Liebert® IntelliSlot™ Modbus RTU, Modbus TCP, BACnet MSTP and BACnet IP Reference Guide Table of Content 1.0 Liebert Equipment Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 What’s New in This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Connectivity to Liebert IntelliSlot Using Modbus RTU, Modbus TCP, BACnet MSTP or BACnet IP . . . . . . . . . . . . . . . . . 1 1.2.1 How to Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2.2 Compatibility with Liebert Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.0 Modbus Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.1 Implementation Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.2 Transmission Format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.3 Modbus Packet Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.3.1 Device Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.2 Function Code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.3 Data Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.4 Error Check Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3.5 RTU Framing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 8 8 8 9 3.0 Modbus RTU and Modbus TCP Protocols. . . . . . . . . . . . . . . . . . . . . . . . 11 3.1 Thermal Management Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.2 Power Distribution and Power Conditioning Products. . . . . . . . . . . . . . . . . . . . . . . . . . . 159 3.3 UPS Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199 3.4 Battery Monitoring Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 4.0 BACnet Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 4.1 BACnet Protocol Implementation Conformance Statement . . . . . . . . . . . . . . . . . . . . . . 373 4.1.1 Segmentation Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 4.1.2 Supported Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373 4.1.3 Standard Object Types SupportedObject Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . 374 4.2 Thermal Management Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378 4.3 UPS Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 511 4.4 Power Distribution and Power Conditioning Products. . . . . . . . . . . . . . . . . . . . . . . . . . . 663 i Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Page intentionally left blank. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide ii List of Tables Table 1-1: Liebert Equipment and Compatible Liebert IntelliSlot Cards Modbus RTU & Modbus TCP Protocols . . 2 Table 1-2: Liebert Equipment and Compatible Liebert IntelliSlot Cards BACnet MSTP & BACnet IP Protocols . . . 5 Table 2-1: Modbus Remote Terminal Unit settings for Liebert IntelliSlot 485/IP interface card . . . . . . . . . . . . . . . . 7 Table 2-2: Supported Modbus function codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Table 2-3: Query sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Table 2-4: Response sample . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Table 3-1: Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil . . . . . . . . . . 11 Table 3-2: Extra notes key to Table 3-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Table 3-3: Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding . . . . . . . . 27 Table 3-4: Extra notes key to Table 3-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Table 3-5: Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary . . . . . . . . . . . . . . . 54 Table 3-6: Liebert CRV™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Table 3-7: Liebert CRV™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Table 3-8: Liebert CRV™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Table 3-9: Liebert HPC™ (Chiller) - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Table 3-10: Liebert HPC™ (Chiller)—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Table 3-11: Extra notes key to Table 3-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Table 3-12: Liebert HPC™ (Chiller)—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Table 3-13: Liebert XDC™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 Table 3-14: Liebert XDC™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 Table 3-15: Liebert XDP™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Table 3-16: Liebert XDP™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Table 3-17: Liebert XDP™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Table 3-18: Liebert iCOM® DCL™—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 Table 3-19: Liebert iCOM® DCL™—Input and Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 Table 3-20: Liebert iCOM® DCL™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Table 3-21: Liebert DS™ and Liebert PeX™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136 Table 3-22: Liebert DS™ and Liebert PeX™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Table 3-23: Liebert XDF™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 Table 3-24: Liebert XDF™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145 Table 3-25: Liebert Challenger 3000™, Liebert Deluxe System/3™, Liebert Himod™, Liebert ICS™—Input and Holding—LAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147 Table 3-26: Liebert DataMate™, Liebert Mini-Mate Plus™, Liebert Mini-Mate2™—Input and Holding—L0B. . . 149 Table 3-27: Liebert DataMate™, Liebert Mini-Mate2™—Input and Holding—MM2 . . . . . . . . . . . . . . . . . . . . . . 150 Table 3-28: Liebert Mini-Mate2™ 8 Ton—Input and Holding—L8T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152 Table 3-29: Liebert Atlas Air™, Liebert Atlas PEC™, Liebert LECS 15™—Input and Holding—C10 2-step. . . . 154 Table 3-30: Liebert Atlas Air™, Liebert Atlas PEC™, Liebert CEMS 100™—Input and Holding—C100 4-step . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156 Table 3-31: Liebert FPC™, Liebert PPC™—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 v Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide Table 3-32: Liebert Datawave™, Liebert FPC™, Liebert PPC™—Input and Holding—PMP Option for Liebert FPC and Liebert PPC . . . . . . . . . . . . 161 Table 3-33: Liebert FPC™, Liebert PPC™—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163 Table 3-34: Liebert FPC™, Liebert PPC™—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167 Table 3-35: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176 Table 3-36: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179 Table 3-37: Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Status and Coil . . . . . . . . . . . . . . 186 Table 3-38: Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Input and Holding . . . . . . . . . . . . 187 Table 3-39: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 Table 3-40: Liebert STS™, Liebert STS/PDU™—Input and Holding—STS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193 Table 3-41: Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 . . . . . . . . . . . . . . . . . . . . . . . . . 195 Table 3-42: Liebert APM™, Liebert NXC™, Liebert NXR™—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . 199 Table 3-43: Liebert APM™, Liebert NXC™, Liebert NXR™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . 201 Table 3-44: Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203 Table 3-45: Liebert APS™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206 Table 3-46: Liebert APS™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208 Table 3-47: Liebert APS™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213 Table 3-48: Liebert EPM™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217 Table 3-49: Liebert EPM™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219 Table 3-50: Liebert EPM™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223 Table 3-51: Liebert eXL™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227 Table 3-52: Liebert eXL™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 Table 3-53: Liebert eXL™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236 Table 3-54: Liebert eXM™—Controller with LCD HMI—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241 Table 3-55: Liebert eXM™—Controller with LCD HMI—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243 Table 3-56: Liebert eXM™—Controller with LCD HMI—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247 Table 3-57: Liebert eXM™—Controller with Touchscreen HMI—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . 251 Table 3-58: Liebert eXM™—Controller with Touchscreen HMI—Input and Holding . . . . . . . . . . . . . . . . . . . . . . 254 Table 3-59: Liebert eXM™—Controller with Touchscreen HMI—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261 Table 3-60: Liebert GXT2™ and Liebert GXT3™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266 Table 3-61: Liebert GXT2™ and Liebert GXT3™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268 Table 3-62: Liebert GXT2™ and Liebert GXT3™—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 Table 3-63: Liebert GXT3™ and Liebert GXT4™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272 Table 3-64: Liebert GXT3™ and Liebert GXT4™—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273 Table 3-65: Liebert GXT3™ and Liebert GXT4™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278 Table 3-66: Liebert HiNet™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281 Table 3-67: Liebert HiNet™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282 Table 3-68: Liebert Nfinity®—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283 Table 3-69: Liebert Nfinity®—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284 Table 3-70: Liebert NX™—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286 Table 3-71: Liebert NX™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288 Table 3-72: Liebert NX™ 225-600kVA UPS—Chloride ManageUPS—Input and Holding 3 . . . . . . . . . . . . . . . . 290 Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide vi Table 3-73: Liebert NX 225-600kVA UPS—IS-UNITY-DP—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293 Table 3-74: Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . 295 Table 3-75: Liebert NX 225-600kVA UPS—IS-UNITY-DP—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 Table 3-76: Liebert NXL™—60Hz, UL version (Model 40)—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . 303 Table 3-77: Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . 306 Table 3-78: Liebert NXL™—60Hz, UL version (Model 40)—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318 Table 3-79: Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil . . . . . . . . . . . . . . . . . . . . 323 Table 3-80: Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding . . . . . . . . . . . . . . . . . . 327 Table 3-81: Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . 338 Table 3-82: Liebert PowerSure™ Interactive (before July 2008)—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . 346 Table 3-83: Liebert PowerSure™ Interactive (before July 2008)—Input and Holding . . . . . . . . . . . . . . . . . . . . . 347 Table 3-84: Liebert PowerSure™ Interactive 2—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348 Table 3-85: Liebert PowerSure™ Interactive 2—Input and Holding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 350 Table 3-86: Liebert Series 300™ UPS—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352 Table 3-87: Liebert Series 300™ UPS—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 Table 3-88: Liebert Series 600™ UPS—Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355 Table 3-89: Liebert Series 600™ UPS—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356 Table 3-90: Liebert Series 610™ SCC UPS—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357 Table 3-91: Liebert Series 610 SCC UPS—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358 Table 3-92: Liebert HiPulse™ and Liebert SICE 7200™—Input and Holding—SMM/SSM. . . . . . . . . . . . . . . . . 359 Table 3-93: Liebert SICE 7200™—Input and Holding—SSC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 361 Table 3-94: Liebert Npower™—Input and Holding—IMP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363 Table 3-95: Alber® BDSU™—Status and Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365 Table 3-96: Alber® BDSU™—Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 367 Table 4-1: Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data . . . . . . . . . . . . . 378 Table 4-2: Extra Notes key to Table 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394 Table 4-3: Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data . . . . . . . . . . . . 394 Table 4-4: Extra Notes key to Table 4-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414 Table 4-5: Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data. . . . . . . . . . 415 Table 4-6: Extra Notes key to Table 4-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429 Table 4-7: Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary . . . . . . . . . . . . . . 430 Table 4-8: Liebert CRV™—Binary Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444 Table 4-9: Liebert CRV™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 448 Table 4-10: Liebert CRV™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452 Table 4-11: Liebert CRV™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457 Table 4-12: Liebert HPC™—Binary Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 465 Table 4-13: Liebert HPC™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468 Table 4-14: Liebert HPC™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471 vii Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide Table 4-15: Liebert HPC™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473 Table 4-16: Liebert XDP™, Liebert XDC™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 477 Table 4-17: Liebert XDP™, Liebert XDC™—Analog Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479 Table 4-18: Liebert XDP™, Liebert XDC™—Multistate Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481 Table 4-19: Liebert XDP™, Liebert XDC™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 488 Table 4-20: Liebert iCOM® DCL™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 495 Table 4-21: Liebert iCOM® DCL™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497 Table 4-22: Liebert iCOM® DCL™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500 Table 4-23: Liebert iCOM® DCL™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 503 Table 4-24: Liebert DataMate™, Liebert Mini-Mate2™—MM2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508 Table 4-25: Liebert Mini-Mate2™ 8 Ton—L8T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 509 Table 4-26: Liebert APM™, Liebert NXC™, Liebert NXR™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 511 Table 4-27: Liebert APM™, Liebert NXC™, Liebert NXR™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 513 Table 4-28: Liebert APM™, Liebert NXC™, Liebert NXR™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 515 Table 4-29: Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516 Table 4-30: Liebert APS™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 519 Table 4-31: Liebert APS™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 521 Table 4-32: Liebert APS™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523 Table 4-33: Liebert APS™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 526 Table 4-34: Liebert EPM™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530 Table 4-35: Liebert EPM™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 532 Table 4-36: Liebert EPM™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 534 Table 4-37: Liebert EPM™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536 Table 4-38: Liebert eXL™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 540 Table 4-39: Liebert eXL™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 544 Table 4-40: Liebert eXL™—Multistate Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 549 Table 4-41: Liebert eXL™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 556 Table 4-42: Liebert eXM™—Controller with LCD HMI—Binary Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565 Table 4-43: Liebert eXM™—Controller with LCD HMI—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 568 Table 4-44: Liebert eXM™—Controller with LCD HMI—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 570 Table 4-45: Liebert eXM™—Controller with LCD HMI—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 571 Table 4-46: Liebert eXM™—Controller with Touchscreen HMI—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 575 Table 4-47: Liebert eXM™—Controller with Touchscreen HMI—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . 578 Table 4-48: Liebert eXM™—Controller with Touchscreen HMI—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . 581 Table 4-49: Liebert eXM™—Controller with Touchscreen HMI—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 583 Table 4-50: Liebert GXT3™ and Liebert GXT4™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 588 Table 4-51: Liebert GXT3™ and Liebert GXT4™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 589 Table 4-52: Liebert GXT3™ and Liebert GXT4™—Multistate Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 591 Table 4-53: Liebert GXT3™ and Liebert GXT4™—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 593 Table 4-54: Liebert NX™ 225-600kVA—Binary Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 596 Table 4-55: Liebert NX™ 225-600kVA—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 598 Table 4-56: Liebert NX™ 225-600kVA—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 601 Table 4-57: Liebert NX™ 225-600kVA—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603 Table 4-58: Liebert NXL™- 60Hz, UL version (Model 40)—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 606 Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide viii Table 4-59: Liebert NXL™- 60Hz, UL version (Model 40)—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 612 Table 4-60: Liebert NXL™ - 60Hz, UL version (Model 40)—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 618 Table 4-61: Liebert NXL™—60Hz, UL version (Model 40)—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 624 Table 4-62: Liebert NXL™—60Hz, UL version (Model 40)—Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 632 Table 4-63: Liebert NXL™—50 Hz, CE version (Models 48 and 49)—Binary Data. . . . . . . . . . . . . . . . . . . . . . . 640 Table 4-64: Liebert NXL™—50 Hz, CE version (Models 48 and 49)—Analog Data . . . . . . . . . . . . . . . . . . . . . . 644 Table 4-65: Liebert NXL™—50 Hz, CE version (Models 48 and 49)—Multistate Data . . . . . . . . . . . . . . . . . . . . 647 Table 4-66: Liebert NXL™—50 Hz, CE version (Models 48 and 49)—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . 655 Table 4-67: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™ and Liebert RX™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 663 Table 4-68: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™ and Liebert RX™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 665 Table 4-69: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™ and Liebert RX™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . 671 Table 4-70: Liebert FDC™, Liebert FPC™, Liebert PPC™ and Liebert RDC™—Binary Data . . . . . . . . . . . . . . 672 Table 4-71: Liebert FDC™, Liebert FPC™, Liebert PPC™ and Liebert RDC™—Analog Data. . . . . . . . . . . . . . 673 Table 4-72: Liebert FDC™, Liebert FPC™, Liebert PPC™and Liebert RDC™—Multistate Data . . . . . . . . . . . . 675 Table 4-73: Liebert FPC™ and Liebert PPC™—Analog Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 676 Table 4-74: Liebert FPC™ and Liebert PPC™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 683 Table 4-75: Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™ and Liebert RX™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 684 Table 4-76: Alber® BDSU™—Binary Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 687 Table 4-77: Alber® BDSU™—Analog Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 691 Table 4-78: Alber® BDSU™—Multistate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 698 Table 4-79: Alber® BDSU™—Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 699 ix Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide Page intentionally left blank. Liebert® IntelliSlot™ Modbus/BACnet™ Reference Guide x Liebert Equipment Compatibility 1.0 Liebert Equipment Compatibility 1.1 What’s New in This Manual The Liebert® IntelliSlot™ Unity Communications Card has been updated to support the Liebert EMP™ UPS and Liebert DCL™ thermal-management equipment. Enhancements have also been added to support modular Liebert eXM UPS equipment and a number of thermal-management products. The supported Modbus and BACnet mapping tables for this equipment when using the IS-UNITY-DP communications card have been added to this document. In addition, Table 1-1 and Table 1-2 are updated to more-easily present the cards available to support the specific BACnet and Modbus protocols. 1.2 Connectivity to Liebert IntelliSlot Using Modbus RTU, Modbus TCP, BACnet MSTP or BACnet IP This document describes the Modbus and BACnet communications protocols available for communication with Emerson Network Power equipment. Included are the Liebert IntelliSlot Modbus RTU, Modbus TCP, BACnet MSTP and the BACnet IP communications cards. • The Modbus information includes implementation basics, supported types, frame format, function code support and similar subjects. • The BACnet information includes the BACnet service listing, object types, device objects, analog objects, binary objects, multistate objects and BACnet engineering units. NOTE Some Building Management Systems can be configured to send continuous updates for device setpoints, usually setting the same value. The BMS should be configured to send, on a sustained average, no more than two writes per second to the device. This will allow the device to catch up after a burst of updates when required while allowing other communication with the device to proceed. The Liebert NX™ 225-600kVA UPS uses the Chloride ManageUPS Net Adapter +B card for Modbus support with the UPS’ native processor. If the UPS is upgraded to use the optional MUND control board, then the IS-UNITY-DP card may be used to provide both Modbus and BACnet support. Both sets of mapping tables are provided in this document and referenced in Table 1-1 and Table 1-2. 1.2.1 How to Use This Manual Table 1-1 and Table 1-2 show the type of Liebert IntelliSlot card required for selected Liebert products. Find the product first and the tables to reference, the columns to the right of that are the cards supported for the product. The information is organized by Product Name, Table Number, Controller Protocol and Card Part Number. Modbus tables are first and BACnet tables second with products in the following sections: • Thermal Management Products • Power Distribution and Power Conditioning Products (Modbus Only) • UPS Systems • Battery Monitoring Products (Modbus Only) Products currently shipping are shown first in each section, followed by older equipment. 1 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Liebert Equipment Compatibility 1.2.2 Compatibility with Liebert Equipment Table 1-1 Liebert Equipment and Compatible Liebert IntelliSlot Cards Modbus RTU & Modbus TCP Protocols Product Supported Compatible Card Part Number Refer to Tables: Modbus TCP Card Modbus RTU Card Liebert iCOM® v4 IS-UNITY-DP IS-IPBML* IS-UNITY-DP IS-485L* Liebert iCOM® v4 IS-UNITY-DP IS-UNITY-DP Liebert iCOM v3 — OC485-LBDS LAM — IS-WEBADPT OC485-ADPT* L0B — IS-WEBADPT OC485-ADPT* MM2 — IS-WEBADPT OC485-ADPT* L8T — IS-WEBADPT OC485-ADPT* C10 2-step — IS-WEBADPT OC485-ADPT* C100 4-step — IS-WEBADPT OC485-ADPT* Controller / Protocol Thermal Management Products Liebert Challenger 3000™ 3-1 to 3-5 Liebert Challenger ITR™ 3-1 to 3-5 ™ 3-1 to 3-5 Liebert CRV ™ 3-6 to 3-8 Liebert CW ™ 3-15 to 3-17 Liebert DCP ™ Liebert Deluxe System/3 ™ 3-1 to 3-5 3-1 to 3-5 Liebert DS DSE™ 3-1 to 3-5 Liebert HPC™ (Chiller) 3-9 to 3-12 Liebert ™ 3-1 to 3-5 Liebert HPM Liebert PeX™ 3-1 to 3-5 Liebert PCW/PDX™ 3-1 to 3-5 Liebert XDC™ 3-13 to 3-10 Liebert XDP™ 3-15 to 3-17 Liebert DCL™ 3-18 to 3-20 Liebert DS 3-21 to 3-22 Liebert PeX 3-21 to 3-22 Liebert XDF™ 3-23 to 3-24 Liebert Challenger 3000 3-25 Liebert Deluxe System/3 3-25 Liebert Himod™ 3-25 Liebert ICS™ Liebert 3-25 DataMate™ Liebert Mini-Mate Plus™ 3-26 3-26 Liebert Mini-Mate2™ 3-26 Liebert DataMate™ 3-27 Liebert Mini-Mate2 3-27 Liebert Mini-Mate2 8 Ton 3-28 Liebert Atlas Air™ 3-29 Liebert Atlas PEC™ 3-29 Liebert LECS 15™ 3-29 Liebert Atlas Air 3-30 Liebert Atlas PEC 3-30 Liebert CEMS 100™ 3-30 *Communication cards marked with an asterisk are Discontinued. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 2 Liebert Equipment Compatibility Table 1-1 Product Supported Liebert Equipment and Compatible Liebert IntelliSlot Cards Modbus RTU & Modbus TCP Protocols (continued) Compatible Card Part Number Refer to Tables: Controller / Protocol Modbus TCP Card Modbus RTU Card IS-UNITY-DP IS-UNITY-DP IS-485S* PMP2 — IS-WEBADPT OC485-ADPT* PMP — IS-WEBADPT OC485-ADPT* STS — IS-WEBADPT OC485-ADPT* — IS-WEBADPT OC485-ADPT* Power Distribution & Power Conditioning Products Liebert EXC™ 3-35,3-36, 3-39 LDMF Liebert FDC™ 3-35 to 3-39 LDMF, CPM FPC™ 3-33 to 3-39 Liebert PPC™ 3-33 to 3-39 VPMP, LDMF, CPM ™ Liebert RDC 3-35 to 3-39 LDMF, CPM Liebert RX™ 3-37 to 3-39 LDMF Liebert Liebert FPC 3-31 Liebert PPC 3-31 Liebert Datawave™ 3-32 Liebert FPC 3-32 Liebert PPC 3-32 Liebert STS™ 3-40 Liebert STS/PDU™ Liebert STS2™ 3-40 3-35 to 3-41 STS2 3-41 Liebert STS2/PDU™ 3-35,3-36, 3-39, 3-41 STS2 with LDMF Liebert APM™ 3-42 to 3-44 — IS-UNITY-DP IS-IPBML* IS-UNITY-DP IS-485L* Liebert APS™ 3-45 to 3-47 — IS-UNITY-DP IS-UNITY-DP ™ 3-48 to 3-50 — IS-UNITY-DP IS-UNITY-DP 3-51 to 3-53 — IS-UNITY-DP IS-UNITY-DP Liebert eXM™ 3-54 to 3-56 Controller with LCD HMI IS-UNITY-DP IS-UNITY-DP Liebert eXM™ 3-57 to 3-59 Controller with Touchscreen HMI IS-UNITY-DP IS-UNITY-DP Liebert GXT2™ 3-61 to 3-62 — — OC-485 UPS Systems Liebert EPM Liebert eXL™ 3-61 to 3-62 — — OC-485 3-63 to 3-65 — IS-UNITY-DP IS-UNITY-DP Liebert GXT4™ 3-63 to 3-65 — IS-UNITY-DP IS-UNITY-DP ™ 3-66 to 3-67 — — OC-485 3-68 to 3-69 — — OC-485 3-70 to 3-71 — — OC-485 3-72 Native Chloride ManageUPS +B Chloride ManageUPS +B 3-73 to 3-74 Mund IS-UNITY-DP IS-UNITY-DP IS-IPBML IS-UNITY-DP IS-IPBML IS-UNITY-DP Liebert GXT3™ Liebert HiNet ™ Liebert Nfinity ™ Liebert NX Liebert NX™ 225-600 Liebert NXC™ 3-42 to 3-44 — IS-485L IS-UNITY-DP Liebert NXR™ 3-42 to 3-44 — IS-485L IS-UNITY-DP *Communication cards marked with an asterisk are Discontinued. 3 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Liebert Equipment Compatibility Table 1-1 Liebert Equipment and Compatible Liebert IntelliSlot Cards Modbus RTU & Modbus TCP Protocols (continued) Compatible Card Part Number Refer to Tables: Controller / Protocol Modbus TCP Card Modbus RTU Card Liebert NXL™- 60 Hz, UL version (Model 40—SA, SR, SN, MM, CD) 3-76 to 3-78 — IS-UNITY-DP IS-IPBMX* IS-UNITY-DP IS-485X* Liebert NXL™- 50 Hz, CE version (Model 48 and 49—SA, SR, SN, MM, CD) 3-79 to 3-81 — IS-UNITY-DP IS-UNITY-DP Liebert PowerSure Interactive™ 3-82 to 3-83 — — OC-485 3-84 to 3-85 — — OC-485 Product Supported UPS Systems (continued) ™ Liebert PowerSure Interactive 2 Liebert Series 300™ UPS 3-86 to 3-87 — — IS-WEBADPT OC485-ADPT* Liebert Series 600™ UPS 3-88 to 3-89 — — IS-WEBADPT OC485-ADPT* Liebert Series 610™ SCC UPS 3-90 to 3-91 — — IS-WEBADPT OC485-ADPT* Liebert HiPulse™ 3-92 SMM/SSM — IS-WEBADPT OC485-ADPT* ™ Liebert SICE 7200 3-92 Liebert SICE 7200™ 3-93 SSC — IS-WEBADPT OC485-ADPT* Liebert Npower™ 3-94 IMP — IS-WEBADPT OC485-ADPT* 3-95 to 3-96 — IS-UNITY-DP IS-IPBMX* IS-UNITY-DP IS-485X* — Battery Monitoring Products Alber BDSU™ *Communication cards marked with an asterisk are Discontinued. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 4 Liebert Equipment Compatibility Table 1-2 Liebert Equipment and Compatible Liebert IntelliSlot Cards BACnet MSTP & BACnet IP Protocols Product Supported Compatible Card Part Number Refer to Tables: Controller / Protocol BACNet IP BACnet MSTP Liebert iCOM v4 IS-UNITY-DP IS-IPBML* IS-UNITY-DP Liebert iCOM v4 IS-UNITY-DP IS-UNITY-DP Thermal Management Products Liebert Challenger 3000™ 4-1 to 4-7 Liebert Challenger ITR™ 4-1 to 4-7 ™ 4-8 to 4-11 Liebert CRV ™ 4-1 to 4-7 Liebert CW Liebert DCP™ 4-16 to 4-19 Liebert Deluxe System/3 4-1 to 4-7 Liebert DS™ 4-1 to 4-7 ™ 4-1 to 4-7 Liebert DSE Liebert HPC™ 4-12 to 4-15 ™ Liebert HPM 4-1 to 4-7 Liebert PDX/PCW™ 4-1 to 4-7 ™ 4-1 to 4-7 Liebert PeX Liebert XDC™ 4-17 to 4-19 Liebert XDP™ 4-17 to 4-19 Liebert DCL™ 4-20 to 4-23 Liebert DataMate™ 4-24 Liebert Mini-Mate2 4-24 Liebert Mini-Mate2™ 8 Ton 4-25 MM2 IS-WEBADPT L8T — — UPS Systems Liebert APM 4-26 to 4-29 — IS-UNITY-DP IS-UNITY-DP Liebert APS 4-30 to 4-33 — IS-UNITY-DP IS-UNITY-DP Liebert EPM™ 4-34 to 4-37 — IS-UNITY-DP IS-UNITY-DP Liebert eXL™ 4-38 to 4-41 — IS-UNITY-DP IS-UNITY-DP Liebert eXM™ 4-42 to 4-45 Controller with LCD HMI IS-UNITY-DP IS-UNITY-DP Liebert eXM™ 4-46 to 4-49 Controller with Touchscreen HMI IS-UNITY-DP IS-UNITY-DP Liebert GXT3™ 4-50 to 4-53 — IS-UNITY-DP IS-UNITY-DP ™ Liebert GXT4 4-50 to 4-53 — IS-UNITY-DP IS-UNITY-DP Liebert NX™ 225-600 4-54 to 4-57 — IS-UNITY-DP IS-UNITY-DP NXC™ 4-26 to 4-29 — IS-UNITY-DP IS-UNITY-DP Liebert NXR™ 4-26 to 4-29 — IS-UNITY-DP IS-UNITY-DP Liebert NXL- 60Hz, UL version (Model 40) 4-58 to 4-62 — IS-UNITY-DP IS-UNITY-DP Liebert NXL™ - 50Hz, CE version (Models 48 and 49) 4-63 to 4-66 — IS-UNITY-DP IS-UNITY-DP Liebert 5 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Liebert Equipment Compatibility Table 1-2 Product Supported Liebert Equipment and Compatible Liebert IntelliSlot Cards BACnet MSTP & BACnet IP Protocols (continued) Compatible Card Part Number Refer to Tables: Controller / Protocol BACNet IP BACnet MSTP IS-UNITY-DP IS-UNITY-DP IS-485S* IS-UNITY-DP IS-UNITY-DP Power Distribution and Power Conditioning Products Liebert EXC™ 4-67 to 4-69, 4-75 LDMF Liebert FDC™ 4-67 to 4-71, 4-75 LDMF, CPM Liebert FPC™ 4-67 to 4-75 Liebert PPC™ 4-67 to 4-75 Liebert RDC™ 4-67 to 4-71, 4-75 LDMF, CPM Liebert RX™ 4-67 to 4-69, 4-75 LDMF 4-76 to 4-79 — VPMP, LDMF, CPM Battery Monitoring Products Alber BDSU™ Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 6 Modbus Communications 2.0 Modbus Communications 2.1 Implementation Basics Modbus protocol provides control and data acquisition, through query and response, between master and slave devices. This protocol comprises the rules for communication, controlling the message format between devices, how master and slave devices initiate communications, as well as unit identification, message-handling and error-checking. The Liebert IntelliSlot 485/IP card acts as a slave device on a network. This network can be a multidrop configuration over EIA-485, where multiple slaves reside on a common wire or loop. 2.2 Transmission Format The Liebert IntelliSlot 485/IP interface card supports Modbus Remote Terminal Unit (RTU) transmission modes. See Table 2-1 below. Table 2-1 Modbus Remote Terminal Unit settings for Liebert IntelliSlot 485/IP interface card Physical Port Transmission Mode Baud Rate Data Bits Parity Bits Stop Bits Start Bits EIA-485/422 2 wire RTU 9600, 19200 or 38400 8 None 1 1 2.3 Modbus Packet Format Each Modbus packet consists of these fields: • Device Address • Function Code • Data Field(s) • Error Check Field 2.3.1 Device Address The address field immediately follows the beginning of the frame and consists of 8-bits (RTU). This bit indicates the user-assigned address of the slave device that is to receive the message from the attached master device. Each slave must be assigned a unique address. Only the addressed slave will respond to a query that contains its address. 7 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus Communications 2.3.2 Function Code The function code field tells the addressed slaves what function to perform. Function codes are designed to invoke a specific action by the slave device. The function code ranges from 1 to 127. Liebert IntelliSlot Modbus server supports the following Modbus function codes. Table 2-2 Code Supported Modbus function codes Function Description 01 Read Coils Read from 1 to 2000 contiguous status of coils managed by the server. Coils in the response message are packed as one per bit of a byte, 1=On and 0=Off. If the requested quantity of coils is not a multiple of 8, zeros are padded in the final byte. 02 Read Discrete Inputs Read from 1 to 2000 contiguous input status managed by the server. Discrete inputs in the response message are packed as one per bit of a byte, 1=On and 0=Off. If the requested number of inputs is not a multiple of 8, zeros are padded in the final byte. 03 Read Holding Registers Read the contents of contiguous block of 1 to 127 holding registers. Data are packed as two bytes per register; the first byte contains the high order bits. 04 Read Input Registers Read the contents of contiguous block of 1 to 127 Input registers. Data are packed as two bytes per register; the first byte contains the high order bits. 05 Write Single Coil Write a single output to either On (1) or Off (0) mapped in coil section. 06 Write Single Register Write a value into a single holding register; 15 Write Multiple Coils Force each coil in a sequence of coils to either On or Off. 16 Write Multiple Registers Write values into a block of contiguous registers (1 to 120) 2.3.3 Data Fields The data field length varies, depending on whether the message is a request or a response to a packet. This field typically contains information required by the slave device to perform the command specified or to the response to a data request from the master device. Because Modbus can return only positive numbers, in registers that contain signed numbers the negative numbers are encoded in two’s-complement form. For example, in a 16-bit register a -7 becomes FFF9 in hexidecimal or 65529 in decimal. 2.3.4 Error Check Field The Error Check Field consists of a 16-bit (2 byte) Cyclical Redundancy Check (CRC16). It allows the receiving device to detect a packet that has been corrupted by transmission errors. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 8 Modbus Communications 2.3.5 RTU Framing The example below shows a typical query and response from a Liebert IntelliSlot interface card. The master device initiates a query asking Slave Device, with address 2, for holding registers starting at holding register 40051 (offset 50) and including next two registers (three total). Table 2-3 Query sample Starting Register Number of Registers CRC16 Slave Address Function Code Hi Byte Lo Byte Hi Byte Lo Byte Hi Byte Lo Byte 02 03 00 32 00 03 E5 FA Table 2-4 Slave Address Function Code Count: Bytes of Data 02 03 6 Response sample Register 40051 Data 40052 Data CRC16 40053 Data Hi Lo Hi Lo Hi Lo Hi Byte Lo Byte 1 58 00 FA 00 54 1B 0D Slave Device, with address 2, responds to Function Code 3 with 6 bytes of hexadecimal data and ends with CRC16 checksum. Register values: 40051 = 158 (hex) = 344 (decimal) 40052 = FA (hex) = 250 (decimal) 40053 = 54 (hex) = 9 84 (decimal) Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus Communications Page intentionally left blank. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 10 Modbus RTU and Modbus TCP Protocols—Thermal Management Products 3.0 Modbus RTU and Modbus TCP Protocols 3.1 Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Ext Reheat Lockout 10009 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Humidifier Lockout 10010 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Minimum Chilled Water Temp Set Point Enable 10013 13 1 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Sensor Event Control 10019 19 1 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Event Control 10020 20 1 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Compressor Lockout 10021 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 — 25 1 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan State 10025 — 1 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Cooling State 10026 — 1 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling State 10027 — 1 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Hot Water / Hot Gas State 10028 — 1 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 System On/Off Control 11 Notes Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Notes Extra Notes (see Table 3-2) 1 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 — 1 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 10031 — 1 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Main Fan Overload 10034 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Loss of Air Flow 10035 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Loss of Flow 10036 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Head Pressure 10037 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Low Suction Pressure 10038 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Thermal Overload 10039 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Pump Down Issue 10040 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Head Pressure 2 10041 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Low Suction Pressure 2 10042 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Thermal Overload 2 10043 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label Status Coil Number of Bits Electric Reheat State 10029 — Humidifier State 10030 Dehumidifier State Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 12 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Compressor Pump Down Issue 2 10044 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Over Temp 1 10045 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Over Temp 2 10046 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Smoke Detected 10047 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Water Under Floor 10048 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Issue 10049 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Standby Glycol Pump On 10050 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Standby Unit On 10051 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Condenser Pump High Water 10052 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Sensor Issue 10053 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Loss of Air Blower 10055 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Low Water 10058 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Over Current 10059 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 13 Notes Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Ext Over Temperature 10060 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Shutdown - Loss Of Power 10061 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Chilled Water Over Temp 10065 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Over Temperature 10067 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Under Temperature 10068 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Return Humidity 10069 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Low Return Humidity 10070 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Over Temperature 10071 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Under Temperature 10072 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A High Humidity 10073 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Low Humidity 10074 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Chilled Water Loss of Flow 10075 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Clogged Air Filter 10076 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 14 Notes Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Supply Air Sensor Issue 10077 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling Temp Sensor Issue 10078 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Issue 10079 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Hours Exceeded 10080 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Hours Exceeded 1 10081 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Hours Exceeded 2 10082 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling Valve Hours Exceeded 10083 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours Exceeded 1 10084 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours Exceeded 2 10085 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours Exceeded 3 10086 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Hot Water / Hot Gas Valve Hours Exceeded 10087 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Hours Exceeded 10088 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dehumidifier Hours Exceeded 10089 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 15 Notes Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Unit Communication Lost 10091 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Master Unit Communication Lost 10092 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Code Missing 10094 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Service Required 10098 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Control Board Not Detected 10099 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 1 10104 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 2 10105 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 3 10106 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 4 10107 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Temp Sensor Issue 1 10108 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Temp Sensor Issue 2 10109 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Air Over Temperature 10209 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Air Under Temperature 10210 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 16 Notes Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Ambient Air Sensor Issue 10211 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9, 11, 12, 13, 14 Compressor Short Cycle 1 10212 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Short Cycle 2 10213 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Free Cooling Lockout 10214 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Reheater Over Temperature 10215 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Cylinder Worn 10216 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Under Current 10217 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Issue 10218 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser TVSS Issue 10219 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser VFD Issue 10220 — 1 Active on Alarm 1, 2, 4, 6, 10 Notes Condenser Issue 1 10221 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser Issue 2 10222 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 BMS Communications Timeout 10223 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 17 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Digital Output Board Not Detected 1 10224 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Digital Output Board Not Detected 2 10225 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Digital Output Board Not Detected 3 10226 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RAM Battery Issue 10227 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Water Leakage Detector Sensor Issue 10228 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 External Fire Detected 10229 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Chilled Water Control Valve Failure 1 10230 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Chilled Water Control Valve Failure 2 10231 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Unit Off 10232 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit On 10233 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Partial Shutdown 10234 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Shutdown 10235 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Power Shutdown 10236 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 18 Notes Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Unit Standby 10237 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Maintenance Due 10238 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Maintenance Completed 10239 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Low Pressure Transducer Issue 1 10240 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Low Pressure Transducer Issue 2 10241 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Pressure Transducer Issue 1 10242 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Pressure Transducer Issue 2 10243 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Capacity Reduced 10244 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dew Point Over Temperature 10345 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Dew Point Under Temperature 10346 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Over Temperature 10347 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Under Temperature 10348 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Compressor Superheat Over Threshold 1 10349 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Compressor Superheat Over Threshold 2 10350 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Unspecified General Event 10351 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 19 Notes Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Remote Sensor Average Over Temperature 10352 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Average Under Temperature 10353 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Average Over Temperature 10354 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Average Under Temperature 10355 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 1 10356 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 2 10357 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 3 10358 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 4 10359 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 5 10360 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 6 10361 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 7 10362 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 8 10363 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 9 10364 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature 10 10365 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 1 10366 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 2 10367 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 3 10368 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 4 10369 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 5 10370 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 20 Notes Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Remote Sensor Under Temperature 6 10371 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 7 10372 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 8 10373 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 9 10374 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature 10 10375 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 1 10376 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 10, 11, 12, 13, 14 Remote Sensor Issue 2 10377 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 3 10378 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 4 10379 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 5 10380 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 6 10381 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 7 10382 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 8 10383 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 9 10384 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue 10 10385 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Air Economizer Emergency Override 10386 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Air Economizer Reduced Airflow 10387 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Temperature Control Sensor Issue 10388 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 21 Notes Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits EEV Unspecified General Event 10488 — 1 Active on Alarm 4, 6, 7, 8, 11, 13, 14 Static Pressure Sensor Issue 10489 — 1 Active on Alarm 3, 5, 6, 7, 8, 9, 11, 12, 13, 14 High Static Pressure 10490 — 1 Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Low Static Pressure 10491 — 1 Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Pump Unspecified General Event 10492 — 1 Active on Alarm 4, 6, 7, 8, 11, 13, 14 Condenser Unit Unspecified General Event 10493 — 1 Active on Alarm 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Circuit Unspecified General Event 10494 — 1 Active on Alarm 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Input Undervoltage 1 10500 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Input Undervoltage 2 10501 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Input Undervoltage 3 10502 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Input Undervoltage 4 10503 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Input Undervoltage 5 10504 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Input Undervoltage 6 10505 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Return Humidity Sensor Issue 10600 — 1 Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Compressor Low Differential Pressure Lockout 1 10601 — 1 Active on Alarm 6, 7, 8, 11, 12, 13, 14 Compressor Low Differential Pressure Lockout 2 10602 — 1 Active on Alarm 6, 7, 8, 11, 12, 13, 14 Airflow Sensor Issue 10603 — 1 Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Ext Air Damper Position Issue 10604 — 1 Active on Alarm 3, 5, 6, 7, 8, 9, 11, 12, 13, 14 Ext Power Source A Failure 10605 — 1 Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 22 Notes Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Ext Power Source B Failure 10606 — 1 Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Static Pressure Sensor Out of Range 10607 — 1 Active on Alarm 3, 5, 6, 7, 8, 9, 11, 12, 13, 14 Fluid Temperature Sensor Issue 1 10608 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Fluid Temperature Sensor Issue 2 10609 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Fluid Flow Sensor Issue 1 10610 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Fluid Flow Sensor Issue 2 10611 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Mixed Mode Lockout 10620 — 1 Active on Alarm 6, 7, 8, 11, 12, 13, 14 Aux Air Temp Device Communication Lost 10630 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost 1 10640 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost 2 10641 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost 3 10642 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost 4 10643 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost 5 10644 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost 6 10645 — 1 Active on Alarm 5, 8, 11, 12, 13, 14 External Condenser TVSS Issue 10655 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 External Condenser VFD Issue 10656 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Outside Air Temp Out of Operating Range 1 10677 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Outside Air Temp Out of Operating Range 2 10678 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Control Board Issue 1 10679 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 23 Notes Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Condenser Control Board Issue 2 10680 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Outside Air Temp Sensor Issue 1 10681 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Outside Air Temp Sensor Issue 2 10682 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Communication Lost 1 10683 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Communication Lost 2 10684 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Remote Shutdown 1 10685 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Remote Shutdown 2 10686 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser TVSS Issue 1 10687 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser TVSS Issue 2 10688 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Sensor Issue 1 10699 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Sensor Issue 2 10700 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Under Threshold 1 10701 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Under Threshold 2 10702 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Over Threshold 1 10703 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Over Threshold 2 10704 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temp Sensor Issue 1 10705 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temp Sensor Issue 2 10706 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Under Temp 1 10707 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 24 Notes Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Extra Notes (see Table 3-2) Data Label Status Coil Number of Bits Condenser Supply Refrigerant Under Temp 2 10708 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Over Temp 1 10709 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Over Temp 2 10710 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Max Fan Speed Override 1 10711 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Max Fan Speed Override 2 10712 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Issue 1 10723 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Issue 2 10724 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Issue 3 10725 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Issue 4 10726 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Issue 5 10727 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Issue 6 10728 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Issue 7 10729 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Issue 8 10730 — 1 Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Compressor 1B Thermal Overload 10741 — 1 Active on Alarm 9 Compressor 2B Thermal Overload 10742 — 1 Active on Alarm 9 Compressor 1B Hours Exceeded 10743 — 1 Active on Alarm 9 Compressor 2B Hours Exceeded 10744 — 1 Active on Alarm 9 Notes Team Static Pressure Sensor Failure 10750 — 1 Active on Alarm 9 Heating Lockout 10751 — 1 Active on Alarm 9 Free Cooling Stopped - High Room Temp 10752 — 1 Active on Alarm 9 Cold Aisle Temperature/Humidity Team Sensor Failure 10753 — 1 Active on Alarm 9 Cold Aisle Air Sensor Failure 1 10760 — 1 Active on Alarm 9 Cold Aisle Air Sensor Failure 2 10761 — 1 Active on Alarm 9 25 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Status and Coil (continued) Controller Liebert iCOM® v4 Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW Liebert Deluxe System/3 Liebert DS Liebert DSE Liebert PeX Units with Liebert Products Liebert iCOM®: Liebert HPM Available Points Status Data Label Coil Number of Bits Notes Extra Notes (see Table 3-2) Cold Aisle Air Sensor Failure 3 10762 — 1 Active on Alarm 9 Chilled Water Inlet Temperature Control Active 10770 — 1 Active on Alarm 9 Chilled Water Inlet Temperature Sensor Failure 1 10780 — 1 Active on Alarm Chilled Water Inlet Temperature Sensor Failure 2 10781 — 1 Active on Alarm Chilled Water Outlet Temperature Sensor Failure 1 10782 — 1 Active on Alarm Chilled Water Outlet Temperature Sensor Failure 2 10783 — 1 Active on Alarm Chilled Water Flow Meter Sensor Failure 1 10784 — 1 Active on Alarm Chilled Water Flow Meter Sensor Failure 2 10785 — 1 Active on Alarm Table 3-2 Number Extra notes key to Table 3-1 Description 1 This point is supported on: iCOM controller version 1.04.042.STD 2 This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version 2.00.12R (for Japan and China – language corrections only) 3 This point is supported on: iCOM controller version 2.01.29.07R 4 This point is supported on: iCOM controller version 2.02.21R 5 This point is supported on: iCOM controller version 2.01.45R 6 This point is supported on: iCOM controller version 2.03.27.06R 7 This point is supported on: iCOM controller version 2.03.33R 8 This point is supported on: iCOM controller version 2.04.32R 9 This point is supported on: iCOM controller version A9HB-1.04.23-R (Similar to Liebert PDX and to be replaced by separate family branch.) 10 This point is supported on: iCOM controller version 1.04.37O-STD 11 This point is supported on: iCOM controller version 2.05.12T 12 This point is supported on: iCOM controller version 2.01.53R 13 This point is supported on: iCOM controller version 2.04.???R (TBD) 14 This point is supported on: iCOM controller version 2.05.19R Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 26 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding Input Holding # of Regs Scale Units / Notes — 0 = Disabled 1 = Contact 2 = Temperature 3 = Set Point 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 1, 9, 10 Data Label Free Cooling Internal Control Mode 30017 40017 1 Extra Notes (see Table 3-4) Humidity Control Type 30018 40018 1 — 0 = Relative 1 = Compensated 2 = Predictive Fan Speed Maximum Set Point 30019 40019 1 — % Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Air Temperature Set Point 30020 40020 1 — deg C Int16 1, 9, 10 Supply Air Temperature Set Point 30733 40733 1 — deg F Int16 1, 9, 10 Free Cooling Internal Temperature Delta 30021 40021 1 10 deg C Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling Internal Temperature Delta 30734 40734 1 10 deg F Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Minimum Chilled Water Temp Set Point 30022 40022 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Minimum Chilled Water Temp Set Point 30735 40735 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Temperature Set Point 30023 40023 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Temperature Set Point 30736 40736 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Temperature Proportional Band 30024 40024 1 10 deg C Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Temperature Proportional Band 30737 40737 1 10 deg F Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Temperature Dead Band 30025 40025 1 10 deg C Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Temperature Dead Band 30738 40738 1 10 deg F Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Temperature Control Integration Time 30026 40026 1 10 min Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidity Set Point 30027 40027 1 — % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidity Proportional Band 30028 40028 1 — % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidity Control Integration Time 30029 40029 1 10 min Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidity Dead Band 30030 40030 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Auto Restart Delay 30031 40031 1 — sec Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 27 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Air Temperature Control Type 30033 40033 1 — 0 = Proportional 1 = Prop+Integral 3 = Intelligent 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 BMS Timeout Period 30045 40045 1 — min Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Return Air Temperature Threshold 30050 40050 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Return Air Temperature Threshold 30739 40739 1 10 deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Low Return Air Temperature Threshold 30051 40051 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Low Return Air Temperature Threshold 30740 40740 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Over Temp Threshold 30052 40052 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Over Temp Threshold 30741 40741 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Under Temp Threshold 30053 40053 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Under Temp Threshold 30742 40742 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Return Humidity Threshold 30054 40054 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Low Return Humidity Threshold 30055 40055 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A High Humidity Threshold 30056 40056 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Low Humidity Threshold 30057 40057 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Fan Hours Threshold 30070 40070 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Compressor Hours Threshold 1 30071 40071 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Compressor Hours Threshold 2 30072 40072 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Humidifier Hours Threshold 30073 40073 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Dehumidifier Hours Threshold 30074 40074 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Free Cooling Valve Hours Threshold 30075 40075 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Electric Reheater Hours Threshold 1 30076 40076 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Electric Reheater Hours Threshold 2 30077 40077 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 28 Extra Notes (see Table 3-4) Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) (Deprecated) Electric Reheater Hours Threshold 3 30078 40078 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Hot Water / Hot Gas Valve Hours Threshold 30079 40079 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Operating State 30100 - 1 — 0 = off 1 = on 2 = standby 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label 1 = Normal Operation 2 = StartUp 1, 2, 3, 4, 5, 6, 7, 8, 8 = Normal with Warning 9, 10, 11, 12, 13, 14 16 = Normal with Alarm 32 = Abnormal Operation System Status 30102 - 1 — Fan Speed 30103 — 1 — % Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Utilization 30104 — 1 — % Uint16 1, 9, 10 Free Cooling Valve Open Position 30105 — 1 — % Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Reheat Utilization 30106 — 1 — % Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Utilization 30107 — 1 — % Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dehumidifier Utilization 30108 — 1 — % Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Free Cooling Status 30109 — 1 — 0 = off 2 = on 3 = No Support 12, 13, 14 Return Air Temperature 30110 — 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Temperature 30743 — 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Air Temperature 30112 — 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Air Temperature 30744 — 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Air Temperature Set Point 30113 — 1 — deg C Int16 1, 9, 10 Supply Air Temperature Set Point 30745 — 1 — deg F Int16 1, 9, 10 Free Cooling Fluid Temperature 30115 — 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling Fluid Temperature 30746 — 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Temperature 30116 — 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 29 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Ext Air Sensor A Temperature 30747 — 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor B Temperature 30117 — 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor B Temperature 30748 — 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor C Temperature 30118 — 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor C Temperature 30749 — 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Temp 1 30119 — 1 — deg C Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Temp 1 30750 — 1 — deg F Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Temp 2 30120 — 1 — deg C Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Temp 2 30751 — 1 — deg F Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Humidity 30130 — 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Humidity 30132 — 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor B Humidity 30133 — 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor C Humidity 30134 — 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Today's High Air Temperature 30151 — 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Today's High Air Temperature 30752 — 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Today's Low Air Temperature 30153 — 1 10 deg C Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Today's Low Air Temperature 30753 — 1 10 deg F Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Today's High Humidity 30155 — 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Today's Low Humidity 30157 — 1 10 % RH Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label Server Class 30257 — 1 — 1 = UPS 2 = AIR 3 = PMP 4 = PDU 5 = MONITOR Today's High Air Temperature Time 30258 — 2 — Seconds since Midnight Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 30 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes 30260 — 2 — Seconds since Midnight 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 9, 10 Data Label Today's Low Air Temperature Time Extra Notes (see Table 3-4) Supply Air Temperature Sensor Control 30262 40262 1 — 0 = Disabled 1 = Limit 2 = Control 3 = Temp Only Return Air Temperature Set Point 30263 40263 1 — deg C Int16 1, 9, 10 Return Air Temperature Set Point 30754 40754 1 — deg F Int16 1, 9, 10 Return Humidity Set Point 30264 40264 1 — % RH Uint16 1, 9, 10 Today's High Humidity Time 30265 - 2 — Seconds since Midnight — Today's Low Humidity Time 30267 — 2 — Seconds since Midnight — Compressor State 1 30269 — 1 — 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor State 2 30270 — 1 — 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Capacity Control State 1 30271 — 1 — 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Capacity Control State 2 30272 — 1 — 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Infrared Humidifier Flush Rate 30273 40273 1 — % Uint16 — 1, 9, 10 Fan Control Mode 30274 40274 1 — 0 = Auto 1 = Manual 2 = Economy 4 = Delta Analog Input Reading 1 30275 — 1 100 Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Analog Input Reading 2 30276 — 1 100 Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Analog Input Reading 3 30277 — 1 100 Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Analog Input Reading 4 30278 — 1 100 Int16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Control Mode 30280 — 1 — 0 = Internal (Auto) 1 = External (Manual) 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 — 0 = Reason Unknown 1 = Network Display 2 = Alarm 3 = Schedule 4 = Remote System 5 = External Input 6 = Local Display 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Operating State Reason 30281 — 1 31 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Maintenance Ramp 30282 — 1 — % Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Calculated Next Maintenance Month 30283 — 1 — Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Calculated Next Maintenance Year 30284 — 1 — Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Hot Water / Hot Gas Valve Open Position 30285 — 1 — % Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Maintenance Tracking State 30286 — 1 — 0 = off 1 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 1 - Event Control 30287 40287 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 1 - Event Type 30288 40288 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 2 - Event Control 30289 40289 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label Customer Input 2 - Event Type 30290 40290 1 — 0 = Message 1 = Warning 2 = Alarm Customer Input 3 - Event Control 30291 40291 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 3 - Event Type 30292 40292 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 4 - Event Control 30293 40293 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Customer Input 4 - Event Type 30294 40294 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Free Cooling Lockout - Event Control 30295 40295 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Free Cooling Lockout - Event Type 30296 40296 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Condenser Pump High Water Event Control 30297 40297 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Condenser Pump High Water Event Type 30298 40298 1 — 0 = Message 1 = Warning 2 = Alarm Ext Standby Glycol Pump On - Event Control 30299 40299 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Standby Glycol Pump On - Event Type 30300 40300 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 32 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Ext Standby Unit On - Event Control 30301 40301 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Standby Unit On - Event Type 30302 40302 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Humidifier Lockout - Event Control 30303 40303 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Humidifier Lockout - Event Type 30304 40304 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Loss of Flow - Event Control 30305 40305 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label Ext Loss of Flow - Event Type 30306 40306 1 — 0 = Message 1 = Warning 2 = Alarm Ext Over Temperature - Event Control 30307 40307 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Over Temperature - Event Type 30308 40308 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Reheat Lockout - Event Control 30309 40309 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Reheat Lockout - Event Type 30310 40310 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Power Shutdown - Event Control 30311 40311 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Power Shutdown - Event Type 30312 40312 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Issue - Event Control 30313 40313 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Issue - Event Type 30314 40314 1 — 0 = Message 1 = Warning 2 = Alarm Master Unit Communication Lost Event Control 30315 40315 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Master Unit Communication Lost Event Type 30316 40316 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Service Required - Event Control 30317 40317 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Service Required - Event Type 30318 40318 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 33 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Shutdown - Loss Of Power - Event Control 30319 40319 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Shutdown - Loss Of Power - Event Type 30320 40320 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Smoke Detected - Event Control 30321 40321 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Smoke Detected - Event Type 30322 40322 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Water Under Floor - Event Control 30323 40323 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label Water Under Floor - Event Type 30324 40324 1 — 0 = Message 1 = Warning 2 = Alarm Ext Compressor Lockout - Event Control 30325 40325 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Compressor Lockout - Event Type 30326 40326 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Clogged Air Filter - Event Control 30327 40327 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Clogged Air Filter - Event Type 30328 40328 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Loss of Air Blower - Event Control 30329 40329 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Loss of Air Blower - Event Type 30330 40330 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Head Pressure Event Control 1 30331 40331 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Head Pressure Event Control 2 30332 40332 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Head Pressure Event Type 1 30333 40333 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Head Pressure Event Type 2 30334 40334 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Low Suction Pressure Event Control 1 30335 40335 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Low Suction Pressure Event Control 2 30336 40336 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 34 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Compressor Low Suction Pressure Event Type 1 30337 40337 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Low Suction Pressure Event Type 2 30338 40338 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Pump Down Issue Event Control 1 30339 40339 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Pump Down Issue Event Control 2 30340 40340 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Pump Down Issue Event Type 1 30341 40341 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Pump Down Issue Event Type 2 30342 40342 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Short Cycle - Event Control 1 30343 40343 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Short Cycle - Event Control 2 30344 40344 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Short Cycle - Event Type 1 30345 40345 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Short Cycle - Event Type 2 30346 40346 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Thermal Overload Event Control 1 30347 40347 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Thermal Overload Event Control 2 30348 40348 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Thermal Overload Event Type 1 30349 40349 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Thermal Overload Event Type 2 30350 40350 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Over Temp - Event Ctrl 1 30351 40351 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Over Temp - Event Ctrl 2 30352 40352 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dig Scroll Comp Discharge Over Temp - Event Type 1 30353 40353 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label 35 Extra Notes (see Table 3-4) Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Dig Scroll Comp Discharge Over Temp - Event Type 2 30354 40354 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A High Humidity Event Control 30355 40355 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A High Humidity Event Type 30356 40356 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Low Humidity Event Control 30357 40357 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Low Humidity Event Type 30358 40358 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Over Temp - Event Control 30359 40359 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label Extra Notes (see Table 3-4) Ext Air Sensor A Over Temp - Event Type 30360 40360 1 — 0 = Message 1 = Warning 2 = Alarm Ext Air Sensor A Under Temp Event Control 30361 40361 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Under Temp Event Type 30362 40362 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Return Humidity - Event Control 30363 40363 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 High Return Humidity - Event Type 30364 40364 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Low Return Humidity - Event Control 30365 40365 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Low Return Humidity - Event Type 30366 40366 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Over Temp - Event Control 30367 40367 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Over Temp - Event Type 30368 40368 1 — 0 = Message 1 = Warning 2 = Alarm Return Air Under Temp - Event Control 30369 40369 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Under Temp - Event Type 30370 40370 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Hours Exceeded - Event Control 30371 40371 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 36 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Fan Hours Exceeded - Event Type 30372 40372 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Issue - Event Control 30373 40373 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Issue - Event Type 30374 40374 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Main Fan Overload - Event Control 30375 40375 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Main Fan Overload - Event Type 30376 40376 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser Issue - Event Control 1 30377 40377 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser Issue - Event Control 2 30378 40378 1 — 0 = disabled 1 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser Issue - Event Type 1 30379 40379 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser Issue - Event Type 2 30380 40380 1 — 0 = Message 1 = Warning 2 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 — 40381 1 — 2 = Reset 4 = Acknowledge 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Temperature Control Sensor 30481 40481 1 — 0 = Supply 1 = Remote 2 = Return 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 High Supply Air Temperature Threshold 30482 40482 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 High Supply Air Temperature Threshold 30755 40755 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Low Supply Air Temperature Threshold 30483 40483 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Low Supply Air Temperature Threshold 30756 40756 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Outside Air Temperature 30484 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Outside Air Temperature 30757 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 — 0 = Relative 1 = Compensated 2 = Predictive 3 = Dew Point 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Data Label System Event Acknowledge/Reset Humidity Control Type 30485 40485 1 37 Extra Notes (see Table 3-4) Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Ext Air Sensor A Dew Point Temp 30486 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Air Sensor A Dew Point Temp 30758 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Over Temp Threshold 30487 40487 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Over Temp Threshold 30759 40759 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Under Temp Threshold 30488 40488 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Under Temp Threshold 30760 40760 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Compressor Lockout 30489 40489 1 — 0 = disabled 1 = enabled 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Main Chilled Water Valve 30491 40491 1 — 0 = Valve 1 1 = Valve 2 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Reheater Lockout 30492 40492 1 — 0 = disabled 1 = enabled 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Humidifier Lockout 30493 40493 1 — 0 = disabled 1 = enabled 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Data Label Fan Control Sensor 30494 40494 1 — 0 = Supply 1 = Remote 2 = Return 3 = Manual Fan Speed Minimum Set Point 30495 40495 1 — % Uint16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Speed Temperature Set Point 30497 40497 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Speed Temperature Set Point 30761 40761 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Standby Units 30498 40498 1 — Uint16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Adjusted Humidity 30499 — 1 10 % RH Uint16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Return Dew Point 30500 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Return Dew Point 30762 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Actual Air Temperature Set Point 30501 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Actual Air Temperature Set Point 30763 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Actual Humidity Set Point 30502 — 1 — % RH Uint16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 38 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Dew Point Set Point 30764 40764 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Supply Air Over/Under Temperature - Event Control 30504 40504 1 — 0 = disabled 1 = enabled 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temp Threshold 30505 40505 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temp Threshold 30765 40765 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temp Threshold 30506 40506 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temp Threshold 30766 40766 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Average Temperature 30507 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Average Temperature 30767 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Maximum Temperature 30508 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Maximum Temperature 30768 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Average Temperature 30509 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Average Temperature 30769 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Maximum Temperature 30510 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Maximum Temperature 30770 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 1 30551 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 1 30771 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 2 30552 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 2 30772 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 3 30553 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 3 30773 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 4 30554 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 4 30774 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Data Label 39 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Remote Sensor Temperature 5 30555 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 5 30775 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 6 30556 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 6 30776 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 7 30557 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 7 30777 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 8 30558 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 8 30778 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 9 30559 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 9 30779 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 10 30560 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature 10 30780 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Air Economizer Availability 30561 — 1 — 0 = Not Available 1 = Available 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Air Economizer Control Source 30562 40562 1 — 0 = disabled 1 = internal 2 = external 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Cooling Capacity 30564 — 1 — % Uint16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Cooling Control Temperature 30565 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Cooling Control Temperature 30781 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Speed Control Temperature 30566 — 1 10 deg C Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Speed Control Temperature 30782 — 1 10 deg F Int16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 — 0 = Disabled 1 = Contact 2 = Temperature 3 = Set Point 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Data Label Free Cooling Internal Control Mode 30567 40567 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 1 40 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Humidity Control Sensor 30667 40667 1 — 0 = Supply 1 = Remote 2 = Return 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Digital Scroll Compressor Loading 1 30668 — 1 — % Uint16 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Digital Scroll Compressor Loading 2 30669 — 1 — % Uint16 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Static Pressure Set Point 30672 40672 1 10 Pa Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Unit Static Pressure 30673 — 1 10 Pa Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 System Static Pressure 30674 — 1 10 Pa Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Low Noise Mode State 30675 — 1 — 0 = Inactive 1 = Active (Interval) 2 = Active (Full Day) 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Low Noise Mode Schedule Control 30676 40676 1 — 0 = disabled 1 = enabled 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Low Noise Mode Max Fan Speed 30677 40677 1 — % Uint16 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Normal Mode Max Fan Speed 30678 40678 1 — % Uint16 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 — 1 = Monday 2 = Tuesday 4 = Wednesday 8 = Thursday 16 = Friday 32 = Saturday 64 = Sunday 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Data Label Condenser Low Noise Mode Interval Days 30679 40679 1 Extra Notes (see Table 3-4) Condenser Low Noise Mode - Full Days 30680 40680 1 — 1 = Monday 2 = Tuesday 4 = Wednesday 8 = Thursday 16 = Friday 32 = Saturday 64 = Sunday Condenser Low Noise Mode Start Time 30681 40681 2 — Seconds since Midnight 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Low Noise Mode Stop Time 30683 40683 2 — Seconds since Midnight 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Pump Hours 1 30685 40685 2 — hr Uint32 6, 7, 8, 11, 13, 14 Pump Hours 2 30687 40687 2 — hr Uint32 6, 7, 8, 11, 13, 14 41 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) System Input RMS A-N 1 30800 — 1 10 VAC Int16 5, 8, 9, 11, 12, 13, 14 System Input RMS A-N 2 30801 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS A-N 3 30802 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS A-N 4 30803 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS A-N 5 30804 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS A-N 6 30805 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-N 1 30810 — 1 10 VAC Int16 5, 8, 9, 11, 12, 13, 14 System Input RMS B-N 2 30811 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-N 3 30812 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-N 4 30813 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-N 5 30814 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-N 6 30815 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-N 1 30820 — 1 10 VAC Int16 5, 8, 9, 11, 12, 13, 14 System Input RMS C-N 2 30821 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-N 3 30822 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-N 4 30823 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-N 5 30824 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-N 6 30825 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase A 1 30830 — 1 10 A AC Int16 5, 8, 9, 11, 12, 13, 14 System Input RMS Current Phase A 2 30831 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase A 3 30832 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase A 4 30833 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 Data Label Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 42 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes System Input RMS Current Phase A 5 30834 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase A 6 30835 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase B 1 30840 — 1 10 A AC Int16 5, 8, 9, 11, 12, 13, 14 System Input RMS Current Phase B 2 30841 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase B 3 30842 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase B 4 30843 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase B 5 30844 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase B 6 30845 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase C 1 30850 — 1 10 A AC Int16 5, 8, 9, 11, 12, 13, 14 System Input RMS Current Phase C 2 30851 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase C 3 30852 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase C 4 30853 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase C 5 30854 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 System Input RMS Current Phase C 6 30855 — 1 10 A AC Int16 5, 8, 11, 12, 13, 14 Energy Consumption 1 30870 40870 2 — kWH Int32 5, 8, 9, 11, 12, 13, 14 Energy Consumption 2 30872 40872 2 — kWH Int32 5, 8, 11, 12, 13, 14 Energy Consumption 3 30874 40874 2 — kWH Int32 5, 8, 11, 12, 13, 14 Energy Consumption 4 30876 40876 2 — kWH Int32 5, 8, 11, 12, 13, 14 Energy Consumption 5 30878 40878 2 — kWH Int32 5, 8, 11, 12, 13, 14 