control
Enable/disable the activation of the [Customer Input 3] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Customer Input 3 - Event Type
The event type for the [Customer Input 3] event.
Customer Input 3
Customer Input 3
Customer Input 4 - Event Control
Enable/disable the activation of the [Customer Input 4] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Customer Input 4 - Event Type
The event type for the [Customer Input 4] event.
Customer Input 4
Customer Input 4
Dehumidification Fan Speed Min Set Point
Minimum fan speed when system dehumidification is active.
Dehumidifier Hours Exceeded
Operating hours for the dehumidifier have exceeded the threshold.
Dehumidifier Hours Threshold
Threshold value used in the [Dehumidifier Hours Exceeded] event.
Dehumidifier Hours
Operating hours for dehumidifier since last reset of this value.
Dehumidifier State
Dehumidifier operational state.
Dehumidifier Utilization
Present dehumidifier utilization expressed as a percentage of the maximum
rated capacity.
Dew Point Dead Band
Value that is divided evenly to form a range above and below [Dew Point Set
Point]. If measured humidity is within this range, no humidification or
dehumidification will occur. This parameter is used when [Humidity Control
Type] is set to Dew Point.
Dew Point Over Temperature
Dew point temperature reading has exceeded the upper threshold.
Dew Point Proportional Band
Value that is divided evenly to form proportional humidity control bands above
and below [Dew Point Set Point]. This parameter is used when [Humidity
Control Type] is set to Dew Point.
Dew Point Set Point
Desired dew point temperature.
Dew Point Under Temperature
Dew point temperature reading has dropped below the lower threshold.
Dig Scroll Comp Discharge Over Temp Event Ctrl
Enable/disable the activation of the [Dig Scroll Comp Discharge Over Temp]
event.
Dig Scroll Comp Discharge Over Temp Event Type
The event type for the [Dig Scroll Comp Discharge Over Temp] event.
Dig Scroll Comp Discharge Temp Sensor
Issue
Digital scroll compressor discharge temperature sensor is disconnected or the
signal is out of range.
Dig Scroll Comp Discharge Temp
Digital scroll compressor discharge temperature.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
434
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Dig Scroll Comp Over Temp
Digital scroll compressor is shut down due to head temperature exceeding an
upper threshold.
Digital Output Board Not Detected
Digital output board is required to be connected, but no signal is detected.
Digital Scroll Compressor Loading
Present digital scroll compressor utilization expressed as a percentage of the
maximum rated capacity.
EEV Unspecified General Event
One or more unspecified electronic expansion valve events active. See local
unit display for further details.
Electric Reheat State
Electric reheater operational state.
Electric Reheater Hours Exceeded
[Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold].
Electric Reheater Hours Threshold
Threshold value used in the [Electric Reheater Hours Exceeded] event.
Electric Reheater Hours
Operating hours for electric reheater since last reset of this value.
Energy Consumption
Energy consumption since the last reset of this value.
Expected Condenser Unit Count
Number of physical condenser units that are expected to be connected to the
system.
Ext Air Damper Position Issue
Air damper position does not match expected value, as indicated by an external
input signal.
Ext Air Sensor A Dew Point Temp
Dew point temperature as measured by external air sensor A.
Ext Air Sensor A Event Control
Enable/disable the activation of events related to measurements by the external
air sensor A.
Ext Air Sensor A High Humidity - Event
Control
Enable/disable the activation of the [Ext Air Sensor A High Humidity] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Ext Air Sensor A High Humidity - Event Type The event type for the [Ext Air Sensor A High Humidity] event.
Ext Air Sensor A High Humidity Threshold
Threshold value used in the [External Air Sensor A High Humidity] event.
Ext Air Sensor A High Humidity
[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity
Threshold].
Ext Air Sensor A Humidity
Relative humidity as measured by external air sensor A.
Ext Air Sensor A Issue
The external air sensor A is disconnected or the signal is out of range.
Ext Air Sensor A Low Humidity - Event
Control
Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Ext Air Sensor A Low Humidity - Event Type The event type for the [Ext Air Sensor A Low Humidity] event.
Ext Air Sensor A Low Humidity Threshold
Threshold value used in the [External Air Sensor A Low Humidity] event.
Ext Air Sensor A Low Humidity
[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity
Threshold].
Enable/disable the activation of the [External Air Sensor A Over Temperature]
Ext Air Sensor A Over Temp - Event Control event. If set to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history list.
Ext Air Sensor A Over Temp - Event Type
The event type for the [External Air Sensor A Over Temperature] event.
Ext Air Sensor A Over Temp Threshold
Threshold value used in the [External Air Sensor A Over Temperature] event.
Ext Air Sensor A Over Temperature
[Ext Air Sensor A Temperature] has exceeded [External Air Sensor A Over
Temp Threshold].
Ext Air Sensor A Temperature
Air temperature as measured by external air sensor A.