Energy Consumption 6 30880 40880 2 — kWH Int32 5, 8, 11, 12, 13, 14 Fluid Input Temperature 1 30900 — 1 10 deg C Int16 5, 8, 11, 12, 13, 14 Fluid Input Temperature 2 30901 — 1 10 deg C Int16 5, 8, 11, 12, 13, 14 Data Label 43 Extra Notes (see Table 3-4) Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Fluid Input Temperature 1 30902 — 1 10 deg F Int16 5, 8, 11, 12, 13, 14 Fluid Input Temperature 2 30903 — 1 10 deg F Int16 5, 8, 11, 12, 13, 14 Fluid Output Temperature 1 30904 — 1 10 deg C Int16 5, 8, 11, 12, 13, 14 Fluid Output Temperature 2 30905 — 1 10 deg C Int16 5, 8, 11, 12, 13, 14 Fluid Output Temperature 1 30906 — 1 10 deg F Int16 5, 8, 11, 12, 13, 14 Fluid Output Temperature 2 30907 — 1 10 deg F Int16 5, 8, 11, 12, 13, 14 Fluid Flow Rate 1 30908 — 2 10 l/min Int32 5, 8, 11, 12, 13, 14 Fluid Flow Rate 2 30910 — 2 10 l/min Int32 5, 8, 11, 12, 13, 14 Unit Cooling Load 31001 — 2 10 kW Int32 5, 8, 11, 12, 13, 14 Circuit Cooling Load 1 31003 — 2 10 kW Int32 5, 8, 11, 12, 13, 14 Circuit Cooling Load 2 31005 — 2 10 kW Int32 5, 8, 11, 12, 13, 14 Instantaneous Power 1 31010 — 2 — W Int32 5, 8, 9, 11, 12, 13, 14 Instantaneous Power 2 31012 — 2 — W Int32 5, 8, 11, 12, 13, 14 Instantaneous Power 3 31014 — 2 — W Int32 5, 8, 11, 12, 13, 14 Instantaneous Power 4 31016 — 2 — W Int32 5, 8, 11, 12, 13, 14 Instantaneous Power 5 31018 — 2 — W Int32 5, 8, 11, 12, 13, 14 Instantaneous Power 6 31020 — 2 — W Int32 5, 8, 11, 12, 13, 14 Raw Auxiliary Air Temperature 31050 41050 1 10 deg C Int16 5, 8, 11, 12, 13, 14 Raw Auxiliary Air Temperature 31051 41051 1 10 deg F Int16 5, 8, 11, 12, 13, 14 Actual Auxiliary Air Temperature 31052 — 1 10 deg C Int16 5, 8, 11, 12, 13, 14 Actual Auxiliary Air Temperature 31053 — 1 10 deg F Int16 5, 8, 11, 12, 13, 14 System Input RMS A-B 1 31060 — 1 10 VAC Int16 5, 8, 9, 11, 12, 13, 14 Data Label Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 44 Extra Notes (see Table 3-4) Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes System Input RMS A-B 2 31061 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS A-B 3 31062 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS A-B 4 31063 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS A-B 5 31064 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS A-B 6 31065 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-C 1 31070 — 1 10 VAC Int16 5, 8, 9, 11, 12, 13, 14 System Input RMS B-C 2 31071 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-C 3 31072 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-C 4 31073 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-C 5 31074 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS B-C 6 31075 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-A 1 31080 — 1 10 VAC Int16 5, 8, 9, 11, 12, 13, 14 System Input RMS C-A 2 31081 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-A 3 31082 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-A 4 31083 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-A 5 31084 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 System Input RMS C-A 6 31085 — 1 10 VAC Int16 5, 8, 11, 12, 13, 14 Pump State 1 31100 — 1 — 0 = off 1 = on 7, 8, 11, 13, 14 Pump State 2 31110 — 1 — 0 = off 1 = on 7, 8, 11, 13, 14 Expected Condenser Unit Count 31130 — 1 — Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Type 31131 — 1 — 0 = R22 1 = R407C 2 = R410A 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Reversal Requested 1 31142 — 1 — 0 = false 1 = true 3, 5, 7, 8, 9, 11, 12, 13, 14 Data Label 45 Extra Notes (see Table 3-4) Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Condenser Fan Reversal Requested 2 31143 — 1 — 0 = false 1 = true 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Outside Air Temperature 1 31144 — 1 10 deg C Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Outside Air Temperature 1 31145 — 1 10 deg F Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Outside Air Temperature 2 31146 — 1 10 deg C Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Outside Air Temperature 2 31147 — 1 10 deg F Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Refrigerant Pressure 1 31158 — 1 10 bar 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure 2 31159 — 1 10 bar Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temperature 1 31160 — 1 10 deg C Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temperature 1 31161 — 1 10 deg F Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temperature 2 31162 — 1 10 deg C Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temperature 2 31163 — 1 10 deg F Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Speed 1 31174 — 1 — % Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Speed 2 31175 — 1 — % Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Speed 3 31176 — 1 — % Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Speed 4 31177 — 1 — % Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Speed 5 31178 — 1 — % Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Speed 6 31179 — 1 — % Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Speed 7 31180 — 1 — % Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Speed 8 31181 — 1 — % Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power 1 31182 — 1 — W Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power 2 31183 — 1 — W Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power 3 31184 — 1 — W Int16 3, 5, 7, 8, 11, 12, 13, 14 Data Label Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 46 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) Condenser Fan Power 4 31185 — 1 — W Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power 5 31186 — 1 — W Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power 6 31187 — 1 — W Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power 7 31188 — 1 — W Int16 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power 8 31189 — 1 — W Int16 3, 5, 7, 8, 11, 12, 13, 14 Cold Aisle Humidity Calculation Method 31200 — 1 — 0 = Highest 1 = Average 9 Cold Aisle Temperature Calculation Method 31201 — 1 — 0 = Highest 1 = Average 9 Cold Aisle Control Enable 31202 — 1 — 0 = disabled 1 = enabled 9 Cold Aisle Force Max Fan/Cooling Ext Control 31203 — 1 — 0 = disabled 1 = enabled 9 Actual Cold Aisle Humidity 31204 — 1 10 % RH Int16 9 Actual Cold Aisle Temperature 31205 — 1 10 deg C Int16 9 Actual Cold Aisle Temperature 31206 — 1 10 deg F Int16 9 Cold Aisle Cascade Fan Speed Max Set Point 31207 — 1 — % Int16 9 Cold Aisle Fan Speed Min Set Point 31208 — 1 — % Int16 9 Cold Aisle Fan Speed Max Set Point 31209 — 1 — % Int16 9 Chilled Water Valve Reset Enable 31211 — 1 — 0 = disabled 1 = enabled 9 Humidification Fan Speed Min Set Point 31212 — 1 — % Int16 9 Heating Fan Speed Min Set Point 31213 — 1 — % Int16 9 Dehumidification Fan Speed Min Set Point 31214 — 1 — % Int16 9 Back Draft Control Fan Speed 31215 — 1 — % Int16 9 Data Label 47 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 8, 11, 12, 13, 14 Data Label Local Fan Override Local Cooling Override Local Electric Heat Override Local Humidifier Override 31300 31301 31302 31303 — — — — 1 1 1 1 Extra Notes (see Table 3-4) Local Dehumidifier Override 31304 — 1 — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection Super Saver Call For Cooling 31320 — 1 — % Int16 9, 11, 14 Tandem 'B' Compressor State 1 31325 — 1 — 0 = off 1 = on 8, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 48 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Tandem 'B' Compressor State 2 31326 — 1 — 0 = off 1 = on 8, 11, 12, 13, 14 Tandem 'B' Compressor Hours 1 31327 41327 2 — hr Int32 8, 11, 12, 13, 14 Tandem 'B' Compressor Hours 2 31329 41329 2 — hr Int32 8, 11, 12, 13, 14 Condenser Fan Current 1 31331 — 1 10 A AC Uint16 8, 11, 13, 14 Condenser Fan Current 2 31332 — 1 10 A AC Uint16 8, 11, 13, 14 Condenser Fan Current 3 31333 — 1 10 A AC Uint16 8, 11, 13, 14 Condenser Fan Current 4 31334 — 1 10 A AC Uint16 8, 11, 13, 14 Condenser Fan Current 5 31335 — 1 10 A AC Uint16 8, 11, 13, 14 Condenser Fan Current 6 31336 — 1 10 A AC Uint16 8, 11, 13, 14 Condenser Fan Current 7 31337 — 1 10 A AC Uint16 8, 11, 13, 14 Condenser Fan Current 8 31338 — 1 10 A AC Uint16 8, 11, 13, 14 Compressor Hours 1 31340 41340 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Hours 2 31342 41342 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Chilled Water Valve Hours 31344 41344 2 — hr Int32 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Free Cooling Valve Hours 31346 41346 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Hot Water / Hot Gas Valve Hours 31348 41348 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours 1 31350 41350 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours 2 31352 41352 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours 3 31354 41354 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Hours 31356 41356 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dehumidifier Hours 31358 41358 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Hours 31360 41360 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Data Label 49 Extra Notes (see Table 3-4) Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Extra Notes (see Table 3-4) (Deprecated) Chilled Water Valve Hours 30563 40563 1 — hr Uint16 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 (Deprecated) Fan Hours 30141 40141 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Compressor Hours 1 30142 40142 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Compressor Hours 2 30143 40143 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Humidifier Hours 30144 40144 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Dehumidifier Hours 30145 40145 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Free Cooling Valve Hours 30146 40146 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Electric Reheater Hours 1 30147 40147 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Electric Reheater Hours 2 30148 40148 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Electric Reheater Hours 3 30149 40149 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 (Deprecated) Hot Water / Hot Gas Valve Hours 30150 40150 1 — hr Uint16 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Static Pressure Set Point 31370 41370 1 1000 inWC Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Unit Static Pressure 31371 — 1 1000 inWC Int16 3, 5, 7, 8, 11, 12, 13, 14 System Static Pressure 31372 — 1 1000 inWC Int16 3, 5, 7, 8, 9, 11, 12, 13, 14 Dew Point Proportional Band 31380 41380 1 10 deg C Int16 Dew Point Proportional Band 31382 41382 1 10 deg F Int16 Dew Point Dead Band 31384 41384 1 10 deg C Int16 Dew Point Dead Band 31386 41386 1 10 deg F Int16 Free Cooling Status 30109 — 1 — 0 = off 1 = start 2 = on 11, 12, 13, 14 Thermal Control Override 31390 41390 1 — 0 = disabled 1 = enabled 11, 14 Thermal Control Override Temperature Control Type 31391 41391 1 — 0 = Cooling 1 = Heating 11, 14 Thermal Control Override Temperature Call 31392 41392 1 — % Int16 11, 14 Data Label Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 50 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Thermal Control Override - Humidity Control Type 31393 41393 1 — 0 = Dehumidification 1 = Humidification 11, 14 Thermal Control Override - Humidity Call 31394 41394 1 — % Int16 11, 14 Underfloor Static Pressure Control Enable 31400 — 1 — 0 = disabled 1 = enabled 2 = visualization only 9 Return Damper Status 31401 — 1 — 0 = closed 1 = open Air Filter Differential Pressure 31402 — 1 — Pa Int16 9 Air Filter Differential Pressure 31403 — 1 100 inWC Int16 9 Cold Aisle Sensor Air Temperature 1 31410 — 1 10 deg C Int16 9 Cold Aisle Sensor Air Temperature 1 31416 — 1 10 deg F Int16 9 Cold Aisle Sensor Air Temperature 2 31411 — 1 10 deg C Int16 9 Cold Aisle Sensor Air Temperature 2 31417 — 1 10 deg F Int16 9 Cold Aisle Sensor Air Temperature 3 31412 — 1 10 deg C Int16 9 Cold Aisle Sensor Air Temperature 3 31418 — 1 10 deg F Int16 9 Cold Aisle Sensor Humidity 1 31413 — 1 10 % RH Int16 9 Cold Aisle Sensor Humidity 2 31414 — 1 10 % RH Int16 9 Cold Aisle Sensor Humidity 3 31415 — 1 10 % RH Int16 9 Chilled Water Inlet Temperature 1 31420 — 1 10 deg C Int16 9 Chilled Water Inlet Temperature 1 31424 — 1 10 deg F Int16 9 Chilled Water Inlet Temperature 2 31421 — 1 10 deg C Int16 9 Chilled Water Inlet Temperature 2 31425 — 1 10 deg F Int16 9 Chilled Water Outlet Temperature 1 31422 — 1 10 deg C Int16 9 Chilled Water Outlet Temperature 1 31426 — 1 10 deg F Int16 9 Chilled Water Outlet Temperature 2 31423 — 1 10 deg C Int16 9 Data Label 51 Extra Notes (see Table 3-4) Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Chilled Water Outlet Temperature 2 31427 — 1 10 deg F Int16 9 Compressor Hours Threshold 1 31430 41430 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Hours Threshold 2 31432 41432 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling Valve Hours Threshold 31434 41434 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Hot Water / Hot Gas Valve Hours Threshold 31436 41436 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours Threshold 1 31438 41438 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours Threshold 2 31440 41440 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater Hours Threshold 3 31442 41442 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidifier Hours Threshold 31444 41444 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dehumidifier Hours Threshold 31446 41446 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Hours Threshold 31448 41448 2 — hr Int32 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Chilled Water Valve Operating Hours Threshold 31450 41450 2 — hr Int32 12, 13, 14 Pump Speed 1 31452 — 1 — % Uint16 13, 14 Pump Speed 2 31453 — 1 — % Uint16 13, 14 Pump Inlet Refrigerant Temperature 1 31454 — 1 10 deg C Int16 13, 14 Pump Inlet Refrigerant Temperature 1 31461 — 1 10 deg F Int16 13, 14 Pump Inlet Refrigerant Temperature 2 31455 — 1 10 deg C Int16 13, 14 Pump Inlet Refrigerant Temperature 2 31462 — 1 10 deg F Int16 13, 14 Pump Outlet Refrigerant Temperature 1 31456 — 1 10 deg C Int16 13, 14 Pump Outlet Refrigerant Temperature 1 31463 — 1 10 deg F Int16 13, 14 Pump Outlet Refrigerant Temperature 2 31457 — 1 10 deg C Int16 13, 14 Pump Outlet Refrigerant Temperature 2 31464 — 1 10 deg F Int16 13, 14 Data Label Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 52 Extra Notes (see Table 3-4) Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Input and Holding (continued) Input Holding # of Regs Scale Units / Notes Pump Hours Threshold 31458 41458 2 — hr Int32 13, 14 Unit Calculated Airflow 31466 — 2 — m3/h Uint32 12, 13, 14 — 0 = Bootup 1 = Idle 2 = Manual 3 = Pump Automatic 4 = Test 13, 14 13, 14 Data Label PRE Operational Mode 1 31468 — 1 PRE Operational Mode 2 31469 — 1 — 0 = Bootup 1 = Idle 2 = Manual 3 = Pump Automatic 4 = Test System Date and Time 39998 49998 2 — Secs since Epoch(UTC) Table 3-4 Extra Notes (see Table 3-4) Extra notes key to Table 3-3 Number Description 1 This point is supported on: iCOM controller version 1.04.042.STD 2 This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version 2.00.12R (for Japan and China – language corrections only) 3 This point is supported on: iCOM controller version 2.01.29.07R 4 This point is supported on: iCOM controller version 2.02.21R 5 This point is supported on: iCOM controller version 2.01.45R 6 This point is supported on: iCOM controller version 2.03.27.06R 7 This point is supported on: iCOM controller version 2.03.33R 8 This point is supported on: iCOM controller version 2.04.32R 9 This point is supported on: iCOM controller version A9HB-1.04.xx (Similar to Liebert PDX and to be replaced by separate family branch.) 10 This point is supported on: iCOM controller version 1.04.37O-STD 11 This point is supported on: iCOM controller version 2.05.18R 12 This point is supported on: iCOM controller version 2.01.53R 13 This point is supported on: iCOM controller version 2.04.???R (TBD) 14 This point is supported on: iCOM controller version 2.05.19R 53 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary Data Label Data Description (Deprecated) Free Cooling Status (Deprecated) Free cooling status. Actual Air Temperature Set Point The actual set point being used for air temperature control. This value may differ from [Air Temperature Set Point] if compensation is applied by the control. Actual Auxiliary Air Temperature Actual auxiliary air temperature value being used for control. This value may differ from the raw value received from the auxiliary device if filtering is applied. Actual Cold Aisle Humidity Actual humidity value being used for cold aisle humidity control. The value is calculated from multiple humidity measurements using [Cold Aisle Humidity Calculation Method]. Actual Cold Aisle Temperature Actual temperature value being used for cold aisle temperature control. The value is calculated from multiple temperature measurements using [Cold Aisle Temperature Calculation Method]. Actual Humidity Set Point The actual set point being used for humidity control. This value may differ from [Humidity Set Point] if compensation is applied by the control. Adjusted Humidity Humidity value being used for control. This value may differ from the actual measured [Return Humidity] based on several factors which may include, but are not limited to, selection of humidity control sensor and humidity control type. Air Economizer Availability Indicates if the outside air conditions are appropriate for cooling with the air economizer or glycol freecooling. Air Economizer Control Source Source of control of the air economizer. Air Economizer Emergency Override Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling. Air Economizer Reduced Airflow Air economizer filter is dirty and needs to be cleaned or replaced. Air Filter Differential Pressure Differential pressure across the air filter. Air Temperature Control Integration Time Time value used when system is under integral air temperature control. Air Temperature Control Sensor Sensor from which air temperature measurements will be used for cooling and heating control. Air Temperature Control Type Type of algorithm used to control the system's output air temperature. Air Temperature Dead Band Value that is divided evenly to form a temperature range above and below [Air Temperature Set Point]. If measured air temperature is within this range, no heating or cooling will occur. Air Temperature Proportional Band Value that is divided evenly to form proportional temperature control bands above and below [Air Temperature Set Point]. Air Temperature Set Point Desired air temperature. This set point is dependent upon which sensor is selected for control. Airflow Sensor Issue Airflow sensor is disconnected or the signal is out of range. Ambient Air Sensor Issue Ambient air sensor is disconnected or the signal is out of range. Analog Input Reading Generic analog input reading (unitless). Auto Restart Delay If power is lost, the control will delay this amount of time after power is restored before restarting the unit. Aux Air Temp Device Communication Lost Communication with external auxiliary device providing an air temperature value has been lost. Back Draft Control Fan Speed Fan speed when in back draft control mode. BMS Communications Timeout Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe. BMS Timeout Period Timeframe within which the Building Management System (or external monitoring system) must communicate with the system to avoid a timeout. Calculated Next Maintenance Month Calculated month of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Year]. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 54 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Calculated Next Maintenance Year Calculated year of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Month]. Chilled Water Control Valve Failure Chilled water valve out of position. Chilled water control valve position does not match expected value. Chilled Water Flow Meter Sensor Failure Chilled water flow meter sensor is disconnected or the signal is out of range. Chilled Water Inlet Temperature Control Active Chilled water inlet temperature control is active. Chilled Water Inlet Temperature Sensor Failure Chilled water inlet temperature sensor is disconnected or the signal is out of range. Chilled Water Inlet Temperature Temperature of the water entering the hydraulic circuit of the chilled water unit. Chilled Water Outlet Temperature Chilled water outlet temperature sensor is disconnected or the signal is out of range. Sensor Failure Chilled Water Outlet Temperature Temperature of the water exiting the hydraulic circuit of the chilled water unit. Chilled Water Valve Hours Operating hours for chilled water valve since last reset of this value. Chilled Water Valve Operating Hours Threshold Operating hours threshold for the chilled water valve. When the number of operating hours reaches this threshold, an event is generated. Chilled Water Valve Reset Enable Enable/disable the ability to reset the chilled water valve. Circuit Cooling Load The amount of heat energy currently being removed by a single refrigeration circuit. Clogged Air Filter - Event Control Enable/disable the activation of the [Clogged Air Filter] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Clogged Air Filter - Event Type The event type for the [Clogged Air Filter] event. Clogged Air Filter Air filter is dirty and needs to be (cleaned or) replaced. Cold Aisle Air Sensor Failure Cold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range. Cold Aisle Cascade Fan Speed Max Set Point Cold aisle maximum fan speed when system is in cascade mode and one or more units in the system are in standby. Cold Aisle Control Enable Enable/disable cold aisle control. Cold Aisle Fan Speed Max Set Point Cold aisle maximum fan speed when system is not in cascade mode OR when system is in cascade mode and no units in the system are in standby. Cold Aisle Fan Speed Min Set Point Cold aisle minimum fan speed. Cold Aisle Force Max Fan/Cooling The cold aisle fan speed and system cooling can be forced to 100% via an external input - Ext Control signal. Use this value to enable/disable that feature. Cold Aisle Humidity Calculation Method Algorithm used to calculate a single cold aisle humidity value from multiple humidity measurements. Cold Aisle Sensor Air Temperature Air temperature measured by cold aisle sensor. Cold Aisle Sensor Humidity Humidity measured by cold aisle sensor. Cold Aisle Temperature Calculation Method Algorithm used to calculate a single cold aisle temperature value from multiple temperature measurements. Cold Aisle Temperature/Humidity Team Sensor Failure Cold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range. Compressor 1B Hours Exceeded Fixed compressor 1B run hours have exceeded the threshold. Compressor 1B Thermal Overload Fixed compressor 1B is shut down due to thermal overload. Compressor 2B Hours Exceeded Fixed compressor 2B run hours have exceeded the threshold. Compressor 2B Thermal Overload Fixed compressor 2B is shut down due to thermal overload. 55 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Compressor Capacity Control State Compressor capacity control state. When 'ON', the cooling capacity of the compressor has been reduced. Compressor Capacity Reduced Compressor capacity has been reduced. Enable/disable the activation of the [Compressor High Head Pressure] event. If set to Compressor High Head Pressure 'disabled', the event will not be annunciated. This implies that the event will not be placed Event Control in any active event list or in any event history list. Compressor High Head Pressure The event type for the [Compressor High Head Pressure] event. Event Type Compressor High Head Pressure Compressor is shut down due to high head pressure. Compressor High Pressure Transducer Issue Compressor high pressure transducer is disconnected or the signal is out of range. Compressor Hours Exceeded [Compressor Hours] has exceeded [Compressor Hours Threshold]. Compressor Hours Threshold Threshold value used in the [Compressor Hours Exceeded] event. Compressor Hours Operating hours for compressor since last reset of this value. Compressor Lockout Enable/disable the use of the compressor. Compressor Low Differential Pressure Lockout Compressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled. Compressor Low Pressure Transducer Issue Compressor low pressure transducer is disconnected or the signal is out of range. Compressor Low Suction Pressure - Event Control Enable/disable the activation of the [Compressor Low Suction Pressure] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor Low Suction Pressure - Event Type The event type for the [Compressor Low Suction Pressure] event. Compressor Low Suction Pressure Compressor is shut down due to low suction pressure. Compressor Pump Down Issue Event Control Enable/disable the activation of the [Compressor Pump Down Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor Pump Down Issue Event Type The event type for the [Compressor Pump Down Issue] event. Compressor Pump Down Issue Unable to pump down suction-side pressure during compressor shutdown. Compressor Short Cycle - Event Control Enable/disable the activation of the [Compressor Short Cycle] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor Short Cycle - Event Type The event type for the [Compressor Short Cycle] event. Compressor Short Cycle Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period. Compressor State Compressor operational state. Compressor Superheat Over Threshold Compressor discharge refrigerant superheat temperature has exceeded an upper threshold. Compressor Thermal Overload Event Control Enable/disable the activation of the [Compressor Thermal Overload] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor Thermal Overload Event Type The event type for the [Compressor Thermal Overload] event. Compressor Thermal Overload Compressor is shut down due to thermal overload. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 56 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Compressor Utilization Present compressor utilization expressed as a percentage of the maximum rated capacity. Condenser Circuit Unspecified General Event One or more unspecified condenser circuit events active. See local unit display for further details. Condenser Communication Lost Communication with condenser unit has been lost. Condenser Control Board Issue The condenser control board is reporting an issue. Condenser Fan Current Condenser fan's measured input current. Condenser Fan Issue Condenser fan is not operating within its operational parameters. Condenser Fan Power Condenser fan's measured input power. Condenser Fan Reversal Requested Request the condenser fans to rotate in the reverse direction. Condenser Fan Speed Condenser fan speed expressed as a percentage of the maximum rated speed. Condenser Issue - Event Control Enable/disable the activation of the [Condenser Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Condenser Issue - Event Type The event type for the [Condenser Issue] event. Condenser Issue Condenser is not operating within its operational parameters. Condenser Low Noise Mode - Full Days of the week selected for low noise mode full day scheduling. Days Condenser Low Noise Mode Interval Days Days of the week selected for low noise mode interval scheduling. Condenser Low Noise Mode Max Fan Speed Maximum fan speed when condenser is placed in low noise mode. Condenser Low Noise Mode Schedule Control Enable/disable scheduled control of condenser low noise mode. Condenser Low Noise Mode Start The time of day at which the condenser will transition into low noise mode. Time Condenser Low Noise Mode State State of condenser low noise mode scheduler control. Condenser Low Noise Mode Stop The time of day at which the condenser will transition out of low noise mode. Time Condenser Max Fan Speed Override Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition. Condenser Normal Mode Max Fan Maximum fan speed when condenser is not in low noise mode. Speed Condenser Outside Air Temp Out of Operating Range [Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold. Condenser Outside Air Temp Sensor Issue Condenser outside air temperature sensor is disconnected or the signal is out of range. Condenser Outside Air Temperature Condenser ambient outside air temperature. Condenser Refrigerant Pressure Over Threshold Condenser refrigerant pressure has exceeded a threshold. Condenser Refrigerant Pressure Sensor Issue Condenser refrigerant pressure sensor is disconnected or the signal is out of range. Condenser Refrigerant Pressure Under Threshold Condenser refrigerant pressure has dropped below a threshold. Condenser Refrigerant Pressure Pressure of the refrigerant in a condenser circuit. Condenser Refrigerant Type Condenser refrigerant type. Condenser Remote Shutdown Condenser is shut down by a remote signal. 57 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Condenser Supply Refrigerant Over Temp Condenser supply refrigerant temperature has exceeded a threshold. Condenser Supply Refrigerant Temp Sensor Issue Condenser supply refrigerant temperature sensor is disconnected or the signal is out of range. Condenser Supply Refrigerant Temperature Temperature of the supply refrigerant in a condenser circuit. Condenser Supply Refrigerant Under Temp Condenser supply refrigerant temperature has dropped below a specified threshold. Condenser TVSS Issue The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed. Condenser Unit Unspecified General Event One or more unspecified condenser unit events active. See local unit display for further details. Condenser VFD Issue The condenser fan Variable Frequency Drive is offline. Cooling Capacity Cooling capacity in use, expressed as a percentage of the maximum rated capacity. Cooling Control Temperature Temperature value being used for cooling capacity control. This value is compared against the temperature set point to determine the amount of cooling to be applied. Cooling State Cooling operational state. Customer Input 1 - Event Control Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 1 - Event Type The event type for the [Customer Input 1] event. Customer Input 1 Customer Input 1 Customer Input 2 - Event Control Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 2 - Event Type The event type for the [Customer Input 2] event. Customer Input 2 Customer Input 2 Customer Input 3 - Event Control Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 3 - Event Type The event type for the [Customer Input 3] event. Customer Input 3 Customer Input 3 Customer Input 4 - Event Control Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 4 - Event Type The event type for the [Customer Input 4] event. Customer Input 4 Customer Input 4 Dehumidification Fan Speed Min Set Point Minimum fan speed when system dehumidification is active. Dehumidifier Hours Exceeded Operating hours for the dehumidifier have exceeded the threshold. Dehumidifier Hours Threshold Threshold value used in the [Dehumidifier Hours Exceeded] event. Dehumidifier Hours Operating hours for dehumidifier since last reset of this value. Dehumidifier State Dehumidifier operational state. Dehumidifier Utilization Present dehumidifier utilization expressed as a percentage of the maximum rated capacity. Dew Point Dead Band Value that is divided evenly to form a range above and below [Dew Point Set Point]. If measured humidity is within this range, no humidification or dehumidification will occur. This parameter is used when [Humidity Control Type] is set to Dew Point. Dew Point Over Temperature Dew point temperature reading has exceeded the upper threshold. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 58 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Dew Point Proportional Band Value that is divided evenly to form proportional humidity control bands above and below [Dew Point Set Point]. This parameter is used when [Humidity Control Type] is set to Dew Point. Dew Point Set Point Desired dew point temperature. Dew Point Under Temperature Dew point temperature reading has dropped below the lower threshold. Dig Scroll Comp Discharge Over Temp - Event Ctrl Enable/disable the activation of the [Dig Scroll Comp Discharge Over Temp] event. Dig Scroll Comp Discharge Over Temp - Event Type The event type for the [Dig Scroll Comp Discharge Over Temp] event. Dig Scroll Comp Discharge Temp Sensor Issue Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range. Dig Scroll Comp Discharge Temp Digital scroll compressor discharge temperature. Dig Scroll Comp Over Temp Digital scroll compressor is shut down due to head temperature exceeding an upper threshold. Digital Output Board Not Detected Digital output board is required to be connected, but no signal is detected. Digital Scroll Compressor Loading Present digital scroll compressor utilization expressed as a percentage of the maximum rated capacity. EEV Unspecified General Event One or more unspecified electronic expansion valve events active. See local unit display for further details. Electric Reheat State Electric reheater operational state. Electric Reheater Hours Exceeded [Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold]. Electric Reheater Hours Threshold Threshold value used in the [Electric Reheater Hours Exceeded] event. Electric Reheater Hours Operating hours for electric reheater since last reset of this value. Energy Consumption Energy consumption since the last reset of this value. Expected Condenser Unit Count Number of physical condenser units that are expected to be connected to the system. Ext Air Damper Position Issue Air damper position does not match expected value, as indicated by an external input signal. Ext Air Sensor A Dew Point Temp Dew point temperature as measured by external air sensor A. Ext Air Sensor A Event Control Enable/disable the activation of events related to measurements by the external air sensor A. Ext Air Sensor A High Humidity Event Control Enable/disable the activation of the [Ext Air Sensor A High Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Air Sensor A High Humidity Event Type The event type for the [Ext Air Sensor A High Humidity] event. Ext Air Sensor A High Humidity Threshold Threshold value used in the [External Air Sensor A High Humidity] event. Ext Air Sensor A High Humidity [Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold]. Ext Air Sensor A Humidity Relative humidity as measured by external air sensor A. Ext Air Sensor A Issue The external air sensor A is disconnected or the signal is out of range. Ext Air Sensor A Low Humidity Event Control Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Air Sensor A Low Humidity Event Type The event type for the [Ext Air Sensor A Low Humidity] event. Ext Air Sensor A Low Humidity Threshold Threshold value used in the [External Air Sensor A Low Humidity] event. 59 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Ext Air Sensor A Low Humidity [Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold]. Ext Air Sensor A Over Temp Event Control Enable/disable the activation of the [External Air Sensor A Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Air Sensor A Over Temp Event Type The event type for the [External Air Sensor A Over Temperature] event. Ext Air Sensor A Over Temp Threshold Threshold value used in the [External Air Sensor A Over Temperature] event. Ext Air Sensor A Over Temperature [Ext Air Sensor A Temperature] has exceeded [External Air Sensor A Over Temp Threshold]. Ext Air Sensor A Temperature Air temperature as measured by external air sensor A. Ext Air Sensor A Under Temp Event Control Enable/disable the activation of the [Ext Air Sensor A Under Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Air Sensor A Under Temp Event Type The event type for the [Ext Air Sensor A Under Temperature] event. Ext Air Sensor A Under Temp Threshold Threshold value used in the [External Air Sensor A Under Temperature] event. Ext Air Sensor A Under Temperature [Ext Air Sensor A Temperature] has dropped below [Ext Air Sensor A Under Temp Threshold]. Ext Air Sensor B Humidity Relative humidity as measured by external air sensor B. Ext Air Sensor B Temperature Air temperature as measured by external air sensor B. Ext Air Sensor C Humidity Relative humidity as measured by external air sensor C. Ext Air Sensor C Temperature Air temperature as measured by external air sensor C. Ext Compressor Lockout - Event Control Enable/disable the activation of the [Ext Compressor Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Compressor Lockout - Event Type The event type for the [Ext Compressor Lockout] event. Ext Compressor Lockout The compressor is shut down and disabled by an external input signal. Ext Condenser Pump High Water - Event Control Enable/disable the activation of the [Ext Condenser Pump High Water] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Condenser Pump High Water - Event Type The event type for the [Ext Condenser Pump High Water] event. Ext Condenser Pump High Water High water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal. Ext Dew Point Over Temp Threshold Threshold value used in the [Ext Dew Point Over Temperature] event. Ext Dew Point Over Temperature At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold]. Ext Dew Point Under Temp Threshold Threshold value used in the [Ext Dew Point Under Temperature] event. At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Ext Dew Point Under Temperature Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold]. Ext Free Cooling Lockout - Event Control Enable/disable the activation of the [Ext Free Cooling Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 60 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Ext Free Cooling Lockout - Event Type The event type for the [Ext Free Cooling Lockout] event. Ext Free Cooling Lockout Free cooling is disabled by an external input signal. Ext Humidifier Lockout - Event Control Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Humidifier Lockout - Event Type The event type for the [Ext Humidifier Lockout] event. Ext Humidifier Lockout The humidifier is shut down and disabled by an external input signal. Ext Loss of Air Blower - Event Control Enable/disable the activation of the [Ext Loss of Air Blower] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Loss of Air Blower - Event Type The event type for the [Ext Loss of Air Blower] event. Ext Loss of Air Blower Loss of air blower is detected, as indicated by an external input signal. Ext Loss of Flow - Event Control Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Loss of Flow - Event Type The event type for the [Ext Loss of Flow] event. Ext Loss of Flow Loss of flow is detected, as indicated by an external input signal. Ext Over Temperature - Event Control Enable/disable the activation of the [Ext Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Over Temperature - Event Type The event type for the [Ext Over Temperature] event. Ext Over Temperature A temperature has exceeded its threshold, as indicated by an external input signal. Ext Power Source A Failure Unit main power source A failure, as indicated by an external input signal. Ext Power Source B Failure Unit main power source B failure, as indicated by an external input signal. Ext Reheat Lockout - Event Control Enable/disable the activation of the [Ext Reheat Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Reheat Lockout - Event Type The event type for the [Ext Reheat Lockout] event. Ext Reheat Lockout The reheater is shut down and disabled by an external input signal. Ext Standby Glycol Pump On Event Control Enable/disable the activation of the [Ext Standby Glycol Pump On] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Standby Glycol Pump On Event Type The event type for the [Ext Standby Glycol Pump On] event. Ext Standby Glycol Pump On The standby glycol pump is on, as indicated by an external input signal. Ext Standby Unit On - Event Control Enable/disable the activation of the [Ext Standby Unit On] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Standby Unit On - Event Type The event type for the [Ext Standby Unit On] event. Ext Standby Unit On Standby unit is on, as indicated by an external input signal. External Condenser TVSS Issue The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal. External Condenser VFD Issue The condenser fan Variable Frequency Drive is offline, as indicated by an external input signal. External Fire Detected Fire detected, as indicated by an external input signal. 61 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Fan Control Mode Fan control mode. Fan Control Sensor Sensor to be used for fan speed control. Fan Hours Exceeded - Event Control Enable/disable the activation of the [Fan Hours Exceeded] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Fan Hours Exceeded - Event Type The event type for the [Fan Hours Exceeded] event. Fan Hours Exceeded Operating hours for the unit blower fan have exceeded the threshold. Fan Hours Threshold Threshold value used in the [Fan Hours Exceeded] event. Fan Hours Operating hours for fan since last reset of this value. Fan Issue - Event Control Enable/disable the activation of the [Fan Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Fan Issue - Event Type The event type for the [Fan Issue] event. Fan Issue One or more fans are not operating within their operational parameters. Fan Speed Control Temperature Temperature value being used for fan speed control. This value is compared against the fan speed temperature set point to determine the fan speed. Fan Speed Maximum Set Point Maximum fan speed. This value may only be modified if iCOM is enabled to allow fan speed changes by the BMS. Fan Speed Minimum Set Point Minimum fan speed. If fan is in decoupled mode and not under manual control, the fan speed will vary Fan Speed Temperature Set Point depending on the delta between the selected fan control sensor temperature and this set point. Fan Speed Fan speed expressed as a percentage of the maximum rated speed. Fan State Fan operational state. Fluid Flow Rate Flow rate of fluid used for cooling. Fluid Flow Sensor Issue The fluid flow sensor is disconnected or the signal is out of range. Fluid Input Temperature Temperature of the fluid entering the cooling coil. Fluid Output Temperature Temperature of the fluid exiting the cooling coil. Fluid Temperature Sensor Issue The fluid temperature sensor is disconnected or the signal is out of range. Free Cooling Fluid Temperature Free cooling fluid temperature. Free Cooling Internal Control Mode Free cooling internal control mode Free Cooling Internal Temperature Delta Minimum temperature delta required between supply fluid and internal ambient air temperatures in order to enable free cooling. Free Cooling State Free cooling operational state. Free Cooling Status Free cooling status. Free Cooling Stopped - High Room Temp Free cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point. Free Cooling Temp Sensor Issue The free cooling fluid temperature sensor is disconnected or the signal is out of range. Free Cooling Valve Hours Exceeded [Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]. Free Cooling Valve Hours Threshold Threshold value used in the [Free Cooling Valve Hours Exceeded] event. Free Cooling Valve Hours Operating hours for free cooling valve since last reset of this value. Free Cooling Valve Open Position Free cooling valve open position. Heating Fan Speed Min Set Point Minimum fan speed when system heating is active. Heating Lockout Heating is shut down and disabled. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 62 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description High Power Shutdown - Event Control Enable/disable the activation of the [High Power Shutdown] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. High Power Shutdown - Event Type The event type for the [High Power Shutdown] event. High Power Shutdown Supply to high power components has been shutdown. High Return Air Temperature Threshold Threshold value used in the [Return Air Over Temperature] event. High Return Humidity - Event Control Enable/disable the activation of the [High Return Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. High Return Humidity - Event Type The event type for the [High Return Humidity] event. High Return Humidity Threshold Threshold value used in the [High Return Humidity] event. High Return Humidity Return air high humidity event. High Static Pressure High static pressure event. High Supply Air Temperature Threshold Threshold value used in the [Supply Air Over Temperature] event. Hot Water / Hot Gas State Hot water / hot gas operational state. Hot Water / Hot Gas Valve Hours Exceeded [Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold]. Hot Water / Hot Gas Valve Hours Threshold Threshold value used in the [Hot Water / Hot Gas Valve Hours Exceeded] event. Hot Water / Hot Gas Valve Hours Operating hours for hot water / hot gas valve since last reset of this value. Hot Water / Hot Gas Valve Open Position Hot water / hot gas valve open position. Humidification Fan Speed Min Set Minimum fan speed when system humidification is active. Point Humidifier Control Board Not Detected Humidifier control board is required to be connected, but no signal is detected. Humidifier Cylinder Worn Humidifier cylinder is not operating properly and needs to be replaced. Humidifier Hours Exceeded Operating hours for the humidifier have exceeded the threshold. Humidifier Hours Threshold Threshold value used in the [Humidifier Hours Exceeded] event. Humidifier Hours Operating hours for humidifier since last reset of this value. Humidifier Issue - Event Control Enable/disable the activation of the [Humidifier Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Humidifier Issue - Event Type The event type for the [Humidifier Issue] event. Humidifier Issue Humidifier issue detected, causing it to be locked out. Humidifier Lockout Enable/disable the use of the humidifier. Humidifier Low Water The water level in the humidifier has dropped below its threshold. Humidifier Over Current The electrical current to the humidifier has exceeded its upper threshold. Humidifier State Humidifier operational state. Humidifier Under Current The electrical current to the humidifier has dropped below its lower threshold. Humidifier Utilization Present humidifier utilization expressed as a percentage of the maximum rated capacity. Humidity Control Integration Time Time value used to add an integral term to humidity control. If set to 0, time will not be a factor in the control algorithm. 63 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Humidity Control Sensor Sensor from which humidity measurements will be used for humidification and dehumidification control. Humidity Control Type Type of algorithm to use for control of output humidity. Humidity Control Type Type of algorithm to use for control of output humidity. Humidity Dead Band Value that is divided evenly to form a range above and below [Humidity Set Point]. If measured humidity is within this range, no humidification or dehumidification will occur. Humidity Proportional Band Value that is divided evenly to form proportional humidity control bands above and below [Humidity Set Point]. This setting applies to Relative, Predictive and Compensated [Humidity Control Type] selections. Humidity Set Point Desired relative humidity. Infrared Humidifier Flush Rate A multiple of an internal time constant that determines the flush duration of the infrared humidifier water pan. Input Undervoltage One or more of the input phase voltages has dropped below the limit. Instantaneous Power Total electrical power currently being consumed. Local Cooling Override The local unit override status for cooling capacity. Local Dehumidifier Override The local unit override status for the dehumidifier. Local Electric Heat Override The local unit override status for electric heat. Local Fan Override The local unit override status for fan speed. Local Humidifier Override The local unit override status for the humidifier. Loss of Air Flow No air flow through the unit due to failure of all fans. Low Return Air Temperature Threshold Threshold value used in the [Return Air Under Temperature] event. Low Return Humidity - Event Control Enable/disable the activation of the [Low Return Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Low Return Humidity - Event Type The event type for the [Low Return Humidity] event. Low Return Humidity Threshold Threshold value used in the [Low Return Humidity] event. Low Return Humidity Return air low humidity event. Low Static Pressure Low static pressure event. Low Supply Air Temperature Threshold Threshold value used in the [Supply Air Under Temperature] event. Main Chilled Water Valve The primary valve in a dual valve chilled water system. Main Fan Overload - Event Control Enable/disable the activation of the [Main Fan Overload] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Main Fan Overload - Event Type The event type for the [Main Fan Overload] event. Main Fan Overload Main fan is shut down due to thermal overload. Maintenance Completed Maintenance has been completed on the unit. Maintenance Due The calculated maintenance date has been reached. Maintenance Ramp The ratio of operations performed to the calculated operations available between maintenance intervals. Maintenance Tracking State Maintenance tracking operational state. Enable/disable the activation of the [Master Unit Communication Lost] event. If set to Master Unit Communication Lost 'disabled', the event will not be annunciated. This implies that the event will not be placed Event Control in any active event list or in any event history list. Master Unit Communication Lost The event type for the [Master Unit Communication Lost] event. Event Type Master Unit Communication Lost Communication with master unit has been lost. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 64 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Minimum Chilled Water Temp Set Enable/disable the activation of [Minimum Chilled Water Temp Set Point]. Point Enable Minimum Chilled Water Temp Set Minimum desired chilled water temperature. Point Mixed Mode Lockout Mixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit. Modbus Power Meter Communication Lost Communication with Modbus power meter has been lost. Outside Air Temperature Ambient outside air temperature. PRE Operational Mode Pumped Refrigerant Economizer operational mode. Pump Hours Threshold Threshold value used in the [Pump Hours Exceeded] event. Pump Hours Operating hours for pump since last reset of this value. Pump Inlet Refrigerant Temperature Refrigerant temperature at the inlet of the pump. Pump Outlet Refrigerant Temperature Refrigerant temperature at the outlet of the pump. Pump Speed Pump speed expressed as a percentage of the maximum rated speed. Pump State Pump operational state. Pump Unspecified General Event One or more unspecified pump events active. See local unit display for further details. RAM Battery Issue RAM or RAM backup battery is not operating correctly. Raw Auxiliary Air Temperature Air temperature value sent by an external auxiliary device, with no additional filtering by the receiving system. This may be an aggregated value from multiple sensors. Reheat Utilization Present reheating utilization expressed as a percentage of the maximum rated capacity. Reheater Lockout Enable/disable the use of the reheater. Reheater Over Temperature The temperature of the reheater has exceeded its threshold. Remote Sensor Average Over Temperature [Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor Average Temperature Average value of remote sensor temperature measurements. Remote Sensor Average Under Temperature [Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Remote Sensor Issue Remote sensor is disconnected or the signal is out of range. Remote Sensor Maximum Temperature Maximum value of remote sensor temperature measurements. Remote Sensor Over Temp Threshold Threshold value used in the remote air sensor over temperature events. Remote Sensor Over Temperature [Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor System Average Over Temperature [Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor System Average Temperature Average value of remote sensor temperature measurements among a group of interconnected units in a single system. Remote Sensor System Average Under Temperature [Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Remote Sensor System Maximum Maximum value of remote sensor temperature measurements among a group of Temperature interconnected units in a single system. Remote Sensor Temperature Air temperature as measured by remote sensor. 65 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Remote Sensor Under Temp Threshold Threshold value used in the remote air sensor under temperature events. Remote Sensor Under Temperature [Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Return Air Over Temp - Event Control Enable/disable the activation of the [Return Air Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Return Air Over Temp - Event Type The event type for the [Return Air Over Temperature] event. Return Air Over Temperature Return air high temperature event. Return Air Sensor Event Control Enable/disable the activation of events related to measurements by the return air sensor. Return Air Sensor Issue The air sensor at the inlet of the unit is disconnected or the signal is out of range. Return Air Temperature Set Point Desired air temperature at the inlet of the unit. Return Air Temperature The temperature of the inlet air Return Air Under Temp - Event Control Enable/disable the activation of the [Return Air Under Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Return Air Under Temp - Event Type The event type for the [Return Air Under Temperature] event. Return Air Under Temperature [Return Air Temperature] has dropped below [Low Return Air Temperature Threshold]. Return Damper Status Status of the return damper. Return Dew Point Dew point temperature measured at the inlet of the unit. Return Humidity Sensor Issue The humidity sensor at the inlet of the unit is disconnected or the signal is out of range. Return Humidity Set Point Desired relative humidity at the inlet of the unit. Return Humidity Relative humidity measured at the inlet of the unit. Server Class The general classification for this system Service Required - Event Control Enable/disable the activation of the [Service Required] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Service Required - Event Type The event type for the [Service Required] event. Service Required Unit requires servicing. Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to 'disabled', Shutdown - Loss Of Power - Event the event will not be annunciated. This implies that the event will not be placed in any Control active event list or in any event history list. Shutdown - Loss Of Power - Event The event type for the [Shutdown - Loss Of Power] event. Type Shutdown - Loss Of Power System lost power. This event becomes active when the unit is powered on following an unexpected loss of power. This event remains active for 90 minutes. Smoke Detected - Event Control Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Smoke Detected - Event Type The event type for the [Smoke Detected] event. Smoke Detected Smoke detected. Standby Units The number of standby units. Static Pressure Sensor Issue The static pressure sensor is disconnected or the signal is out of range. Static Pressure Sensor Out of Range Static pressure sensor signal is out of its configured range. Static Pressure Set Point Desired static pressure. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 66 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Super Saver Call For Cooling Call for cooling value used for Super Saver functionality. A higher call for cooling value indicates a need for a lower coolant temperature. Supply Air Over Temperature Supply air high temperature event. Supply Air Over/Under Temperature - Event Control Enable/disable the activation of the [Supply Air Over Temperature] and [Supply Air Under Temperature] events. Supply Air Sensor Issue The air sensor at the outlet of the unit is disconnected or the signal is out of range. Supply Air Temperature Sensor Control Control mode to be used with the supply air temperature sensor. Supply Air Temperature Set Point Desired supply air temperature. Supply Air Temperature Air temperature measured at the outlet of the unit. Supply Air Under Temperature Supply air low temperature event. Supply Chilled Water Loss of Flow Supply chilled water or glycol flow is too low. Supply Chilled Water Over Temp Chilled water temperature is too high, as indicated by an external input signal. System Date and Time The system date and time System Event Acknowledge/Reset Reset and/or acknowledge all events. System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase The system input RMS current for Phase A A System Input RMS Current Phase The system input RMS current for Phase B B System Input RMS Current Phase The system input RMS current for Phase C C System On/Off Control Turn system functionality on or off. System Static Pressure Static pressure measurement among a group of interconnected units in a single system. System Status The operating status for the system Tandem 'B' Compressor Hours Operating hours for the 'B' compressor in a tandem configuration since last reset of this value. Tandem 'B' Compressor State Operational state for the 'B' compressor in a tandem configuration. Team Static Pressure Sensor Failure The team static pressure sensor is disconnected or the signal is out of range. Temperature Control Sensor Issue The air sensor selected for cooling control is disconnected or the signal is out of range. Thermal Control Override Temperature Call If [Thermal Control Override] is enabled, this value sets the percent call for cooling or heating. Thermal Control Override Humidity Call If [Thermal Control Override] is enabled, this value sets the percent call for humidification or dehumidification. Thermal Control Override Humidity Control Type If [Thermal Control Override] is enabled, this value selects if the humidity override is applied to humidification or dehumidification. Thermal Control Override Temperature Control Type If [Thermal Control Override] is enabled, this value selects if the temperature override is applied to cooling or heating. Thermal Control Override Override internal programmatic control of thermal conditions. This includes, but may not be limited to, temperature and humidity. The ability to enable this override may require additional system configuration. 67 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Today's High Air Temperature Time [Today's High Air Temperature] was measured at this time. Today's High Air Temperature The highest external air temperature measured since midnight. Today's High Humidity Time [Today's High Humidity] was measured at this time Today's High Humidity The highest external humidity measured since midnight. Today's Low Air Temperature Time [Today's Low Air Temperature] was measured at this time. Today's Low Air Temperature The lowest external air temperature measured since midnight. Today's Low Humidity Time [Today's Low Humidity] was measured at this time Today's Low Humidity The lowest external humidity measured since midnight. Underfloor Static Pressure Control Enable/disable the underfloor static pressure control. Enable Unit Calculated Airflow Total airflow calculated for the unit. Unit Code Missing Unit code has not been entered and saved. Unit Communication Lost Master has lost communication with one or more networked units. Unit Control Mode Unit control mode. Unit Cooling Load The total amount of heat energy currently being removed by the unit. Unit Off Unit was turned off. Unit On Unit was turned on. Unit Operating State Reason The reason the unit is in the current operating state. Unit Operating State Current operating state of the unit. Unit Partial Shutdown An event has occurred requiring some system components to be shutdown and disabled. Unit Shutdown An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit Standby Unit was placed in standby mode. Unit Static Pressure Static pressure measurement for a single unit. Unspecified General Event One or more unspecified events active. See local unit display for further details. Water Leakage Detector Sensor Issue The water leakage detector sensor is disconnected or the signal is out of range. Enable/disable the activation of the [Water Under Floor] event. If set to 'disabled', the Water Under Floor - Event Control event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Water Under Floor - Event Type The event type for the [Water Under Floor] event. Water Under Floor Water under the floor is detected. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 68 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-6 Liebert CRV™—Status and Coil Data Label Status Coil Number of Bits Notes 10001 — 1 Active on Alarm Air Temperature Supply Air Over Temperature Supply Air Under Temperature 10002 — 1 Active on Alarm Return Air Over Temperature 10003 — 1 Active on Alarm Supply Air Sensor Issue 10004 — 1 Active on Alarm Return Air Sensor Issue 10077 — 1 Active on Alarm High Return Humidity 10005 — 1 Active on Alarm Low Return Humidity 10006 — 1 Active on Alarm Humidifier Hours Exceeded 10007 — 1 Active on Alarm Dehumidifier Hours Exceeded 10008 — 1 Active on Alarm Humidifier Under Current 10009 — 1 Active on Alarm Humidifier Over Current 10010 — 1 Active on Alarm Humidifier Low Water 10011 — 1 Active on Alarm Humidifier Cylinder Worn 10012 — 1 Active on Alarm Humidifier Issue 10013 — 1 Active on Alarm Humidity Ext Humidifier Lockout 10014 — 1 Active on Alarm Humidifier Control Board Not Detected 10015 — 1 Active on Alarm Return Humidity Out Of Proportional Band 10016 — 1 Active on Alarm Loss of Air Flow 10017 — 1 Active on Alarm Fan Hours Exceeded 10018 — 1 Active on Alarm Fans Top Fan Issue 10019 — 1 Active on Alarm Bottom Fan Issue 10020 — 1 Active on Alarm Remote Sensor Issue 10021 — 1 Active on Alarm Remote Sensor Issue 10022 — 1 Active on Alarm Remote Sensor Issue 10023 — 1 Active on Alarm Remote Sensor Issue 10024 — 1 Active on Alarm Remote Sensor Issue 10025 — 1 Active on Alarm Remote Sensor Issue 10026 — 1 Active on Alarm Remote Sensor Issue 10027 — 1 Active on Alarm Remote Sensor Issue 10028 — 1 Active on Alarm Remote Sensor Issue 10029 — 1 Active on Alarm Remote Sensor Issue 10030 — 1 Active on Alarm Remote Sensor Average Under Temperature 10120 — 1 Active on Alarm Remote Sensor Average Over Temperature 10121 — 1 Active on Alarm Remote Sensor System Average Under Temperature 10122 — 1 Active on Alarm Remote Sensor System Average Over Temperature 10123 — 1 Active on Alarm Remote Sensor Average Low Humidity 10124 — 1 Active on Alarm Remote Sensor Average High Humidity 10125 — 1 Active on Alarm Remote Sensor System Average Low Humidity 10126 — 1 Active on Alarm Remote Sensor System Average High Humidity 10127 — 1 Active on Alarm Compressor 1 High Head Pressure 10031 — 1 Active on Alarm Compressor 1 Low Suction Pressure 10032 — 1 Active on Alarm Remote Sensors Compressor 69 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-6 Liebert CRV™—Status and Coil (continued) Data Label Status Coil Number of Bits Notes Compressor 1 Hours Exceeded 10033 — 1 Active on Alarm Dig Scroll Comp 1 Temp Sensor Issue 10034 — 1 Active on Alarm Dig Scroll Comp 1 Over Temp 10035 — 1 Active on Alarm Compressor 1 Low Pressure Transducer Issue 10036 — 1 Active on Alarm Ext Compressor Lockout 10037 — 1 Active on Alarm Compressor 1 Short Cycle 10038 — 1 Active on Alarm Compressor 1 High Pressure Transducer Issue 10039 — 1 Active on Alarm Compressor 1 Pump Down Issue 10040 — 1 Active on Alarm Compressor Capacity Reduced 10180 — 1 Active on Alarm Compressor Superheat Over Threshold 10181 — 1 Active on Alarm Reheater Over Temperature 10041 — 1 Active on Alarm Electric Reheater Hours Exceeded 10042 — 1 Active on Alarm Ext Reheat Lockout 10043 — 1 Active on Alarm Electric Reheater Hours Exceeded 10190 — 1 Active on Alarm Reheater Condenser Condenser 1 Issue 10044 — 1 Active on Alarm Condenser VFD Issue 10045 — 1 Active on Alarm Condenser TVSS Issue 10046 — 1 Active on Alarm External Condenser VFD Issue 10200 — 1 Active on Alarm External Condenser TVSS Issue 10201 — 1 Active on Alarm Supply Chilled Water Over Temp 10047 — 1 Active on Alarm Chilled Water Control Valve Failure 10048 — 1 Active on Alarm Supply Chilled Water Loss of Flow 10049 — 1 Active on Alarm Chilled Water System Events Supply Fluid Temp Sensor Issue 10050 — 1 Active on Alarm Customer Input 1 10051 — 1 Active on Alarm Customer Input 2 10052 — 1 Active on Alarm Customer Input 3 10053 — 1 Active on Alarm Customer Input 4 10054 — 1 Active on Alarm Smoke Detected 10055 — 1 Active on Alarm Water Under Floor 10056 — 1 Active on Alarm Service Required 10057 — 1 Active on Alarm Shutdown - Loss Of Power 10058 — 1 Active on Alarm Ext Over Temperature 10059 — 1 Active on Alarm Ext Loss of Flow 10060 — 1 Active on Alarm Ext Condenser Pump High Water 10061 — 1 Active on Alarm Ext Standby Glycol Pump On 10062 — 1 Active on Alarm External Fire Detected 10063 — 1 Active on Alarm Unit On 10064 — 1 Active on Alarm Unit Off 10065 — 1 Active on Alarm Unit Standby 10066 — 1 Active on Alarm Unit Partial Shutdown 10067 — 1 Active on Alarm Unit Shutdown 10068 — 1 Active on Alarm Water Leakage Detector Sensor Issue 10069 — 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 70 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-6 Liebert CRV™—Status and Coil (continued) Status Coil Number of Bits Notes BMS Communications Timeout 10070 — 1 Active on Alarm Maintenance Due 10071 — 1 Active on Alarm Maintenance Completed 10072 — 1 Active on Alarm Clogged Air Filter 10073 — 1 Active on Alarm RAM Battery Issue 10074 — 1 Active on Alarm Master Unit Communication Lost 10075 — 1 Active on Alarm Data Label High Power Shutdown 10076 — 1 Active on Alarm Unspecified General Event 10100 — 1 Active on Alarm SEC Unspecified General Event 10210 — 1 Active on Alarm SEC Communication Lost 10211 — 1 Active on Alarm Static Pressure Sensor Issue 10212 — 1 Active on Alarm Static Pressure Sensor Out of Range 10213 — 1 Active on Alarm Power Source 'A' Issue 10214 — 1 Active on Alarm Power Source B Failure 10215 — 1 Active on Alarm Fluid Flow Sensor Issue 10216 — 1 Active on Alarm Fluid Temperature Sensor Issue 10217 — 1 Active on Alarm Unit Code Missing 10218 — 1 Active on Alarm Global Condenser Condenser Outside Air Temp Sensor Issue 10078 — 1 Active on Alarm Condenser Outside Air Temp Out of Operating Range 10079 — 1 Active on Alarm Condenser Control Board Issue 10080 — 1 Active on Alarm Condenser Refrigerant Pressure Over Threshold 10081 — 1 Active on Alarm Condenser Refrigerant Pressure Under Threshold 10082 — 1 Active on Alarm Condenser Refrigerant Pressure Sensor Issue 10083 — 1 Active on Alarm Condenser Supply Refrigerant Over Temp 10084 — 1 Active on Alarm Condenser Supply Refrigerant Under Temp 10085 — 1 Active on Alarm Condenser Supply Refrigerant Temp Sensor Issue 10086 — 1 Active on Alarm Condenser Max Fan Speed Override 10087 — 1 Active on Alarm Condenser Unit Unspecified General Event 10101 — 1 Active on Alarm Condenser Circuit Unspecified General Event 10102 — 1 Active on Alarm Condenser Fan Issue 10088 — 1 Active on Alarm Condenser Fan Issue 10089 — 1 Active on Alarm Condenser Fan Issue 10090 — 1 Active on Alarm Condenser Fan Issue 10091 — 1 Active on Alarm 10111 — 1 Active on Alarm Condenser Fan Auxiliary Air Aux Air Temp Device Communication Lost Remote Sensor 1 Remote Sensor Low Humidity 10130 — 1 Active on Alarm Remote Sensor High Humidity 10140 — 1 Active on Alarm Remote Sensor Under Temperature 10150 — 1 Active on Alarm Remote Sensor Over Temperature 10160 — 1 Active on Alarm 71 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-6 Liebert CRV™—Status and Coil (continued) Status Coil Number of Bits Notes Remote Sensor Low Humidity 10131 — 1 Active on Alarm Remote Sensor High Humidity 10141 — 1 Active on Alarm Remote Sensor Under Temperature 10151 — 1 Active on Alarm Remote Sensor Over Temperature 10161 — 1 Active on Alarm Data Label Remote Sensor 2 Remote Sensor 10 Remote Sensor Low Humidity 10139 — 1 Active on Alarm Remote Sensor High Humidity 10149 — 1 Active on Alarm Remote Sensor Under Temperature 10159 — 1 Active on Alarm Remote Sensor Over Temperature 10169 — 1 Active on Alarm 10230 — 1 Active on Alarm EEV EEV Superheat Below Threshold EEV Discharge Temp Above Threshold 10231 — 1 Active on Alarm EEV Battery Issue 10232 — 1 Active on Alarm EEV Power Issue 10233 — 1 Active on Alarm EEV Unspecified General Event 10234 — 1 Active on Alarm Condenser Communication Lost 10253 — 1 Active on Alarm Condenser Remote Shutdown 10254 — 1 Active on Alarm Liebert Condenser Power Measurement Input Undervoltage 10270 — 1 Active on Alarm Modbus Power Meter Communication Lost 10271 — 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 72 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding Input Holding # of Reg Scale Notes/Units Supply Air Temperature 30385 — 1 10 Units : deg C Int16 Supply Air Temperature 30386 — 1 10 Units : deg F Int16 Return Air Temperature 30387 — 1 10 Units : deg C Int16 Return Air Temperature 30388 — 1 10 Units : deg F Int16 Return Dew Point 30389 — 1 10 Units : deg C Int16 Return Dew Point 30390 — 1 10 Units : deg F Int16 Remote Sensor Minimum Temperature 30391 — 1 10 Units : deg C Int16 Remote Sensor Minimum Temperature 30392 — 1 10 Units : deg F Int16 Remote Sensor Maximum Temperature 30393 — 1 10 Units : deg C Int16 Remote Sensor Maximum Temperature 30394 — 1 10 Units : deg F Int16 Remote Sensor Average Temperature 30395 — 1 10 Units : deg C Int16 Remote Sensor Average Temperature 30396 — 1 10 Units : deg F Int16 Air Temperature Set Point 30397 40397 1 10 Units : deg C Int16 Air Temperature Set Point 30398 40398 1 10 Units : deg F Int16 Cooling Proportional Band 30399 40399 1 10 Units : deg C Uint16 Cooling Proportional Band 30400 40400 1 10 Units : deg F Uint16 Heating Proportional Band 30401 40401 1 10 Units : deg C Uint16 Heating Proportional Band 30402 40402 1 10 Units : deg F Uint16 Air Temperature Dead Band 30403 40403 1 10 Units : deg C Uint16 Air Temperature Dead Band 30404 40404 1 10 Units : deg F Uint16 Supply Air Over Temp Threshold 30405 40405 1 10 Units : deg C Int16 Supply Air Over Temp Threshold 30406 40406 1 10 Units : deg F Int16 Supply Air Under Temp Threshold 30407 40407 1 10 Units : deg C Int16 Supply Air Under Temp Threshold 30408 40408 1 10 Units : deg F Int16 Return Air Over Temp Threshold 30409 40409 1 10 Units : deg C Int16 Return Air Over Temp Threshold 30410 40410 1 10 Units : deg F Int16 Data Label Air Temperature If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 73 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Air Temperature Control Sensor 30460 40460 1 — 0 = Supply 1 = Remote 2 = Return Remote Sensor Temperature Calculation 30461 40461 1 — 0 = Average 1 = Maximum Supply Humidity 30411 — 1 10 Units : % RH Uint16 Return Humidity 30412 — 1 10 Units : % RH Uint16 Humidity Set Point 30413 40413 1 — Units : % RH Uint16 Humidification Proportional Band 30414 40414 1 — Units : % RH Uint16 Dehumidification Proportional Band 30415 40415 1 — Units : % RH Uint16 Humidity Dead Band 30416 40416 1 10 Units : % RH Uint16 High Return Humidity Threshold 30417 40417 1 10 Units : % RH Uint16 Low Return Humidity Threshold 30418 40418 1 10 Units : % RH Uint16 Fan Speed Proportional Band 30419 40419 1 10 Units : deg C Uint16 Fan Speed Proportional Band 30420 40420 1 10 Units : deg F Uint16 Fan Speed Manual Set Point 30421 40421 1 — Units : % Uint16 Fan Speed Maximum Set Point 30422 40422 1 — Units : % Uint16 Fan Speed Minimum Set Point 30423 40423 1 — Units : % Uint16 Fan Control Mode 30462 40462 1 — 0 = Internal (Auto) 1 = External (Manual) Fan Control Sensor 30463 40463 1 — 0 = Supply 1 = Remote 2 = Return Remote Sensor Temperature 30424 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30425 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30425 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30426 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30426 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30427 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30427 — 1 10 Units : deg C Int16 Humidity Fans Remote Sensors If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 74 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Remote Sensor Temperature 30428 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30428 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30429 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30429 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30430 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30430 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30431 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30431 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30432 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30432 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30433 — 1 10 Units : deg F Int16 Remote Sensor Temperature 30433 — 1 10 Units : deg C Int16 Remote Sensor Temperature 30434 — 1 10 Units : deg F Int16 Remote Sensor Function 30464 40464 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30465 40465 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30466 40466 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30467 40467 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30468 40468 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30469 40469 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30470 40470 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30471 40471 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30472 40472 1 — 0 = Disable 1 = Reference 2 = Control If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 75 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Remote Sensor Function 30473 40473 1 — 0 = Disable 1 = Reference 2 = Control Remote Sensor System Average Temperature 30520 — 1 10 Units : deg C Int16 Remote Sensor System Average Temperature 30521 — 1 10 Units : deg F Int16 Remote Sensor System Maximum Temperature 30522 — 1 10 Units : deg C Int16 Remote Sensor System Maximum Temperature 30523 — 1 10 Units : deg F Int16 Remote Sensor Under Temp Threshold 30524 40524 1 10 Units : deg C Int16 Remote Sensor Under Temp Threshold 30525 40525 1 10 Units : deg F Int16 Remote Sensor Over Temp Threshold 30526 40526 1 10 Units : deg C Int16 Remote Sensor Over Temp Threshold 30527 40527 1 10 Units : deg F Int16 Supply Chilled Water Temperature 30444 — 1 10 Units : deg C Int16 Supply Chilled Water Temperature 30445 — 1 10 Units : deg F Int16 Supply Chilled Water Over Temp Threshold 30446 40446 1 10 Units : deg C Int16 Supply Chilled Water Over Temp Threshold 30447 40447 1 10 Units : deg F Int16 BMS Timeout Period 30448 40448 1 — Units : min Uint16 Auto Restart Delay 30449 40449 1 — Units : sec Uint16 Chilled Water System Info System Status 30474 — 1 — 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation System Operating State 30475 — 1 — 0 = off 1 = on 2 = standby System Control Mode 30476 — 1 — 0 = Internal (Auto) 1 = External (Manual) — 0 = Reason Unknown 1 = Network Display 2 = Alarm 3 = Schedule 4 = Remote System 5 = External Input 6 = Local Display System Operating State Reason 30477 — 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 76 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding (continued) Input Holding # of Reg Scale Notes/Units Operating Efficiency 30450 — 1 — Units : % Uint16 Fan Speed 30451 — 1 — Units : % Uint16 Cooling Capacity (Primary) 30452 — 1 — Units : % Uint16 Dehumidifier Utilization 30453 — 1 — Units : % Uint16 Reheat Utilization 30454 — 1 — Units : % Uint16 Humidifier Utilization 30455 — 1 — Units : % Uint16 Calculated Next Maintenance Month 30456 — 1 — Uint16 Calculated Next Maintenance Year 30457 — 1 — Uint16 Data Label System Operations Maintenance Ramp 30458 — 1 — Units : % Uint16 System On/Off Control 30478 40478 1 — 0 = off 1 = on — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection Local Fan Override Local Cooling Override Local Electric Heat Override Local Humidifier Override 30540 — 30541 — 30542 — 30543 — 1 1 1 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 77 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding (continued) Data Label Local Dehumidifier Override Input Holding 30544 — # of Reg 1 Scale Notes/Units — 0 = Normal operation 1 = Increased for internal protection 2 = Decreased for internal protection 3 = Disabled for internal protection 4 = Limited or disabled for low limit protection Protocol 30459 — 1 — 1 = UPS 2 = AIR 3 = PMP 4 = PDU 5 = MONITOR Condenser Refrigerant Type 30479 — 1 — 0 = R22 1 = R407C 2 = R410A Condenser Outside Air Temperature 30480 — 1 10 Units : deg C Int16 Condenser Outside Air Temperature 30481 — 1 10 Units : deg F Int16 Condenser Fan Speed 30482 — 1 — Units : % Int16 Condenser Fan Speed 30483 — 1 — Units : % Int16 Condenser Fan Speed 30484 — 1 — Units : % Int16 Condenser Fan Speed 30485 — 1 — Units : % Int16 Condenser Fan Power 30486 — 1 10 Units : kW Uint16 Condenser Fan Power 30487 — 1 10 Units : kW Uint16 Condenser Fan Power 30488 — 1 10 Units : kW Uint16 Condenser Fan Power 30489 — 1 10 Units : kW Uint16 Condenser Low Noise Mode State 30490 — 1 — 0 = Inactive 1 = Active (Interval) 2 = Active (Full Day) Condenser Low Noise Mode Schedule Control 30491 40491 1 — 0 = disabled 1 = enabled Condenser Low Noise Mode Max Fan Speed 30492 40492 1 — Units : % Uint16 Condenser Normal Mode Max Fan Speed 30493 40493 1 — Units : % Uint16 Server Class Global Condenser Condenser Fan Low Noise Mode If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 78 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding (continued) Data Label Condenser Low Noise Mode - Interval Days Input 30494 Holding 40494 # of Reg 1 Scale Notes/Units — 1 = Monday 2 = Tuesday 4 = Wednesday 8 = Thursday 16 = Friday 32 = Saturday 64 = Sunday Condenser Low Noise Mode - Full Days 30495 40495 1 — 1 = Monday 2 = Tuesday 4 = Wednesday 8 = Thursday 16 = Friday 32 = Saturday 64 = Sunday Condenser Low Noise Mode Start Time 30496 40496 2 — Secs since Epoch(UTC) Condenser Low Noise Mode Stop Time 30498 40498 2 — Secs since Epoch(UTC) 1 — Units : % Int16 Super Saver Super Saver Call For Cooling 30502 Auxiliary Air Raw Auxiliary Air Temperature 30510 40510 1 10 Units : deg C Int16 Raw Auxiliary Air Temperature 30511 40511 1 10 Units : deg F Int16 Actual Auxiliary Air Temperature 30512 — 1 10 Units : deg C Int16 Actual Auxiliary Air Temperature 30513 — 1 10 Units : deg F Int16 30550 — 1 10 Units : % Uint16 30560 — 1 — Int16 EEV EEV Open Position Liebert Condenser Expected Condenser Unit Count Condenser Fan Reversal Requested 30562 — 1 — 0 = false 1 = true Condenser Refrigerant Pressure 30563 — 1 10 Units : bar Int16 Condenser Supply Refrigerant Temperature 30564 — 1 10 Units : deg C Int16 Condenser Supply Refrigerant Temperature 30565 — 1 10 Units : deg F Int16 System Input RMS A-B 30570 — 1 10 Units : VAC Int16 System Input RMS A-N 30571 — 1 10 Units : VAC Int16 System Input RMS Current Phase A 30572 — 1 10 Units : A AC Int16 System Input RMS B-C 30573 — 1 10 Units : VAC Int16 System Input RMS B-N 30574 — 1 10 Units : VAC Int16 Power Measurement If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 79 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units System Input RMS Current Phase B 30575 — 1 10 Units : A AC Int16 System Input RMS C-A 30576 — 1 10 Units : VAC Int16 System Input RMS C-N 30577 — 1 10 Units : VAC Int16 System Input RMS Current Phase C 30578 — 1 10 Units : A AC Int16 Energy Consumption 30579 40579 2 — Units : kWH Int32 Instantaneous Power 30581 — 2 — Units : W Int32 Smoke Detected - Event Control 30592 40592 1 — 0 = disabled 1 = enabled Smoke Detected - Event Type 30593 40593 1 — 0 = Message 1 = Warning 2 = Alarm Water Under Floor - Event Control 30594 40594 1 — 0 = disabled 1 = enabled Water Under Floor - Event Type 30595 40595 1 — 0 = Message 1 = Warning 2 = Alarm Customer Input 1 - Event Control 30596 40596 1 — 0 = disabled 1 = enabled Customer Input 1 - Event Type 30597 40597 1 — 0 = Message 1 = Warning 2 = Alarm Customer Input 2 - Event Control 30598 40598 1 — 0 = disabled 1 = enabled Customer Input 2 - Event Type 30599 40599 1 — 0 = Message 1 = Warning 2 = Alarm Customer Input 3 - Event Control 30600 40600 1 — 0 = disabled 1 = enabled Customer Input 3 - Event Type 30601 40601 1 — 0 = Message 1 = Warning 2 = Alarm Customer Input 4 - Event Control 30602 40602 1 — 0 = disabled 1 = enabled Customer Input 4 - Event Type 30603 40603 1 — 0 = Message 1 = Warning 2 = Alarm Service Required - Event Control 30604 40604 1 — 0 = disabled 1 = enabled Service Required - Event Type 30605 40605 1 — 0 = Message 1 = Warning 2 = Alarm Shutdown - Loss Of Power - Event Control 30606 40606 1 — 0 = disabled 1 = enabled Shutdown - Loss Of Power - Event Type 30607 40607 1 — 0 = Message 1 = Warning 2 = Alarm Event Configuration If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 80 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-7 Liebert CRV™—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Ext Loss of Flow - Event Control 30608 40608 1 — 0 = disabled 1 = enabled Ext Loss of Flow - Event Type 30609 40609 1 — 0 = Message 1 = Warning 2 = Alarm Ext Reheat Lockout - Event Control 30610 40610 1 — 0 = disabled 1 = enabled Ext Reheat Lockout - Event Type 30611 40611 1 — 0 = Message 1 = Warning 2 = Alarm Ext Humidifier Lockout - Event Control 30612 40612 1 — 0 = disabled 1 = enabled Ext Humidifier Lockout - Event Type 30613 40613 1 — 0 = Message 1 = Warning 2 = Alarm Ext Compressor Lockout - Event Control 30614 40614 1 — 0 = disabled 1 = enabled Ext Compressor Lockout - Event Type 30615 40615 1 — 0 = Message 1 = Warning 2 = Alarm Ext Over Temperature - Event Control 30616 40616 1 — 0 = disabled 1 = enabled Ext Over Temperature - Event Type 30617 40617 1 — 0 = Message 1 = Warning 2 = Alarm Condenser VFD Issue - Event Control 30618 40618 1 — 0 = disabled 1 = enabled Condenser VFD Issue - Event Type 30619 40619 1 — 0 = Message 1 = Warning 2 = Alarm Condenser TVSS Issue - Event Control 30620 40620 1 — 0 = disabled 1 = enabled Condenser TVSS Issue - Event Type 30621 40621 1 — 0 = Message 1 = Warning 2 = Alarm Condenser 1 Issue - Event Control 30622 40622 1 — 0 = disabled 1 = enabled Condenser 1 Issue - Event Type 30623 40623 1 — 0 = Message 1 = Warning 2 = Alarm 39998 49998 2 — Secs since Epoch(UTC) Time System Date and Time If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 81 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-8 Liebert CRV™—Glossary Data Label Data Description Actual Auxiliary Air Temperature Actual auxiliary air temperature value being used for control. This value may differ from the raw value received from the auxiliary device if filtering is applied. Air Temperature Control Sensor Sensor from which air temperature measurements will be used for cooling and heating control. Air Temperature Dead Band Value that is divided evenly to form a temperature range above and below [Air Temperature Set Point]. If measured air temperature is within this range, no heating or cooling will occur. Air Temperature Set Point Desired air temperature. This set point is dependent upon which sensor is selected for control. Auto Restart Delay If power is lost, the control will delay this amount of time after power is restored before restarting the unit. Aux Air Temp Device Communication Lost Communication with external auxiliary device providing an air temperature value has been lost. BMS Communications Timeout Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe. BMS Timeout Period Timeframe within which the Building Management System (or external monitoring system) must communicate with the system to avoid a timeout. Bottom Fan Issue The bottom fan is not operating within its normal parameters. Calculated Next Maintenance Month Calculated month of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Year]. Calculated Next Maintenance Year Calculated year of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Month]. Chilled Water Control Valve Failure Chilled water valve out of position. Chilled water control valve position does not match expected value. Clogged Air Filter Air filter is dirty and needs to be (cleaned or) replaced. Compressor 1 High Head Pressure Compressor 1 high head pressure. Compressor 1 High Pressure Transducer Issue Compressor 1 high pressure transducer is disconnected or the signal is out of range. Compressor 1 Hours Exceeded Operating hours for compressor 1 have exceeded the threshold. Compressor 1 Low Pressure Transducer Issue Compressor 1 low pressure transducer is disconnected or the signal is out of range. Compressor 1 Low Suction Pressure Compressor 1 low suction pressure. Compressor 1 Pump Down Issue Unable to pump down suction-side pressure during compressor 1 shutdown. Compressor 1 Short Cycle Compressor 1 short cycle. A short cycle is defined as turning on and off a number of times over a set time period. Compressor Capacity Reduced Compressor capacity has been reduced. Compressor Superheat Over Threshold Compressor discharge refrigerant superheat temperature has exceeded an upper threshold. Condenser 1 Issue - Event Control Enable/disable the activation of the [Condenser 1 Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Condenser 1 Issue - Event Type The event type for the [Condenser 1 Issue] event. Condenser 1 Issue Condenser 1 is not operating within its normal parameters. Condenser Circuit Unspecified General Event One or more unspecified condenser circuit events active. See local unit display for further details. Condenser Communication Lost Communication with condenser unit has been lost. Condenser Control Board Issue The condenser control board is reporting an issue. Condenser Fan Issue Condenser fan is not operating within its operational parameters. Condenser Fan Power Condenser fan's measured input power. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 82 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-8 Liebert CRV™—Glossary (continued) Data Label Data Description Condenser Fan Reversal Requested Request the condenser fans to rotate in the reverse direction. Condenser Fan Speed Condenser fan speed expressed as a percentage of the maximum rated speed. Condenser Low Noise Mode - Full Days Days of the week selected for low noise mode full day scheduling. Condenser Low Noise Mode - Interval Days Days of the week selected for low noise mode interval scheduling. Condenser Low Noise Mode Max Fan Speed Maximum fan speed when condenser is placed in low noise mode. Condenser Low Noise Mode Schedule Control Enable/disable scheduled control of condenser low noise mode. Condenser Low Noise Mode Start Time The time of day at which the condenser will transition into low noise mode. Condenser Low Noise Mode State State of condenser low noise mode scheduler control. Condenser Low Noise Mode Stop Time The time of day at which the condenser will transition out of low noise mode. Condenser Max Fan Speed Override Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition. Condenser Normal Mode Max Fan Speed Maximum fan speed when condenser is not in low noise mode. Condenser Outside Air Temp Out of Operating Range [Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold. Condenser Outside Air Temp Sensor Issue Condenser outside air temperature sensor is disconnected or the signal is out of range. Condenser Outside Air Temperature Condenser ambient outside air temperature. Condenser Refrigerant Pressure Over Threshold Condenser refrigerant pressure has exceeded a threshold. Condenser Refrigerant Pressure Sensor Issue Condenser refrigerant pressure sensor is disconnected or the signal is out of range. Condenser Refrigerant Pressure Under Threshold Condenser refrigerant pressure has dropped below a threshold. Condenser Refrigerant Pressure Pressure of the refrigerant in a condenser circuit. Condenser Refrigerant Type Condenser refrigerant type. Condenser Remote Shutdown Condenser is shut down by a remote signal. Condenser Supply Refrigerant Over Temp Condenser supply refrigerant temperature has exceeded a threshold. Condenser Supply Refrigerant Temp Sensor Issue Condenser supply refrigerant temperature sensor is disconnected or the signal is out of range. Condenser Supply Refrigerant Temperature Temperature of the supply refrigerant in a condenser circuit. Condenser Supply Refrigerant Under Temp Condenser supply refrigerant temperature has dropped below a specified threshold. Condenser TVSS Issue - Event Control Enable/disable the activation of the [Condenser TVSS or SPD Issue] event (Transient Voltage Surge Suppressor or Surge Protection Device). If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Condenser TVSS Issue - Event Type The event type for the [Condenser TVSS or SPD Issue] event (Transient Voltage Surge Suppressor or Surge Protection Device). Condenser TVSS Issue The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed. Condenser Unit Unspecified General Event One or more unspecified condenser unit events active. See local unit display for further details. Condenser VFD Issue - Event Control Enable/disable the activation of the [Condenser VFD Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Condenser VFD Issue - Event Type The event type for the [Condenser VFD Issue] event. Condenser VFD Issue The condenser fan Variable Frequency Drive is offline. 83 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-8 Liebert CRV™—Glossary (continued) Data Label Data Description Cooling Capacity (Primary) Compressor utilization or chilled water valve position, based on unit type. Cooling Proportional Band Temperature control band above [Air Temperature Set Point]. If measured air temperature is within this band, cooling operations are proportionally controlled. Customer Input 1 - Event Control Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 1 - Event Type The event type for the [Customer Input 1] event. Customer Input 1 Customer Input 1. Customer Input 2 - Event Control Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 2 - Event Type The event type for the [Customer Input 2] event. Customer Input 2 Customer input 2. Customer Input 3 - Event Control Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 3 - Event Type The event type for the [Customer Input 3] event. Customer Input 3 Customer input 3. Customer Input 4 - Event Control Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 4 - Event Type The event type for the [Customer Input 4] event. Customer Input 4 Customer input 4. Dehumidification Proportional Band Humidity control band above [Humidity Set Point]. If measured humidity is within this band, dehumidification operations are proportionally controlled. Dehumidifier Hours Exceeded Operating hours for the dehumidifier have exceeded the threshold. Dehumidifier Utilization Present dehumidifier utilization expressed as a percentage of the maximum rated capacity. Dig Scroll Comp 1 Over Temp Digital scroll compressor 1 shut off because its head temperature has exceeded the upper threshold. Dig Scroll Comp 1 Temp Sensor Issue Digital scroll compressor 1 temperature sensor is disconnected or the signal is out of range. EEV Battery Issue Electronic expansion valve battery cannot be recharged and needs to be replaced. EEV Discharge Temp Above Threshold Electronic expansion valve refrigerant high discharge temperature event. EEV Open Position Electronic expansion valve open position. EEV Power Issue Electronic expansion valve lost power and is running on battery backup. EEV Superheat Below Threshold Electronic expansion valve refrigerant low superheat event. EEV Unspecified General Event One or more unspecified electronic expansion valve events active. See local unit display for further details. Electric Reheater 1 Hours Exceeded Operating hours for electric reheater 1 have exceeded the threshold. Electric Reheater Hours Exceeded [Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold]. Energy Consumption Energy consumption since the last reset of this value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 84 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-8 Liebert CRV™—Glossary (continued) Data Label Data Description Expected Condenser Unit Count Number of physical condenser units that are expected to be connected to the system. Ext Compressor Lockout - Event Control Enable/disable the activation of the [Ext Compressor Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Compressor Lockout - Event Type The event type for the [Ext Compressor Lockout] event. Ext Compressor Lockout The compressor is shut down and disabled by an external input signal. Ext Condenser Pump High Water High water is detected in the condenser, as indicated by an external input signal. Ext Humidifier Lockout - Event Control Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Humidifier Lockout - Event Type The event type for the [Ext Humidifier Lockout] event. Ext Humidifier Lockout The humidifier is shut down and disabled by an external input signal. Ext Loss of Flow - Event Control Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Loss of Flow - Event Type The event type for the [Ext Loss of Flow] event. Ext Loss of Flow Loss of flow is detected, as indicated by an external input signal. Ext Over Temperature - Event Control Enable/disable the activation of the [Ext Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Over Temperature - Event Type The event type for the [Ext Over Temperature] event. Ext Over Temperature A temperature has exceeded its threshold, as indicated by an external input signal. Ext Reheat Lockout - Event Control Enable/disable the activation of the [Ext Reheat Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Reheat Lockout - Event Type The event type for the [Ext Reheat Lockout] event. Ext Reheat Lockout The reheater is shut down and disabled by an external input signal. Ext Standby Glycol Pump On The standby glycol pump is on, as indicated by an external input signal. External Condenser TVSS Issue The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal. External Condenser VFD Issue The condenser fan Variable Frequency Drive is offline, as indicated by an external input signal. External Fire Detected Fire detected, as indicated by an external input signal. Fan Control Mode Fan control mode. Allowable modes are: (0) Auto - Fan speed is controlled via the selected fan control sensor, and, (1) Manual - Fan will operate at a fixed speed. Fan Control Sensor Sensor from which air temperature measurements will be used for fan speed control. Fan Hours Exceeded Operating hours for the unit blower fan have exceeded the threshold. Fan Speed Manual Set Point Manual fan speed. Fan Speed Maximum Set Point Maximum fan speed. Fan Speed Minimum Set Point Minimum fan speed. 85 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-8 Liebert CRV™—Glossary (continued) Data Label Data Description Fan Speed Proportional Band Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled. Fan Speed Fan speed expressed as a percentage of the maximum rated speed. Fluid Flow Sensor Issue The fluid flow sensor is disconnected or the signal is out of range. Fluid Temperature Sensor Issue The fluid temperature sensor is disconnected or the signal is out of range. Heating Proportional Band Temperature control band below [Air Temperature Set Point]. If measured air temperature is within this band, heating operations are proportionally controlled. High Power Shutdown Supply to high power components has been shutdown. High Return Humidity Threshold Threshold value used in the [High Return Humidity] event. High Return Humidity Return air high humidity event. Humidification Proportional Band Humidity control band below [Humidity Set Point]. If measured humidity is within this band, humidification operations are proportionally controlled. Humidifier Control Board Not Detected Humidifier control board is required to be connected, but no signal is detected. Humidifier Cylinder Worn Humidifier cylinder is not operating properly and needs to be replaced. Humidifier Hours Exceeded Operating hours for the humidifier have exceeded the threshold. Humidifier Issue Humidifier issue detected, causing it to be locked out. Humidifier Low Water The water level in the humidifier has dropped below its threshold. Humidifier Over Current The electrical current to the humidifier has exceeded its upper threshold. Humidifier Under Current The electrical current to the humidifier has dropped below its lower threshold. Humidifier Utilization Present humidifier utilization expressed as a percentage of the maximum rated capacity. Humidity Dead Band Value that is divided evenly to form a range above and below [Humidity Set Point]. If measured humidity is within this range, no humidification or dehumidification will occur. Humidity Set Point Desired relative humidity. Input Undervoltage One or more of the input phase voltages has dropped below the limit. Instantaneous Power Total electrical power currently being consumed. Local Cooling Override The local unit override status for cooling capacity. Local Dehumidifier Override The local unit override status for the dehumidifier. Local Electric Heat Override The local unit override status for electric heat. Local Fan Override The local unit override status for fan speed. Local Humidifier Override The local unit override status for the humidifier. Loss of Air Flow No air flow through the unit due to failure of all fans. Low Return Humidity Threshold Threshold value used in the [Low Return Humidity] event. Low Return Humidity Return air low humidity event. Maintenance Completed Maintenance has been completed on the unit. Maintenance Due The calculated maintenance date has been reached. Maintenance Ramp The ratio of operations performed to the calculated operations available between maintenance intervals. Master Unit Communication Lost Communication with master unit has been lost. Modbus Power Meter Communication Lost Communication with Modbus power meter has been lost. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 86 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-8 Liebert CRV™—Glossary (continued) Data Label Data Description Operating Efficiency The ratio of cooling energy provided to the amount of total energy being used. Power Source 'A' Issue No power is detected at power source input 'A'. Power Source B Failure No power is detected at power source input B. RAM Battery Issue RAM or RAM backup battery is not operating correctly. Raw Auxiliary Air Temperature Air temperature value sent by an external auxiliary device, with no additional filtering by the receiving system. This may be an aggregated value from multiple sensors. Reheat Utilization Present reheating utilization expressed as a percentage of the maximum rated capacity. Reheater Over Temperature The temperature of the reheater has exceeded its threshold. Remote Sensor Average High Humidity The average humidity of multiple remote sensors on the cooling unit has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. Remote Sensor Average Low Humidity The average humidity of multiple remote sensors on the cooling unit has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. Remote Sensor Average Over Temperature [Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor Average Temperature Average value of remote sensor temperature measurements. Remote Sensor Average Under Temperature [Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Remote Sensor Function Function assigned to remote sensor. Available values are: (0) Control - sensor will be used in calculation of remote sensor temperature that may be used for heating and cooling control, (1) Reference - sensor will not be used in calculation of remote sensor temperature, but is enabled, (2) Disable - sensor is disabled Remote Sensor High Humidity Remote sensor humidity has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. Remote Sensor Issue Remote sensor is disconnected or the signal is out of range. Remote Sensor Low Humidity Remote sensor humidity has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. Remote Sensor Maximum Temperature Maximum value of remote sensor temperature measurements. Remote Sensor Minimum Temperature Minimum value of remote sensor temperature measurements. Remote Sensor Over Temp Threshold Threshold value used in the remote air sensor over temperature events. Remote Sensor Over Temperature [Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor System Average High Humidity The average humidity of multiple remote sensors on interconnected cooling units in a single system has exceeded an upper threshold. The event is deactivated when the humidity drops below the threshold. Remote Sensor System Average Low Humidity The average humidity of multiple remote sensors on interconnected cooling units in a single system has dropped below a lower threshold. The event is deactivated when the humidity rises above the threshold. Remote Sensor System Average Over Temperature [Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor System Average Temperature Average value of remote sensor temperature measurements among a group of interconnected units in a single system. Remote Sensor System Average Under Temperature Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Remote Sensor System Maximum Temperature Maximum value of remote sensor temperature measurements among a group of interconnected units in a single system. 87 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-8 Liebert CRV™—Glossary (continued) Data Label Data Description Remote Sensor Temperature Calculation Calculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control. Remote Sensor Temperature Air temperature as measured by remote sensor. Remote Sensor Under Temp Threshold Threshold value used in the remote air sensor under temperature events. Remote Sensor Under Temperature [Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Return Air Over Temp Threshold Threshold value used in the [Return Air Over Temperature] event. Return Air Over Temperature Return air high temperature event. Return Air Sensor Issue The air sensor at the inlet of the unit is disconnected or the signal is out of range. Return Air Temperature The temperature of the inlet air Return Dew Point Dew point temperature measured at the inlet of the unit. Return Humidity Out Of Proportional Band [Return Humidity] has exceeded the upper limit of [Dehumidification Proportional Band], or has dropped below the lower limit of [Humidification Proportional Band] ], for an extended period of time. Return Humidity Relative humidity measured at the inlet of the unit. SEC Communication Lost Communication with the Superheat and Envelope Controller has been lost. The event is deactivated when communication is reestablished. SEC Unspecified General Event One or more unspecified events active for the Superheat and Envelope Controller. See local unit display for further details. Server Class The general classification for this system Service Required - Event Control Enable/disable the activation of the [Service Required] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Service Required - Event Type The event type for the [Service Required] event. Service Required Unit requires servicing. Shutdown - Loss Of Power - Event Control Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Shutdown - Loss Of Power - Event Type The event type for the [Shutdown - Loss Of Power] event. Shutdown - Loss Of Power System lost power. This event becomes active when the unit is powered on following an unexpected loss of power. This event remains active for 90 minutes. Smoke Detected - Event Control Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Smoke Detected - Event Type The event type for the [Smoke Detected] event. Smoke Detected Smoke detected. Static Pressure Sensor Issue The static pressure sensor is disconnected or the signal is out of range. Static Pressure Sensor Out of Range Static pressure sensor signal is out of its configured range. Super Saver Call For Cooling Call for cooling value used for Super Saver functionality. A higher call for cooling value indicates a need for a lower coolant temperature. Supply Air Over Temp Threshold Threshold value used in the [Supply Air Over Temperature] event. Supply Air Over Temperature Supply air high temperature event. Supply Air Sensor Issue The air sensor at the outlet of the unit is disconnected or the signal is out of range. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 88 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-8 Liebert CRV™—Glossary (continued) Data Label Data Description Supply Air Temperature Air temperature measured at the outlet of the unit. Supply Air Under Temp Threshold Threshold value used in the [Supply Air Under Temperature] event. Supply Air Under Temperature Supply air low temperature event. Supply Chilled Water Loss of Flow Supply chilled water flow is too low. Supply Chilled Water Over Temp Threshold Threshold value used in the [Supply Chilled Water Over Temp] event. Supply Chilled Water Over Temp [Supply Chilled Water Temperature] has exceeded [Supply Chilled Water Over Temp Threshold]. Supply Chilled Water Temperature Supply chilled water temperature. Supply Fluid Temp Sensor Issue The supply fluid temperature sensor is disconnected or the signal is out of range. Supply Humidity Relative humidity at the outlet of the unit. System Control Mode System control mode. System Date and Time The system date and time System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System On/Off Control Turn system functionality on or off. System Operating State Reason The reason the system is in the current operating state. System Operating State Current operating state of the system. System Status The operating status for the system Top Fan Issue The top fan is not operating within its normal parameters. Unit Code Missing Unit code has not been entered and saved. Unit Off Unit was turned off. Unit On Unit was turned on. Unit Partial Shutdown An event has occurred requiring some system components to be shutdown and disabled. Unit Shutdown An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit Standby Unit was placed in standby mode. Unspecified General Event One or more unspecified events active. See local unit display for further details. Water Leakage Detector Sensor Issue The water leakage detector sensor is disconnected or the signal is out of range. Water Under Floor - Event Control Enable/disable the activation of the [Water Under Floor] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Water Under Floor - Event Type The event type for the [Water Under Floor] event. Water Under Floor Water under the floor is detected. 89 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-9 Liebert HPC™ (Chiller) - Status and Coil Status Coil Number of Bits Notes Compressor Not Stopping 10001 — 1 Active on Alarm Compressor Superheat Over Threshold 10002 — 1 Active on Alarm Data Label Compressors Compressor 1 Compressor Hours Exceeded 10012 — 1 Active on Alarm Compressor High Head Pressure 10013 — 1 Active on Alarm Compressor Low Suction Pressure 10014 — 1 Active on Alarm Compressor Thermal Overload 10015 — 1 Active on Alarm Compressor Low Oil Pressure 10016 — 1 Active on Alarm Compressor Loss of Differential Pressure 10018 — 1 Active on Alarm Compressor Capacity Reduced 10019 — 1 Active on Alarm Compressor Capacity Normal 10020 — 1 Active on Alarm Compressor Contactor Issue 10021 — 1 Active on Alarm Compressor 2 Compressor Hours Exceeded 10029 — 1 Active on Alarm Compressor High Head Pressure 10030 — 1 Active on Alarm Compressor Low Suction Pressure 10031 — 1 Active on Alarm Compressor Thermal Overload 10032 — 1 Active on Alarm Compressor Low Suction Pressure 10033 — 1 Active on Alarm Compressor Loss of Differential Pressure 10035 — 1 Active on Alarm Compressor Capacity Reduced 10036 — 1 Active on Alarm Compressor Capacity Normal 10037 — 1 Active on Alarm Compressor Contactor Issue 10038 — 1 Active on Alarm Compressor 4 Compressor Hours Exceeded 10230 — 1 Active on Alarm Compressor High Head Pressure 10231 — 1 Active on Alarm Compressor Low Suction Pressure 10232 — 1 Active on Alarm Compressor Thermal Overload 10233 — 1 Active on Alarm Compressor Low Suction Pressure 10234 — 1 Active on Alarm Compressor Loss of Differential Pressure 10236 — 1 Active on Alarm Compressor Capacity Reduced 10237 — 1 Active on Alarm Compressor Capacity Normal 10238 — 1 Active on Alarm Compressor Contactor Issue 10239 — 1 Active on Alarm Condensers 1 Condenser Fan Issue 10046 — 1 Active on Alarm Low Condenser Refrigerant Pressure 10047 — 1 Active on Alarm Condenser Max Fan Speed Override 10048 — 1 Active on Alarm Condensers 2 Condenser Fan Issue 10058 — 1 Active on Alarm Low Condenser Refrigerant Pressure 10059 — 1 Active on Alarm Condenser Max Fan Speed Override 10060 — 1 Active on Alarm Condensers 4 Condenser Fan Issue 10066 1 Active on Alarm Low Condenser Refrigerant Pressure 10067 1 Active on Alarm Condenser Max Fan Speed Override 10068 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 90 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-9 Liebert HPC™ (Chiller) - Status and Coil (continued) Data Label Status Coil Number of Bits Notes 10070 1 Active on Alarm 10081 1 Active on Alarm Fluid Low Fluid Pressure Supply (Outlet) Fluid Supply Fluid Over Temp Supply Fluid Under Temp 10082 1 Active on Alarm Supply Fluid Temp Sensor Issue 10083 1 Active on Alarm 10096 1 Active on Alarm All Pumps Loss of Flow 10107 1 Active on Alarm Pump 1 Loss of Flow 10108 1 Active on Alarm Pump 2 Loss of Flow 10109 1 Active on Alarm 10120 1 Active on Alarm 10131 1 Active on Alarm Free Cooling Valve Hours Exceeded 10142 1 Active on Alarm Ambient Air Temperature Sensor Issue 10143 1 Active on Alarm Evaporator Inlet Temp Sensor Issue 10154 1 Active on Alarm Evaporator Return Fluid Over Temp 10155 1 Active on Alarm Evaporator Return Fluid Under Temp 10156 1 Active on Alarm Evaporator Fluid Freeze - Auto Reset 10165 1 Active on Alarm Evaporator Fluid Freeze - Manual Reset Required 10166 1 Active on Alarm Supply Refrigerant Temp Sensor Issue 10167 1 Active on Alarm Evaporator Fluid Freeze - Auto Reset 10178 1 Active on Alarm Evaporator Fluid Freeze - Manual Reset Required 10179 1 Active on Alarm Supply Refrigerant Temp Sensor Issue 10180 1 Active on Alarm Customer Input 1 10191 1 Active on Alarm Customer Input 2 10192 1 Active on Alarm Customer Input 3 10251 1 Active on Alarm Customer Input 4 10252 1 Active on Alarm Unit On 10193 1 Active on Alarm Unit Off 10194 1 Active on Alarm Return (Inlet) Fluid Return Fluid Temp Sensor Issue Pumps Pump 1 Pump Hours Exceeded Pump 2 Pump Hours Exceeded Free Cooling Evaporators Evaporator 1 Evaporator 2 System Events Master Unit Communication Lost 10195 1 Active on Alarm Subgroup Event Occurred During Communication Loss 10196 1 Active on Alarm Humidifier Control Board Not Detected 10197 1 Active on Alarm RAM Battery Issue 10198 1 Active on Alarm Unit Code Missing 10199 1 Active on Alarm Unspecified General Event 10200 1 Active on Alarm Unit Shutdown Unspecified General Event 10250 1 Active on Alarm 91 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-9 Liebert HPC™ (Chiller) - Status and Coil (continued) Data Label Status Coil Number of Bits Notes 10270 1 Active on Alarm 10280 1 Active on Alarm 10300 1 Active on Alarm 10311 1 Active on Alarm 10322 1 Active on Alarm EEV 1 EEV Unspecified General Event EEV 2 EEV Unspecified General Event EEV 4 EEV Unspecified General Event Power Measurement 1 Modbus Power Meter Communication Lost Power Measurement 2 Modbus Power Meter Communication Lost Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 92 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-10 Liebert HPC™ (Chiller)—Input and Holding Data Label Input Holding # of Reg Scale Notes/Units Protocol Server Class 30385 1 1 = UPS 2 = AIR 3 = PMP 4 = PDU 5 = MONITOR Compressors Compressor Shut Down - Ambient Air Low Temp Limit 30389 40389 1 Units : deg C Int16 Compressor Shut Down - Ambient Air Low Temp Limit 30390 40390 1 Units : deg F Int16 Compressor 1 Compressor State 30394 1 0 = off 1 = on Compressor Capacity Control State 30395 1 0 = off 1 = on Compressor Head Pressure 30396 1 Compressor Hours 30397 40397 1 Units : hr Uint16 Compressor Hours Threshold 30398 40398 1 Units : hr Uint16 10 Units : bar Uint16 Compressor 2 Compressor State 30402 1 0 = off 1 = on Compressor Capacity Control State 30403 1 0 = off 1 = on Compressor Head Pressure 30404 1 Compressor Hours 30405 40405 1 Units : hr Uint16 Compressor Hours Threshold 30406 40406 1 Units : hr Uint16 10 Units : bar Uint16 Compressor 4 Compressor State 30550 1 0 = off 1 = on Compressor Capacity Control State 30551 1 0 = off 1 = on Compressor Head Pressure 30552 1 Compressor Hours 30553 40553 1 Units : hr Uint16 Compressor Hours Threshold 30554 40554 1 Units : hr Uint16 30410 1 Units : % Uint16 30414 1 Units : % Uint16 10 Units : bar Uint16 Condensers 1 Condenser Fan Speed Condensers 2 Condenser Fan Speed If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 93 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-10 Liebert HPC™ (Chiller)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Condensers 4 Condenser Fan Speed Units : % Uint16 30417 1 Fluid Pressure 30418 1 10 Units : bar Int16 Fluid Cooling Proportional Band 30419 40419 1 10 Units : deg C Uint16 Fluid Cooling Proportional Band 30420 40420 1 10 Units : deg F Uint16 Supply Fluid Temp Set Point 1 30424 40424 1 10 Units : deg C Int16 Supply Fluid Temp Set Point 1 30425 40425 1 10 Units : deg F Int16 Supply Fluid Temp Set Point 2 30426 40426 1 Units : deg C Int16 Supply Fluid Temp Set Point 2 30427 40427 1 Units : deg F Int16 Supply Fluid Over Temp Alarm Threshold 30430 40430 1 Units : deg C Int16 Supply Fluid Over Temp Alarm Threshold 30431 40431 1 Units : deg F Int16 Supply Fluid Under Temp Alarm Threshold 30434 40434 1 Units : deg C Int16 Supply Fluid Under Temp Alarm Threshold 30435 40435 1 Units : deg F Int16 Pump Hours 30450 40450 1 Units : hr Uint16 Pump Hours Threshold 30451 40451 1 Units : hr Uint16 Pump Hours 30455 40455 1 Units : hr Uint16 Pump Hours Threshold 30456 40456 1 Units : hr Uint16 Free Cooling External Temperature Delta 30460 40460 1 Units : deg C Uint16 Free Cooling External Temperature Delta 30461 40461 1 Units : deg F Uint16 Free Cooling Status 30462 1 0 = off 2 = on 3 = No Support Free Cooling Valve Open Position 30463 1 Units : % Uint16 Free Cooling Valve Hours 30464 40464 1 Units : hr Uint16 Free Cooling Valve Hours Threshold 30465 40465 1 Units : hr Uint16 Fluid Supply (Outlet) Fluid Pump 1 Pump 2 Free Cooling If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 94 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-10 Liebert HPC™ (Chiller)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Evaporators Evaporator Return Fluid Temperature 30469 1 10 Units : deg C Int16 Evaporator Return Fluid Temperature 30470 1 10 Units : deg F Int16 Evaporator Return Fluid Over Temp Alarm Threshold 30615 40615 1 Units : deg C Int16 Evaporator Return Fluid Over Temp Alarm Threshold 30616 40616 1 Units : deg F Int16 Evaporator Return Fluid Over Temp Warning Threshold 30617 40617 1 Units : deg C Int16 Evaporator Return Fluid Over Temp Warning Threshold 30618 40618 1 Units : deg F Int16 Evaporator Return Fluid Under Temp Warning Threshold 30619 40619 1 Units : deg C Int16 Evaporator Return Fluid Under Temp Warning Threshold 30620 40620 1 Units : deg F Int16 Evaporator Return Fluid Under Temp Alarm Threshold 30621 40621 1 Units : deg C Int16 Supply Brine Temp Set Point 30474 40474 1 Units : deg C Int16 Supply Brine Temp Set Point 30475 40475 1 Units : deg F Int16 30479 40479 1 Uint16 Brine Standby Units Standby Units System Info System Status 30483 1 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation System Operating State 30484 1 0 = off 1 = on 2 = standby System Control Mode 30485 1 0 = Internal (Auto) 1 = External (Manual) 1 0 = Reason Unknown 1 = Network Display 2 = Alarm 3 = Schedule 4 = Remote System 5 = External Input 6 = Local Display 1 0 = off 1 = on System Operating State Reason 30486 System On/Off Control 30487 40487 System Operations Return Fluid Temperature 30491 1 10 Units : deg C Int16 Return Fluid Temperature 30492 1 10 Units : deg F Int16 Supply Fluid Temperature 30493 1 10 Units : deg C Int16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 95 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-10 Liebert HPC™ (Chiller)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Supply Fluid Temperature 30494 — 1 10 Units : deg F Int16 Actual Supply Fluid Temp Set Point 30495 — 1 10 Units : deg C Int16 Actual Supply Fluid Temp Set Point 30496 — 1 10 Units : deg F Int16 Condenser Inlet Water Temperature 30497 — 1 10 Units : deg C Int16 Condenser Inlet Water Temperature 30498 — 1 10 Units : deg F Int16 Condenser Outlet Water Temperature 30499 — 1 10 Units : deg C Int16 Condenser Outlet Water Temperature 30500 — 1 10 Units : deg F Int16 Supply Heated Water Temp Set Point 30501 40501 1 — Units : deg C Int16 Supply Heated Water Temp Set Point 30502 40502 1 — Units : deg F Int16 Free Cooling Utilization 30503 — 1 — Units : % Uint16 Reheat Utilization 30504 — 1 — Units : % Uint16 Compressor Utilization 30505 — 1 — Units : % Uint16 Ambient Air Temperature 30506 — 1 10 Units : deg C Int16 Ambient Air Temperature 30507 — 1 10 Units : deg F Int16 Compressor Economizer Utilization 30508 — 1 — Units : % Uint16 Condenser Adiabatic Cooling Utilization 30509 — 1 — Units : % Uint16 Pump 1 State 30510 — 1 — 0 = off 1 = on Pump 2 State 30511 — 1 — 0 = off 1 = on 40515 1 — 2 = Reset 4 = Acknowledge System Events System Event Acknowledge/Reset Power Measurement 1 System Input RMS A-B 30707 — 1 — Units : VAC Int16 System Input RMS A-N 30708 — 1 — Units : VAC Int16 System Input RMS Current Phase A 30709 — 1 — Units : A AC Int16 System Input RMS B-C 30710 — 1 — Units : VAC Int16 System Input RMS B-N 30711 — 1 — Units : VAC Int16 System Input RMS Current Phase B 30712 — 1 — Units : A AC Int16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 96 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-10 Liebert HPC™ (Chiller)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units System Input RMS C-A 30713 — 1 — Units : VAC Int16 System Input RMS C-N 30714 — 1 — Units : VAC Int16 System Input RMS Current Phase C 30715 — 1 — Units : A AC Int16 Energy Consumption 30716 — 2 — Units : kWH Int32 Instantaneous Power 30718 — 2 — Units : W Int32 Output Power Factor 30720 — 1 — Int16 System Input RMS A-B 30731 — 1 — Units : VAC Int16 System Input RMS A-N 30732 — 1 — Units : VAC Int16 System Input RMS Current Phase A 30733 — 1 — Units : A AC Int16 System Input RMS B-C 30734 — 1 — Units : VAC Int16 System Input RMS B-N 30735 — 1 — Units : VAC Int16 System Input RMS Current Phase B 30736 — 1 — Units : A AC Int16 System Input RMS C-A 30737 — 1 — Units : VAC Int16 System Input RMS C-N 30738 — 1 — Units : VAC Int16 System Input RMS Current Phase C 30739 — 1 — Units : A AC Int16 Energy Consumption 30740 — 2 — Units : kWH Int32 Instantaneous Power 30742 — 2 — Units : W Int32 Output Power Factor 30744 — 1 — Int16 39998 49998 2 — Secs since Epoch(UTC) Power Measurement 2 Time System Date and Time If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Table 3-11 Extra notes key to Table 3-10 Number Description 1 This point is supported on iCOM Controller Version 2.02.xxx 2 This point is supported on iCOM Controller Version 2.03.xxx 97 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-12 Liebert HPC™ (Chiller)—Glossary Data Label Data Description Actual Supply Fluid Temp Set Point The actual set point value being used for the desired fluid temperature at the outlet of the unit. All Pumps Loss of Flow System is shut down due to loss of flow in all available pumps. Ambient Air Temperature Sensor Issue The ambient air temperature sensor is disconnected or the signal is out of range. Ambient Air Temperature Ambient air temperature. Compressor Capacity Control State Compressor capacity control state. When 'ON', the cooling capacity of the compressor has been reduced. Compressor Capacity Normal Compressor has returned to normal load capacity. Compressor Capacity Reduced Compressor capacity has been reduced. Compressor Contactor Issue Compressor contactor is not closing during compressor startup or is not opening during compressor shutdown. Compressor Economizer Utilization Present compressor economizer utilization expressed as a percentage of the maximum. Compressor Head Pressure Compressor head pressure. Compressor High Head Pressure Compressor is shut down due to high head pressure. Compressor Hours Exceeded [Compressor Hours] has exceeded [Compressor Hours Threshold]. Compressor Hours Threshold Threshold value used in the [Compressor Hours Exceeded] event. Compressor Hours Operating hours for compressor since last reset of this value. Compressor Loss of Differential Pressure Compressor is shut down due to low differential pressure. Compressor Low Oil Pressure Compressor low oil pressure. Compressor Low Suction Pressure Compressor is shut down due to low suction pressure. Compressor Not Stopping Compressor commanded to stop, but continues to run. Compressor Shut Down - Ambient Air Low Temp Limit When the temperature of ambient air falls below this lower threshold, the compressor will be shut off. Correct condensing pressure cannot be achieved when temperature is too low. Compressor State Compressor operational state. Compressor Superheat Over Threshold Compressor discharge refrigerant superheat temperature has exceeded an upper threshold. Compressor Thermal Overload Compressor is shut down due to thermal overload. Compressor Utilization Present compressor utilization expressed as a percentage of the maximum rated capacity. Condenser Adiabatic Cooling Utilization Present adiabatic cooling utilization expressed as a percentage of the maximum. Condenser Fan Issue Condenser fan is not operating within its operational parameters. Condenser Fan Speed Condenser fan speed expressed as a percentage of the maximum rated speed. Condenser Inlet Water Temperature For water cooled condensers, the temperature of the water entering the heat exchanger, before cooling the refrigerant. Condenser Max Fan Speed Override Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition. Condenser Outlet Water Temperature For water cooled condensers, the temperature of the water exiting the heat exchanger, after cooling the refrigerant. Customer Input 1 Customer input 1. Customer Input 2 Customer input 2. Customer Input 3 Customer input 3. Customer Input 4 Customer input 4. EEV Unspecified General Event One or more unspecified electronic expansion valve events active. See local unit display for further details. Energy Consumption Energy consumption since the last reset of this value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 98 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-12 Liebert HPC™ (Chiller)—Glossary (continued) Data Label Data Description Evaporator Fluid Freeze - Auto Reset Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down, but will restart when the temperature rises above the threshold. Evaporator Fluid Freeze - Manual Reset Required Evaporator outlet fluid temperature has dropped below the freeze threshold. Evaporator has been shut down and requires a manual reset. Evaporator Inlet Temp Sensor Issue The evaporator inlet temperature sensor is disconnected or the signal is out of range. Evaporator Return Fluid Over Temp Alarm Threshold Alarm threshold value used in the [Evaporator Return Fluid Over Temp] event. Evaporator Return Fluid Over Temp Warning Threshold Warning threshold value used in the [Evaporator Return Fluid Over Temp] event. Evaporator Return Fluid Over Temp [Evaporator Return Fluid Temperature] has exceeded a threshold. The event is deactivated when the temperature drops below the threshold. Evaporator Return Fluid Temperature Fluid temperature measured at the inlet of the evaporator. Evaporator Return Fluid Under Temp Alarm Threshold Alarm threshold value used in the [Evaporator Return Fluid Under Temp] event. Evaporator Return Fluid Under Temp Warning Threshold Warning threshold value used in the [Evaporator Return Fluid Under Temp] event. Evaporator Return Fluid Under Temp [Evaporator Return Fluid Temperature] has dropped below a threshold. The event is deactivated when the temperature rises above the threshold. Fluid Cooling Proportional Band Temperature control band above [Actual Supply Fluid Temp Set Point]. If [Return Fluid Temperature] is within this band, fluid cooling operations are proportionally controlled. Fluid Pressure Fluid pressure. This is the pressure within a closed water/glycol circuit. Free Cooling External Temperature Delta Minimum temperature delta required between return fluid and external ambient air temperatures in order to enable free cooling. Free Cooling Status Free cooling status. Free Cooling Utilization Present free cooling utilization expressed as a percentage of the maximum. Free Cooling Valve Hours Exceeded [Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]. Free Cooling Valve Hours Threshold Threshold value used in the [Free Cooling Valve Hours Exceeded] event. Free Cooling Valve Hours Operating hours for free cooling valve since last reset of this value. Free Cooling Valve Open Position Free cooling valve open position. Humidifier Control Board Not Detected Humidifier control board is required to be connected, but no signal is detected. Instantaneous Power Total electrical power currently being consumed. Low Condenser Refrigerant Pressure Refrigerant pressure in condenser coil is too low. Low Fluid Pressure [Fluid Pressure] has dropped below a specified threshold. Master Unit Communication Lost Communication with master unit has been lost. Modbus Power Meter Communication Lost Communication with Modbus power meter has been lost. Output Power Factor Total power factor, real power/apparent power for all phases combined Pump 1 Loss of Flow Loss of flow is detected in pump 1. This condition occurs when no flow is detected through the flow switch. Pump 1 State Pump 1 operational state. Pump 2 Loss of Flow Loss of flow is detected in pump 2. This condition occurs when no flow is detected through the flow switch. 99 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-12 Liebert HPC™ (Chiller)—Glossary (continued) Data Label Data Description Pump 2 State Pump 2 operational state. Pump Hours Exceeded [Pump Hours] has exceeded [Pump Hours Threshold]. Pump Hours Threshold Threshold value used in the [Pump Hours Exceeded] event. Pump Hours Operating hours for pump since last reset of this value. RAM Battery Issue RAM or RAM backup battery is not operating correctly. Reheat Utilization Present reheating utilization expressed as a percentage of the maximum rated capacity. Return Fluid Temp Sensor Issue The return fluid temperature sensor is disconnected or the signal is out of range. Return Fluid Temperature Fluid temperature measured at the inlet of the unit. Server Class The general classification for this system Standby Units The number of standby units. Subgroup Event Occurred During Communication Loss While subgroup unit communication was lost, an event occurred on the subgroup unit. Please check subgroup unit event log. Supply Brine Temp Set Point Desired brine fluid temperature at the outlet of the unit. Supply Fluid Over Temp Alarm Threshold Threshold value used to generate a [Supply Fluid Over Temp] alarm. Supply Fluid Over Temp [Supply Fluid Temperature] has exceeded a specified threshold. Supply Fluid Temp Sensor Issue The supply fluid temperature sensor is disconnected or the signal is out of range. Supply Fluid Temp Set Point 1 Set point 1 of desired fluid temperature at the outlet of the unit. Supply Fluid Temp Set Point 2 Set point 2 of desired fluid temperature at the outlet of the unit. Supply Fluid Temperature Fluid temperature measured at the outlet of the unit. Supply Fluid Under Temp Alarm Threshold Threshold value used to generate a [Supply Fluid Under Temp] alarm. Supply Fluid Under Temp [Supply Fluid Temperature] has dropped below a specified threshold. Supply Heated Water Temp Set Point Desired heated water temperature at the outlet of the unit. Supply Refrigerant Temp Sensor Issue The supply refrigeramt temperature sensor is disconnected or the signal is out of range. System Control Mode System control mode. System Date and Time The system date and time System Event Acknowledge/Reset Reset and/or acknowledge all events. System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System On/Off Control Turn system functionality on or off. System Operating State Reason The reason the system is in the current operating state. System Operating State Current operating state of the system. System Status The operating status for the system Unit Code Missing Unit code has not been entered and saved. Unit Off Unit was turned off. Unit On Unit was turned on. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 100 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-12 Liebert HPC™ (Chiller)—Glossary (continued) Data Label Data Description Unit Shutdown Unspecified General Event One or more unspecified unit shutdown events active. See local unit display for further details. Unspecified General Event One or more unspecified events active. See local unit display for further details. 101 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-13 Liebert XDC™—Status and Coil Controller Liebert iCOM® v4 Status Coil Number of Bits Scale Notes / Units Pump 1 Loss of Flow 10001 — 1 — Active on Alarm Pump 2 Loss of Flow 10002 — 1 — Active on Alarm Data Description Fan Issue 10003 — 1 — Active on Alarm System Condensation Detected 10004 — 1 — Active on Alarm Customer Input 1 10005 — 1 — Active on Alarm Supply Refrigerant Over Temp 10006 — 1 — Active on Alarm Supply Refrigerant Under Temp 10007 — 1 — Active on Alarm Supply Refrigerant Temp Sensor Issue 10008 — 1 — Active on Alarm Ext Air Sensor A Over Temperature 10009 — 1 — Active on Alarm Ext Air Sensor A Under Temperature 10010 — 1 — Active on Alarm Ext Air Sensor A Issue 10011 — 1 — Active on Alarm Ext Air Sensor B Over Temperature 10012 — 1 — Active on Alarm Ext Air Sensor B Under Temperature 10013 — 1 — Active on Alarm Ext Air Sensor B Issue 10014 — 1 — Active on Alarm Ext Dew Point Over Temperature 10015 — 1 — Active on Alarm Pump Short Cycle 10016 — 1 — Active on Alarm Compressor 1A High Head Pressure 10017 — 1 — Active on Alarm Compressor 1B High Head Pressure 10018 — 1 — Active on Alarm Compressor 2A High Head Pressure 10019 — 1 — Active on Alarm Compressor 2B High Head Pressure 10020 — 1 — Active on Alarm Compressor 1A Short Cycle 10021 — 1 — Active on Alarm Compressor 1B Short Cycle 10022 — 1 — Active on Alarm Compressor 2A Short Cycle 10023 — 1 — Active on Alarm Compressor 2B Short Cycle 10024 — 1 — Active on Alarm Circuit 1 Low Suction Pressure 10025 — 1 — Active on Alarm Circuit 2 Low Suction Pressure 10026 — 1 — Active on Alarm Shutdown - Loss Of Power 10027 — 1 — Active on Alarm Smoke Detected 10028 — 1 — Active on Alarm Water Under Floor 10029 — 1 — Active on Alarm Service Required 10030 — 1 — Active on Alarm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 102 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-14 Liebert XDC™—Input and Holding Controller Liebert iCOM® v4 Input Register Holding Register # of Reg. Scale Pump 1 State 30385 — 1 — 0 = Off / 1 = On Pump 2 State 30386 — 1 — 0 = Off / 1 = On Supply Refrigerant Temperature 30387 — 1 10 deg C Supply Refrigerant Temperature 30388 — 1 10 deg F System Operating State 30389 — 1 — Ext Air Sensor A Temperature 30390 — 1 10 deg C Ext Air Sensor A Temperature 30391 — 1 10 deg F Ext Air Sensor A Humidity 30392 — 1 10 % RH Ext Air Sensor A Dew Point Temp 30393 — 1 10 deg C Ext Air Sensor A Dew Point Temp 30394 — 1 10 deg F Ext Air Sensor B Temperature 30395 — 1 10 deg C Ext Air Sensor B Temperature 30396 — 1 10 deg F Ext Air Sensor B Humidity 30397 — 1 10 % RH Ext Air Sensor B Dew Point Temp 30398 — 1 10 deg C Ext Air Sensor B Dew Point Temp 30399 — 1 10 deg F Dew Point Temperature 30400 — 1 10 deg C Dew Point Temperature 30401 — 1 10 deg F Minimum Room Temperature Set Point 30402 40402 1 — deg C Minimum Room Temperature Set Point 30403 40403 1 — deg F Ext Air Over Temp Threshold 30404 40404 1 — deg C Ext Air Over Temp Threshold 30405 40405 1 — deg F Ext Air Under Temp Threshold 30406 40406 1 — deg C Ext Air Under Temp Threshold 30407 40407 1 — deg F Ext Dew Point Over Temp Threshold 30408 40408 1 — deg C Ext Dew Point Over Temp Threshold 30409 40409 1 — deg F Supply Refrig Over Temp Threshold 30410 40410 1 — deg C Supply Refrig Over Temp Threshold 30411 40411 1 — deg F Hot Gas Valve 1 Open Position 30412 — 1 100 % Hot Gas Valve 2 Open Position 30413 — 1 100 % Hot Gas Solenoid Valve 1 Position 30414 — 1 — 0 = Closed 1 = Open Hot Gas Solenoid Valve 2 Position 30415 — 1 — 0 = Closed 1 = Open Data Description Notes / Units 0 = Off / 1 = On 2 = Standby Compressor 1A State 30416 — 1 — 0 = Off / 1 = On Compressor 1B State 30417 — 1 — 0 = Off / 1 = On Compressor 2A State 30418 — 1 — 0 = Off / 1 = On Compressor 2B State 30419 — 1 — 0 = Off / 1 = On Calculated Next Maintenance Month 30420 — 1 — — Calculated Next Maintenance Year 30421 — 1 — — System Status 30422 — 1 — 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 103 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-14 Liebert XDC™—Input and Holding (continued) Controller Liebert iCOM® v4 Data Description System Control Mode Input Register Holding Register # of Reg. Scale 30423 — 1 — Notes / Units 0 = Internal (Auto) 1 = External (Manual) Maintenance Ramp 30424 — 1 — % Auto Restart Delay 30425 40425 1 — sec System On/Off Control 30426 40426 1 — 0 = Off / 1 = On — 40427 1 — 2 = Reset 4 = Acknowledge System Event Acknowledge/Reset If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 104 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-15 Liebert XDP™—Status and Coil Controller Liebert iCOM® v4 Status Coil Number of Bits Notes Pump 1 Loss of Flow 10001 — 1 Active on Alarm Pump 2 Loss of Flow 10002 — 1 Active on Alarm Pump Short Cycle 10020 — 1 Active on Alarm Data Label Pumps System Events Fan Issue 10003 — 1 Active on Alarm System Condensation Detected 10004 — 1 Active on Alarm Customer Input 1 10005 — 1 Active on Alarm Shutdown - Loss Of Power 10019 — 1 Active on Alarm Water Under Floor 10021 — 1 Active on Alarm Smoke Detected 10022 — 1 Active on Alarm Service Required 10023 — 1 Active on Alarm Unit Communication Lost 10262 — 1 Active on Alarm RAM Battery Issue 10263 — 1 Active on Alarm Master Unit Communication Lost 10264 — 1 Active on Alarm Remote Shutdown 10265 — 1 Active on Alarm Unit Code Missing 10266 — 1 Active on Alarm Supply Chilled Water Over Temp 10006 — 1 Active on Alarm Supply Chilled Water Temp Sensor Issue 10007 — 1 Active on Alarm Chilled Water Control Valve Position 10018 — 1 Active on Alarm 10008 — 1 Active on Alarm Chilled Water Refrigerant Supply Refrigerant Over Temp Supply Refrigerant Under Temp 10009 — 1 Active on Alarm Supply Refrigerant Temp Sensor Issue 10010 — 1 Active on Alarm Ext Air Sensor A Over Temperature 10011 — 1 Active on Alarm Ext Air Sensor A Under Temperature 10012 — 1 Active on Alarm Ext Air Sensor A Issue 10013 — 1 Active on Alarm Ext Air Sensor B Over Temperature 10014 — 1 Active on Alarm Ext Air Sensor B Under Temperature 10015 — 1 Active on Alarm External Air Ext Air Sensor B Issue 10016 — 1 Active on Alarm Ext Dew Point Over Temperature 10017 — 1 Active on Alarm 10030 — 1 Active on Alarm 10036 — 1 Active on Alarm 10042 — 1 Active on Alarm Pump Hours 1 Pump Hours Exceeded Pump Hours 2 Pump Hours Exceeded XD System 1 Ext System Condensation Detected — Ext Fan Issue 10043 — 1 Active on Alarm Sensor Issue 10044 — 1 Active on Alarm Ext Remote Shutdown 10045 — 1 Active on Alarm Hot Aisle Temp Out of Range 10046 — 1 Active on Alarm Cold Aisle Temp Out of Range 10047 — 1 Active on Alarm 105 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-15 Liebert XDP™—Status and Coil (continued) Controller Liebert iCOM® v4 Status Coil Number of Bits Notes Ext System Condensation Detected 10053 — 1 Active on Alarm Ext Fan Issue 10054 — 1 Active on Alarm Data Label XD System 2 Sensor Issue 10055 — 1 Active on Alarm Ext Remote Shutdown 10056 — 1 Active on Alarm Hot Aisle Temp Out of Range 10057 — 1 Active on Alarm Cold Aisle Temp Out of Range 10058 — 1 Active on Alarm 10251 — 1 Active on Alarm XD System 20 Ext System Condensation Detected Ext Fan Issue 10252 — 1 Active on Alarm Sensor Issue 10253 — 1 Active on Alarm Ext Remote Shutdown 10254 — 1 Active on Alarm Hot Aisle Temp Out of Range 10255 — 1 Active on Alarm Cold Aisle Temp Out of Range 10256 — 1 Active on Alarm Messages Unit On 10272 — 1 Active on Alarm Unit Off 10273 — 1 Active on Alarm Unit Standby 10274 — 1 Active on Alarm Unit Partial Shutdown 10275 — 1 Active on Alarm Unit Shutdown 10276 — 1 Active on Alarm Maintenance Due 10277 — 1 Active on Alarm Maintenance Completed 10278 — 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 106 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding Controller Liebert iCOM® v4 Input Holding Pump 1 State 30385 — 1 — 0 = off 1 = on Pump 2 State 30386 — 1 — 0 = off 1 = on Supply Refrigerant Temperature 30387 — 1 10 Units : deg C Supply Refrigerant Temperature 30388 — 1 10 Units : deg F Supply Refrig Over Temp Threshold 30411 40411 1 10 Units : deg C Supply Refrig Over Temp Threshold 30412 40412 1 10 Units : deg F Supply Chilled Water Temperature 30389 — 1 10 Units : deg C Supply Chilled Water Temperature 30390 — 1 10 Units : deg F Supply Chilled Water Over Temp Threshold 30413 40413 1 10 Units : deg C Supply Chilled Water Over Temp Threshold 30414 40414 1 10 Units : deg F Chilled Water Valve Open Position 31710 — 1 — — Data Label # of Reg Scale Notes/Units Pumps Refrigerant Chilled Water System Information System Status 30391 — 1 — 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation System Operating State 30392 — 1 — 0 = off 1 = on 2 = standby Auto Restart Delay 30417 40417 1 — Units : sec System Control Mode 30418 — 1 — 0 = Internal (Auto) 1 = External (Manual) Maintenance Ramp 30419 — 1 — Units : % Calculated Next Maintenance Month 30420 — 1 — Calculated Next Maintenance Year 30421 — 1 — System On/Off Control 30422 40422 1 — 0 = off 1 = on 31704 — 1 — 0 = Reason Unknown 1 = Network Display 2 = Alarm 3 = Schedule 4 = Remote System 5 = External Input 6 = Local Display Ext Air Sensor A Temperature 30393 — 1 10 Units : deg C Ext Air Sensor A Temperature 30394 — 1 10 Units : deg F Ext Air Sensor A Humidity 30395 — 1 10 Units : % RH Ext Air Sensor A Dew Point Temp 30396 — 1 10 Units : deg C System Operating State Reason External Air Ext Air Sensor A Dew Point Temp 30397 — 1 10 Units : deg F Ext Air Sensor B Temperature 30398 — 1 10 Units : deg C Ext Air Sensor B Temperature 30399 — 1 10 Units : deg F Ext Air Sensor B Humidity 30400 — 1 10 Units : % RH If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 107 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Data Label Input Holding Ext Air Sensor B Dew Point Temp 30401 — # of Reg Scale 1 10 Notes/Units Units : deg C Ext Air Sensor B Dew Point Temp 30402 — 1 10 Units : deg F Minimum Room Temperature Set Point 30403 40403 1 10 Units : deg C Minimum Room Temperature Set Point 30404 40404 1 10 Units : deg F Ext Air Over Temp Threshold 30405 40405 1 10 Units : deg C Ext Air Over Temp Threshold 30406 40406 1 10 Units : deg F Ext Air Under Temp Threshold 30407 40407 1 10 Units : deg C Ext Air Under Temp Threshold 30408 40408 1 10 Units : deg F Ext Dew Point Over Temp Threshold 30409 40409 1 10 Units : deg C Ext Dew Point Over Temp Threshold 30410 40410 1 10 Units : deg F Dew Point Temperature 30415 — 1 10 Units : deg C Dew Point Temperature 30416 — 1 10 Units : deg F 39998 49998 2 — Secs since Epoch (UTC) Time System Date and Time Pump Hours 1 Pump Hours 30430 40430 1 — Units : hr Pump Hours Threshold 30431 40431 1 — Units : hr Pump Hours 30437 40437 1 — Units : hr Pump Hours Threshold 30438 40438 1 — Units : hr Communication Status 30444 — 1 — 0 = Connected 1 = Not Connected Fan On/Off Control 30445 40445 1 — 0 = off 1 = on Primary Fan Group State 30446 — 1 — 0 = off 1 = on 2 = economy Fan Button Control 30447 40447 1 — 0 = enabled 1 = disabled Visual ID Control 30448 40448 1 — 0 = disabled 1 = enabled Cooling Capacity 30449 — 1 — Units : % Cooling Capacity 30450 — 1 — Units : kW Pump Hours 2 XD System 1 Ext System Condensation Detected - Event Control 30451 40451 1 — 0 = disabled 1 = enabled Ext System Condensation Detected - Event Type 30452 40452 1 — 0 = Message 1 = Warning 2 = Alarm Ext Fan Issue - Event Control 30453 40453 1 — 0 = disabled 1 = enabled Ext Fan Issue - Event Type 30454 40454 1 — 0 = Message 1 = Warning 2 = Alarm Sensor Issue - Event Control 30455 40455 1 — 0 = disabled 1 = enabled Sensor Issue - Event Type 30456 40456 1 — 0 = Message 1 = Warning 2 = Alarm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 108 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Data Label Input Holding # of Reg Scale Notes/Units Ext Remote Shutdown - Event Control 30457 40457 1 — 0 = disabled 1 = enabled Ext Remote Shutdown - Event Type 30458 40458 1 — 0 = Message 1 = Warning 2 = Alarm Hot Aisle Over Temp Threshold 30459 40459 1 — Units : deg C Hot Aisle Over Temp Threshold 30460 40460 1 — Units : deg F Hot Aisle Under Temp Threshold 30461 40461 1 — Units : deg C Hot Aisle Under Temp Threshold 30462 40462 1 — Units : deg F Cold Aisle Over Temp Threshold 30463 40463 1 — Units : deg C Cold Aisle Over Temp Threshold 30464 40464 1 — Units : deg F Cold Aisle Under Temp Threshold 30465 40465 1 — Units : deg C Cold Aisle Under Temp Threshold 30466 40466 1 — Units : deg F Communication Status 30472 — 1 — 0 = Connected 1 = Not Connected Fan On/Off Control 30473 40473 1 — 0 = off 1 = on Primary Fan Group State 30474 — 1 — 0 = off 1 = on 2 = economy Fan Button Control 30475 40475 1 — 0 = enabled 1 = disabled Visual ID Control 30476 40476 1 — 0 = disabled 1 = enabled XD System 2 Cooling Capacity 30477 — 1 — Units : % Cooling Capacity 30478 — 1 — Units : kW Ext System Condensation Detected - Event Control 30479 40479 1 — 0 = disabled 1 = enabled Ext System Condensation Detected - Event Type 30480 40480 1 — 0 = Message 1 = Warning 2 = Alarm Ext Fan Issue - Event Control 30481 40481 1 — 0 = disabled 1 = enabled Ext Fan Issue - Event Type 30482 40482 1 — 0 = Message 1 = Warning 2 = Alarm Sensor Issue - Event Control 30483 40483 1 — 0 = disabled 1 = enabled Sensor Issue - Event Type 30484 40484 1 — 0 = Message 1 = Warning 2 = Alarm Ext Remote Shutdown - Event Control 30485 40485 1 — 0 = disabled 1 = enabled Ext Remote Shutdown - Event Type 30486 40486 1 — 0 = Message 1 = Warning 2 = Alarm Hot Aisle Over Temp Threshold 30487 40487 1 — Units : deg C Hot Aisle Over Temp Threshold 30488 40488 1 — Units : deg F Hot Aisle Under Temp Threshold 30489 40489 1 — Units : deg C If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 109 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Data Label Input Holding # of Reg Scale Notes/Units Hot Aisle Under Temp Threshold 30490 40490 1 — Units : deg F Cold Aisle Over Temp Threshold 30491 40491 1 — Units : deg C Cold Aisle Over Temp Threshold 30492 40492 1 — Units : deg F Cold Aisle Under Temp Threshold 30493 40493 1 — Units : deg C Cold Aisle Under Temp Threshold 30494 40494 1 — Units : deg F Communication Status 30976 — 1 — 0 = Connected 1 = Not Connected Fan On/Off Control 30977 40977 1 — 0 = off 1 = on Primary Fan Group State 30978 — 1 — 0 = off 1 = on 2 = economy Fan Button Control 30979 40979 1 — 0 = enabled 1 = disabled Visual ID Control 30980 40980 1 — 0 = disabled 1 = enabled XD System 20 Cooling Capacity 30981 — 1 — Units : % Cooling Capacity 30982 — 1 — Units : kW Ext System Condensation Detected - Event Control 30983 40983 1 — 0 = disabled 1 = enabled Ext System Condensation Detected - Event Type 30984 40984 1 — 0 = Message 1 = Warning 2 = Alarm Ext Fan Issue - Event Control 30985 40985 1 — 0 = disabled 1 = enabled Ext Fan Issue - Event Type 30986 40986 1 — 0 = Message 1 = Warning 2 = Alarm Sensor Issue - Event Control 30987 40987 1 — 0 = disabled 1 = enabled Sensor Issue - Event Type 30988 40988 1 — 0 = Message 1 = Warning 2 = Alarm Ext Remote Shutdown - Event Control 30989 40989 1 — 0 = disabled 1 = enabled Ext Remote Shutdown - Event Type 30990 40990 1 — 0 = Message 1 = Warning 2 = Alarm Hot Aisle Over Temp Threshold 30991 40991 1 — Units : deg C Hot Aisle Over Temp Threshold 30992 40992 1 — Units : deg F Hot Aisle Under Temp Threshold 30993 40993 1 — Units : deg C Hot Aisle Under Temp Threshold 30994 40994 1 — Units : deg F Cold Aisle Over Temp Threshold 30995 40995 1 — Units : deg C Cold Aisle Over Temp Threshold 30996 40996 1 — Units : deg F Cold Aisle Under Temp Threshold 30997 40997 1 — Units : deg C Cold Aisle Under Temp Threshold 30998 40998 1 — Units : deg F Remote Sensor Temperature 31004 — 1 10 Units : deg C Remote Sensor Temperature 31005 — 1 10 Units : deg F XD System 1 Temperature Sensor 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 110 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Input Holding Remote Sensor Temperature 31011 — 1 10 Units : deg C Remote Sensor Temperature 31012 — 1 10 Units : deg F Remote Sensor Temperature 31025 — 1 10 Units : deg C Remote Sensor Temperature 31026 — 1 10 Units : deg F Fan State 31032 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31033 41033 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31039 — 1 10 Units : deg C Remote Sensor Temperature 31040 — 1 10 Units : deg F Remote Sensor Temperature 31046 — 1 10 Units : deg C Remote Sensor Temperature 31047 — 1 10 Units : deg F Remote Sensor Temperature 31060 — 1 10 Units : deg C Remote Sensor Temperature 31061 — 1 10 Units : deg F Fan State 31067 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31068 41068 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31074 — 1 10 Units : deg C Remote Sensor Temperature 31075 — 1 10 Units : deg F Remote Sensor Temperature 31081 — 1 10 Units : deg C Remote Sensor Temperature 31082 — 1 10 Units : deg F Remote Sensor Temperature 31095 — 1 10 Units : deg C Remote Sensor Temperature 31096 — 1 10 Units : deg F Fan State 31102 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31103 41103 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31109 — 1 10 Units : deg C Remote Sensor Temperature 31110 — 1 10 Units : deg F Data Label # of Reg Scale Notes/Units XD System 1 Temperature Sensor 2 XD System 1 Temperature Sensor 4 XD System 1 Secondary Fans XD System 2 Temperature Sensor 1 XD System 2 Temperature Sensor 2 XD System 2 Temperature Sensor 4 XD System 2 Secondary Fans XD System 3 Temperature Sensor 1 XD System 3 Temperature Sensor 2 XD System 3 Temperature Sensor 4 XD System 3 Secondary Fans XD System 4 Temperature Sensor 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 111 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Input Holding Remote Sensor Temperature 31116 — 1 10 Units : deg C Remote Sensor Temperature 31117 — 1 10 Units : deg F Remote Sensor Temperature 31130 — 1 10 Units : deg C Remote Sensor Temperature 31131 — 1 10 Units : deg F Fan State 31137 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31138 41138 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31144 — 1 10 Units : deg C Remote Sensor Temperature 31145 — 1 10 Units : deg F Data Label # of Reg Scale Notes/Units XD System 4 Temperature Sensor 2 XD System 4 Temperature Sensor 4 XD System 4 Secondary Fans XD System 5 Temperature Sensor 1 XD System 5 Temperature Sensor 2 Remote Sensor Temperature 31151 — 1 10 Units : deg C Remote Sensor Temperature 31152 — 1 10 Units : deg F Remote Sensor Temperature 31165 — 1 10 Units : deg C Remote Sensor Temperature 31166 — 1 10 Units : deg F Fan State 31172 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31173 41173 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31179 — 1 10 Units : deg C Remote Sensor Temperature 31180 — 1 10 Units : deg F XD System 5 Temperature Sensor 4 XD System 5 Secondary Fans XD System 6 Temperature Sensor 1 XD System 6 Temperature Sensor 2 Remote Sensor Temperature 31186 — 1 10 Units : deg C Remote Sensor Temperature 31187 — 1 10 Units : deg F Remote Sensor Temperature 31200 — 1 10 Units : deg C Remote Sensor Temperature 31201 — 1 10 Units : deg F Fan State 31207 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31208 41208 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31214 — 1 10 Units : deg C Remote Sensor Temperature 31215 — 1 10 Units : deg F XD System 6 Temperature Sensor 4 XD System 6 Secondary Fans XD System 7 Temperature Sensor 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 112 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Input Holding Remote Sensor Temperature 31221 — 1 10 Units : deg C Remote Sensor Temperature 31222 — 1 10 Units : deg F Remote Sensor Temperature 31235 — 1 10 Units : deg C Remote Sensor Temperature 31236 — 1 10 Units : deg F Fan State 31242 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31243 41243 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31249 — 1 10 Units : deg C Remote Sensor Temperature 31250 — 1 10 Units : deg F Remote Sensor Temperature 31256 — 1 10 Units : deg C Remote Sensor Temperature 31257 — 1 10 Units : deg F Remote Sensor Temperature 31270 — 1 10 Units : deg C Remote Sensor Temperature 31271 — 1 10 Units : deg F Fan State 31277 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31278 41278 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31284 — 1 10 Units : deg C Remote Sensor Temperature 31285 — 1 10 Units : deg F Remote Sensor Temperature 31291 — 1 10 Units : deg C Remote Sensor Temperature 31292 — 1 10 Units : deg F Remote Sensor Temperature 31305 — 1 10 Units : deg C Remote Sensor Temperature 31306 — 1 10 Units : deg F Fan State 31312 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31313 41313 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31319 — 1 10 Units : deg C Remote Sensor Temperature 31320 — 1 10 Units : deg F Data Label # of Reg Scale Notes/Units XD System 7 Temperature Sensor 2 XD System 7 Temperature Sensor 4 XD System 7 Secondary Fans XD System 8 Temperature Sensor 1 XD System 8 Temperature Sensor 2 XD System 8 Temperature Sensor 4 XD System 8 Secondary Fans XD System 9 Temperature Sensor 1 XD System 9 Temperature Sensor 2 XD System 9 Temperature Sensor 4 XD System 9 Secondary Fans XD System 10 Temperature Sensor 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 113 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Input Holding Remote Sensor Temperature 31326 — 1 10 Units : deg C Remote Sensor Temperature 31327 — 1 10 Units : deg F Remote Sensor Temperature 31340 — 1 10 Units : deg C Remote Sensor Temperature 31341 — 1 10 Units : deg F Fan State 31347 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31348 41348 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31354 — 1 10 Units : deg C Remote Sensor Temperature 31355 — 1 10 Units : deg F Remote Sensor Temperature 31361 — 1 10 Units : deg C Remote Sensor Temperature 31362 — 1 10 Units : deg F Remote Sensor Temperature 31375 — 1 10 Units : deg C Remote Sensor Temperature 31376 — 1 10 Units : deg F Fan State 31382 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31383 41383 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31389 — 1 10 Units : deg C Remote Sensor Temperature 31390 — 1 10 Units : deg F Remote Sensor Temperature 31396 — 1 10 Units : deg C Remote Sensor Temperature 31397 — 1 10 Units : deg F Remote Sensor Temperature 31410 — 1 10 Units : deg C Remote Sensor Temperature 31411 — 1 10 Units : deg F Fan State 31417 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31418 41418 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31424 — 1 10 Units : deg C Remote Sensor Temperature 31425 — 1 10 Units : deg F Data Label # of Reg Scale Notes/Units XD System 10 Temperature Sensor 2 XD System 10 Temperature Sensor 4 XD System 10 Secondary Fans XD System 11 Temperature Sensor 1 XD System 11 Temperature Sensor 2 XD System 11 Temperature Sensor 4 XD System 11 Secondary Fans XD System 12 Temperature Sensor 1 XD System 12 Temperature Sensor 2 XD System 12 Temperature Sensor 4 XD System 12 Secondary Fans XD System 13 Temperature Sensor 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 114 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Input Holding Remote Sensor Temperature 31431 — 1 10 Units : deg C Remote Sensor Temperature 31432 — 1 10 Units : deg F Remote Sensor Temperature 31445 — 1 10 Units : deg C Remote Sensor Temperature 31446 — 1 10 Units : deg F Fan State 31452 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31453 41453 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31459 — 1 10 Units : deg C Remote Sensor Temperature 31460 — 1 10 Units : deg F Remote Sensor Temperature 31466 — 1 10 Units : deg C Remote Sensor Temperature 31467 — 1 10 Units : deg F Remote Sensor Temperature 31480 — 1 10 Units : deg C Remote Sensor Temperature 31481 — 1 10 Units : deg F Fan State 31487 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31488 41488 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31494 — 1 10 Units : deg C Remote Sensor Temperature 31495 — 1 10 Units : deg F Remote Sensor Temperature 31501 — 1 10 Units : deg C Remote Sensor Temperature 31502 — 1 10 Units : deg F Remote Sensor Temperature 31515 — 1 10 Units : deg C Remote Sensor Temperature 31516 — 1 10 Units : deg F Fan State 31522 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31523 41523 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31529 — 1 10 Units : deg C Remote Sensor Temperature 31530 — 1 10 Units : deg F Data Label # of Reg Scale Notes/Units XD System 13 Temperature Sensor 2 XD System 13 Temperature Sensor 4 XD System 13 Secondary Fans XD System 14 Temperature Sensor 1 XD System 14 Temperature Sensor 2 XD System 14 Temperature Sensor 4 XD System 14 Secondary Fans XD System 15 Temperature Sensor 1 XD System 15 Temperature Sensor 2 XD System 15 Temperature Sensor 4 XD System 15 Secondary Fans XD System 16 Temperature Sensor 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 115 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Input Holding Remote Sensor Temperature 31536 — 1 10 Units : deg C Remote Sensor Temperature 31537 — 1 10 Units : deg F Remote Sensor Temperature 31550 — — 10 Units : deg C Remote Sensor Temperature 31551 — — 10 Units : deg F Fan State 31557 — — — 0 = off 1 = on 2 = economy Fan Economy Mode 31558 41558 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31564 — 1 10 Units : deg C Remote Sensor Temperature 31565 — 1 10 Units : deg F Remote Sensor Temperature 31571 — 1 10 Units : deg C Remote Sensor Temperature 31572 — 1 10 Units : deg F Remote Sensor Temperature 31585 — 1 10 Units : deg C Remote Sensor Temperature 31586 — 1 10 Units : deg F Fan State 31592 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31593 41593 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31599 — 1 10 Units : deg C Remote Sensor Temperature 31600 — 1 10 Units : deg F Data Label # of Reg Scale Notes/Units XD System 16 Temperature Sensor 2 XD System 16 Temperature Sensor 4 XD System 16 Secondary Fans XD System 17 Temperature Sensor 1 XD System 17 Temperature Sensor 2 XD System 17 Temperature Sensor 4 XD System 17 Secondary Fans XD System 18 Temperature Sensor 1 XD System 18 Temperature Sensor 2 — Remote Sensor Temperature 31606 — 1 10 Units : deg C Remote Sensor Temperature 31607 — 1 10 Units : deg F Remote Sensor Temperature 31620 — 1 10 Units : deg C Remote Sensor Temperature 31621 — 1 10 Units : deg F Fan State 31627 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31628 41628 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31634 — 1 10 Units : deg C Remote Sensor Temperature 31635 — 1 10 Units : deg F XD System 18 Temperature Sensor 4 XD System 18 Secondary Fans XD System 19 Temperature Sensor 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 116 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-16 Liebert XDP™—Input and Holding (continued) Controller Liebert iCOM® v4 Input Holding Remote Sensor Temperature 31641 — 1 10 Units : deg C Remote Sensor Temperature 31642 — 1 10 Units : deg F Remote Sensor Temperature 31655 — 1 10 Units : deg C Remote Sensor Temperature 31656 — 1 10 Units : deg F Fan State 31662 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31663 41663 1 — 0 = disabled 1 = automatic 2 = manual Remote Sensor Temperature 31669 — 1 10 Units : deg C Remote Sensor Temperature 31670 — 1 10 Units : deg F Remote Sensor Temperature 31676 — 1 10 Units : deg C Remote Sensor Temperature 31677 — 1 10 Units : deg F Remote Sensor Temperature 31690 — 1 10 Units : deg C Remote Sensor Temperature 31691 — 1 10 Units : deg F Fan State 31697 — 1 — 0 = off 1 = on 2 = economy Fan Economy Mode 31698 41698 1 — 0 = disabled 1 = automatic 2 = manual Data Label # of Reg Scale Notes/Units XD System 19 Temperature Sensor 2 XD System 19 Temperature Sensor 4 XD System 19 Secondary Fans XD System 20 Temperature Sensor 1 XD System 20 Temperature Sensor 2 XD System 20 Temperature Sensor 4 XD System 20 Secondary Fans If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 117 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-17 Liebert XDP™—Glossary Controller Liebert iCOM® v4 Data Label Data Description Auto Restart Delay If power is lost, the control will delay this amount of time after power is restored before restarting the unit. Calculated Next Maintenance Month Calculated month of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Year]. Calculated Next Maintenance Year Calculated year of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Month]. Chilled Water Control Valve Failure Chilled water valve out of position. Chilled water control valve position does not match expected value. Chilled Water Valve Open Position Chilled water valve open position. Cold Aisle Over Temp Threshold Upper threshold value used in the [Cold Aisle Temp Out of Range] event. Cold Aisle Temp Out of Range The air temperature in the cold aisle is either above [Cold Aisle Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]. Cold Aisle Under Temp Threshold Lower threshold value used in the [Cold Aisle Temp Out of Range] event. Communication Status Communication status of remote device. Cooling Capacity Cooling capacity in use, expressed as a percentage of the maximum rated capacity. Cooling Capacity Cooling capacity in use, expressed in kilowatts. Customer Input 1 Customer input 1. Dew Point Temperature Dew point temperature, using the highest reading from all sensors. Ext Air Over Temp Threshold Threshold value used in the ([Ext Air Sensor A Over Temperature], [Ext Air Sensor B Over Temperature]...) events. Ext Air Sensor A Dew Point Temp Dew point temperature as measured by External Air Sensor A. Ext Air Sensor A Humidity Relative humidity as measured by External Air Sensor A. Ext Air Sensor A Issue The External Air Sensor A is disconnected or the signal is out of range. Ext Air Sensor A Over Temperature [Ext Air Sensor A Temperature] has exceeded [Ext Air Over Temp Threshold]. Ext Air Sensor A Temperature Air temperature as measured by External Air Sensor A. Ext Air Sensor A Under Temperature [Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp Threshold]. Ext Air Sensor B Dew Point Temp Dew point temperature as measured by External Air Sensor B. Ext Air Sensor B Humidity Relative humidity as measured by External Air Sensor B. Ext Air Sensor B Issue The External Air Sensor B is disconnected or the signal is out of range. Ext Air Sensor B Over Temperature [Ext Air Sensor B Temperature] has exceeded [Ext Air Over Temp Threshold]. Ext Air Sensor B Temperature Air temperature as measured by External Air Sensor B. Ext Air Sensor B Under Temperature [Ext Air Sensor B Temperature] has dropped below [Ext Air Under Temp Threshold]. Ext Air Under Temp Threshold Threshold value used in the ([Ext Air Sensor A Under Temperature], [Ext Air Sensor B Under Temperature]...) events. Ext Dew Point Over Temp Threshold Threshold value used in the [Ext Dew Point Over Temperature] event. Ext Dew Point Over Temperature At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold]. Ext Fan Issue - Event Control Enable/disable the activation of the [Ext Fan Issue] event. If set to “disabled,” the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Fan Issue - Event Type The event type for the [Ext Fan Issue] event. Ext Fan Issue One or more fans are not operating within their operational parameters. Enable/disable the activation of the [Remote Shutdown] event. If set to “disabled,” the Ext Remote Shutdown - Event Control event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Remote Shutdown - Event Type The event type for the [Remote Shutdown] event. Ext Remote Shutdown Unit is shut down by a remote signal. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 118 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-17 Liebert XDP™—Glossary (continued) Controller Liebert iCOM® v4 Data Label Data Description Ext System Condensation Detected Event Control Enable/disable the activation of the [Ext System Condensation Detected] event. If set to “disabled,” the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext System Condensation Detected Event Type The event type for the [Ext System Condensation Detected] event. Ext System Condensation Detected External system condensation detected. Fan Button Control Enable or disable the buttons from controlling the state of the fans. Fan Economy Mode Mode in which system secondary fans are to be controlled. Fan Issue One or more fans are not operating within their operational parameters. Fan On/Off Control Turn system fans on or off. Fan State Current operational state of a group of fans. Hot Aisle Over Temp Threshold Upper threshold value used in the [Hot Aisle Temp Out of Range] event. Hot Aisle Temp Out of Range The air temperature in the Hot aisle is either above [Hot Aisle Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]. Hot Aisle Under Temp Threshold Lower threshold value used in the [Hot Aisle Temp Out of Range] event. Maintenance Completed Maintenance has been completed on the unit. Maintenance Due The calculated maintenance date has been reached. Maintenance Ramp The ratio of operations performed to the calculated operations available between maintenance intervals. Master Unit Communication Lost Communication with master unit has been lost. Minimum Room Temperature Set Point Minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling. Primary Fan Group State Current operational state of the primary fan group. Pump 1 Loss of Flow Loss of flow is detected in pump 1. The loss of flow condition occurs when no differential pressure is detected across the pump. Pump 1 State Pump 1 operational state. Pump 2 Loss of Flow Loss of flow is detected in pump 2. The loss of flow condition occurs when no differential pressure is detected across the pump. Pump 2 State Pump 2 operational state. Pump Hours Exceeded [Pump Hours] has exceeded [Pump Hours Threshold]. Pump Hours Threshold Threshold value used in the [Pump Hours Exceeded] event. Pump Hours Operating hours for pump since last reset of this value. Pump Short Cycle Pumps have short cycled. A short cycle is defined as turning on and off a number of times over a set time period. RAM Battery Issue RAM or RAM backup battery is not operating correctly. Remote Shutdown Unit is shut down by a remote signal. Sensor Issue - Event Control Enable/disable the activation of the [Sensor Issue] event. If set to “disabled,” the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Sensor Issue - Event Type The event type for the [Sensor Issue] event. Sensor Issue One or more sensors are disconnected or the signals are out of range. Sensor Temperature Temperature as measured by sensor. Service Required Unit requires servicing. Shutdown - Loss Of Power System lost power. This event becomes active when the unit is powered on following an unexpected loss of power. Smoke Detected Smoke detected. Supply Chilled Water Over Temp Threshold Threshold value used in the [Supply Chilled Water Over Temp] event. Supply Chilled Water Over Temp Chilled water temperature is too high, as indicated by an external input signal. 119 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-17 Liebert XDP™—Glossary (continued) Controller Liebert iCOM® v4 Data Label Data Description Supply Chilled Water Temp Sensor Issue The supply chilled water temperature sensor is disconnected or the signal is out of range. Supply Chilled Water Temperature Supply chilled water temperature. Supply Refrig Over Temp Threshold Threshold value used in the [Supply Refrigerant Over Temp] event. Supply Refrigerant Over Temp Event that is activated when [Supply Refrigerant Temperature] exceeds [Supply Refrig Over Temp Threshold]. The event is deactivated when the temperature drops below the threshold. Supply Refrigerant Temp Sensor Issue The supply refrigeramt temperature sensor is disconnected or the signal is out of range. Supply Refrigerant Temperature Supply refrigerant temperature. Supply Refrigerant Under Temp [Supply Refrigerant Temperature] has dropped below a specified threshold. System Condensation Detected System condensation detected. System Control Mode System control mode. System Date and Time The system date and time System On/Off Control Turn system functionality on or off. System Operating State Reason The reason the system is in the current operating state. System Operating State Current operating state of the system. System Status The operating status for the system Unit Code Missing Unit code has not been entered and saved. Unit Communication Lost Master has lost communication with one or more networked units. Unit Off Unit was turned off. Unit On Unit was turned on. Unit Partial Shutdown An event has occurred requiring some system components to be shutdown and disabled. Unit Shutdown An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit Standby Unit was placed in standby mode. Visual ID Control Visual identification control to display an LED flashing sequence, allowing it to be visually located. Water Under Floor Water under the floor is detected. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 120 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-18 Liebert iCOM® DCL™—Status and Coil Data Label Status Coil Number of Bits Notes Air Temperature Supply Air Over Temperature 10001 1 Active on Alarm Supply Air Under Temperature 10002 1 Active on Alarm Return Air Over Temperature 10003 1 Active on Alarm Supply Air Sensor Issue 10004 1 Active on Alarm Return Air Sensor Issue 10005 1 Active on Alarm Unit Top Return Air Sensor Failure 10006 1 Active on Alarm Unit Middle Return Air Sensor Failure 10007 1 Active on Alarm Unit Bottom Return Air Sensor Failure 10008 1 Active on Alarm Unit Top Supply Air Sensor Failure 10009 1 Active on Alarm Unit Middle First Supply Air Sensor Failure 10010 1 Active on Alarm Unit Middle Second Supply Air Sensor Failure 10011 1 Active on Alarm Unit Bottom Supply Air Sensor Failure 10012 1 Active on Alarm Pipe Temperature Sensor Failure 10013 1 Active on Alarm Humidity High Return Humidity 10024 1 Active on Alarm Low Return Humidity 10025 1 Active on Alarm Dehumidifier Hours Exceeded 10026 1 Active on Alarm Loss of Air Flow 10037 1 Active on Alarm Fan Hours Exceeded 10038 1 Active on Alarm Top Fan Issue 10039 1 Active on Alarm Bottom Fan Issue 10040 1 Active on Alarm 10051 1 Active on Alarm 10062 1 Active on Alarm 10084 1 Active on Alarm 10095 1 Active on Alarm Fans Remote Sensors 1 Remote Sensor Issue Remote Sensors 2 Remote Sensor Issue Remote Sensors 4 Remote Sensor Issue Chilled Water Chilled Water Control Valve Failure Supply Chilled Water Loss of Flow 10096 1 Active on Alarm Chilled Water Control Active 10097 1 Active on Alarm Modbus 0-10V Module Communication Failure 10098 1 Active on Alarm Chilled Water Circuit 1 Chilled Water Flow Transducer Failure 10109 1 Active on Alarm Chilled Water Inlet Temperature Sensor Failure 10110 1 Active on Alarm Chilled Water High Inlet Temperature 10111 1 Active on Alarm Chilled Water Circuit 2 Chilled Water Flow Transducer Failure 10122 1 Active on Alarm Chilled Water Inlet Temperature Sensor Failure 10123 1 Active on Alarm Chilled Water High Inlet Temperature 10124 1 Active on Alarm Customer Input 1 10135 1 Active on Alarm Customer Input 2 10136 1 Active on Alarm Customer Input 3 10137 1 Active on Alarm System Events 121 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-18 Liebert iCOM® DCL™—Status and Coil (continued) Data Label Status Coil Number of Bits Notes Customer Input 4 10138 1 Active on Alarm Smoke Detected 10139 1 Active on Alarm Water Under Floor 10140 1 Active on Alarm Service Required 10141 1 Active on Alarm Ext Over Temperature 10142 1 Active on Alarm Ext Loss of Flow 10143 1 Active on Alarm Ext Condenser Pump High Water 10144 1 Active on Alarm Ext Standby Glycol Pump On 10145 1 Active on Alarm External Fire Detected 10146 1 Active on Alarm Unit On 10147 1 Active on Alarm Unit Off 10148 1 Active on Alarm Unit Partial Shutdown 10149 1 Active on Alarm Unit Shutdown 10150 1 Active on Alarm Water Leakage Detector Sensor Issue 10151 1 Active on Alarm BMS Communications Timeout 10152 1 Active on Alarm Maintenance Due 10153 1 Active on Alarm Maintenance Completed 10154 1 Active on Alarm RAM Battery Issue 10155 1 Active on Alarm High Power Shutdown 10156 1 Active on Alarm Unspecified General Event 10157 1 Active on Alarm Rack Doors Open 10158 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 122 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-19 Liebert iCOM® DCL™—Input and Status Data Label Input Holding # of Reg Scale Notes/Units Protocol Server Class 1 = UPS 2 = AIR 3 = PMP 4 = PDU 5 = MONITOR 30385 1 Supply Air Temperature 30396 1 10 Units : deg C Int16 Supply Air Temperature 30397 1 10 Units : deg F Int16 Return Air Temperature 30398 1 10 Units : deg C Int16 Return Air Temperature 30399 1 10 Units : deg F Int16 Return Dew Point 30400 1 10 Units : deg C Int16 Return Dew Point 30401 1 10 Units : deg F Int16 Remote Sensor Minimum Temperature 30402 1 10 Units : deg C Int16 Remote Sensor Minimum Temperature 30403 1 10 Units : deg F Int16 Remote Sensor Maximum Temperature 30404 1 10 Units : deg C Int16 Remote Sensor Maximum Temperature 30405 1 10 Units : deg F Int16 Remote Sensor Average Temperature 30406 1 10 Units : deg C Int16 Remote Sensor Average Temperature 30407 1 10 Units : deg F Int16 Air Temperature Set Point 30408 40408 1 10 Units : deg C Int16 Air Temperature Set Point 30409 40409 1 10 Units : deg F Int16 Cooling Proportional Band 30410 40410 1 10 Units : deg C Int16 Cooling Proportional Band 30411 40411 1 10 Units : deg F Int16 Air Temperature Dead Band 30412 40412 1 10 Units : deg C Int16 Air Temperature Dead Band 30413 40413 1 10 Units : deg F Int16 Air Temperature Control Sensor 30414 40414 1 0 = Supply 1 = Remote 2 = Return Remote Sensor Temperature Calculation 30415 40415 1 0 = Average 1 = Maximum Air Temperature 123 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-19 Liebert iCOM® DCL™—Input and Status (continued) Data Label Input Holding # of Reg Scale Notes/Units High Supply Air Temperature Threshold 30416 40416 1 10 Units : deg C Int16 High Supply Air Temperature Threshold 30417 40417 1 10 Units : deg F Int16 Return Temperature/Humidity Sensor Control Type 30418 40418 1 0 = Average 1 = Maximum 2 = Top Sensor 3 = Middle Sensor 1 4 = Middle Sensor 2 5 = Bottom Sensor Supply Temperature Sensor Control Type 30419 Unit Top Return Sensor Temperature 30420 1 10 Units : deg C Int16 Unit Top Return Sensor Temperature 30421 1 10 Units : deg F Int16 Unit Middle Return Sensor Temperature 30422 1 10 Units : deg C Int16 Unit Middle Return Sensor Temperature 30423 1 10 Units : deg F Int16 Unit Bottom Return Sensor Temperature 30424 1 10 Units : deg C Int16 Unit Bottom Return Sensor Temperature 30425 1 10 Units : deg F Int16 Unit Top Supply Sensor Temperature 30426 1 10 Units : deg C Int16 Unit Top Supply Sensor Temperature 30427 1 10 Units : deg F Int16 Unit Middle First Supply Sensor Temperature 30428 1 10 Units : deg C Int16 Unit Middle First Supply Sensor Temperature 30429 1 10 Units : deg F Int16 Unit Middle Second Supply Sensor Temperature 30430 1 10 Units : deg C Int16 Unit Middle Second Supply Sensor Temperature 30431 1 10 Units : deg F Int16 Unit Bottom Supply Sensor Temperature 30432 1 10 Units : deg C Int16 Unit Bottom Supply Sensor Temperature 30433 1 10 Units : deg F Int16 Low Supply Air Temperature Threshold 30434 40434 1 10 Units : deg C Int16 Low Supply Air Temperature Threshold 30435 40435 1 10 Units : deg F Int16 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 40419 1 0 = Average 1 = Maximum 2 = Top Sensor 3 = Middle Sensor 4 = Bottom Sensor 124 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-19 Liebert iCOM® DCL™—Input and Status (continued) Data Label Input Holding # of Reg Scale Notes/Units High Return Air Temperature Threshold 30436 40436 1 10 Units : deg C Int16 High Return Air Temperature Threshold 30437 40437 1 10 Units : deg F Int16 Humidity Supply Humidity 30448 1 10 Units : % RH Uint16 Return Humidity 30449 1 10 Units : % RH Uint16 Humidity Set Point 30450 40450 1 High Return Humidity Threshold 30451 40451 1 10 Units : % RH Uint16 Low Return Humidity Threshold 30452 40452 1 10 Units : % RH Uint16 Dehumidifier State 30453 40453 1 Unit Top Return Sensor Humidity 30454 1 10 Units : % RH Int16 Unit Middle Return Sensor Humidity 30455 1 10 Units : % RH Int16 Unit Bottom Return Sensor Humidity 30456 1 10 Units : % RH Int16 Units : % RH Uint16 0 = off 1 = on Fans 0 = Internal (Auto) 1 = External (Manual) Fan Control Mode 30467 40467 1 Fan Speed Proportional Band 30468 40468 1 10 Units : deg C Uint16 Fan Speed Proportional Band 30469 40469 1 10 Units : deg F Uint16 Fan Speed Manual Set Point 30470 40470 1 Units : % Uint16 Fan Speed Maximum Set Point 30471 40471 1 Units : % Uint16 Fan Speed Minimum Set Point 30472 40472 1 Units : % Uint16 0 = Supply Sensor 1 = Remote Sensor 2 = Return Sensor 3 = Delta Ret-Sup 4 = Delta Remote 5 = Pipe Sensor Fan Control Sensor 30473 40473 1 Pipe Temperature Set Point 30474 40474 1 10 Units : deg C Int16 Pipe Temperature Set Point 30475 40475 1 10 Units : deg F Int16 Pipe Temperature Dead Band 30476 40476 1 10 Units : deg C Int16 125 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-19 Liebert iCOM® DCL™—Input and Status (continued) Data Label Input Holding # of Reg Scale Notes/Units Pipe Temperature Dead Band 30477 40477 1 10 Units : deg F Int16 Fan Control Mode 30467 40467 1 Fan Speed Proportional Band 30468 40468 1 10 Units : deg C Uint16 Fan Speed Proportional Band 30469 40469 1 10 Units : deg F Uint16 Fan Speed Manual Set Point 30470 40470 1 Units : % Uint16 Fan Speed Maximum Set Point 30471 40471 1 Units : % Uint16 Fan Speed Minimum Set Point 30472 40472 1 Units : % Uint16 Remote Sensors 1 0 = Internal (Auto) 1 = External (Manual) 0 = Supply Sensor 1 = Remote Sensor 2 = Return Sensor 3 = Delta Ret-Sup 4 = Delta Remote 5 = Pipe Sensor Fan Control Sensor 30473 40473 1 Pipe Temperature Set Point 30474 40474 1 10 Units : deg C Int16 Pipe Temperature Set Point 30475 40475 1 10 Units : deg F Int16 Pipe Temperature Dead Band 30476 40476 1 10 Units : deg C Int16 Pipe Temperature Dead Band 30477 40477 1 10 Units : deg F Int16 Remote Sensor Function 30488 40488 1 Remote Sensor Temperature 30489 1 10 Units : deg C Int16 Remote Sensor Temperature 30490 1 10 Units : deg F Int16 0 = Disable 1 = Reference 2 = Control Remote Sensors 2 40501 0 = Disable 1 = Reference 2 = Control Remote Sensor Function 30501 1 Remote Sensor Temperature 30502 1 10 Units : deg C Int16 Remote Sensor Temperature 30503 1 10 Units : deg F Int16 Remote Sensors 4 Remote Sensor Function 30527 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 40527 126 1 0 = Disable 1 = Reference 2 = Control Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-19 Liebert iCOM® DCL™—Input and Status (continued) Data Label Input Remote Sensor Temperature Remote Sensor Temperature Holding # of Reg Scale Notes/Units 30528 1 10 Units : deg C Int16 30529 1 10 Units : deg F Int16 Chilled Water High Supply Fluid Temperature Threshold 30540 40540 1 10 Units : deg C Int16 High Supply Fluid Temperature Threshold 30541 40541 1 10 Units : deg F Int16 Int16 Chilled Water Valve Control 30542 40542 1 0 = Single 1 = 2 Parallel 2 = 2 Alternate 3 = 2 Cascade Chilled Water Main Valve 30543 40543 1 0=1 1=2 Chilled Water Auto Valve Rotation 30544 40544 1 0 = disabled 1 = enabled Chilled Water Valve Rotation Hour 30545 40545 1 Chilled Water Inlet Temperature Control 30546 40546 1 Chilled Water Inlet High Temperature Threshold 30547 40547 1 10 Units : deg C Int16 Chilled Water Inlet High Temperature Threshold 30548 40548 1 10 Units : deg F Int16 30549 40549 1 Chilled Water Inlet Temperature Hysteresis 30550 40550 1 10 Units : deg C Int16 Chilled Water Inlet Temperature Hysteresis 30551 40551 1 10 Units : deg F Int16 Units : hr Int16 0 = disabled 1 = enabled Int16 Chilled Water Valve Open Position Units : % Int16 Int16 Chilled Water Circuit 1 Chilled Water Outlet Temperature 30562 1 10 Units : deg C Int16 Chilled Water Outlet Temperature 30563 1 10 Units : deg F Int16 Chilled Water Inlet Temperature 30564 1 10 Units : deg C Int16 Chilled Water Inlet Temperature 30565 1 10 Units : deg F Int16 127 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-19 Liebert iCOM® DCL™—Input and Status (continued) Data Label Input Holding # of Reg Scale Notes/Units Chilled Water Circuit 2 Chilled Water Outlet Temperature 30576 1 10 Units : deg C Int16 Chilled Water Outlet Temperature 30577 1 10 Units : deg F Int16 Chilled Water Inlet Temperature 30578 1 10 Units : deg C Int16 Chilled Water Inlet Temperature 30579 1 10 Units : deg F Int16 System Info System Status 30590 1 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation Unit Operating State 30591 1 0 = off 1 = on 2 = standby Unit Control Mode 30592 1 0 = Internal (Auto) 1 = External (Manual) 1 0 = Reason Unknown 1 = Network Display 2 = Alarm 3 = Schedule 4 = Remote System 5 = External Input 6 = Local Display Unit Operating State Reason 30593 BMS Timeout Period 30594 40594 1 Units : min Uint16 Auto Restart Delay 30595 40595 1 Units : sec Uint16 System Operations Cooling Capacity 30606 1 Units : % Uint16 Fan Speed 30607 1 Units : % Uint16 Dehumidifier Utilization 30608 1 Units : % Uint16 Calculated Next Maintenance Month 30609 1 Uint16 Calculated Next Maintenance Year 30610 1 Uint16 Maintenance Ramp 30611 1 Units : % Uint16 System On/Off Control 30612 40612 1 Rack Door Open High Supply Air Temperature Threshold 30613 40613 1 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 128 0 = off 1 = on 10 Units : deg C Int16 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-19 Liebert iCOM® DCL™—Input and Status (continued) Data Label Input Holding # of Reg Scale Notes/Units Rack Door Open High Supply Air Temperature Threshold 30614 40614 1 10 Units : deg F Int16 1 0 = Supply Sensor 1 = Rack Sensor 1 2 = Rack Sensor 2 3 = Rack Sensor 3 4 = Rack Sensor 4 40626 1 0 = disabled 1 = enabled 30627 40627 1 0 = Message 1 = Warning 2 = Alarm 30628 40628 1 0 = disabled 1 = enabled Rack Door Open Sensor Selection 30615 Smoke Detected - Event Control 30626 Smoke Detected - Event Type Water Under Floor - Event Control Water Under Floor - Event Type 30629 40629 1 0 = Message 1 = Warning 2 = Alarm Customer Input 1 - Event Control 30630 40630 1 0 = disabled 1 = enabled Customer Input 1 - Event Type 30631 40631 1 0 = Message 1 = Warning 2 = Alarm Customer Input 2 - Event Control 30632 40632 1 0 = disabled 1 = enabled Customer Input 2 - Event Type 30633 40633 1 0 = Message 1 = Warning 2 = Alarm Customer Input 3 - Event Control 30634 40634 1 0 = disabled 1 = enabled Customer Input 3 - Event Type 30635 40635 1 0 = Message 1 = Warning 2 = Alarm Customer Input 4 - Event Control 30636 40636 1 0 = disabled 1 = enabled Customer Input 4 - Event Type 30637 40637 1 0 = Message 1 = Warning 2 = Alarm Service Required - Event Control 30638 40638 1 0 = disabled 1 = enabled Service Required - Event Type 30639 40639 1 0 = Message 1 = Warning 2 = Alarm Ext Loss of Flow - Event Control 30640 40640 1 0 = disabled 1 = enabled Ext Loss of Flow - Event Type 30641 40641 1 0 = Message 1 = Warning 2 = Alarm 129 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-19 Liebert iCOM® DCL™—Input and Status (continued) Data Label Input Holding # of Reg Ext Over Temperature - Event Control 30642 40642 1 0 = disabled 1 = enabled 40643 1 0 = Message 1 = Warning 2 = Alarm 40644 1 2 = Reset 4 = Acknowledge Ext Over Temperature - Event Type 30643 System Event Acknowledge/Reset Scale Notes/Units Power Measurement System Input RMS A-B 30655 1 Units : VAC Int16 System Input RMS A-N 30656 1 Units : VAC Int16 System Input RMS Current Phase A 30657 1 Units : A AC Int16 System Input RMS B-C 30658 1 Units : VAC Int16 System Input RMS B-N 30659 1 Units : VAC Int16 System Input RMS Current Phase B 30660 1 Units : A AC Int16 System Input RMS C-A 30661 1 Units : VAC Int16 System Input RMS C-N 30662 1 Units : VAC Int16 System Input RMS Current Phase C 30663 1 Units : A AC Int16 Energy Consumption 30664 2 Units : kWH Int32 Instantaneous Power 30666 2 Units : W Int32 2 Units : Secs since Epoch(UTC) Time System Date and Time 39998 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 49998 130 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-20 Liebert iCOM® DCL™—Glossary Data Label Data Description Air Temperature Control Sensor Sensor from which air temperature measurements will be used for cooling and heating control. Air Temperature Dead Band Value that is divided evenly to form a temperature range above and below [Air Temperature Set Point]. If measured air temperature is within this range, no heating or cooling will occur. Air Temperature Set Point Desired air temperature. This set point is dependent upon which sensor is selected for control. Auto Restart Delay If power is lost, the control will delay this amount of time after power is restored before restarting the unit. BMS Communications Timeout Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe. BMS Timeout Period Timeframe within which the Building Management System (or external monitoring system) must communicate with the system to avoid a timeout. Bottom Fan Issue The bottom fan is not operating within its normal parameters. Calculated Next Maintenance Month Calculated month of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Year]. Calculated Next Maintenance Year Calculated year of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Month]. Chilled Water Auto Valve Rotation If enabled, the priority of the chilled water valves will change daily. Chilled Water Control Active Chilled water inlet temperature control function is enabled due to 'bad' water. Chilled Water Control Valve Failure Chilled water valve out of position. Chilled water control valve position does not match expected value. Chilled Water Flow Transducer Failure Chilled water flow transducer is disconnected or the signal is out of range. Chilled Water High Inlet Temperature Chilled water inlet temperature has exceeded an upper threshold. Chilled Water Inlet High Temperature Threshold Defines the threshold for considering the inlet water temperature too high. Chilled Water Inlet Temperature Control Enable/disable the function to switch off the fan and open the chilled water valve in case of 'bad' inlet water. Chilled Water Inlet Temperature Hysteresis Hysteresis used before returning to standard control mode when [Chilled Water Inlet Temperature Control] is enabled. Chilled Water Inlet Temperature Sensor Failure Chilled water inlet temperature sensor is disconnected or the signal is out of range. The sensor is mandatory for the chilled water flow function. Chilled Water Inlet Temperature Temperature of the water entering the hydraulic circuit of the chilled water unit. Chilled Water Main Valve Specifies which of the two chilled water valves is the main valve. Chilled Water Outlet Temperature Temperature of the water exiting the hydraulic circuit of the chilled water unit. Chilled Water Valve Control Method for controlling the chilled water cooling capacity. The options available are: single, parallel, alternate and cascade. Chilled Water Valve Open Position Chilled water valve open position. Chilled Water Valve Rotation Hour Hour of the day for switching the priority of the valves. Cooling Capacity Cooling capacity in use, expressed as a percentage of the maximum rated capacity. Cooling Proportional Band Temperature control band above [Air Temperature Set Point]. If measured air temperature is within this band, cooling operations are proportionally controlled. Customer Input 1 - Event Control Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 1 - Event Type The event type for the [Customer Input 1] event. Customer Input 1 Customer Input 1. 131 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-20 Liebert iCOM® DCL™—Glossary (continued) Data Label Data Description Customer Input 2 - Event Control Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 2 - Event Type The event type for the [Customer Input 2] event. Customer Input 2 Customer input 2. Customer Input 3 - Event Control Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 3 - Event Type The event type for the [Customer Input 3] event. Customer Input 3 Customer input 3. Customer Input 4 - Event Control Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 4 - Event Type The event type for the [Customer Input 4] event. Customer Input 4 Customer input 4. Dehumidifier Hours Exceeded Operating hours for the dehumidifier have exceeded the threshold. Dehumidifier State Dehumidifier operational state. Dehumidifier Utilization Present dehumidifier utilization expressed as a percentage of the maximum rated capacity. Energy Consumption Energy consumption since the last reset of this value. Ext Condenser Pump High Water High water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal. Ext Loss of Flow - Event Control Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Loss of Flow - Event Type The event type for the [Ext Loss of Flow] event. Ext Loss of Flow Loss of flow is detected, as indicated by an external input signal. Ext Over Temperature - Event Control Enable/disable the activation of the [Ext Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Over Temperature - Event Type The event type for the [Ext Over Temperature] event. Ext Over Temperature A temperature has exceeded its threshold, as indicated by an external input signal. Ext Standby Glycol Pump On The standby glycol pump is on, as indicated by an external input signal. External Fire Detected Fire detected, as indicated by an external input signal. Fan Control Mode Fan control mode. Allowable modes are: (0) Auto - Fan speed is controlled via the selected fan control sensor, and, (1) Manual - Fan will operate at a fixed speed. Fan Control Sensor Sensor from which air temperature measurements will be used for fan speed control. Fan Hours Exceeded Operating hours for the unit blower fan have exceeded the threshold. Fan Speed Manual Set Point Manual fan speed. Fan Speed Maximum Set Point Maximum fan speed. Fan Speed Minimum Set Point Minimum fan speed. Fan Speed Proportional Band Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled. Fan Speed Fan speed expressed as a percentage of the maximum rated speed. High Power Shutdown Supply to high power components has been shutdown. High Return Air Temperature Threshold Threshold value used in the [Return Air Over Temperature] event. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 132 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-20 Liebert iCOM® DCL™—Glossary (continued) Data Label Data Description High Return Humidity Threshold Threshold value used in the [High Return Humidity] event. High Return Humidity Return air high humidity event. High Supply Air Temperature Threshold Threshold value used in the [Supply Air Over Temperature] event. High Supply Fluid Temperature Threshold Threshold value used in the [Supply Chilled Water Over Temp] event. Humidity Set Point Desired relative humidity. Instantaneous Power Total electrical power currently being consumed. Loss of Air Flow No air flow through the unit due to failure of all fans. Low Return Humidity Threshold Threshold value used in the [Low Return Humidity] event. Low Return Humidity Return air low humidity event. Low Supply Air Temperature Threshold Threshold value used in the [Supply Air Under Temperature] event. Maintenance Completed Maintenance has been completed on the unit. Maintenance Due The calculated maintenance date has been reached. Maintenance Ramp The ratio of operations performed to the calculated operations available between maintenance intervals. Modbus 0-10V Module Communication Failure Modbus 0-10V module for managing the second Chilled Water circuit valve is disconnected or the signal is out of range. Pipe Temperature Dead Band Value that is divided evenly to form a temperature range above and below [Pipe Temperature Set Point]. If measured air temperature is within this range, the fan speed will not change. Pipe Temperature Sensor Failure Air temperature sensor located in the pipe is not sending a valid value. Pipe Temperature Set Point This value will be used as a comparison against pipe air temperature measurements in order to manage the speed of the fans. Rack Door Open High Supply Air Temperature If the rack supply air temperature exceeds this threshold, the rack doors are Threshold opened. Rack Door Open Sensor Selection Specifies the temperature sensor to be used by the control to manage the automatic rack door opening function. Rack Doors Open Rack doors opened due to supply air temperature exceeding the [Rack Door Open High Supply Air Temperature Threshold]. RAM Battery Issue RAM or RAM backup battery is not operating correctly. Remote Sensor Average Temperature Average value of remote sensor temperature measurements. Remote Sensor Function Function assigned to remote sensor. Available values are: (0) Control sensor will be used in calculation of remote sensor temperature that may be used for heating and cooling control, (1) Reference - sensor will not be used in calculation of remote sensor temperature, but is enabled, (2) Disable sensor is disabled Remote Sensor Issue Remote sensor is disconnected or the signal is out of range. Remote Sensor Maximum Temperature Maximum value of remote sensor temperature measurements. Remote Sensor Minimum Temperature Minimum value of remote sensor temperature measurements. Remote Sensor Temperature Calculation Calculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control. Remote Sensor Temperature Air temperature as measured by remote sensor. Return Air Over Temperature Return air high temperature event. Return Air Sensor Issue The air sensor at the inlet of the unit is disconnected or the signal is out of range. Return Air Temperature The temperature of the inlet air Return Dew Point Dew point temperature measured at the inlet of the unit. Return Humidity Relative humidity measured at the inlet of the unit. Return Temperature/Humidity Sensor Control Type Specifies whether the average, maximum, or only one of the return sensor values is to be used for return humidity and temperature control. 133 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-20 Liebert iCOM® DCL™—Glossary (continued) Data Label Data Description Server Class The general classification for this system Service Required - Event Control Enable/disable the activation of the [Service Required] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Service Required - Event Type The event type for the [Service Required] event. Service Required Unit requires servicing. Smoke Detected - Event Control Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Smoke Detected - Event Type The event type for the [Smoke Detected] event. Smoke Detected Smoke detected. Supply Air Over Temperature Supply air high temperature event. Supply Air Sensor Issue The air sensor at the outlet of the unit is disconnected or the signal is out of range. Supply Air Temperature Air temperature measured at the outlet of the unit. Supply Air Under Temperature Supply air low temperature event. Supply Chilled Water Loss of Flow Supply chilled water or glycol flow is too low. Supply Humidity Relative humidity at the outlet of the unit. Supply Temperature Sensor Control Type Specifies whether the average, maximum, or only one of the supply sensor values is to be used for supply temperature control. System Date and Time The system date and time System Event Acknowledge/Reset Reset and/or acknowledge all events. System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System On/Off Control Turn system functionality on or off. System Status The operating status for the system Top Fan Issue The top fan is not operating within its normal parameters. Unit Bottom Return Air Sensor Failure Return air sensor at the bottom of the unit is disconnected or the signal is out of range. Unit Bottom Return Sensor Humidity Return humidity as measured by the sensor located at the bottom of the unit. Unit Bottom Return Sensor Temperature Return air temperature as measured by the sensor located at the bottom of the unit. Unit Bottom Supply Air Sensor Failure Supply air sensor at the bottom of the unit is disconnected or the signal is out of range. Unit Bottom Supply Sensor Temperature Supply air temperature as measured by the sensor located at the bottom of the unit. Unit Control Mode Unit control mode. Unit Middle First Supply Air Sensor Failure First supply air sensor in the middle of the unit is disconnected or the signal is out of range. Unit Middle First Supply Sensor Temperature Supply air temperature as measured by the first sensor located in the middle of the unit. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 134 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-20 Liebert iCOM® DCL™—Glossary (continued) Data Label Data Description Unit Middle Return Air Sensor Failure Return air sensor in the middle of the unit is disconnected or the signal is out of range. Unit Middle Return Sensor Humidity Return humidity as measured by the sensor located in the middle of the unit. Unit Middle Return Sensor Temperature Return air temperature as measured by the sensor located in the middle of the unit. Unit Middle Second Supply Air Sensor Failure Second supply air sensor in the middle of the unit is disconnected or the signal is out of range. Unit Middle Second Supply Sensor Temperature Supply air temperature as measured by the second sensor located in the middle of the unit. Unit Off Unit was turned off. Unit On Unit was turned on. Unit Operating State Reason The reason the unit is in the current operating state. Unit Operating State Current operating state of the unit. Unit Partial Shutdown An event has occurred requiring some system components to be shutdown and disabled. Unit Shutdown An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit Top Return Air Sensor Failure Return air sensor at the top of the unit is disconnected or the signal is out of range. Unit Top Return Sensor Humidity Return humidity as measured by the sensor located at the top of the unit. Unit Top Return Sensor Temperature Return air temperature as measured by the sensor located at the top of the unit. Unit Top Supply Air Sensor Failure Supply air sensor at the top of the unit is disconnected or the signal is out of range. Unit Top Supply Sensor Temperature Supply air temperature as measured by the sensor located at the top of the unit. Unspecified General Event One or more unspecified events active. See local unit display for further details. Water Leakage Detector Sensor Issue The water leakage detector sensor is disconnected or the signal is out of range. Water Under Floor - Event Control Enable/disable the activation of the [Water Under Floor] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Water Under Floor - Event Type The event type for the [Water Under Floor] event. Water Under Floor Water under the floor is detected. 135 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-21 Liebert DS™ and Liebert PeX™—Status and Coil Controller Liebert iCOM™ v3 Coil Number of Bits Data Description Status Scale Notes / Units Sleep on Monday 10001 1 1 — — Sleep on Tuesday 10002 2 1 — — Sleep on Wednesday 10003 3 1 — — Sleep on Thursday 10004 4 1 — — Sleep on Friday 10005 5 1 — — Sleep on Saturday 10006 6 1 — — Sleep on Sunday 10007 7 1 — — Supply Limit Enable 10008 8 1 — — Reheat Lockout 10009 9 1 — — Humidifier Lockout 10010 10 1 — — Temperature Indication 1 10011 11 1 — — 10012 12 1 — — Minimum Chilled Water Temp Enable 10013 13 1 — — Std. Sensor Alarms Enable 10019 19 1 — — Sensor A Alarms Enable 10020 20 1 — — Compressor Lockout 10021 21 1 — — VSD Fan speed 10022 22 1 — — — 25 1 — — Timer Mode Type Unit Control Reset Alarm — 26 1 — — Acknowledge Alarm — 27 1 — — Reset Total Run Hours Fan Motor — 28 1 — — Reset Comp1Run Hour — 29 1 — — Reset Comp2Run Hour — 30 1 — — Reset Humidifier Run Hour — 31 1 — — Reset Dehumidifier Run Hour — 32 1 — — Reset CW/FC Run Hour — 33 1 — — Reset E-Heater1RunHour — 34 1 — — Reset E-heater2RunHour — 35 1 — — Reset E-heater3 Run Hour — 36 1 — — Reset HG/HW Run Hour — 37 1 — — Fan On 10025 — 1 — — Cool On 10026 — 1 — — Free Cool On 10027 — 1 — — Hot Water On 10028 — 1 — — Electrical Heater On 10029 — 1 — — Humidification On 10030 — 1 — — Dehumidification On 10031 — 1 — — Audible Alarm On 10032 — 1 — — Reserved 10033 — 1 — — Main Fan Overload 10034 — 1 — — Loss of Airflow 10035 — 1 — — Loss of Flow 10036 — 1 — — Reference Document: ST100I&C PA Parameters and Events, Version 18.0 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 136 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-21 Liebert DS™ and Liebert PeX™—Status and Coil (continued) Controller Liebert iCOM™ v3 Data Description Status Coil Number of Bits Scale Notes / Units Comp 1 High Pressure 10037 — 1 — — Comp 1 Low Pressure 10038 — 1 — — Comp 1 Overload 10039 — 1 — — Comp 1 Pumpdown Fail 10040 — 1 — — Comp 2 High Pressure 10041 — 1 — — Comp 2 Low Pressure 10042 — 1 — — Comp 2 Overload 10043 — 1 — — Comp 2 Pumpdown Fail 10044 — 1 — — Digital Scroll Compressor 1 High Temperature 10045 — 1 — — Digital Scroll Compressor 2 High Temperature 10046 — 1 — — Smoke Detected 10047 — 1 — — Water Under Floor 10048 — 1 — — Humidifier Problem 10049 — 1 — — Stby Glycol Pump On 10050 — 1 — — Standby Unit On 10051 — 1 — — Cond Pump-high Water 10052 — 1 — — Room Sensor Failure 10053 — 1 — — Loss Compressor Power 10054 — 1 — — Loss of Air Blower 1 10055 — 1 — — Humidifier Low Water 10058 — 1 — — Humidifier High Amps 10059 — 1 — — High Temperature 10060 — 1 — — Loss of Power 10061 — 1 — — Unspecified Event(s) 1 10064 — 1 — — High CW Temp 10065 — 1 — — Reserved 10066 — 1 — — High Room Temp 10067 — 1 — — Low Room Temp 10068 — 1 — — High Room Hum 10069 — 1 — — Low Room Hum 10070 — 1 — — High Temp Sensor A 10071 — 1 — — Low Temp Sensor A 10072 — 1 — — High Hum Sensor A 10073 — 1 — — Low Hum Sensor A 10074 — 1 — — Loss of CW Flow 10075 — 1 — — Clogged Filters 10076 — 1 — — Supply Sensor Failure 10077 — 1 — — Freecool Temp Sensor 10078 — 1 — — Sensor A Failure 10079 — 1 — — Unit Hrs Exceeded 10080 — 1 — — Comp 1 Hrs Exceeded 10081 — 1 — — Comp 2 Hrs Exceeded 10082 — 1 — — Reference Document: ST100I&C PA Parameters and Events, Version 18.0 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event. 137 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-21 Liebert DS™ and Liebert PeX™—Status and Coil (continued) Controller Liebert iCOM™ v3 Status Coil Number of Bits Scale Notes / Units FC Hrs Exceeded 10083 — 1 — — El Heat1 Hrs Exceeded 10084 — 1 — — El Heat2 Hrs Exceeded 10085 — 1 — — El Heat3 Hrs Exceeded 10086 — 1 — — HW/HG Hrs Exceeded 10087 — 1 — — Hum Hrs Exceeded 10088 — 1 — — Dehum Hrs Exceeded 10089 — 1 — — Network Failure 10091 — 1 — — Data Description No Connection W/Unit 10092 — 1 — — Unit(s) Disconnected 10093 — 1 — — Unit Code Missing 10094 — — — — Unit Code Mismatch 10095 — — — — Call Service 10096 — — — — Low Memory 1 10097 — — — — RAM / Battery Failure 10098 — — — — HCB not connected 10099 — — — — (Parallel Flash) Memory 1 Fail 10100 — — — — (Serial Flash) Memory 2 Fail 10101 — — — — Customer Input 1 10104 — — — — Customer Input 2 10105 — — — — Customer Input 3 10106 — — — — Customer Input 4 10107 — — — — Digital Scroll Compressor 1 Sensor Fail 10108 — — — — Digital Scroll Compressor 2 Sensor Fail 10109 — — — — Low Int Temperature 10110 — — — — High Ext Dewpoint 10111 — — — — Cabinet Temp Sensor Fail 10112 — — — — Cabinet Humidity Sensor Fail 10113 — — — — Ambient Temp Sensor Fail 10114 — — — — Comp 1 Short Cycle 10132 — — — — Comp 2 Short Cycle 10133 — — — — Reheat Lockout 10140 — — — — Humidifier Lockout 10141 — — — — Compressor(s) Lockout 10142 — — — — Fire Alarm 10148 — — — — Heaters Overheated 10149 — — — — Condenser 1 Failure 10150 — — — — Condenser 2 Failure 10151 — — — — Humidifier Cylinder Worn 10152 — — — — Heat Rej VFD 10153 — — — — Heat Rej TVSS 10154 — — — — Humidifier Low Amps 10155 — — — — Reference Document: ST100I&C PA Parameters and Events, Version 18.0 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 138 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-21 Liebert DS™ and Liebert PeX™—Status and Coil (continued) Controller Liebert iCOM™ v3 Status Coil Number of Bits Scale Notes / Units FC Lockout 10156 — — — — Water Leak Sensor Fail 10157 — — — — Data Description Reference Document: ST100I&C PA Parameters and Events, Version 18.0 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 1. Any non-recognized alarm code by current firmware received from the DS control will trigger this event. 139 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-22 Liebert DS™ and Liebert PeX™—Input and Holding Controller Liebert iCOM® v3 Data Description Input Register Holding Register # of Reg. Scale Notes / Units Vendor ID 30001 40001 1 — — Device ID 30002 40002 1 — — Version Number 30003 40003 1 — — UPS/Env/Pwr 30004 40004 1 — — Mode 1 30016 40016 1 — — 30017 40017 1 — — Timer Type of DT Room-FC 2 Humidity Control 3 30018 40018 1 — — VSD Setpoint 30019 40019 1 — % (HP) Supply Temperature Limit 30020 40020 1 10 deg C DT between Room and FC 30021 40021 1 10 deg C Minimum CW Temperature 30022 40022 1 10 deg C Temperature Setpoint 30023 40023 1 10 deg C Temperature Proportional Band 30024 40024 1 10 deg C Temperature Deadband 30025 40025 1 10 deg C Temperature Integration Time 30026 40026 1 — Minutes Humidity Setpoint 30027 40027 1 — % Humidity Proportional Band 30028 40028 1 — % Humidity Integration Time 30029 40029 1 — Minutes Humidity Deadband 30030 40030 1 — % Single Unit Auto-Restart Delay 30031 40031 1 — Seconds Infrared Flush Rate 30032 40032 1 — % Temp Control Type 4 30033 40033 1 — — Sleep Interval 1 Start Time Hour: Minute 30040 40040 1 — LSB:Min Sleep Interval 1 End Time Hour: Minute 30041 40041 1 — LSB:Min Sleep Interval 2 Start Time Hour: Minute 30042 40042 1 — LSB:Min Sleep Interval 2 End Time Hour: Minute 30043 40043 1 — LSB:Min Timer Deadband 30044 40044 1 10 deg C Manual VSD Timer/Counter 5 30045 40045 1 — — High Temperature 30050 40050 1 10 deg C Low Temperature 30051 40051 1 10 deg C High Temperature Sensor A 30052 40052 1 10 deg C Low Temperature Sensor A 30053 40053 1 10 deg C High Humidity 30054 40054 1 — % Low Humidity 30055 40055 1 — % High Humidity Sensor A 30056 40056 1 — % Low Humidity Sensor A 30057 40057 1 — % Fan Run Hour Threshold 30070 40070 — — Hours Compressor 1 Run Hour Threshold 30071 40071 — — Hours Compressor 2 Run Hour Threshold 30072 40072 — — Hours Humidifier Run Hours Threshold 30073 40073 — — Hours Dehumidification Run Hours Threshold 30074 40074 — — Hours CW/FC Run Hours Threshold 30075 40075 — — Hours Electrical Heaters #1 Run Hours Threshold 30076 40076 — — Hours Electrical Heaters #2 Run Hours Threshold 30077 40077 — — Hours Electrical Heaters #3 Run Hours Threshold 30078 40078 — — Hours Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 140 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-22 Liebert DS™ and Liebert PeX™—Input and Holding (continued) Controller Liebert iCOM® v3 Input Register Holding Register # of Reg. Scale Notes / Units Hot Water / Hot Gas Run Hours Threshold 30079 40079 — — Hours Operating State 6 30100 — — — — Number of Active Events/Alarm 30101 — — — — Summary Alarm Status 7 30102 — — — — Data Description Fan Ramp 30103 — — — % Cooling Ramp 30104 — — — % Free Cooling Ramp 30105 — — — % Heating Ramp 30106 — — — % Humidification Ramp 30107 — — — % Dehumidifier Ramp 30108 — — — % FreeCooling Status 8 Return Temperature 30109 — — — % 30110 — — 10 deg C Actual Temperature SP 30111 — — 10 deg C Supply Temperature 30112 — — 10 deg C Actual Supply Temperature SP 30113 — — 10 deg C FC Temperature 30115 — — 10 deg C Sensor A Temperature 30116 — — 10 deg C Sensor B Temperature 30117 — — 10 deg C Sensor C Temperature 30118 — — 10 deg C Digital Scroll Compressor 1 High Temperature 30119 — — 10 deg C Digital Scroll Compressor 2 High Temperature 30120 — — 10 deg C Return Humidity 30130 — — — % Actual Humidity SP 30131 — — — % Sensor A Humidity 30132 — — — % Sensor B Humidity 30133 — — — % Sensor C Humidity 30134 — — — % Fan Run Hour 30141 — — — Hours Compressor 1 Run Hour 30142 — — — Hours Compressor 2 Run Hour 30143 — — — Hours Humidifier Run Hours 30144 — — — Hours Dehumidification Run Hours 30145 — — — Hours Free cooling Run Hours 30146 — — — Hours Electrical Heaters #1 Run Hours 30147 — — — Hours Electrical Heaters #2 Run Hours 30148 — — — Hours Electrical Heaters #3 Run Hours 30149 — — — Hours Hot Water / Hot Gas Run Hours 30150 — — — Hours Daily High Temperature 30151 — — 10 deg C Daily High Temp Time 30152 — — — Hh:mm Daily Low Temperature 30153 — — 10 deg C Daily Low Temp Time 30154 — — — Hh:mm Daily High Humidity 30155 — — — %RH Daily High Hum Time 30156 — — — Hh:mm Daily Low Humidity 30157 — — — %RH 141 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-22 Liebert DS™ and Liebert PeX™—Input and Holding (continued) Controller Liebert iCOM® v3 Data Description Daily Low Hum Time Input Register Holding Register # of Reg. Scale Notes / Units 30158 — — — Hh:mm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Reference Document: ST100I&C PA Parameters and Events, Version 18.0 1. Timer mode: 0 = no, 1 = yes 2. Type of DT Room-Glycol: 0 = no, 1 = contact, 2 = value 3. Predictive Hum Control: 0 = relative, 1 = compensated, 2 = predictive 4. Temp Control Algorithm: 0 = proportional, 1 = PD, 2 = PDI; 3 = intelligent 5. When VFD is set to manual mode (coil 22), the host can control the VFD by the value of register 40019. The Manual VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information. 6. Operating state: Bit 0-1: 00 unit off, 01 unit on, 10 unit standby Bit 2-3: 00 auto, 01 manual Bit 4-7: 0000 none 0001 local user 0010 alarm 0011 schedule 0100 remote user 0101 external device 0110 local display 7. Alarm state bit map: Bit 0 = Reset state Bit 1 = Active state Bit 2 = Acknowledge state Bit 3-7 = Alarm Type 00000: Message 00001: Warning 00010: Alarm 8. Free-cool state: 0 = Off, 1 = Start, 2 = On Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 142 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-23 Liebert XDF™—Status and Coil Controller Liebert iCOM® v3 Temperature Indication Coil Number of Bits Scale Notes / Units 10011 11 1 — — — 25 1 — — Status Data Description 1 Unit Control Reset Alarm — 26 1 — — Acknowledge Alarm — 27 1 — — Cabinet Sensor Alarm Enable 10023 23 1 — — Fan On 10025 — 1 — — Cool On 10026 — 1 — — Compressor 1 High Pressure 10037 — 1 — — Compressor 1 Low Pressure 10038 — 1 — — Cond Pump-High Water 10052 — 1 — — Loss Compressor Power 10054 — 1 — — Emergency Damper Fail 10056 — 1 — — High Internal Temperature 10057 — 1 — — Loss of Power 10061 — 1 — — Remote Shutdown 10062 — 1 — — Unspecified Event(s) 1 10064 — 1 — — Unit Hrs Exceeded 10080 — 1 — — Comp 1 Hrs Exceeded 10081 — 1 — — Network Failure 10091 — 1 — — No Connection W/Unit 1 10092 — 1 — — Unit(s) Disconnected 10093 — 1 — — Unit Code Missing 10094 — — — — Unit Code Mismatch 10095 — — — — Low Memory 1 10097 — — — — Ram / Battery Failure 10098 — — — — (Parallel Flash) MEMORY 1 FAIL 10100 — — — — (Serial Flash) MEMORY 2 FAIL 10101 — — — — Front Door Open 10102 — — — — Rear Door Open 10103 — — — — Digital Scroll Compressor 1 Sensor Fail 10108 — — — — Low Int Temperature 10110 — — — — High Ext Dewpoint 10111 — — — — Cabinet Temp Sensor Fail 10112 — — — — Cabinet Humidity Sensor Fail 10113 — — — — Ambient Temp Sensor Fail 10114 — — — — Comp 1 Short Cycle 10132 — — — — Reheat Lockout 10140 — — — — Humidifier Lockout 10141 — — — — Compressor(s) Lockout 10142 — — — — Backup Ventilation 10143 — — — — Door Open 10144 — — — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Reference Document: ST100I&C PA Parameters and Events, Version 18.0 1. Any non-recognized alarm code by current firmware received from the XDF control will trigger this event. 143 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-23 Liebert XDF™—Status and Coil (continued) Controller Liebert iCOM® v3 Data Description Status Coil Number of Bits Scale Notes / Units Device Load 10146 — — — — Alarm Status 10147 — — — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Reference Document: ST100I&C PA Parameters and Events, Version 18.0 1. Any non-recognized alarm code by current firmware received from the XDF control will trigger this event. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 144 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-24 Liebert XDF™—Input and Holding Controller Liebert iCOM® v3 Data Description Input Register Holding Register # of Reg. Scale Notes / Units Vendor ID 30001 40001 1 — — Device ID 30002 40002 1 — — Version number 30003 40003 1 — — UPS/Env/Pwr 30004 40004 1 — — Temperature Setpoint 30023 40023 1 10 deg C Delay after safe Temp has been reached 30034 40034 — — Minutes Allowable deviation between internal temp sensors 30035 40035 — — deg C High Cabinet Temperature Setpoint 30058 40058 — 10 deg C Low Cabinet Temperature Setpoint 30059 40059 — 10 deg C Fan Run Hour Threshold 30070 40070 — — Hours Compressor 1 Run Hour Threshold 30071 40071 — — Hours Service Ramp 30099 — — — % 30100 — — — — 30101 — — — — Operating State 6 Number of Active Events/Alarm Summary Alarm Status 7 30102 — — — — Fan Ramp 30103 — — — % Cooling Ramp 30104 — — — % Digital Scroll Compressor 1 High Temperature 30119 — — 10 deg C Sensor 1 Temp 30121 — — 10 deg C Sensor 2 Temp 30122 — — 10 deg C Sensor 3 Temp 30123 — — 10 deg C Sensor 4 Temp 30124 — — 10 deg C Ambient Temp 30125 — — 10 deg C Ambient Humidity 30126 — — — % Dew Point Temp 30127 — — — deg C Adjusted Setpoint Temp 30128 — — 10 deg C Cabinet Temperature 30129 — — 10 deg C Service Due Year 30135 — — — — Service Due Month 30136 — — — — Device kW Load 30137 — — — kW Fan Run Hour 30141 — — — Hours 145 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-24 Liebert XDF™—Input and Holding (continued) Controller Liebert iCOM® v3 Data Description Compressor 1 Run Hour Input Register Holding Register # of Reg. Scale Notes / Units 30142 — — — Hours NOTES If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Reference Document: ST100I&C PA Parameters and Events, Version 18.0 1. Timer mode: 0 = no, 1 = yes 2. Type of DT Room-Glycol: 0 = no, 1 = contact, 2 = value 3. Predictive Hum Control: 0 = relative, 1 = compensated, 2 = predictive 4. Temp Control Algorithm: 0 = proportional, 1 = PD, 2 = PDI; 3 = intelligent 5. When VFD is set to manual mode (coil 22), the host can control the VFD by the value of register 40019. The Manual VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information. 6. Operating state: Bit 0-1: 00 unit off, 01 unit on, 10 unit standby Bit 2-3: 00 auto, 01 manual Bit 4-7: 0000 none 0001 local user 0010 alarm 0011 schedule 0100 remote user 0101 external device 0110 local display 7. Alarm state bit map: Bit 0 = Reset state Bit 1 = Active state Bit 2 = Acknowledge state Bit 3-7 = Alarm Type 00000: Message 00001: Warning 00010: Alarm 8. Free-cool state: 0 = Off, 1 = Start, 2 = On Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 146 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-25 Liebert Challenger 3000™, Liebert Deluxe System/3™, Liebert Himod™, Liebert ICS™— Input and Holding—LAM Controller Advanced Microprocessor - LAM Liebert Challenger 3000 Liebert Deluxe System/3 Liebert Products Liebert Himod (LNA version - Using Liebert SiteScan®) Liebert ICS Available Points Input Register Holding Register Temperature — 40001 1 — — Humidity — 40002 1 — — Data Description # of Reg. Scale Notes / Units Status Points (View) Cooling — 40003 1 — 1=On / 0=Off Heating — 40004 1 — 1=On / 0=Off Humidification — 40005 1 — 1=On / 0=Off De-humidification — 40006 1 — 1=On / 0=Off Econ-O-Cycle — 40007 1 — 1=On / 0=Off Stages — 40008 1 — — % Capacity — 40009 1 — — Unit Status (On / Off) — 40018 1 — 1=On / 0=Off (Read Only) Discrete alarm objects available; use autodiscover for this unit Alarm Points Communications — 40289 1 — Bit 0 Local Off — 40289 1 — Bit 1 Remote Off — 40289 1 — Bit 2 High Head Pressure 1 — 40289 1 — Bit 3 High Head Pressure 2 — 40289 1 — Bit 4 Loss of Airflow — 40289 1 — Bit 5 Standby Glycol Unit On — 40289 1 — Bit 6 Liquid Detected — 40289 1 — Bit 7 Change Filters — 40289 1 — Bit 8 High Temperature — 40289 1 — Bit 9 Low Temperature — 40289 1 — Bit 10 High Humidity — 40290 1 — Bit 0 Low Humidity — 40290 1 — Bit 1 Humidifier Problem — 40290 1 — Bit 2 No Water in Humidifier Pan — 40290 1 — Bit 3 Compressor 1 Overload — 40290 1 — Bit 4 Compressor 2 Overload — 40290 1 — Bit 5 Main Fan Overload — 40290 1 — Bit 6 Manual Override — 40290 1 — Bit 7 Smoke Detected — 40290 1 — Bit 8 Loss of Water — 40290 1 — Bit 9 Standby Unit On — 40290 1 — Bit 10 Low Suction — 40291 1 — Bit 0 Short Cycle — 40291 1 — Bit 1 Loss of Power — 40291 1 — Bit 2 Inverter on Bypass — 40291 1 — Bit 3 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 147 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-25 Liebert Challenger 3000™, Liebert Deluxe System/3™, Liebert Himod™, Liebert ICS™— Input and Holding—LAM (continued) Controller Advanced Microprocessor - LAM Liebert Challenger 3000 Liebert Deluxe System/3 Liebert Products Liebert Himod (LNA version - Using Liebert SiteScan®) Liebert ICS Available Points Input Register Holding Register # of Reg. Scale Notes / Units Standby Fan On — 40291 1 — Bit 4 Loss of Emergency Power — 40291 1 — Bit 5 Local Alarm 1 — 40291 1 — Bit 6 Data Description Local Alarm 2 — 40291 1 — Bit 7 Off by Remote Shutdown — 40291 1 — Bit 8 Local Alarm 3 — 40291 1 — Bit 9 Local Alarm 4 — 40291 1 — Bit 10 Compressor 1 Run Hours — 40019 1 — — Compressor 2 Run Hours — 40020 1 — — Fan Motor Run Hours — 40021 1 — — Humidifier Run Hours — 40022 1 — — Temperature Setpoint — 40010 1 — (R/W) Temperature Tolerance — 40011 1 — (R/W) Humidity Setpoint — 40012 1 — (R/W) Setpoints (View) Humidity Tolerance — 40013 1 — (R/W) High Temp Alarm Setpoint — 40014 1 — (R/W) Low Temp Alarm Setpoint — 40015 1 — (R/W) High Humd Alarm Setpoint — 40016 1 — (R/W) Low Humidity Alarm Setpoint — 40017 1 — (R/W) Winter Start Delay — 40028 1 — Minutes (R/W) Auto Flush Rate — 40029 1 — % (R/W) Chill Water Flush Rate — 40030 1 — Hours (R/W) Auto Restart Delay — 40031 1 — 0.1 minute (R/W) Control Points (Set) Unit On / Off — 40349 1 — Temperature Setpoint — 40350 1 — Bit 0 On=unit Off; Bit 1 On=unit On — Temperature Tolerance — 40350 1 1000 — Humidity Setpoint — 40351 1 — — Humidity Tolerance — 40351 1 1000 Reheat Lockout — 40349 1 — Bit 2 On=RH Off; Bit 3 On=RH On Humidifier Lockout — 40349 1 — Bit 4 On=HL Off; Bit 5 On=HL On — Trendable Points (Set) Temperature — — 1 — — Humidity — — 1 — — Reports — — — — Trend — — 1 — — Status — — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 148 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-26 Liebert DataMate™, Liebert Mini-Mate Plus™, Liebert Mini-Mate2™—Input and Holding—L0B Controller Small Systems - L0B Liebert DataMate Liebert Products Liebert Mini-Mate Plus Liebert Mini-Mate2 Available Points Input Register Holding Register # of Reg. Scale Notes / Units Temperature — 40001 1 — — Humidity — 40002 1 — — Cooling — 40003 1 — 1=On / 0=Off Data Description Status Points (View) Heating — 40004 1 — 1=On / 0=Off Humidification — 40005 1 — 1=On / 0=Off Dehumidification — 40006 1 — 1=On / 0=Off Econ-o-Cycle — 40007 1 — 1=On / 0=Off Stages — 40008 1 — — % Capacity — 40009 1 — — Communications — 40289 1 — Bit 0 Local Off — 40289 1 — Bit 1 Remote Off — 40289 1 — Bit 2 High Temperature — 40289 1 — Bit 3 Low Temperature — 40289 1 — Bit 4 High Humidity — 40289 1 — Bit 5 Low Humidity — 40289 1 — Bit 6 — — 1 — — Unit On/Off — 40011 1 — 1=On / 0=Off (R/W) Remote On/Off — 40349 1 — Temperature — — 1 — — Humidity — — 1 — — Reports — — — — Trend — — 1 — — Status — — 1 — — Alarm Points Setpoints (View) None Control Points (Set) Bit 0 On=unit Off Bit 1 On=unit On (W) Trendable Points (Set) If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 149 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-27 Liebert DataMate™, Liebert Mini-Mate2™—Input and Holding—MM2 Controller MM2 Liebert Products Liebert DataMate Liebert Mini-Mate2 Available Points Input Register Holding Register # of Reg. Scale Notes / Units Temperature — 40001 1 — — Humidity — 40002 1 — — Data Description Status Points (View) Cooling — 40003 1 — 1=On / 0=Off Heating — 40004 1 — 1=On / 0=Off Humidification — 40005 1 — 1=On / 0=Off Dehumidification — 40006 1 — 1=On / 0=Off Econ-o-Cycle — 40007 1 — 1=On / 0=Off Stages — 40008 1 — — % Capacity — 40009 1 — — Communications — 40289 1 — Bit 0 Local Off — 40289 1 — Bit 1 Alarm Points Remote Off — 40289 1 — Bit 2 High Head Pressure 1 — 40289 1 — Bit 3 Loss of Airflow — 40289 1 — Bit 5 Standby Glycol Unit On — 40289 1 — Bit 6 Change Filters — 40289 1 — Bit 8 High Temperature — 40289 1 — Bit 9 Low Temperature — 40289 1 — Bit 10 High Humidity — 40290 1 — Bit 0 Low Humidity — 40290 1 — Bit 1 Humidifier Problem — 40290 1 — Bit 2 Smoke Detected — 40290 1 — Bit 8 Loss of Water Flow — 40290 1 — Bit 9 Standby Unit On — 40290 1 — Bit 10 Short Cycle — 40291 1 — Bit 1 Loss of Power — 40291 1 — Bit 2 Local Alarm 1 — 40291 1 — Bit 6 Local Alarm 2 — 40291 1 — Bit 7 Local Alarm 3 — 40291 1 — Bit 9 Local Alarm 4 — 40291 1 — Bit 10 Compressor 1 — 40019 1 — — Fan Motor — 40020 1 — — Humidifier — 40021 1 — — Run Hours (View) If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 150 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-27 Liebert DataMate™, Liebert Mini-Mate2™—Input and Holding—MM2 (continued) Controller MM2 Liebert Products Liebert DataMate Liebert Mini-Mate2 Available Points Input Register Holding Register Temperature — 40010 1 — — Temp Tolerance — 40011 1 — — Data Description # of Reg. Scale Notes / Units Setpoints (View) Humidity — 40012 1 — — Humidity Tolerance — 40013 1 — — High Temperature Alarm — 40014 1 — — Low Temperature Alarm — 40015 1 — — High Humidity Alarm — 40016 1 — — Low Humidity Alarm — 40017 1 — — Chill Water Flush Rate — 40025 1 — Hours (R/W) Auto Restart Delay — 40026 1 — 0.1 minute (R/W) Unit On/Off — 40018 1 — 1=On / 0=Off (Read Only) Remote On/Off — 40349 1 — Bit 0 On=unit Off Bit 1 On=unit On (W) Temperature Setpoint — 40350 1 — Control Points (Set) (W) Multiply desired value by 1000 (Modbus only) 0=No Change (W) Temperature Tolerance — 40350 1 1000 Humidity Setpoint — 40351 1 - Humidity Tolerance — 40351 1 1000 Temperature — — 1 — — Humidity — — 1 — — Trend — — 1 — — Status — — 1 — — (W) Multiply desired value by 1000 (Modbus only) 0=No Change (W) Trendable Points (Set) Reports If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 151 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-28 Liebert Mini-Mate2™ 8 Ton—Input and Holding—L8T Controller L8T Liebert Products Liebert Mini-Mate2 8 Ton Available Points Input Register Holding Register # of Reg. Scale Notes / Units Temperature — 40001 1 — — Humidity — 40002 1 — — Cooling — 40003 1 — 1=On / 0=Off Data Description Status Points (View) Heating — 40004 1 — 1=On / 0=Off Humidification — 40005 1 — 1=On / 0=Off De-humidification — 40006 1 — 1=On / 0=Off Econ-O-Cycle — 40007 1 — 1=On / 0=Off Stages — 40008 1 — — % Capacity — 40009 1 — — Analog input 1 — 40023 1 — A/D raw value w/ slope =1 and offset = 0 Analog input 2 — 40024 1 — A/D raw value w/ slope =1 and offset = 0 Analog input 3 — 40025 1 — A/D raw value w/ slope =1 and offset = 0 Analog input 4 — 40026 1 — A/D raw value w/ slope =1 and offset = 0 Communications — 40289 1 — Bit 0 Local Off — 40289 1 — Bit 1 Remote Off — 40289 1 — Bit 2 High Head Pressure 1 — 40289 1 — Bit 3 High Head Pressure 2 — 40289 1 — Bit 4 Loss of Airflow — 40289 1 — Bit 5 Standby Glycol Unit On — 40289 1 — Bit 6 Alarm Points Not Used — 40289 1 — Bit 7 Change Filters — 40289 1 — Bit 8 High Temperature — 40289 1 — Bit 9 Low Temperature — 40289 1 — Bit 10 High Humidity — 40290 1 — Bit 0 Low Humidity — 40290 1 — Bit 1 Humidifier Problem — 40290 1 — Bit 2 Smoke Detected — 40290 1 — Bit 8 Loss of Water — 40290 1 — Bit 9 Standby Unit On — 40290 1 — Bit 10 Not Used — 40291 1 — Bit 0 Short Cycle — 40291 1 — Bit 1 Loss of Power — 40291 1 — Bit 2 Local Alarm 1 — 40291 1 — Bit 6 Local Alarm 2 — 40291 1 — Bit 7 EPO Shutdown — 40291 1 — Bit 8 Local Alarm 3 — 43291 1 — Bit 9 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 152 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-28 Liebert Mini-Mate2™ 8 Ton—Input and Holding—L8T (continued) Controller L8T Liebert Products Liebert Mini-Mate2 8 Ton Available Points Input Register Holding Register # of Reg. Scale Notes / Units — 40291 1 — Bit 10 Compressor 1 Run Hours — 40019 1 — — Compressor 2 Run Hours — 40020 1 — — Data Description Local Alarm 4 Run Times (View) Glycol Run Hours — — 1 — — Fan Motor Run Hours — 40021 1 — — Humidifier Run Hours — 40022 1 — — Reheat 1 Run Hours — — 1 — — Reheat 2 Run Hours — — 1 — — Reheat 3 Run Hours — — 1 — — Chilled H2O Valve Run Hours — — 1 — — Temperature Setpoint — 40010 1 — (R/W) Temperature Tolerance — 40011 1 — (R/W) Setpoints (View) Humidity Setpoint — 40012 1 — (R/W) Humidity Tolerance — 40013 1 — (R/W) High Temperature Alarm Setpoint — 40014 1 — (R/W) Low Temp Alarm Setpoint — 40015 1 — (R/W) High Humidity Alarm Setpoint — 40016 1 — (R/W) Low Humidity Alarm Setpoint — 40017 1 — (R/W) Winter Start Delay — 40028 1 — Minutes (R/W) Auto Flush Rate — 40029 1 — % (R/W) Chill Water Flush Rate — 40030 1 — Hours (R/W) Auto Restart Delay — 40031 1 — 0.1 minute (R/W) Unit Status (On / Off) — 40018 1 — 1=On / 0=Off (Read Only) Unit On / Off — 40349 1 — Temperature Setpoint — 40350 1 — (W) Temperature Tolerance — 40350 1 1000 (W) Control Points (Set) Bit 0 On=unit Off Bit 1 On=unit On (W) Humidity Setpoint — 40351 1 - (W) Humidity Tolerance — 40351 1 1000 (W) Reheat Lockout — 40349 1 — Bit 2 On=RH Off Bit 3 On=RH On Humidifier Lockout — 40349 1 — Bit 4 On=HL Off Bit 5 On=HL On If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 153 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-29 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert LECS 15™—Input and Holding—C10 2-step Controller C10 Liebert Atlas Air Liebert Products Liebert Atlas PEC Liebert LECS 15 Available Points Input Register Holding Register # of Reg. Scale Notes / Units Unit Number — 40001 1 — 1-99 Average Return Air Temp. — 40002 1 10 deg C Average Return Air Humidity — 40003 1 10 % Data Description Status Points (View) Average Supply Air Temp. — 40004 1 10 deg C Average Supply Air Humidity — 40005 1 10 % Fan Status — 40007 1 — 1=On / 0=Off Cool 1 Status — 40008 1 — 1=On / 0=Off Cool 2 Status — 40009 1 — 1=On / 0=Off Heat 1 Status — 40010 1 — 1=On / 0=Off Heat 2 Status — 40011 1 — 1=On / 0=Off Humidifier Status — 40012 1 — — De-humidifier Status — 40013 1 — — Cooling Capacity — 40014 1 — % Heating Capacity — 40015 1 — % Temperature Control Status — 40019 1 — 0=Return / 1=Supply Battery Voltage Level — 40020 1 10 V Remote Shutdown Status — 40021 1 — 1=Enabled / 0=Disabled Temperature Control Select — 40024 1 — 0=Return / 1=Supply 2=Remote / 3=Auto Communications — 40289 1 — Bit 0 Faulty Sensor — 40289 1 — Bit 1 High Temperature — 40289 1 — Bit 2 Low Temperature — 40289 1 — Bit 3 High Humidity — 40289 1 — Bit 4 Alarm Points Low Humidity — 40289 1 — Bit 5 Loss of Airflow — 40289 1 — Bit 6 Water Under Floor — 40289 1 — Bit 7 Cool 1 Low Pressure Alarm — 40289 1 — Bit 8 Cool 2 Low Pressure Alarm — 40289 1 — Bit 9 Cool 1 High Pressure Alarm — 40289 1 — Bit 10 Cool 2 High Pressure Alarm — 40290 1 — Bit 0 Cool Service — 40290 1 — Bit 1 Humidifier Service — 40290 1 — Bit 2 Filter Service — 40290 1 — Bit 3 Humidity Low Level — 40290 1 — Bit 4 Battery Level Low — 40290 1 — Bit 5 Loss of Power — 40290 1 — Bit 6 Local Alarm 1 — 40290 1 — Bit 7 Local Alarm 2 — 40290 1 — Bit 8 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 154 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-29 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert LECS 15™—Input and Holding—C10 2-step Controller C10 Liebert Atlas Air Liebert Products Liebert Atlas PEC Liebert LECS 15 Available Points Data Description Input Register Holding Register # of Reg. Scale Notes / Units — 40016 1 10 deg C (R/W) Setpoints (View) Return Air Temperature Return Air Humidity — 40017 1 10 deg C (R/W) Supply Air Temperature — 40018 1 10 deg C (R/W) High Temp Alarm — 40025 1 10 deg C (R/W) Low Temp Alarm — 40026 1 10 deg C (R/W) High Hum Alarm — 40027 1 10 % (R/W) Low Hum Alarm — 40028 1 10 % (R/W) Restart Delay — 40029 1 — Seconds (R/W) Activation Mode — 40006 1 — 1=On / 0=Off (R/W) General Alarm Status — 40022 1 — 1=On / 0=Off; write 0 to reset alarm Control Points (Set) Audible Alarm Status — 40023 1 — 1=On / 0=Off; write 0 to ack alarm Return Air Temperature — 40349 1 10 deg C (R/W) Return Air Humidity — 40350 1 10 deg C (R/W) Supply Air Temperature — 40351 1 10 deg C (R/W) If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 155 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-30 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert CEMS 100™—Input and Holding— C100 4-step Controller CEMS 100 Liebert Atlas Air Liebert Products Liebert Atlas PEC Liebert CEMS 100 Available Points Input Register Holding Register # of Reg. Scale Notes / Units Unit Number — 40001 1 — 1-99 Average Return Air Temp. — 40002 1 10 deg C Average Return Air Humidity — 40003 1 10 % Data Description Status Points (View) Average Supply Air Temp. — 40004 1 10 deg C Average Supply Air Humidity — 40005 1 10 % Fan Status — 40007 1 — 1=On / 0=Off Cool 1 Status — 40008:0 1 — 1=On / 0=Off Cool 2 Status — 40009:0 1 — 1=On / 0=Off Cool 3 Status — 40008:4 1 — 1=On / 0=Off Cool 4 Status — 40009:4 1 — 1=On / 0=Off Heat 1 Status — 40010 1 — 1=On / 0=Off Heat 2 Status — 40011 1 — 1=On / 0=Off Humidifier Status — 40012 1 — — De-humidifier Status — 40013 1 — — Cooling Capacity — 40014 1 — % Heating Capacity — 40015 1 — % Temperature Control Status — 40019 1 — 0=Return / 1=Supply Battery Voltage Level — 40020 1 100 V Remote Shutdown Status — 40021 1 — 1=Enabled / 0=Disabled Temperature Control Select — 40024 1 — 0=Return / 1=Supply 2=Remote / 3=Auto Communications — 40289 1 — Bit 0 Faulty Sensor — 40289 1 — Bit 1 High Temperature — 40289 1 — Bit 2 Low Temperature — 40289 1 — Bit 3 High Humidity — 40289 1 — Bit 4 Alarm Points Low Humidity — 40289 1 — Bit 5 Loss of Airflow — 40289 1 — Bit 6 Water Under Floor — 40289 1 — Bit 7 Cool 1 Low Pressure Alarm — 40289 1 — Bit 8 Cool 2 Low Pressure Alarm — 40289 1 — Bit 9 Cool 1 High Pressure Alarm — 40289 1 — Bit 10 Cool 2 High Pressure Alarm — 40290 1 — Bit 0 Cool Service — 40290 1 — Bit 1 Humidifier Service — 40290 1 — Bit 2 Filter Service — 40290 1 — Bit 3 Humidity Low Level — 40290 1 — Bit 4 Battery Level Low — 40290 1 — Bit 5 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 156 Modbus RTU and Modbus TCP Protocols—Thermal Management Products Table 3-30 Liebert Atlas Air™, Liebert Atlas PEC™, Liebert CEMS 100™—Input and Holding— C100 4-step (continued) Controller CEMS 100 Liebert Atlas Air Liebert Products Liebert Atlas PEC Liebert CEMS 100 Available Points Input Register Holding Register # of Reg. Scale Notes / Units Loss of Power — 40290 1 — Bit 6 Local Alarm 1 — 40290 1 — Bit 7 Local Alarm 2 — 40290 1 — Bit 8 Cool 3 Low Pressure — 40290 1 — Bit 9 Cool 4 Low Pressure — 40290 1 — Bit 10 Cool 3 High Pressure — 40290 1 — Bit 11 Cool 4 High Pressure — 40290 1 — Bit 12 Air Flow 2 Loss — 40290 1 — Bit 13 — 40016 1 10 deg C (R/W) Data Description Setpoints (View) Return Air Temperature Return Air Humidity — 40017 1 10 deg C (R/W) Supply Air Temperature — 40018 1 10 deg C (R/W) High Temp Alarm — 40025 1 10 deg C (R/W) Low Temp Alarm — 40026 1 10 deg C (R/W) High Hum Alarm — 40027 1 10 % (R/W) Low Hum Alarm — 40028 1 10 % (R/W) Restart Delay — 40029 1 — Seconds (R/W) Activation Mode — 40006 1 — 1=On / 0=Off (R/W) General Alarm Status — 40022 1 — 1=On / 0=Off; write 0 to reset alarm Control Points (Set) Audible Alarm Status — 40023 1 — 1=On / 0=Off; write 0 to ack alarm Return Air Temperature — 40349 1 10 deg C (R/W) Return Air Humidity — 40350 1 10 deg C (R/W) Supply Air Temperature — 40351 1 10 deg C (R/W) If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 157 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Thermal Management Products Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 158 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products 3.2 Power Distribution and Power Conditioning Products Table 3-31 Liebert FPC™, Liebert PPC™—Input and Holding Controller Power Monitoring Panel - PMP2 Liebert Products Liebert FPC Liebert PPC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Voltage In X-Y — 40001 1 — V Voltage In Y-Z — 40002 1 — V Voltage In Z-X — 40003 1 — V Data Description Status Points (View) Voltage Out A-B — 40004 1 — V Voltage Out B-C — 40005 1 — V Voltage Out C-A — 40006 1 — V Voltage Out A-N — 40007 1 — V Voltage Out B-N — 40008 1 — V Voltage Out C-N — 40009 1 — V Current Out A — 40010 1 — A Current Out B — 40011 1 — A Current Out C — 40012 1 — A Ground Current — 40013 1 10 A Neutral Current — 40014 1 — A kVA — 40015 1 — kVA kW — 40016 1 — kW Frequency — 40017 1 10 Hz % Capacity A — 40018 1 — % % Capacity B — 40019 1 — % % Capacity C — 40020 1 — % Power Factor — 40021 1 100 — Kilowatt Hours — — 1 — — THD Voltage X — — 1 — — THD Voltage Y — — 1 — — THD Voltage Z — — 1 — — THD Current X — — 1 — — THD Current Y — — 1 — — THD Current Z — — 1 — — K Factor Current X — — 1 — — K Factor Current Y — — 1 — — K Factor Current Z — — 1 — — CREST Factor Current X — — 1 — — CREST Factor Current Y — — 1 — — CREST Factor Current Z — — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value 159 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-31 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller Power Monitoring Panel - PMP2 Liebert Products Liebert FPC Liebert PPC Available Points Data Description Input Register Holding Register # of Reg. Scale Alarm Points Communications Notes / Units Discrete alarm objects available; use auto-discover for this unit — 40289 1 — Bit 0 Output Undervoltage — 40289 1 — Bit 1 Output Overvoltage — 40289 1 — Bit 2 Output Overcurrent — 40289 1 — Bit 3 Frequency Deviation — 40289 1 — Bit 4 Ground Overcurrent — 40289 1 — Bit 5 Transformer Overtemp — 40289 1 — Bit 6 Ground Fault — 40289 1 — Bit 7 Ground Failure — 40289 1 — Bit 8 Liquid Detected — 40289 1 — Bit 9 Security Alarm — 40289 1 — Bit 10 Phase Rotation/Loss — 40290 1 — Bit 0 Datawave Overtemperature — 40290 1 — Bit 1 Emergency Shutdown — 40290 1 — Bit 2 Load On Bypass — 40290 1 — Bit 3 Local Alarm #1 — 40290 1 — Bit 4 Local Alarm #2 — 40290 1 — Bit 5 Output Voltage THD — 40290 1 — Bit 6 Custom Alarm #1 — 40290 1 — Bit 7 Custom Alarm #2 — 40290 1 — Bit 8 — — 1 — — — — 1 — — Setpoints (View) None Control Points (Set) None If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 160 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-32 Liebert Datawave™, Liebert FPC™, Liebert PPC™—Input and Holding— PMP Option for Liebert FPC and Liebert PPC Controller Power Monitoring Panel - PMP Option for Liebert FPC and Liebert PPC Liebert Datawave Liebert Products Liebert FPC Liebert PPC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Voltage In X-Y — 40001 1 — V Voltage In Y-Z — 40002 1 — V Voltage In Z-X — 40003 1 — V Data Description Status Points (View) Voltage Out A-B — 40004 1 — V Voltage Out B-C — 40005 1 — V Voltage Out C-A — 40006 1 — V Voltage Out A-N — 40007 1 — V Voltage Out B-N — 40008 1 — V Voltage Out C-N — 40009 1 — V Current Out A — 40010 1 — A Current Out B — 40011 1 — A Current Out C — 40012 1 — A Ground Current — 40013 1 10 A Neutral Current — 40014 1 — A kVA — 40015 1 — kVA kW — 40016 1 — kW Frequency — 40017 1 10 Hz % Capacity A — 40018 1 — % % Capacity B — 40019 1 — % % Capacity C — 40020 1 — Alarm Points Communications % Discrete alarm objects available; use auto-discover for this unit — 40289 1 — Bit 0 Output Undervoltage — 40289 1 — Bit 1 Output Overvoltage — 40289 1 — Bit 2 Output Overcurrent — 40289 1 — Bit 3 Frequency Deviation — 40289 1 — Bit 4 Ground Overcurrent — 40289 1 — Bit 5 Transformer Overtemp — 40289 1 — Bit 6 Ground Fault — 40289 1 — Bit 7 Ground Failure — 40289 1 — Bit 8 Liquid Detected — 40289 1 — Bit 9 Security Alarm — 40289 1 — Bit 10 Phase Rotation/Loss — 40290 1 — Bit 0 Datawave Overtemperature — 40290 1 — Bit 1 Emergency Shutdown — 40290 1 — Bit 2 Load On Bypass — 40290 1 — Bit 3 Local Alarm — 40290 1 — Bit 4 Custom Alarm #1 — 40290 1 — Bit 5 161 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-32 Liebert Datawave™, Liebert FPC™, Liebert PPC™—Input and Holding— PMP Option for Liebert FPC and Liebert PPC (continued) Controller Power Monitoring Panel - PMP Option for Liebert FPC and Liebert PPC Liebert Datawave Liebert Products Liebert FPC Liebert PPC Available Points Data Description Input Register Holding Register # of Reg. Scale Notes / Units Custom Alarm #2 — 40290 1 — Bit 6 1 — — 1 — — Setpoints (View) None — Control Points (Set) None — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 162 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-33 Liebert FPC™, Liebert PPC™—Status and Coil Controller Liebert iCOM® v4 Liebert Products Liebert FPC, Liebert PPC Available Points Status Coil Number of Bits Scale Notes / Units Phase Loss 10001 — 1 — Active on Alarm Phase Rotation Error 10002 — 1 — Active on Alarm Phase Loss 10013 — 1 — Active on Alarm Phase Rotation Error 10014 — 1 — Active on Alarm 10025 — 1 — Active on Alarm Data Label Input Power 1 Input Power 2 (used only with 2nd VPMP controller) Output Power 1 Output Overvoltage Output Undervoltage 10026 — 1 — Active on Alarm Output Overcurrent 10027 — 1 — Active on Alarm Neutral Overcurrent 10028 — 1 — Active on Alarm Ground Overcurrent 10029 — 1 — Active on Alarm Output Voltage THD 10030 — 1 — Active on Alarm Frequency Deviation 10031 — 1 — Active on Alarm Transformer Overtemperature Power Off 10032 — 1 — Active on Alarm Transformer Overtemperature 10033 — 1 — Active on Alarm Transformer Temperature Sensor Fail 10034 — 1 — Active on Alarm Output Power 2 (used only with 2nd VPMP controller for Dual-output Transformer) Output Overvoltage 10045 — 1 — Active on Alarm Output Undervoltage 10046 — 1 — Active on Alarm Output Overcurrent 10047 — 1 — Active on Alarm Neutral Overcurrent 10048 — 1 — Active on Alarm Ground Overcurrent 10049 — 1 — Active on Alarm Output Voltage THD 10050 — 1 — Active on Alarm Frequency Deviation 10051 — 1 — Active on Alarm Transformer Overtemperature Power Off 10052 — 1 — Active on Alarm Transformer Overtemperature 10053 — 1 — Active on Alarm Transformer Temperature Sensor Fail 10054 — 1 — Active on Alarm Panel Summary Alarm 10065 — 1 — Active on Alarm Panel Overvoltage 10066 — 1 — Active on Alarm Panel Undervoltage 10067 — 1 — Active on Alarm Panel 1 Panel Phase Overcurrent 10068 — 1 — Active on Alarm Panel Phase Overcurrent 10069 — 1 — Active on Warning Panel Neutral Overcurrent 10070 — 1 — Active on Alarm Panel Ground Overcurrent 10071 — 1 — Active on Alarm Panel Summary Alarm 10082 — 1 — Active on Alarm Panel Overvoltage 10083 — 1 — Active on Alarm Panel Undervoltage 10084 — 1 — Active on Alarm Panel 2 Panel Phase Overcurrent 10085 — 1 — Active on Alarm Panel Phase Overcurrent 10086 — 1 — Active on Warning If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 163 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-33 Liebert FPC™, Liebert PPC™—Status and Coil (continued) Controller Liebert iCOM® v4 Liebert Products Liebert FPC, Liebert PPC Available Points Data Label Status Coil Number of Bits Scale Notes / Units Panel Neutral Overcurrent 10087 — 1 — Active on Alarm Panel Ground Overcurrent 10088 — 1 — Active on Alarm Panel Summary Alarm 10116 — 1 — Active on Alarm Panel Overvoltage 10117 — 1 — Active on Alarm Panel Undervoltage 10118 — 1 — Active on Alarm Panel 4 Panel Phase Overcurrent 10119 — 1 — Active on Alarm Panel Phase Overcurrent 10120 — 1 — Active on Warning Panel Neutral Overcurrent 10121 — 1 — Active on Alarm Panel Ground Overcurrent 10122 — 1 — Active on Alarm 10133 — 1 — Active on Alarm Branch Overcurrent 10134 — 1 — Active on Warning Branch Undercurrent Warning 10135 — 1 — Active on Alarm 10146 — 1 — Active on Alarm Branch Overcurrent 10147 — 1 — Active on Warning Branch Undercurrent Warning 10148 — 1 — Active on Alarm 11212 — 1 — Active on Alarm Panel 1 Position 1 Branch Overcurrent Panel 1 Position 2 Branch Overcurrent Panel 1 Position 84 Branch Overcurrent Branch Overcurrent 11213 — 1 — Active on Warning Branch Undercurrent Warning 11214 — 1 — Active on Alarm 11225 — 1 — Active on Alarm Panel 2 Position 1 Branch Overcurrent Branch Overcurrent 11226 — 1 — Active on Warning Branch Undercurrent Warning 11227 — 1 — Active on Alarm 11238 — 1 — Active on Alarm Panel 2 Position 2 Branch Overcurrent Branch Overcurrent 11239 — 1 — Active on Warning Branch Undercurrent Warning 11240 — 1 — Active on Alarm 12304 — 1 — Active on Alarm Branch Overcurrent 12305 — 1 — Active on Warning Branch Undercurrent Warning 12306 — 1 — Active on Alarm 12317 — 1 — Active on Alarm Branch Overcurrent 12318 — 1 — Active on Warning Branch Undercurrent Warning 12319 — 1 — Active on Alarm 12330 — 1 — Active on Alarm Branch Overcurrent 12331 — 1 — Active on Warning Branch Undercurrent Warning 12332 — 1 — Active on Alarm Panel 2 Position 84 Branch Overcurrent Panel 3 Position 1 Branch Overcurrent Panel 3 Position 2 Branch Overcurrent If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 164 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-33 Liebert FPC™, Liebert PPC™—Status and Coil (continued) Controller Liebert iCOM® v4 Liebert Products Liebert FPC, Liebert PPC Available Points Status Coil Number of Bits Scale Notes / Units 13396 — 1 — Active on Alarm Branch Overcurrent 13397 — 1 — Active on Warning Branch Undercurrent Warning 13398 — 1 — Active on Alarm Branch Overcurrent 13409 — 1 — Active on Alarm Branch Overcurrent 13410 — 1 — Active on Warning Branch Undercurrent Warning 13411 — 1 — Active on Alarm 13422 — 1 — Active on Alarm Branch Overcurrent 13423 — 1 — Active on Warning Branch Undercurrent Warning 13424 — 1 — Active on Alarm 14488 — 1 — Active on Alarm Branch Overcurrent 14489 — 1 — Active on Warning Branch Undercurrent Warning 14490 — 1 — Active on Alarm Subfeed Phase Overcurrent 14501 — 1 — Active on Alarm Subfeed Phase Overcurrent 14502 — 1 — Active on Warning Subfeed Neutral Overcurrent 14503 — 1 — Active on Alarm Subfeed Ground Overcurrent 14504 — 1 — Active on Alarm Data Label Panel 3 Position 84 Branch Overcurrent Panel 4 Position 1 Panel 4 Position 2 Branch Overcurrent Panel 4 Position 84 Branch Overcurrent Subfeed 1 Subfeed 2 Subfeed Phase Overcurrent 14515 — 1 — Active on Alarm Subfeed Phase Overcurrent 14516 — 1 — Active on Warning Subfeed Neutral Overcurrent 14517 — 1 — Active on Alarm Subfeed Ground Overcurrent 14518 — 1 — Active on Alarm Subfeed Phase Overcurrent 15383 — 1 — Active on Alarm Subfeed Phase Overcurrent 15384 — 1 — Active on Warning Subfeed Neutral Overcurrent 15385 — 1 — Active on Alarm Subfeed Ground Overcurrent 15386 — 1 — Active on Alarm Subfeed 64 Customer Events 1 (Alarms 1 - 5 for 1 VPMP, Alarms 6 - 10 only if 2nd VPMP is used) Event State 15397 — 1 — Active on Alarm 15408 — 1 — Active on Alarm 15496 — 1 — Active on Alarm Customer Events 2 Event State Customer Events 10 Event State If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 165 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-33 Liebert FPC™, Liebert PPC™—Status and Coil (continued) Controller Liebert iCOM® v4 Liebert Products Liebert FPC, Liebert PPC Available Points Data Label Status Coil Number of Bits Scale Notes / Units 15507 — 1 — Active on Alarm System System Shutdown - EPO System Shutdown - REPO 15508 — 1 — Active on Alarm Transformer Overtemperature Shutdown 15509 — 1 — Active on Alarm Transformer Overtemperature 15510 — 1 — Active on Alarm Equipment Temperature Sensor Fail 15511 — 1 — Active on Alarm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 166 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Input Voltage A-B 30385 — 1 — VAC Input Voltage B-C 30386 — 1 — VAC Input Voltage C-A 30387 — 1 — VAC Data Label Input Power 1 Input Power 2 (used only with 2nd VPMP controller) Input Voltage A-B 30391 — 1 — VAC Input Voltage B-C 30392 — 1 — VAC Input Voltage C-A 30393 — 1 — VAC Output Voltage X-Y 30397 — 1 — VAC Output Voltage Y-Z 30398 — 1 — VAC Output Voltage Z-X 30399 — 1 — VAC Output Voltage Vx 30400 — 1 — VAC Output Voltage Vy 30401 — 1 — VAC Output Voltage Vz 30402 — 1 — VAC Output Current Ix 30403 — 1 — A AC Output Current Iy 30404 — 1 — A AC Output Current Iz 30405 — 1 — A AC Output Power 1 — — Output Neutral Current 30406 — 1 — A AC Ground Current 30407 — 1 10 A AC Output Frequency 30408 — 1 — Hz Output Power (kVA) 30409 — 1 — kVA Output Power (kW) 30410 — 1 — kW Output kW-Hrs 30411 40411 2 — kWH Output Power Factor 30413 — 1 100 — Output Percent Load 30414 — 1 — % Output Voltage Vx THD 30415 — 1 10 % THD Output Voltage Vy THD 30416 — 1 10 % THD Output Voltage Vz THD 30417 — 1 10 % THD Output Current Ix THD 30418 — 1 10 % THD Output Current Iy THD 30419 — 1 10 % THD Output Current Iz THD 30420 — 1 10 % THD Output Current Ix K-Factor 30421 — 1 10 — Output Current Iy K-Factor 30422 — 1 10 — Output Current Iz K-Factor 30423 — 1 10 — Output Current Ix Crest Factor 30424 — 1 10 — Output Current Iy Crest Factor 30425 — 1 10 — Output Current Iz Crest Factor 30426 — 1 10 — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 167 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Data Label Input Register Holding Register # of Reg. Scale Notes / Units Output Power 2 (used only with 2nd VPMP controller) Output Voltage X-Y 30430 — 1 — VAC Output Voltage Y-Z 30431 — 1 — VAC Output Voltage Z-X 30432 — 1 — VAC Output Voltage Vx 30433 — 1 — VAC Output Voltage Vy 30434 — 1 — VAC Output Voltage Vz 30435 — 1 — VAC Output Current Ix 30436 — 1 — A AC Output Current Iy 30437 — 1 — A AC Output Current Iz 30438 — 1 — A AC Output Neutral Current 30439 — 1 — A AC Ground Current 30440 — 1 10 A AC Output Frequency 30441 — 1 — Hz Output Power (kVA) 30442 — 1 — kVA Output Power (kW) 30443 — 1 — kW Output kW-Hrs 30444 40444 2 — kWH Output Power Factor 30446 — 1 100 — Output Percent Load 30447 — 1 - % Output Voltage Vx THD 30448 — 1 10 % THD Output Voltage Vy THD 30449 — 1 10 % THD Output Voltage Vz THD 30450 — 1 10 % THD Output Current Ix THD 30451 — 1 10 % THD Output Current Iy THD 30452 — 1 10 % THD Output Current Iz THD 30453 — 1 10 % THD Output Current Ix K-Factor 30454 — 1 10 — Output Current Iy K-Factor 30455 — 1 10 — Output Current Iz K-Factor 30456 — 1 10 — Output Current Ix Crest Factor 30457 — 1 10 — Output Current Iy Crest Factor 30458 — 1 10 — Output Current Iz Crest Factor 30459 — 1 10 — 30463 — 1 — — Panel 1 Columns of Breakers Number of Breakers 30464 — 1 — — Panel Main Voltage X-Y 30465 — 1 — VAC Panel Main Voltage Y-Z 30466 — 1 — VAC Panel Main Voltage Z-X 30467 — 1 — VAC Panel Main Voltage X-N 30468 — 1 — VAC Panel Main Voltage Y-N 30469 — 1 — VAC Panel Main Voltage Z-N 30470 — 1 — VAC Panel Main Current Ix 30471 — 1 — A AC Panel Main Current Iy 30472 — 1 — A AC Panel Main Current Iz 30473 — 1 — A AC If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 168 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Data Label Input Register Holding Register # of Reg. Scale Notes / Units Panel Main Neutral Current 30474 — 1 — A AC Panel Main Ground Current 30475 — 1 10 A AC Panel Main Output Power (kVA) 30476 — 1 — kVA Panel Main Output Power (kW) 30477 — 1 — kW Panel Main Output kW-Hrs 30478 40478 2 10 kWH Panel Main Output Power Factor 30480 — 1 100 — Panel Main Output Percent Load 30481 — 1 — % Panel Main Voltage Vx THD 30482 — 1 10 % THD Panel Main Voltage Vy THD 30483 — 1 10 % THD Panel Main Voltage Vz THD 30484 — 1 10 % THD Panel Main Current Ix THD 30485 — 1 10 % THD Panel Main Current Iy THD 30486 — 1 10 % THD Panel Main Current Iz THD 30487 — 1 10 % THD Panel Main Current Ix Crest Factor 30488 — 1 10 — Panel Main Current Iy Crest Factor 30489 — 1 10 — Panel Main Current Iz Crest Factor 30490 — 1 10 — 30494 — 1 — — Panel 2 Columns of Breakers Number of Breakers 30495 — 1 — — Panel Main Voltage X-Y 30496 — 1 — VAC Panel Main Voltage Y-Z 30497 — 1 — VAC Panel Main Voltage Z-X 30498 — 1 — VAC Panel Main Voltage X-N 30499 — 1 — VAC Panel Main Voltage Y-N 30500 — 1 — VAC Panel Main Voltage Z-N 30501 — 1 — VAC Panel Main Current Ix 30502 — 1 — A AC Panel Main Current Iy 30503 — 1 — A AC Panel Main Current Iz 30504 — 1 — A AC Panel Main Neutral Current 30505 — 1 — A AC Panel Main Ground Current 30506 — 1 10 A AC Panel Main Output Power (kVA) 30507 — 1 — kVA Panel Main Output Power (kW) 30508 — 1 — kW Panel Main Output kW-Hrs 30509 40509 2 10 kWH Panel Main Output Power Factor 30511 — 1 100 — Panel Main Output Percent Load 30512 — 1 — % Panel Main Voltage Vx THD 30513 — 1 10 % THD Panel Main Voltage Vy THD 30514 — 1 10 % THD Panel Main Voltage Vz THD 30515 — 1 10 % THD Panel Main Current Ix THD 30516 — 1 10 % THD Panel Main Current Iy THD 30517 — 1 10 % THD Panel Main Current Iz THD 30518 — 1 10 % THD Panel Main Current Ix Crest Factor 30519 — 1 10 — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 169 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Panel Main Current Iy Crest Factor 30520 — 1 10 — Panel Main Current Iz Crest Factor 30521 — 1 10 — 30556 — 1 — — Data Label Panel 4 Columns of Breakers Number of Breakers 30557 — 1 — — Panel Main Voltage X-Y 30558 — 1 — VAC Panel Main Voltage Y-Z 30559 — 1 — VAC Panel Main Voltage Z-X 30560 — 1 — VAC Panel Main Voltage X-N 30561 — 1 — VAC Panel Main Voltage Y-N 30562 — 1 — VAC Panel Main Voltage Z-N 30563 — 1 — VAC Panel Main Current Ix 30564 — 1 — A AC Panel Main Current Iy 30565 — 1 — A AC Panel Main Current Iz 30566 — 1 — A AC Panel Main Neutral Current 30567 — 1 — A AC Panel Main Ground Current 30568 — 1 10 A AC Panel Main Output Power (kVA) 30569 — 1 — kVA Panel Main Output Power (kW) 30570 — 1 — kW Panel Main Output kW-Hrs 30571 40571 2 10 kWH Panel Main Output Power Factor 30573 — 1 100 — Panel Main Output Percent Load 30574 — 1 - % Panel Main Voltage Vx THD 30575 — 1 10 % THD Panel Main Voltage Vy THD 30576 — 1 10 % THD Panel Main Voltage Vz THD 30577 — 1 10 % THD Panel Main Current Ix THD 30578 — 1 10 % THD Panel Main Current Iy THD 30579 — 1 10 % THD Panel Main Current Iz THD 30580 — 1 10 % THD Panel Main Current Ix Crest Factor 30581 — 1 10 — Panel Main Current Iy Crest Factor 30582 — 1 10 — Panel Main Current Iz Crest Factor 30583 — 1 10 — Breaker position 30587 — 1 — — Branch Current Phase 1 30588 — 1 10 A AC Branch Current Phase 2 30589 — 1 10 A AC Panel 1 Position 1 Branch Current Phase 3 30590 — 1 10 A AC Branch Output Power (kW) 30591 — 1 1000 kW Output kW-Hrs 30592 — 2 1000 kWH Branch Output Power Factor 30594 — 1 100 - Branch Output Percent Load 30595 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 170 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Breaker position 30599 — 1 — — Branch Current Phase 1 30600 — 1 10 A AC Branch Current Phase 2 30601 — 1 10 A AC Data Label Panel 1 Position 2 Branch Current Phase 3 30602 — 1 10 A AC Branch Output Power (kW) 30603 — 1 1000 kW Output kW-Hrs 30604 — 2 1000 kWH Branch Output Power Factor 30606 — 1 100 — Branch Output Percent Load 30607 — 1 — % Panel 1 Position 84 Breaker position 31583 — 1 — — Branch Current Phase 1 31584 — 1 10 A AC Branch Current Phase 2 31585 — 1 10 A AC Branch Current Phase 3 31586 — 1 10 A AC Branch Output Power (kW) 31587 — 1 1000 kW Output kW-Hrs 31588 — 2 1000 kWH Branch Output Power Factor 31590 — 1 100 — Branch Output Percent Load 31591 — 1 — % Breaker position 31595 — 1 - — Branch Current Phase 1 31596 — 1 10 A AC Branch Current Phase 2 31597 — 1 10 A AC Panel 2 Position 1 Branch Current Phase 3 31598 — 1 10 A AC Branch Output Power (kW) 31599 — 1 1000 kW Output kW-Hrs 31600 — 2 1000 kWH Branch Output Power Factor 31602 — 1 100 — Branch Output Percent Load 31603 — 1 — % Panel 2 Position 2 Breaker position 31607 — 1 — — Branch Current Phase 1 31608 — 1 10 A AC Branch Current Phase 2 31609 — 1 10 A AC Branch Current Phase 3 31610 — 1 10 A AC Branch Output Power (kW) 31611 — 1 1000 kW Output kW-Hrs 31612 — 2 1000 kWH Branch Output Power Factor 31614 — 1 100 — Branch Output Percent Load 31615 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 171 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Breaker position 32591 — 1 — — Branch Current Phase 1 32592 — 1 10 A AC Branch Current Phase 2 32593 — 1 10 A AC Data Label Panel 2 Position 84 Branch Current Phase 3 32594 — 1 10 A AC Branch Output Power (kW) 32595 — 1 1000 kW Output kW-Hrs 32596 — 2 1000 kWH Branch Output Power Factor 32598 — 1 100 — Branch Output Percent Load 32599 — 1 — % Panel 3 Position 1 Breaker position 32603 — 1 — — Branch Current Phase 1 32604 — 1 10 A AC Branch Current Phase 2 32605 — 1 10 A AC Branch Current Phase 3 32606 — 1 10 A AC Branch Output Power (kW) 32607 — 1 1000 kW Output kW-Hrs 32608 — 2 1000 kWH Branch Output Power Factor 32610 — 1 100 — Branch Output Percent Load 32611 — 1 — % Breaker position 32615 — 1 — — Branch Current Phase 1 32616 — 1 10 A AC Branch Current Phase 2 32617 — 1 10 A AC Panel 3 Position 2 Branch Current Phase 3 32618 — 1 10 A AC Branch Output Power (kW) 32619 — 1 1000 kW Output kW-Hrs 32620 — 2 1000 kWH Branch Output Power Factor 32622 — 1 100 — Branch Output Percent Load 32623 — 1 — % Panel 3 Position 84 Breaker position 33599 — 1 — — Branch Current Phase 1 33600 — 1 10 A AC Branch Current Phase 2 33601 — 1 10 A AC Branch Current Phase 3 33602 — 1 10 A AC Branch Output Power (kW) 33603 — 1 1000 kW Output kW-Hrs 33604 — 2 1000 kWH Branch Output Power Factor 33606 — 1 100 — Branch Output Percent Load 33607 — 1 — % Panel 4 Position 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 172 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Input Register Holding Register # of Reg. Breaker position 33611 — 1 — — Branch Current Phase 1 33612 — 1 10 A AC Branch Current Phase 2 33613 — 1 10 A AC Branch Current Phase 3 33614 — 1 10 A AC Branch Output Power (kW) 33615 — 1 1000 kW Output kW-Hrs 33616 — 2 1000 kWH Branch Output Power Factor 33618 — 1 100 — Branch Output Percent Load 33619 — 1 — % Breaker position 33623 — 1 — — Branch Current Phase 1 33624 — 1 10 A AC Branch Current Phase 2 33625 — 1 10 A AC Data Label Scale Notes / Units Panel 4 Position 2 Branch Current Phase 3 33626 — 1 10 A AC Branch Output Power (kW) 33627 — 1 1000 kW Output kW-Hrs 33628 — 2 1000 kWH Branch Output Power Factor 33630 — 1 100 — Branch Output Percent Load 33631 — 1 - % Panel 4 Position 84 Breaker position 34607 — 1 — — Branch Current Phase 1 34608 — 1 10 A AC Branch Current Phase 2 34609 — 1 10 A AC Branch Current Phase 3 34610 — 1 10 A AC Branch Output Power (kW) 34611 — 1 1000 kW Output kW-Hrs 34612 — 2 1000 kWH Branch Output Power Factor 34614 — 1 100 — Branch Output Percent Load 34615 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 173 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Subfeed Current Ix 34619 — 1 — A AC Subfeed Current Iy 34620 — 1 — A AC Subfeed Current Iz 34621 — 1 — A AC Data Label Subfeed 1 Subfeed Neutral Current 34622 — 1 — A AC Subfeed Ground Current 34623 — 1 10 A AC Subfeed Output Power (kVA) 34624 — 1 — kVA Subfeed Output Power (kW) 34625 — 1 — kW Subfeed Output kW-Hrs 34626 44626 2 10 kWH Subfeed Power Factor 34628 — 1 100 — Subfeed Output Percent Load 34629 — 1 - % Subfeed Current Ix THD 34630 — 1 10 % Subfeed Current Iy THD 34631 — 1 10 % Subfeed Current Iz THD 34632 — 1 10 % Subfeed Current Ix Crest Factor 34633 — 1 10 — Subfeed Current Iy Crest Factor 34634 — 1 10 — Subfeed Current Iz Crest Factor 34635 — 1 10 — Subfeed Current Ix 34639 — 1 — A AC Subfeed Current Iy 34640 — 1 — A AC Subfeed Current Iz 34641 — 1 — A AC Subfeed Neutral Current 34642 — 1 — A AC Subfeed Ground Current 34643 — 1 10 A AC Subfeed Output Power (kVA) 34644 — 1 — kVA Subfeed 2 Subfeed Output Power (kW) 34645 — 1 — kW Subfeed Output kW-Hrs 34646 44646 2 10 kWH Subfeed Power Factor 34648 — 1 100 — Subfeed Output Percent Load 34649 — 1 - % Subfeed Current Ix THD 34650 — 1 10 % Subfeed Current Iy THD 34651 — 1 10 % Subfeed Current Iz THD 34652 — 1 10 % Subfeed Current Ix Crest Factor 34653 — 1 10 — Subfeed Current Iy Crest Factor 34654 — 1 10 — Subfeed Current Iz Crest Factor 34655 — 1 10 — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 174 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-34 Liebert FPC™, Liebert PPC™—Input and Holding (continued) Controller VPMP Liebert Products Liebert FPC, Liebert PPC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Subfeed Current Ix 35879 — 1 — A AC Subfeed Current Iy 35880 — 1 — A AC Subfeed Current Iz 35881 — 1 — A AC Data Label Subfeed 64 Subfeed Neutral Current 35882 — 1 — A AC Subfeed Ground Current 35883 — 1 10 A AC Subfeed Output Power (kVA) 35884 — 1 — kVA Subfeed Output Power (kW) 35885 — 1 — kW Subfeed Output kW-Hrs 35886 45886 2 10 kWH Subfeed Power Factor 35888 — 1 100 — Subfeed Output Percent Load 35889 — 1 - % Subfeed Current Ix THD 35890 — 1 10 % Subfeed Current Iy THD 35891 — 1 10 % Subfeed Current Iz THD 35892 — 1 10 % Subfeed Current Ix Crest Factor 35893 — 1 10 — Subfeed Current Iy Crest Factor 35894 — 1 10 — Subfeed Current Iz Crest Factor 35895 — 1 10 — System System Status System Event Acknowledge/Reset System Date and Time 35899 — 1 — 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation — 45900 1 — 2 = Reset 4 = Acknowledge 39998 49998 2 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 175 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-35 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Status and Coil Controller Liebert LDMF Liebert Products Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Data Label Status Coil Number of Bits Scale Notes / Units Panel 1 – Panelboard Main 1 (if panelboards are installed) Panel Summary Alarm 10065 — 1 — Active on Alarm Panel Overvoltage 10066 — 1 — Active on Alarm Panel Undervoltage 10067 — 1 — Active on Alarm Panel Phase Overcurrent 10068 — 1 — Active on Alarm Panel Phase Overcurrent 10069 — 1 — Active on Warning Panel Neutral Overcurrent 10070 — 1 — Active on Alarm Panel Ground Overcurrent 10071 — 1 — Active on Alarm Panel 2 – Panelboard Main 2 (if panelboards are installed) Panel Summary Alarm 10082 — 1 — Active on Alarm Panel Overvoltage 10083 — 1 — Active on Alarm Panel Undervoltage 10084 — 1 — Active on Alarm Panel Phase Overcurrent 10085 — 1 — Active on Alarm Panel Phase Overcurrent 10086 — 1 — Active on Warning Panel Neutral Overcurrent 10087 — 1 — Active on Alarm Panel Ground Overcurrent 10088 — 1 — Active on Alarm Panel 4 – Panelboard Main 4 (if panelboards are installed) Panel Summary Alarm 10116 — 1 — Active on Alarm Panel Overvoltage 10117 — 1 — Active on Alarm Panel Undervoltage 10118 — 1 — Active on Alarm Panel Phase Overcurrent 10119 — 1 — Active on Alarm Panel Phase Overcurrent 10120 — 1 — Active on Warning Panel Neutral Overcurrent 10121 — 1 — Active on Alarm Panel Ground Overcurrent 10122 — 1 — Active on Alarm Branch Overcurrent 10133 — 1 — Active on Alarm Branch Overcurrent 10134 — 1 — Active on Warning Branch Undercurrent Warning 10135 — 1 — Active on Alarm Branch Overcurrent 10146 — 1 — Active on Alarm Branch Overcurrent 10147 — 1 — Active on Warning Branch Undercurrent Warning 10148 — 1 — Active on Alarm Branch Overcurrent 11212 — 1 — Active on Alarm Branch Overcurrent 11213 — 1 — Active on Warning Branch Undercurrent Warning 11214 — 1 — Active on Alarm Branch Overcurrent 11225 — 1 — Active on Alarm Branch Overcurrent 11226 — 1 — Active on Warning Branch Undercurrent Warning 11227 — 1 — Active on Alarm Panel 1 Position 1 Panel 1 Position 2 Panel 1 Position 84 Panel 2 Position 1 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 176 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-35 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Status and Coil (continued) Controller Liebert LDMF Liebert Products Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Status Coil Number of Bits Scale Notes / Units Branch Overcurrent 11238 — 1 — Active on Alarm Branch Overcurrent 11239 — 1 — Active on Warning Branch Undercurrent Warning 11240 — 1 — Active on Alarm Branch Overcurrent 12304 — 1 — Active on Alarm Branch Overcurrent 12305 — 1 — Active on Warning Branch Undercurrent Warning 12306 — 1 — Active on Alarm Branch Overcurrent 12317 — 1 — Active on Alarm Branch Overcurrent 12318 — 1 — Active on Warning Branch Undercurrent Warning 12319 — 1 — Active on Alarm Branch Overcurrent 12330 — 1 — Active on Alarm Branch Overcurrent 12331 — 1 — Active on Warning Branch Undercurrent Warning 12332 — 1 — Active on Alarm Branch Overcurrent 13396 — 1 — Active on Alarm Branch Overcurrent 13397 — 1 — Active on Warning Branch Undercurrent Warning 13398 — 1 — Active on Alarm Branch Overcurrent 13409 — 1 — Active on Alarm Branch Overcurrent 13410 — 1 — Active on Warning Branch Undercurrent Warning 13411 — 1 — Active on Alarm Panel 4 Position 2 Branch Overcurrent 13422 — 1 — Active on Alarm Branch Overcurrent 13423 — 1 — Active on Warning Branch Undercurrent Warning 13424 — 1 — Active on Alarm Branch Overcurrent 14488 — 1 — Active on Alarm Branch Overcurrent 14489 — 1 — Active on Warning Branch Undercurrent Warning 14490 — 1 — Active on Alarm 14501 — 1 — Active on Alarm Data Label Panel 2 Position 2 Panel 2 Position 84 Panel 3 Position 1 Panel 3 Position 2 Panel 3 Position 84 Panel 4 Position 1 Panel 4 Position 84 Subfeed 1 Subfeed Phase Overcurrent Subfeed Phase Overcurrent 14502 — 1 — Active on Warning Subfeed Neutral Overcurrent 14503 — 1 — Active on Alarm Subfeed Ground Overcurrent 14504 — 1 — Active on Alarm 177 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-35 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Status and Coil (continued) Controller Liebert LDMF Liebert Products Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Data Label Status Coil Number of Bits Scale Notes / Units 14515 — 1 — Active on Alarm Subfeed 2 Subfeed Phase Overcurrent Subfeed Phase Overcurrent 14516 — 1 — Active on Warning Subfeed Neutral Overcurrent 14517 — 1 — Active on Alarm Subfeed Ground Overcurrent 14518 — 1 — Active on Alarm Subfeed 64 Subfeed Phase Overcurrent 15383 — 1 — Active on Alarm Subfeed Phase Overcurrent 15384 — 1 — Active on Warning Subfeed Neutral Overcurrent 15385 — 1 — Active on Alarm Subfeed Ground Overcurrent 15386 — 1 — Active on Alarm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 178 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Input and Holding Controller Liebert Products Liebert LDMF Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Data Label Input Register Holding Register # of Reg. Scale Notes / Units Panel 1 Columns of Breakers 30463 — 1 — — Number of Breakers 30464 — 1 — — Panel Main Voltage X-Y 30465 — 1 — VAC Panel Main Voltage Y-Z 30466 — 1 — VAC Panel Main Voltage Z-X 30467 — 1 — VAC Panel Main Voltage X-N 30468 — 1 — VAC Panel Main Voltage Y-N 30469 — 1 — VAC Panel Main Voltage Z-N 30470 — 1 — VAC Panel Main Current Ix 30471 — 1 — A AC Panel Main Current Iy 30472 — 1 — A AC Panel Main Current Iz 30473 — 1 — A AC Panel Main Neutral Current 30474 — 1 — A AC Panel Main Ground Current 30475 — 1 10 A AC Panel Main Output Power (kVA) 30476 — 1 — kVA Panel Main Output Power (kW) 30477 — 1 — kW Panel Main Output kW-Hrs 30478 40478 2 10 kWH Panel Main Output Power Factor 30480 — 1 100 — Panel Main Output Percent Load 30481 — 1 — % Panel Main Voltage Vx THD 30482 — 1 10 % THD Panel Main Voltage Vy THD 30483 — 1 10 % THD Panel Main Voltage Vz THD 30484 — 1 10 % THD Panel Main Current Ix THD 30485 — 1 10 % THD Panel Main Current Iy THD 30486 — 1 10 % THD Panel Main Current Iz THD 30487 — 1 10 % THD Panel Main Current Ix Crest Factor 30488 — 1 10 — Panel Main Current Iy Crest Factor 30489 — 1 10 — Panel Main Current Iz Crest Factor 30490 — 1 10 — Panel 2 Columns of Breakers 30494 — 1 — — Number of Breakers 30495 — 1 — — Panel Main Voltage X-Y 30496 — 1 — VAC Panel Main Voltage Y-Z 30497 — 1 — VAC Panel Main Voltage Z-X 30498 — 1 — VAC Panel Main Voltage X-N 30499 — 1 — VAC Panel Main Voltage Y-N 30500 — 1 — VAC Panel Main Voltage Z-N 30501 — 1 — VAC If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 179 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued) Controller Liebert Products Liebert LDMF Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Input Register Holding Register # of Reg. Scale Notes / Units Panel Main Current Ix 30502 — 1 — A AC Panel Main Current Iy 30503 — 1 — A AC Panel Main Current Iz 30504 — 1 — A AC Panel Main Neutral Current 30505 — 1 — A AC Panel Main Ground Current 30506 — 1 10 A AC Data Label Panel Main Output Power (kVA) 30507 — 1 — kVA Panel Main Output Power (kW) 30508 — 1 — kW Panel Main Output kW-Hrs 30509 40509 2 10 kWH Panel Main Output Power Factor 30511 — 1 100 — Panel Main Output Percent Load 30512 — 1 — % Panel Main Voltage Vx THD 30513 — 1 10 % THD Panel Main Voltage Vy THD 30514 — 1 10 % THD Panel Main Voltage Vz THD 30515 — 1 10 % THD Panel Main Current Ix THD 30516 — 1 10 % THD Panel Main Current Iy THD 30517 — 1 10 % THD Panel Main