Ext Air Sensor A Under Temp - Event
Control
Enable/disable the activation of the [Ext Air Sensor A Under Temperature]
event. If set to 'disabled', the event will not be annunciated. This implies that the
event will not be placed in any active event list or in any event history list.
Ext Air Sensor A Under Temp - Event Type
The event type for the [Ext Air Sensor A Under Temperature] event.
Ext Air Sensor A Under Temp Threshold
Threshold value used in the [External Air Sensor A Under Temperature] event.
435
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Ext Air Sensor A Under Temperature
[Ext Air Sensor A Temperature] has dropped below [Ext Air Sensor A Under
Temp Threshold].
Ext Air Sensor B Humidity
Relative humidity as measured by external air sensor B.
Ext Air Sensor B Temperature
Air temperature as measured by external air sensor B.
Ext Air Sensor C Humidity
Relative humidity as measured by external air sensor C.
Ext Air Sensor C Temperature
Air temperature as measured by external air sensor C.
Ext Compressor Lockout - Event Control
Enable/disable the activation of the [Ext Compressor Lockout] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Compressor Lockout - Event Type
The event type for the [Ext Compressor Lockout] event.
Ext Compressor Lockout
The compressor is shut down and disabled by an external input signal.
Ext Condenser Pump High Water - Event
Control
Enable/disable the activation of the [Ext Condenser Pump High Water] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Ext Condenser Pump High Water - Event
Type
The event type for the [Ext Condenser Pump High Water] event.
Ext Condenser Pump High Water
High water is detected in the condensate pump by the auxiliary float, as
indicated by an external input signal.
Ext Dew Point Over Temp Threshold
Threshold value used in the [Ext Dew Point Over Temperature] event.
Ext Dew Point Over Temperature
At least one dew point temperature reading ([Ext Air Sensor A Dew Point
Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point
Over Temp Threshold].
Ext Dew Point Under Temp Threshold
Threshold value used in the [Ext Dew Point Under Temperature] event.
Ext Dew Point Under Temperature
At least one dew point temperature reading ([Ext Air Sensor A Dew Point
Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew
Point Under Temp Threshold].
Ext Free Cooling Lockout - Event Control
Enable/disable the activation of the [Ext Free Cooling Lockout] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Free Cooling Lockout - Event Type
The event type for the [Ext Free Cooling Lockout] event.
Ext Free Cooling Lockout
Free cooling is disabled by an external input signal.
Ext Humidifier Lockout - Event Control
Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Humidifier Lockout - Event Type
The event type for the [Ext Humidifier Lockout] event.
Ext Humidifier Lockout
The humidifier is shut down and disabled by an external input signal.
Ext Loss of Air Blower - Event Control
Enable/disable the activation of the [Ext Loss of Air Blower] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Loss of Air Blower - Event Type
The event type for the [Ext Loss of Air Blower] event.
Ext Loss of Air Blower
Loss of air blower is detected, as indicated by an external input signal.
Ext Loss of Flow - Event Control
Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Ext Loss of Flow - Event Type
The event type for the [Ext Loss of Flow] event.
Ext Loss of Flow
Loss of flow is detected, as indicated by an external input signal.
Ext Over Temperature - Event Control
Enable/disable the activation of the [Ext Over Temperature] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
436
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Ext Over Temperature - Event Type
The event type for the [Ext Over Temperature] event.
Ext Over Temperature
A temperature has exceeded its threshold, as indicated by an external input
signal.
Ext Power Source A Failure
Unit main power source A failure, as indicated by an external input signal.
Ext Power Source B Failure
Unit main power source B failure, as indicated by an external input signal.
Ext Reheat Lockout - Event Control
Enable/disable the activation of the [Ext Reheat Lockout] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Reheat Lockout - Event Type
The event type for the [Ext Reheat Lockout] event.
Ext Reheat Lockout
The reheater is shut down and disabled by an external input signal.
Ext Standby Glycol Pump On - Event
Control
Enable/disable the activation of the [Ext Standby Glycol Pump On] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Ext Standby Glycol Pump On - Event Type
The event type for the [Ext Standby Glycol Pump On] event.
Ext Standby Glycol Pump On
The standby glycol pump is on, as indicated by an external input signal.
Ext Standby Unit On - Event Control
Enable/disable the activation of the [Ext Standby Unit On] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Ext Standby Unit On - Event Type
The event type for the [Ext Standby Unit On] event.
Ext Standby Unit On
Standby unit is on, as indicated by an external input signal.
External Condenser TVSS Issue
The condenser Transient Voltage Surge Suppressor or Surge Protection
Device has failed, as indicated by an external input signal.
External Condenser VFD Issue
The condenser fan Variable Frequency Drive is offline, as indicated by an
external input signal.
External Fire Detected
Fire detected, as indicated by an external input signal.
Fan Control Mode
Fan control mode.
Fan Control Sensor
Sensor to be used for fan speed control.