Current Iz THD 30518 — 1 10 % THD Panel Main Current Ix Crest Factor 30519 — 1 10 — Panel Main Current Iy Crest Factor 30520 — 1 10 — Panel Main Current Iz Crest Factor 30521 — 1 10 — 30556 — 1 — — Number of Breakers 30557 — 1 — — Panel Main Voltage X-Y 30558 — 1 — VAC Panel Main Voltage Y-Z 30559 — 1 — VAC Panel Main Voltage Z-X 30560 — 1 — VAC Panel Main Voltage X-N 30561 — 1 — VAC Panel Main Voltage Y-N 30562 — 1 — VAC Panel Main Voltage Z-N 30563 — 1 — VAC Panel Main Current Ix 30564 — 1 — A AC Panel Main Current Iy 30565 — 1 — A AC Panel Main Current Iz 30566 — 1 — A AC Panel Main Neutral Current 30567 — 1 — A AC Panel Main Ground Current 30568 — 1 10 A AC Panel 4 Columns of Breakers Panel Main Output Power (kVA) 30569 — 1 — kVA Panel Main Output Power (kW) 30570 — 1 — kW Panel Main Output kW-Hrs 30571 40571 2 10 kWH Panel Main Output Power Factor 30573 — 1 100 — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 180 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued) Controller Liebert Products Liebert LDMF Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Data Label Panel Main Output Percent Load Input Register Holding Register # of Reg. Scale Notes / Units 30574 — 1 - % Panel Main Voltage Vx THD 30575 — 1 10 % THD Panel Main Voltage Vy THD 30576 — 1 10 % THD Panel Main Voltage Vz THD 30577 — 1 10 % THD Panel Main Current Ix THD 30578 — 1 10 % THD Panel Main Current Iy THD 30579 — 1 10 % THD Panel Main Current Iz THD 30580 — 1 10 % THD Panel Main Current Ix Crest Factor 30581 — 1 10 — Panel Main Current Iy Crest Factor 30582 — 1 10 — Panel Main Current Iz Crest Factor 30583 — 1 10 — Breaker position 30587 — 1 — — Branch Current Phase 1 30588 — 1 10 A AC Branch Current Phase 2 30589 — 1 10 A AC Branch Current Phase 3 30590 — 1 10 A AC Branch Output Power (kW) 30591 — 1 1000 kW Output kW-Hrs 30592 — 2 1000 kWH Branch Output Power Factor 30594 — 1 100 - Branch Output Percent Load 30595 — 1 — % Breaker position 30599 — 1 — — Branch Current Phase 1 30600 — 1 10 A AC Branch Current Phase 2 30601 — 1 10 A AC Branch Current Phase 3 30602 — 1 10 A AC Branch Output Power (kW) 30603 — 1 1000 kW Output kW-Hrs 30604 — 2 1000 kWH Branch Output Power Factor 30606 — 1 100 — Branch Output Percent Load 30607 — 1 — % Breaker position 31583 — 1 — — Branch Current Phase 1 31584 — 1 10 A AC Branch Current Phase 2 31585 — 1 10 A AC Branch Current Phase 3 31586 — 1 10 A AC Branch Output Power (kW) 31587 — 1 1000 kW Panel 1 Position 1 Panel 1 Position 2 Panel 1 Position 84 Output kW-Hrs 31588 — 2 1000 kWH Branch Output Power Factor 31590 — 1 100 — Branch Output Percent Load 31591 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 181 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued) Controller Liebert Products Liebert LDMF Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Input Register Holding Register # of Reg. Breaker position 31595 — 1 — — Branch Current Phase 1 31596 — 1 10 A AC Branch Current Phase 2 31597 — 1 10 A AC Branch Current Phase 3 31598 — 1 10 A AC Branch Output Power (kW) 31599 — 1 1000 kW Output kW-Hrs 31600 — 2 1000 kWH Branch Output Power Factor 31602 — 1 100 — Branch Output Percent Load 31603 — 1 — % Breaker position 31607 — 1 — — Branch Current Phase 1 31608 — 1 10 A AC Branch Current Phase 2 31609 — 1 10 A AC Branch Current Phase 3 31610 — 1 10 A AC Branch Output Power (kW) 31611 — 1 1000 kW Output kW-Hrs 31612 — 2 1000 kWH Branch Output Power Factor 31614 — 1 100 — Branch Output Percent Load 31615 — 1 — % Breaker position 32591 — 1 — — Branch Current Phase 1 32592 — 1 10 A AC Branch Current Phase 2 32593 — 1 10 A AC Branch Current Phase 3 32594 — 1 10 A AC Branch Output Power (kW) 32595 — 1 1000 kW Output kW-Hrs 32596 — 2 1000 kWH Branch Output Power Factor 32598 — 1 100 — Branch Output Percent Load 32599 — 1 — % Breaker position 32603 — 1 — — Branch Current Phase 1 32604 — 1 10 A AC Branch Current Phase 2 32605 — 1 10 A AC Branch Current Phase 3 32606 — 1 10 A AC Branch Output Power (kW) 32607 — 1 1000 kW Data Label Scale Notes / Units Panel 2 Position 1 Panel 2 Position 2 Panel 2 Position 84 Panel 3 Position 1 Output kW-Hrs 32608 — 2 1000 kWH Branch Output Power Factor 32610 — 1 100 — Branch Output Percent Load 32611 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 182 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued) Controller Liebert Products Liebert LDMF Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Input Register Holding Register # of Reg. Breaker position 32615 — 1 — — Branch Current Phase 1 32616 — 1 10 A AC Branch Current Phase 2 32617 — 1 10 A AC Branch Current Phase 3 32618 — 1 10 A AC Branch Output Power (kW) 32619 — 1 1000 kW Output kW-Hrs 32620 — 2 1000 kWH Branch Output Power Factor 32622 — 1 100 — Branch Output Percent Load 32623 — 1 — % Breaker position 33599 — 1 — — Branch Current Phase 1 33600 — 1 10 A AC Branch Current Phase 2 33601 — 1 10 A AC Data Label Scale Notes / Units Panel 3 Position 2 Panel 3 Position 84 Branch Current Phase 3 33602 — 1 10 A AC Branch Output Power (kW) 33603 — 1 1000 kW Output kW-Hrs 33604 — 2 1000 kWH Branch Output Power Factor 33606 — 1 100 — Branch Output Percent Load 33607 — 1 — % Breaker position 33611 — 1 — — Branch Current Phase 1 33612 — 1 10 A AC Branch Current Phase 2 33613 — 1 10 A AC Branch Current Phase 3 33614 — 1 10 A AC Branch Output Power (kW) 33615 — 1 1000 kW Output kW-Hrs 33616 — 2 1000 kWH Branch Output Power Factor 33618 — 1 100 — Branch Output Percent Load 33619 — 1 — % Breaker position 33623 — 1 — — Branch Current Phase 1 33624 — 1 10 A AC Branch Current Phase 2 33625 — 1 10 A AC Branch Current Phase 3 33626 — 1 10 A AC Branch Output Power (kW) 33627 — 1 1000 kW Panel 4 Position 1 Panel 4 Position 2 Output kW-Hrs 33628 — 2 1000 kWH Branch Output Power Factor 33630 — 1 100 — Branch Output Percent Load 33631 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 183 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued) Controller Liebert Products Liebert LDMF Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Input Register Holding Register # of Reg. Breaker position 34607 — 1 — — Branch Current Phase 1 34608 — 1 10 A AC Branch Current Phase 2 34609 — 1 10 A AC Branch Current Phase 3 34610 — 1 10 A AC Branch Output Power (kW) 34611 — 1 1000 kW Output kW-Hrs 34612 — 2 1000 kWH Branch Output Power Factor 34614 — 1 100 — Branch Output Percent Load 34615 — 1 — % Subfeed Current Ix 34619 — 1 — A AC Subfeed Current Iy 34620 — 1 — A AC Subfeed Current Iz 34621 — 1 — A AC Subfeed Neutral Current 34622 — 1 — A AC Subfeed Ground Current 34623 — 1 10 A AC Subfeed Output Power (kVA) 34624 — 1 — kVA Subfeed Output Power (kW) 34625 — 1 — kW Subfeed Output kW-Hrs 34626 44626 2 10 kWH Subfeed Power Factor 34628 — 1 100 — Subfeed Output Percent Load 34629 — 1 — % Subfeed Current Ix THD 34630 — 1 10 % Subfeed Current Iy THD 34631 — 1 10 % Subfeed Current Iz THD 34632 — 1 10 % Subfeed Current Ix Crest Factor 34633 — 1 10 — Subfeed Current Iy Crest Factor 34634 — 1 10 — Subfeed Current Iz Crest Factor 34635 — 1 10 — Subfeed Current Ix 34639 — 1 — A AC Subfeed Current Iy 34640 — 1 — A AC Subfeed Current Iz 34641 — 1 — A AC Subfeed Neutral Current 34642 — 1 — A AC Subfeed Ground Current 34643 — 1 10 A AC Subfeed Output Power (kVA) 34644 — 1 — kVA Data Label Scale Notes / Units Panel 4 Position 84 Subfeed 1 Subfeed 2 Subfeed Output Power (kW) 34645 — 1 — kW Subfeed Output kW-Hrs 34646 44646 2 10 kWH Subfeed Power Factor 34648 — 1 100 — Subfeed Output Percent Load 34649 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 184 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-36 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Input and Holding (continued) Controller Liebert Products Liebert LDMF Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX, Liebert STS2/PDU Available Points Input Register Holding Register # of Reg. Scale Notes / Units Subfeed Current Ix THD 34650 — 1 10 % Subfeed Current Iy THD 34651 — 1 10 % Subfeed Current Iz THD 34652 — 1 10 % Subfeed Current Ix Crest Factor 34653 — 1 10 — Subfeed Current Iy Crest Factor 34654 — 1 10 — Subfeed Current Iz Crest Factor 34655 — 1 10 — Subfeed Current Ix 35879 — 1 — A AC Subfeed Current Iy 35880 — 1 — A AC Subfeed Current Iz 35881 — 1 — A AC Subfeed Neutral Current 35882 — 1 — A AC Subfeed Ground Current 35883 — 1 10 A AC Subfeed Output Power (kVA) 35884 — 1 — kVA Data Label Subfeed 64 Subfeed Output Power (kW) 35885 — 1 — kW Subfeed Output kW-Hrs 35886 45886 2 10 kWH Subfeed Power Factor 35888 — 1 100 — Subfeed Output Percent Load 35889 — 1 - % Subfeed Current Ix THD 35890 — 1 10 % Subfeed Current Iy THD 35891 — 1 10 % Subfeed Current Iz THD 35892 — 1 10 % Subfeed Current Ix Crest Factor 35893 — 1 10 — Subfeed Current Iy Crest Factor 35894 — 1 10 — Subfeed Current Iz Crest Factor 35895 — 1 10 — System System Status System Event Acknowledge/Reset System Date and Time 35899 — 1 — 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation — 45900 1 — 2 = Reset 4= Acknowledge 39998 49998 2 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 185 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-37 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Status and Coil Controller Liebert CPM Liebert Products Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC Available Points Data Label Status Coil Number of Bits Scale Notes / Units Panel 1 – Panelboard Main 1 (if panelboards are installed) Panel Summary Alarm 10065 — 1 — Active on Alarm Panel Overvoltage 10066 — 1 — Active on Alarm Panel Undervoltage 10067 — 1 — Active on Alarm Panel Phase Overcurrent 10068 — 1 — Active on Alarm Panel Phase Overcurrent 10069 — 1 — Active on Warning Panel Neutral Overcurrent 10070 — 1 — Active on Alarm Panel Ground Overcurrent 10071 — 1 — Active on Alarm Panel 2 – Panelboard Main 2 (if panelboards are installed) Panel Summary Alarm 10082 — 1 — Active on Alarm Panel Overvoltage 10083 — 1 — Active on Alarm Panel Undervoltage 10084 — 1 — Active on Alarm Panel Phase Overcurrent 10085 — 1 — Active on Alarm Panel Phase Overcurrent 10086 — 1 — Active on Warning Panel Neutral Overcurrent 10087 — 1 — Active on Alarm Panel Ground Overcurrent 10088 — 1 — Active on Alarm Panel 4 – Panelboard Main 4 (if panelboards are installed) Panel Summary Alarm 10116 — 1 — Active on Alarm Panel Overvoltage 10117 — 1 — Active on Alarm Panel Undervoltage 10118 — 1 — Active on Alarm Panel Phase Overcurrent 10119 — 1 — Active on Alarm Panel Phase Overcurrent 10120 — 1 — Active on Warning Panel Neutral Overcurrent 10121 — 1 — Active on Alarm Panel Ground Overcurrent 10122 — 1 — Active on Alarm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 186 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-38 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Input and Holding Controller Liebert Products Liebert CPM Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Columns of Breakers 30463 — 1 — — Number of Breakers 30464 — 1 — — Panel Main Voltage X-Y 30465 — 1 — VAC Panel Main Voltage Y-Z 30466 — 1 — VAC Panel Main Voltage Z-X 30467 — 1 — VAC Panel Main Voltage X-N 30468 — 1 — VAC Panel Main Voltage Y-N 30469 — 1 — VAC Data Label Panel 1 Panel Main Voltage Z-N 30470 — 1 — VAC Panel Main Current Ix 30471 — 1 — A AC Panel Main Current Iy 30472 — 1 — A AC Panel Main Current Iz 30473 — 1 — A AC Panel Main Neutral Current 30474 — 1 — A AC Panel Main Ground Current 30475 — 1 10 A AC Panel Main Output Power (kVA) 30476 — 1 — kVA Panel Main Output Power (kW) 30477 — 1 — kW Panel Main Output kW-Hrs 30478 40478 2 10 kWH Panel Main Output Power Factor 30480 — 1 100 — Panel Main Output Percent Load 30481 — 1 — % Panel Main Voltage Vx THD 30482 — 1 10 % THD Panel Main Voltage Vy THD 30483 — 1 10 % THD Panel Main Voltage Vz THD 30484 — 1 10 % THD Panel Main Current Ix THD 30485 — 1 10 % THD Panel Main Current Iy THD 30486 — 1 10 % THD Panel Main Current Iz THD 30487 — 1 10 % THD Panel Main Current Ix Crest Factor 30488 — 1 10 — Panel Main Current Iy Crest Factor 30489 — 1 10 — Panel Main Current Iz Crest Factor 30490 — 1 10 — Columns of Breakers 30494 — 1 — — Number of Breakers 30495 — 1 — — Panel Main Voltage X-Y 30496 — 1 — VAC Panel Main Voltage Y-Z 30497 — 1 — VAC Panel Main Voltage Z-X 30498 — 1 — VAC Panel Main Voltage X-N 30499 — 1 — VAC Panel Main Voltage Y-N 30500 — 1 — VAC Panel 2 Panel Main Voltage Z-N 30501 — 1 — VAC Panel Main Current Ix 30502 — 1 — A AC Panel Main Current Iy 30503 — 1 — A AC Panel Main Current Iz 30504 — 1 — A AC Panel Main Neutral Current 30505 — 1 — A AC If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 187 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-38 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Input and Holding (continued) Controller Liebert Products Liebert CPM Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Panel Main Ground Current 30506 — 1 10 A AC Panel Main Output Power (kVA) 30507 — 1 — kVA Data Label Panel Main Output Power (kW) 30508 — 1 — kW Panel Main Output kW-Hrs 30509 40509 2 10 kWH Panel Main Output Power Factor 30511 — 1 100 — Panel Main Output Percent Load 30512 — 1 — % Panel Main Voltage Vx THD 30513 — 1 10 % THD Panel Main Voltage Vy THD 30514 — 1 10 % THD Panel Main Voltage Vz THD 30515 — 1 10 % THD Panel Main Current Ix THD 30516 — 1 10 % THD Panel Main Current Iy THD 30517 — 1 10 % THD Panel Main Current Iz THD 30518 — 1 10 % THD Panel Main Current Ix Crest Factor 30519 — 1 10 — Panel Main Current Iy Crest Factor 30520 — 1 10 — Panel Main Current Iz Crest Factor 30521 — 1 10 — Panel 4 Columns of Breakers 30556 — 1 — — Number of Breakers 30557 — 1 — — Panel Main Voltage X-Y 30558 — 1 — VAC Panel Main Voltage Y-Z 30559 — 1 — VAC Panel Main Voltage Z-X 30560 — 1 — VAC Panel Main Voltage X-N 30561 — 1 — VAC Panel Main Voltage Y-N 30562 — 1 — VAC Panel Main Voltage Z-N 30563 — 1 — VAC Panel Main Current Ix 30564 — 1 — A AC Panel Main Current Iy 30565 — 1 — A AC Panel Main Current Iz 30566 — 1 — A AC Panel Main Neutral Current 30567 — 1 — A AC Panel Main Ground Current 30568 — 1 10 A AC Panel Main Output Power (kVA) 30569 — 1 — kVA Panel Main Output Power (kW) 30570 — 1 — kW Panel Main Output kW-Hrs 30571 40571 2 10 kWH Panel Main Output Power Factor 30573 — 1 100 — Panel Main Output Percent Load 30574 — 1 - % Panel Main Voltage Vx THD 30575 — 1 10 % THD Panel Main Voltage Vy THD 30576 — 1 10 % THD Panel Main Voltage Vz THD 30577 — 1 10 % THD Panel Main Current Ix THD 30578 — 1 10 % THD Panel Main Current Iy THD 30579 — 1 10 % THD Panel Main Current Iz THD 30580 — 1 10 % THD Panel Main Current Ix Crest Factor 30581 — 1 10 — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 188 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-38 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™—Input and Holding (continued) Controller Liebert Products Liebert CPM Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC Available Points Input Register Holding Register # of Reg. Scale Notes / Units Panel Main Current Iy Crest Factor 30582 — 1 10 — Panel Main Current Iz Crest Factor 30583 — 1 10 — Data Label System System Status System Event Acknowledge/Reset System Date and Time 35899 — 1 — 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation — 45900 1 — 2 = Reset 4 = Acknowledge 39998 49998 2 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 189 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-39 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Glossary Data Label Data Description Branch Current Phase 1 Branch breaker Phase 1 RMS current Branch Current Phase 2 Branch Breaker Phase 2 RMS current Branch Current Phase 3 Branch breaker Phase 3 RMS current Branch Output Percent Load Branch breaker percent load of rated current Branch Output Power (W) Branch breaker W Branch Output Power Factor Branch breaker Power Factor (real power/apparent power) Branch Overcurrent Branch breaker current has exceeded the limit. Branch Undercurrent Warning Branch breaker current is less than the limit. Breaker position Panelboard pole position of the branch breaker. First position if 2 or 3 pole breaker Columns of Breakers The breakers in this panel are physically arranged in this many columns. Equipment Temperature Sensor Fail Transformer temperature sensor has failed Event State Alarm present Frequency Deviation The output frequency is outside a specified range. Ground Current Unit Ground RMS current. Ground Overcurrent Unit ground current has exceeded the limit. Input Voltage A-B Unit Input RMS Voltage between Phase A and Phase B Input Voltage B-C Unit Input RMS Voltage between Phase B and Phase C Input Voltage C-A Unit Input RMS Voltage between Phase C and Phase A Neutral Overcurrent Unit neutral current has exceeded the limit. Number of Breakers Number of Breakers in this panelboard. Output Current Ix Crest Factor Unit phase X Current Crest Factor (peak/RMS). Output Current Ix K-Factor Unit output Current Harmonic K-Factor for phase X. Output Current Ix THD Unit Current Total Harmonic Distortion for phase X. Output Current Ix Unit Phase X output RMS current. Output Current Iy Crest Factor Unit phase Y Current Crest Factor (peak/RMS). Output Current Iy K-Factor Unit output Current Harmonic K-Factor for phase Y. Output Current Iy THD Unit Current Total Harmonic Distortion for phase Y. Output Current Iy Unit Phase Y output RMS current. Output Current Iz Crest Factor Unit phase Z Current Crest Factor (peak/RMS). Output Current Iz K-Factor Unit output Current Harmonic K-Factor for phase Z. Output Current Iz THD Unit Current Total Harmonic Distortion for phase Z. Output Current Iz Unit Phase Z output RMS current. Output Frequency The system output frequency. Output kW-Hrs Branch Breaker accumulated KW-Hours since last KW-Hours reset. Output kW-Hrs Unit accumulated KW-Hours since last KW-Hours reset. Output Neutral Current Unit output Neutral RMS current. Output Overcurrent Unit phase current has exceeded the limit. Output Overvoltage Unit voltage has exceeded the limit. Output Percent Load Unit percent load of rated current Output Power (kVA) Unit output kVA Output Power (kW) Unit output KW Output Power Factor Unit output Power Factor (real power/apparent power) Output Undervoltage Unit voltage is less than the limit. Output Voltage THD Unit output Voltage Total Harmonic Distortion has exceeded the limit. Output Voltage Vx THD Unit Voltage Total Harmonic Distortion for phase X. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 190 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-39 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Glossary (continued) Data Label Data Description Output Voltage Vx Unit output RMS voltage between phase X and Neutral Output Voltage Vy THD Unit Voltage Total Harmonic Distortion for phase Y. Output Voltage Vy Unit output RMS voltage between phase Y and Neutral Output Voltage Vz THD Unit Voltage Total Harmonic Distortion for phase Z. Output Voltage Vz Unit output RMS voltage between phase Z and Neutral Output Voltage X-Y Unit output RMS voltage between phases X and Y Output Voltage Y-Z Unit output RMS voltage between phases Y and Z. Output Voltage Z-X Unit output RMS voltage between phases Z and X. Panel Ground Overcurrent Panelboard Ground current has exceeded the limit. Panel Main Current Ix Crest Factor Panelboard phase X Current Crest Factor (peak/RMS). Panel Main Current Ix THD Current Total Harmonic Distortion for Panelboard phase X. Panel Main Current Ix Panelboard RMS current for phase X. Panel Main Current Iy Crest Factor Panelboard phase Y Current Crest Factor (peak/RMS). Panel Main Current Iy THD Current Total Harmonic Distortion for Panelboard phase Y. Panel Main Current Iy Panelboard RMS current for phase Y. Panel Main Current Iz Crest Factor Panelboard phase Z Current Crest Factor (peak/RMS). Panel Main Current Iz THD Current Total Harmonic Distortion for Panelboard phase Z. Panel Main Current Iz Panelboard RMS current for phase Z. Panel Main Ground Current Panelboard Ground RMS current. Panel Main Neutral Current Panelboard Neutral RMS current. Panel Main Output kW-Hrs Panelboard accumulated KW-Hours since last KW-Hours reset. Panel Main Output Percent Load Panelboard percent load of rated current Panel Main Output Power (kVA) Panelboard output kVA. Panel Main Output Power (kW) Panelboard output KW Panel Main Output Power Factor Panelboard Output Power Factor (real power/apparent power) Panel Main Voltage Vx THD Voltage Total Harmonic Distortion for Panelboard phase X. Panel Main Voltage Vy THD Voltage Total Harmonic Distortion for Panelboard phase Y. Panel Main Voltage Vz THD Voltage Total Harmonic Distortion for Panelboard phase Z. Panel Main Voltage X-N Panelboard RMS voltage between Phase X and Neutral. Panel Main Voltage X-Y Panelboard RMS voltage between phases X and Y. Panel Main Voltage Y-N Panelboard RMS voltage between Phase Y and Neutral. Panel Main Voltage Y-Z Panelboard RMS voltage between phases Y and Z. Panel Main Voltage Z-N Panelboard RMS voltage between Phase Z and Neutral. Panel Main Voltage Z-X Panelboard RMS voltage between phases Z and X. Panel Neutral Overcurrent Panelboard Neutral current has exceeded the limit. Panel Overvoltage Panelboard voltage has exceeded the limit. Panel Phase Overcurrent Panelboard phase current has exceeded the limit. Panel Summary Alarm Panelboard Summary Alarm. Annunciates upon occurrence of any branch or panelboard main breaker alarm. Panel Undervoltage Panelboard voltage is less than the limit. Phase Loss Voltage and/or Frequency on one or more of the phases is outside the limit. Phase Rotation Error Unit input phase sequence is not A, B, C. The phase sequence should be verified and corrected. Subfeed Current Ix Crest Factor Subfeed breaker phase X Current Crest Factor (peak/RMS). Subfeed Current Ix THD Current Total Harmonic Distortion for Subfeed breaker phase X. Subfeed Current Ix Subfeed breaker RMS current for phase X. 191 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-39 Liebert EXC™, Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™, Liebert RX™, Liebert STS2/PDU™—Glossary (continued) Data Label Data Description Subfeed Current Iy Crest Factor Subfeed breaker phase Y Current Crest Factor (peak/RMS). Subfeed Current Iy THD Current Total Harmonic Distortion for Subfeed breaker phase Y. Subfeed Current Iy Subfeed breaker RMS current for phase Y. Subfeed Current Iz Crest Factor Subfeed breaker phase Z Current Crest Factor (peak/RMS). Subfeed Current Iz THD Current Total Harmonic Distortion for Subfeed breaker phase Z. Subfeed Current Iz Subfeed breaker RMS current for phase Z. Subfeed Ground Current Subfeed breaker Ground RMS current. Subfeed Ground Overcurrent Subfeed breaker Ground current has exceeded the limit. Subfeed Neutral Current Subfeed breaker Neutral RMS current. Subfeed Neutral Overcurrent Subfeed breaker Neutral current has exceeded the limit. Subfeed Output kW-Hrs Subfeed breaker accumulated KW-Hours since last KW-Hours reset. Subfeed Output Percent Load Subfeed breaker percent load of rated current Subfeed Output Power (kVA) Subfeed breaker output kVA. Subfeed Output Power (kW) Subfeed breaker output KW Subfeed Phase Overcurrent Subfeed breaker phase current has exceeded the limit. Subfeed Power Factor Subfeed breaker Power Factor (real power/apparent power) System Date and Time Unit date and time System Event Acknowledge/Reset Alarm Present/Reset System Shutdown - EPO Unit shutdown by Emergency Power Off (EPO) switch System Shutdown - REPO Unit shutdown by Remote Emergency Power Off (REPO) switch System Status The operating status for the system Transformer Overtemperature Power Off Output power shutdown due to high transformer temperature Transformer Overtemperature Shutdown Unit shutdown due to transformer over temperature Transformer Overtemperature Transformer temperature has exceeded the limit Transformer Overtemperature Transformer temperature has exceeded the limit Transformer Temperature Sensor Fail Transformer temperature sensor has failed Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 192 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-40 Liebert STS™, Liebert STS/PDU™—Input and Holding—STS Controller STS Liebert Products Liebert STS Liebert STS/PDU Available Points Input Register Holding Register # of Reg. Scale Transfer Count — 40001 1 — — Preferred Source — 40002 1 — 1=Source 1 / 2=Source 2 Data Description Notes / Units Status Points (View) Load On Source — 40003 1 — 1=Source 1 / 2=Source 2 Source 1 Voltage A-B — 40004 1 — V Source 1 Voltage B-C — 40005 1 — V Source 1 Voltage C-A — 40006 1 — V Source 1 Current A — 40007 1 — A Source 1 Current B — 40008 1 — A Source 1 Current C — 40009 1 — A Source 1 Frequency — 40010 1 10 Hz Source 2 Voltage A-B — 40011 1 — V Source 2 Voltage B-C — 40012 1 — V Source 2 Voltage C-A — 40013 1 — V Source 2 Current A — 40014 1 — A Source 2 Current B — 40015 1 — A Source 2 Current C — 40016 1 — A Source 2 Frequency — 40017 1 10 Hz kW — 40018 1 — kW kVA — 40019 1 — kVA Auto Transfer Timer — 40020 1 — Seconds Nominal Voltage Deviation — 40021 1 — V Phase Differential Limit — 40022 1 — Degree Frequency Deviation — 40023 1 10 Hz Alarm Points Communications — 40289 1 — Bit 0 Logic Failure — 40289 1 — Bit 1 Equipment Overtemp — 40289 1 — Bit 2 Power Supply 1 Fault — 40289 1 — Bit 3 Source 1 Overvoltage — 40289 1 — Bit 4 Source 1 Undervoltage — 40289 1 — Bit 5 Source 2 Overvoltage — 40289 1 — Bit 6 Source 2 Undervoltage — 40289 1 — Bit 7 Source 1 Overload — 40289 1 — Bit 8 Shorted SCR1 — 40289 1 — Bit 9 Shorted SCR2 — 40289 1 — Bit 10 Open SCR1 — 40290 1 — Bit 0 Open SCR2 — 40290 1 — Bit 1 Fan Failure — 40290 1 — Bit 2 Source 2 Overload — 40290 1 — Bit 3 Power Supply 2 Fault — 40290 1 — Bit 4 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 193 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-40 Liebert STS™, Liebert STS/PDU™—Input and Holding—STS (continued) Controller STS Liebert Products Liebert STS Liebert STS/PDU Available Points Input Register Holding Register # of Reg. Scale Notes / Units Frequency Deviation — 40290 1 — Bit 5 Transfer Inhibit — 40290 1 — Bit 6 Auto Retransfer Primed — 40290 1 — Bit 7 Out of Synchronization — 40290 1 — Bit 8 Source 1 Failure — 40290 1 — Bit 9 Data Description Source 2 Failure — 40290 1 — Bit 10 Auto Retransfer Failed — 40291 1 — Bit 0 Overload — 40291 1 — Bit 1 Control Fuse 1 Blown — 40291 1 — Bit 2 Control Fuse 2 Blown — 40291 1 — Bit 3 Source 1 CB1 Open — 40291 1 — Bit 4 Source 2 CB2 Open — 40291 1 — Bit 5 Output CB3 Open — 40291 1 — Bit 6 Custom Alarm 1 — 40291 1 — Bit 7 Custom Alarm 2 — 40291 1 — Bit 8 Bypass CB4 Closed — 40291 1 — Bit 9 Bypass CB5 Closed — 40291 1 — Bit 10 Custom Alarm 3 — 40292 1 — Bit 0 Custom Alarm 4 — 40292 1 — Bit 1 Custom Alarm 5 — 40292 1 — Bit 2 Custom Alarm 6 — 40292 1 — Bit 3 Custom Alarm 7 — 40292 1 — Bit 4 Custom Alarm 8 — 40292 1 — Bit 5 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 194 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-41 Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 Controller STS2 Liebert Products Liebert STS2 Liebert STS2/PDU Available Points Data Description Input Register Holding Register # of Reg. Scale Notes / Units Status Points (View) Total Transfer Count — 40001 1 — — Preferred Source — 40002 1 — 1=Source 1, 2=Source 2 Active Source — 40003 1 — 1=Source 1, 2=Source 2 Source 1 Volts A-B — 40004 1 — V Source 1 Volts B-C — 40005 1 — V Source 1 Volts C-A — 40006 1 — V Source 1 Current A — 40007 1 — A Source 1 Current B — 40008 1 — A Source 1 Current C — 40009 1 — A Source 1 Frequency — 40010 1 10 Hz Source 2 Volts A-B — 40011 1 — V Source 2 Volts B-C — 40012 1 — V Source 2 Volts C-A — 40013 1 — V Source 2 Current A — 40014 1 — A Source 2 Current B — 40015 1 — A Source 2 Current C — 40016 1 — A Source 2 Frequency — 40017 1 10 Hz Output kW — 40018 1 — kW Output kVA — 40019 1 — kVA CB 1 Status — 40024 1 — Bit 0 CB 2 Status — 40024 1 — Bit 1 CB 3 Status — 40024 1 — Bit 2 CB 3A Status — 40024 1 — Bit 3 CB 4 Status — 40024 1 — Bit 4 CB 5 Status — 40024 1 — Bit 5 CB Spare 1 Status — 40024 1 — Bit 6 CB Spare 2 Status — 40024 1 — Bit 7 CB 7 Status — 40024 1 — Bit 8 CB 8 Status — 40024 1 — Bit 9 Auto Xfer Enabled — 40025 1 — Bit 0 Has Dual Out Breakers — 40025 1 — Bit 1 Has PDU Equipped — 40025 1 — Bit 2 Has 4 pole Switch — 40025 1 — Bit 3 Has Shunt Trip — 40025 1 — Bit 4 Has Wye Out Xfmr — 40025 1 — Bit 5 Has Rmt Sorce Sel — 40025 1 — Bit 6 Manual I peak Reset — 40025 1 — Bit 7 Auto Restart Enabled — 40025 1 — Bit 8 LoadKVA % — 40026 1 — % Source 1 Volts A-N — 40027 1 — V (4 Pole only) If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 195 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-41 Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 (continued) Controller STS2 Liebert Products Liebert STS2 Liebert STS2/PDU Available Points Data Description Input Register Holding Register # of Reg. Scale Notes / Units Source 1 Volts B-N — 40028 1 — V (4 Pole only) Source 1 Volts C-N — 40029 1 — V (4 Pole only) Source 2 Volts A-N — 40030 1 — V (4 Pole only) Source 2 Volts B-N — 40031 1 — V (4 Pole only) Source 2 Volts C-N — 40032 1 — V (4 Pole only) Source 1 Neutral Current — 40033 1 — A (4 Pole only) Source 2 Neutral Current — 40034 1 — A (4 Pole only) — 40020 1 — Seconds Setpoints (View) Retransfer Delay STS2 Voltage Rating — 40021 1 — V Max Xfer Phase Angle — 40022 1 — Degree Freq. Deviation Trip Point — 40023 1 10 Hz Source 1 Neutral Current Limit — 40035 1 — A (4 Pole only) Source 2 Neutral Current Limit — 40036 1 — A (4 Pole only) Discrete alarm objects available; use auto-discover for this unit Alarm Points Communications Lost — 40289 1 — Bit 0 S1 SCR Short — 40289 1 — Bit 1 S2 SCR Short — 40289 1 — Bit 2 S1 SCR Open — 40289 1 — Bit 3 S2 SCR Open — 40289 1 — Bit 4 Primary Fan Fail — 40289 1 — Bit 5 Control Module Fail — 40289 1 — Bit 6 PWR Supply DC A Fail — 40289 1 — Bit 7 PWR Supply DC B Fail — 40289 1 — Bit 8 PWR Supply SRC 1 AC Fail — 40289 1 — Bit 9 PWR Supply SRC 2 AC Fail — 40289 1 — Bit 10 PWR Supply Logic Fail — 40289 1 — Bit 11 Output Voltage Sense Fail — 40289 1 — Bit 12 S1 Voltage Sense Fail — 40289 1 — Bit 13 S2 Voltage Sense Fail — 40289 1 — Bit 14 S1 SCR Sense Fail — 40289 1 — Bit 15 S2 SCR Sense Fail — 40290 1 — Bit 0 S1 Current Sense Fail — 40290 1 — Bit 1 S2 Current Sense Fail — 40290 1 — Bit 2 S1 Gate Drive Fail — 40290 1 — Bit 3 S2 Gate Drive Fail — 40290 1 — Bit 4 Internal Comm Fail — 40290 1 — Bit 5 External Comm Fail — 40290 1 — Bit 6 CB1 Shunt Trip Fail — 40290 1 — Bit 7 CB2 Shunt Trip Fail — 40290 1 — Bit 8 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 196 Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-41 Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 (continued) Controller STS2 Liebert Products Liebert STS2 Liebert STS2/PDU Available Points Data Description Input Register Holding Register # of Reg. Scale Notes / Units CB6 Neutral Open — 40290 1 — Bit 9 (N/A to 4P) Contactor Neutral Fail — 40290 1 — Bit 10 (N/A to 4P) Heatsink Overtemp — 40290 1 — Bit 11 Equipment Overtemp — 40290 1 — Bit 12 (N/A to 4P) Ambient Overtemp — 40290 1 — Bit 13 (N/A to 4P) S1 Undervolts — 40290 1 — Bit 14 S1 Undervolts (RMS) — 40290 1 — Bit 15 S1 Overvolts — 40291 1 — Bit 0 S1 Over/Under Freq — 40291 1 — Bit 1 S1 Fail — 40291 1 — Bit 2 S2 Undervolts — 40291 1 — Bit 3 S2 Undervolts (RMS) — 40291 1 — Bit 4 S2 Overvolts — 40291 1 — Bit 5 S2 Over/Under Frequency — 40291 1 — Bit 6 S2 Fail — 40291 1 — Bit 7 S1 Overcurrent — 40291 1 — Bit 8 S2 Overcurrent — 40291 1 — Bit 9 S1 I-Peak — 40291 1 — Bit 10 S2 I-Peak — 40291 1 — Bit 11 Sources Out of Sync — 40291 1 — Bit 12 Load On Alternate Source — 40291 1 — Bit 13 Auto Retransfer Inhibit — 40291 1 — Bit 14 CB1 (S1) Open — 40292 1 — Bit 0 CB2 (S2) Open — 40292 1 — Bit 1 CB4 (S1 BYP) Closed — 40292 1 — Bit 2 CB5 (S2 BYP) Closed — 40292 1 — Bit 3 CB3 Output Bkr Open — 40292 1 — Bit 4 CB3A Output Bkr Open — 40292 1 — Bit 5 S1 Phase Rotation Error — 40292 1 — Bit 6 S2 Phase Rotation Error — 40292 1 — Bit 7 Transfer Inhibited — 40292 1 — Bit 8 Output Undervoltage — 40292 1 — Bit 9 History Logs Full — 40292 1 — Bit 10 Equipment Fan Fail — 40292 1 — Bit 11 Load Volt THD High — 40292 1 — Bit 12 Load Over-current — 40292 1 — Bit 13 Ground Over-current — 40292 1 — Bit 14 Neutral Over-current — 40292 1 — Bit 15 Customer Alarm #1 — 40293 1 — Bit 0 Customer Alarm #2 — 40293 1 — Bit 1 Customer Alarm #3 — 40293 1 — Bit 2 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 197 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Power Distribution and Power Conditioning Products Table 3-41 Liebert STS2™, Liebert STS2/PDU™—Input and Holding—STS2 (continued) Controller STS2 Liebert Products Liebert STS2 Liebert STS2/PDU Available Points Input Register Holding Register # of Reg. Scale Notes / Units Customer Alarm #4 — 40293 1 — Bit 3 Customer Alarm #5 — 40293 1 — Bit 4 Customer Alarm #6 — 40293 1 — Bit 5 Customer Alarm #7 — 40293 1 — Bit 6 Customer Alarm #8 — 40293 1 — Bit 7 Neutral Current 1 Over Limit — 40294 1 — Bit 13 (4P Only) Neutral Current 2 Over Limit — 40294 1 — Bit 14 (4P Only) Data Description Neutral Snubber Fail — 40294 1 — Bit 15 (4P Only) Neutral 1 SCR Short — 40295 1 — Bit 0 (4P Only) Neutral 2 SCR Short — 40295 1 — Bit 1 (4P Only) Neutral 1 SCR Open — 40295 1 — Bit 2 (4P Only) Neutral 2 SCR Open — 40295 1 — Bit 3 (4P Only) If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 198 Modbus RTU and Modbus TCP Protocols—UPS Systems 3.3 UPS Systems Table 3-42 Liebert APM™, Liebert NXC™, Liebert NXR™—Status and Coil Status Coil Number of Bits Scale Notes / Units Battery Auto Test In Progress 10001 — 1 — Active on Alarm Battery Equalize 10002 — 1 — Active on Alarm Battery Charging Inhibited 10003 — 1 — Active on Alarm On Generator 10004 — 1 — Active on Alarm Data Label System Status System Events System Input Power Problem 10015 — 1 — Active on Alarm Rectifier Failure 10016 — 1 — Active on Alarm Inverter Failure 10017 — 1 — Active on Alarm Bypass Not Available 10018 — 1 — Active on Alarm Battery Low 10019 — 1 — Active on Alarm LBS Inhibited 10020 — 1 — Active on Alarm System Fan Failure 10021 — 1 — Active on Alarm Equipment Over Temperature 10022 — 1 — Active on Alarm System Shutdown - EPO 10023 — 1 — Active on Alarm Bypass Static Switch Unavailable 10024 — 1 — Active on Alarm Bypass - Excess Auto Retransfers 10025 — 1 — Active on Alarm Parallel Comm Warning 10026 — 1 — Active on Alarm Power Supply Failure 10027 — 1 — Active on Alarm Battery Over Temperature 10028 — 1 — Active on Alarm System Input Phs Rotation Error 10029 — 1 — Active on Alarm Fuse Failure 10030 — 1 — Active on Alarm Inverter Overload Phase A 10031 — 1 — Active on Alarm Inverter Overload Phase B 10032 — 1 — Active on Alarm Inverter Overload Phase C 10033 — 1 — Active on Alarm MMS Overload 10034 — 1 — Active on Alarm Inverter Shutdown - Overload 10035 — 1 — Active on Alarm System Output Fault 10036 — 1 — Active on Alarm Internal Communications Failure 10037 — 1 — Active on Alarm Battery Charging Error 10038 — 1 — Active on Alarm System Input Current Imbalance 10039 — 1 — Active on Alarm Main Battery Disconnect Open 10040 — 1 — Active on Alarm Inverter Static Switch SCR Short 10041 — 1 — Active on Alarm Battery Not Qualified 10042 — 1 — Active on Alarm Battery Terminals Reversed 10043 — 1 — Active on Alarm Battery Converter Failure 10044 — 1 — Active on Alarm Inverter SCR Open 10045 — 1 — Active on Alarm Load Sharing Fault 10046 — 1 — Active on Alarm DC Bus Abnormal 10047 — 1 — Active on Alarm Mains Input Neutral Lost 10048 — 1 — Active on Alarm Load Impact Transfer 10049 — 1 — Active on Alarm User Operation Invalid 10050 — 1 — Active on Alarm Power Sub Module Fault 10051 — 1 — Active on Alarm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 199 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-42 Liebert APM™, Liebert NXC™, Liebert NXR™—Status and Coil (continued) Data Label Status Coil Number of Bits Scale Notes / Units Battery Discharging 10052 — 1 — Active on Alarm UPS Output on Bypass 10053 — 1 — Active on Alarm Output Load on Maint. Bypass 10054 — 1 — Active on Alarm Battery Capacity Low 10055 — 1 — Active on Alarm MMS On Battery 10056 — 1 — Active on Alarm Loss of Redundancy 10057 — 1 — Active on Alarm Top Outlet Fan Fault 10058 — 1 — Active on Alarm MMS Over Capacity 10059 — 1 — Active on Alarm Battery Charge Equalization Timeout 10060 — 1 — Active on Alarm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 200 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-43 Liebert APM™, Liebert NXC™, Liebert NXR™—Input and Holding Data Label Input Register Holding Register # of Reg. Scale Notes / Units Input System Input RMS A-B 30385 — 1 — VAC System Input RMS B-C 30386 — 1 — VAC System Input RMS C-A 30387 — 1 — VAC System Input RMS Current Phase A 30388 — 1 — A AC System Input RMS Current Phase B 30389 — 1 — A AC System Input RMS Current Phase C 30390 — 1 — A AC System Input Frequency 30391 — 1 10 Hz System Input RMS A-N 30392 — 1 — VAC System Input RMS B-N 30393 — 1 — VAC System Input RMS C-N 30394 — 1 — VAC System Input Power Factor Phs A 30395 — 1 100 — System Input Power Factor Phs B 30396 — 1 100 — System Input Power Factor Phs C 30397 — 1 100 — Bypass Input Voltage RMS A-N 30401 — 1 — VAC Bypass Input Voltage RMS B-N 30402 — 1 — VAC Bypass Bypass Input Voltage RMS C-N 30403 — 1 — VAC Bypass Input Frequency 30404 — 1 10 Hz 30408 — 1 — min Battery Battery Time Remaining Battery Volts for Cabinet 30409 — 1 — VDC Battery Temperature for Cabinet 30410 — 1 — deg C Battery Temperature for Cabinet 30411 — 1 — deg F Inlet Air Temperature 30412 — 1 — deg C Inlet Air Temperature 30413 — 1 — deg F DC Bus Current 30414 — 1 — A DC UPS battery1 status 30415 — 1 — 1 = Unknown 2 = Normal 3 = Low 4 = Depleted System Output Voltage RMS A-N 30419 — 1 — VAC System Output Voltage RMS B-N 30420 — 1 — VAC System Output Voltage RMS C-N 30421 — 1 — VAC System Output RMS Current Phs A 30422 — 1 — A AC System Output RMS Current Phs B 30423 — 1 — A AC System Output RMS Current Phs C 30424 — 1 — A AC System Output Frequency 30425 — 1 10 Hz Output System Output Voltage RMS A-B 30426 — 1 — VAC System Output Voltage RMS B-C 30427 — 1 — VAC System Output Voltage RMS C-A 30428 — 1 — VAC System Output Power Factor Phs A 30429 — 1 100 — System Output Power Factor Phs B 30430 — 1 100 — System Output Power Factor Phs C 30431 — 1 100 — System Output Pct Power Phase A 30432 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 201 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-43 Liebert APM™, Liebert NXC™, Liebert NXR™—Input and Holding (continued) Data Label System Output Pct Power Phase B Input Register Holding Register # of Reg. Scale Notes / Units 30433 — 1 — % System Output Pct Power Phase C 30434 — 1 — % MMS Output Apparent Power 30435 — 1 — kVA MMS Output Power 30436 — 1 — kW System Output Apparent Power 30437 — 1 — kVA System Output Power 30438 — 1 — kW Output Current Crest Factor Phs A 30439 — 1 10 — Output Current Crest Factor Phs B 30440 — 1 10 — Output Current Crest Factor Phs C 30441 — 1 10 — Inverter On/Off State 30445 — 1 — 0 = Off / 1 = On Maintenance Bypass Breaker (MBB) 30446 — 1 — 0 = Open / 1 = Closed 2 = Not Installed — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer System Status UPS Output Source 30447 — 1 System Status 30448 — 1 — 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation ECO Mode Operation State 30449 — 1 — 0 = disabled 1 = enabled 39998 49998 2 — Secs since Epoch(UTC) System Configuration System Date and Time If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 202 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-44 Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary Data Label Data Description Battery Auto Test In Progress Automatic battery test is in progress Battery Capacity Low Battery capacity is low Battery Charging Error The battery is not charging properly Battery Charging Inhibited Battery charging is inhibited due to an external inhibit signal Battery Converter Failure Battery converter failure. This is a summary event caused by one or more power submodules in a UPS module. Battery Discharging The battery is discharging Battery Equalize The rectifier output voltage is increased to equalize the battery voltage level. Battery Low The calculated battery time remaining has reached the low battery threshold Battery Not Qualified The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open. Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Temperature for Cabinet The battery temperature for a cabinet Battery Terminals Reversed The measured battery voltage is a negative value due to reverse battery terminal connections. Battery Time Remaining The calculated available time on battery Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Bypass - Excess Auto Retransfers The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval Bypass Input Frequency The bypass input frequency Bypass Input Voltage RMS A-N The bypass input RMS voltage between phase A and Neutral Bypass Input Voltage RMS B-N The bypass input RMS voltage between phase B and Neutral Bypass Input Voltage RMS C-N The bypass input RMS voltage between phase C and Neutral Bypass Not Available A problem associated with the bypass has been detected Bypass Static Switch Unavailable The static bypass switch is off, and unable to operate DC Bus Abnormal The system has detected an abnormal DC Bus Voltage. DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value Equipment Over Temperature Equipment over temperature summary event Fuse Failure A summary event indicating one or more fuse failures Inlet Air Temperature The temperature of the inlet air Internal Communications Failure The control has detected a communication failure of a component on the internal communication bus Inverter Failure Inverter failure - inverter output is off Inverter On/Off State inverter on/off state Inverter Overload Phase A Inverter is operating with an overload on phase A Inverter Overload Phase B Inverter is operating with an overload on phase B Inverter Overload Phase C Inverter is operating with an overload on phase C Inverter SCR Open The system has detected an open across one or more inverter static switch Silicon Controlled Rectifiers. Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload Inverter Static Switch SCR Short The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR) LBS Inhibited The system has detected that conditions to perform Load Bus Sync are not satisfied Load Impact Transfer On bypass as result of load impact. Load Sharing Fault Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current. Main Battery Disconnect Open Main battery disconnect is open Mains Input Neutral Lost Loss of neutral in the input source is detected. 203 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-44 Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary (continued) Data Label Data Description Maintenance Bypass Breaker (MBB) Maintenance bypass breaker (MBB) MMS On Battery The multi-module system is on battery MMS Output Apparent Power The sum total apparent power of all system output modules MMS Output Power The sum total power of all system output modules MMS Overload Multi-module system overload On Generator A generator is supplying the power to the system Output Current Crest Factor Phs A Output current crest factor of Phase A. Output Current Crest Factor Phs B Output current crest factor of Phase B. Output Current Crest Factor Phs C Output current crest factor of Phase C. Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Parallel Comm Warning Parallel communication bus warning Power Sub Module Fault One or more failures detected in power module, inverter or rectifier. Power Supply Failure Power supply failure Rectifier Failure Rectifier failure - rectifier is off System Date and Time The system date and time System Fan Failure System fan failure - one or more fans have failed System Input Current Imbalance System Input Currents are Imbalanced System Input Frequency The system input frequency System Input Phs Rotation Error The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C) System Input Power Factor Phs A The system input power factor for Phase A System Input Power Factor Phs B The system input power factor for Phase B System Input Power Factor Phs C The system input power factor for Phase C System Input Power Problem The input is not qualified to provide power to the system System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power The sum total apparent power of all system output phases System Output Fault A fault has been detected in the system output System Output Frequency The system output frequency System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity System Output Power Factor Phs A The system output power factor of phase A System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power The sum total power of all system output phases System Output RMS Current Phs A The system output RMS current for Phase A System Output RMS Current Phs B The system output RMS current for Phase B System Output RMS Current Phs C The system output RMS current for Phase C System Output Voltage RMS A-B The system output RMS voltage between phases A and B Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 204 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-44 Liebert APM™, Liebert NXC™, Liebert NXR™—Glossary (continued) Data Label Data Description System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral System Output Voltage RMS B-C The system output RMS voltage between phases B and C System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral System Output Voltage RMS C-A The system output RMS voltage between phases C and A System Output Voltage RMS C-N The system output RMS voltage between phases C and Neutral System Shutdown - EPO System shutdown due to Emergency Power Off (EPO) System Status The operating status for the system UPS battery1 status UPS battery status UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source User Operation Invalid User attempted an invalid operation. 205 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-45 Liebert APS™—Status and Coil Status Coil Number of Bits Notes Rectifier Failure 10001 — 1 Active on Alarm System Input Power Problem 10002 — 1 Active on Alarm System Input Current Imbalance 10003 — 1 Active on Alarm UPS Output on Bypass 10014 — 1 Active on Alarm Output Load on Maint. Bypass 10015 — 1 Active on Alarm Data Label Input Bypass Bypass Not Available 10016 — 1 Active on Alarm Bypass Overload 10017 — 1 Active on Alarm Bypass Frequency Error 10018 — 1 Active on Alarm Bypass Auto Retransfer Failed 10019 — 1 Active on Alarm Battery Discharging 10030 — 1 Active on Alarm Battery Manual Test In Progress 10031 — 1 Active on Alarm Battery Auto Test In Progress 10032 — 1 Active on Alarm Battery Battery Test Passed 10033 — 1 Active on Alarm Battery Test Failed 10034 — 1 Active on Alarm Low Battery - Shutdown Imminent 10035 — 1 Active on Alarm Battery Module Fault 10036 — 1 Active on Alarm Battery Module Warning 10037 — 1 Active on Alarm Battery Over Temperature 10038 — 1 Active on Alarm Battery Temperature Imbalance 10039 — 1 Active on Alarm Output Overload 10050 — 1 Active on Alarm Output Off Pending 10051 — 1 Active on Alarm System Output Off 10052 — 1 Active on Alarm System Shutdown - Transformer Over Temperature 10053 — 1 Active on Alarm Output Inverter Shutdown - Overload 10054 — 1 Active on Alarm System Shutdown - Output Short 10055 — 1 Active on Alarm System Shutdown - Low Battery 10056 — 1 Active on Alarm System Shutdown - Remote Shutdown 10057 — 1 Active on Alarm System Shutdown - Hardware Fault 10058 — 1 Active on Alarm Maximum Load Alarm 10059 — — Active on Alarm Loss of Redundancy 10070 — 1 Active on Alarm Power Module Failure 10071 — 1 Active on Alarm Power Module Warning 10072 — 1 Active on Alarm Unspecified General Event 10083 — 1 Active on Alarm Check Air Filter 10084 — 1 Active on Alarm Frame Fan Fault 10085 — 1 Active on Alarm Inverter System Status Transformer Fan Fault 10086 — 1 Active on Alarm Transformer Overtemperature 10087 — 1 Active on Alarm No Load Warning 10088 — 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 206 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-45 Liebert APS™—Status and Coil (continued) Status Data Label Coil Number of Bits Notes PowerModule 1 Power Module Fan Fault 10099 — 1 Active on Alarm Power Module Over Temperature 10100 — 1 Active on Alarm Power Module Shutdown - Over Temperature 10101 — 1 Active on Alarm PowerModule 2 Power Module Fan Fault 10112 — 1 Active on Alarm Power Module Over Temperature 10113 — 1 Active on Alarm Power Module Shutdown - Over Temperature 10114 — 1 Active on Alarm PowerModule 10 Power Module Fan Fault 10216 — 1 Active on Alarm Power Module Over Temperature 10217 — 1 Active on Alarm Power Module Shutdown - Over Temperature 10218 — 1 Active on Alarm Battery Module Temperature Sensor Fault 10229 — 1 Active on Alarm Battery Module Over Temperature 10230 — 1 Active on Alarm Replace Battery Module 10231 — 1 Active on Alarm Battery Module Temperature Sensor Fault 10242 — 1 Active on Alarm Battery Module Over Temperature 10243 — 1 Active on Alarm Replace Battery Module 10244 — 1 Active on Alarm Battery Module Temperature Sensor Fault 11256 — 1 Active on Alarm Battery Module Over Temperature 11257 — 1 Active on Alarm Replace Battery Module 11258 — 1 Active on Alar 11269 — 1 Active on Alarm BatteryModule 1 BatteryModule 2 BatteryModule 80 ChargerModule Charger Module Fan Fault 207 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-46 Liebert APS™—Input and Holding Input Register Holding Register # of Reg. Scale Notes / Units 30385 — — — 1 = UPS 2 = AIR 3 = PMP 4 = PDU System Input RMS L1-N 30396 — 1 10 Units : VAC Uint 16 System Input RMS L2-N 30397 — 1 10 Units : VAC Uint 16 System Input RMS L3-N 30398 — 1 10 Units : VAC Uint 16 System Input RMS L1-L2 30399 — 1 10 Units : VAC Uint 16 System Input RMS L2-L3 30400 — 1 10 Units : VAC Uint 16 System Input RMS L3-L1 30401 — 1 10 Units : VAC Uint 16 System Input RMS Current L1 30402 — 1 10 Units : A AC Uint 16 System Input RMS Current L2 30403 — 1 10 Units : A AC Uint 16 System Input RMS Current L3 30404 — 1 10 Units : A AC Uint 16 System Input Frequency 30405 — 1 100 Units : Hz Uint 16 System Input Power Factor L1 30406 — 1 100 Uint 16 System Input Power Factor L2 30407 — 1 100 Uint 16 System Input Power Factor L3 30408 — 1 100 Uint 16 System Input Brown Out Count 30409 — 1 — Uint 16 System Input Black Out Count 30410 — 1 — Uint 16 Bypass Input Voltage RMS L1-N 30421 — 1 10 Units : VAC Uint 16 Bypass Input Voltage RMS L2-N 30422 — 1 10 Units : VAC Uint 16 Bypass Input Voltage RMS L1-L2 30423 — 1 10 Units : VAC Uint 16 Bypass Input Frequency 30424 — 1 100 Units : Hz Uint 16 Number Of Transfers To Bypass 30425 — 1 — Uint 16 Bypass Qualification Status 30426 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High Data Label Protocol Server Class Input Bypass Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 208 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-46 Liebert APS™—Input and Holding (continued) Input Register Holding Register # of Reg. Scale Notes / Units Battery Time Remaining 30437 — 1 — Units : min Uint 16 Battery Volts for Cabinet 30438 — 1 10 Units : VDC Uint 16 DC Bus Current 30439 — 1 100 Units : A DC Uint 16 Battery Percentage Charge 30440 — 1 — Units : % Uint16 UPS Battery Status 30441 — 1 — 1 = Unknown 2 = Normal 3 = Low 4 = Depleted Data Label Battery Battery is 30442 — 1 — 0 = fully charged 1 = charging 2 = discharging 3 = not charging (charger off) Battery Temperature 30443 — 1 10 Units : deg C Int16 Battery Temperature 30444 — 10 Units : degF Int16 Number of Discharge Cycles 30445 — 1 — Uint 16 Accumulated Discharge Time 30446 — 1 10 Units : hr Uint 16 Time Until Next Auto Battery Test 30447 — 2 — Units : min Uint32 Number of EBC Installed 30449 — 1 — Uint 16 Low Battery Warning Time 30450 40450 1 — Units : min Uint 16 Automatic Battery Test 30451 40451 1 — 0 = disabled 1 = enabled 30452 40452 1 — 0 = 8 weeks 1 = 12 weeks 2 = 16 weeks 3 = 20 weeks 4 = 26 weeks — 40453 1 — 1 = Start Test System Output Voltage RMS L1-N 30464 — 1 10 Units : VAC Uint 16 System Output Voltage RMS L2-N 30465 — 1 10 Units : VAC Uint 16 System Output Voltage RMS L1-L2 30466 — 1 10 Units : VAC Uint 16 System Output RMS Current L1 30467 — 1 10 Units : A AC Uint 16 System Output RMS Current L2 30468 — 1 10 Units : A AC Uint16 System Output Frequency 30469 — 1 100 Units : Hz Uint 16 System Output Power Factor L1 30470 — 1 100 Uint 16 System Output Power Factor L2 30471 — 1 100 Uint 16 Auto Battery Test Interval Manual Battery Test Output 209 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-46 Liebert APS™—Input and Holding (continued) Input Register Holding Register # of Reg. Scale Notes / Units System Output Apparent Power 30472 — 1 100 Units : kVA Uint 16 System Output Apparent Power L1 30473 — 1 100 Units : kVA Uint 16 System Output Apparent Power L2 30474 — 1 100 Units : kVA Uint 16 System Output Power 30475 — 1 100 Units : kW Uint 16 System Output Power L1 30476 — 1 100 Units : kW Uint 16 System Output Power L2 30477 — 1 100 Units : kW Uint 16 System Output Pct Power L1 30478 — 1 10 Units : % Uint 16 System Output Pct Power L2 30479 — 1 10 Units : % Uint 16 Data Label Output Qualification Status 30480 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High Maximum Load Alarm Limit 30481 40481 1 10 Units : kVA Uint16 Shutdown After Delay 30482 40482 1 — Units : sec Uint 16 Reboot After Delay 30483 40483 1 — Units : sec Uint 16 Output On Delay 30484 40484 1 — Units : sec Uint 16 Inverter On/Off State 30495 — 1 — 0 = off 1 = on System Set To Operate With 30496 40496 1 — 0 = No Redundancy 1 = Redundancy System Capacity 30507 — 1 — Units : VA Uint 16 Frame Capacity 30508 — 1 — Units : VA Uint 16 Inverter Number of Installed Power Modules 30509 — 1 — Uint 16 Number Of Active Power Modules 30510 — 1 — Uint 16 Number Of Power Modules With Warnings 30511 — 1 — Uint 16 Number Of Failed Power Modules 30512 — 1 — Uint 16 Number of Installed Battery Strings 30513 — 1 — Uint 16 Number of Active Battery Strings 30514 — 1 — Uint 16 Number of Battery Strings With Warnings 30515 — 1 — Uint 16 Number of Failed Battery Strings 30516 — 1 — Uint 16 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer UPS Output Source 30517 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide — 210 1 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-46 Liebert APS™—Input and Holding (continued) Data Label Input Register Holding Register # of Reg. Scale Notes / Units System Status 30518 — 1 — 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation Auto Restart 30519 — 40519 1 0 = disabled 1 = enabled Auto Restart Delay 30520 — 40520 1 Units : sec Uint 16 Auto Restart Minimum Battery Setting 30521 — 40521 1 0 = 0% 1 = 10% 2 = 20% 3 = 30% 4 = 40% 5 = 50% 6 = 60% 7 = 70% 8 = 80% 9 = 90% No Load Warning Current Threshold 30522 40522 1 — Units : A AC Int16 No Load Warning Delay 30523 40523 1 — Units : min Uint 16 PowerModule 1 Module Operating Status 30534 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30535 — 1 — 0 = Inverter Inactive 1 = Inverter Active Module Operating Status 30546 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30547 — 1 — 0 = Inverter Inactive 1 = Inverter Active PowerModule 2 PowerModule 10 Module Operating Status 30642 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30643 — 1 — 0 = Inverter Inactive 1 = Inverter Active Module Operating Status 30654 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Battery String Voltage 30655 — 1 10 Units : VDC Uint16 Battery Module Temperature 30656 — 1 10 Units : deg C Int16 Battery Module Temperature 30657 — 1 10 Units : degF Int16 Number of Discharge Cycles 30658 — 1 — Uint 16 BatteryModule 1 211 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-46 Liebert APS™—Input and Holding (continued) Input Register Holding Register # of Reg. Scale Notes / Units 30659 — 1 10 Units : hr Uint 16 Module Operating Status 30670 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Battery String Voltage 30671 — 1 10 Units : VDC Uint16 Battery Module Temperature 30672 — 1 10 Units : deg C Int16 Battery Module Temperature 30673 — 1 10 Units : degF Int16 Number of Discharge Cycles 30674 — 1 — Uint 16 Data Label Accumulated Discharge Time BatteryModule 2 30675 — 1 10 Units : hr Uint 16 Module Operating Status 31918 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Battery String Voltage 31919 — 1 10 Units : VDC Uint16 Battery Module Temperature 31920 — 1 10 Units : deg C Int16 Battery Module Temperature 31921 — 1 10 Units : degF Int16 Number of Discharge Cycles 31922 — 1 — Uint 16 Accumulated Discharge Time BatteryModule 80 Accumulated Discharge Time 31923 — 1 10 Units : hr Uint 16 31934 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault ChargerModule Module Operating Status Charger Mode 31935 — 1 — 0 = Not Charging 1 = Float Charging 2 = Current Limit Charging 3 = Equalize Charging 31946 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault 31957 41957 2 — Secs since Epoch(UTC) 39998 49998 2 — Secs since Epoch(UTC) BypassControlModule Module Operating Status System Configuration System Date and Time SystemConfiguration System Date and Time If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 212 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-47 Liebert APS™—Glossary Data Label Data Description Accumulated Discharge Time The highest accumulated battery discharge time among installed battery modules. Accumulated Discharge Time Total accumulated discharge time for the Battery Module since it was made. Auto Battery Test Interval The time between automatic battery tests. Auto Restart Delay If 'Auto Restart' is set to 'enabled' the UPS will not restart the load after a battery discharge until this amount of time has elapsed since the restoration of utility power. Auto Restart Minimum Battery Setting The percent state of charge that the batteries must have before the unit is allowed to auto restart. Auto Restart When 'enabled', the UPS will automatically restart the load when utility power is restored after a battery discharge. Automatic Battery Test Enable/disable the automatic battery test schedule. Battery Auto Test In Progress Automatic battery test is in progress Battery Discharging The battery is discharging Battery is Battery charge status. Battery Manual Test In Progress Manual battery test is in progress Battery Module Fault One or more battery modules are reporting a fault condition. Battery Module Over Temperature The Battery Module has detected an over temperature condition. Battery Module Temperature Sensor Fault A Battery Module temperature sensor fault has been detected. Battery Module Temperature The battery temperature measured by the Battery Module. Battery Module Warning One or more battery modules are reporting a warning condition. Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Percentage Charge The percentage of battery charge Battery String Voltage The voltage between the positive and negative battery terminals of a battery string. Battery Temperature Imbalance Excessive temperature differences between battery sensors detected Battery Temperature The highest battery temperature among all installed Battery Modules. Battery Test Failed Battery test failed Battery Test Passed Battery test passed Battery Time Remaining The calculated available time on battery Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Bypass Auto Retransfer Failed After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed Bypass Frequency Error The bypass frequency is outside the inverter synchronization limits Bypass Input Frequency The bypass input frequency Bypass Input Voltage RMS L1-L2 The bypass input RMS voltage between Lines 1 and 2 Bypass Input Voltage RMS L1-N The bypass input RMS voltage between Line 1 and Neutral Bypass Input Voltage RMS L2-N The bypass input RMS voltage between Line 2 and Neutral Bypass Not Available A problem associated with the bypass has been detected Bypass Overload Bypass overloaded, reduce load immediately. Bypass Qualification Status bypass qualification status Charger Mode The Charger Module is operating in the stated charging mode. Charger Module Fan Fault The Charger Module has detected a fan fault. Check Air Filter Please check air filter, it may need to be cleaned or replaced. DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value 213 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-47 Liebert APS™—Glossary (continued) Data Label Data Description Frame Capacity Total system capacity supported when the maximum number of power modules are installed. Frame Fan Fault The frame top outlet fan has failed. Inverter On/Off State inverter on/off state Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload Inverter Status Status of the inverter output. Active means the inverter is online with regulated output voltage and ready to power the load. Inactive means the inverter is offline and not ready to power the load. Loss of Redundancy The system has an insufficient number of power modules to provide redundancy. Low Battery - Shutdown Imminent If active and guaranteed shutdown is enabled, a low battery reserve condition exists that will shutdown the UPS. Low Battery Warning Time When battery time remaining falls to, or below, this value the low battery alarm is activated. Manual Battery Test Command to initiate a manual battery test. Maximum Load Alarm Limit Maximum load [VA] supportable without a 'Maximum Load Alarm' condition. Maximum Load Alarm Maximum load alarm indicating load setting has been exceeded. Module Operating Status The operating status for this Battery Module. Module Operating Status The operating status for this Bypass Control Module. Module Operating Status The operating status for this Charger Module. Module Operating Status The operating status for this Power Module. No Load Warning Current Threshold If the output current is below this number of amps for a period of [No Load Warning Delay] time, the [No Load Warning] will become active. No Load Warning Delay If the output current is below the [No Load Warning Current Threshold] number of amps for this period of time, the [No Load Warning] will become active. No Load Warning Indicates the UPS has output voltage but the output current is below a set threshold [No Load Warning Current Threshold] for a set period of time [No Load Warning Delay]. Number of Active Battery Strings The total number of active battery strings. Number Of Active Power Modules The total number of active power modules. Number of Battery Strings With Warnings The total number of battery strings with warnings. Number of Discharge Cycles The highest number of battery discharge cycles among all installed Battery Modules. Number of Discharge Cycles The total number of battery discharge cycles for the Battery Module since it was made. Number of EBC Installed The total number of Extended Battery Cabinets installed. Number of Failed Battery Strings The total number of failed battery strings. Number Of Failed Power Modules The total number of failed power modules. Number of Installed Battery Strings The total number of battery strings installed. Number of Installed Power Modules The total number of Power Modules installed. Number Of Power Modules With Warnings The total number of power modules with warnings. Number Of Transfers To Bypass The total number of transfers to bypass from inverter since system startup. Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Output Off Pending Output off pending - shutdown imminent. Output On Delay When a value is written to this point the output will be turned on after the specified time has elapsed. Output Overload An overload exists on the output. Output Qualification Status output qualification status Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 214 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-47 Liebert APS™—Glossary (continued) Data Label Data Description Power Module Failure One or more conditions indicate a power module failure, service is required. Power Module Fan Fault The Power Module has detected a fan fault. Power Module Over Temperature The Power Module has detected an over temperature condition. Power Module Shutdown - Over Temperature Power Module has shutdown due to over temperature. Power Module Warning One or more power modules is reporting a warning condition. Reboot After Delay When a value is written to this point the output will be turned off after the specified time has elapsed and then turned back on 10-30 seconds later. Rectifier Failure Rectifier failure - rectifier is off Replace Battery Module The Battery Module needs to be replaced. Server Class The general classification for this system Shutdown After Delay When a value is written to this point the system will shutdown after the specified time has elapsed and output will remain off. System Capacity System capacity supported by the installed power modules. System Date and Time The system date and time System Input Black Out Count The number of occurrences, since the last reset, where the input was not qualified to provide power to the system System Input Brown Out Count The number of occurrences, since the last reset, where the system input voltage has fallen below a pre-determined threshold for a specified amount of time System Input Current Imbalance System Input Currents are Imbalanced System Input Frequency The system input frequency System Input Power Factor L1 The system input power factor for Line 1 System Input Power Factor L2 The system input power factor for Line 2 System Input Power Factor L3 The system input power factor for Line 3 System Input Power Problem The input is not qualified to provide power to the system System Input RMS Current L1 The system input RMS current for Line 1 System Input RMS Current L2 The system input RMS current for Line 2 System Input RMS Current L3 The system input RMS current for Line 3 System Input RMS L1-L2 The System Input RMS Voltage between Line 1 and Line 2 System Input RMS L1-N The System Input RMS Voltage between Line 1 and Neutral System Input RMS L2-L3 The System Input RMS Voltage between Line 2 and Line 3 System Input RMS L2-N The System Input RMS Voltage between Line 2 and Neutral System Input RMS L3-L1 The System Input RMS Voltage between Line 3 and Line 1 System Input RMS L3-N The System Input RMS Voltage between Line 3 and Neutral System Output Apparent Power L1 System output apparent power on Line 1 System Output Apparent Power L2 System output apparent power on Line 2 System Output Apparent Power The sum total apparent power of all system output phases System Output Frequency The system output frequency System Output Off The system output is off System Output Pct Power L1 The system output power on Line 1 as a percentage of the rated capacity System Output Pct Power L2 The system output power on Line 2 as a percentage of the rated capacity System Output Power Factor L1 The system output power factor of Line 1 System Output Power Factor L2 The system output power factor of Line 2 System Output Power L1 The system output power on Line 1. System Output Power L2 The system output power on Line 2. 215 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-47 Liebert APS™—Glossary (continued) Data Label Data Description System Output Power The sum total power of all system output phases System Output RMS Current L1 The system output RMS current for Line 1 System Output RMS Current L2 The system output RMS current for Line 2 System Output Voltage RMS L1-L2 The system output RMS voltage between Lines 1 and 2 System Output Voltage RMS L1-N The system output RMS voltage between Line 1 and Neutral System Output Voltage RMS L2-N The system output RMS voltage between Line 2 and Neutral System Set To Operate With If this point reports 'Redundancy' then the system is configured for redundancy and the 'Loss of Redundancy' alarm is enabled. System Shutdown - Hardware Fault Shutdown was due to an externally applied hardware control signal. System Shutdown - Low Battery Shutdown was due to a low battery condition. System Shutdown - Output Short Shutdown was due to a short on the output. System Shutdown - Remote Shutdown Shutdown was due to a remote communications shutdown command. System Shutdown - Transformer Over Temperature System shutdown due to transformer over temperature. System Status The operating status for the system Time Until Next Auto Battery Test The time until the next automatic battery test is started. Transformer Fan Fault The transformer fan has failed. Transformer Overtemperature Transformer temperature has exceeded the limit Unspecified General Event One or more unspecified events active. See local unit display for further details. UPS Battery Status UPS battery status UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 216 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-48 Liebert EPM™—Status and Coil Data Label Status Coil Number of Bits Notes System Status Battery Equalize 10001 1 Active on Alarm Battery Charging Inhibited 10002 1 Active on Alarm On Generator 10003 1 Active on Alarm Battery Self Test 10004 1 Active on Alarm Battery Circuit Breaker 1 Open 10005 1 Active on Alarm Battery Circuit Breaker 2 Open 10006 1 Active on Alarm Battery Circuit Breaker 3 Open 10007 1 Active on Alarm Battery Circuit Breaker 4 Open 10008 1 Active on Alarm Main Battery Disconnect Open 10009 1 Active on Alarm System Events System Input Power Problem 10020 1 Active on Alarm Rectifier Failure 10021 1 Active on Alarm Inverter Failure 10022 1 Active on Alarm Bypass Not Available 10023 1 Active on Alarm Battery Low 10024 1 Active on Alarm LBS Inhibited 10025 1 Active on Alarm System Fan Failure 10026 1 Active on Alarm Equipment Over Temperature 10027 1 Active on Alarm System Shutdown - EPO 10028 1 Active on Alarm Bypass Static Switch Unavailable 10029 1 Active on Alarm Bypass - Excess Auto Retransfers 10030 1 Active on Alarm Parallel Comm Warning 10031 1 Active on Alarm Power Supply Failure 10032 1 Active on Alarm Battery Over Temperature 10033 1 Active on Alarm System Input Phs Rotation Error 10034 1 Active on Alarm Fuse Failure 10035 1 Active on Alarm Inverter Overload 10036 1 Active on Alarm MMS Overload 10037 1 Active on Alarm Inverter Shutdown - Overload 10038 1 Active on Alarm System Output Fault 10039 1 Active on Alarm Internal Communications Failure 10040 1 Active on Alarm Battery Charging Error 10041 1 Active on Alarm System Input Current Imbalance 10042 1 Active on Alarm Battery Not Qualified 10043 1 Active on Alarm Battery Terminals Reversed 10044 1 Active on Alarm Battery Converter Failure 10045 1 Active on Alarm Load Sharing Fault 10046 1 Active on Alarm DC Bus Abnormal 10047 1 Active on Alarm Mains Input Neutral Lost 10048 1 Active on Alarm Load Impact Transfer 10049 1 Active on Alarm User Operation Invalid 10050 1 Active on Alarm Battery Discharging 10051 1 Active on Alarm UPS Output on Bypass 10052 1 Active on Alarm Output Load on Maint. Bypass 10053 1 Active on Alarm Battery Capacity Low 10054 1 Active on Alarm 217 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-48 Liebert EPM™—Status and Coil (continued) Data Label Status Coil Number of Bits Notes MMS On Battery 10055 1 Active on Alarm Loss of Redundancy 10056 1 Active on Alarm Top Outlet Fan Fault 10057 1 Active on Alarm MMS Over Capacity 10058 1 Active on Alarm Bypass Input Voltage Fault 10059 1 Active on Alarm Power Module Over Temperature 10060 1 Active on Alarm Excess ECO Suspends 10061 1 Active on Alarm Battery Ground Fault 10062 1 Active on Alarm System Input Current Limit 10063 1 Active on Alarm Inverter Relay Fault 10064 1 Active on Alarm Transfer to Bypass - System Overload 10065 1 Active on Alarm Input Source Backfeed 10066 1 Active on Alarm Loss of Synchronization 10067 1 Active on Alarm Battery Converter Current Limit 10068 1 Active on Alarm LBS Cable Failure 10069 1 Active on Alarm Battery Charge Equalization Timeout 10070 1 Active on Alarm Parallel Cable Failure 10071 1 Active on Alarm Battery Fault 10072 1 Active on Alarm Battery Room Alarm 10073 1 Active on Alarm Battery Breaker 1 Open Failure 10074 1 Active on Alarm Battery Breaker 2 Open Failure 10075 1 Active on Alarm Battery Breaker 3 Open Failure 10076 1 Active on Alarm Battery Breaker 4 Open Failure 10077 1 Active on Alarm Bypass Backfeed Detected 10078 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 218 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-49 Liebert EPM™—Input and Holding Data Label Input Holding # of Reg Scale Notes/Units Input System Input RMS A-B 30385 1 Units : VAC Uint16 System Input RMS B-C 30386 1 Units : VAC Uint16 System Input RMS C-A 30387 1 Units : VAC Uint16 System Input RMS Current Phase A 30388 1 Units : A AC Uint16 System Input RMS Current Phase B 30389 1 Units : A AC Uint16 System Input RMS Current Phase C 30390 1 Units : A A Uint16 System Input Frequency 30391 1 System Input RMS A-N 30392 1 Units : VAC Uint16 System Input RMS B-N 30393 1 Units : VAC Uint16 System Input RMS C-N 30394 1 Units : VAC Uint16 System Input Power Factor Phs A 30395 1 100 Uint16 System Input Power Factor Phs B 30396 1 100 Uint16 System Input Power Factor Phs C 30397 1 100 Uint16 Bypass Input Voltage RMS A-N 30408 1 Units : VAC Uint16 Bypass Input Voltage RMS B-N 30409 1 Units : VAC Uint16 Bypass Input Voltage RMS C-N 30410 1 Units : VAC Uint16 Bypass Input Frequency 30411 1 Bypass Input Voltage RMS A-B 30412 1 Units : VAC Uint16 Bypass Input Voltage RMS B-C 30413 1 Units : VAC Uint16 Bypass Input Voltage RMS C-A 30414 1 Units : VAC Uint16 Battery Time Remaining 30425 1 Units : min Uint16 Battery Volts for Cabinet 30426 1 Units : VDC Int16 Battery Temperature for Cabinet 30427 1 Units : deg C Int16 Battery Temperature for Cabinet 30428 1 Units : deg F Int16 DC Bus Current 30429 1 Units : A DC Int16 10 Units : Hz Uint16 Bypass 10 Units : Hz Uint16 Battery 219 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-49 Liebert EPM™—Input and Holding (continued) Data Label UPS battery1 status Input Holding # of Reg Scale Notes/Units 1 = Unknown 2 = Normal 3 = Low 4 = Depleted 30430 1 System Output Voltage RMS A-N 30441 1 Units : VAC Uint16 System Output Voltage RMS B-N 30442 1 Units : VAC Uint16 System Output Voltage RMS C-N 30443 1 Units : VAC Uint16 System Output RMS Current Phs A 30444 1 Units : A AC Uint16 System Output RMS Current Phs B 30445 1 Units : A AC Uint16 System Output RMS Current Phs C 30446 1 Units : A AC Uint16 System Output Frequency 30447 1 System Output Voltage RMS A-B 30448 1 Units : VAC Uint16 System Output Voltage RMS B-C 30449 1 Units : VAC Uint16 System Output Voltage RMS C-A 30450 1 Units : VAC Uint16 System Output Power Factor Phs A 30451 1 100 Uint16 System Output Power Factor Phs B 30452 1 100 Uint16 System Output Power Factor Phs C 30453 1 100 Output 10 Units : Hz Uint16 Uint16 System Output Pct Power Phase A 30454 1 Units : % Uint16 System Output Pct Power Phase B 30455 1 Units : % Uint16 System Output Pct Power Phase C 30456 1 Units : % Uint16 MMS Output Apparent Power 30457 1 Units : kVA Uint16 MMS Output Power 30458 1 Units : kW Uint16 Output Current Crest Factor Phs A 30459 1 10 Uint16 Output Current Crest Factor Phs B 30460 1 10 Uint16 Output Current Crest Factor Phs C 30461 1 10 Uint16 System Output Power Phase A 30462 1 Units : kW Uint16 System Output Power Phase B 30463 1 Units : kW Uint16 System Output Power Phase C 30464 1 Units : kW Uint16 System Output Apparent Power Phs A 30465 1 Units : kVA Uint16 System Output Apparent Power Phs B 30466 1 Units : kVA Uint16 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 220 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-49 Liebert EPM™—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units System Output Apparent Power Phs C 30467 1 Units : kVA Uint16 System Output Power 30468 1 Units : kW Uint16 System Output Apparent Power 30469 1 Units : kVA Uint16 Inverter On/Off State 30480 1 0 = off 1 = on Maintenance Bypass Breaker 30481 1 0 = Open 1 = Close 2 = Not Installed 1 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer System Status UPS Output Source 30482 System Status 30483 1 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation ECO Mode Operation State 30484 1 0 = disabled 1 = enabled 1 0 = Open 1 = Close 2 = Not Installed 1 0 = Open 1 = Close 2 = Not Installed Input Breaker Internal Bypass Breaker 30485 30486 Output Breaker 30487 1 0 = Open 1 = Close 2 = Not Installed UPS Application Mode 30488 1 0 = UPS Mode 1 = Frequency converter mode MMS UPS Output Source 30489 1 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Intelligent Parallel Operation State 30490 1 0 = disabled 1 = enabled 221 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-49 Liebert EPM™—Input and Holding (continued) Data Label Advanced Efficiency Mode Input Holding # of Reg Scale Notes/Units 0 = unknown 1 = ECO mode 2 = Intelligent ECO mode 3 = Active Inverter ECO mode 30491 1 System Input Nominal Voltage 30502 1 System Input Nominal Frequency 30503 1 System Input Nominal Current 30504 1 Units : A AC Uint16 Bypass Nominal Voltage 30505 1 Units : VAC Uint16 System Output Nominal Voltage 30506 1 Units : VAC Uint16 System Output Nominal Frequency 30507 1 Total System Operating Time 30518 2 Average system efficiency 30520 1 Inlet Air Temperature 30521 1 Units : deg C Uint16 Inlet Air Temperature 30522 1 Units : deg F Uint16 2 Secs since Epoch(UTC) System Configuration Units : VAC Uint16 10 10 Units : Hz Uint16 Units : Hz Uint16 System Analog Units : hr Uint32 10 Units : % Uint16 System Configuration System Date and Time 39998 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 222 49998 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-50 Liebert EPM™—Glossary Data Label Advanced Efficiency Mode Data Description Advanced efficiency modes where the UPS supports the critical load using the static bypass. Average system efficiency Average system efficiency Battery Breaker 1 Open Failure Battery circuit breaker 1 failed to open Battery Breaker 2 Open Failure Battery circuit breaker 2 failed to open Battery Breaker 3 Open Failure Battery circuit breaker 3 failed to open Battery Breaker 4 Open Failure Battery circuit breaker 4 failed to open Battery Capacity Low Battery capacity is low Battery Charge Equalization Timeout The battery equalizing is time out. Battery Charging Error The battery is not charging properly Battery Charging Inhibited Battery charging is inhibited due to an external inhibit signal Battery Circuit Breaker 1 Open Battery circuit breaker 1 is open Battery Circuit Breaker 2 Open Battery circuit breaker 2 is open Battery Circuit Breaker 3 Open Battery circuit breaker 3 is open Battery Circuit Breaker 4 Open Battery circuit breaker 4 is open Battery Converter Current Limit The battery converter has reached is maximum current limit. Battery Converter Failure Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module. Battery Discharging The battery is discharging Battery Equalize The rectifier output voltage is increased to equalize the battery voltage level. Battery Fault A short circuit exists in the battery system. Battery Ground Fault Battery system ground fault amperage exceeds the threshold Battery Low The calculated battery time remaining has reached the low battery threshold Battery Not Qualified The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open. Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Room Alarm The ambient temperature of the battery room is abnormal. Battery Self Test Battery self test is in progress Battery Temperature for Cabinet The battery temperature for a cabinet Battery Terminals Reversed The measured battery voltage is a negative value due to reverse battery terminal connections. Battery Time Remaining The calculated available time on battery Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Bypass - Excess Auto Retransfers The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval Bypass Backfeed Detected The system detected a voltage on the bypass when none was expected Bypass Input Frequency The bypass input frequency Bypass Input Voltage Fault The system has detected the bypass voltage is unqualified. Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B Bypass Input Voltage RMS A-N The bypass input RMS voltage between phase A and Neutral Bypass Input Voltage RMS B-C The bypass input RMS voltage between phases B and C Bypass Input Voltage RMS B-N The bypass input RMS voltage between phase B and Neutral Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A Bypass Input Voltage RMS C-N The bypass input RMS voltage between phase C and Neutral 223 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-50 Liebert EPM™—Glossary (continued) Data Label Data Description Bypass Nominal Voltage Bypass nominal (or rated) voltage Bypass Not Available A problem associated with the bypass has been detected Bypass Static Switch Unavailable The static bypass is unavailable to support the critical load. DC Bus Abnormal The system has detected an abnormal DC Bus Voltage. DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value ECO Mode Operation State This setting is used to enable or disable ECO Mode. Equipment Over Temperature Equipment over temperature summary event Excess ECO Suspends Number of automatic suspensions has exceeded the ECO Mode Maximum Auto Suspensions setting. Fuse Failure A summary event indicating one or more fuse failures Inlet Air Temperature The temperature of the inlet air Input Breaker Input breaker Input Source Backfeed The battery is backfeeding the input source. Intelligent Parallel Operation State This setting is used to enable or disable Intelligent Paralleling. Internal Bypass Breaker Internal bypass breaker Internal Communications Failure The control has detected a communication failure of a component on the internal communication bus Inverter Failure Inverter failure - inverter output is off Inverter On/Off State inverter on/off state Inverter Overload Inverter in overload fault Inverter Relay Fault The inverter relay has malfunctioned. Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload LBS Cable Failure Load Bus Sync communications is abnormal. A problem with the LBS cable may exist. LBS Inhibited The system has detected that conditions to perform Load Bus Sync are not satisfied Load Impact Transfer On bypass as result of load impact. Load Sharing Fault Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current. Loss of Redundancy The multi-module collection doesn't have enough modules to satisfy the redundancy configuration. Loss of Synchronization The inverter and bypass are no longer synchronized. Main Battery Disconnect Open Main battery disconnect is open Mains Input Neutral Lost Loss of neutral in the input source is detected. Maintenance Bypass Breaker Maintenance bypass breaker MMS On Battery The multi-module system is on battery MMS Output Apparent Power The sum total apparent power of all system output modules MMS Output Power The sum total power of all system output modules MMS Over Capacity The multi-module system load is larger than the apparent power limit setting. MMS Overload Multi-module system overload MMS UPS Output Source Multi-module UPS output source On Generator A generator is supplying the power to the system Output Breaker Output breaker Output Current Crest Factor Phs A Output current crest factor of Phase A. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 224 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-50 Liebert EPM™—Glossary (continued) Data Label Data Description Output Current Crest Factor Phs B Output current crest factor of Phase B. Output Current Crest Factor Phs C Output current crest factor of Phase C. Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Parallel Cable Failure The UPS parallel system communications is abnormal. A problem with the parallel cable may exist. Parallel Comm Warning Parallel communication bus warning Power Module Over Temperature The Power Module has detected an over temperature condition. Power Supply Failure Power supply failure Rectifier Failure Rectifier failure - rectifier is off System Date and Time The system date and time System Fan Failure System fan failure - one or more fans have failed System Input Current Imbalance System Input Currents are Imbalanced System Input Current Limit The RMS input current has reached the input current limit threshold System Input Frequency The system input frequency System Input Nominal Current The nominal (or rated) system input current System Input Nominal Frequency The nominal (or rated) system input frequency System Input Nominal Voltage The nominal (or rated) system input voltage System Input Phs Rotation Error The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C) System Input Power Factor Phs A The system input power factor for Phase A System Input Power Factor Phs B The system input power factor for Phase B System Input Power Factor Phs C The system input power factor for Phase C System Input Power Problem The input is not qualified to provide power to the system System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power Phs A System output apparent power on phase A System Output Apparent Power Phs B System output apparent power on phase B System Output Apparent Power Phs C System output apparent power on phase C System Output Apparent Power The sum total apparent power of all system output phases System Output Fault A fault has been detected in the system output System Output Frequency The system output frequency System Output Nominal Frequency The nominal (or rated) system output frequency System Output Nominal Voltage The nominal (or rated) system output voltage System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity System Output Power Factor Phs A The system output power factor of phase A 225 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-50 Liebert EPM™—Glossary (continued) Data Label Data Description System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power Phase A The system output power on phase A. System Output Power Phase B The system output power on phase B. System Output Power Phase C The system output power on phase C. System Output Power The sum total power of all system output phases System Output RMS Current Phs A The system output RMS current for Phase A System Output RMS Current Phs B The system output RMS current for Phase B System Output RMS Current Phs C The system output RMS current for Phase C System Output Voltage RMS A-B The system output RMS voltage between phases A and B System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral System Output Voltage RMS B-C The system output RMS voltage between phases B and C System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral System Output Voltage RMS C-A The system output RMS voltage between phases C and A System Output Voltage RMS C-N The system output RMS voltage between phases C and Neutral System Shutdown - EPO System shutdown due to Emergency Power Off (EPO) System Status The operating status for the system Top Outlet Fan Fault Top outlet fan fault - one or more top outlet fans have failed. Total System Operating Time The cumulative operation time of the unit Transfer to Bypass - System Overload The UPS System has transferred to bypass because the active power modules cannot support the critical load. UPS Application Mode UPS application mode. UPS battery1 status UPS battery status UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source User Operation Invalid User attempted an invalid operation. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 226 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-51 Liebert eXL™—Status and Coil Data Label Status Coil Number of Bits Notes Input Mains Input Neutral Lost 10001 1 Active on Alarm System Input Phs Rotation Error 10002 1 Active on Alarm System Input Power Problem 10003 1 Active on Alarm Input Source Backfeed 10004 1 Active on Alarm 10015 1 Active on Alarm Bypass Bypass Not Available Bypass Static Switch Unavailable 10016 1 Active on Alarm Bypass - Excess Auto Retransfers 10017 1 Active on Alarm UPS Output on Bypass 10018 1 Active on Alarm Output Load on Maint. Bypass 10019 1 Active on Alarm Bypass Overload 10020 1 Active on Alarm Bypass Frequency Error 10021 1 Active on Alarm Bypass Input Voltage Fault 10022 1 Active on Alarm Bypass Backfeed Detected 10023 1 Active on Alarm Main Battery Disconnect Open 10034 1 Active on Alarm Battery Circuit Breaker 4 Open 10035 1 Active on Alarm Battery Circuit Breaker 3 Open 10036 1 Active on Alarm Battery Circuit Breaker 2 Open 10037 1 Active on Alarm Battery Circuit Breaker 1 Open 10038 1 Active on Alarm Battery Battery Self Test 10039 1 Active on Alarm Battery Charging Inhibited 10040 1 Active on Alarm Battery Discharging 10041 1 Active on Alarm Battery Manual Test In Progress 10042 1 Active on Alarm Battery Auto Test In Progress 10043 1 Active on Alarm Battery Test Passed 10044 1 Active on Alarm Battery Test Failed 10045 1 Active on Alarm Battery Over Temperature 10046 1 Active on Alarm Battery Low 10047 1 Active on Alarm Battery Ground Fault 10048 1 Active on Alarm Battery Not Qualified 10049 1 Active on Alarm Battery Terminals Reversed 10050 1 Active on Alarm Battery Capacity Low 10051 1 Active on Alarm Battery Converter Current Limit 10052 1 Active on Alarm Battery Charge Equalization Timeout 10053 1 Active on Alarm Battery Fault 10054 1 Active on Alarm Battery Room Alarm 10055 1 Active on Alarm Battery Breaker 1 Open Failure 10056 1 Active on Alarm Battery Breaker 2 Open Failure 10057 1 Active on Alarm Battery Breaker 3 Open Failure 10058 1 Active on Alarm Battery Breaker 4 Open Failure 10059 1 Active on Alarm Battery Equalize 10060 1 Active on Alarm 10071 1 Active on Alarm Inverter Loss of Synchronization 227 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-51 Liebert eXL™—Status and Coil (continued) Data Label Status Coil Number of Bits Notes Output Output Overload 10082 1 Active on Alarm System Output Fault 10083 1 Active on Alarm Power Module Input Current Abnormal 10094 1 Active on Alarm Rectifier Failure 10095 1 Active on Alarm Inverter Failure 10096 1 Active on Alarm DC Bus Abnormal 10097 1 Active on Alarm Load Sharing Fault 10098 1 Active on Alarm Power Modules 1 Inverter Relay Fault 10099 1 Active on Alarm Battery Charging Error 10100 1 Active on Alarm Battery Converter Failure 10101 1 Active on Alarm Power Module Balancer of DC Bus Failure 10102 1 Active on Alarm Inverter Shutdown - Overload 10103 1 Active on Alarm Power Module Fuse Failure 10104 1 Active on Alarm Power Module Power Supply Failure 10105 1 Active on Alarm Power Module Fan Fault 10106 1 Active on Alarm Power Module Over Temperature 10107 1 Active on Alarm Inverter Overload 10108 1 Active on Alarm Power Module Input Current Abnormal 10119 1 Active on Alarm Rectifier Failure 10120 1 Active on Alarm Inverter Failure 10121 1 Active on Alarm DC Bus Abnormal 10122 1 Active on Alarm Load Sharing Fault 10123 1 Active on Alarm Power Modules 2 Inverter Relay Fault 10124 1 Active on Alarm Battery Charging Error 10125 1 Active on Alarm Battery Converter Failure 10126 1 Active on Alarm Power Module Balancer of DC Bus Failure 10127 1 Active on Alarm Inverter Shutdown - Overload 10128 1 Active on Alarm Power Module Fuse Failure 10129 1 Active on Alarm Power Module Power Supply Failure 10130 1 Active on Alarm Power Module Fan Fault 10131 1 Active on Alarm Power Module Over Temperature 10132 1 Active on Alarm Inverter Overload 10133 1 Active on Alarm Power Module Input Current Abnormal 10569 1 Active on Alarm Rectifier Failure 10570 1 Active on Alarm Inverter Failure 10571 1 Active on Alarm DC Bus Abnormal 10572 1 Active on Alarm Load Sharing Fault 10573 1 Active on Alarm Power Modlues 20 Inverter Relay Fault 10574 1 Active on Alarm Battery Charging Error 10575 1 Active on Alarm Battery Converter Failure 10576 1 Active on Alarm Power Module Balancer of DC Bus Failure 10577 1 Active on Alarm Inverter Shutdown - Overload 10578 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 228 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-51 Liebert eXL™—Status and Coil (continued) Number of Bits Notes 10579 1 Active on Alarm Power Module Power Supply Failure 10580 1 Active on Alarm Power Module Fan Fault 10581 1 Active on Alarm Data Label Status Power Module Fuse Failure Coil Power Module Over Temperature 10582 1 Active on Alarm Inverter Overload 10583 1 Active on Alarm 10594 1 Active on Alarm System Status Loss of Redundancy Parallel Cable Failure 10595 1 Active on Alarm LBS Cable Failure 10596 1 Active on Alarm Transfer to Bypass - System Overload 10597 1 Active on Alarm Excess ECO Suspends 10598 1 Active on Alarm Transformer Overtemperature 10599 1 Active on Alarm MMS Over Capacity 10600 1 Active on Alarm Loss of Redundancy 10601 1 Active on Alarm User Operation Invalid 10602 1 Active on Alarm Load Impact Transfer 10603 1 Active on Alarm Internal Communications Failure 10604 1 Active on Alarm MMS Overload 10605 1 Active on Alarm Parallel Comm Warning 10606 1 Active on Alarm Equipment Over Temperature 10607 1 Active on Alarm LBS Inhibited 10608 1 Active on Alarm On Generator 10609 1 Active on Alarm LBS Active 10610 1 Active on Alarm System Shutdown - EPO 10611 1 Active on Alarm Top Outlet Fan Fault 10612 1 Active on Alarm 229 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-52 Liebert eXL™—Input and Holding Data Label Input Register Holding Register # of Reg. Scale Notes / Units Input System Input RMS A-B 30385 1 Units : VAC Uint16 System Input RMS B-C 30386 1 Units : VAC Uint16 System Input RMS C-A 30387 1 Units : VAC Uint16 System Input RMS Current Phase A 30388 1 Units : A AC Uint16 System Input RMS Current Phase B 30389 1 Units : A AC Uint16 System Input RMS Current Phase C 30390 1 Units : A AC Uint16 System Input Frequency 30391 1 System Input RMS A-N 30392 1 Units : VAC Uint16 System Input RMS B-N 30393 1 Units : VAC Uint16 System Input RMS C-N 30394 1 Units : VAC Uint16 System Input Power Factor Phs A 30395 1 10 100 Units : Hz Uint16 Uint16 System Input Power Factor Phs B 30396 1 100 Uint16 System Input Power Factor Phs C 30397 1 100 Uint16 System Input Nominal Voltage 30398 1 System Input Nominal Frequency 30399 1 System Input Nominal Current 30400 1 Units : A AC Uint16 System Input Brown Out Count 30401 1 Uint16 System Input Black Out Count 30402 1 Uint16 Input Breaker 30403 1 0 = Open 1 = Close 2 = Not Installed Bypass Input Voltage RMS A-N 30414 1 Units : VAC Uint16 Bypass Input Voltage RMS B-N 30415 1 Units : VAC Uint16 Bypass Input Voltage RMS C-N 30416 1 Units : VAC Uint16 Bypass Input Frequency 30417 1 Bypass Input Voltage RMS A-B 30418 1 Units : VAC Uint16 10 Units : Hz Uint16 Bypass 10 Units : Hz Uint16 Units : VAC Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 230 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-52 Liebert eXL™—Input and Holding (continued) Data Label Input Register Holding Register # of Reg. Scale Notes / Units Bypass Input Voltage RMS B-C 30419 1 Units : VAC Uint16 Bypass Input Voltage RMS C-A 30420 1 Units : VAC Uint16 Bypass Nominal Voltage 30421 1 Units : VAC Uint16 30422 1 0 = Open 1 = Close 2 = Not Installed Battery Time Remaining 30433 1 Units : min Uint16 DC Bus Current 30434 1 Units : A DC Int16 Time Until Next Auto Battery Test 30435 2 Units : min Uint32 Battery Percentage Charge 30437 1 Units : % Uint16 Number of Discharge Cycles 30438 1 Uint16 Internal Bypass Breaker Battery Accumulated Discharge Time 30439 1 Units : hr Uint16 Low Battery Warning Time 30440 1 Units : min Uint16 1 1 = Unknown 2 = Normal 3 = Low 4 = Depleted UPS Battery Status 30441 Battery charge status. 30442 1 0 = fully charged 1 = charging 2 = discharging 3 = not charging (charger off) Manual Battery Test 30443 1 1 = Start Test Automatic Battery Test 30444 1 0 = disabled 1 = enabled 0 = 8 weeks 1 = 12 weeks 2 = 16 weeks 3 = 20 weeks 4 = 26 weeks Auto Battery Test Interval 30445 1 DC Bus Voltage 30446 1 Battery Temperature 30447 1 Units : deg C Int16 Battery Temperature 30448 1 Units : deg F Int16 10 Units : VDC Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 231 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-52 Liebert eXL™—Input and Holding (continued) Data Label Input Register Holding Register # of Reg. Scale Notes / Units Battery Cabinets 1 Battery Temperature for Cabinet 30459 1 Units : deg C Int16 Battery Temperature for Cabinet 30460 1 Units : deg F Int16 Battery Volts for Cabinet 30461 1 Units : VDC Uint16 Battery Temperature for Cabinet 30472 1 Units : deg C Int16 Battery Temperature for Cabinet 30473 1 Units : deg F Int16 Battery Volts for Cabinet 30474 1 Units : VDC Uint16 Battery Temperature for Cabinet 30550 1 Units : deg C Int16 Battery Temperature for Cabinet 30551 1 Units : deg F Int16 Battery Volts for Cabinet 30552 1 Units : VDC Uint16 Output Breaker 30563 1 0 = Open 1 = Close 2 = Not Installed Inverter On/Off State 30564 1 0 = off 1 = on System Output Voltage RMS A-N 30575 1 Units : VAC Uint16 System Output Voltage RMS B-N 30576 1 Units : VAC Uint16 System Output Voltage RMS C-N 30577 1 Units : VAC Uint16 System Output RMS Current Phs A 30578 1 Units : A AC Uint16 System Output RMS Current Phs B 30579 1 Units : A AC Uint16 System Output RMS Current Phs C 30580 1 Units : A AC Uint16 System Output Frequency 30581 1 System Output Voltage RMS A-B 30582 1 Units : VAC Uint16 System Output Voltage RMS B-C 30583 1 Units : VAC Uint16 Battery Cabinets 2 Battery Cabinets 8 Inverter Output 10 Units : Hz Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 232 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-52 Liebert eXL™—Input and Holding (continued) Data Label Input Register Holding Register # of Reg. Scale Notes / Units Units : VAC Uint16 System Output Voltage RMS C-A 30584 1 System Output Power Factor Phs A 30585 1 100 Uint16 System Output Power Factor Phs B 30586 1 100 Uint16 System Output Power Factor Phs C 30587 1 100 Uint16 System Output Pct Power Phase A 30588 1 Units : % Uint16 System Output Pct Power Phase B 30589 1 Units : % Uint16 System Output Pct Power Phase C 30590 1 Units : % Uint16 MMS Output Apparent Power 30591 1 Units : kVA Uint16 MMS Output Power 30592 1 Units : kW Uint16 Output Current Crest Factor Phs A 30593 1 10 Uint16 Output Current Crest Factor Phs B 30594 1 10 Uint16 Output Current Crest Factor Phs C 30595 1 10 Uint16 System Output Power Phase A 30596 1 Units : kW Uint16 System Output Power Phase B 30597 1 Units : kW Uint16 System Output Power Phase C 30598 1 Units : kW Uint16 System Output Apparent Power Phs A 30599 1 Units : kVA Uint16 System Output Apparent Power Phs B 30600 1 Units : kVA Uint16 System Output Apparent Power Phs C 30601 1 Units : kVA Uint16 System Output Power 30602 1 Units : kW Uint16 System Output Apparent Power 30603 1 Units : kVA Uint16 System Output Pct Pwr (VA) Phs A 30604 1 Units : % Uint16 System Output Pct Pwr (VA) Phs B 30605 1 Units : % Uint16 System Output Pct Pwr (VA) Phs C 30606 1 Units : % Uint16 System Output Nominal Voltage 30607 1 Units : VAC Uint16 System Output Nominal Frequency 30608 1 10 Units : Hz Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 233 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-52 Liebert eXL™—Input and Holding (continued) Data Label Input Register Holding Register # of Reg. Scale Notes / Units Power Modules 1 Power Module Sleep Status 30619 1 0 = Sleeping 1 = Not Sleeping Module Operating Status 30620 1 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30621 1 0 = Inverter Inactive 1 = Inverter Active 30632 1 0 = Sleeping 1 = Not Sleeping Power Modules 2 Power Module Sleep Status Module Operating Status 30633 1 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30634 1 0 = Inverter Inactive 1 = Inverter Active 30866 1 0 = Sleeping 1 = Not Sleeping Power Modules 20 Power Module Sleep Status Module Operating Status 30867 1 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30868 1 0 = Inverter Inactive 1 = Inverter Active Power Module Bypass Input Frequency 30879 1 Power Module Bypass Input Voltage RMS A-N 30880 1 Units : VAC Uint16 Power Module Bypass Input Voltage RMS B-N 30881 1 Units : VAC Uint16 Power Module Bypass Input Voltage RMS C-N 30882 1 Units : VAC Uint16 Power Module Bypass Input Voltage RMS A-B 30883 1 Units : VAC Uint16 Power Module Bypass Input Voltage RMS B-C 30884 1 Units : VAC Uint16 Power Module Bypass Input Voltage RMS C-A 30885 1 Units : VAC Uint16 System Set To Operate With 30896 1 0 = No Redundancy 1 = Redundancy Number Of Active Power Modules 30897 1 Uint16 Bypass Control Module 10 Units : Hz Uint16 System Status If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 234 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-52 Liebert eXL™—Input and Holding (continued) Data Label Input Register Holding Register # of Reg. Scale Notes / Units Number of Installed Power Modules 30898 1 Uint16 Inlet Air Temperature 30899 1 Units : deg C Uint16 Inlet Air Temperature 30900 1 Units : deg F Uint16 Average system efficiency 30901 1 Maintenance Bypass Breaker 30902 1 0 = Open 1 = Close 2 = Not Installed ECO Mode Operation State 30903 1 0 = disabled 1 = enabled UPS Application Mode 30904 1 0 = UPS Mode 1 = Frequency converter mode 10 Units : % Uint16 MMS UPS Output Source 30905 1 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Intelligent Parallel Operation State 30906 1 0 = disabled 1 = enabled Bypass Isolation Breaker 30907 1 0 = Open 1 = Close 2 = Not Installed Total System Operating Time 30918 2 Units : hr Uint32 System Capacity 30920 1 Units : kVA Uint16 1 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer 1 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 2 Units : Secs since Epoch(UTC) System Configuration UPS Output Source 30921 System Status 30922 System Date and Time 39998 49998 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 235 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-53 Liebert eXL™—Glossary Data Label Data Description Accumulated Discharge Time Total accumulated discharge time for the Battery Module since it was made. Auto Battery Test Interval The time between automatic battery tests. Automatic Battery Test Enable/disable the automatic battery test schedule. Average system efficiency Average system efficiency Battery Auto Test In Progress Automatic battery test is in progress Battery Breaker 1 Open Failure Battery circuit breaker 1 failed to open Battery Breaker 2 Open Failure Battery circuit breaker 2 failed to open Battery Breaker 3 Open Failure Battery circuit breaker 3 failed to open Battery Breaker 4 Open Failure Battery circuit breaker 4 failed to open Battery Capacity Low Battery capacity is low Battery Charge Equalization Timeout The battery equalizing is time out. Battery charge status. Battery charge status. Battery Charging Error The battery is not charging properly Battery Charging Inhibited Battery charging is inhibited due to an external inhibit signal Battery Circuit Breaker 1 Open Battery circuit breaker 1 is open Battery Circuit Breaker 2 Open Battery circuit breaker 2 is open Battery Circuit Breaker 3 Open Battery circuit breaker 3 is open Battery Circuit Breaker 4 Open Battery circuit breaker 4 is open Battery Converter Current Limit The battery converter has reached is maximum current limit. Battery Converter Failure Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module. Battery Discharging The battery is discharging Battery Equalize The rectifier output voltage is increased to equalize the battery voltage level. Battery Fault A short circuit exists in the battery system. Battery Ground Fault Battery system ground fault amperage exceeds the threshold Battery Low The calculated battery time remaining has reached the low battery threshold Battery Manual Test In Progress Manual battery test is in progress Battery Not Qualified The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open. Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Percentage Charge The percentage of battery charge Battery Room Alarm The ambient temperature of the battery room is abnormal. Battery Self Test Battery self test is in progress Battery Temperature for Cabinet The battery temperature for a cabinet Battery Temperature The highest battery temperature among all Battery Cabinets Battery Terminals Reversed The measured battery voltage is a negative value due to reverse battery terminal connections. Battery Test Failed Battery test failed Battery Test Passed Battery test passed Battery Time Remaining The calculated available time on battery Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Bypass - Excess Auto Retransfers The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval Bypass Backfeed Detected The system detected a voltage on the bypass when none was expected Bypass Frequency Error The bypass frequency is outside the inverter synchronization limits Bypass Input Frequency The bypass input frequency Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 236 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-53 Liebert eXL™—Glossary (continued) Data Label Data Description Bypass Input Voltage Fault The system has detected the bypass voltage is unqualified. Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B Bypass Input Voltage RMS A-N The bypass input RMS voltage between phase A and Neutral Bypass Input Voltage RMS B-C The bypass input RMS voltage between phases B and C Bypass Input Voltage RMS B-N The bypass input RMS voltage between phase B and Neutral Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A Bypass Input Voltage RMS C-N The bypass input RMS voltage between phase C and Neutral Bypass Isolation Breaker Bypass isolation breaker Bypass Nominal Voltage Bypass nominal (or rated) voltage Bypass Not Available A problem associated with the bypass has been detected Bypass Overload Bypass overloaded, reduce load immediately. Bypass Static Switch Unavailable The static bypass is unavailable to support the critical load. DC Bus Abnormal The system has detected an abnormal DC Bus Voltage. DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value DC Bus Voltage The voltage between the positive and negative terminals of the DC bus at the battery input ECO Mode Operation State This setting is used to enable or disable ECO Mode. Equipment Over Temperature Equipment over temperature summary event Excess ECO Suspends Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting. Inlet Air Temperature The temperature of the inlet air Input Breaker Input breaker Input Source Backfeed The battery is backfeeding the input source. Intelligent Parallel Operation State This setting is used to enable or disable Intelligent Paralleling. Internal Bypass Breaker Internal bypass breaker Internal Communications Failure The control has detected a communication failure of a component on the internal communication bus Inverter Failure Inverter failure - inverter output is off Inverter On/Off State inverter on/off state Inverter Overload Inverter in overload fault Inverter Relay Fault The inverter relay has malfunctioned. Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload Inverter Status Status of the inverter output. Active means the inverter is online with regulated output voltage and ready to power the load. Inactive means the inverter is offline and not ready to power the load. LBS Active The Load Bus Sync option is active LBS Cable Failure Load Bus Sync communications is abnormal. A problem with the LBS cable may exist. LBS Inhibited The system has detected that conditions to perform Load Bus Sync are not satisfied Load Impact Transfer On bypass as result of load impact. Load Sharing Fault Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current. Loss of Redundancy The multi-module collection doesn't have enough modules to satisfy the redundancy configuration. Loss of Redundancy The system has an insufficient number of power modules to provide redundancy. 237 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-53 Liebert eXL™—Glossary (continued) Data Label Data Description Loss of Synchronization The inverter and bypass are no longer synchronized. Low Battery Warning Time When battery time remaining falls to, or below, this value the low battery alarm is activated. Main Battery Disconnect Open Main battery disconnect is open Mains Input Neutral Lost Loss of neutral in the input source is detected. Maintenance Bypass Breaker Maintenance bypass breaker Manual Battery Test Command to initiate a manual battery test. MMS Output Apparent Power The sum total apparent power of all system output modules MMS Output Power The sum total power of all system output modules MMS Over Capacity The multi-module system load is larger than the apparent power limit setting. MMS Overload Multi-module system overload MMS UPS Output Source Multi-module UPS output source Module Operating Status The operating status for this Power Module. Number Of Active Power Modules The total number of active power modules. Number of Discharge Cycles The total number of battery discharge cycles for the Battery Module since it was made. Number of Installed Power Modules The total number of Power Modules installed. On Generator A generator is supplying the power to the system Output Breaker Output breaker Output Current Crest Factor Phs A Output current crest factor of Phase A. Output Current Crest Factor Phs B Output current crest factor of Phase B. Output Current Crest Factor Phs C Output current crest factor of Phase C. Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Output Overload An overload exists on the output. Parallel Cable Failure The UPS parallel system communications is abnormal. A problem with the parallel cable may exist. Parallel Comm Warning Parallel communication bus warning Power Module Balancer of DC Bus Failure Balancer of DC Bus in the power module has failed Power Module Bypass Input Frequency The bypass input frequency detected by power module Power Module Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B detected by power module Power Module Bypass Input Voltage RMS A-N The bypass input RMS voltage between phase A and Neutral detected by power module Power Module Bypass Input Voltage RMS B-C The bypass input RMS voltage between phases B and C detected by power module Power Module Bypass Input Voltage RMS B-N The bypass input RMS voltage between phase B and Neutral detected by power module Power Module Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A detected by power module Power Module Bypass Input Voltage RMS C-N The bypass input RMS voltage between phase C and Neutral detected by power module Power Module Fan Fault The Power Module has detected a fan fault. Power Module Fuse Failure A summary event indicating one or more fuse failures in the power module Power Module Input Current Abnormal Input current of the power module is abnormal Power Module Over Temperature The Power Module has detected an over temperature condition. Power Module Power Supply Failure Power module power supply failure Power Module Sleep Status Sleep status of the Power module Rectifier Failure Rectifier failure - rectifier is off Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 238 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-53 Liebert eXL™—Glossary (continued) Data Label Data Description System Capacity System capacity supported by the installed power modules. System Date and Time The system date and time System Input Black Out Count The number of occurrences, since the last reset, where the input was not qualified to provide power to the system System Input Brown Out Count The number of occurrences, since the last reset, where the system input voltage has fallen below a pre-determined threshold for a specified amount of time System Input Frequency The system input frequency System Input Nominal Current The nominal (or rated) system input current System Input Nominal Frequency The nominal (or rated) system input frequency System Input Nominal Voltage The nominal (or rated) system input voltage System Input Phs Rotation Error The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C) System Input Power Factor Phs A The system input power factor for Phase A System Input Power Factor Phs B The system input power factor for Phase B System Input Power Factor Phs C The system input power factor for Phase C System Input Power Problem The input is not qualified to provide power to the system System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power Phs A System output apparent power on phase A System Output Apparent Power Phs B System output apparent power on phase B System Output Apparent Power Phs C System output apparent power on phase C System Output Apparent Power The sum total apparent power of all system output phases System Output Fault A fault has been detected in the system output System Output Frequency The system output frequency System Output Nominal Frequency The nominal (or rated) system output frequency System Output Nominal Voltage The nominal (or rated) system output voltage System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity System Output Pct Pwr (VA) Phs A The system output apparent power on phase A as a percentage of the rated capacity System Output Pct Pwr (VA) Phs B The system output apparent power on phase B as a percentage of the rated capacity System Output Pct Pwr (VA) Phs C The system output apparent power on phase C as a percentage of the rated capacity System Output Power Factor Phs A The system output power factor of phase A System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power Phase A The system output power on phase A. System Output Power Phase B The system output power on phase B. System Output Power Phase C The system output power on phase C. 239 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-53 Liebert eXL™—Glossary (continued) Data Label Data Description System Output Power The sum total power of all system output phases System Output RMS Current Phs A The system output RMS current for Phase A System Output RMS Current Phs B The system output RMS current for Phase B System Output RMS Current Phs C The system output RMS current for Phase C System Output Voltage RMS A-B The system output RMS voltage between phases A and B System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral System Output Voltage RMS B-C The system output RMS voltage between phases B and C System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral System Output Voltage RMS C-A The system output RMS voltage between phases C and A System Output Voltage RMS C-N The system output RMS voltage between phases C and Neutral System Set To Operate With If this point reports 'Redundancy' then the system is configured for redundancy and the 'Loss of Redundancy' alarm is enabled. System Shutdown - EPO System shutdown due to Emergency Power Off (EPO) System Status The operating status for the system Time Until Next Auto Battery Test The time until the next automatic battery test is started. Top Outlet Fan Fault Top outlet fan fault - one or more top outlet fans have failed. Total System Operating Time The cumulative operation time of the unit Transfer to Bypass - System Overload The UPS System has transferred to bypass because the active power modules cannot support the critical load. Transformer Overtemperature Transformer temperature has exceeded the limit UPS Application Mode UPS application mode. UPS Battery Status UPS battery status UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source User Operation Invalid User attempted an invalid operation. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 240 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-54 Liebert eXM™—Controller with LCD HMI—Status and Coil Data Label Status Coil Number of Bits Notes System Status Battery Equalize 10001 — 1 Active on Alarm Battery Charging Inhibited 10002 — 1 Active on Alarm On Generator 10003 — 1 Active on Alarm Battery Self Test 10004 — 1 Active on Alarm Battery Circuit Breaker 1 Open 10005 — 1 Active on Alarm Battery Circuit Breaker 2 Open 10006 — 1 Active on Alarm Battery Circuit Breaker 3 Open 10007 — 1 Active on Alarm Battery Circuit Breaker 4 Open 10008 — 1 Active on Alarm Main Battery Disconnect Open 10009 — 1 Active on Alarm System Events System Input Power Problem 10020 — 1 Active on Alarm Rectifier Failure 10021 — 1 Active on Alarm Inverter Failure 10022 — 1 Active on Alarm Bypass Not Available 10023 — 1 Active on Alarm Battery Low 10024 — 1 Active on Alarm LBS Inhibited 10025 — 1 Active on Alarm System Fan Failure 10026 — 1 Active on Alarm Equipment Over Temperature 10027 — 1 Active on Alarm System Shutdown - EPO 10028 — 1 Active on Alarm Bypass Static Switch Unavailable 10029 — 1 Active on Alarm Bypass - Excess Auto Retransfers 10030 — 1 Active on Alarm Parallel Comm Warning 10031 — 1 Active on Alarm Power Supply Failure 10032 — 1 Active on Alarm Battery Over Temperature 10033 — 1 Active on Alarm System Input Phs Rotation Error 10034 — 1 Active on Alarm Fuse Failure 10035 — 1 Active on Alarm Inverter Overload 10036 — 1 Active on Alarm MMS Overload 10037 — 1 Active on Alarm Inverter Shutdown - Overload 10038 — 1 Active on Alarm System Output Fault 10039 — 1 Active on Alarm Internal Communications Failure 10040 — 1 Active on Alarm Battery Charging Error 10041 — 1 Active on Alarm System Input Current Imbalance 10042 — 1 Active on Alarm Battery Not Qualified 10043 — 1 Active on Alarm Battery Terminals Reversed 10044 — 1 Active on Alarm Battery Converter Failure 10045 — 1 Active on Alarm Load Sharing Fault 10046 — 1 Active on Alarm DC Bus Abnormal 10047 — 1 Active on Alarm Mains Input Neutral Lost 10048 — 1 Active on Alarm Load Impact Transfer 10049 — 1 Active on Alarm User Operation Invalid 10050 — 1 Active on Alarm Battery Discharging 10051 — 1 Active on Alarm UPS Output on Bypass 10052 — 1 Active on Alarm Output Load on Maint. Bypass 10053 — 1 Active on Alarm Battery Capacity Low 10054 — 1 Active on Alarm 241 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-54 Liebert eXM™—Controller with LCD HMI—Status and Coil (continued) Data Label Status Coil Number of Bits Notes MMS On Battery 10055 — 1 Active on Alarm Loss of Redundancy 10056 — 1 Active on Alarm Top Outlet Fan Fault 10057 — 1 Active on Alarm MMS Over Capacity 10058 — 1 Active on Alarm Bypass Input Voltage Fault 10059 — 1 Active on Alarm Power Module Over Temperature 10060 — 1 Active on Alarm Excess ECO Suspends 10061 — 1 Active on Alarm Battery Ground Fault 10062 — 1 Active on Alarm System Input Current Limit 10063 — 1 Active on Alarm Inverter Relay Fault 10064 — 1 Active on Alarm Transfer to Bypass - System Overload 10065 — 1 Active on Alarm Input Source Backfeed 10066 — 1 Active on Alarm Loss of Synchronization 10067 — 1 Active on Alarm Battery Converter Current Limit 10068 — 1 Active on Alarm LBS Cable Failure 10069 — 1 Active on Alarm Battery Charge Equalization Timeout 10070 — 1 Active on Alarm Parallel Cable Failure 10071 — 1 Active on Alarm Battery Fault 10072 — 1 Active on Alarm Battery Room Alarm 10073 — 1 Active on Alarm Battery Breaker 1 Open Failure 10074 — 1 Active on Alarm Battery Breaker 2 Open Failure 10075 — 1 Active on Alarm Battery Breaker 3 Open Failure 10076 — 1 Active on Alarm Battery Breaker 4 Open Failure 10077 — 1 Active on Alarm Bypass Backfeed Detected 10078 — 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 242 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-55 Liebert eXM™—Controller with LCD HMI—Input and Holding Data Label Input Holding # of Reg Scale Notes/Units System Input RMS A-B 30385 — 1 — Units : VAC Uint16 System Input RMS B-C 30386 — 1 — Units : VAC Uint16 System Input RMS C-A 30387 — 1 — Units : VAC Uint16 System Input RMS Current Phase A 30388 — 1 — Units : A AC Uint16 System Input RMS Current Phase B 30389 — 1 — Units : A AC Uint16 System Input RMS Current Phase C 30390 — 1 — Units : A AC Uint16 System Input Frequency 30391 — 1 10 Units : Hz Uint16 System Input RMS A-N 30392 — 1 — Units : VAC Uint16 System Input RMS B-N 30393 — 1 — Units : VAC Uint16 System Input RMS C-N 30394 — 1 — Units : VAC Uint16 System Input Power Factor Phs A 30395 — 1 100 Uint16 Input System Input Power Factor Phs B 30396 — 1 100 Uint16 System Input Power Factor Phs C 30397 — 1 100 Uint16 Bypass Input Voltage RMS A-N 30408 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS B-N 30409 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS C-N 30410 — 1 — Units : VAC Uint16 Bypass Input Frequency 30411 — 1 10 Units : Hz Uint16 Bypass Input Voltage RMS A-B 30412 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS B-C 30413 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS C-A 30414 — 1 — Units : VAC Uint16 Battery Time Remaining 30425 — 1 — Units : min Uint16 Battery Volts for Cabinet 30426 — 1 — Units : VDC Int16 Battery Temperature for Cabinet 30427 — 1 — Units : deg C Int16 Battery Temperature for Cabinet 30428 — 1 — Units : deg F Int16 DC Bus Current 30429 — 1 — Units : A DC Int16 Bypass Battery If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 243 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-55 Liebert eXM™—Controller with LCD HMI—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units 30430 — 1 — 1 = Unknown 2 = Normal 3 = Low 4 = Depleted System Output Voltage RMS A-N 30441 — 1 — Units : VAC Uint16 System Output Voltage RMS B-N 30442 — 1 — Units : VAC Uint16 System Output Voltage RMS C-N 30443 — 1 — Units : VAC Uint16 System Output RMS Current Phs A 30444 — 1 — Units : A AC Uint16 System Output RMS Current Phs B 30445 — 1 — Units : A AC Uint16 System Output RMS Current Phs C 30446 — 1 — Units : A AC Uint16 System Output Frequency 30447 — 1 10 Units : Hz Uint16 System Output Voltage RMS A-B 30448 — 1 — Units : VAC Uint16 System Output Voltage RMS B-C 30449 — 1 — Units : VAC Uint16 System Output Voltage RMS C-A 30450 — 1 — Units : VAC Uint16 System Output Power Factor Phs A 30451 — 1 100 Uint16 UPS Battery1 Status Output System Output Power Factor Phs B 30452 — 1 100 Uint16 System Output Power Factor Phs C 30453 — 1 100 Uint16 System Output Pct Power Phase A 30454 — 1 — Units : % Uint16 System Output Pct Power Phase B 30455 — 1 — Units : % Uint16 System Output Pct Power Phase C 30456 — 1 — Units : % Uint16 MMS Output Apparent Power 30457 — 1 — Units : kVA Uint16 MMS Output Power 30458 — 1 — Units : kW Uint16 Output Current Crest Factor Phs A 30459 — 1 10 Uint16 Output Current Crest Factor Phs B 30460 — 1 10 Uint16 Output Current Crest Factor Phs C 30461 — 1 10 Uint16 System Output Power Phase A 30462 — 1 — Units : kW Uint16 System Output Power Phase B 30463 — 1 — Units : kW Uint16 System Output Power Phase C 30464 — 1 — Units : kW Uint16 System Output Apparent Power Phs A 30465 — 1 — Units : kVA Uint16 System Output Apparent Power Phs B 30466 — 1 — Units : kVA Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 244 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-55 Liebert eXM™—Controller with LCD HMI—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units System Output Apparent Power Phs C 30467 — 1 — Units : kVA Uint16 System Output Power 30468 — 1 — Units : kW Uint16 System Output Apparent Power 30469 — 1 — Units : kVA Uint16 Inverter On/Off State 30480 — 1 — 0 = off 1 = on Maintenance Bypass Breaker 30481 — 1 — 0 = Open 1 = Close 2 = Not Installed — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer System Status UPS Output Source 30482 — 1 System Status 30483 — 1 — 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation ECO Mode Operation State 30484 — 1 — 0 = disabled 1 = enabled Input Breaker 30485 — 1 — 0 = Open 1 = Close 2 = Not Installed Internal Bypass Breaker 30486 — 1 — 0 = Open 1 = Close 2 = Not Installed Output Breaker 30487 — 1 — 0 = Open 1 = Close 2 = Not Installed UPS Application Mode 30488 — 1 — 0 = UPS Mode 1 = Frequency converter mode MMS UPS Output Source 30489 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Intelligent Parallel Operation State 30490 — 1 — 0 = disabled 1 = enabled — 0 = unknown 1 = ECO mode 2 = Intelligent ECO mode 3 = Active Inverter ECO mode Advanced Efficiency Mode 30491 — 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 245 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-55 Liebert eXM™—Controller with LCD HMI—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units System Input Nominal Voltage 30502 — 1 — Units : VAC Uint16 System Input Nominal Frequency 30503 — 1 10 Units : Hz Uint16 System Input Nominal Current 30504 — 1 — Units : A AC Uint16 Bypass Nominal Voltage 30505 — 1 — Units : VAC Uint16 System Output Nominal Voltage 30506 — 1 — Units : VAC Uint16 System Output Nominal Frequency 30507 — 1 10 Units : Hz Uint16 Total System Operating Time 30518 — 2 — Units : hr Uint32 Average system efficiency 30520 — 1 10 Units : % Uint16 Inlet Air Temperature 30521 — 1 — Units : deg C Uint16 Inlet Air Temperature 30522 — 1 — Units : deg F Uint16 39998 49998 2 — Secs since Epoch(UTC) System Configuration System Analog SystemAnalog System Date and Time If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 246 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-56 Liebert eXM™—Controller with LCD HMI—Glossary Data Label Data Description Advanced Efficiency Mode Advanced efficiency modes where the UPS supports the critical load using the static bypass. Average system efficiency Average system efficiency Battery Breaker 1 Open Failure Battery circuit breaker 1 failed to open Battery Breaker 2 Open Failure Battery circuit breaker 2 failed to open Battery Breaker 3 Open Failure Battery circuit breaker 3 failed to open Battery Breaker 4 Open Failure Battery circuit breaker 4 failed to open Battery Capacity Low Battery capacity is low Battery Charge Equalization Timeout The battery equalizing is time out. Battery Charging Error The battery is not charging properly Battery Charging Inhibited Battery charging is inhibited due to an external inhibit signal Battery Circuit Breaker 1 Open Battery circuit breaker 1 is open Battery Circuit Breaker 2 Open Battery circuit breaker 2 is open Battery Circuit Breaker 3 Open Battery circuit breaker 3 is open Battery Circuit Breaker 4 Open Battery circuit breaker 4 is open Battery Converter Current Limit The battery converter has reached is maximum current limit. Battery Converter Failure Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module. Battery Discharging The battery is discharging Battery Equalize The rectifier output voltage is increased to equalize the battery voltage level. Battery Fault A short circuit exists in the battery system. Battery Ground Fault Battery system ground fault amperage exceeds the threshold Battery Low The calculated battery time remaining has reached the low battery threshold Battery Not Qualified The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open. Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Room Alarm The ambient temperature of the battery room is abnormal. Battery Self Test Battery self test is in progress Battery Temperature for Cabinet The battery temperature for a cabinet Battery Terminals Reversed The measured battery voltage is a negative value due to reverse battery terminal connections. Battery Time Remaining The calculated available time on battery Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Bypass - Excess Auto Retransfers The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval Bypass Backfeed Detected The system detected a voltage on the bypass when none was expected Bypass Input Frequency The bypass input frequency Bypass Input Voltage Fault The system has detected the bypass voltage is unqualified. Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B Bypass Input Voltage RMS A-N The bypass input RMS voltage between phase A and Neutral Bypass Input Voltage RMS B-C The bypass input RMS voltage between phases B and C Bypass Input Voltage RMS B-N The bypass input RMS voltage between phase B and Neutral Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A Bypass Input Voltage RMS C-N The bypass input RMS voltage between phase C and Neutral Bypass Nominal Voltage Bypass nominal (or rated) voltage Bypass Not Available A problem associated with the bypass has been detected Bypass Static Switch Unavailable The static bypass is unavailable to support the critical load. DC Bus Abnormal The system has detected an abnormal DC Bus Voltage. 247 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-56 Liebert eXM™—Controller with LCD HMI—Glossary (continued) Data Label Data Description DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value ECO Mode Operation State This setting is used to enable or disable ECO Mode. Equipment Over Temperature Equipment over temperature summary event Excess ECO Suspends Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting. Fuse Failure A summary event indicating one or more fuse failures Inlet Air Temperature The temperature of the inlet air Input Breaker Input breaker Input Source Backfeed The battery is backfeeding the input source. Intelligent Parallel Operation State This setting is used to enable or disable Intelligent Paralleling. Internal Bypass Breaker Internal bypass breaker Internal Communications Failure The control has detected a communication failure of a component on the internal communication bus Inverter Failure Inverter failure - inverter output is off Inverter On/Off State inverter on/off state Inverter Overload Inverter in overload fault Inverter Relay Fault The inverter relay has malfunctioned. Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload LBS Cable Failure Load Bus Sync communications is abnormal. A problem with the LBS cable may exist. LBS Inhibited The system has detected that conditions to perform Load Bus Sync are not satisfied Load Impact Transfer On bypass as result of load impact. Load Sharing Fault Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current. Loss of Redundancy The multi-module collection doesn't have enough modules to satisfy the redundancy configuration. Loss of Synchronization The inverter and bypass are no longer synchronized. Main Battery Disconnect Open Main battery disconnect is open Mains Input Neutral Lost Loss of neutral in the input source is detected. Maintenance Bypass Breaker Maintenance bypass breaker MMS On Battery The multi-module system is on battery MMS Output Apparent Power The sum total apparent power of all system output modules MMS Output Power The sum total power of all system output modules MMS Over Capacity The multi-module system load is larger than the apparent power limit setting. MMS Overload Multi-module system overload MMS UPS Output Source Multi-module UPS output source On Generator A generator is supplying the power to the system Output Breaker Output breaker Output Current Crest Factor Phs A Output current crest factor of Phase A. Output Current Crest Factor Phs B Output current crest factor of Phase B. Output Current Crest Factor Phs C Output current crest factor of Phase C. Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Parallel Cable Failure The UPS parallel system communications is abnormal. A problem with the parallel cable may exist. Parallel Comm Warning Parallel communication bus warning Power Module Over Temperature The Power Module has detected an over temperature condition. Power Supply Failure Power supply failure Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 248 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-56 Liebert eXM™—Controller with LCD HMI—Glossary (continued) Data Label Data Description Rectifier Failure Rectifier failure - rectifier is off System Date and Time The system date and time System Fan Failure System fan failure - one or more fans have failed System Input Current Imbalance System Input Currents are Imbalanced System Input Current Limit The RMS input current has reached the input current limit threshold System Input Frequency The system input frequency System Input Nominal Current The nominal (or rated) system input current System Input Nominal Frequency The nominal (or rated) system input frequency System Input Nominal Voltage The nominal (or rated) system input voltage System Input Phs Rotation Error The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C) System Input Power Factor Phs A The system input power factor for Phase A System Input Power Factor Phs B The system input power factor for Phase B System Input Power Factor Phs C The system input power factor for Phase C System Input Power Problem The input is not qualified to provide power to the system System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power Phs A System output apparent power on phase A System Output Apparent Power Phs B System output apparent power on phase B System Output Apparent Power Phs C System output apparent power on phase C System Output Apparent Power The sum total apparent power of all system output phases System Output Fault A fault has been detected in the system output System Output Frequency The system output frequency System Output Nominal Frequency The nominal (or rated) system output frequency System Output Nominal Voltage The nominal (or rated) system output voltage System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity System Output Power Factor Phs A The system output power factor of phase A System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power Phase A The system output power on phase A. System Output Power Phase B The system output power on phase B. System Output Power Phase C The system output power on phase C. System Output Power The sum total power of all system output phases System Output RMS Current Phs A The system output RMS current for Phase A System Output RMS Current Phs B The system output RMS current for Phase B System Output RMS Current Phs C The system output RMS current for Phase C System Output Voltage RMS A-B The system output RMS voltage between phases A and B System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral 249 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-56 Liebert eXM™—Controller with LCD HMI—Glossary (continued) Data Label Data Description System Output Voltage RMS B-C The system output RMS voltage between phases B and C System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral System Output Voltage RMS C-A The system output RMS voltage between phases C and A System Output Voltage RMS C-N The system output RMS voltage between phases C and Neutral System Shutdown - EPO System shutdown due to Emergency Power Off (EPO) System Status The operating status for the system Top Outlet Fan Fault Top outlet fan fault - one or more top outlet fans have failed. Total System Operating Time The cumulative operation time of the unit Transfer to Bypass - System Overload The UPS System has transferred to bypass because the active power modules cannot support the critical load. UPS Application Mode UPS application mode. UPS battery1 status UPS battery status UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source User Operation Invalid User attempted an invalid operation. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 250 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-57 Liebert eXM™—Controller with Touchscreen HMI—Status and Coil Status Coil Number of Bits Notes Mains Input Neutral Lost 10001 — 1 Active on Alarm System Input Phs Rotation Error 10002 — 1 Active on Alarm System Input Power Problem 10003 — 1 Active on Alarm Input Source Backfeed 10004 — 1 Active on Alarm Bypass Not Available 10015 — 1 Active on Alarm Bypass Static Switch Unavailable 10016 — 1 Active on Alarm Bypass - Excess Auto Retransfers 10017 — 1 Active on Alarm UPS Output on Bypass 10018 — 1 Active on Alarm Output Load on Maint. Bypass 10019 — 1 Active on Alarm Data Label Input Bypass Bypass Input Voltage Fault 10020 — 1 Active on Alarm Bypass Backfeed Detected 10021 — 1 Active on Alarm Main Battery Disconnect Open 10032 — 1 Active on Alarm Battery Circuit Breaker 4 Open 10033 — 1 Active on Alarm Battery Circuit Breaker 3 Open 10034 — 1 Active on Alarm Battery Circuit Breaker 2 Open 10035 — 1 Active on Alarm Battery Circuit Breaker 1 Open 10036 — 1 Active on Alarm Bypass Battery Self Test 10037 — 1 Active on Alarm Battery Charging Inhibited 10038 — 1 Active on Alarm Battery Discharging 10039 — 1 Active on Alarm Battery Manual Test In Progress 10040 — 1 Active on Alarm Battery Auto Test In Progress 10041 — 1 Active on Alarm Battery Test Passed 10042 — 1 Active on Alarm Battery Test Failed 10043 — 1 Active on Alarm Battery Over Temperature 10044 — 1 Active on Alarm Battery Low 10045 — 1 Active on Alarm Battery Ground Fault 10046 — 1 Active on Alarm Battery Not Qualified 10047 — 1 Active on Alarm Battery Terminals Reversed 10048 — 1 Active on Alarm Battery Capacity Low 10049 — 1 Active on Alarm Battery Converter Current Limit 10050 — 1 Active on Alarm Battery Charge Equalization Timeout 10051 — 1 Active on Alarm Battery Room Alarm 10052 — 1 Active on Alarm Battery Breaker 1 Open Failure 10053 — 1 Active on Alarm Battery Breaker 2 Open Failure 10054 — 1 Active on Alarm Battery Breaker 3 Open Failure 10055 — 1 Active on Alarm Battery Breaker 4 Open Failure 10056 — 1 Active on Alarm Battery Equalize 10057 — 1 Active on Alarm 10068 — 1 Active on Alarm Output Overload 10079 — 1 Active on Alarm System Output Fault 10080 — 1 Active on Alarm Inverter Loss of Synchronization Output 251 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-57 Liebert eXM™—Controller with Touchscreen HMI—Status and Coil (continued) Data Label Status Coil Number of Bits Notes Power Modules 1 Power Module Input Current Abnormal 10091 — 1 Active on Alarm Rectifier Failure 10092 — 1 Active on Alarm Inverter Failure 10093 — 1 Active on Alarm DC Bus Abnormal 10094 — 1 Active on Alarm Load Sharing Fault 10095 — 1 Active on Alarm Inverter Relay Fault 10096 — 1 Active on Alarm Battery Charging Error 10097 — 1 Active on Alarm Battery Converter Failure 10098 — 1 Active on Alarm Power Module Balancer of DC Bus Failure 10099 — 1 Active on Alarm Inverter Shutdown - Overload 10100 — 1 Active on Alarm Power Module Fuse Failure 10101 — 1 Active on Alarm Power Module Power Supply Failure 10102 — 1 Active on Alarm Power Module Fan Fault 10103 — 1 Active on Alarm Power Module Over Temperature 10104 — 1 Active on Alarm Power Module Input Current Abnormal 10115 — 1 Active on Alarm Rectifier Failure 10116 — 1 Active on Alarm Inverter Failure 10117 — 1 Active on Alarm DC Bus Abnormal 10118 — 1 Active on Alarm Load Sharing Fault 10119 — 1 Active on Alarm Power Modules 2 Inverter Relay Fault 10120 — 1 Active on Alarm Battery Charging Error 10121 — 1 Active on Alarm Battery Converter Failure 10122 — 1 Active on Alarm Power Module Balancer of DC Bus Failure 10123 — 1 Active on Alarm Inverter Shutdown - Overload 10124 — 1 Active on Alarm Power Module Fuse Failure 10125 — 1 Active on Alarm Power Module Power Supply Failure 10126 — 1 Active on Alarm Power Module Fan Fault 10127 — 1 Active on Alarm Power Module Over Temperature 10128 — 1 Active on Alarm Power Modules 20 Power Module Input Current Abnormal 10547 — 1 Active on Alarm Rectifier Failure 10548 — 1 Active on Alarm Inverter Failure 10549 — 1 Active on Alarm DC Bus Abnormal 10550 — 1 Active on Alarm Load Sharing Fault 10551 — 1 Active on Alarm Inverter Relay Fault 10552 — 1 Active on Alarm Battery Charging Error 10553 — 1 Active on Alarm Battery Converter Failure 10554 — 1 Active on Alarm Power Module Balancer of DC Bus Failure 10555 — 1 Active on Alarm Inverter Shutdown - Overload 10556 — 1 Active on Alarm Power Module Fuse Failure 10557 — 1 Active on Alarm Power Module Power Supply Failure 10558 — 1 Active on Alarm Power Module Fan Fault 10559 — 1 Active on Alarm Power Module Over Temperature 10560 — 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 252 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-57 Liebert eXM™—Controller with Touchscreen HMI—Status and Coil (continued) Status Coil Number of Bits Notes Loss of Redundancy 10571 — 1 Active on Alarm Parallel Cable Failure 10572 — 1 Active on Alarm Data Label System Status LBS Cable Failure 10573 — 1 Active on Alarm Transfer to Bypass - System Overload 10574 — 1 Active on Alarm Excess ECO Suspends 10575 — 1 Active on Alarm User Operation Invalid 10576 — 1 Active on Alarm Load Impact Transfer 10577 — 1 Active on Alarm Internal Communications Failure 10578 — 1 Active on Alarm MMS Overload 10579 — 1 Active on Alarm Parallel Comm Warning 10580 — 1 Active on Alarm Equipment Over Temperature 10581 — 1 Active on Alarm LBS Inhibited 10582 — 1 Active on Alarm On Generator 10583 — 1 Active on Alarm LBS Active 10584 — 1 Active on Alarm System Shutdown - EPO 10585 — 1 Active on Alarm Top Outlet Fan Fault 10586 — 1 Active on Alarm 253 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding Data Label Input Holding # of Reg Scale Notes/Units System Input RMS A-B 30385 — 1 System Input RMS B-C 30386 — 1 — Units : VAC Uint16 System Input RMS C-A 30387 — 1 — Units : VAC Uint16 System Input RMS Current Phase A 30388 — 1 — Units : A AC Uint16 System Input RMS Current Phase B 30389 — 1 — Units : A AC Uint16 System Input RMS Current Phase C 30390 — 1 — Units : A AC Uint16 System Input Frequency 30391 — 1 10 Units : Hz Uint16 System Input RMS A-N 30392 — 1 — Units : VAC Uint16 System Input RMS B-N 30393 — 1 — Units : VAC Uint16 System Input RMS C-N 30394 — 1 — Units : VAC Uint16 System Input Power Factor Phs A 30395 — 1 100 Uint16 System Input Power Factor Phs B 30396 — 1 100 Uint16 System Input Power Factor Phs C 30397 — 1 100 Uint16 Input Units : VAC Uint16 System Input Nominal Voltage 30398 — 1 — Units : VAC Uint16 System Input Nominal Frequency 30399 — 1 10 Units : Hz Uint16 System Input Nominal Current 30400 — 1 — Units : A AC Uint16 System Input Brown Out Count 30401 — 1 — Uint16 System Input Black Out Count 30402 — 1 — Uint16 30403 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Input Voltage RMS A-N 30414 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS B-N 30415 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS C-N 30416 — 1 — Units : VAC Uint16 Bypass Input Frequency 30417 — 1 10 Units : Hz Uint16 Bypass Input Voltage RMS A-B 30418 — 1 — Units : VAC Uint16 Input Breaker Bypass If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 254 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Bypass Input Voltage RMS B-C 30419 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS C-A 30420 — 1 — Units : VAC Uint16 Bypass Nominal Voltage 30421 — 1 — Units : VAC Uint16 External Bypass Breaker 30422 — 1 — 0 = Open 1 = Close 2 = Not Installed Battery Time Remaining 30433 — 1 — Units : min Uint16 DC Bus Current 30434 — 1 — Units : A DC Int16 Time Until Next Auto Battery Test 30435 — 2 — Units : min Uint32 Battery Percentage Charge 30437 — 1 — Units : % Uint16 Number of Discharge Cycles 30438 — 1 — Uint16 Accumulated Discharge Time 30439 — 1 — Units : hr Uint16 Low Battery Warning Time 30440 — 1 — Units : min Uint16 — 1 = Unknown 2 = Normal 3 = Low 4 = Depleted Battery UPS Battery Status 30441 — 1 Battery charge status. 30442 — 1 — 0 = fully charged 1 = charging 2 = discharging 3 = not charging (charger off) Automatic Battery Test 30443 — 1 — 0 = disabled 1 = enabled Battery Self Test Cycle Time 30444 — 1 — Units : day Uint16 DC Bus Voltage 30445 — 1 — Units : VDC Uint16 Battery Temperature 30446 — 1 — Units : deg C Int16 Battery Temperature 30447 — 1 — Units : deg F Int16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 255 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Battery Temperature for Cabinet 30458 — 1 — Units : deg C Int16 Battery Temperature for Cabinet 30459 — 1 — Units : deg F Int16 Battery Volts for Cabinet 30460 — 1 — Units : VDC Uint16 Battery Temperature for Cabinet 30471 — 1 — Units : deg C Int16 Battery Temperature for Cabinet 30472 — 1 — Units : deg F Int16 Battery Volts for Cabinet 30473 — 1 — Units : VDC Uint16 Battery Temperature for Cabinet 30549 — 1 — Units : deg C Int16 Battery Temperature for Cabinet 30550 — 1 — Units : deg F Int16 Battery Volts for Cabinet 30551 — 1 — Units : VDC Uint16 Battery Cabinets 1 Battery Cabinets 2 Battery Cabinets 8 Inverter Output Breaker 30562 — 1 — 0 = Open 1 = Close 2 = Not Installed Inverter On/Off State 30563 — 1 — 0 = off 1 = on System Output Voltage RMS A-N 30574 — 1 — Units : VAC Uint16 System Output Voltage RMS B-N 30575 — 1 — Units : VAC Uint16 System Output Voltage RMS C-N 30576 — 1 — Units : VAC Uint16 System Output RMS Current Phs A 30577 — 1 — Units : A AC Uint16 System Output RMS Current Phs B 30578 — 1 — Units : A AC Uint16 System Output RMS Current Phs C 30579 — 1 — Units : A AC Uint16 System Output Frequency 30580 — 1 10 Units : Hz Uint16 System Output Voltage RMS A-B 30581 — 1 — Units : VAC Uint16 System Output Voltage RMS B-C 30582 — 1 — Units : VAC Uint16 Output If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 256 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units System Output Voltage RMS C-A 30583 — 1 — Units : VAC Uint16 System Output Power Factor Phs A 30584 — 1 100 Uint16 System Output Power Factor Phs B 30585 — 1 100 Uint16 System Output Power Factor Phs C 30586 — 1 100 Uint16 System Output Pct Power Phase A 30587 — 1 — Units : % Uint16 System Output Pct Power Phase B 30588 — 1 — Units : % Uint16 System Output Pct Power Phase C 30589 — 1 — Units : % Uint16 MMS Output Apparent Power 30590 — 1 — Units : kVA Uint16 MMS Output Power 30591 — 1 — Units : kW Uint16 Output Current Crest Factor Phs A 30592 — 1 10 Uint16 Output Current Crest Factor Phs B 30593 — 1 10 Uint16 Output Current Crest Factor Phs C 30594 — 1 10 Uint16 System Output Power Phase A 30595 — 1 — Units : kW Uint16 System Output Power Phase B 30596 — 1 — Units : kW Uint16 System Output Power Phase C 30597 — 1 — Units : kW Uint16 System Output Apparent Power Phs A 30598 — 1 — Units : kVA Uint16 System Output Apparent Power Phs B 30599 — 1 — Units : kVA Uint16 System Output Apparent Power Phs C 30600 — 1 — Units : kVA Uint16 System Output Power 30601 — 1 — Units : kW Uint16 System Output Apparent Power 30602 — 1 — Units : kVA Uint16 System Output Pct Pwr (VA) Phs A 30603 — 1 — Units : % Uint16 System Output Pct Pwr (VA) Phs B 30604 — 1 — Units : % Uint16 System Output Pct Pwr (VA) Phs C 30605 — 1 — Units : % Uint16 System Output Nominal Voltage 30606 — 1 — Units : VAC Uint16 System Output Nominal Frequency 30607 — 1 10 Units : Hz Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 257 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units 30618 — 1 — 0 = Sleeping 1 = Not Sleeping Power Modules 1 Power Module Sleep Status Module Operating Status 30619 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30620 — 1 — 0 = Inverter Inactive 1 = Inverter Active 30631 — 1 — 0 = Sleeping 1 = Not Sleeping Power Modules 2 Power Module Sleep Status Module Operating Status 30632 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30633 — 1 — 0 = Inverter Inactive 1 = Inverter Active 30865 — 1 — 0 = Sleeping 1 = Not Sleeping Power Modules 20 Power Module Sleep Status Module Operating Status 30866 — 1 — 0 = Normal 1 = Warning 2 = Alarm 4 = Fault Inverter Status 30867 — 1 — 0 = Inverter Inactive 1 = Inverter Active Power Module Bypass Input Frequency 30878 — 1 10 Units : Hz Uint16 Power Module Bypass Input Voltage RMS A-N 30879 — 1 — Units : VAC Uint16 Power Module Bypass Input Voltage RMS B-N 30880 — 1 — Units : VAC Uint16 Power Module Bypass Input Voltage RMS C-N 30881 — 1 — Units : VAC Uint16 Power Module Bypass Input Voltage RMS A-B 30882 — 1 — Units : VAC Uint16 Power Module Bypass Input Voltage RMS B-C 30883 — 1 — Units : VAC Uint16 Power Module Bypass Input Voltage RMS C-A 30884 — 1 — Units : VAC Uint16 Bypass Control Module If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 258 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units System Set To Operate With 30895 — 1 — 0 = No Redundancy 1 = Redundancy Number Of Active Power Modules 30896 — 1 — Uint16 Number of Installed Power Modules 30897 — 1 — Uint16 Inlet Air Temperature 30898 — 1 — Units : deg C Uint16 Inlet Air Temperature 30899 — 1 — Units : deg F Uint16 Average system efficiency 30900 — 1 10 Units : % Uint16 Maintenance Bypass Breaker 30901 — 1 — 0 = Open 1 = Close 2 = Not Installed ECO Mode Operation State 30902 — 1 — 0 = disabled 1 = enabled UPS Application Mode 30903 — 1 — 0 = UPS Mode 1 = Frequency converter mode System Status MMS UPS Output Source 30904 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Intelligent Parallel Operation State 30905 — 1 — 0 = disabled 1 = enabled Total System Operating Time 30916 — 2 — Units : hr Uint32 System Capacity 30918 — 1 — Units : kVA Uint16 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer System Configuration UPS Output Source 30919 — 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 259 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-58 Liebert eXM™—Controller with Touchscreen HMI—Input and Holding (continued) Data Label Input Holding # of Reg System Status 30920 — 1 System Date and Time 39998 49998 2 Scale Notes/Units — 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation Units : Secs since Epoch(UTC) If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 260 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary Data Label Data Description Accumulated Discharge Time Total accumulated discharge time for the Battery Module since it was made. Automatic Battery Test Enable/disable the automatic battery test schedule. Average system efficiency Average system efficiency Battery Auto Test In Progress Automatic battery test is in progress Battery Breaker 1 Open Failure Battery circuit breaker 1 failed to open Battery Breaker 2 Open Failure Battery circuit breaker 2 failed to open Battery Breaker 3 Open Failure Battery circuit breaker 3 failed to open Battery Breaker 4 Open Failure Battery circuit breaker 4 failed to open Battery Capacity Low Battery capacity is low Battery Charge Equalization Timeout The battery equalizing is time out. Battery charge status. Battery charge status. Battery Charging Error The battery is not charging properly Battery Charging Inhibited Battery charging is inhibited due to an external inhibit signal Battery Circuit Breaker 1 Open Battery circuit breaker 1 is open Battery Circuit Breaker 2 Open Battery circuit breaker 2 is open Battery Circuit Breaker 3 Open Battery circuit breaker 3 is open Battery Circuit Breaker 4 Open Battery circuit breaker 4 is open Battery Converter Current Limit The battery converter has reached is maximum current limit. Battery Converter Failure Battery converter failure. This is a summary event caused by one or more power sub-modules in a UPS module. Battery Discharging The battery is discharging Battery Equalize The rectifier output voltage is increased to equalize the battery voltage level. Battery Ground Fault Battery system ground fault amperage exceeds the threshold Battery Low The calculated battery time remaining has reached the low battery threshold Battery Manual Test In Progress Manual battery test is in progress Battery Not Qualified The UPS battery voltage is not qualified. This event will be detected even in the absence of battery disconnect or when it is open. Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Percentage Charge The percentage of battery charge Battery Room Alarm The ambient temperature of the battery room is abnormal. Battery Self Test Cycle Time The time between automatic battery self test cycles. Battery Self Test Battery self test is in progress Battery Temperature for Cabinet The battery temperature for a cabinet Battery Temperature The highest battery temperature among all Battery Cabinets Battery Terminals Reversed The measured battery voltage is a negative value due to reverse battery terminal connections. Battery Test Failed Battery test failed Battery Test Passed Battery test passed Battery Time Remaining The calculated available time on battery Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Bypass - Excess Auto Retransfers The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval Bypass Backfeed Detected The system detected a voltage on the bypass when none was expected Bypass Input Frequency The bypass input frequency Bypass Input Voltage Fault The system has detected the bypass voltage is unqualified. Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B Bypass Input Voltage RMS A-N The bypass input RMS voltage between phase A and Neutral 261 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary (continued) Data Label Bypass Input Voltage RMS B-C Data Description The bypass input RMS voltage between phases B and C Bypass Input Voltage RMS B-N The bypass input RMS voltage between phase B and Neutral Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A Bypass Input Voltage RMS C-N The bypass input RMS voltage between phase C and Neutral Bypass Nominal Voltage Bypass nominal (or rated) voltage Bypass Not Available A problem associated with the bypass has been detected Bypass Static Switch Unavailable The static bypass is unavailable to support the critical load. DC Bus Abnormal The system has detected an abnormal DC Bus Voltage. DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value DC Bus Voltage The voltage between the positive and negative terminals of the DC bus at the battery input ECO Mode Operation State This setting is used to enable or disable ECO Mode. Equipment Over Temperature Equipment over temperature summary event Excess ECO Suspends Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting. External Bypass Breaker The status of the external bypass breaker. Inlet Air Temperature The temperature of the inlet air Input Breaker Input breaker Input Source Backfeed The battery is backfeeding the input source. Intelligent Parallel Operation State This setting is used to enable or disable Intelligent Paralleling. Internal Communications Failure The control has detected a communication failure of a component on the internal communication bus Inverter Failure Inverter failure - inverter output is off Inverter On/Off State inverter on/off state Inverter Relay Fault The inverter relay has malfunctioned. Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload Inverter Status Status of the inverter output. Active means the inverter is online with regulated output voltage and ready to power the load. Inactive means the inverter is offline and not ready to power the load. LBS Active The Load Bus Sync option is active LBS Cable Failure Load Bus Sync communications is abnormal. A problem with the LBS cable may exist. LBS Inhibited The system has detected that conditions to perform Load Bus Sync are not satisfied Load Impact Transfer On bypass as result of load impact. Load Sharing Fault Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nominal current. Loss of Redundancy The system has an insufficient number of power modules to provide redundancy. Loss of Synchronization The inverter and bypass are no longer synchronized. Low Battery Warning Time When battery time remaining falls to, or below, this value the low battery alarm is activated. Main Battery Disconnect Open Main battery disconnect is open Mains Input Neutral Lost Loss of neutral in the input source is detected. Maintenance Bypass Breaker Maintenance bypass breaker MMS Output Apparent Power The sum total apparent power of all system output modules MMS Output Power The sum total power of all system output modules MMS Overload Multi-module system overload MMS UPS Output Source Multi-module UPS output source Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 262 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary (continued) Data Label Module Operating Status Data Description The operating status for this Power Module. Number Of Active Power Modules The total number of active power modules. Number of Discharge Cycles The total number of battery discharge cycles for the Battery Module since it was made. Number of Installed Power Modules The total number of Power Modules installed. On Generator A generator is supplying the power to the system Output Breaker Output breaker Output Current Crest Factor Phs A Output current crest factor of Phase A. Output Current Crest Factor Phs B Output current crest factor of Phase B. Output Current Crest Factor Phs C Output current crest factor of Phase C. Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Output Overload An overload exists on the output. Parallel Cable Failure The UPS parallel system communications is abnormal. A problem with the parallel cable may exist. Parallel Comm Warning Parallel communication bus warning Power Module Balancer of DC Bus Failure Balancer of DC Bus in the power module has failed Power Module Bypass Input Frequency The bypass input frequency detected by power module Power Module Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B detected by power module Power Module Bypass Input Voltage RMS A-N The bypass input RMS voltage between phase A and Neutral detected by power module Power Module Bypass Input Voltage RMS B-C The bypass input RMS voltage between phases B and C detected by power module Power Module Bypass Input Voltage RMS B-N The bypass input RMS voltage between phase B and Neutral detected by power module Power Module Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A detected by power module Power Module Bypass Input Voltage RMS C-N The bypass input RMS voltage between phase C and Neutral detected by power module Power Module Fan Fault The Power Module has detected a fan fault. Power Module Fuse Failure A summary event indicating one or more fuse failures in the power module Power Module Input Current Abnormal Input current of the power module is abnormal Power Module Over Temperature The Power Module has detected an over temperature condition. Power Module Power Supply Failure Power module power supply failure Power Module Sleep Status Sleep status of the Power module Rectifier Failure Rectifier failure - rectifier is off System Capacity System capacity supported by the installed power modules. System Date and Time The system date and time System Input Black Out Count The number of occurrences, since the last reset, where the input was not qualified to provide power to the system System Input Brown Out Count The number of occurrences, since the last reset, where the system input voltage has fallen below a pre-determined threshold for a specified amount of time System Input Frequency The system input frequency System Input Nominal Current The nominal (or rated) system input current System Input Nominal Frequency The nominal (or rated) system input frequency System Input Nominal Voltage The nominal (or rated) system input voltage System Input Phs Rotation Error The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C) 263 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary (continued) Data Label System Input Power Factor Phs A Data Description The system input power factor for Phase A System Input Power Factor Phs B The system input power factor for Phase B System Input Power Factor Phs C The system input power factor for Phase C System Input Power Problem The input is not qualified to provide power to the system System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power Phs A System output apparent power on phase A System Output Apparent Power Phs B System output apparent power on phase B System Output Apparent Power Phs C System output apparent power on phase C System Output Apparent Power The sum total apparent power of all system output phases System Output Fault A fault has been detected in the system output System Output Frequency The system output frequency System Output Nominal Frequency The nominal (or rated) system output frequency System Output Nominal Voltage The nominal (or rated) system output voltage System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity System Output Pct Pwr (VA) Phs A The system output apparent power on phase A as a percentage of the rated capacity System Output Pct Pwr (VA) Phs B The system output apparent power on phase B as a percentage of the rated capacity System Output Pct Pwr (VA) Phs C The system output apparent power on phase C as a percentage of the rated capacity System Output Power Factor Phs A The system output power factor of phase A System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power Phase A The system output power on phase A. System Output Power Phase B The system output power on phase B. System Output Power Phase C The system output power on phase C. System Output Power The sum total power of all system output phases System Output RMS Current Phs A The system output RMS current for Phase A System Output RMS Current Phs B The system output RMS current for Phase B System Output RMS Current Phs C The system output RMS current for Phase C System Output Voltage RMS A-B The system output RMS voltage between phases A and B System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral System Output Voltage RMS B-C The system output RMS voltage between phases B and C System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral System Output Voltage RMS C-A The system output RMS voltage between phases C and A System Output Voltage RMS C-N The system output RMS voltage between phases C and Neutral Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 264 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-59 Liebert eXM™—Controller with Touchscreen HMI—Glossary (continued) Data Label Data Description System Set To Operate With If this point reports 'Redundancy' then the system is configured for redundancy and the 'Loss of Redundancy' alarm is enabled. System Shutdown - EPO System shutdown due to Emergency Power Off (EPO) System Status The operating status for the system Time Until Next Auto Battery Test The time until the next automatic battery test is started. Top Outlet Fan Fault Top outlet fan fault - one or more top outlet fans have failed. Total System Operating Time The cumulative operation time of the unit Transfer to Bypass - System Overload The UPS System has transferred to bypass because the active power modules cannot support the critical load. UPS Application Mode UPS application mode. UPS Battery Status UPS battery status UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source User Operation Invalid User attempted an invalid operation. 265 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-60 Liebert GXT2™ and Liebert GXT3™—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Audible Alarm Enabled 10002 2 1 — — Automatic Battery Test Enabled 10003 3 1 — — DC-to-DC Converter On 10042 — 1 — — Battery Charge Compensation 10046 — 1 — — Inverter Ready 10047 — 1 — — Power Factor Correction State 10050 — 1 — — Load Circuit 1 State 10057 — 1 — — Load Circuit 2 State 10058 — 1 — — Load Circuit 3 State 10059 — 1 — — Load Circuit 4 State 10060 — 1 — — Load Circuit 5 State 10061 — 1 — — Load Circuit 6 State 10062 — 1 — — Load Circuit 7 State 10063 — 1 — — Load Circuit 8 State 10064 — 1 — — Load Circuit 9 State 10065 — 1 — — Load Circuit 10 State 10066 — 1 — — Load Circuit 11 State 10067 — 1 — — Load Circuit 12 State 10068 — 1 — — Load Circuit 13 State 10069 — 1 — — Load Circuit 14 State 10070 — 1 — — Load Circuit 15 State 10071 — 1 — — Load Circuit 16 State 10072 — 1 — — Load On Inverter 10073 — 1 — — Bypass Active 10074 — 1 — — Replace Battery 10081 — 1 — — Battery Under Test 10082 — 1 — — Shutdown Reason - Over Temperature 10086 — 1 — — Shutdown Reason - Overload 10087 — 1 — — Shutdown Reason - Link Over Voltage 10088 — 1 — — Shutdown Reason - Output Short 10089 — 1 — — Shutdown Reason - Line Neutral Swap 10090 — 1 — — Shutdown Reason - Low Battery 10092 — 1 — — Shutdown Reason - Remote Shutdown 10093 — 1 — — Shutdown Reason - Input Under Voltage 10094 — 1 — — Shutdown Reason - PFC Startup 10095 — 1 — — Shutdown Reason - Hardware 10096 — 1 — — Load on Battery 10128 — 1 — — Output Off Pending 10151 — 1 — — Low Battery - Shutdown Imminent 10152 — 1 — — Output Overload 10154 — 1 — — Over Temperature Warning 10171 — 1 — — Battery Over Temperature CB Trip 10172 — 1 — — Input Power Supply Fail 10186 — 1 — — Input Over Voltage 10187 — 1 — — Input Under Voltage 10188 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 266 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-60 Liebert GXT2™ and Liebert GXT3™—Status and Coil (continued) Data Description Status Coil Number of Bits Scale Notes / Units Bad Input Frequency 10190 — 1 — — Bypass Input Voltage/Frequency Fault 10202 — 1 — — Output Under Voltage 10218 — 1 — — Output Over Voltage 10219 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 267 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-61 Liebert GXT2™ and Liebert GXT3™—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Audible Alarm Enabled 10002 2 1 — — Automatic Battery Test Enabled 10003 3 1 — — DC-to-DC Converter On 10042 — 1 — — Battery Charge Compensation 10046 — 1 — — Inverter Ready 10047 — 1 — — Power Factor Correction State 10050 — 1 — — Load Circuit 1 State 10057 — 1 — — Load Circuit 2 State 10058 — 1 — — Load Circuit 3 State 10059 — 1 — — Load Circuit 4 State 10060 — 1 — — Load Circuit 5 State 10061 — 1 — — Load Circuit 6 State 10062 — 1 — — Load Circuit 7 State 10063 — 1 — — Load Circuit 8 State 10064 — 1 — — Load Circuit 9 State 10065 — 1 — — Load Circuit 10 State 10066 — 1 — — Load Circuit 11 State 10067 — 1 — — Load Circuit 12 State 10068 — 1 — — Load Circuit 13 State 10069 — 1 — — Load Circuit 14 State 10070 — 1 — — Load Circuit 15 State 10071 — 1 — — Load Circuit 16 State 10072 — 1 — — Load On Inverter 10073 — 1 — — Bypass Active 10074 — 1 — — Replace Battery 10081 — 1 — — Battery Under Test 10082 — 1 — — Shutdown Reason - Over Temperature 10086 — 1 — — Shutdown Reason - Overload 10087 — 1 — — Shutdown Reason - Link Over Voltage 10088 — 1 — — Shutdown Reason - Output Short 10089 — 1 — — Shutdown Reason - Line Neutral Swap 10090 — 1 — — Shutdown Reason - Low Battery 10092 — 1 — — Shutdown Reason - Remote Shutdown 10093 — 1 — — Shutdown Reason - Input Under Voltage 10094 — 1 — — Shutdown Reason - PFC Startup 10095 — 1 — — Shutdown Reason - Hardware 10096 — 1 — — Load on Battery 10128 — 1 — — Output Off Pending 10151 — 1 — — Low Battery - Shutdown Imminent 10152 — 1 — — Output Overload 10154 — 1 — — Over Temperature Warning 10171 — 1 — — Battery Over Temperature CB Trip 10172 — 1 — — Input Power Supply Fail 10186 — 1 — — Input Over Voltage 10187 — 1 — — Input Under Voltage 10188 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 268 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-61 Liebert GXT2™ and Liebert GXT3™—Status and Coil (continued) Data Description Status Coil Number of Bits Scale Notes / Units Bad Input Frequency 10190 — 1 — — Bypass Input Voltage/Frequency Fault 10202 — 1 — — Output Under Voltage 10218 — 1 — — Output Over Voltage 10219 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 269 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-62 Liebert GXT2™ and Liebert GXT3™—Input and Holding Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of Output Lines 30004 40004 1 — Bits 8 - 11 Number of SubModules 30009 40009 1 — — — There are 16 possible Load Circuits. Each bit represents 1 Load Circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1, then the Load Circuit is supported. Data Description Load Circuit Present 30013 40013 1 Battery Cabinet Type 30018 40018 2 — — Battery Cabinet Number 30019 40019 1 — — Battery AmpHour 30020 40020 1 — AH Nominal Power Rating 30021 40021 2 — VA Nominal Input Voltage 30027 40027 1 — V Nominal Output Voltage 30028 40028 1 — V Nominal Static Bypass Switch Voltage 30029 40029 1 — V Nominal Input Current 30030 40030 1 — A Nominal Input Frequency 30031 40031 1 10 Hz Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 — Nominal Battery Voltage 30034 40034 1 — V Auto Restart Delay 30051 40051 1 — Seconds Device Low Battery Time 30053 40053 1 — Minutes Load (Apparent Power) 30102 — 2 — VA Load (Real Power) 30104 — 2 — W Load / Capacity 30106 — 1 — % Input Frequency 30107 — 1 10 Hz Output Frequency 30108 — 1 10 Hz Bypass Frequency 30109 — 1 10 Hz — 1 — 1 - 100% Charged 2 - Less than 100% Charged 3 - Charging 4 - Discharging 5 - Float Charging 6 - Equalize Charging Battery Charge Status 30112 Battery Voltage 30113 — 1 — V Battery Time Remaining 30115 — 1 — Minutes Battery Charge Percentage 30116 — 1 — % Ambient Temperature 30119 — 1 — deg C Battery Test Result 30130 — 1 — 1 - Unknown 2 - Passed 3 - Failed 4 - In Progress 5 - System Failure 6 - Inhibited Input Voltage L1 30153 — 1 — V Bypass Voltage L1 30159 — 1 — V Output Voltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 270 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-62 Liebert GXT2™ and Liebert GXT3™—Input and Holding (continued) Data Description Input Maximum Voltage L1 Input Register Holding Register # of Reg. Scale Notes / Units 30180 — 1 — V Input Minimum Voltage L1 30181 — 1 — V Output Maximum Voltage L1 30182 — 1 — V Output Minimum Voltage L1 30183 — 1 — V Black Out Count 30301 — 1 — — Brown Out Count 30302 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 271 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-63 Liebert GXT3™ and Liebert GXT4™—Status and Coil Data Label Status Coil Number of Bits Notes Input Input Undervoltage 10001 1 Active on Alarm Input Overvoltage 10002 1 Active on Alarm 10013 1 Active on Alarm Bypass Bypass Not Available Battery Battery Self Test 10024 1 Active on Alarm Battery Low 10025 1 Active on Alarm Battery Under Voltage 10026 1 Active on Alarm Battery Over Voltage 10027 1 Active on Alarm Battery Test Failed 10028 1 Active on Alarm Replace Battery 10029 1 Active on Alarm 10040 1 Active on Alarm Output Output Overload Output Undervoltage 10041 1 Active on Alarm Output Overvoltage 10042 1 Active on Alarm System Output Off 10043 1 Active on Alarm UPS Output on Bypass 10054 1 Active on Alarm Battery Discharging 10055 1 Active on Alarm System System Input Power Problem 10056 1 Active on Alarm Equipment Over Temperature 10057 1 Active on Alarm Input Frequency Deviation 10058 1 Active on Alarm Shutdown Pending 10059 1 Active on Alarm Unspecified General Event 10060 1 Active on Alarm Parallel Comm Warning 10061 1 Active on Alarm Loss of Redundancy 10062 1 Active on Alarm Charger Failure 10063 1 Active on Alarm Rectifier Failure 10064 1 Active on Alarm Inverter Failure 10065 1 Active on Alarm Maintenance Bypass Breaker Closed 10066 1 Active on Alarm System Fan Failure 10067 1 Active on Alarm Emergency Power Off - Latched 10068 1 Active on Alarm Input Wiring Fault 10069 1 Active on Alarm DC to DC Converter Fault 10070 1 Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 272 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding Data Label Input Holding # of Reg Scale Notes/Units Protocol Server Class 1 = UPS 2 = AIR 3 = PMP 4 = PDU 5 = MONITOR 30385 1 System Input RMS L1-N 30396 1 10 Units : VAC Uint16 System Input RMS L2-N 30397 1 10 Units : VAC Uint16 System Input RMS L1-L2 30398 1 10 Units : VAC Uint16 System Input RMS Current L1 30399 1 10 Units : A AC Uint16 System Input RMS Current L2 30400 1 10 Units : A AC Uint16 System Input Frequency 30401 1 10 Units : Hz Uint16 System Input Max Voltage L1-N 30402 1 10 Units : VAC Uint16 System Input Min Voltage L1-N 30403 1 10 Units : VAC Uint16 System Input Max Voltage L2-N 30404 1 10 Units : VAC Uint16 System Input Min Voltage L2-N 30405 1 10 Units : VAC Uint16 System Input Nominal Voltage 30406 1 Units : VAC Uint16 System Input Nominal Current 30407 1 Units : A AC Uint16 System Input Nominal Frequency 30408 1 Units : Hz Uint16 Bypass Input Voltage RMS L1-N 30419 1 10 Units : VAC Uint16 Bypass Input Voltage RMS L1-L2 30420 1 10 Units : VAC Uint16 Bypass Input Voltage RMS L2-N 30421 1 10 Units : VAC Uint16 Bypass Input RMS Current 30422 1 10 Units : A AC Uint16 Bypass Input RMS Current Line 2 30423 1 10 Units : A AC Uint16 Bypass Input Frequency 30424 1 10 Units : Hz Uint16 Input Bypass If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 273 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding (continued) Data Label Bypass Nominal Voltage Input Holding 30425 # of Reg Scale Notes/Units 1 Units : VAC Uint16 Battery UPS Battery Status 30436 1 1 = Unknown 2 = Normal 3 = Low 4 = Depleted Battery Time Remaining 30437 1 Units : min Uint16 Battery Percentage Charge 30438 1 Units : % Uint16 Battery Charge Status 30439 1 0 = fully charged 1 = charging 2 = discharging 3 = not charging (charger off) DC Bus Voltage 30440 1 Units : VDC Uint16 DC Bus Nominal Voltage 30441 1 Units : VDC Uint16 Battery Cabinet Type 30442 1 0 = Internal 1 = External 2 = LRT Battery Rating 30443 1 Units : AH Uint16 Low Battery Warning Time 30444 1 Units : min Uint16 Number of EBC Installed 30445 40444 1 Uint16 Battery Charge Compensating 30446 1 0 = false 1 = true Battery Charger State 30447 1 0 = off 1 = on Nominal Battery Capacity 30448 1 Units : min Uint16 Battery Discharge Time 30449 1 Units : min Uint16 Battery Float Voltage 30450 1 Units : VDC Uint16 Battery Test Result 30451 1 0 = Unknown 1 = Passed 2 = Failed 3 = In Progress 4 = System Failure 5 = Inhibited Automatic Battery Test 30452 1 0 = disabled 1 = enabled 1 1 = Start Test Manual Battery Test 40453 Output If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 274 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units System Output Voltage RMS L1-N 30464 1 10 Units : VAC Uint16 System Output Voltage RMS L1-L2 30465 1 10 Units : VAC Uint16 System Output RMS Current L1 30466 1 10 Units : A AC Uint16 System Output Voltage RMS L2-N 30467 1 10 Units : VAC Uint16 System Output RMS Current L2 30468 1 10 Units : A AC Uint16 System Output Frequency 30469 1 10 Units : Hz Uint16 System Output Max Voltage L1-N 30470 1 10 Units : VAC Uint16 System Output Min Voltage L1-N 30471 1 10 Units : VAC Uint16 System Output Max Voltage L2-N 30472 1 10 Units : VAC Uint16 System Output Min Voltage L2-N 30473 1 10 Units : VAC Uint16 System Output Power 30474 1 Units : W Uint16 System Output Power L1 30475 1 Units : W Uint16 System Output Power L2 30476 1 Units : W Uint16 System Output Pct Power 30477 1 Units : % Uint16 System Output Pct Power L1 30478 1 Units : % Uint16 System Output Pct Power L2 30479 1 Units : % Uint16 System Output Apparent Power 30480 1 Units : VA Uint16 System Output Apparent Power L1 30481 1 Units : VA Uint16 System Output Apparent Power L2 30482 1 Units : VA Uint16 System Output Nominal Voltage 30483 1 Units : VAC Uint16 Output Apparent Power Rating 30484 1 Units : VA Uint16 System Output Nominal Frequency 30485 1 Units : Hz Uint16 Output On Delay 30486 40486 1 Units : sec Uint16 Reboot With Delay 30487 40487 1 Units : sec Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 275 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding (continued) Data Label Shutdown After Delay Input Holding # of Reg Scale Notes/Units 30488 40488 1 Units : sec Uint16 UPS Output Source 30489 1 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Power Factor Correction 30490 1 0 = off 1 = on Nominal Power Factor 30491 1 Outlet Group Identifier 30502 1 Uint16 Outlet Group Power Control 30503 1 0 = Off 1 = On 2 = Cycle Power 1 Uint16 1 0 = Off 1 = On 2 = Cycle Power 1 0 = off 1 = on 1 0 = disabled 1 = enabled 1 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 100 Int16 Outlet Group 1 40503 Outlet Group 2 Outlet Group Identifier 30514 Outlet Group Power Control 30515 40515 ECO Mode ECO Mode Status 30526 ECO Mode Operation State 30527 40527 System System Status 30538 System Input Black Out Count 30539 1 