Fan Hours Exceeded - Event Control
Enable/disable the activation of the [Fan Hours Exceeded] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Fan Hours Exceeded - Event Type
The event type for the [Fan Hours Exceeded] event.
Fan Hours Exceeded
Operating hours for the unit blower fan have exceeded the threshold.
Fan Hours Threshold
Threshold value used in the [Fan Hours Exceeded] event.
Fan Hours
Operating hours for fan since last reset of this value.
Fan Issue - Event Control
Enable/disable the activation of the [Fan Issue] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in
any active event list or in any event history list.
Fan Issue - Event Type
The event type for the [Fan Issue] event.
Fan Issue
One or more fans are not operating within their operational parameters.
Fan Speed Control Temperature
Temperature value being used for fan speed control. This value is compared
against the fan speed temperature set point to determine the fan speed.
Fan Speed Maximum Set Point
Maximum fan speed. This value may only be modified if iCOM is enabled to
allow fan speed changes by the BMS.
Fan Speed Minimum Set Point
Minimum fan speed.
Fan Speed Temperature Set Point
If fan is in decoupled mode and not under manual control, the fan speed will
vary depending on the delta between the selected fan control sensor
temperature and this set point.
Fan Speed
Fan speed expressed as a percentage of the maximum rated speed.
437
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Fan State
Fan operational state.
Fluid Flow Rate
Flow rate of fluid used for cooling.
Fluid Flow Sensor Issue
The fluid flow sensor is disconnected or the signal is out of range.
Fluid Input Temperature
Temperature of the fluid entering the cooling coil.
Fluid Output Temperature
Temperature of the fluid exiting the cooling coil.
Fluid Temperature Sensor Issue
The fluid temperature sensor is disconnected or the signal is out of range.
Free Cooling Fluid Temperature
Free cooling fluid temperature.
Free Cooling Internal Control Mode
Free cooling internal control mode
Free Cooling Internal Control Mode
Free cooling internal control mode
Free Cooling Internal Temperature Delta
Minimum temperature delta required between supply fluid and internal ambient
air temperatures in order to enable free cooling.
Free Cooling State
Free cooling operational state.
Free Cooling Status
Free cooling status.
Free Cooling Status
Free cooling status.
Free Cooling Stopped - High Room Temp
Free cooling is temporarily disabled due to room temperature exceeding a
preset delta above the the set point.
Free Cooling Temp Sensor Issue
The free cooling fluid temperature sensor is disconnected or the signal is out of
range.
Free Cooling Valve Hours Exceeded
[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours
Threshold].
Free Cooling Valve Hours Threshold
Threshold value used in the [Free Cooling Valve Hours Exceeded] event.
Free Cooling Valve Hours
Operating hours for free cooling valve since last reset of this value.
Free Cooling Valve Open Position
Free cooling valve open position.
Heating Fan Speed Min Set Point
Minimum fan speed when system heating is active.
Heating Lockout
Heating is shut down and disabled.
High Power Shutdown - Event Control
Enable/disable the activation of the [High Power Shutdown] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
High Power Shutdown - Event Type
The event type for the [High Power Shutdown] event.
High Power Shutdown
Supply to high power components has been shutdown.
High Return Air Temperature Threshold
Threshold value used in the [Return Air Over Temperature] event.
High Return Humidity - Event Control
Enable/disable the activation of the [High Return Humidity] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
High Return Humidity - Event Type
The event type for the [High Return Humidity] event.
High Return Humidity Threshold
Threshold value used in the [High Return Humidity] event.
High Return Humidity
Return air high humidity event.
High Static Pressure
High static pressure event.
High Supply Air Temperature Threshold
Threshold value used in the [Supply Air Over Temperature] event.
Hot Water / Hot Gas State
Hot water / hot gas operational state.
Hot Water / Hot Gas Valve Hours Exceeded
[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve
Hours Threshold].
Hot Water / Hot Gas Valve Hours Threshold
Threshold value used in the [Hot Water / Hot Gas Valve Hours Exceeded]
event.
Hot Water / Hot Gas Valve Hours
Operating hours for hot water / hot gas valve since last reset of this value.
Hot Water / Hot Gas Valve Open Position
Hot water / hot gas valve open position.
Humidification Fan Speed Min Set Point
Minimum fan speed when system humidification is active.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
438
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Humidifier Control Board Not Detected
Humidifier control board is required to be connected, but no signal is detected.
Humidifier Cylinder Worn
Humidifier cylinder is not operating properly and needs to be replaced.
Humidifier Hours Exceeded
Operating hours for the humidifier have exceeded the threshold.
Humidifier Hours Threshold
Threshold value used in the [Humidifier Hours Exceeded] event.
Humidifier Hours
Operating hours for humidifier since last reset of this value.
Humidifier Issue - Event Control
Enable/disable the activation of the [Humidifier Issue] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Humidifier Issue - Event Type
The event type for the [Humidifier Issue] event.
Humidifier Issue
Humidifier issue detected, causing it to be locked out.
Humidifier Lockout
Enable/disable the use of the humidifier.
Humidifier Low Water
The water level in the humidifier has dropped below its threshold.
Humidifier Over Current
The electrical current to the humidifier has exceeded its upper threshold.
Humidifier State
Humidifier operational state.
Humidifier Under Current
The electrical current to the humidifier has dropped below its lower threshold.
Humidifier Utilization
Present humidifier utilization expressed as a percentage of the maximum rated
capacity.
Humidity Control Integration Time
Time value used to add an integral term to humidity control. If set to 0, time will
not be a factor in the control algorithm.
Humidity Control Sensor
Sensor from which humidity measurements will be used for humidification and
dehumidification control.
Humidity Control Type
Type of algorithm to use for control of output humidity.
Humidity Control Type
Type of algorithm to use for control of output humidity.
Humidity Dead Band
Value that is divided evenly to form a range above and below [Humidity Set
Point]. If measured humidity is within this range, no humidification or
dehumidification will occur.
Humidity Proportional Band
Value that is divided evenly to form proportional humidity control bands above
and below [Humidity Set Point]. This setting applies to Relative, Predictive and
Compensated [Humidity Control Type] selections.
Humidity Set Point
Desired relative humidity.
Infrared Humidifier Flush Rate
A multiple of an internal time constant that determines the flush duration of the
infrared humidifier water pan.
Input Undervoltage
One or more of the input phase voltages has dropped below the limit.
Instantaneous Power
Total electrical power currently being consumed.
Local Cooling Override
The local unit override status for cooling capacity.
Local Dehumidifier Override
The local unit override status for the dehumidifier.
Local Electric Heat Override
The local unit override status for electric heat.
Local Fan Override
The local unit override status for fan speed.
Local Humidifier Override
The local unit override status for the humidifier.
Loss of Air Flow
No air flow through the unit due to failure of all fans.
Low Return Air Temperature Threshold
Threshold value used in the [Return Air Under Temperature] event.
Low Return Humidity - Event Control
Enable/disable the activation of the [Low Return Humidity] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Low Return Humidity - Event Type
The event type for the [Low Return Humidity] event.
Low Return Humidity Threshold
Threshold value used in the [Low Return Humidity] event.
Low Return Humidity
Return air low humidity event.
439
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Low Static Pressure
Low static pressure event.
Low Supply Air Temperature Threshold
Threshold value used in the [Supply Air Under Temperature] event.
Main Chilled Water Valve
The primary valve in a dual valve chilled water system.
Main Fan Overload - Event Control
Enable/disable the activation of the [Main Fan Overload] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Main Fan Overload - Event Type
The event type for the [Main Fan Overload] event.
Main Fan Overload
Main fan is shut down due to thermal overload.
Maintenance Completed
Maintenance has been completed on the unit.
Maintenance Due
The calculated maintenance date has been reached.
Maintenance Ramp
The ratio of operations performed to the calculated operations available
between maintenance intervals.
Maintenance Tracking State
Maintenance tracking operational state.
Master Unit Communication Lost - Event
Control
Enable/disable the activation of the [Master Unit Communication Lost] event. If
set to 'disabled', the event will not be annunciated. This implies that the event
will not be placed in any active event list or in any event history list.
Master Unit Communication Lost - Event
Type
The event type for the [Master Unit Communication Lost] event.
Master Unit Communication Lost
Communication with master unit has been lost.
Minimum Chilled Water Temp Set Point
Enable
Enable/disable the activation of [Minimum Chilled Water Temp Set Point].
Minimum Chilled Water Temp Set Point
Minimum desired chilled water temperature.
Mixed Mode Lockout
Mixed mode has been entered too many times over a rolling time period and
has been temporarily disabled. Mixed mode is defined as the use of a
compressor on one refrigeration circuit and the use of a refrigerant pump on the
other circuit.
Modbus Power Meter Communication Lost
Communication with Modbus power meter has been lost.
Outside Air Temperature
Ambient outside air temperature.
PRE Operational Mode
Pumped Refrigerant Economizer operational mode.
Pump Hours Threshold
Threshold value used in the [Pump Hours Exceeded] event.
Pump Hours
Operating hours for pump since last reset of this value.
Pump Inlet Refrigerant Temperature
Refrigerant temperature at the inlet of the pump.
Pump Outlet Refrigerant Temperature
Refrigerant temperature at the outlet of the pump.
Pump Speed
Pump speed expressed as a percentage of the maximum rated speed.
Pump State
Pump operational state.
Pump Unspecified General Event
One or more unspecified pump events active. See local unit display for further
details.
RAM Battery Issue
RAM or RAM backup battery is not operating correctly.
Raw Auxiliary Air Temperature
Air temperature value sent by an external auxiliary device, with no additional
filtering by the receiving system. This may be an aggregated value from multiple
sensors.
Reheat Utilization
Present reheating utilization expressed as a percentage of the maximum rated
capacity.