Uint16 System Input Brown Out Count 30540 1 Uint16 Auto Restart 30541 40541 1 0 = disabled 1 = enabled Auto Restart Delay 30542 40542 1 Units : sec Uint16 Inverter On/Off State 30543 1 0 = off 1 = on Inlet Air Temperature 30544 1 Units : deg C Int16 Inlet Air Temperature 30545 1 Units : deg F Int16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 276 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-64 Liebert GXT3™ and Liebert GXT4™—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Shutdown Reason 30546 1 0 = None 1 = Over Temperature 2 = Overload 3 = DC Bus Overload 4 = Output Short 5 = Line Swap 6 = Low Battery 7 = Remote Command 8 = Input Under Voltage 9 = Power Factor Correction Fail 10 = External Signal Command DC Converter Status 30547 1 0 = off 1 = on UPS Topology 30548 1 0 = unknown 1 = Offline 2 = Line Interactive 3 = Online Bypass/Inverter Input Config 30549 1 1 = Single/Combined Source 2 = Dual/Separate Sources Audible Alarm Control 30550 40550 1 0 = off 1 = on 40551 1 1 = Issue Command Abort Command Reset Power Statistics 40552 1 1 = Reset Silence Audible Alarm 40553 1 1 = Silence Alarm If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 277 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-65 Liebert GXT3™ and Liebert GXT4™—Glossary Data Label Data Description Abort Command Attempt to abort a previously issued command to the device that is still pending Audible Alarm Control Audible Alarm Control Auto Restart Delay If power is lost, the control will delay this amount of time after power is restored before restarting the unit. Auto Restart When 'enabled', the UPS will automatically restart the load when utility power is restored after a battery discharge. Automatic Battery Test Enable/disable the automatic battery test schedule. Battery Cabinet Type Type of extended battery cabinets. Battery Charge Compensating Battery charge algorithm changed due to battery temperature Battery Charge Status Battery charge status. Battery Charger State Current state of the battery charger Battery Discharge Time The time on battery operation for this discharge Battery Discharging The battery is discharging Battery Float Voltage The cell voltage of the battery at float recharging. Battery Low The calculated battery time remaining has reached the low battery threshold Battery Over Voltage The system has detected that the battery voltage has exceeded a predetermined limit. Battery Percentage Charge The percentage of battery charge Battery Rating Total rating of all parallel strings in the battery. Battery Self Test Battery self test is in progress Battery Test Failed Battery test failed Battery Test Result The outcome of the previous battery test. Battery Time Remaining The calculated available time on battery Battery Under Voltage Battery voltage is too low. Bypass Input Frequency The bypass input frequency Bypass Input RMS Current Line 2 The bypass input RMS current for Line 2 Bypass Input RMS Current The bypass input RMS current. Bypass Input Voltage RMS L1-L2 The bypass input RMS voltage between Lines 1 and 2 Bypass Input Voltage RMS L1-N The bypass input RMS voltage between Line 1 and Neutral Bypass Input Voltage RMS L2-N The bypass input RMS voltage between Line 2 and Neutral Bypass Nominal Voltage Bypass nominal (or rated) voltage Bypass Not Available A problem associated with the bypass has been detected Bypass/Inverter Input Config Input source configuration for the bypass and inverter. Charger Failure Charger Failure - Charger is off DC Bus Nominal Voltage The nominal (or rated) voltage between the positive and negative terminals of the DC bus at the battery input DC Bus Voltage The voltage between the positive and negative terminals of the DC bus at the battery input DC Converter Status The operating state of the dc converter. DC to DC Converter Fault A failure has occurred in the battery discharge circuit. ECO Mode Operation State This setting is used to enable or disable ECO Mode. ECO Mode Status Current ECO Mode Status Emergency Power Off - Latched System output is off - 'Emergency Power Off (EPO) - latched' requires manual reset Equipment Over Temperature Equipment over temperature summary event Inlet Air Temperature The temperature of the inlet air Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 278 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-65 Liebert GXT3™ and Liebert GXT4™—Glossary Data Label Data Description Input Frequency Deviation The input frequency is outside of the normal range. Input Overvoltage One or more of the input phase voltages has exceeded the limit. Input Undervoltage One or more of the input phase voltages has dropped below the limit. Input Wiring Fault The neutral/ground conductors on the input wiring are not properly bonded, or the line/neutral conductors have been swapped. Inverter Failure Inverter failure - inverter output is off Inverter On/Off State inverter on/off state Loss of Redundancy The multi-module collection doesn't have enough modules to satisfy the redundancy configuration. Low Battery Warning Time When battery time remaining falls to, or below, this value the low battery alarm is activated. Maintenance Bypass Breaker Closed The maintenance bypass breaker is closed. Manual Battery Test Command to initiate a manual battery test. Nominal Battery Capacity The nominal (or rated) battery capacity time at full load Nominal Power Factor The nominal (or rated) system power factor. Number of EBC Installed The total number of Extended Battery Cabinets installed. Outlet Group Identifier A runtime assigned outlet group identification number Outlet Group Power Control Outlet Group Power Control (OFF, ON, Cycle, etc) Output Apparent Power Rating Output apparent power rating Output On Delay When a value is written to this point the output will be turned on after the specified time has elapsed. Output Overload An overload exists on the output. Output Overvoltage One or more of the output phase voltages has exceeded the limit. Output Undervoltage One or more of the output phase voltages has dropped below the limit. Parallel Comm Warning Parallel communication bus warning Power Factor Correction The state of the power factor correction circuitry of the system Reboot With Delay When a value is written to this point the output will be turned off immediately and then turned back on after the specified time has elapsed. Rectifier Failure Rectifier failure - rectifier is off Replace Battery The battery is due for replacement. Reset Power Statistics Reset Power Statistics Server Class The general classification for this system Shutdown After Delay When a value is written to this point the system will shutdown after the specified time has elapsed and output will remain off. Shutdown Pending Shutdown is pending. Shutdown Reason The reason for the most recent shutdown Silence Audible Alarm Silence Audible Alarm System Fan Failure System fan failure - one or more fans have failed System Input Black Out Count The number of occurrences, since the last reset, where the input was not qualified to provide power to the system System Input Brown Out Count The number of occurrences, since the last reset, where the system input voltage has fallen below a pre-determined threshold for a specified amount of time System Input Frequency The system input frequency System Input Max Voltage L1-N The maximum system input voltage measurement for Line 1-N since the last reset System Input Max Voltage L2-N The maximum system input voltage measurement for Line 2-N since the last reset 279 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-65 Liebert GXT3™ and Liebert GXT4™—Glossary Data Label Data Description System Input Min Voltage L1-N The minimum system input voltage measurement for Line 1-N since the last reset System Input Min Voltage L2-N The minimum system input voltage measurement for Line 2-N since the last reset System Input Nominal Current The nominal (or rated) system input current System Input Nominal Frequency The nominal (or rated) system input frequency System Input Nominal Voltage The nominal (or rated) system input voltage System Input Power Problem The input is not qualified to provide power to the system System Input RMS Current L1 The system input RMS current for Line 1 System Input RMS Current L2 The system input RMS current for Line 2 System Input RMS L1-L2 The System Input RMS Voltage between Line 1 and Line 2 System Input RMS L1-N The System Input RMS Voltage between Line 1 and Neutral System Input RMS L2-N The System Input RMS Voltage between Line 2 and Neutral System Output Apparent Power L1 System output apparent power on Line 1 System Output Apparent Power L2 System output apparent power on Line 2 System Output Apparent Power The sum total apparent power of all system output phases System Output Frequency The system output frequency System Output Max Voltage L1-N The maximum system output voltage measurement for Line 1-N since the last reset. System Output Max Voltage L2-N The maximum system output voltage measurement for Line 2-N since the last reset. System Output Min Voltage L1-N The minimum system output voltage measurement for Line 1-N since the last reset. System Output Min Voltage L2-N The minimum system output voltage measurement for Line 2-N since the last reset. System Output Nominal Frequency The nominal (or rated) system output frequency System Output Nominal Voltage The nominal (or rated) system output voltage System Output Off The system output is off System Output Pct Power L1 The system output power on Line 1 as a percentage of the rated capacity System Output Pct Power L2 The system output power on Line 2 as a percentage of the rated capacity System Output Pct Power The system output power as a percentage of the rated capacity. System Output Power L1 The system output power on Line 1. System Output Power L2 The system output power on Line 2. System Output Power The sum total power of all system output phases System Output RMS Current L1 The system output RMS current for Line 1 System Output RMS Current L2 The system output RMS current for Line 2 System Output Voltage RMS L1-L2 The system output RMS voltage between Lines 1 and 2 System Output Voltage RMS L1-N The system output RMS voltage between Line 1 and Neutral System Output Voltage RMS L2-N The system output RMS voltage between Line 2 and Neutral System Status The operating status for the system Unspecified General Event One or more unspecified events active. See local unit display for further details. UPS Battery Status UPS battery status UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source UPS Topology UPS Topology Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 280 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-66 Liebert HiNet™—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units DC-To-DC Converter On 10042 — 1 — — Load On Inverter 10073 — 1 — — Bypass Active 10074 — 1 — — Load On Battery 10128 — 1 — — Permanently On Bypass 10133 — 1 — — Bypass SCR Open Circuit 10149 — 1 — — Low Battery - Shutdown Imminent 10152 — 1 — — Output Overload 10154 — 1 — — Inverter Unsynchronized 10160 — 1 — — Input Power Supply Fail 10186 — 1 — — Bypass Input Voltage/Frequency Fault 10202 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 281 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-67 Liebert HiNet™—Input and Holding Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of Output Lines 30004 40004 1 — Bits 8 - 11 Number of SubModules 30009 40009 1 — - Number of Battery Cells 30012 40012 1 — - Load (Apparent Power) 30102 — 2 — VA Load (Real Power) 30104 — 2 — W Input Frequency 30107 — 1 10 Hz Output Frequency 30108 — 1 10 Hz Battery Voltage 30113 — 1 — V Battery Current (Charge/Discharge) 30114 — 1 — A Battery Charge Percentage 30116 — 1 — % Ambient Temperature 30119 — 1 — deg C Input Voltage L1 30153 — 1 — V Input Current L1 30154 — 1 — A Output Voltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A Data Description Input Voltage L2 30203 — 1 — V Input Current L2 30204 — 1 — A Input Voltage L3 30253 — 1 — V Input Current L3 30254 — 1 — A If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 282 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-68 Liebert Nfinity®—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Automatic Battery Test Enabled 10003 3 1 — — Battery Charger On 10044 — 1 — — Inverter Ready 10047 — 1 — — Power Factor Correction State 10050 — 1 — — Load on Inverter 10073 — 1 — — Bypass Active 10074 — 1 — — Replace Battery 10081 — 1 — — Battery Under Test 10082 — 1 — — Load on Battery 10128 — 1 — — Load on Bypass 10129 — 1 — — Load on Manual Bypass 10132 — 1 — — Load Transferred to Bypass Due to UPS Fault 10134 — 1 — — Transfer Inhibit 10146 — 1 — — Output Off Pending 10151 — 1 — — Low Battery - Shutdown Imminent 10152 — 1 — — Output Overload 10154 — 1 — — UPS Overload 10155 — 1 — — Output Off 10158 — 1 — — Check Air Filter - Replace 10170 — 1 — — Transformer Over Temperature 10178 — 1 — — Input Power Supply Fail 10186 — 1 — — Internal Device Communication Failure 10284 — 1 — — Device Active Alarm 10290 — 1 — — Main Control Warning 10291 — 1 — — Redundant Control Warning 10292 — 1 — — Control Module Failure 10293 — 1 — — Redundant Control Module Failed 10294 — 1 — — User Interface Module Failed 10295 — 1 — — UPS Power Not Redundant 10296 — 1 — — Power Module Failure 10298 — 1 — — Battery Module Failure 10299 — 1 — — Power Module Warning 10300 — 1 — — Battery Module Warning 10301 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 283 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-69 Liebert Nfinity®—Input and Holding Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of Output Lines 30004 40004 1 — Bits 8 - 11 Number of Power Mod. 30010 40010 1 — — Number of Battery Modules Installed 30011 40011 1 — — Data Description Device Maximum Frame Capacity 30023 40023 2 — — Device System Capacity 30025 40025 2 — VA Nominal Input Voltage 30027 40027 1 — V Nominal Output Voltage 30028 40028 1 — V Nominal Static Bypass Switch Voltage 30029 40029 1 — V Nominal Input Frequency 30031 40031 1 10 Hz Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 — Nominal Battery Voltage 30034 40034 1 — V Auto Restart Delay 30051 40051 1 — Seconds Device Auto Restart Percent Setpt 30052 40052 1 — % Device Low Battery Time 30053 40053 1 — Minutes Next Battery Auto Test Time 30057 40057 1 — Minutes Overload Alarm Limit 30067 40067 2 — VA Minimum Redundant Power Modules 30074 40074 1 — — Load (Apparent Power) 30102 — 2 — VA Load (Real Power) 30104 — 2 — W Load / Capacity 30106 — 1 — % Input Frequency 30107 — 1 10 Hz Output Frequency 30108 — 1 10 Hz Bypass Frequency 30109 — 1 10 Hz 1 - 100% Charged 2 - Less than 100% Charged 3 - Charging 4 - Discharging 5 - Float Charging 6 - Equalize Charging Battery Charge Status 30112 — 1 — Battery Voltage 30113 — 1 — V Battery Time Remaining 30115 — 1 — Minutes Battery Charge Percentage 30116 — 1 — % Battery Temperature 30117 — 1 — deg C Transformer Temperature 30121 — 1 — deg C Redundant Power Modules 30124 — 1 — — Active Power Module Count 30126 — 1 — — Battery Module Active Count 30127 — 1 — — Battery Test Result 30130 — 1 — - Input Voltage L1 30153 — 1 — V Input Current L1 30154 — 1 — A Bypass Voltage L1 30159 — 1 — V Bypass Current L1 30160 — 1 — A Output Voltage L1 30163 — 1 — V If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 284 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-69 Liebert Nfinity®—Input and Holding (continued) Data Description Input Register Holding Register # of Reg. Scale Notes / Units Output Current L1 30164 — 1 — A Power Module Failure Count 30304 — 1 — — Battery Module Failure Count 30305 — 1 — — Power Module Warning Count 30306 — 1 — — Battery Module Warning Count 30307 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 285 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-70 Liebert NX™—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Economode 10005 5 — — — DC-To-DC Converter On 10042 — — — — Battery Charge Compensation 10046 — — — — Inverter Ready 10047 — — — — Power Factor Correction State 10050 — — — — Battery Charge Mode 10051 — — — — Load On Inverter 10073 — — — — Bypass Active 10074 — — — — Battery Under Test 10082 — — — — Load On Battery 10128 — — — — Overload Transfer To Bypass 10131 — — — — Input Switch Open 10137 — — — — Generator Disconnected 10141 — — — — Bypass Transfer Count Block 10147 — — — — Static Bypass Switch Disabled 10148 — — — — Low Battery - Shutdown Imminent 10152 — — — — Output Overload 10154 — — — — UPS Load Joint Mode 10156 — — — — Output Off 10158 — — — — Inverter Unsynchronized 10160 — — — — Main Neutral Lost 10161 — — — — Fan Failure 10169 — — — — Ambient Over Temperature 10173 — — — — Rectifier Over Temperature 10174 — — — — Rectifier Inductor Over Temperature 10175 — — — — Inverter Over Temperature 10176 — — — — Inverter Inductor Over Temperature 10177 — — — — Battery Converter Over Temperature 10179 — — — — DC Bus Balancer Over Temperature 10180 — — — — Input Power Supply Fail 10186 — — — — Input BrownOut 10189 — — — — Bad Input Frequency 10190 — — — — Bypass Phase Rotation Error 10191 — — — — Bypass Phase Loss 10201 — — — — Bypass Input Voltage/Frequency Fault 10202 — — — — Output Fuse Blown 10217 — — — — Output Over Voltage 10219 — — — — Charger Failed 10234 — — — — Battery Fault 10235 — — — — Battery Contact Fail 10236 — — — — Battery Converter Over Current 10237 — — — — Battery Converter Fail 10238 — — — — DC Bus Balancer Over Current 10239 — — — — DC Bus Balancer Fault 10240 — — — — DC Bus 1 Power Supply Fail 10251 — — — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 286 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-70 Liebert NX™—Status and Coil (continued) Data Description Status Coil Number of Bits Scale Notes / Units Rectifier Fuse Fail 10257 — — — — Rectifier Startup Failure 10258 — — — — Rectifier Fault 10259 — — — — Rectifier Current Limit 10260 — — — — Inverter DC Voltage Low Shutdown 10262 — — — — Inverter Fault 10263 — — — — Inverter DC Offset Overload 10264 — — — — Inverter Contactor Fail 10265 — — — — Inverter Current Limit 10266 — — — — Parallel Low Battery Warning 10267 — — — — Load Share Fault 10268 — — — — Parallel System Fault 10269 — — — — Parallel Connection Error 10270 — — — — Parallel System Overload 10271 — — — — Parallel Transfer To Static Bypass Switch 10272 — — — — Inverter Communication Fail 10281 — — — — Rectifier Communication Failure 10282 — — — — Parallel Communication Fault 10283 — — — — Operation Fault 10289 — — — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 287 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-71 Liebert NX™—Input and Holding Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of Output Lines 30004 40004 1 — Bits 8 - 11 Data Description Number of SubModules 30009 40009 1 — — Module Number 30014 40014 1 — — Device Module Count 30015 40015 1 — — Device Redundant Count 30016 40016 1 — — Device Module Mode 30017 40017 1 — — Nominal Power Rating 30021 40021 2 — VA Nominal Input Voltage 30027 40027 1 — V Nominal Output Voltage 30028 40028 1 — V Nominal Static Bypass Switch Voltage 30029 40029 1 — V Nominal Input Frequency 30031 40031 1 10 Hz Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 — Nominal DC Bus #1 Voltage 30035 40035 1 — V Nominal DC Bus #2 Voltage 30036 40036 1 — — Nominal Battery Float Voltage 30038 40038 1 — V Load Bus Sync Mode 30040 40040 1 — — Auto Restart Delay 30051 40051 1 — Seconds Device Low Battery Time 30053 40053 1 — Minutes Input Frequency 30107 — 1 10 Hz Output Frequency 30108 — 1 10 Hz Bypass Frequency 30109 — 1 10 Battery Charge Status 30112 — 1 — Battery Voltage 30113 — 1 — Hz 1 - 100% Charged 2 - Less than 100% Charged 3 - Charging 4 - Discharging 5 - Float Charging 6 - Equalize Charging V Battery Current (Charge/Discharge) 30114 — 1 — A Battery Time Remaining 30115 — 1 — Minutes Battery Charge Percentage 30116 — 1 — % Battery Temperature 30117 — 1 — C Ambient Temperature 30119 — 1 — C Parallel Load Source 30128 — 1 — — Rotary Breaker 30129 — 1 — — Battery Test Result 30130 — 1 — 1 - Unknown 2 - Passed 3 - Failed 4 - In Progress 5 - System Failure 6 - Inhibited Input Voltage L1-L2 30151 — 1 — V Input Voltage L1 30153 — 1 — V Input Current L1 30154 — 1 — A Input Power Factor L1 30155 — 1 100 — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 288 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-71 Liebert NX™—Input and Holding (continued) Data Description Input Register Holding Register # of Reg. Scale Notes / Units Bypass Voltage L1 30159 — 1 — V Output Voltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A Output Load L1 30165 — 1 — — Output Power Factor L1 30166 — 1 100 % Apparent Output Power L1 30168 — 2 — VA Reactive Output Power L1 30170 — 2 — VAR Output Power L1 30172 — 2 — W Output Current Crest Factor L1 30186 — 1 — % Input Voltage L2-L3 30201 — 1 — V Input Voltage L2 30203 — 1 — V Input Current L2 30204 — 1 — A Input Power Factor L2 30205 — 1 100 — Bypass Voltage L2 30209 — 1 — V Output Voltage L2 30213 — 1 — V Output Current L2 30214 — 1 — A Output Load L2 30215 — 1 — % Output Power Factor L2 30216 — 1 100 — Apparent Output Power L2 30218 — 2 — VA Reactive Output Power L2 30220 — 2 — VAR Output Power L2 30222 — 2 — W Output Current Crest Factor L2 30236 — 1 — % Input Voltage L3-L1 30251 — 1 — V Input Voltage L3 30253 — 1 — V Input Current L3 30254 — 1 — A Input Power Factor L3 30255 — 1 100 — Bypass Voltage L3 30259 — 1 — V Output Voltage L3 30263 — 1 — V Output Current L3 30264 — 1 — A Output Load L3 30265 — 1 — % Output Power Factor L3 30266 — 1 100 — Apparent Output Power L3 30268 — 2 — VA Reactive Output Power L3 30270 — 2 — VAR Output Power L3 30272 — 2 — W Output Current Crest Factor L3 30286 — 1 — % If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 289 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-72 Liebert NX™ 225-600kVA UPS—Chloride ManageUPS—Input and Holding 3 Input Holding Register # of Reg Scale Modbus Protocol Version — 40002 1 — XX.YY Manufacturer — 40003 1 — 0 = Chloride Data Description Notes/Units Identification Model — 40004 1 — 8 = 80Net UPS Software 1 Version — 40005 1 — HH Major – LL Minor UPS Software 1 Date Year — 40006 1 — — UPS Software 1 Date Month — 40007 1 — — UPS Software 1 Date Day — 40008 1 — — UPS Software 1 Code — 40009 1 — 10HXXXXX code UPS Software 2 Version — 40010 1 — HH Major – LL Minor UPS Software 2 Date Year — 40011 1 — — UPS Software 2 Date Month — 40012 1 — — UPS Software 2 Date Day — 40013 1 — — UPS Software 2 Code — 40014 1 — 10HXXXXX code Battery Status — 40020 1 — 1 = Unknown 2 = Battery Normal 3 = Battery Low 4 = Battery Depleted Seconds On Battery — 40021 1 — Units: Seconds Estimated Seconds Remaining — 40022 1 — Units: Seconds Battery Estimated Charge Remaining — 40023 1 — Units: % Battery Voltage — 40024 1 10 Units: V Battery Current — 40025 1 10 Units: A Battery Temperature — 40026 1 — Units: Deg C Line Bads — 40032 1 — — Frequency — 40033 1 10 Units: Hz Number Lines — 40034 1 — Voltage L1 — 40035 1 — Units: V Voltage L2 — 40036 1 — Units: V Voltage L3 — 40037 1 — Units: V Current L1 — 40038 1 10 Units: Amps Current L2 — 40039 1 10 Units: A Current L3 — 40040 1 10 Units: A Real Power L1 — 40041 1 10 Units: kW Real Power L2 — 40042 1 10 Units: kW Input Real Power L3 — 40043 1 10 Units: kW DC Voltage — 40044 1 — Units: V 1. If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 2. The Modbus mapping in this table assumes the default Modbus offset is 1. This value is configurable via the Web interface. If the Modbus offset is changed you will need to adjust the above Holding registers accordingly. 3. This mapping table defines Liebert NX 225-600kVA UPS support using the Chloride ManageUPS Net Adapter +B communication card. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 290 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-72 Liebert NX™ 225-600kVA UPS—Chloride ManageUPS—Input and Holding 3 (continued) Data Description Input Holding Register # of Reg Scale Notes/Units Output Source — 40050 1 — 1 = Other 2 = None 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Frequency — 40051 1 10 Units: Hz Number Lines — 40052 1 — — Voltage L1 — 40053 1 — Units: V Voltage L2 — 40054 1 — Units: V Voltage L3 — 40055 1 — Units: V Current L1 — 40056 1 10 Units: A Current L2 — 40057 1 10 Units: A Current L3 — 40058 1 10 Units: A Real Power L1 — 40059 1 10 Units: kW Real Power L2 — 40060 1 10 Units: kW Real Power L3 — 40061 1 10 Units: kW Percent Load L1 — 40062 1 — Units: % Percent Load L2 — 40063 1 — Units: % Percent Load L3 — 40064 1 — Units: % Bypass Line Bads — 40070 1 — — Frequency — 40071 1 10 Units: Hz Number Lines — 40072 1 — — Voltage L1 — 40073 1 — Units: V Voltage L2 — 40074 1 — Units: V Voltage L3 — 40075 1 — Units: V Current L1 — 40076 1 10 Units: A Current L2 — 40077 1 10 Units: A Current L3 — 40078 1 10 Units: A Alarms Present — 40087 1 — Bit 0 On Battery — 40087 1 — Bit 2 Low Battery — 40087 1 — Bit 3 Depleted Battery — 40087 1 — Bit 4 Temperature Bad — 40087 1 — Bit 5 Input Bad — 40087 1 — Bit 6 Alarms Output Overload — 40088 1 — Bit 0 On Bypass — 40088 1 — Bit 1 Bypass Bad — 40088 1 — Bit 2 Charger Failed — 40088 1 — Bit 5 Fan Failure — 40089 1 — Bit 0 1. If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 2. The Modbus mapping in this table assumes the default Modbus offset is 1. This value is configurable via the Web interface. If the Modbus offset is changed you will need to adjust the above Holding registers accordingly. 3. This mapping table defines Liebert NX 225-600kVA UPS support using the Chloride ManageUPS Net Adapter +B communication card. 291 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-72 Liebert NX™ 225-600kVA UPS—Chloride ManageUPS—Input and Holding 3 (continued) Input Holding Register # of Reg Scale Notes/Units General Fault — 40089 1 — Bit 2 Diagnostic Test Failed — 40089 1 — Bit 3 Communications Lost — 40089 1 — Bit 4 Data Description Shutdown Pending — 40089 1 — Bit 6 Test In Progress — 40090 1 — Bit 0 General Warning — 40090 1 — Bit 2 — 0 = Bypass not present 1 = Bypass on 2 = Bypass off 3 = Bypass fault 4 = Bypass not prepared Condition Bypass — 40091 1 Inverter — 40092 1 — 0 = Inverter off 1 = Inverter turning on 2 = Inverter on 3 = Inverter fault 4 = Inverter turning off Rectifier — 40093 1 — 0 = Rectifier Off 1 = Rectifier Turning On 2 = Rectifier On 3 = Rectifier Fault Battery Connected — 40094 1 — — NonSynchronism — 40095 1 — — In Parallel Set — 40101 1 — 0 = UPS is Single 1 = UPS is part of parallel set Customer-Dedicated Information — — — Customer Info 1 — 40108 1 — — Customer Info 2 — 40109 1 — — Customer Info 3 — 40110 1 — — Customer Info 4 — 40111 1 — — Customer Info 5 — 40112 1 — — Parallel Condition 1. If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 2. The Modbus mapping in this table assumes the default Modbus offset is 1. This value is configurable via the Web interface. If the Modbus offset is changed you will need to adjust the above Holding registers accordingly. 3. This mapping table defines Liebert NX 225-600kVA UPS support using the Chloride ManageUPS Net Adapter +B communication card. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 292 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-73 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Status and Coil Status Coil Number of Bits Notes Rectifier Failure 10001 — 1 Active on Alarm System Input Phs Rotation Error 10002 — 1 Active on Alarm System Input Current Limit 10003 — 1 Active on Alarm System Input Power Problem 10004 — 1 Active on Alarm 10015 — 1 Active on Alarm Bypass Input Voltage Fault 10016 — 1 Active on Alarm Bypass Not Available 10017 — 1 Active on Alarm Bypass Overload 10018 — 1 Active on Alarm Data Label Input Bypass Bypass Static Switch Unavailable Battery Battery Test Failed 10029 — 1 Active on Alarm Battery Test Passed 10030 — 1 Active on Alarm Battery Terminals Reversed 10031 — 1 Active on Alarm Battery Over Voltage 10032 — 1 Active on Alarm Battery Temperature Out of Range 10033 — 1 Active on Alarm Battery Low 10034 — 1 Active on Alarm Battery Over Temperature 10035 — 1 Active on Alarm Battery Discharging 10036 — 1 Active on Alarm Battery Auto Test In Progress 10037 — 1 Active on Alarm Battery Manual Test In Progress 10038 — 1 Active on Alarm Battery Ground Fault 10039 — 1 Active on Alarm DC Bus Abnormal 10040 — 1 Active on Alarm 10051 — 1 Active on Alarm Output System Output Off Output Load on Maint. Bypass 10052 — 1 Active on Alarm UPS Output on Bypass 10053 — 1 Active on Alarm Inverter Inverter Failure 10065 — 1 Active on Alarm Inverter Overload 10066 — 1 Active on Alarm System Output Fault 10067 — 1 Active on Alarm Output Of/Uf 10068 — 1 Active on Alarm System Shutdown - Output Short 10069 — 1 Active on Alarm Inverter Desaturation 10070 — 1 Active on Alarm Booster-Charger Booster Failure 10081 — 1 Active on Alarm Charger Failure 10082 — 1 Active on Alarm System Shutdown - EPO 10093 — 1 Active on Alarm Generic DIC Fault 10094 — 1 Active on Alarm Inlet Air Over Temperature 10095 — 1 Active on Alarm Generic Test Event 10096 — 1 Active on Alarm System Status Fan Hours Exceeded 10097 — 1 Active on Alarm Unit Shutdown 10098 — 1 Active on Alarm Main Controller Fault 10099 — 1 Active on Alarm Equipment Over Temperature 10100 — 1 Active on Alarm 293 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-73 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Status and Coil (continued) Data Label Status Coil Number of Bits Notes Maximum Load Alarm 10101 — 1 Active on Alarm Ground Fault 10102 — 1 Active on Alarm Backfeed Breaker Open 10113 — 1 Active on Alarm Input Breaker Open 10114 — 1 Active on Alarm Output Breaker Open 10115 — 1 Active on Alarm Maintenance Bypass Breaker Closed 10116 — 1 Active on Alarm Battery Breaker Open 10117 — 1 Active on Alarm Switch Gear Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 294 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding Input Holding # of Reg Scale Notes/Units System Input RMS A-B 30385 — 1 10 Units : VAC Uint16 System Input RMS B-C 30386 — 1 10 Units : VAC Uint16 System Input RMS C-A 30387 — 1 10 Units : VAC Uint16 System Input RMS Current Phase A 30388 — 1 10 Units : A AC Uint16 System Input RMS Current Phase B 30389 — 1 10 Units : A AC Uint16 System Input RMS Current Phase C 30390 — 1 10 Units : A AC Uint16 System Input Frequency 30391 — 1 10 Units : Hz Uint16 Rectifier Status 30392 — 1 — 0 = off 1 = on Rectifier Phase A Temperature sensor 30403 — 1 — Units : deg C Int16 Rectifier Phase A Temperature sensor 30404 — 1 — Units : deg F Int16 Rectifier Phase B Temperature sensor 30405 — 1 — Units : deg C Int16 Rectifier Phase B Temperature sensor 30406 — 1 — Units : deg F Int16 Rectifier Phase C Temperature sensor 30407 — 1 — Units : deg C Int16 Rectifier Phase C Temperature sensor 30408 — 1 — Units : deg F Int16 Data Label Input Rectifier Module Temperatures 1 Rectifier Module Temperatures 2 — — Rectifier Phase A Temperature sensor 30419 — 1 — Units : deg C Int16 Rectifier Phase A Temperature sensor 30420 — 1 — Units : deg F Int16 Rectifier Phase B Temperature sensor 30421 — 1 — Units : deg C Int16 Rectifier Phase B Temperature sensor 30422 — 1 — Units : deg F Int16 Rectifier Phase C Temperature sensor 30423 — 1 — Units : deg C Int16 Rectifier Phase C Temperature sensor 30424 — 1 — Units : deg F Int16 295 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding (continued) Input Holding # of Reg Scale Notes/Units Rectifier Phase A Temperature sensor 30451 — 1 — Units : deg C Int16 Rectifier Phase A Temperature sensor 30452 — 1 — Units : deg F Int16 Rectifier Phase B Temperature sensor 30453 — 1 — Units : deg C Int16 Rectifier Phase B Temperature sensor 30454 — 1 — Units : deg F Int16 Rectifier Phase C Temperature sensor 30455 — 1 — Units : deg C Int16 Rectifier Phase C Temperature sensor 30456 — 1 — Units : deg F Int16 Bypass Input Voltage RMS A-B 30467 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS B-C 30468 — 1 — Units : VAC Uint16 Bypass Input Voltage RMS C-A 30469 — 1 — Units : VAC Uint16 Bypass Input Frequency 30470 — 1 — Units : Hz Uint16 Static Bypass Switch 30471 — 1 — 0 = off 1 = on Data Label Rectifier Module Temperatures 4 Bypass 30472 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High DC Bus Voltage 30483 — 1 — Units : VDC Uint16 Battery Volts for Cabinet 30484 — 1 — Units : VDC Int16 DC Bus Current 30485 — 1 — Units : A DC Int16 Battery Time Remaining 30486 — 1 — Units : min Uint16 Battery Percentage Charge 30487 — 1 — Units : % Uint16 Battery Temperature for Cabinet 30488 — 1 — Units : deg C Int16 Battery Temperature for Cabinet 30489 — 1 — Units : deg F Int16 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High — 1 = Unknown 2 = Normal 3 = Low 4 = Depleted Bypass Qualification Status Battery DC Bus Qualification Status UPS battery1 status 30490 30491 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide — 1 — 1 296 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding (continued) Input Holding # of Reg Scale Notes/Units System Output Voltage RMS A-B 30502 — 1 10 Units : VAC Uint16 System Output Voltage RMS B-C 30503 — 1 10 Units : VAC Uint16 System Output Voltage RMS C-A 30504 — 1 10 Units : VAC Uint16 System Output RMS Current Phs A 30505 — 1 10 Units : A AC Uint16 System Output RMS Current Phs B 30506 — 1 10 Units : A AC Uint16 System Output RMS Current Phs C 30507 — 1 10 Units : A AC Uint16 System Output Frequency 30508 — 1 10 Units : Hz Uint16 System Output Apparent Power 30509 — 1 — Units : kVA Uint16 System Output Power 30510 — 1 — Units : kW Uint16 System Output Apparent Power Phs A 30511 — 1 — Units : kVA Uint16 System Output Apparent Power Phs B 30512 — 1 — Units : kVA Uint16 System Output Apparent Power Phs C 30513 — 1 — Units : kVA Uint16 System Output Power Phase A 30514 — 1 — Units : kW Uint16 System Output Power Phase B 30515 — 1 — Units : kW Uint16 System Output Power Phase C 30516 — 1 — Units : kW Uint16 System Output Pct Power Phase A 30517 — 1 — Units : % Uint16 System Output Pct Power Phase B 30518 — 1 — Units : % Uint16 System Output Pct Power Phase C 30519 — 1 — Units : % Uint16 Output Percent Load 30520 — 1 — Units : % Uint16 Temperature 30521 — 1 — Units : deg C Int16 Temperature 30522 — 1 — Units : deg F Int16 Data Label Output UPS Output Source 30523 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Load Power Source 30524 — 1 — 0 = Load Off 1 = UPS 2 = Maintenance Bypass 297 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding (continued) Input Holding # of Reg Scale Notes/Units Inverter Overload Time Remaining 30535 — 1 — Units : sec Uint16 Inverter On/Off State 30536 — 1 — 0 = off 1 = on Data Label Inverter 30537 — 1 — 0 = External 1 = Self clock (internal) 2 = Output 3 = Bypass Inverter Phase A Temperature sensor 30548 — 1 — Units : deg C Int16 Inverter Phase A Temperature sensor 30549 — 1 — Units : deg F Int16 Inverter Phase B Temperature sensor 30550 — 1 — Units : deg C Int16 Inverter Phase B Temperature sensor 30551 — 1 — Units : deg F Int16 Inverter Phase C temperature sensor 30552 — 1 — Units : deg C Int16 Inverter Phase C temperature sensor 30553 — 1 — Units : deg F Int16 Inverter Phase A Temperature sensor 30564 — 1 — Units : deg C Int16 Inverter Phase A Temperature sensor 30565 — 1 — Units : deg F Int16 Inverter Phase B Temperature sensor 30566 — 1 — Units : deg C Int16 Inverter Phase B Temperature sensor 30567 — 1 — Units : deg F Int16 Inverter Phase C temperature sensor 30568 — 1 — Units : deg C Int16 Inverter Phase C temperature sensor 30569 — 1 — Units : deg F Int16 Inverter Phase A Temperature sensor 30596 — 1 — Units : deg C Int16 Inverter Phase A Temperature sensor 30597 — 1 — Units : deg F Int16 Inverter Phase B Temperature sensor 30598 — 1 — Units : deg C Int16 Inverter Phase B Temperature sensor 30599 — 1 — Units : deg F Int16 Inverter Phase C temperature sensor 30600 — 1 — Units : deg C Int16 Inverter Phase C temperature sensor 30601 — 1 — Units : deg F Int16 30612 — 1 100 Units : VDC Uint16 Inverter Synchronization Source Inverter Module Temperatures 1 Inverter Module Temperatures 2 Inverter Module Temperatures 4 Booster-Charger Battery Recharge Voltage Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 298 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-74 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Max Charge Current 30613 — 1 — Units : A DC Int16 Booster On/Off State 30614 — 1 — 0 = off 1 = on Charger On/Off State 30615 — 1 — 0 = off 1 = on Booster-Charger Temperature 30626 — 1 — Units : deg C Int16 Booster-Charger Temperature 30627 — 1 — Units : deg F Int16 Booster Charger Module Temperatures 1 Booster Charger Module Temperatures 2 — — Booster-Charger Temperature 30638 — 1 — Units : deg C Int16 Booster-Charger Temperature 30639 — 1 — Units : deg F Int16 Booster Charger Module Temperatures 4 — — Booster-Charger Temperature 30662 — 1 — Units : deg C Int16 Booster-Charger Temperature 30663 — 1 — Units : deg F Int16 — 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation System Status System Status 30674 — 1 UPS Operating Mode 30675 — 1 — 0 = Idle 1 = Double Conversion Mode (VFI) 2 = Interactive Mode (VI) 3 = Stand-By Mode (VFD) 4 = CR Mode (CR) 5 = ECO Mode (DIM) ECO Mode Operation State 30676 — 1 — 0 = disabled 1 = enabled Output Apparent Power Rating 30687 — 1 — Units : kVA Uint16 System Input Nominal Voltage 30688 — 1 — Units : VAC Uint16 System Input Nominal Frequency 30689 — 1 — Units : Hz Uint16 Ratings 299 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-75 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Glossary Data Label Data Description Backfeed Breaker Open The backfeed breaker is in the open position Battery Auto Test In Progress Automatic battery test is in progress Battery Breaker Open The battery circuit is open. Battery Discharging The battery is discharging Battery Ground Fault Battery system ground fault amperage exceeds the threshold Battery Low The calculated battery time remaining has reached the low battery threshold Battery Manual Test In Progress Manual battery test is in progress Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Over Voltage The system has detected that the battery voltage has exceeded a predetermined limit. Battery Percentage Charge The percentage of battery charge Battery Recharge Voltage The recharge cell voltage for the battery. Battery Temperature for Cabinet The battery temperature for a cabinet Battery Temperature Out of Range Battery temperature is outside of acceptable range. Battery Terminals Reversed The measured battery voltage is a negative value due to reverse battery terminal connections. Battery Test Failed Battery test failed Battery Test Passed Battery test passed Battery Time Remaining The calculated available time on battery Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Booster Failure Booster failure - boost is off Booster On/Off State Booster on/off state Booster-Charger Temperature Temperature measured at the charger stage Bypass Input Frequency The bypass input frequency Bypass Input Voltage Fault The system has detected the bypass voltage is unqualified. Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B Bypass Input Voltage RMS B-C The bypass input RMS voltage between phases B and C Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A Bypass Not Available A problem associated with the bypass has been detected Bypass Overload Bypass overloaded, reduce load immediately. Bypass Qualification Status bypass qualification status Bypass Static Switch Unavailable The static bypass is unavailable to support the critical load. Charger Failure Charger Failure - Charger is off Charger On/Off State Charger on/off state DC Bus Abnormal The system has detected an abnormal DC Bus Voltage. DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value DC Bus Qualification Status dc bus qualification status DC Bus Voltage The voltage between the postivie and negative terminals of the internal DC Bus. ECO Mode Operation State This setting is used to enable or disable ECO Mode. Equipment Over Temperature Equipment over temperature summary event Fan Hours Exceeded Operating hours for the unit blower fan have exceeded the threshold. Generic DIC Fault The control board reports a fault - Service required. Generic Test Event A generic test event designed to evaluate system handling of events Ground Fault An AC phase to ground fault or three phase fault to ground exists on the output of the UPS. Inlet Air Over Temperature The inlet air exceeds the maximum temperature threshold Input Breaker Open The main input breaker is open. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 300 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-75 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Glossary (continued) Data Label Data Description Inverter Desaturation Inverter Desaturation Inverter Failure Inverter failure - inverter output is off Inverter On/Off State inverter on/off state Inverter Overload Time Remaining The calculated time remaining before inverter shutdown Inverter Overload Inverter in overload fault Inverter Phase A Temperature sensor Inverter temperature sensor reading for Phase A. Inverter Phase B Temperature sensor Inverter temperature sensor reading for Phase B. Inverter Phase C temperature sensor Inverter temperature sensor reading for Phase C. Inverter Synchronization Source The reference source for inverter synchronization Load Power Source Load power source Main Controller Fault A Main Controller fault has been detected. Maintenance Bypass Breaker Closed The maintenance bypass breaker is closed. Max Charge Current The maximum allowed current to be used for charging the batteries. Maximum Load Alarm Maximum load alarm indicating load setting has been exceeded. Output Apparent Power Rating Output apparent power rating Output Breaker Open The output breaker is open. Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Output Of/Uf The output frequency has exceeded a specified range for a specified period of time. Output Percent Load The percentage of the system's total rated output current that is flowing from the system. Rectifier Failure Rectifier failure - rectifier is off Rectifier Phase A Temperature sensor Rectifier temperature sensor reading for Phase A. Rectifier Phase B Temperature sensor Rectifier temperature sensor reading for Phase B. Rectifier Phase C Temperature sensor Rectifier temperature sensor reading for Phase C. Rectifier Status rectifier status Static Bypass Switch Static Bypass Switch state - On/Off System Input Current Limit The RMS input current has reached the input current limit threshold System Input Frequency The system input frequency System Input Nominal Frequency The nominal (or rated) system input frequency System Input Nominal Voltage The nominal (or rated) system input voltage System Input Phs Rotation Error The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C) System Input Power Problem The input is not qualified to provide power to the system System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power Phs A System output apparent power on phase A System Output Apparent Power Phs B System output apparent power on phase B System Output Apparent Power Phs C System output apparent power on phase C System Output Apparent Power The sum total apparent power of all system output phases System Output Fault A fault has been detected in the system output System Output Frequency The system output frequency System Output Off The system output is off System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity 301 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-75 Liebert NX 225-600kVA UPS—IS-UNITY-DP—Glossary (continued) Data Label Data Description System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity System Output Power Phase A The system output power on phase A. System Output Power Phase B The system output power on phase B. System Output Power Phase C The system output power on phase C. System Output Power The sum total power of all system output phases System Output RMS Current Phs A The system output RMS current for Phase A System Output RMS Current Phs B The system output RMS current for Phase B System Output RMS Current Phs C The system output RMS current for Phase C System Output Voltage RMS A-B The system output RMS voltage between phases A and B System Output Voltage RMS B-C The system output RMS voltage between phases B and C System Output Voltage RMS C-A The system output RMS voltage between phases C and A System Shutdown - EPO System shutdown due to Emergency Power Off (EPO) System Shutdown - Output Short Shutdown was due to a short on the output. System Status The operating status for the system Temperature Temperature measured at the temperature sensor Unit Shutdown An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. UPS battery1 status UPS battery status UPS Operating Mode UPS Operating Mode UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 302 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-76 Liebert NXL™—60Hz, UL version (Model 40)—Status and Coil Data Label Status Coil # of Bits Notes NXL Type Battery Self Test 10082 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Low Shutdown 10092 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Shutdown - REPO 10093 — 1 Active on Alarm N+1, 1+N, 1+1, SMS UPS Output on Bypass 10129 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Output Load on Maint. Bypass 10132 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Main Battery Disconnect Open 10136 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Bypass - Excess Auto Retransfers 10147 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Battery Low 10152 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Shutdown - EPO 10157 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Output Off 10158 — 1 Active on Alarm Deprecated Battery Over Temperature 10172 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Inlet Air Over Temperature 10173 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Input Current Imbalance 10185 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Input Phs Rotation Error 10191 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Rectifier Failure 10259 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Inverter Failure 10263 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Main Controller Fault 10293 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Bypass Not Available 10321 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Overload Phase A 10322 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Overload Phase B 10323 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Overload Phase C 10324 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Auto Retransfer Failed 10325 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Static Switch Unavailable 10326 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Static Switch Overload 10327 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Excessive Pulse Parallel 10328 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Auto Transfer Failed 10329 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Frequency Error 10330 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass - Manual Rexfr Inhibited 10331 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass - Manual Xfr Inhibited 10332 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Bypass Static Switch Off Extrnl 10333 — 1 Active on Alarm CE only Battery Charging Reduced-Extrnl 10334 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Capacity Low 10335 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Discharging 10336 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Temperature Imbalance 10337 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Temperature Sensor Fault 10338 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Charging Inhibited 10339 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Circuit Breaker 1 Open 10340 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Circuit Breaker 2 Open 10341 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Circuit Breaker 3 Open 10342 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Circuit Breaker 4 Open 10343 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Circuit Breaker 5 Open 10344 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Circuit Breaker 6 Open 10345 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Circuit Breaker 7 Open 10346 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Circuit Breaker 8 Open 10347 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery - External Monitor 1 10348 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery - External Monitor 2 10349 — 1 Active on Alarm N+1, 1+N, 1+1, SMS 303 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-76 Liebert NXL™—60Hz, UL version (Model 40)—Status and Coil (continued) Data Label Status Coil # of Bits Notes NXL Type Battery Over Temperature 10350 — 1 Active on Warning N+1, 1+N, 1+1, SMS DC Bus Ground Fault - Positive 10351 — 1 Active on Alarm N+1, 1+N, 1+1, SMS DC Bus Ground Fault - Negative 10352 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Output Low Power Factor 10353 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Leading Power Factor 10354 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Output Amp Over User Limit-Phs A 10355 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Output Amp Over User Limit-Phs B 10356 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Output Amp Over User Limit-Phs C 10357 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Output Fault 10358 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Inverter Overload Phase A 10359 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Inverter Overload Phase B 10360 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Inverter Overload Phase C 10361 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Inverter Inhibit - External 10362 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Inverter Shutdown - Overload 10363 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Inverter Off - External 10364 — 1 Active on Alarm CE only Inverter Static Switch SCR Short 10365 — 1 Active on Alarm CE only Equipment Over Temperature 10366 — 1 Active on Warning SCC, N+1, 1+N, 1+1, SMS Equipment Over Temperature 10367 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Equipment Temperature Sensor Fail 10368 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 01 10369 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 02 10370 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 03 10371 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 04 10372 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 05 10373 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 06 10374 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 07 10375 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 08 10376 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 09 10377 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 10 10378 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 11 10379 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 12 10380 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 13 10381 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 14 10382 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 15 10383 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Contact 16 10384 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Rectifier Operation Inhibit-Ext 10385 — 1 Active on Alarm Deprecated System Fan Failure - Redundant 10386 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Multiple Fan Failure 10387 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Auto Restart In Progress 10388 — 1 Active on Alarm SCC, SMS Automatic Restart Failed 10389 — 1 Active on Alarm SCC, SMS Fuse Failure 10390 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS System Breaker(s) Open Failure 10391 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS System Breaker(s) Close Failure 10392 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Input Filter Cycle Lock 10393 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Service Code Active 10394 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS LBS Inhibited 10396 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 304 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-76 Liebert NXL™—60Hz, UL version (Model 40)—Status and Coil (continued) Status Coil # of Bits Notes NXL Type Controls Reset Required 10397 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Battery Test Failed 10398 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Auto Restart Inhibited - Ext 10399 — 1 Active on Alarm SCC, SMS Battery Test Inhibited 10400 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Data Label Battery Equalize 10401 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Backfeed Breaker Open 10402 — 1 Active on Alarm SCC, 1+N, 1+1, SMS On Generator 10403 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Power Supply Failure 10404 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Battery Ground Fault 10405 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Charging Error 10406 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Input Power Problem 10407 — 1 Active on Alarm N+1, 1+N, 1+1, SMS System Input Current Limit 10408 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Internal Communications Failure 10409 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS System Controller Error 10410 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS 10510 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Parallel Comm Warning 10521 — 1 Active on Alarm SCC, N+1, 1+N, 1+1 System Comm Fail 10522 — 1 Active on Alarm SCC, N+1, 1+N, 1+1 Loss of Redundancy 10523 — 1 Active on Alarm SCC, 1+N, 1+1 Output Output Of/Uf MultiModule BPSS Startup Inhibit 10524 — 1 Active on Alarm Deprecated MMS Transfer Inhibit 10525 — 1 Active on Alarm SCC, 1+N, 1+1 MMS Retransfer Inhibit 10526 — 1 Active on Alarm SCC, 1+N, 1+1 MMS Loss of Sync Pulse 10527 — 1 Active on Alarm Deprecated MMS Overload 10528 — 1 Active on Alarm SCC MMS On Battery 10529 — 1 Active on Alarm SCC, 1+N, 1+1 MMS Low Battery Warning 10530 — 1 Active on Alarm SCC, 1+N, 1+1 MMS Module Alarm Active 10531 — 1 Active on Alarm SCC MMS Sharing Calib Active 10532 — 1 Active on Alarm SCC 10543 — 1 Active on Alarm SCC, N+1, 1+N, 1+1 ECO Mode Active 10554 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS ECO Mode Suspended 10555 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS Excess ECO Suspends 10556 — 1 Active on Alarm SCC, N+1, 1+N, 1+1, SMS LBS Active - Master 10567 — 1 Active on Alarm SCC, 1+N, 1+1, SMS LBS Active - Slave 10568 — 1 Active on Alarm SCC, 1+N, 1+1, SMS Intelligent Paralleling Module In Standby - Intelligent Paralleling ECO Mode System EMO Shutdown 10575 — 1 Active on Alarm SMS, 1+N, N+1, SCC Cont Tie Active 10576 — 1 Active on Alarm SMS, 1+N, N+1, SCC User kWh Reset 10577 — 1 Active on Alarm SMS, 1+N, N+1, SCC Peak kW Reset 10578 — 1 Active on Alarm SMS, 1+N, N+1, SCC 10580 — 1 Active on Alarm SCC, SMS, 1+N, N+1 10590 — 1 Active on Alarm SMS, 1+N, N+1, SCC Environment Outlet Air Overtemperature Limit Service Reminder Service Required 305 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types System Date and Time 30005 — 2 — Masks: Year 0xFFFF 0000 Mon 0x0000 FF00 Day 0x0000 00FF SCC, N+1, 1+N, 1+1, SMS System Date and Time 30007 — 2 — Masks: Hour 0xFF00 0000 Min 0x00FF 0000 Sec 0x0000 FF00 SCC, N+1, 1+N, 1+1, SMS Output Apparent Power Rating 30021 — 2 — kVA SCC, N+1, 1+N, 1+1, SMS System Input Nominal Voltage 30027 — 1 — VAC SCC, N+1, 1+N, 1+1, SMS System Output Nominal Voltage 30028 — 1 — VAC SCC, N+1, 1+N, 1+1, SMS Bypass Nominal Voltage 30029 — 1 — VAC SCC, 1+N, 1+1, SMS System Input Nominal Frequency 30031 — 1 10 Hz SCC, N+1, 1+N, 1+1, SMS System Output Nominal Frequency 30032 — 1 10 Hz SCC, N+1, 1+N, 1+1, SMS System Output Apparent Power 30102 — 2 — kVA N+1, 1+N, 1+1, SMS System Output Power 30104 — 2 — kW N+1, 1+N, 1+1, SMS System Input Frequency 30107 — 1 10 Hz N+1, 1+N, 1+1, SMS System Output Frequency 30108 — 1 10 Hz N+1, 1+N, 1+1, SMS Bypass Input Frequency 30109 — 1 10 Hz SCC, 1+N, 1+1, SMS Battery Volts at Main Disconnect 30113 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Time Remaining 30115 — 1 — min N+1, 1+N, 1+1, SMS Battery Percentage Charge 30116 — 1 — — N+1, 1+N, 1+1, SMS Inlet Air Temperature 30119 — 1 — deg C SCC, N+1, 1+N, 1+1, SMS System Input RMS A-B 30151 — 1 — VAC N+1, 1+N, 1+1, SMS System Input RMS Current Phase A 30154 — 1 — A AC N+1, 1+N, 1+1, SMS Bypass Input Voltage RMS A-B 30157 — 1 — VAC SCC, 1+N, 1+1, SMS System Output Voltage RMS A-B 30161 — 1 — VAC N+1, 1+N, 1+1, SMS If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 306 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types System Output Voltage RMS A-N 30162 — 1 — VAC N+1, 1+N, 1+1, SMS System Output RMS Current Phs A 30164 — 1 — A AC N+1, 1+N, 1+1, SMS System Output Pct Power Phase A 30165 — 1 — % N+1, 1+N, 1+1, SMS System Output Power Factor Phs A 30166 — 1 100 — N+1, 1+N, 1+1, SMS System Input RMS B-C 30201 — 1 — VAC N+1, 1+N, 1+1, SMS System Input RMS Current Phase B 30204 — 1 — A AC N+1, 1+N, 1+1, SMS Bypass Input Voltage RMS B-C 30207 — 1 — VAC SCC, 1+N, 1+1, SMS System Output Voltage RMS B-C 30211 — 1 — VAC N+1, 1+N, 1+1, SMS System Output Voltage RMS B-N 30212 — 1 — VAC N+1, 1+N, 1+1, SMS System Output RMS Current Phs B 30214 — 1 — A AC N+1, 1+N, 1+1, SMS System Output Pct Power Phase B 30215 — 1 — % N+1, 1+N, 1+1, SMS System Output Power Factor Phs B 30216 — 1 100 — N+1, 1+N, 1+1, SMS System Input RMS C-A 30251 — 1 — VAC N+1, 1+N, 1+1, SMS System Input RMS Current Phase C 30254 — 1 — A AC N+1, 1+N, 1+1, SMS Bypass Input Voltage RMS C-A 30257 — 1 — VAC SCC, 1+N, 1+1, SMS System Output Voltage RMS C-A 30261 — 1 — VAC N+1, 1+N, 1+1, SMS System Output Voltage RMS C-N 30262 — 1 — VAC N+1, 1+N, 1+1, SMS System Output RMS Current Phs C 30264 — 1 — A AC N+1, 1+N, 1+1, SMS System Output Pct Power Phase C 30265 — 1 — % N+1, 1+N, 1+1, SMS System Output Power Factor Phs C 30266 — 1 100 — N+1, 1+N, 1+1, SMS Battery Discharge Time 30309 — 1 — sec N+1, 1+N, 1+1, SMS Battery Amp-Hours Consumed This Discharge 30310 — 1 — AH N+1, 1+N, 1+1, SMS Input Qualification Status 30312 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High N+1, 1+N, 1+1, SMS Bypass Sync Phase Difference 30313 — 1 — deg SCC, 1+N, 1+1, SMS Bypass SS Overload Time Remain 30314 — 1 — sec SCC, 1+N, 1+1, SMS If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 307 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types Bypass Qualification Status 30315 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High SCC, 1+N, 1+1, SMS Battery Total Discharge Time 30316 — 1 — hr N+1, 1+N, 1+1, SMS Battery Discharge Power 30317 — 1 — W N+1, 1+N, 1+1, SMS Battery Last Discharge Date 30318 — 2 — Masks: Year 0xFFFF 0000 Mon 0x0000 FF00 Day 0x0000 00FF N+1, 1+N, 1+1, SMS Battery Last Discharge Date 30320 — 2 — Masks: Hour 0xFF00 0000 Min 0x00FF 0000 Sec 0x0000 FF00 N+1, 1+N, 1+1, SMS Battery Commission Date 30322 — 2 — Masks: Year 0xFFFF 0000 Mon 0x0000 FF00 Day 0x0000 00FF N+1, 1+N, 1+1, SMS Battery Commission Date 30324 — 2 — Masks: Hour 0xFF00 0000 Min 0x00FF 0000 Sec 0x0000 FF00 N+1, 1+N, 1+1, SMS DC Bus Voltage 30326 — 1 — VDC N+1, 1+N, 1+1, SMS DC Bus Current 30327 — 1 — A DC N+1, 1+N, 1+1, SMS DC Bus Qualification Status 30328 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High N+1, 1+N, 1+1, SMS System Output Pct Pwr (VA) Phs A 30329 — 1 — % N+1, 1+N, 1+1, SMS System Output Pct Pwr (VA) Phs B 30330 — 1 — % N+1, 1+N, 1+1, SMS System Output Pct Pwr (VA) Phs C 30331 — 1 — % N+1, 1+N, 1+1, SMS Output Qualification Status 30332 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High N+1, 1+N, 1+1, SMS Inverter Overload Time Remaining 30333 — 1 — sec N+1, 1+N, 1+1, SMS Inverter Output Qualification Status 30334 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High N+1, 1+N, 1+1, SMS Total System Operating Time 30335 — 2 — hr SCC, N+1, 1+N, 1+1, SMS — 0 = 6 Pulse 1 = 12 Pulse 2 = 18 Pulse 3 = 24 Pulse N+1, 1+N, 1+1, SMS Rectifier Pulse Count 30337 — 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 308 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types Rectifier Input Passive Filter 30338 — 1 — 0 = Not Installed 1 = Installed N+1, 1+N, 1+1, SMS Rectifier Passive Filter Switch 30339 — 1 — 0 = Not Installed 1 = Installed N+1, 1+N, 1+1, SMS Rectifier Active Filter 30340 — 1 — 0 = Not Installed 1 = Installed N+1, 1+N, 1+1, SMS Rectifier Status 30341 — 1 — 0 = off 1 = on N+1, 1+N, 1+1, SMS — 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation SCC, N+1, 1+N, 1+1, SMS — 0 = Single Module System 1 = Module (1 + 1) 2 = Module (1 + N) 3 = Module (N + 1) 4 = System Control Cabinet 5 = Main Static Switch SCC, N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS System Status UPS Module Type 30342 30343 — — 1 1 Static Switch Type 30344 — 1 — 0 = Not Applicable 1 = Continuous Duty 2 = Momentary Duty System Input Power Source 30345 — 1 — 0 = None 1 = Utility (mains) 2 = Generator SCC, N+1, 1+N, 1+1, SMS Output Real Power Rating 30346 — 2 — kW SCC, N+1, 1+N, 1+1, SMS Input Isolation Transformer 30348 — 1 — 0 = Not Installed 1 = Installed SCC, N+1, 1+N, 1+1, SMS System Output Maximum Amp Rating 30350 — 1 — A AC SCC, 1+N, 1+1 SCC, N+1, 1+N, 1+1, SMS Output Wire Configuration 30353 — 1 — 0 = Two Wire (single phase + return) 1 = Two Wire (2 phase, no neutral) 2 = Three Wire (2 phase + neutral) 3 = Three Wire (3-phase, no neutral) 4 = Four Wire (3 phases + neutral) Battery Cell Count - Lead Acid 30354 — 1 — — SCC, N+1, 1+N, 1+1, SMS Battery Cell Count-Nickel Cadmium 30355 — 1 — — SCC, N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS UPS System Output Source 30356 — 1 — 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass Static Bypass Switch 30357 — 1 — 0 = off 1 = on If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 309 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types Battery Volts for Cabinet 1 30358 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Volts for Cabinet 2 30359 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Volts for Cabinet 3 30360 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Volts for Cabinet 4 30361 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Volts for Cabinet 5 30362 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Volts for Cabinet 6 30363 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Volts for Cabinet 7 30364 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Volts for Cabinet 8 30365 — 1 — VDC N+1, 1+N, 1+1, SMS Battery Temperature for Cabinet 1 30366 — 1 — deg C N+1, 1+N, 1+1, SMS Battery Temperature for Cabinet 2 30367 — 1 — deg C N+1, 1+N, 1+1, SMS Battery Temperature for Cabinet 3 30368 — 1 — deg C N+1, 1+N, 1+1, SMS Battery Temperature for Cabinet 4 30369 — 1 — deg C N+1, 1+N, 1+1, SMS Battery Temperature for Cabinet 5 30370 — 1 — deg C N+1, 1+N, 1+1, SMS Battery Temperature for Cabinet 6 30371 — 1 — deg C N+1, 1+N, 1+1, SMS Battery Temperature for Cabinet 7 30372 — 1 — deg C N+1, 1+N, 1+1, SMS Battery Temperature for Cabinet 8 30373 — 1 — deg C N+1, 1+N, 1+1, SMS Backfeed Breaker 30374 — 1 — 0 = Open 1 = Close 2 = Not Installed N+1, 1+N, 1+1, SMS SBS Load Disconnect 30375 — 1 — 0 = Open 1 = Close 2 = Not Installed Deprecated Input Breaker (CB1/RIB) 30376 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, N+1, 1+N, 1+1, SMS Trap Filter Disconnect 30377 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, N+1, 1+N, 1+1, SMS Output Breaker (CB2/IOB) 30378 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, N+1, 1+N, 1+1, SMS Internal Bypass Breaker (CB3) 30379 — 1 — 0 = Open 1 = Close 2 = Not Installed Deprecated Bypass Isolation Breaker (BIB) 30380 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, 1+N, 1+1, SMS If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 310 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types Rectifier Feed Breaker (RFB) 30381 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS Maintenance Bypass Breaker (MBB) 30382 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, 1+N, 1+1, SMS Maintenance Isolation Breaker (MIB) 30383 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, 1+N, 1+1, SMS Output Series Static Switch 30384 — 1 — 0 = Open 1 = Close 2 = Not Installed LEU/LAP only Module Output Breaker (MOB) 30385 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, 1+N, 1+1 Battery Amp-Hours Consumed 30386 — 2 — AH N+1, 1+N, 1+1, SMS Auto Retransfer Time Remaining 30388 — 1 — sec SCC, 1+N, 1+1, SMS Inverter On/Off State 30389 — 1 — 0 = off 1 = on SCC, N+1, 1+N, 1+1, SMS UPS Battery Status 30390 — 1 — 1 = Unknown 2 = Normal 3 = Low 4 = Depleted N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS UPS Output Source 30391 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer System Date and Time 39998 49998 2 — — SCC, N+1, 1+N, 1+1, SMS Total kW Hours Saved 30491 — 2 — Units : kWH SCC, N+1, 1+N, 1+1, SMS System Date and Time 39998 49998 2 — Secs since Epoch(UTC) SCC, N+1, 1+N, 1+1, SMS Environment If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 311 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs NXL Types Scale Units / Notes — 0 = Two Wire (single phase + return) 1 = Two Wire (2 phase, no neutral) 2 = Three Wire (2 phase + neutral) 3 = Three Wire (3 phase, no neutral) 4 = Four Wire (3 phases + neutral) SCC, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS System Bypass Input Wire Configuration 30496 — 1 Configuration Description 30497 — 1 — 0 = Single Module System 33 1 = Single Module System 34 2 = Single Module System 44 3 = 1+1 33 4 = 1+1 34 5 = 1+1 44 6 = 1+N 33 7 = 1+N 34 8 = 1+N 44 9 = N+1 33 10 = N+1 34 11 = N+1 44 12 = SCC w/Continuous Duty SS 33 13 = SCC w/ Continuous Duty SS 44 14 = SCC w/ Momentary Duty SS 15 = Main Static Switch System Accumulated Energy 30810 40810 2 10 Units: kWH SCC, 1+N, N+1 Module Accumulated Energy 30812 40812 10 Units: kWH SMS, 1+N, N+1, SCC Output kWh Reset Timestamp 30814 — — Secs since Epoch(UTC) SMS, 1+N, N+1, SCC Output Peak kW Demand 30816 — — Units: kWH SMS, 1+N, N+1, SCC Output Peak kW Demand Hist 30817 — — Units: kW SMS, 1+N, N+1, SCC SMS, 1+N, N+1, SCC 2 1 Peak kW Demand Period 30818 — 1 — 1 = Hourly 2 = Daily 3 = Weekly 4 = Monthly 5 = Yearly Peak kW Demand Timestamp 30819 — 2 — Secs since Epoch(UTC) SMS, 1+N, N+1, SCC 30501 — 1 — — SCC, 1+N, 1+1, SMS Ratings System UPS Module Count If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 312 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types MultiModule Multi-module System Output Voltage RMS A-B 30505 — 1 — Units : VAC 1+N, SCC Multi-module System Output Voltage RMS B-C 30506 — 1 — Units : VAC 1+N, SCC Multi-module System Output Voltage RMS C-A 30507 — 1 — Units : VAC 1+N, SCC Multi-module System Output Voltage RMS A-N 30508 — 1 — Units : VAC 1+N, SCC Multi-module System Output Voltage RMS B-N 30509 — 1 — Units : VAC 1+N, SCC Multi-module System Output Voltage RMS C-N 30510 — 1 — Units : VAC 1+N, SCC Sum of MMS Output RMS Currents for Phase A 30511 — 1 — Units : A AC 1+N, SCC Sum of MMS Output RMS Currents for Phase B 30512 — 1 — Units : A AC 1+N, SCC Sum of MMS Output RMS Currents for Phase C 30513 — 1 — Units : A AC 1+N, SCC MMS Output Frequency 30514 — 1 10 Units : Hz 1+N, SCC MMS Output Power 30515 — 1 — Units : kW 1+N, SCC MMS Output Apparent Power 30516 — 1 — Units : kVA 1+N, SCC MMS Output Power Factor Phase A 30517 — 1 100 — 1+N, SCC MMS Output Power Factor Phase B 30518 — 1 100 — 1+N, SCC MMS Output Power Factor Phase C 30519 — 1 100 — 1+N, SCC MMS Output Pct Power Phase A 30520 — 1 — Units : % 1+N, SCC MMS Output Pct Power Phase B 30521 — 1 — Units : % 1+N, SCC MMS Output Pct Power Phase C 30522 — 1 — Units : % 1+N, SCC MMS Output Pct Apparent Pwr (kVA) Phase A 30523 — 1 — Units : % 1+N, SCC MMS Output Pct Apparent Pwr (kVA) Phase B 30524 — 1 — Units : % 1+N, SCC MMS Output Pct Apparent Pwr (kVA) Phase C 30525 — 1 — Units : % 1+N, SCC Number of Redundant Modules 30526 — 1 — — 1+N, SCC MMS Module Number 30527 — 1 — — 1+N, SCC Number of Modules in an MMS 30528 — 1 — — 1+N, SCC Module Output Breaker for Module 1 (MOB1) 30529 — 1 — 0 = Open 1 = Close 2 = Not Installed 1+N, SCC Module Output Breaker for Module 2 (MOB2) 30530 — 1 — 0 = Open 1 = Close 2 = Not Installed 1+N, SCC Module Output Breaker for Module 3 (MOB3) 30531 — 1 — 0 = Open 1 = Close 2 = Not Installed 1+N, SCC If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 313 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types Module Output Breaker for Module 4 (MOB4) 30532 — 1 — 0 = Open 1 = Close 2 = Not Installed 1+N, SCC Module Output Breaker for Module 5 (MOB5) 30533 — 1 — 0 = Open 1 = Close 2 = Not Installed 1+N, SCC Module Output Breaker for Module 6 (MOB6) 30534 — 1 — 0 = Open 1 = Close 2 = Not Installed 1+N, SCC Module Output Breaker for Module 7 (MOB7) 30535 — 1 — 0 = Open 1 = Close 2 = Not Installed 1+N, SCC Module Output Breaker for Module 8 (MOB8) 30536 — 1 — 0 = Open 1 = Close 2 = Not Installed 1+N, SCC Bypass Isolation Breaker for Module 1 (BIB1) 30537 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for Module 2 (BIB2) 30538 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for Module 3 (BIB3) 30539 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for Module 4 (BIB4) 30540 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for Module 5 (BIB5) 30541 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for Module 6 (BIB6) 30542 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for Module 7 (BIB7) 30543 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N Bypass Isolation Breaker for Module 8 (BIB8) 30544 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, SMS, 1+N System Output Breaker (UOB) 30545 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC System Load Bank Breaker (LBB) 30546 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC System Isolation Output Breaker (IOB) 30547 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC SCC Event Summary 30548 — 1 — 0 = None 1 = Alarm 2 = Fault SCC — 1 = Unknown 2 = Normal 3 = Low 4 = Depleted SCC, N+1, 1+N, MMS UPS Battery Status 30549 — 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 314 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs NXL Types Scale Units / Notes SCC, 1+N, 30550 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer MMS Inter-Module Comm Status 30554 — 1 — 0 = Failed 1 = Normal 1+N, SCC MMS Event Summary 30555 — 1 — 0 = None 1 = Alarm 2 = Fault 1+N, SCC MMS Module Inverter Status 30556 — 1 — 0 = off 1 = on SCC, 1+N — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High 1+N, SCC 1+N, SCC MMS UPS Output Source ModuleList 1 MMS Module Output Voltage Status 30557 — 1 MMS Module Output Source 30558 — 1 — 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass MMS Module Total kW Output 30559 — 1 — Units : kW SCC MMS Module Total kVA Output 30560 — 1 — Units : kVA SCC MMS Module DC Bus Voltage 30561 — 1 — Units : VDC SCC MMS Module Battery Current 30562 — 1 — Units : A DC SCC MMS Module Battery Time Remaining 30563 — 1 — Units : min SCC MMS Inter-Module Comm Status 30567 — 1 — 0 = Failed 1 = Normal 1+N, SCC MMS Event Summary 30568 — 1 — 0 = None 1 = Alarm 2 = Fault 1+N, SCC MMS Module Inverter Status 30569 — 1 — 0 = off 1 = on 1+N, SCC MMS Module Output Voltage Status 30570 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High 1+N, SCC MMS Module Output Source 30571 — 1 — 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass 1+N, SCC MMS Module Total kW Output 30572 — 1 — Units : kW SCC MMS Module Total kVA Output 30573 — 1 — Units : kVA SCC MMS Module DC Bus Voltage 30574 — 1 — Units : VDC SCC MMS Module Battery Current 30575 — 1 — Units : A DC SCC MMS Module Battery Time Remaining 30576 — 1 — Units : min SCC ModuleList 2 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 315 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types ModuleList 8 MMS Inter-Module Comm Status 30645 — 1 — 0 = Failed 1 = Normal 1+N, SCC MMS Event Summary 30646 — 1 — 0 = None 1 = Alarm 2 = Fault 1+N, SCC MMS Module Inverter Status 30647 — 1 — 0 = off 1 = on 1+N, SCC — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High 1+N, SCC 1+N, SCC MMS Module Output Voltage Status 30648 — 1 MMS Module Output Source 30649 — 1 — 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass MMS Module Total kW Output 30650 — 1 — Units : kW SCC MMS Module Total kVA Output 30651 — 1 — Units : kVA SCC MMS Module DC Bus Voltage 30652 — 1 — Units : VDC SCC MMS Module Battery Current 30653 — 1 — Units : A DC SCC MMS Module Battery Time Remaining 30654 — 1 — Units : min SCC Intelligent Parallel Operation State 30658 — 1 — 0 = disabled 1 = enabled N+1, 1+N, SCC Intelligent Parallel Mode 30659 — 1 — 1 = Disconnect (More Efficient) N+1, 1+N, SCC Intelligent Paralleling Shutdown Delay 30660 — 1 — Units : min N+1, 1+N, SCC Intelligent Parallel Minimum Redundancy 30661 — 1 — — N+1, 1+N, SCC Intelligent Parallel Maximum Time in Standby 30662 — 1 — Units : day N+1, 1+N, SCC ECO Mode Operation State 30666 40666 1 — 0 = disabled 1 = enabled SMS, 1+N, SCC Continuous Operation - ECO Mode 30667 — 1 — 0 = disabled 1 = enabled SMS, 1+N, SCC Maximum Auto Suspensions - ECO Mode 30668 — 1 — — SMS, 1+N, SCC Restart Delay - ECO Mode 30669 — 1 — Units : min SMS, 1+N, SCC Time Remaining - ECO Mode 30670 — 1 — Units : min SMS, 1+N, SCC Intelligent Paralleling ECO Mode If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 316 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-77 Liebert NXL™—60Hz, UL version (Model 40)—Input and Holding (continued) Data Label Input Holding # of Register Register Regs Scale Units / Notes NXL Types EcoModeSchedule 1 Schedule Operation State - ECO Mode 30674 — 1 — 0 = disabled 1 = enabled SMS, 1+N, SCC Schedule Action - ECO Mode 30675 — 1 — 0 = stop 1 = start SMS, 1+N, SCC SMS, 1+N, SCC Schedule Day of Week - ECO Mode 30676 — 1 — 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Schedule Hour - ECO Mode 30677 — 1 — Units : hr SMS, 1+N, SCC Schedule Minute - ECO Mode 30678 — 1 — Units : min SMS, 1+N, SCC Schedule Operation State - ECO Mode 30682 — 1 — 0 = disabled 1 = enabled SMS, 1+N, SCC Schedule Action - ECO Mode 30683 — 1 — 0 = stop 1 = start SMS, 1+N, SCC SMS, 1+N, SCC EcoModeSchedule 2 Schedule Day of Week - ECO Mode 30684 — 1 — 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Schedule Hour - ECO Mode 30685 — 1 — Units : hr SMS, 1+N, SCC Schedule Minute - ECO Mode 30686 — 1 — Units : min SMS, 1+N, SCC Schedule Operation State - ECO Mode 30794 — 1 — 0 = disabled 1 = enabled SMS, 1+N, SCC Schedule Action - ECO Mode 30795 — 1 — 0 = stop 1 = start SMS, 1+N, SCC SMS, 1+N, SCC EcoModeSchedule 16 Schedule Day of Week - ECO Mode 30796 — 1 — 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Schedule Hour - ECO Mode 30797 — 1 — Units : hr SMS, 1+N, SCC Schedule Minute - ECO Mode 30798 — 1 — Units : min SMS, 1+N, SCC 30821 — 1 — — SMS, 1+N, N+1 Battery Total Number of Battery Discharges If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 317 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary Data Label Data Description Auto Restart In Progress Auto restart is in progress Auto Restart Inhibited - Ext Auto restart inhibited due to an external signal Auto Retransfer Time Remaining Time remaining before an inverter overload or inverter fault can be cleared and auto retransfer from the bypass to the inverter can take place Automatic Restart Failed Automatic restart failed Backfeed Breaker Open The backfeed breaker is in the open position Backfeed Breaker Backfeed breaker Battery - External Monitor 1 External battery monitor 1 - battery maintenance required Battery - External Monitor 2 External battery monitor 2 - battery maintenance required Battery Amp-Hours Consumed This Discharge Battery amp-hours withdrawn this discharge. Battery Amp-Hours Consumed Cumulative battery amp-hours withdrawn over the life of the battery Battery Capacity Low Battery capacity is low Battery Cell Count - Lead Acid Battery cell count - lead acid Battery Cell Count-Nickel Cadmium Battery cell count - nickel cadmium Battery Charging Inhibited Battery charging is inhibited due to an external inhibit signal Battery Charging Reduced-Extrnl Using a reduced battery charging algorithm due to an external signal Battery Circuit Breaker 1 Open Battery circuit breaker 1 is open Battery Circuit Breaker 2 Open Battery circuit breaker 2 is open Battery Circuit Breaker 3 Open Battery circuit breaker 3 is open Battery Circuit Breaker 4 Open Battery circuit breaker 4 is open Battery Circuit Breaker 5 Open Battery circuit breaker 5 is open Battery Circuit Breaker 6 Open Battery circuit breaker 6 is open Battery Circuit Breaker 7 Open Battery circuit breaker 7 is open Battery Circuit Breaker 8 Open Battery circuit breaker 8 is open Battery Commission Date Date and time when battery placed into service Battery Discharge Power Instantaneous battery power while discharging Battery Discharge Time The time on battery operation for this discharge Battery Discharging The battery is discharging Battery Equalize The rectifier output voltage is increased to equalize the battery voltage level. Battery Ground Fault Battery system ground fault amperage exceeds the threshold Battery Last Discharge Date The date and time of the last battery discharge Battery Low Shutdown Battery disconnect due to end-of-discharge. Battery Low The calculated battery time remaining has reached the low battery threshold Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Percentage Charge The percentage of battery charge Battery Self Test Battery self test is in progress Battery Temperature for Cabinet The battery temperature for a cabinet Battery Temperature Imbalance Excessive temperature differences between battery sensors detected Battery Temperature Sensor Fault A battery temperature sensor fault has been detected Battery Test Failed Battery test failed Battery Test Inhibited Automatic (scheduled) battery tests are inhibited Battery Time Remaining The calculated available time on battery Battery Total Discharge Time The cumulative battery discharge time Battery Volts at Main Disconnect The voltage between the positive and the negative battery terminals of the common battery disconnect Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 318 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary (continued) Data Label Data Description Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Bypass - Excess Auto Retransfers The number of auto retransfers, from bypass to inverter, has exceeded the maximum for a specified time interval Bypass - Manual Rexfr Inhibited Manual transfer from bypass to inverter is inhibited. Bypass - Manual Xfr Inhibited Manual transfer from inverter to bypass is inhibited. Bypass Auto Retransfer Failed After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed Bypass Auto Transfer Failed An automatic transfer to static bypass failed Bypass Excessive Pulse Parallel The system has performed too many pulse parallel operations within a specified time interval Bypass Frequency Error The bypass frequency is outside the inverter synchronization limits Bypass Input Frequency The bypass input frequency Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B Bypass Input Voltage RMS B-C The bypass input RMS voltage between phases B and C Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A Bypass Isolation Breaker (BIB) Bypass isolation breaker (BIB) Bypass Nominal Voltage Bypass nominal (or rated) voltage Bypass Not Available A problem associated with the bypass has been detected Bypass Overload Phase A An overload exists on output phase A while operating on the bypass Bypass Overload Phase B An overload exists on output phase B while operating on the bypass Bypass Overload Phase C An overload exists on output phase C while operating on the bypass Bypass Qualification Status bypass qualification status Bypass SS Overload Time Remain The calculated time remaining before bypass static switch shutdown due to the present overload condition Bypass Static Switch Off Extrnl Bypass static switch is off due to the state of an external signal Bypass Static Switch Overload Bypass off due to static switch overload Bypass Static Switch Unavailable The static bypass switch is off, and unable to operate Bypass Sync Phase Difference The phase angle difference between the inverter output and bypass source Controls Reset Required A controls reset is required due to one or more critical settings changing DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value DC Bus Ground Fault - Negative A ground fault has been detected on the negative DC Bus link DC Bus Ground Fault - Positive A ground fault has been detected on the positive DC Bus link DC Bus Qualification Status DC bus qualification status DC Bus Voltage The voltage between the positive and negative terminals of the DC bus at the battery input Equipment Over Temperature Equipment over temperature summary event Equipment Temperature Sensor Fail One or more temperature sensors report a temperature outside of the range of expected operation. Fuse Failure A summary event indicating one or more fuse failures Inlet Air Over Temperature The inlet air exceeds the maximum temperature threshold Inlet Air Temperature The temperature of the inlet air Input Breaker (CB1/RIB) Input breaker (CB1/RIB) Input Contact 01 The external input contact 1 Input Contact 02 The external input contact 2 Input Contact 03 The external input contact 3 Input Contact 04 The external input contact 4 319 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary (continued) Data Label Data Description Input Contact 05 The external input contact 5 Input Contact 06 The external input contact 6 Input Contact 07 The external input contact 7 Input Contact 08 The external input contact 8 Input Contact 09 The external input contact 9 Input Contact 10 The external input contact 10 Input Contact 11 The external input contact 11 Input Contact 12 The external input contact 12 Input Contact 13 The external input contact 13 Input Contact 14 The external input contact 14 Input Contact 15 The external input contact 15 Input Contact 16 The external input contact 16 Input Filter Cycle Lock The input filter disconnect is open due to exceeding the maximum number of cycles. Input Isolation Transformer Input isolation transformer Input Qualification Status input qualification status Internal Bypass Breaker (CB3) Internal bypass breaker (CB3) Internal Communications Failure The control has detected a communication failure of a component on the internal communication bus Inverter Failure Inverter failure - inverter output is off Inverter Inhibit - External Restart of the inverter is inhibited by an external signal Inverter Off - External Inverter is off (operation is inhibited) due to external signal state Inverter On/Off State inverter on/off state Inverter Output Qualification Status inverter output qualification status Inverter Overload Phase A Inverter is operating with an overload on phase A Inverter Overload Phase B Inverter is operating with an overload on phase B Inverter Overload Phase C Inverter is operating with an overload on phase C Inverter Overload Time Remaining The calculated time remaining before inverter shutdown Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload Inverter Static Switch SCR Short The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR) LBS Inhibited The system has detected that conditions to perform Load Bus Sync are not satisfied Leading Power Factor The leading output Power Factor has fallen below a specified value Main Battery Disconnect Open Main battery disconnect is open Main Controller Fault A Main Controller fault has been detected. Maintenance Bypass Breaker (MBB) Maintenance bypass breaker (MBB) Maintenance Isolation Breaker (MIB) Maintenance isolation breaker (MIB) Module Output Breaker (MOB) Module output breaker (MOB) Multiple Fan Failure Multiple fan failure On Generator A generator is supplying the power to the system Output Amp Over User Limit-Phs A The phase A output has exceeded the user amperage threshold Output Amp Over User Limit-Phs B The phase B output has exceeded the user amperage threshold Output Amp Over User Limit-Phs C The phase C output has exceeded the user amperage threshold Output Apparent Power Rating Output apparent power rating Output Breaker (CB2/IOB) Output breaker (CB2/IOB) Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Output Qualification Status output qualification status Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 320 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary (continued) Data Label Data Description Output Real Power Rating Output real power rating Output Series Static Switch output series static switch Output Wire Configuration Output wire configuration Power Supply Failure Power supply failure Rectifier Active Filter Rectifier input active filter configuration Rectifier Failure Rectifier failure - rectifier is off Rectifier Feed Breaker (RFB) Rectifier feed breaker (RFB) Rectifier Input Passive Filter Rectifier input passive filter configuration Rectifier Operation Inhibit-Ext The operation of the rectifier is inhibited by an external signal Rectifier Passive Filter Switch Rectifier input passive filter switch configuration Rectifier Pulse Count Rectifier pulse count per cycle configuration Rectifier Status rectifier status SBS Load Disconnect SBS load disconnect Service Code Active Service code is running Static Bypass Switch Static Bypass Switch state - On/Off Static Switch Type Static switch type configuration System Breaker(s) Close Failure One or more breakers in the system failed to close System Breaker(s) Open Failure One or more breakers in the system failed to open System Controller Error System controller internal error System Date and Time The system date and time System Fan Failure - Redundant Redundant system fan failure System Input Current Imbalance System Input Currents are Imbalanced System Input Current Limit The RMS input current has reached the input current limit threshold System Input Frequency The system input frequency System Input Nominal Frequency The nominal (or rated) system input frequency System Input Nominal Voltage The nominal (or rated) system input voltage System Input Phs Rotation Error The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C) System Input Power Problem The input is not qualified to provide power to the system System Input Power Source System input power source System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power The sum total apparent power of all system output phases System Output Fault A fault has been detected in the system output System Output Frequency The system output frequency System Output Low Power Factor The system output power factor is low, resulting in reduced output capacity System Output Maximum Amp Rating System output maximum amperage rating System Output Nominal Frequency The nominal (or rated) system output frequency System Output Nominal Voltage The nominal (or rated) system output voltage System Output Off The system output is off System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity 321 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-78 Liebert NXL™—60Hz, UL version (Model 40)—Glossary (continued) Data Label Data Description System Output Pct Pwr (VA) Phs A The system output apparent power on phase A as a percentage of the rated capacity System Output Pct Pwr (VA) Phs B The system output apparent power on phase B as a percentage of the rated capacity System Output Pct Pwr (VA) Phs C The system output apparent power on phase C as a percentage of the rated capacity System Output Power Factor Phs A The system output power factor of phase A System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power The sum total power of all system output phases System Output RMS Current Phs A The system output RMS current for Phase A System Output RMS Current Phs B The system output RMS current for Phase B System Output RMS Current Phs C The system output RMS current for Phase C System Output Voltage RMS A-B The system output RMS voltage between phases A and B System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral System Output Voltage RMS B-C The system output RMS voltage between phases B and C System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral System Output Voltage RMS C-A The system output RMS voltage between phases C and A System Output Voltage RMS C-N The system output RMS voltage between phases C and Neutral System Shutdown - EPO System shutdown due to Emergency Power Off (EPO) System Shutdown - REPO System shutdown due to Remote Emergency Power Off (REPO) System Status The operating status for the system Total System Operating Time The cumulative operation time of the unit Trap Filter Disconnect Trap filter disconnect UPS Battery Status UPS battery status UPS Module Type UPS module type UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source UPS System Output Source The UPS system's output power source Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 322 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-79 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil Status Data Description Coil Number of Bits Notes / Units Input System Input Power Problem 10001 — 1 Active on Alarm System Input Phs Rotation Error 10002 — 1 Active on Alarm System Input Current Limit 10003 — 1 Active on Alarm System Input Current Imbalance 10004 — 1 Active on Alarm Bypass Not Available 10015 — 1 Active on Alarm Bypass Overload Phase A 10016 — 1 Active on Alarm Bypass Overload Phase B 10017 — 1 Active on Alarm Bypass Overload Phase C 10018 — 1 Active on Alarm Bypass Auto Retransfer Failed 10019 — 1 Active on Alarm Bypass Static Switch Overload 10020 — 1 Active on Alarm Bypass Static Switch Unavailable 10021 — 1 Active on Alarm Bypass Auto Transfer Failed 10022 — 1 Active on Alarm Bypass Frequency Error 10023 — 1 Active on Alarm Bypass Bypass - Manual Rexfr Inhibited 10024 — 1 Active on Alarm Bypass - Manual Xfr Inhibited 10025 — 1 Active on Alarm Battery Automatic Test Inhibited 10036 — 1 Active on Alarm Battery Capacity Low 10037 — 1 Active on Alarm Battery Discharging 10038 — 1 Active on Alarm Battery Battery Temperature Imbalance 10039 — 1 Active on Alarm Battery Equalize 10040 — 1 Active on Alarm Battery Auto Test In Progress 10041 — 1 Active on Alarm Main Battery Disconnect Open 10042 — 1 Active on Alarm Battery Low 10043 — 1 Active on Alarm Battery Temperature Sensor Fault 10044 — 1 Active on Alarm Battery Circuit Breaker 1 Open 10045 — 1 Active on Alarm Battery Circuit Breaker 2 Open 10046 — 1 Active on Alarm Battery Circuit Breaker 3 Open 10047 — 1 Active on Alarm Battery Circuit Breaker 4 Open 10048 — 1 Active on Alarm Battery Circuit Breaker 5 Open 10049 — 1 Active on Alarm Battery Circuit Breaker 6 Open 10050 — 1 Active on Alarm Battery - External Monitor 1 10051 — 1 Active on Alarm Battery - External Monitor 2 10052 — 1 Active on Alarm Battery Ground Fault 10053 — 1 Active on Alarm Battery Over Temperature Limit 10054 — 1 Active on Alarm Battery Low Shutdown 10055 — 1 Active on Alarm Battery Over Temperature 10056 — 1 Active on Alarm Battery Test Failed 10057 — 1 Active on Alarm Unexpected Main Battery Disconnect Closure 10058 — 1 Active on Alarm Battery Over Voltage 10059 — 1 Active on Alarm Battery Fuse Fault 10060 — 1 Active on Alarm Main Battery Disconnect Forced To Unlock 10061 — 1 Active on Alarm Battery Test Manually Stopped 10062 — 1 Active on Alarm Battery Test Passed 10063 — 1 Active on Alarm 323 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-79 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil (continued) Status Coil Number of Bits Notes / Units 10074 — 1 Active on Alarm System Shutdown - EPO 10085 — 1 Active on Alarm System Shutdown - REPO 10086 — 1 Active on Alarm System Output Low Power Factor 10088 — 1 Active on Alarm Output Amp Over User Limit-Phs A 10089 — 1 Active on Alarm Data Description DC Bus DC Bus Low Fault Output Output Amp Over User Limit-Phs B 10090 — 1 Active on Alarm Output Amp Over User Limit-Phs C 10091 — 1 Active on Alarm System Output Fault 10092 — 1 Active on Alarm Output Of/Uf 10093 — 1 Active on Alarm Inverter Failure 10104 — 1 Active on Alarm Inverter Overload Phase A 10105 — 1 Active on Alarm Inverter Overload Phase B 10106 — 1 Active on Alarm Inverter Inverter Overload Phase C 10107 — 1 Active on Alarm Inverter Inhibit - External 10108 — 1 Active on Alarm Inverter Shutdown - Overload 10109 — 1 Active on Alarm Inverter Static Switch SCR Short 10110 — 1 Active on Alarm 10121 — 1 Active on Alarm Environment Inlet Air Over Temperature Outlet Air Overtemperature Limit 10122 — 1 Active on Alarm Equipment Temperature Sensor Fail 10123 — 1 Active on Alarm Input Contact 01 10134 — 1 Active on Alarm Input Contact 02 10135 — 1 Active on Alarm Input Contact 03 10136 — 1 Active on Alarm Input Contact 04 10137 — 1 Active on Alarm Input Contact 05 10138 — 1 Active on Alarm Input Contact 06 10139 — 1 Active on Alarm Input Contact 07 10140 — 1 Active on Alarm Input Contact 08 10141 — 1 Active on Alarm Input Contact 09 10142 — 1 Active on Alarm Input Contact 10 10143 — 1 Active on Alarm Input Contact 11 10144 — 1 Active on Alarm Input Contact 12 10145 — 1 Active on Alarm Input Contact 13 10146 — 1 Active on Alarm Input Contact 14 10147 — 1 Active on Alarm Input Contact 15 10148 — 1 Active on Alarm Input Contact 16 10149 — 1 Active on Alarm Rectifier Failure 10160 — 1 Active on Alarm Vdc Backfeed 10162 — 1 Active on Alarm Rectifier Configuration Change Request 10163 — 1 Active on Alarm External Input Signals Rectifier Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 324 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-79 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil (continued) Status Data Description Coil Number of Bits Notes / Units System System Fan Failure - Redundant 10174 — 1 Active on Alarm Multiple Fan Failure 10175 — 1 Active on Alarm Internal Communications Failure 10176 — 1 Active on Alarm UPS Output on Bypass 10177 — 1 Active on Alarm Output Load on Maint. Bypass 10178 — 1 Active on Alarm Backfeed Breaker Open 10179 — 1 Active on Alarm Auto Restart In Progress 10180 — 1 Active on Alarm Power Supply Failure 10181 — 1 Active on Alarm Auto Restart Inhibited - Ext 10183 — 1 Active on Alarm Automatic Restart Failed 10184 — 1 Active on Alarm Main Controller Fault 10185 — 1 Active on Alarm Fuse Failure 10186 — 1 Active on Alarm System Controller Error 10187 — 1 Active on Alarm System Breaker(s) Open Failure 10188 — 1 Active on Alarm System Breaker(s) Close Failure 10189 — 1 Active on Alarm Input Filter Cycle Lock 10190 — 1 Active on Alarm EMO Shutdown 10191 — 1 Active on Alarm Service Code Active 10192 — 1 Active on Alarm LBS Active 10193 — 1 Active on Alarm LBS Inhibited 10194 — 1 Active on Alarm Regeneration Active 10195 — 1 Active on Alarm Regeneration Operation Terminated 10196 — 1 Active on Alarm Regeneration Operation Failure 10197 — 1 Active on Alarm Leading Power Factor 10198 — 1 Active on Alarm Controls Reset Required 10199 — 1 Active on Alarm Loss of Redundancy 10212 — 1 Active on Alarm MMS Overload 10215 — 1 Active on Alarm MMS On Battery 10216 — 1 Active on Alarm MMS Module Alarm Active 10218 — 1 Active on Alarm Program Input Contact 01 10229 — 1 Active on Alarm Program Input Contact 02 10230 — 1 Active on Alarm Program Input Contact 03 10231 — 1 Active on Alarm Program Input Contact 04 10232 — 1 Active on Alarm Program Input Contact 05 10233 — 1 Active on Alarm Program Input Contact 06 10234 — 1 Active on Alarm Program Input Contact 07 10235 — 1 Active on Alarm Program Input Contact 08 10236 — 1 Active on Alarm Program Input Contact 09 10237 — 1 Active on Alarm Program Input Contact 10 10238 — 1 Active on Alarm Program Input Contact 11 10239 — 1 Active on Alarm Program Input Contact 12 10240 — 1 Active on Alarm MultiModule Program Input Signals 325 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-79 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Status and Coil (continued) Status Coil Number of Bits Notes / Units 10251 — 1 Active on Alarm ECO Mode Active 10262 — 1 Active on Alarm ECO Mode Suspended 10263 — 1 Active on Alarm Excess ECO Suspends 10264 — 1 Active on Alarm Data Description Intelligent Paralleling IP Inhibit ECO Mode Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 326 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding Input Holding # of Reg Scale Notes/Units System Input RMS A-B 30385 — 1 10 Units : VAC Uint16 System Input RMS B-C 30386 — 1 10 Units : VAC Uint16 System Input RMS C-A 30387 — 1 10 Units : VAC Uint16 System Input RMS Current Phase A 30388 — 1 — Units : A AC Uint16 System Input RMS Current Phase B 30389 — 1 — Units : A AC Uint16 System Input RMS Current Phase C 30390 — 1 — Units : A AC Uint16 System Input Frequency 30391 — 1 100 Units : Hz Uint16 Data Label Input 30392 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High Bypass Input Voltage RMS A-B 30403 — 1 10 Units : VAC Uint16 Bypass Input Voltage RMS B-C 30404 — 1 10 Units : VAC Uint16 Bypass Input Voltage RMS C-A 30405 — 1 10 Units : VAC Uint16 Bypass Input Frequency 30406 — 1 100 Units : Hz Uint16 Bypass Sync Phase Difference 30407 — 1 — Units : deg Int16 Bypass SS Overload Time Remain 30408 — 1 — Units : sec Uint16 Static Bypass Switch 30409 — 1 — 0 = off 1 = on Bypass Qualification Status 30410 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High Auto Retransfer Time Remaining 30411 — 1 — Units : sec Uint16 Battery Total Discharge Time 30422 — 1 — Units : hr Uint16 Battery Percentage Charge 30423 — 1 — Uint16 Battery Volts at Main Disconnect 30424 — 1 — Units : VDC Uint16 Battery Volts for Cabinet 1 30425 — 1 — Units : VDC Uint16 Battery Volts for Cabinet 2 30426 — 1 — Units : VDC Uint16 Battery Volts for Cabinet 3 30427 — 1 — Units : VDC Uint16 Input Qualification Status Bypass Battery If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 327 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Battery Volts for Cabinet 4 30428 — 1 — Units : VDC Uint16 Battery Volts for Cabinet 5 30429 — 1 — Units : VDC Uint16 Battery Volts for Cabinet 6 30430 — 1 — Units : VDC Uint16 Battery Temperature for Cabinet 30431 — 1 10 Units : deg C Int16 Battery Temperature for Cabinet 1 30432 — 1 10 Units : deg F Int16 Battery Temperature for Cabinet 2 30433 — 1 10 Units : deg C Int16 Battery Temperature for Cabinet 2 30434 — 1 10 Units : deg F Int16 Battery Temperature for Cabinet 3 30435 — 1 10 Units : deg C Int16 Battery Temperature for Cabinet 3 30436 — 1 10 Units : deg F Int16 Battery Temperature for Cabinet 4 30437 — 1 10 Units : deg C Int16 Battery Temperature for Cabinet 4 30438 — 1 10 Units : deg F Int16 Battery Temperature for Cabinet 5 30439 — 1 10 Units : deg C Int16 Battery Temperature for Cabinet 5 30440 — 1 10 Units : deg F Int16 Battery Temperature for Cabinet 6 30441 — 1 10 Units : deg C Int16 Battery Temperature for Cabinet 6 30442 — 1 10 Units : deg F Int16 Battery Amp-Hours Consumed This Discharge 30443 — 1 — Units : AH Uint16 Battery Time Remaining 30444 — 1 — Units : min Uint16 Battery Discharge Time 30445 — 1 — Units : sec Uint16 Battery Discharge Power 30446 — 1 — Units : W Uint16 Battery Last Discharge Date 30447 — 2 — Secs since Epoch(UTC) Battery Amp-Hours Consumed 30449 — 2 — Units : AH Uint32 UPS Battery Status 30451 — 1 — 1 = Unknown 2 = Normal 3 = Low 4 = Depleted The main battery disconnect status. 