Reheater Lockout
Enable/disable the use of the reheater.
Reheater Over Temperature
The temperature of the reheater has exceeded its threshold.
Remote Sensor Average Over Temperature
[Remote Sensor Average Temperature] has exceeded [Remote Sensor Over
Temp Threshold].
Remote Sensor Average Temperature
Average value of remote sensor temperature measurements.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
440
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Remote Sensor Average Under
Temperature
[Remote Sensor Average Temperature] has dropped below [Remote Sensor
Under Temp Threshold].
Remote Sensor Issue
Remote sensor is disconnected or the signal is out of range.
Remote Sensor Maximum Temperature
Maximum value of remote sensor temperature measurements.
Remote Sensor Over Temp Threshold
Threshold value used in the remote air sensor over temperature events.
Remote Sensor Over Temperature
[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp
Threshold].
Remote Sensor System Average Over
Temperature
[Remote Sensor System Average Temperature] has exceeded [Remote Sensor
Over Temp Threshold].
Remote Sensor System Average
Temperature
Average value of remote sensor temperature measurements among a group of
interconnected units in a single system.
Remote Sensor System Average Under
Temperature
[Remote Sensor System Average Temperature] has dropped below [Remote
Sensor Under Temp Threshold].
Remote Sensor System Maximum
Temperature
Maximum value of remote sensor temperature measurements among a group
of interconnected units in a single system.
Remote Sensor Temperature
Air temperature as measured by remote sensor.
Remote Sensor Under Temp Threshold
Threshold value used in the remote air sensor under temperature events.
Remote Sensor Under Temperature
[Remote Sensor Temperature] has dropped below [Remote Sensor Under
Temp Threshold].
Return Air Over Temp - Event Control
Enable/disable the activation of the [Return Air Over Temperature] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Return Air Over Temp - Event Type
The event type for the [Return Air Over Temperature] event.
Return Air Over Temperature
Return air high temperature event.
Return Air Sensor Event Control
Enable/disable the activation of events related to measurements by the return
air sensor.
Return Air Sensor Issue
The air sensor at the inlet of the unit is disconnected or the signal is out of
range.
Return Air Temperature Set Point
Desired air temperature at the inlet of the unit.
Return Air Temperature
The temperature of the inlet air
Return Air Under Temp - Event Control
Enable/disable the activation of the [Return Air Under Temperature] event. If set
to 'disabled', the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Return Air Under Temp - Event Type
The event type for the [Return Air Under Temperature] event.
Return Air Under Temperature
[Return Air Temperature] has dropped below [Low Return Air Temperature
Threshold].
Return Damper Status
Status of the return damper.
Return Dew Point
Dew point temperature measured at the inlet of the unit.
Return Humidity Sensor Issue
The humidity sensor at the inlet of the unit is disconnected or the signal is out of
range.
Return Humidity Set Point
Desired relative humidity at the inlet of the unit.
Return Humidity
Relative humidity measured at the inlet of the unit.
Server Class
The general classification for this system
Service Required - Event Control
Enable/disable the activation of the [Service Required] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Service Required - Event Type
The event type for the [Service Required] event.
Service Required
Unit requires servicing.
441
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Shutdown - Loss Of Power - Event Control
Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Shutdown - Loss Of Power - Event Type
The event type for the [Shutdown - Loss Of Power] event.
Shutdown - Loss Of Power
System lost power. This event becomes active when the unit is powered on
following an unexpected loss of power. This event remains active for 90
minutes.
Smoke Detected - Event Control
Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled',
the event will not be annunciated. This implies that the event will not be placed
in any active event list or in any event history list.
Smoke Detected - Event Type
The event type for the [Smoke Detected] event.
Smoke Detected
Smoke detected.
Standby Units
The number of standby units.
Static Pressure Control Enable
Enable/disable underfloor static pressure control.
Static Pressure Sensor Issue
The static pressure sensor is disconnected or the signal is out of range.
Static Pressure Sensor Out of Range
Static pressure sensor signal is out of its configured range.
Static Pressure Set Point
Desired static pressure.
Super Saver Call For Cooling
Call for cooling value used for Super Saver functionality. A higher call for
cooling value indicates a need for a lower coolant temperature.
Supply Air Over Temperature
Supply air high temperature event.
Supply Air Over/Under Temperature - Event Enable/disable the activation of the [Supply Air Over Temperature] and [Supply
Control
Air Under Temperature] events.
Supply Air Sensor Issue
The air sensor at the outlet of the unit is disconnected or the signal is out of
range.
Supply Air Temperature Sensor Control
Control mode to be used with the supply air temperature sensor.
Supply Air Temperature Set Point
Desired supply air temperature.
Supply Air Temperature
Air temperature measured at the outlet of the unit.
Supply Air Under Temperature
Supply air low temperature event.
Supply Chilled Water Loss of Flow
Supply chilled water or glycol flow is too low.
Supply Chilled Water Over Temp
Chilled water temperature is too high, as indicated by an external input signal.
System Date and Time
The system date and time
System Event Acknowledge/Reset
Reset and/or acknowledge all events.
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS A-N
The System Input RMS Voltage between Phase A and Neutral
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS B-N
The System Input RMS Voltage between Phase B and Neutral
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS C-N
The System Input RMS Voltage between Phase C and Neutral
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System On/Off Control
Turn system functionality on or off.
System Static Pressure
Static pressure measurement among a group of interconnected units in a single
system.
System Status
The operating status for the system
Tandem 'B' Compressor Hours
Operating hours for the 'B' compressor in a tandem configuration since last
reset of this value.
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
442
BACnet Communications—Thermal Management Products
Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™,
Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™,
Liebert PeX™, Liebert PDX/PCW™—Glossary (continued)
Data Label
Data Description
Tandem 'B' Compressor State
Operational state for the 'B' compressor in a tandem configuration.
Team Static Pressure Sensor Failure
The team static pressure sensor is disconnected or the signal is out of range.
Temperature Control Sensor Issue
The air sensor selected for cooling control is disconnected or the signal is out of
range.
Thermal Control Override - Temperature
Call
If [Thermal Control Override] is enabled, this value sets the percent call for
cooling or heating.
Thermal Control Override - Humidity Call
If [Thermal Control Override] is enabled, this value sets the percent call for
humidification or dehumidification.
Thermal Control Override - Humidity Control If [Thermal Control Override] is enabled, this value selects if the humidity
Type
override is applied to humidification or dehumidification.
Thermal Control Override - Temperature
Control Type
If [Thermal Control Override] is enabled, this value selects if the temperature
override is applied to cooling or heating.
Thermal Control Override
Override internal programmatic control of thermal conditions. This includes, but
may not be limited to, temperature and humidity. The ability to enable this
override may require additional system configuration.
Today's High Air Temperature Time
[Today's High Air Temperature] was measured at this time.
Today's High Air Temperature
The highest external air temperature measured since midnight.
Today's High Humidity Time
[Today's High Humidity] was measured at this time
Today's High Humidity
The highest external humidity measured since midnight.
Today's Low Air Temperature Time
[Today's Low Air Temperature] was measured at this time.
Today's Low Air Temperature
The lowest external air temperature measured since midnight.
Today's Low Humidity Time
[Today's Low Humidity] was measured at this time
Today's Low Humidity
The lowest external humidity measured since midnight.
Underfloor Static Pressure Control Enable
Enable/disable the underfloor static pressure control.
Unit Calculated Airflow
Total airflow calculated for the unit.
Unit Code Missing
Unit code has not been entered and saved.
Unit Communication Lost
Master has lost communication with one or more networked units.
Unit Control Mode
Unit control mode.
Unit Cooling Load
The total amount of heat energy currently being removed by the unit.
Unit Off
Unit was turned off.
Unit On
Unit was turned on.
Unit Operating State Reason
The reason the unit is in the current operating state.
Unit Operating State
Current operating state of the unit.
Unit Partial Shutdown
An event has occurred requiring some system components to be shutdown and
disabled.
Unit Shutdown
An event has occurred requiring the unit to be shutdown and disabled to
prevent damage to the system.
Unit Standby
Unit was placed in standby mode.
Unit Static Pressure
Static pressure measurement for a single unit.
Unspecified General Event
One or more unspecified events active. See local unit display for further details.
Water Leakage Detector Sensor Issue
The water leakage detector sensor is disconnected or the signal is out of range.
Water Under Floor - Event Control
Enable/disable the activation of the [Water Under Floor] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Water Under Floor - Event Type
The event type for the [Water Under Floor] event.
Water Under Floor
Water under the floor is detected.
443
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-8
Liebert CRV™—Binary Data
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Air
Supply Air Over Temperature
Binary_Value
1
5015_1
RD
Active on Alarm
Supply Air Under Temperature
Binary_Value
2
5019_1
RD
Active on Alarm
Return Air Over Temperature
Binary_Value
3
5023_1
RD
Active on Alarm
Supply Air Sensor Issue
Binary_Value
4
5026_1
RD
Active on Alarm
Return Air Sensor Issue
Binary_Value
5
5147_1
RD
Active on Alarm
Binary_Value
6
5966_1_1
RD
Active on Alarm
Air - Auxiliary Air
Aux Air Temp Device Communication Lost
Humidity
High Return Humidity
Binary_Value
16
5034_1
RD
Active on Alarm
Low Return Humidity
Binary_Value
17
5036_1
RD
Active on Alarm
Humidifier Hours Exceeded
Binary_Value
18
5037_1
RD
Active on Alarm
Dehumidifier Hours Exceeded
Binary_Value
19
5038_1
RD
Active on Alarm
Humidifier Under Current
Binary_Value
20
5039_1
RD
Active on Alarm
Humidifier Over Current
Binary_Value
21
5040_1
RD
Active on Alarm
Humidifier Low Water
Binary_Value
22
5041_1
RD
Active on Alarm
Humidifier Cylinder Worn
Binary_Value
23
5042_1
RD
Active on Alarm
Humidifier Issue
Binary_Value
24
5043_1
RD
Active on Alarm
Ext Humidifier Lockout
Binary_Value
25
5044_1
RD
Active on Alarm
Humidifier Control Board Not Detected
Binary_Value
26
5045_1
RD
Active on Alarm
Return Humidity Out Of Proportional Band
Binary_Value
27
5046_1
RD
Active on Alarm
Binary_Value
38
5053_1
RD
Active on Alarm
Fans
Loss of Air Flow
Fan Hours Exceeded
Binary_Value
39
5054_1
RD
Active on Alarm
Top Fan Issue
Binary_Value
40
5055_1
RD
Active on Alarm
Bottom Fan Issue
Binary_Value
41
5056_1
RD
Active on Alarm
Remote Sensors
Remote Sensor Average Under Temperature
Binary_Value
43
5594_1
RD
Active on Alarm
Remote Sensor Average Over Temperature
Binary_Value
44
5593_1
RD
Active on Alarm
Remote Sensor System Average Under
Temperature
Binary_Value
45
5596_1
RD
Active on Alarm
Remote Sensor System Average Over
Temperature
Binary_Value
46
5595_1
RD
Active on Alarm
Remote Sensor Average Low Humidity
Binary_Value
47
6227_1
RD
Active on Alarm
Remote Sensor Average High Humidity
Binary_Value
48
6228_1
RD
Active on Alarm
Remote Sensor System Average Low Humidity
Binary_Value
49
6229_1
RD
Active on Alarm
Remote Sensor System Average High Humidity
Binary_Value
50
6230_1
RD
Active on Alarm
Remote Sensor Issue
Binary_Value
52
5060_1_1
RD
Active on Alarm
Remote Sensor Low Humidity
Binary_Value
53
6225_1_1
RD
Active on Alarm
Remote Sensor High Humidity
Binary_Value
54
6226_1_1
RD
Active on Alarm
Remote Sensor Under Temperature
Binary_Value
55
5598_1_1
RD
Active on Alarm
Remote Sensor Over Temperature
Binary_Value
56
5597_1_1
RD
Active on Alarm
Remote Sensors - Remote Sensor 1
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
444
BACnet Communications—Thermal Management Products
Table 4-8
Liebert CRV™—Binary Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Remote Sensor Issue
Binary_Value
63
5060_1_2
RD
Active on Alarm
Remote Sensor Low Humidity
Binary_Value
64
6225_1_2
RD
Active on Alarm
Remote Sensor High Humidity
Binary_Value
65
6226_1_2
RD
Active on Alarm
Remote Sensor Under Temperature
Binary_Value
66
5598_1_2
RD
Active on Alarm
Remote Sensor Over Temperature
Binary_Value
67
5597_1_2
RD
Active on Alarm
Remote Sensor Issue
Binary_Value
151
5060_1_1
0
RD
Active on Alarm
Remote Sensor Low Humidity
Binary_Value
152
6225_1_1
0
RD
Active on Alarm
Remote Sensor High Humidity
Binary_Value
153
6226_1_1
0
RD
Active on Alarm
Remote Sensor Under Temperature
Binary_Value
154
5598_1_1
0
RD
Active on Alarm
Remote Sensor Over Temperature
Binary_Value
155
5597_1_1
0
RD
Active on Alarm
Compressor 1 High Head Pressure
Binary_Value
162
4669_1
RD
Active on Alarm
Compressor 1 Low Suction Pressure
Binary_Value
163
5062_1
RD
Active on Alarm
Compressor 1 Hours Exceeded
Binary_Value
164
5063_1
RD
Active on Alarm
Dig Scroll Comp 1 Temp Sensor Issue
Binary_Value
165
5064_1
RD
Active on Alarm
Remote Sensors - Remote Sensor 2
Remote Sensors - Remote Sensor 10
Compressor
Dig Scroll Comp 1 Over Temp
Binary_Value
166
5065_1
RD
Active on Alarm
Compressor 1 Low Pressure Transducer Issue
Binary_Value
167
5066_1
RD
Active on Alarm
Compressor 1 High Pressure Transducer Issue
Binary_Value
168
5148_1
RD
Active on Alarm
Ext Compressor Lockout
Binary_Value
169
5067_1
RD
Active on Alarm
Compressor 1 Short Cycle
Binary_Value
170
4681_1
RD
Active on Alarm
Compressor 1 Pump Down Issue
Binary_Value
171
5146_1
RD
Active on Alarm
Compressor Capacity Reduced
Binary_Value
172
5513_1
RD
Active on Alarm
Compressor Superheat Over Threshold
Binary_Value
173
5604_1
RD
Active on Alarm
Reheater Over Temperature
Binary_Value
182
5068_1
RD
Active on Alarm
Electric Reheater 1 Hours Exceeded
Binary_Value
183
5069_1
RD
Active on Alarm
Ext Reheat Lockout
Binary_Value
184
5070_1
RD
Active on Alarm
Electric Reheater Hours Exceeded
Binary_Value
185
5368_1
RD
Active on Alarm
Reheater
Condenser
Condenser 1 Issue
Binary_Value
195
5071_1
RD
Active on Alarm
Condenser VFD Issue
Binary_Value
196
5072_1
RD
Active on Alarm
Condenser TVSS Issue
Binary_Value
197
5073_1
RD
Active on Alarm
External Condenser VFD Issue
Binary_Value
198
6106_1
RD
Active on Alarm
External Condenser TVSS Issue
Binary_Value
199
6105_1
RD
Active on Alarm
445
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
BACnet Communications—Thermal Management Products
Table 4-8
Liebert CRV™—Binary Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Chilled Water
Supply Chilled Water Over Temp
Binary_Value
208
4626_1
RD
Active on Alarm
Chilled Water Control Valve Failure
Binary_Value
209
4703_1
RD
Active on Alarm
Supply Chilled Water Loss of Flow
Binary_Value
210
4980_1
RD
Active on Alarm
Customer Input 1
Binary_Value
221
4270_1
RD
Active on Alarm
Customer Input 2
Binary_Value
222
4271_1
RD
Active on Alarm
Customer Input 3
Binary_Value
223
4272_1
RD
Active on Alarm
Customer Input 4
Binary_Value
224
4273_1
RD
Active on Alarm
Smoke Detected
Binary_Value
225
4720_1
RD
Active on Alarm
Water Under Floor
Binary_Value
226
4723_1
RD
Active on Alarm
Service Required
Binary_Value
227
4726_1
RD
Active on Alarm
Shutdown - Loss Of Power
Binary_Value
228
4714_1
RD
Active on Alarm
System Events
Ext Over Temperature
Binary_Value
229
5104_1
RD
Active on Alarm
Ext Loss of Flow
Binary_Value
230
5105_1
RD
Active on Alarm
Ext Condenser Pump High Water
Binary_Value
231
5106_1
RD
Active on Alarm
Ext Standby Glycol Pump On
Binary_Value
232
5107_1
RD
Active on Alarm
External Fire Detected
Binary_Value
233
5108_1
RD
Active on Alarm
Unit On
Binary_Value
234
5109_1
RD
Active on Alarm
Unit Off
Binary_Value
235
5110_1
RD
Active on Alarm
Unit Standby
Binary_Value
236
5111_1
RD
Active on Alarm
Unit Partial Shutdown
Binary_Value
237
5112_1
RD
Active on Alarm
Unit Shutdown
Binary_Value
238
5113_1
RD
Active on Alarm
Water Leakage Detector Sensor Issue
Binary_Value
239
5114_1
RD
Active on Alarm
BMS Communications Timeout
Binary_Value
240
5115_1
RD
Active on Alarm
Maintenance Due
Binary_Value
241
5116_1
RD
Active on Alarm
Maintenance Completed
Binary_Value
242
5117_1
RD
Active on Alarm
Clogged Air Filter
Binary_Value
243
5118_1
RD
Active on Alarm
RAM Battery Issue
Binary_Value
244
5119_1
RD
Active on Alarm
Master Unit Communication Lost
Binary_Value
245
5120_1
RD
Active on Alarm
High Power Shutdown
Binary_Value
246
5121_1
RD
Active on Alarm
Supply Fluid Temp Sensor Issue
Binary_Value
247
4651_1
RD
Active on Alarm
Unspecified General Event
Binary_Value
248
5588_1
RD
Active on Alarm
SEC Unspecified General Event
Binary_Value
249
6232_1
RD
Active on Alarm
SEC Communication Lost
Binary_Value
250
6233_1
RD
Active on Alarm
Static Pressure Sensor Issue
Binary_Value
251
5629_1
RD
Active on Alarm
Static Pressure Sensor Out of Range
Binary_Value
252
5910_1
RD
Active on Alarm
Power Source 'A' Issue
Binary_Value
253
6236_1
RD
Active on Alarm
Power Source B Failure
Binary_Value
254
6237_1
RD
Active on Alarm
Fluid Flow Sensor Issue
Binary_Value
255
5912_1
RD
Active on Alarm
Fluid Temperature Sensor Issue
Binary_Value
256
5911_1
RD
Active on Alarm
Unit Code Missing
Binary_Value
257
5418_1
RD
Active on Alarm
Liebert® IntelliSlot™ Modbus/BACnet Reference Guide
446
BACnet Communications—Thermal Management Products
Table 4-8
Liebert CRV™—Binary Data (continued)
Controller Liebert iCOM® v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Condenser Outside Air Temp Sensor Issue
Binary_Value
259
5535_1
RD
Active on Alarm
Condenser Outside Air Temp Out of Opera