30452 — 1 — 0 = Open 1 = Closed 2 = Disabled Battery SCR Status 30453 — 1 — 0 = OK 1 = Fault 2 = unknown Main Battery Disconnect Switch Lock Status 30454 — 1 — 0 = Locked 1 = Unlocked 2 = unknown If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 328 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Input Holding # of Reg Scale Notes/Units DC Bus Voltage 30465 — 1 — Units : VDC Uint16 DC Bus Current 30466 — 1 — Units : A DC Int16 Data Label DC Bus 30467 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High System Output Voltage RMS A-B 30478 — 1 10 Units : VAC Uint16 System Output Voltage RMS B-C 30479 — 1 10 Units : VAC Uint16 System Output Voltage RMS C-A 30480 — 1 10 Units : VAC Uint16 System Output Voltage RMS A-N 30481 — 1 10 Units : VAC Uint16 System Output Voltage RMS B-N 30482 — 1 10 Units : VAC Uint16 System Output Voltage RMS C-N 30483 — 1 10 Units : VAC Uint16 System Output RMS Current Phs A 30484 — 1 — Units : A AC Uint16 System Output RMS Current Phs B 30485 — 1 — Units : A AC Uint16 System Output RMS Current Phs C 30486 — 1 — Units : A AC Uint16 System Output Frequency 30487 — 1 100 Units : Hz Uint16 System Output Power 30488 — 1 — Units : kW Uint16 System Output Apparent Power 30489 — 1 — Units : kVA Uint16 DC Bus Qualification Status Output System Output Power Factor Phs A 30490 — 1 100 Uint16 System Output Power Factor Phs B 30491 — 1 100 Uint16 System Output Power Factor Phs C 30492 — 1 100 Uint16 System Output Pct Power Phase A 30493 — 1 — Units : % Uint16 System Output Pct Power Phase B 30494 — 1 — Units : % Uint16 System Output Pct Power Phase C 30495 — 1 — Units : % Uint16 System Output Pct Pwr (VA) Phs A 30496 — 1 — Units : % Uint16 System Output Pct Pwr (VA) Phs B 30497 — 1 — Units : % Uint16 System Output Pct Pwr (VA) Phs C 30498 — 1 — Units : % Uint16 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High Output Qualification Status 30499 — 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 329 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units 30510 — 1 — Units : sec Uint16 Inverter Inverter Overload Time Remaining Inverter Output Qualification Status 30511 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High Inverter On/Off State 30512 — 1 — 0 = off 1 = on Inlet Air Temperature 30523 — 1 — Units : deg C Int16 Inlet Air Temperature 30524 — 1 — Units : deg F Int16 Total System Operating Time 30525 — 2 — Units : hr Uint32 System Date and Time 30527 40527 2 — Secs since Epoch(UTC) System Date and Time 39998 49998 2 — Secs since Epoch(UTC) Environment Rectifier Rectifier Pulse Count 30539 — 1 — 0 = 6 Pulse 1 = 12 Pulse 2 = 18 Pulse 3 = 24 Pulse Rectifier Input Passive Filter 30540 — 1 — 0 = Not Installed 1 = Installed Rectifier Passive Filter Switch 30541 — 1 — 0 = Not Installed 1 = Installed Rectifier Active Filter 30542 — 1 — 0 = Not Installed 1 = Installed Rectifier Status 30543 — 1 — 0 = off 1 = on — 0 = Single Module System 1 = Module (1 + 1) 2 = Module (1 + N) 3 = Module (N + 1) 4 = System Control Cabinet 5 = Main Static Switch — 0 = Two Wire (single phase + return) 1 = Two Wire (2 phase, no neutral) 2 = Three Wire (2 phase + neutral) 3 = Three Wire (3 phase, no neutral) 4 = Four Wire (3 phases + neutral) System UPS Module Type Bypass Input Wire Configuration 30554 30555 — — 1 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 330 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Output Wire Configuration 30556 — 1 — 0 = Two Wire (single phase + return) 1 = Two Wire (2 phase, no neutral) 2 = Three Wire (2 phase + neutral) 3 = Three Wire (3 phase, no neutral) 4 = Four Wire (3 phases + neutral) Static Switch Type 30557 — 1 — 0 = Not Applicable 1 = Continuous Duty 2 = Momentary Duty Configuration Description 30558 — 1 — 0 = Single Module System 33 1 = Single Module System 34 2 = Single Module System 44 3 = 1+1 33 4 = 1+1 34 5 = 1+1 44 6 = 1+N 33 7 = 1+N 34 8 = 1+N 44 9 = N+1 33 10 = N+1 34 11 = N+1 44 12 = SCC w/Continuous Duty SS 33 13 = SCC w/Continuous Duty SS 44 14 = SCC w/Momentary Duty SS 15 = Main Static Switch UPS System Output Source 30559 — 1 — 0 = None 1 = Inverter 2 = Bypass System Input Power Source 30560 — 1 — 0 = None 1 = Utility (mains) 2 = Generator — 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation System Status 30561 — 1 UPS Output Source 30562 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer System Fan Status 30563 — 1 — 0 = Unknown 1 = Normal 2 = Failure System Fan Redundant Status 30564 — 1 — 0 = Unknown 1 = Redundancy Available 2 = Loss of Redundancy System Fan Capacity Status 30565 — 1 — 0 = Unknown 1 = Normal 2 = Failure If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 331 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Input Holding # of Reg Scale Notes/Units Bypass Nominal Voltage 30576 — 1 — Units : VAC Uint16 System Input Nominal Voltage 30577 — 1 — Units : VAC Uint16 System Input Nominal Frequency 30578 — 1 10 Units : Hz Uint16 System Output Nominal Voltage 30579 — 1 — Units : VAC Uint16 System Output Nominal Frequency 30580 — 1 10 Units : Hz Uint16 Battery Cell Count - Lead Acid 30581 — 1 — Uint16 Battery Cell Count-Nickel Cadmium 30582 — 1 — Uint16 Data Label Ratings Output Apparent Power Rating 30583 — 1 — Units : kVA Uint16 Output Real Power Rating 30584 — 1 — Units : kW Uint16 Input Isolation Transformer 30585 — 1 — 0 = Not Installed 1 = Installed System UPS Module Count 30586 — 1 — Uint16 System Output Maximum Amp Rating 30587 — 1 — Units : A AC Uint16 System Redundant UPS Modules 30588 — 1 — Uint16 Backfeed Breaker 30599 — 1 — 0 = Open 1 = Close 2 = Not Installed SBS Load Disconnect 30600 — 1 — 0 = Open 1 = Close 2 = Not Installed Input Breaker 30601 — 1 — 0 = Open 1 = Close 2 = Not Installed Trap Filter Disconnect 30602 — 1 — 0 = Open 1 = Close 2 = Not Installed Output Breaker 30603 — 1 — 0 = Open 1 = Close 2 = Not Installed Internal Bypass Breaker 30604 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker 30605 — 1 — 0 = Open 1 = Close 2 = Not Installed Maintenance Bypass Breaker 30606 — 1 — 0 = Open 1 = Close 2 = Not Installed Maintenance Isolation Breaker 30607 — 1 — 0 = Open 1 = Close 2 = Not Installed Output Series Static Switch 30608 — 1 — 0 = Off 1 = On 2 = Not Installed Device Status If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 332 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Module Output Breaker 30609 — 1 — 0 = Open 1 = Close 2 = Not Installed Multi-module System Output Voltage RMS A-B 30620 — 1 10 Units : VAC Uint16 Multi-module System Output Voltage RMS B-C 30621 — 1 10 Units : VAC Uint16 Multi-module System Output Voltage RMS C-A 30622 — 1 10 Units : VAC Uint16 Multi-module System Output Voltage RMS A-N 30623 — 1 10 Units : VAC Uint16 Multi-module System Output Voltage RMS B-N 30624 — 1 10 Units : VAC Uint16 Multi-module System Output Voltage RMS C-N 30625 — 1 10 Units : VAC Uint16 Sum of MMS Output RMS Currents for Phase A 30626 — 1 — Units : A AC Uint16 Sum of MMS Output RMS Currents for Phase B 30627 — 1 — Units : A AC Uint16 Sum of MMS Output RMS Currents for Phase C 30628 — 1 — Units : A AC Uint16 MMS Output Frequency 30629 — 1 10 Units : Hz Uint16 MMS Output Power 30630 — 1 — Units : kW Uint16 MMS Output Apparent Power 30631 — 1 — Units : kVA Uint16 MMS Output Power Factor Phase A 30632 — 1 100 Int16 MMS Output Power Factor Phase B 30633 — 1 100 Int16 MMS Output Power Factor Phase C 30634 — 1 100 Int16 MultiModule MMS Output Pct Power Phase A 30635 — 1 — Units : % Int16 MMS Output Pct Power Phase B 30636 — 1 — Units : % Int16 MMS Output Pct Power Phase C 30637 — 1 — Units : % Int16 MMS Output Pct Apparent Pwr (kVA) Phase A 30638 — 1 — Units : % Uint16 MMS Output Pct Apparent Pwr (kVA) Phase B 30639 — 1 — Units : % Uint16 MMS Output Pct Apparent Pwr (kVA) Phase C 30640 — 1 — Units : % Uint16 Number of Redundant Modules 30641 — 1 — Uint16 MMS Module Number 30642 — 1 — Int16 Number of Modules in a MMS 30643 — 1 — Uint16 Module Output Breaker for Module 1 30644 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output Breaker for Module 2 30645 — 1 — 0 = Open 1 = Close 2 = Not Installed If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 333 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units Module Output Breaker for Module 3 30646 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output Breaker for Module 4 30647 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output Breaker for Module 5 30648 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output Breaker for Module 6 30649 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output Breaker for Module 7 30650 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output Breaker for Module 8 30651 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker for Module 1 30652 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker for Module 2 30653 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker for Module 3 30654 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker for Module 4 30655 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker for Module 5 30656 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker for Module 6 30657 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker for Module 7 30658 — 1 — 0 = Open 1 = Close 2 = Not Installed Bypass Isolation Breaker for Module 8 30659 — 1 — 0 = Open 1 = Close 2 = Not Installed System Output Breaker 30660 — 1 — 0 = Open 1 = Close 2 = Not Installed System Load Bank Breaker 30661 — 1 — 0 = Open 1 = Close 2 = Not Installed System Isolation Output Breaker 30662 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC Event Summary 30663 — 1 — 0 = None 1 = Alarm 2 = Fault If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 334 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Data Label Input Holding # of Reg Scale Notes/Units 30665 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer MMS Inter-Module Comm Status 30676 — 1 — 0 = Failed 1 = Normal MMS Event Summary 30677 — 1 — 0 = None 1 = Alarm 2 = Fault MMS Module Inverter Status 30678 — 1 — 0 = off 1 = on — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High MMS UPS Output Source ModuleList 1 MMS Module Output Voltage Status 30679 — 1 30680 — 1 — 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass MMS Inter-Module Comm Status 30691 — 1 — 0 = Failed 1 = Normal MMS Event Summary 30692 — 1 — 0 = None 1 = Alarm 2 = Fault MMS Module Inverter Status 30693 — 1 — 0 = off 1 = on — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High MMS Module Output Source ModuleList 2 MMS Module Output Voltage Status 30694 — 1 30695 — 1 — 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass MMS Inter-Module Comm Status 30781 — 1 — 0 = Failed 1 = Normal MMS Event Summary 30782 — 1 — 0 = None 1 = Alarm 2 = Fault MMS Module Inverter Status 30783 — 1 — 0 = off 1 = on — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal High — 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass MMS Module Output Source ModuleList 8 MMS Module Output Voltage Status MMS Module Output Source 30784 30785 — — 1 1 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 335 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Input Holding # of Reg Scale Notes/Units Intelligent Parallel Operation State 30796 — 1 — 0 = disabled 1 = enabled Intelligent Parallel Minimum Redundancy 30797 — 1 — Uint16 Intelligent Parallel Maximum Time in Standby 30798 — 1 — Units : day Uint16 ECO Mode Operation State 30809 40809 1 — 0 = disabled 1 = enabled Continuous Operation - ECO Mode 30810 — 1 — 0 = disabled 1 = enabled Maximum Auto Suspensions - ECO Mode 30811 — 1 — Uint16 Restart Delay - ECO Mode 30812 — 1 — Units : min Uint16 Time Remaining - ECO Mode 30813 — 1 — Units : min Uint16 Schedule Operation State - ECO Mode 30824 — 1 — 0 = disabled 1 = enabled Schedule Action - ECO Mode 30825 — 1 — 0 = stop 1 = start Data Label Intelligent Paralleling ECO Mode EcoModeSchedule 1 Schedule Day of Week - ECO Mode 30826 — 1 — 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Schedule Hour - ECO Mode 30827 — 1 — Units : hr Uint16 Schedule Minute - ECO Mode 30828 — 1 — Units : min Uint16 Schedule Operation State - ECO Mode 30839 — 1 — 0 = disabled 1 = enabled Schedule Action - ECO Mode 30840 — 1 — 0 = stop 1 = start EcoModeSchedule 2 Schedule Day of Week - ECO Mode 30841 — 1 — 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Schedule Hour - ECO Mode 30842 — 1 — Units : hr Uint16 Schedule Minute - ECO Mode 30843 — 1 — Units : min Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 336 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-80 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Input and Holding (continued) Input Holding # of Reg Scale Notes/Units Schedule Operation State - ECO Mode 31019 — 1 — 0 = disabled 1 = enabled Schedule Action - ECO Mode 31020 — 1 — 0 = stop 1 = start Data Label EcoModeSchedule 14 Schedule Day of Week - ECO Mode 31021 — 1 — 0 = Unknown 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = Sunday Schedule Hour - ECO Mode 31022 — 1 — Units : hr Uint16 Schedule Minute - ECO Mode 31023 — 1 — Units : min Uint16 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 337 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary Data Label Data Description Auto Restart In Progress Auto restart is in progress Auto Restart Inhibited - Ext Auto restart inhibited due to an external signal Auto Retransfer Time Remaining Time remaining before an inverter overload or inverter fault can be cleared and auto retransfer from the bypass to the inverter can take place Automatic Restart Failed Automatic restart failed Backfeed Breaker Open The backfeed breaker is in the open position Backfeed Breaker Backfeed breaker Battery - External Monitor 1 External battery monitor 1 - battery maintenance required Battery - External Monitor 2 External battery monitor 2 - battery maintenance required Battery Amp-Hours Consumed This Discharge Battery amp-hours withdrawn this discharge. Battery Amp-Hours Consumed Cumulative battery amp-hours withdrawn over the life of the battery Battery Auto Test In Progress Automatic battery test is in progress Battery Automatic Test Inhibited Automatic (scheduled) battery tests are inhibited Battery Capacity Low Battery capacity is low Battery Cell Count - Lead Acid Battery cell count - lead acid Battery Cell Count-Nickel Cadmium Battery cell count - nickel cadmium Battery Circuit Breaker 1 Open Battery circuit breaker 1 is open Battery Circuit Breaker 2 Open Battery circuit breaker 2 is open Battery Circuit Breaker 3 Open Battery circuit breaker 3 is open Battery Circuit Breaker 4 Open Battery circuit breaker 4 is open Battery Circuit Breaker 5 Open Battery circuit breaker 5 is open Battery Circuit Breaker 6 Open Battery circuit breaker 6 is open Battery Discharge Power Instantaneous battery power while discharging Battery Discharge Time The time on battery operation for this discharge Battery Discharging The battery is discharging Battery Equalize The rectifier output voltage is increased to equalize the battery voltage level. Battery Fuse Fault One or more battery fuse faults has occurred. Battery Ground Fault Battery system ground fault amperage exceeds the threshold Battery Last Discharge Date The date and time of the last battery discharge Battery Low Shutdown The battery voltage has dropped to the End of Discharge value. Battery Low The calculated battery time remaining has reached the low battery threshold Battery Over Temperature Limit A battery temperature sensor is reporting a value above a predetermined limit. Battery Over Temperature A battery temperature sensor is reporting a value above a threshold Battery Over Voltage The system has detected that the battery voltage has exceeded a predetermined limit. Battery Percentage Charge The percentage of battery charge Battery SCR Status The status of the battery SCR. Battery Temperature for Cabinet The battery temperature for a cabinet Battery Temperature Imbalance Excessive temperature differences between battery sensors detected Battery Temperature Sensor Fault A battery temperature sensor fault has been detected Battery Test Failed Battery test failed Battery Test Manually Stopped The battery test was manually stopped prior to completion Battery Test Passed Battery test passed Battery Time Remaining The calculated available time on battery Battery Total Discharge Time The cumulative battery discharge time Battery Volts at Main Disconnect The voltage between the positive and the negative battery terminals of the common battery disconnect Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 338 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued) Data Label Data Description Battery Volts for Cabinet The voltage between the positive and negative battery terminals of a battery cabinet Bypass - Manual Rexfr Inhibited Manual transfer from bypass to inverter is inhibited. Bypass - Manual Xfr Inhibited Manual transfer from inverter to bypass is inhibited. Bypass Auto Retransfer Failed After performing a recoverable transfer to bypass, an attempt to auto retransfer from bypass to inverter failed Bypass Auto Transfer Failed An automatic transfer to static bypass failed Bypass Frequency Error The bypass frequency is outside the inverter synchronization limits Bypass Input Frequency The bypass input frequency Bypass Input Voltage RMS A-B The bypass input RMS voltage between phases A and B Bypass Input Voltage RMS B-C The bypass input RMS voltage between phases B and C Bypass Input Voltage RMS C-A The bypass input RMS voltage between phases C and A Bypass Input Wire Configuration Bypass input wire configuration Bypass Isolation Breaker for Module 1 Bypass isolation breaker for module 1 Bypass Isolation Breaker for Module 2 Bypass isolation breaker for module 2 Bypass Isolation Breaker for Module 3 Bypass isolation breaker for module 3 Bypass Isolation Breaker for Module 4 Bypass isolation breaker for module 4 Bypass Isolation Breaker for Module 5 Bypass isolation breaker for module 5 Bypass Isolation Breaker for Module 6 Bypass isolation breaker for module 6 Bypass Isolation Breaker for Module 7 Bypass isolation breaker for module 7 Bypass Isolation Breaker for Module 8 Bypass isolation breaker for module 8 Bypass Isolation Breaker Bypass isolation breaker Bypass Nominal Voltage Bypass nominal (or rated) voltage Bypass Not Available A problem associated with the bypass has been detected Bypass Overload Phase A An overload exists on output phase A while operating on the bypass Bypass Overload Phase B An overload exists on output phase B while operating on the bypass Bypass Overload Phase C An overload exists on output phase C while operating on the bypass Bypass Qualification Status bypass qualification status Bypass SS Overload Time Remain The calculated time remaining before bypass static switch shutdown due to the present overload condition Bypass Static Switch Overload Bypass off due to static switch overload Bypass Static Switch Unavailable The static bypass switch is off, and unable to operate Bypass Sync Phase Difference The phase angle difference between the inverter output and bypass source Configuration Description Configuration description Continuous Operation - ECO Mode This setting gives the user the ability to Enable/Disable ECO Mode continuous operation. Controls Reset Required A controls reset is required due to one or more critical settings changing DC Bus Current The current at the battery input terminals. In charging mode, the current will be a positive value. In discharging mode, the current will be a negative value DC Bus Low Fault The DC Bus voltage has reached a critical low level. DC Bus Qualification Status dc bus qualification status DC Bus Voltage The voltage between the positive and negative terminals of the DC bus at the battery input ECO Mode Active Conditions for Activation or Automatic Reactivation have been satisfied. ECO Mode Operation State This setting is used to enable or disable ECO Mode. ECO Mode Suspended ECO Mode session is suspended. EMO Shutdown An Emergency Module Off command has been detected. Equipment Temperature Sensor Fail One or more temperature sensors report a temperature outside of the range of expected operation. 339 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued) Data Label Data Description Excess ECO Suspends Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto Suspensions setting. Fuse Failure A summary event indicating one or more fuse failures Inlet Air Over Temperature The inlet air exceeds the maximum temperature threshold Inlet Air Temperature The temperature of the inlet air Input Breaker Input breaker Input Contact 01 The external input contact 1 Input Contact 02 The external input contact 2 Input Contact 03 The external input contact 3 Input Contact 04 The external input contact 4 Input Contact 05 The external input contact 5 Input Contact 06 The external input contact 6 Input Contact 07 The external input contact 7 Input Contact 08 The external input contact 8 Input Contact 09 The external input contact 9 Input Contact 10 The external input contact 10 Input Contact 11 The external input contact 11 Input Contact 12 The external input contact 12 Input Contact 13 The external input contact 13 Input Contact 14 The external input contact 14 Input Contact 15 The external input contact 15 Input Contact 16 The external input contact 16 Input Filter Cycle Lock The input filter disconnect is open due to exceeding the maximum number of cycles. Input Isolation Transformer Input isolation transformer Input Qualification Status input qualification status Intelligent Parallel Maximum Time in Standby The maximum time a module can be in standby mode due to Intelligent Paralleling. Intelligent Parallel Minimum Redundancy This is the minimum Number of Redundant Modules that the system will allow before bringing one or more modules back to normal operation and terminating Intelligent Paralleling. Intelligent Parallel Operation State This setting is used to enable or disable Intelligent Paralleling. Internal Communications Failure The control has detected a communication failure of a component on the internal communication bus Inverter Failure Inverter failure - inverter output is off Inverter Inhibit - External Restart of the inverter is inhibited by an external signal Inverter On/Off State inverter on/off state Inverter Output Qualification Status inverter output qualification status Inverter Overload Phase A Inverter is operating with an overload on phase A Inverter Overload Phase B Inverter is operating with an overload on phase B Inverter Overload Phase C Inverter is operating with an overload on phase C Inverter Overload Time Remaining The calculated time remaining before inverter shutdown Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload Inverter Static Switch SCR Short The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCR) IP Inhibit The intelligent paralleling operation is inhibited. LBS Inhibited The system has detected that conditions to perform Load Bus Sync are not satisfied Leading Power Factor The leading output Power Factor has fallen below a specified value Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 340 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued) Data Label Data Description Loss of Redundancy The multi-module collection doesn't have enough modules to redundantly support the load. Main Battery Disconnect Forced To Unlock The main battery disconnect is forced to the unlocked state. Main Battery Disconnect Open Main battery disconnect is open Main Battery Disconnect Switch Lock Status The main battery disconnect switch lock status. Main Controller Fault A Main Controller fault has been detected. Maintenance Bypass Breaker Maintenance bypass breaker Maintenance Isolation Breaker Maintenance isolation breaker Maximum Auto Suspensions - ECO Mode This setting sets the maximum number of automatic ECO Mode suspensions in a session. MMS Event Summary Summary of any active user alarm or fault of this module in a multi-module system MMS Inter-Module Comm Status Inter-module communication status of this module in a multi-module system MMS Module Alarm Active Active alarm or fault of any module in a multi-module system MMS Module Inverter Status Multi-module inverter status of this module (on/off) MMS Module Number MMS module number MMS Module Output Source Module output source in a multi-module system (normal/bypass/maintenance bypass/off) MMS Module Output Voltage Status Output voltage status of this module in multi-module system MMS On Battery The multi-module system is on battery MMS Output Apparent Power The sum total apparent power of all system output modules MMS Output Frequency The multi-module system output frequency MMS Output Pct Apparent Pwr (kVA) Phase A The multi-module system output apparent power on phase A as a percentage of the rated capacity MMS Output Pct Apparent Pwr (kVA) Phase B The multi-module system output apparent power on phase B as a percentage of the rated capacity MMS Output Pct Apparent Pwr (kVA) Phase C The multi-module system output apparent power on phase C as a percentage of the rated capacity MMS Output Pct Power Phase A The multi-module system output power on phase A as a percentage of the rated capacity MMS Output Pct Power Phase B The multi-module system output power on phase B as a percentage of the rated capacity MMS Output Pct Power Phase C The multi-module system output power on phase C as a percentage of the rated capacity MMS Output Power Factor Phase A The multi-module system output power factor for phase A MMS Output Power Factor Phase B The multi-module system output power factor for phase B MMS Output Power Factor Phase C The multi-module system output power factor for phase C MMS Output Power The sum total power of all system output modules MMS Overload Multi-module system overload MMS UPS Output Source Multi-module UPS output source Module Output Breaker for Module 1 Module output breaker for module 1 Module Output Breaker for Module 2 Module output breaker for module 2 Module Output Breaker for Module 3 Module output breaker for module 3 Module Output Breaker for Module 4 Module output breaker for module 4 Module Output Breaker for Module 5 Module output breaker for module 5 Module Output Breaker for Module 6 Module output breaker for module 6 Module Output Breaker for Module 7 Module output breaker for module 7 Module Output Breaker for Module 8 Module output breaker for module 8 Module Output Breaker Module output breaker 341 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued) Data Label Data Description Multi-module System Output Voltage RMS A-B Multi-module system output RMS voltage between phases A and B Multi-module System Output Voltage RMS A-N Multi-module system output RMS voltage between phase A and Neutral Multi-module System Output Voltage RMS B-C Multi-module system output RMS voltage between phases B and C Multi-module System Output Voltage RMS B-N Multi-module system output RMS voltage between phase B and Neutral Multi-module System Output Voltage RMS C-A Multi-module system output RMS voltage between phases C and A Multi-module System Output Voltage RMS C-N Multi-module system output RMS voltage between phase C and Neutral Multiple Fan Failure Multiple fan failure Number of Modules in a MMS The number of modules in a multi-module system Number of Redundant Modules The number of redundant modules in a multi-module collective. Outlet Air Overtemperature Limit The difference between the outlet air temperature and inlet air temperature exceeds a specified maximum temperature. Output Amp Over User Limit-Phs A The phase A output has exceeded the user amperage threshold Output Amp Over User Limit-Phs B The phase B output has exceeded the user amperage threshold Output Amp Over User Limit-Phs C The phase C output has exceeded the user amperage threshold Output Apparent Power Rating Output apparent power rating Output Breaker Output breaker Output Load on Maint. Bypass The output power is supplied by the maintenance bypass Output Of/Uf The output frequency has exceeded a specified range for a specified period of time. Output Qualification Status output qualification status Output Real Power Rating Output real power rating Output Series Static Switch output series static switch Output Wire Configuration Output wire configuration Power Supply Failure Power supply failure Program Input Contact 01 When the signal from [Program Input Contact 01] is active the function assigned to this contact is executed. Program Input Contact 02 When the signal from [Program Input Contact 02] is active the function assigned to this contact is executed. Program Input Contact 03 When the signal from [Program Input Contact 03] is active the function assigned to this contact is executed. Program Input Contact 04 When the signal from [Program Input Contact 04] is active the function assigned to this contact is executed. Program Input Contact 05 When the signal from [Program Input Contact 05] is active the function assigned to this contact is executed. Program Input Contact 06 When the signal from [Program Input Contact 06] is active the function assigned to this contact is executed. Program Input Contact 07 When the signal from [Program Input Contact 07] is active the function assigned to this contact is executed. Program Input Contact 08 When the signal from [Program Input Contact 08] is active the function assigned to this contact is executed. Program Input Contact 09 When the signal from [Program Input Contact 09] is active the function assigned to this contact is executed. Program Input Contact 10 When the signal from [Program Input Contact 10] is active the function assigned to this contact is executed. Program Input Contact 11 When the signal from [Program Input Contact 11] is active the function assigned to this contact is executed. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 342 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued) Data Label Data Description Program Input Contact 12 When the signal from [Program Input Contact 12] is active the function assigned to this contact is executed. Rectifier Active Filter Rectifier input active filter configuration Rectifier Configuration Change Request This event indicates that the battery is not configured and PFC is not enabled. Rectifier Failure Rectifier failure - rectifier is off Rectifier Input Passive Filter Rectifier input passive filter configuration Rectifier Passive Filter Switch Rectifier input passive filter switch configuration Rectifier Pulse Count Rectifier pulse count per cycle configuration Rectifier Status rectifier status Regeneration Active Regeneration operation is active. Regeneration Operation Failure Regeneration operation has been terminated due to bypass source instability or unit misoperation. Regeneration Operation Terminated Regeneration operation is not active. Restart Delay - ECO Mode The time delay that the conditions to activate ECO Mode must be satisfied before ECO Mode can be reactivated during an active session. SCC Event Summary Summary of any active user alarms or faults on the SCC Schedule Action - ECO Mode This setting gives the user the ability to choose the action of a schedule entry to be either stop or start. Schedule Day of Week - ECO Mode This setting represents the day of the week when an associated ECO Mode schedule entry action will take effect. Schedule Hour - ECO Mode This setting represents the hour of the day when an associated schedule entry action will take effect. Schedule Minute - ECO Mode This setting represents the minute of the hour when an associated schedule entry action will take effect. Schedule Operation State - ECO Mode This setting gives the user the ability to either enable or disable a schedule entry if the action is Start. Service Code Active Service code is running Static Bypass Switch Static Bypass Switch state - On/Off Static Switch Type Static switch type configuration Sum of MMS Output RMS Currents for The sum of the multi-module system output RMS currents for phase A Phase A Sum of MMS Output RMS Currents for The sum of the multi-module system output RMS currents for phase B Phase B Sum of MMS Output RMS Currents for The sum of the multi-module system output RMS currents for phase C Phase C System Breaker(s) Close Failure One or more breakers in the system failed to close System Breaker(s) Open Failure One or more breakers in the system failed to open System Controller Error System controller internal error System Date and Time The system date and time System Fan Capacity Status System fan capacity status System Fan Failure - Redundant Redundant system fan failure System Fan Redundant Status System fan redundant status System Fan Status System fan status System Input Current Imbalance System Input Currents are Imbalanced System Input Current Limit The RMS input current has reached the input current limit threshold System Input Frequency The system input frequency System Input Nominal Frequency The nominal (or rated) system input frequency System Input Nominal Voltage The nominal (or rated) system input voltage 343 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued) Data Label Data Description System Input Phs Rotation Error The power conductors on the input line are not wired to the UPS in the sequence preferred for the rectifier (A-B-C) System Input Power Problem The input is not qualified to provide power to the system System Input Power Source System input power source System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System Isolation Output Breaker System isolation output breaker System Load Bank Breaker System load bank breaker System Output Apparent Power The sum total apparent power of all system output phases System Output Breaker System output breaker System Output Fault A fault has been detected in the system output System Output Frequency The system output frequency System Output Low Power Factor The system output power factor is low, resulting in reduced output capacity System Output Maximum Amp Rating System output maximum amperage rating System Output Nominal Frequency The nominal (or rated) system output frequency System Output Nominal Voltage The nominal (or rated) system output voltage System Output Pct Power Phase A The system output power on phase A as a percentage of the rated capacity System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Output Pct Power Phase C The system output power on phase C as a percentage of the rated capacity System Output Pct Pwr (VA) Phs A The system output apparent power on phase A as a percentage of the rated capacity System Output Pct Pwr (VA) Phs B The system output apparent power on phase B as a percentage of the rated capacity System Output Pct Pwr (VA) Phs C The system output apparent power on phase C as a percentage of the rated capacity System Output Power Factor Phs A The system output power factor of phase A System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power The sum total power of all system output phases System Output RMS Current Phs A The system output RMS current for Phase A System Output RMS Current Phs B The system output RMS current for Phase B System Output RMS Current Phs C The system output RMS current for Phase C System Output Voltage RMS A-B The system output RMS voltage between phases A and B System Output Voltage RMS A-N The system output RMS voltage between phases A and Neutral System Output Voltage RMS B-C The system output RMS voltage between phases B and C System Output Voltage RMS B-N The system output RMS voltage between phases B and Neutral System Output Voltage RMS C-A The system output RMS voltage between phases C and A System Output Voltage RMS C-N The system output RMS voltage between phases C and Neutral System Redundant UPS Modules Number of redundant UPS modules in the system System Shutdown - EPO System shutdown due to Emergency Power Off (EPO) System Shutdown - REPO System shutdown due to Remote Emergency Power Off (REPO) System Status The operating status for the system System UPS Module Count Number of UPS modules in the system The main battery disconnect status. Main Battery Disconnect Status Time Remaining - ECO Mode Time remaining before current active ECO Mode session stops. Total System Operating Time The cumulative operation time of the unit Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 344 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-81 Liebert NXL™—50Hz, CE version (Models 48 and 49)—Glossary (continued) Data Label Data Description Trap Filter Disconnect Trap filter disconnect Unexpected Main Battery Disconnect Closure The main battery disconnect has closed unexpectedly. UPS Battery Status UPS battery status UPS Module Type UPS module type UPS Output on Bypass The output power is supplied by the bypass UPS Output Source UPS output source UPS System Output Source The UPS system's output power source VDC Backfeed The voltage between battery and DC bus measurements is out of tolerance. 345 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-82 Liebert PowerSure™ Interactive (before July 2008)—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Audible Alarm Enabled 10002 2 1 — — Automatic Battery Test Enabled 10003 3 1 — — Battery Charge Compensation 10046 — 1 — — Inverter Ready 10047 — 1 — — Load Circuit 1 State 10057 — 1 — — Load Circuit 2 State 10058 — 1 — — Load Circuit 3 State 10059 — 1 — — Load Circuit 4 State 10060 — 1 — — Load Circuit 5 State 10061 — 1 — — Load Circuit 6 State 10062 — 1 — — Load Circuit 7 State 10063 — 1 — — Load Circuit 8 State 10064 — 1 — — Load Circuit 9 State 10065 — 1 — — Load Circuit 10 State 10066 — 1 — — Load Circuit 11 State 10067 — 1 — — Load Circuit 12 State 10068 — 1 — — Load Circuit 13 State 10069 — 1 — — Load Circuit 14 State 10070 — 1 — — Load Circuit 15 State 10071 — 1 — — Load Circuit 16 State 10072 — 1 — — Load On Inverter 10073 — 1 — — Boost Mode On 10075 — 1 — — Buck Mode On 10076 — 1 — — Battery Under Test 10082 — 1 — — Shutdown Reason - Over Temperature 10086 — 1 — — Shutdown Reason - Overload 10087 — 1 — — Shutdown - Output Short 10089 — 1 — — Shutdown Reason - Remote Shutdown 10093 — 1 — — Load On Battery 10128 — 1 — — Output Off Pending 10151 — 1 — — Low Battery - Shutdown Imminent 10152 — 1 — — Output Overload 10154 — 1 — — Over Temperature Warning 10171 — 1 — — Battery Over Temperature CB Trip 10172 — 1 — — Input Power Supply Fail 10186 — 1 — — Input Over Voltage 10187 — 1 — — Input Under Voltage 10188 — 1 — — Bad Input Frequency 10190 — 1 — — Output Under Voltage 10218 — 1 — — Output Over Voltage 10219 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 346 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-83 Liebert PowerSure™ Interactive (before July 2008)—Input and Holding Data Description Number of Input Lines Input Register Holding Register # of Reg. Scale Notes / Units 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of Output Lines 30004 40004 1 — Bits 8 - 11 Number of SubModules 30009 40009 1 — - Load Circuit Present 30013 40013 1 — There are 16 possible Load Circuits. Each bit represents 1 load circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1, then the Load Circuit is supported. Nominal Power Rating 30021 40021 2 — VA Nominal Input Voltage 30027 40027 1 — V Nominal Output Voltage 30028 40028 1 — V Nominal Input Current 30030 40030 1 — A Nominal Input Frequency 30031 40031 1 10 Hz Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 — Nominal Battery Voltage 30034 40034 1 — V Auto Restart Delay 30051 40051 1 — Seconds Device Low Battery Time 30053 40053 1 — Minutes Load (Apparent Power) 30102 — 2 — VA Load / Capacity 30106 — 1 — % Input Frequency 30107 — 1 10 Hz Output Frequency 30108 — 1 10 Hz 1 - 100% Charged 2 - Less than 100% Charged 3 - Charging 4 - Discharging 5 - Float Charging 6 - Equalize Charging Battery Charge Status 30112 — 1 — Battery Voltage 30113 — 1 — V Battery Time Remaining 30115 — 1 — Minutes Battery Charge Percentage 30116 — 1 — % Battery Test Result 30130 — 1 — 1 - Unknown 2 - Passed 3 - Failed 4 - In Progress 5 - System Failure 7 - Inhibited Input Voltage L1 30153 — 1 — V Output Voltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A Input Maximum Voltage L1 30180 — 1 — V Input Minimum Voltage L1 30181 — 1 — V Output Maximum Voltage L1 30182 — 1 — V Output Minimum Voltage L1 30183 — 1 — V Black Out Count 30301 — 1 — — Brown Out Count 30302 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 347 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-84 Liebert PowerSure™ Interactive 2—Status and Coil Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153) Status Coil Number of Bits Scale Notes / Units Audible Alarm Enabled 10002 2 1 — — Automatic Battery Test Enabled 10003 3 1 — — DC-To-DC Converter On 10042 — 1 — — Battery Charger On 10044 — 1 — — Load Circuit 1 State 10057 — 1 — — Load Circuit 2 State 10058 — 1 — — Load Circuit 3 State 10059 — 1 — — Load Circuit 4 State 10060 — 1 — — Load Circuit 5 State 10061 — 1 — — Load Circuit 6 State 10062 — 1 — — Load Circuit 7 State 10063 — 1 — — Load Circuit 9 State 10065 — 1 — — Load Circuit 10 State 10066 — 1 — — Load Circuit 11 State 10067 — 1 — — Load Circuit 12 State 10068 — 1 — — Load Circuit 13 State 10069 — 1 — — Load Circuit 14 State 10070 — 1 — — Load Circuit 15 State 10071 — 1 — — Data Description Load Circuit 16 State 10072 — 1 — — Load On Inverter 10073 — 1 — — Boost Mode On 10075 — 1 — — Buck Mode On 10076 — 1 — — Replace Battery 10081 — 1 — — Battery Under Test 10082 — 1 — — Shutdown Reason - Over Temperature 10086 — 1 — — Shutdown Reason - Overload 10087 — 1 — — Shutdown Reason - Output Short 10089 — 1 — — Shutdown Reason - Line Neutral Swap 10090 — 1 — — Shutdown Reason - Low Battery 10092 — 1 — — Shutdown Reason - Remote Shutdown 10093 — 1 — — Shutdown Reason - Input Under Voltage 10094 — 1 — — Shutdown Reason - Hardware 10096 — 1 — — Load On Battery 10128 — 1 — — Output Off Pending 10151 — 1 — — Low Battery - Shutdown Imminent 10152 — 1 — — Output Overload 10154 — 1 — — Over Temperature Warning 10171 — 1 — — Input Power Supply Fail 10186 — 1 — — Input Over Voltage 10187 — 1 — — Input Under Voltage 10188 — 1 — — Input BrownOut 10189 — 1 — — Bad Input Frequency 10190 — 1 — — Output Under Voltage 10218 — 1 — — Output Over Voltage 10219 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 348 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-84 Liebert PowerSure™ Interactive 2—Status and Coil (continued) Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153) Coil Number of Bits Data Description Status Scale Notes / Units Charger Failed 10234 — 1 — — Battery Under Voltage 10241 — 1 — — Battery Over Voltage 10242 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 349 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-85 Liebert PowerSure™ Interactive 2—Input and Holding Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153) Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Output Lines 30004 40004 1 — Bits 8 - 11 Number of SubModules 30009 40009 1 — — — There are 16 possible Load Circuits. Each bit represents 1 load circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1, then the Load Circuit is supported. Data Description Load Circuit Present 30013 40013 1 Nominal Power Rating 30021 40021 2 — VA Nominal Input Voltage 30027 40027 1 — V Nominal Output Voltage 30028 40028 1 — V Nominal Input Current 30030 40030 1 — A Nominal Input Frequency 30031 40031 1 10 Hz Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 — Nominal Battery Voltage 30034 40034 1 — V Nominal Battery Capacity 30037 40037 1 — Minutes Nominal Battery Float Voltage 30038 40038 1 — V Auto Restart Delay 30051 40051 1 — Seconds Device Low Battery Time 30053 40053 1 — Minutes Ambient Temperature Warning Point 30069 40069 1 — deg C Over Temperature Limit Point 30072 40072 1 — deg C Load (Apparent Power) 30102 — 2 — VA Load (Real Power) 30104 — 2 — W Load / Capacity 30106 — 1 — % Input Frequency 30107 — 1 10 Hz Output Frequency 30108 — 1 10 Hz 1 - 100% Charged 2 - Less than 100% Charged 3 - Charging 4 - Discharging 5 - Float Charging 6 - Equalize Charging Battery Charge Status 30112 — 1 — Battery Voltage 30113 — 1 — V Battery Time Remaining 30115 — 1 — Minutes Battery Charge Percentage 30116 — 1 — % Ambient Temperature 30119 — 1 — deg C Battery Test Result 30130 — 1 — — Input Voltage L1 30153 — 1 — V Input Current L1 30154 — 1 — A Output Voltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A Input Maximum Voltage L1 30180 — 1 — V Input Minimum Voltage L1 30181 — 1 — V Output Maximum Voltage L1 30182 — 1 — V Output Minimum Voltage L1 30183 — 1 — V If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 350 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-85 Liebert PowerSure™ Interactive 2—Input and Holding (continued) Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153) Data Description Input Register Holding Register # of Reg. Scale Notes / Units Black Out Count 30301 — 1 — — Brown Out Count 30302 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 351 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-86 Liebert Series 300™ UPS—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Automatic Restart Enabled 10001 1 1 — — Battery Charge Compensation 10046 — 1 — — Inverter Ready 10047 — 1 — — Load Circuit 1 State 10057 — 1 — — Load Circuit 2 State 10058 — 1 — — Load Circuit 3 State 10059 — 1 — — Load Circuit 4 State 10060 — 1 — — Load Circuit 5 State 10061 — 1 — — Load Circuit 6 State 10062 — 1 — — Load Circuit 7 State 10063 — 1 — — Load Circuit 8 State 10064 — 1 — — Load Circuit 9 State 10065 — 1 — — Load Circuit 10 State 10066 — 1 — — Load Circuit 11 State 10067 — 1 — — Load Circuit 12 State 10068 — 1 — — Load Circuit 13 State 10069 — 1 — — Load Circuit 14 State 10070 — 1 — — Load Circuit 15 State 10071 — 1 — — Load Circuit 16 State 10072 — 1 — — Load On Inverter 10073 — 1 — — Bypass Active 10074 — 1 — — Buck On 10076 — 1 — — Replace Battery 10081 — 1 — — Battery Under Test 10082 — 1 — — Load On Battery 10128 — 1 — — Low Battery - Shutdown Imminent 10152 — 1 — — Output Overload 10154 — 1 — — Over Temperature Warning 10171 — 1 — — Battery Over Temperature CB Trip 10172 — 1 — — Input Power Supply Fail 10186 — 1 — — Input Over Voltage 10187 — 1 — — Input Under Voltage 10188 — 1 — — Bad Input Frequency 10190 — 1 — — Bypass Input Voltage/Frequency Fault 10202 — 1 — — Output Under Voltage 10218 — 1 — — Output Over Voltage 10219 — 1 — — Battery Charger Fail 10234 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 352 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-87 Liebert Series 300™ UPS—Input and Holding Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of Output Lines 30004 40004 1 — Bits 8 - 11 Number of SubModules 30009 40009 1 — — Data Description Load Circuit Present 30013 40013 1 — There are 16 possible Load Circuits. Each bit represents 1 Load Circuit. Load Circuit 1 is bit 0, Load Circuit 2 is bit 1 and so on. If the bit is 1, then the Load Circuit is supported. Nominal Power Rating 30021 40021 2 — VA Nominal Input Voltage 30027 40027 1 — V Nominal Output Voltage 30028 40028 1 — V Nominal Static Bypass Switch Voltage 30029 40029 1 — V Nominal Input Current 30030 40030 1 — A Nominal Input Frequency 30031 40031 1 10 Hz Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 — Nominal Battery Voltage 30034 40034 1 — V Device Low Battery Time 30053 40053 1 — Minutes Load (Apparent Power) 30102 — 2 — VA Load (Real Power) 30104 — 2 — W Load / Capacity 30106 — 1 — % Input Frequency 30107 — 1 10 Hz Output Frequency 30108 — 1 10 Hz Bypass Frequency 30109 — 1 10 Hz Battery Charge Status 30112 — 1 — Battery Voltage 30113 — 1 — V Battery Current 30114 — 1 — A 1 - 100% Charged 2 - Less than 100% Charged Battery Time Remaining 30115 — 1 — Minutes Battery Charge Percentage 30116 — 1 — % Battery Test Result 30130 — 1 — 1 - Unknown 2 - Passed 3 - Failed 4 - In Progress 5 - System Failure 6 - Inhibited Input Voltage L1 30153 — 1 — V Input Current 30154 — 1 — A Bypass Voltage L1 30159 — 1 — V Bypass Current L1 30160 — 1 — A Output Voltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A Input Voltage L2 30203 — 1 — V Input Current L2 30204 — 1 — A Bypass Voltage L2 30209 — 1 — V Bypass Current L2 30210 — 1 — A Output Voltage L2 30213 — 1 — V If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 353 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-87 Liebert Series 300™ UPS—Input and Holding (continued) Data Description Input Register Holding Register # of Reg. Scale Notes / Units Output Current L2 30214 — 1 — A Input Voltage L3 30253 — 1 — V Input Current L3 30254 — 1 — A Bypass Voltage L3 30259 — 1 — V Bypass Current L3 30260 — 1 — A Output Voltage L3 30263 — 1 — V Output Current L3 30264 — 1 — A Black Out Count 30301 — 1 — — Brown Out Count 30302 — 1 — — Transient Count 30301 — 1 — — 40101 — — Silent Audible Alarm — Any value Battery Start — 40102 1 — 1=Start, 0=Abort Open UPS Output Switch — 40104 — — Delay time in Seconds, last digit will be ignored Reboot UPS Output Switch — 40105 1 — Delay time in Seconds, last digit will be ignored Close UPS Output Switch — 40106 — — Delay time in Seconds, last digit will be ignored Transfer Load to Bypass — 40107 1 — Any value Transfer Load to Inverter — 40108 — — Any value Reset UPS Statistic data — 40111 1 — Any value Turn UPS Outlets On — 40112 1 — Bitmap mask for Outlet 1-16. All bits set to 1 will be turned On Turn UPS Outlets Off — 40113 1 — Bitmap mask for Outlet 1-16. All bits set to 1 will be turned Off If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 354 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-88 Liebert Series 600™ UPS—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Auto Retransfer Primed 10049 — 1 — — Load On Inverter 10073 — 1 — — Load On Bypass 10074 — 1 — — Battery data Buffer Full 10084 — 1 — — Shutdown Reason - Hardware 10096 — 1 — — Load On Battery 10128 — 1 — — Load On Bypass 10129 — 1 — — Manual Reset Transfer 10130 — 1 — — Emergency Transfer 10134 — 1 — — Battery Switch Open 10136 — 1 — — Input Switch Open 10137 — 1 — — Output Switch open 10138 — 1 — — SBS Unable 10148 — 1 — — Low Battery - Shutdown Imminent 10152 — 1 — — Output Frequency Off 10153 — 1 — — Output Overload 10154 — 1 — — System Emergency Off 10157 — 1 — — Reverse Power 10159 — 1 — — Fan Fail 10169 — 1 — — Over Temperature Warning 10171 — 1 — — Ambient Over Temperature 10173 — 1 — — Input Power Supply Fail 10186 — 1 — — Input Phase Rotation Error 10191 — 1 — — Bypass Input Voltage Fail 10202 — 1 — — Output Under Voltage 10218 — 1 — — Output Over Voltage 10219 — 1 — — DC Ground Fault 10233 — 1 — — DC Cap Fuse Blown 10252 — 1 — — Rectifier Fuse Blown 10257 — 1 — — Inverter Fuse Blown 10261 — 1 — — Customer Alarm 1 10313 — 1 — — Customer Alarm 2 10314 — 1 — — Customer Alarm 3 10315 — 1 — — Customer Alarm 4 10316 — 1 — — Customer Alarm 5 10317 — 1 — — Customer Alarm 6 10318 — 1 — — Customer Alarm 7 10319 — 1 — — Customer Alarm 8 10320 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 355 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-89 Liebert Series 600™ UPS—Input and Holding Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Number of Output Lines 30004 40004 1 — Bits 8 - 11 Nominal Power Rating 30021 40021 2 — VA Nominal Input Voltage 30027 40027 1 — V Data Description Nominal Output Voltage 30028 40028 1 — V Nominal Static Bypass Switch Voltage 30029 40029 1 — V Nominal Input Current 30030 40030 1 — A Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 — Nominal Battery Voltage 30034 40034 1 — V — 40101 1 — — 30102 — 2 — VA Silence Alarm Load (Apparent Power) Load (Real Power) 30104 — 2 — W Load / Capacity 30106 — 1 — % Output Frequency 30108 — 1 10 Hz Bypass Frequency 30109 — 1 10 Hz Battery Charge Status 30112 — 1 — Battery Voltage 30113 — 1 — V Battery Current 30114 — 1 — A 1 - 100% Charged 2 - Less than 100% Charged Battery Time Remaining 30115 — 1 — Minutes Battery Charge Percentage 30116 — 1 — % Input Voltage L1 30153 — 1 — V Input Current L1 30154 — 1 — A Bypass Voltage L1 30159 — 1 — V Bypass Current L1 30160 — 1 — A Output Voltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A Input Voltage L2 30203 — 1 — V Input Current L2 30204 — 1 — A Bypass Voltage L2 30209 — 1 — V Bypass Current L2 30210 — 1 — A Output Voltage L2 30213 — 1 — V Output Current L2 30214 — 1 — A Input Voltage L3 30253 — 1 — V Input Current L3 30254 — 1 — A Bypass Voltage L3 30259 — 1 — V Bypass Current L3 30260 — 1 — A Output Voltage L3 30263 — 1 — V Output Current L3 30264 — 1 — A Battery Discharge Count 30308 — 1 — — Battery Discharge duration 30309 — 1 — Seconds Battery Amp-Hour 30310 — 1 — AH Battery Watt-Hour 30311 — 2 — WH If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 356 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-90 Liebert Series 610™ SCC UPS—Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Auto Retransfer Primed 10049 — 1 — — Load On Inverter 10073 — 1 — — Load On Bypass 10074 — 1 — — Load On Bypass 10129 — 1 — — Manual Reset Transfer 10130 — 1 — — Emergency Transfer 10134 — 1 — — Output Switch open 10138 — 1 — — SBS Unable 10148 — 1 — — Output Frequency Off 10153 — 1 — — Output Overload 10154 — 1 — — System Emergency Off 10157 — 1 — — Input Power Supply Fail 10186 — 1 — — Input Phase Rotation Error 10191 — 1 — — Bypass Input Voltage Fail 10202 — 1 — — Output Under Voltage 10218 — 1 — — Output Over Voltage 10219 — 1 — — Module Alarm Active 10304 — 1 — — Customer Alarm 1 10313 — 1 — — Customer Alarm 2 10314 — 1 — — Customer Alarm 3 10315 — 1 — — Customer Alarm 4 10316 — 1 — — Customer Alarm 5 10317 — 1 — — Customer Alarm 6 10318 — 1 — — Customer Alarm 7 10319 — 1 — — Customer Alarm 8 10320 — 1 — — If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 357 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-91 Liebert Series 610 SCC UPS—Input and Holding Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines 30004 40004 1 — Bits 4 - 7 Data Description Number of Output Lines 30004 40004 1 — Bits 8 - 11 Nominal Power Rating 30021 40021 2 — VA Nominal Input Voltage 30027 40027 1 — V Nominal Output Voltage 30028 40028 1 — V Nominal Static Bypass Switch Voltage 30029 40029 1 — V Nominal Output Frequency 30032 40032 1 10 Hz Nominal Power Factor 30033 40033 1 100 — — 40101 1 — — 30102 — 2 — VA W Silence Alarm Load (Apparent Power) Load (Real Power) 30104 — 2 — Load / Capacity 30106 — 1 — % Output Frequency 30108 — 1 10 Hz Bypass Frequency 30109 — 1 10 Hz Input Voltage L1 30153 — 1 — V Bypass Voltage L1 30159 — 1 — V Bypass Current L1 30160 — 1 — A Output Voltage L1 30163 — 1 — V Output Current L1 30164 — 1 — A Input Voltage L2 30203 — 1 — V Bypass Voltage L2 30209 — 1 — V Bypass Current L2 30210 — 1 — A Output Voltage L2 30213 — 1 — V Output Current L2 30214 — 1 — A Input Voltage L3 30253 — 1 — V Bypass Voltage L3 30259 — 1 — V Bypass Current L3 30260 — 1 — A Output Voltage L3 30263 — 1 — V Output Current L3 30264 — 1 — A If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 358 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-92 Liebert HiPulse™ and Liebert SICE 7200™—Input and Holding—SMM/SSM Controller Multi Module Series - SMM Liebert HiPulse Liebert Products Liebert SICE 7200 Available Points Data Description Status Points (View) Output Voltage L1-L2 Output Voltage L2-L3 Output Voltage L3-L1 Output Amps L1 Output Amps L2 Output Amps L3 Power L1 Power L2 Power L3 Bypass Frequency Inverter Frequency Battery Voltage Battery Amperage Apparent Power L1 Apparent Power L2 Apparent Power L3 % Load L1 % Load L2 % Load L3 % Battery Charge Battery Temperature Battery Time Remaining Alarm Points Communications Bypass Switch Open Output Switch Open Rectifier Switch Open Battery CB Open Manual Bypass Closed Bypass Absent Bypass Overvoltage Bypass Undervoltage Bypass Frequency Error Byp Phase Rotation Error Bypass SCR Failure Bypass Off Bypass Off Load On Bypass Bypass Overtemperature Rectifier Under Voltage Rectifier Block Rectifier Block Rectifier Current Limit Input Register Holding Register # of Reg. Scale Notes / Units — — — — — — — — — — — — — — — — — — — — — — 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 — — — — — — — — — 10 10 — — — — — — — — — — — V V V A A A kW kW kW Hz Hz V A kVA kVA kVA % % % — deg C Minutes — — — — — — — — — — — — — — — — — — — — 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40289 40290 40290 40290 40290 40290 40290 40290 40290 40290 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 — — — — — — — — — — — — — — — — — — — — Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 359 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-92 Liebert HiPulse™ and Liebert SICE 7200™—Input and Holding—SMM/SSM (continued) Controller Multi Module Series - SMM Liebert HiPulse Liebert Products Liebert SICE 7200 Available Points Data Description Rectifier Overtemperature Rectifier Fuse Failure Inverter Voltage Fault Inverter Disable Inverter Disable Inverter Current Limit Inverter Overtemperature Inverter Non Sync Inverter Overvoltage Inverter Undervoltage Inverter Fuse Failure Output Overvoltage Output Undervoltage Output Undervoltage Output Waveform Error Inverter Frequency Error Inverter Parallel Error Contactor Failure Battery Test Battery Test Failed Battery On Load Battery End of Discharge Boost Time Expired DC Overvoltage DC Undervoltage Battery Fuse Failure DC Overvoltage Transfer Count Block Overload Shutdown Overtemperature SD Emergency Stop Overload Present Overload Shutdown TO Display Error Display Error Inverter Over Capacity Bypass ECO Mode Fan Failure Input Register Holding Register # of Reg. Scale Notes / Units — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 40290 40290 40291 40291 40291 40291 40291 40291 40291 40291 40291 40291 40291 40292 40292 40292 40292 40292 40292 40292 40292 40292 40292 40292 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 40293 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 360 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-93 Liebert SICE 7200™—Input and Holding—SSC Controller System Control Cabinet - SSC Liebert Products Liebert SICE 7200 Available Points Input Register Holding Register # of Reg. Scale Notes / Units Output Voltage L1-L2 — 40001 1 — V Output Voltage L2-L3 — 40002 1 — V Data Description Output Voltage L3-L1 — 40003 1 — V Output Amps L1 — 40004 1 — A Output Amps L2 — 40005 1 — A Output Amps L3 — 40006 1 — A Power L1 — 40007 1 — kW Power L2 — 40008 1 — kW Power L3 — 40009 1 — kW Bypass Frequency — 40010 1 10 Hz Battery Voltage — 40012 1 — V Battery Amperage — 40013 1 — A Apparent Power L1 — 40014 1 — kVA Apparent Power L2 — 40015 1 — kVA Apparent Power L3 — 40016 1 — kVA % Load L1 — 40017 1 — % % Load L2 — 40018 1 — % % Load L3 — 40019 1 — % % Battery Charge — 40020 1 — % Battery Temperature — 40021 1 — deg C Battery Time Remaining — 40022 1 — Minutes Communications — 40289 1 — Bit 0 Bypass Switch Open — 40289 1 — Bit 1 Output Switch Open — 40289 1 — Bit 2 Battery CB Open — 40289 1 — Bit 3 Manual Bypass Closed — 40289 1 — Bit 4 Bypass Absent — 40289 1 — Bit 5 Bypass Overvoltage — 40289 1 — Bit 6 Bypass Undervoltage — 40289 1 — Bit 7 Bypass Frequency Error — 40289 1 — Bit 8 Bypass Ph Rotation Error — 40289 1 — Bit 9 Bypass SCR Failure — 40289 1 — Bit 10 Bypass Off — 40290 1 — Bit 0 Bypass Off — 40290 1 — Bit 1 Load On Bypass — 40290 1 — Bit 2 Bypass Overtemperature — 40290 1 — Bit 3 Inverter Non Sync — 40290 1 — Bit 4 Output Overvoltage — 40290 1 — Bit 5 Output Undervoltage — 40290 1 — Bit 6 Output Undervoltage — 40290 1 — Bit 7 Output Waveform Error — 40290 1 — Bit 8 Transfer Count Block — 40290 1 — Bit 9 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 361 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-93 Liebert SICE 7200™—Input and Holding—SSC (continued) Controller System Control Cabinet - SSC Liebert Products Liebert SICE 7200 Available Points Data Description Input Register Holding Register # of Reg. Scale Notes / Units Overload Shutdown — 40290 1 — Bit 10 Overtemperature Shutdown — 40291 1 — Bit 0 Emergency Stop — 40291 1 — Bit 1 Overload Present — 40291 1 — Bit 2 Overload Shutdown TO — 40291 1 — Bit 3 Display Error — 40291 1 — Bit 4 Display Error — 40291 1 — Bit 5 Invewrter Over Capacity — 40291 1 — Bit 6 Parallel Bus Open — 40291 1 — Bit 7 Battery Ground Fault — 40291 1 — Bit 8 Bypass Backfeed — 40291 1 — Bit 9 Bypass Sync Inhibited — 40291 1 — Bit 10 Bypass ECO Mode — 40291 1 — Bit 11 Fan Failure — 40291 1 — Bit 12 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 362 Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-94 Liebert Npower™—Input and Holding—IMP Controller Single Module Series - SMS Liebert Products Liebert Npower - SMS Available Points Input Register Holding Register # of Reg. Scale Notes / Units Input Voltage A-B — 40001 1 — V Input Voltage B-C — 40002 1 — V Input Voltage C-A — 40003 1 — V Data Description Status Points (View) Bypass Voltage A-B — 40004 1 — V Bypass Voltage B-C — 40005 1 — V Bypass Voltage C-A — 40006 1 — V Battery Voltage — 40007 1 — V Battery Current — 40008 1 10 A Battery Temperature — 40009 1 — deg C Output Voltage A-B — 40010 1 — V Output Voltage B-C — 40011 1 — V Output Voltage C-A — 40012 1 — V Output Current A — 40013 1 10 A Output Current B — 40014 1 10 A Output Current C — 40015 1 10 A Output kVA A — 40016 1 — kVA Output kVA B — 40017 1 — kVA Output kVA C — 40018 1 — kVA Output kW A — 40019 1 — kW Output kW B — 40020 1 — kW Output kW C — 40021 1 — kW Output Frequency — 40022 1 10 Hz Rated kVA Percentage — 40023 1 — % Rated kW Percentage — 40024 1 — % Communications Loss — 40289 1 — Bit 0 Battery Fuse Fail — 40289 1 — Bit 1 Battery Low Transfer — 40289 1 — Bit 2 DC Over Voltage Transient — 40289 1 — Bit 3 Input Phase Rotation Error — 40289 1 — Bit 4 Rectifier/Trap Fuse Fail — 40289 1 — Bit 5 Any of Rectifier / Trap Fuse Bypass Frequency Error — 40289 1 — Bit 6 Alarm Points Bypass Overload Shutdown — 40289 1 — Bit 7 Bypass Phase Rotation Error — 40289 1 — Bit 8 Inverter Over Voltage Transfer — 40289 1 — Bit 9 Inverter Fuse Fail — 40289 1 — Bit 10 Output Over Voltage Transfer — 40289 1 — Bit 11 Output Under Voltage Transfer — 40289 1 — Bit 12 SBS SCR Open — 40289 1 — Bit 13 SBS SCR Short — 40289 1 — Bit 14 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 363 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—UPS Systems Table 3-94 Liebert Npower™—Input and Holding—IMP (continued) Controller Single Module Series - SMS Liebert Products Liebert Npower - SMS Available Points Input Register Holding Register # of Reg. Scale Notes / Units Inverter Over Current Transfer — 40289 1 — Bit 15 Equipment Over Temperature — 40290 1 — Bit 0 Any of Battery / Heatsink / Ambient / Timeout Shutdown Battery Ground Fault CB Trip — 40290 1 — Bit 1 — Bit 2 Any of Input / Bypass / Output / F1 / SWGR / MM / Option / AuEPO / LBS Power Fail Data Description Power Supply Fail — 40290 1 EPO Shutdown — 40290 1 — Bit 3 Rectifier Fail — 40290 1 — Bit 4 Inverter Fail — 40290 1 — Bit 5 Hardware Shutdown — 40290 1 — Bit 6 Battery Discharge — 40290 1 — Bit 7 Input Current Imbalance — 40290 1 — Bit 8 Input Line fail — 40290 1 — Bit 9 Input Under Voltage — 40290 1 — Bit 10 Input Over Voltage — 40290 1 — Bit 11 Input Over Current — 40290 1 — Bit 12 Battery CB Open — 40290 1 — Bit 13 Bypass Sync Error — 40290 1 — Bit 14 Bypass Voltage Out of Tolerance — 40290 1 — Bit 15 Bypass Line Fail — 40291 1 — Bit 0 Inverter Over Current — 40291 1 — Bit 1 Output OF/UF — 40291 1 — Bit 2 Inverter Overload — 40291 1 — Bit 3 Any of Inverter Phase A / B / C Overload Excessive Auto Retransfer — 40291 1 — Bit 4 Equipment Over Temperature Warning — 40291 1 — Bit 5 Any of AuBattery / Ambient / Heatsink / Inlet Over Temp Warning Fan Fail — 40291 1 — Bit 6 Any of Power Pole Fan 1 / 2 / 3, Primary Fan 1 / 2 / 3 and System Fan Fail SBS Unable — 40291 1 — Bit 7 Inverter Off By User — 40291 1 — Bit 8 Battery low Warning — 40291 1 — Bit 9 Battery Test Fail — 40291 1 — Bit 10 User Shutdown — 40291 1 — Bit 11 Load On Bypass — 40291 1 — Bit 12 Input Contact Alarms — 40291 1 — Bit 13 Any of Input Contact 1-8 Alarms Generic Alarms — 40291 1 — Bit 14 Any other alarm conditions that are not mapped Bypass Overload — 40291 1 — Bit 15 Any of Bypass A / B / C Overload If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 364 Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products 3.4 Battery Monitoring Products Table 3-95 Alber® BDSU™—Status and Coil Status Coil Number of Bits Notes / Units 10001-10032 — 1 Active on Alarm High Ambient Temperature String 1 - 32 10033-10064 — 1 Active on Alarm Low Ambient Temperature String 1 - 32 10065-10096 — 1 Active on Alarm Low Ambient Temperature Probe Two String 1 - 32 10097-10128 — 1 Active on Alarm High Ambient Temperature Probe Two String 1 - 32 10129-10160 — 1 Active on Alarm Low Overall Voltage String 1 - 32 10161-10192 — 1 Active on Alarm High Overall Voltage String 1 - 32 10193-10224 — 1 Active on Alarm High Battery String Current String 1 - 32 10225-10256 — 1 Active on Alarm Low Battery String Float Current String 1 - 32 10257-10288 — 1 Active on Alarm High Battery String Float Current String 1 - 32 10289-10320 — 1 Active on Alarm High Battery String Ripple Current String 1 - 32 10321-10352 — 1 Active on Alarm Battery String Discharge Detected String 1 - 32 10353-10384 — 1 Active on Alarm Maximum Discharge Time Exceeded String 1 - 32 10385-10416 — 1 Active on Alarm Discharge Low Overall Voltage String 1 - 32 10417-10448 — 1 Active on Alarm Discharge Low Cell Voltage String 1 - 32 10449-10480 — 1 Active on Alarm Discharge High Battery String Current String 1 - 32 10481-10512 — 1 Active on Alarm Excessive Cell to Cell Temperature Deviation String 1 - 32 10513-10544 — 1 Active on Alarm Excessive Cell to Ambient Temperature Deviation String 1 - 32 10545-10576 — 1 Active on Alarm Thermal Runaway Detected String 1 - 32 10577-10608 — 1 Active on Alarm Battery String Equalize String 1 - 32 10609-10640 — 1 Active on Alarm Battery String Offline String 1 - 32 10641-10672 — 1 Active on Alarm Thermal Runaway Cell to Ambient Temperature Event String 1 - 32 13233-13264 — 1 Active on Alarm Thermal Runaway Cell to Cell Temperature Event String 1 - 32 13265-13296 — 1 Active on Alarm Thermal Runaway Charger Current Level One Event String 1 - 32 13297-13328 — 1 Active on Alarm Data Description Battery Entity Battery Discharging Battery 1 - 32 String Entity 365 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products Table 3-95 Alber® BDSU™—Status and Coil (continued) Status Coil Number of Bits Notes / Units Thermal Runaway Charger Current Level Two Event String 1 - 32 13329-13360 — 1 Active on Alarm Ground Fault Detected String 1 - 32 14041-14072 — 1 Active on Alarm Low Cell Voltage Cell 1 - 320 10673-10992 — 1 Active on Alarm High Cell Voltage Cell 1 - 320 10993-11312 — 1 Active on Alarm Low Cell Temperature Cell 1 - 320 11313-11632 — 1 Active on Alarm High Cell Temperature Cell 1 - 320 11633-11952 — 1 Active on Alarm Low Internal Resistance Cell 1 - 320 11953-12272 — 1 Active on Alarm High Internal Resistance Cell 1 - 320 12273-12592 — 1 Active on Alarm High Intercell Resistance Cell 1 - 320 12593-12912 — 1 Active on Alarm Discharge Low Cell Voltage Cell 1 - 320 12913-13232 — 1 Active on Alarm Intertier Resistance High Cell 1 - 320 13361-13680 — 1 Active on Alarm Low Cell Voltage Cell 321 - 360 13681-13720 — 1 Active on Alarm High Cell Voltage Cell 321 – 360 13721-13760 — 1 Active on Alarm Low Cell Temperature Cell 321 – 360 13761-13800 — 1 Active on Alarm High Cell Temperature Cell 321 – 360 13801-13840 — 1 Active on Alarm Low Internal Resistance Cell 321 – 360 13841-13780 — 1 Active on Alarm High Internal Resistance Cell 321 – 360 13881-13920 — 1 Active on Alarm High Intercell Resistance Cell 321 – 360 13921-12860 — 1 Active on Alarm Discharge Low Cell Voltage Cell 321 – 360 13961-14000 — 1 Active on Alarm Intertier Resistance High Cell 321 - 360 14001-14040 — 1 Active on Alarm Data Description Cell Entity (Cells 1 – 320) Cell Entity (Cells 321 – 360) Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 366 Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products Table 3-96 Alber® BDSU™—Input and Holding Data Description Input Register Holding Register # of Reg. Scale Notes / Units Battery Measurement and Control 30385 — 1 — 1 = Normal Operation 2 = StartUp 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation Battery Name Battery 1 - 32 30386-31057 — 21 — Each 16-bit register is a single Unicode character of a null terminated string Battery Rating Battery 1 - 32 31186-31217 — 1 — Units : AH Battery Time Remaining Battery 1 - 32 31058-31121 — 2 — Units : sec Battery Discharge Time Battery 1 - 32 31122-31185 — 2 — Units : sec Ordinal Position of Battery Battery 1 - 32 31218-31249 — 1 — — Battery String Name String 1 - 32 31250-31921 — 21 — Each 16-bit register is a single Unicode character of a null terminated string Installation Date String 1 - 32 33170-33233 — 2 — Secs since Epoch(UTC) Cell/Monobloc Rating String 1 - 32 33234-33265 — 1 — Units : AH String Ambient Temperature 1 String 1 - 32 31922-31953 — 1 Scale : x / 10 Units : deg C String Ambient Temperature 2 String 1 - 32 31954-31985 — 1 Scale : x / 10 Units : deg C String Ambient Temperature 1 String 1 - 32 31986-32017 — 1 Scale : x / 10 Units : deg F String Ambient Temperature 2 String 1 - 32 32018-32049 — 1 Scale : x / 10 Units : deg F String Overall Voltage String 1 - 32 32050-32081 — 1 Scale : x / 10 Units : VDC String Current String 1 - 32 32082-32113 — 1 — Units : A DC Float Current String 1 - 32 32114-32145 — 1 — Units : mA DC Ripple Current String 1 - 32 32146-32177 — 1 — Units : A AC Total Active Alarms on a Battery String String 1 - 32 32178-32209 — 1 — Units : 0 Discharge State String 1 - 32 32210-32241 — 1 — 0 = Not In Progress 1 = In Progress Battery String Discharge Time String 1 - 32 32338-32401 — 2 — Units : sec Cell to Cell Temperature Deviation Threshold String 1 - 32 33042-33073 — 1 — Units : deg C System Status Battery Entity String Entity If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 367 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products Table 3-96 Alber® BDSU™—Input and Holding (continued) Input Register Holding Register # of Reg. Scale Notes / Units Cell to Cell Temperature Deviation Threshold String 1 - 32 33074-33105 — 1 — Units : deg F Cell to Ambient Temperature Deviation Threshold String 1 - 32 33106-33137 — 1 — Units : deg C Cell to Ambient Temperature Deviation Threshold String 1 - 32 33138-33169 — 1 — Units : deg F — 43490-43521 1 — 2 = Reset 4 = Acknowledge Battery String Time-To-Go String 1 - 32 32242-32305 — 2 — Units : min Amp-Hours Remaining in Battery String String 1 - 32 32306-32337 — 1 — Units : AH Low Ambient Temperature Global Threshold String 1 - 32 32402-32433 — 1 Scale : x / 10 Units : deg C Low Ambient Temperature Global Threshold String 1 - 32 32434-32465 — 1 Scale : x / 10 Units : deg F High Ambient Temperature Global Threshold String 1 - 32 32466-32497 — 1 Scale : x / 10 Units : deg C High Ambient Temperature Global Threshold String 1 - 32 32498-32529 — 1 Scale : x / 10 Units : deg F Battery String Overall Voltage Low Threshold String 1 - 32 32530-32561 — 1 Scale : x / 10 Units : VDC Battery String Overall Voltage High Threshold String 1 - 32 32562-32593 — 1 Scale : x / 10 Units : VDC Battery String Current High Threshold String 1 - 32 32594-32625 — 1 — Units : A DC Battery String Float Current Low Threshold String 1 - 32 32626-32657 — 1 — Units : mA DC Battery String Float Current High Threshold String 1 - 32 32658-32689 — 1 — Units : mA DC Battery String Ripple Current High Threshold String 1 - 32 32690-32721 — 1 — Units : A AC Cell Voltage Low Global Threshold String 1 - 32 32722-32753 — 1 Scale : x/ 1000 Units : VDC Cell Voltage High Global Threshold String 1 - 32 32754-32785 — 1 Scale : x/ 1000 Units : VDC Cell Temperature Low Global Threshold String 1 - 32 32786-32817 — 1 Scale : x / 10 Units : deg C Cell Temperature Low Global Threshold String 1 - 32 32818-32849 — 1 Scale : x / 10 Units : deg F Cell Temperature High Global Threshold String 1 - 32 32850-32881 — 1 Scale : x / 10 Units : deg C Data Description Battery String Alarm Reset or Acknowledge String 1 - 32 If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 368 Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products Table 3-96 Alber® BDSU™—Input and Holding (continued) Input Register Holding Register # of Reg. Cell Temperature High Global Threshold String 1 - 32 32882-32913 — Internal Resistance Low Global Threshold String 1 - 32 32914-32945 Internal Resistance High Global Threshold String 1 - 32 Scale Notes / Units 1 Scale : x / 10 Units : deg F — 1 — Units : microOhm 32946-32977 — 1 — Units : microOhm Intercell Resistance High Global Threshold String 1 - 32 32978-33009 — 1 — Units : microOhm Intertier Resistance High Global Threshold String 1 - 32 33010-33041 — 1 — Units : microOhm Cell to Cell Temperature Deviation Threshold String 1 - 32 39027-39058 — 1 Scale : x / 10 Units : deg C Cell to Cell Temperature Deviation Threshold String 1 - 32 39059-39090 — 1 Scale : x / 10 Units : deg F Cell to Ambient Temperature Deviation Threshold String 1 - 32 39091-39122 — 1 Scale : x / 10 Units : deg C Cell to Ambient Temperature Deviation Threshold String 1 - 32 39123-39154 — 1 Scale : x / 10 Units : deg F Discharge Low Cell Voltage Threshold String 1 - 32 33266-33297 — 1 Scale : x/ 1000 Units : VDC Discharge Low Overall Voltage Threshold String 1 - 32 33298-33329 — 1 Scale : x / 10 Units : VDC Discharge Battery String Current High Threshold String 1 - 32 33330-33361 — 1 — Units : A DC Discharge Maximum Time String 1 - 32 33362-33393 — 1 — Units : min Startup Date String 1 - 32 33394-33457 — 2 — Secs since Epoch(UTC) Battery String Commissioned Status String 1 - 32 33458-33489 — 1 — 0 = Not Commissioned 1 = Commissioned Cell to Cell Temperature Deviation Threshold String 1 - 32 39027-39058 — 1 Scale : x / 10 Units : deg C Cell to Cell Temperature Deviation Threshold String 1 - 32 39059-39090 — 1 Scale : x / 10 Units : deg F Cell to Ambient Temperature Deviation Threshold String 1 - 32 39091-39122 — 1 Scale : x / 10 Units : deg C Cell to Ambient Temperature Deviation Threshold String 1 - 32 39123-39152 — 1 Scale : x / 10 Units : deg F Ordinal Position of String String 1 - 32 33522-33553 — 1 — — Index of Parent Battery String 1 - 32 33554-33585 — 1 — — Data Description If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 369 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products Table 3-96 Alber® BDSU™—Input and Holding (continued) Input Register Holding Register # of Reg. Cell Voltage Cell 1 - 320 33586-33905 — Cell Temperature Cell 1 - 320 33906-34225 Cell Temperature Cell 1 - 320 Scale Notes / Units 1 Scale : x/ 1000 Units : VDC — 1 Scale : x / 10 Units : deg C 34226-34545 — 1 Scale : x / 10 Units : deg F Internal Resistance Value Cell 1 - 320 34546-34865 — 1 — Units : microOhm Intercell Resistance Value Cell 1 - 320 34866-35185 — 1 — Units : microOhm Cell Voltage Low Threshold Cell 1 - 320 35186-35505 — 1 Scale : x/ 1000 Units : VDC Cell Voltage High Threshold Cell 1 - 320 35506-35825 — 1 Scale : x/ 1000 Units : VDC Cell Temperature Low Threshold Cell 1 - 320 35826-36145 — 1 Scale : x / 10 Units : deg C Cell Temperature Low Threshold Cell 1 - 320 36146-36465 — 1 Scale : x / 10 Units : deg F Cell Temperature High Threshold Cell 1 - 320 36466-36785 — 1 Scale : x / 10 Units : deg C Cell Temperature High Threshold Cell 1 - 320 36786-37105 — 1 Scale : x / 10 Units : deg F Internal Resistance Low Threshold Cell 1 - 320 37106-37425 — 1 — Units : microOhm Internal Resistance High Threshold Cell 1 - 320 37426-37745 — 1 — Units : microOhm Intercell Resistance High Threshold Cell 1 - 320 37746-38065 — 1 — Units : microOhm Ordinal Position of Cell Cell 1 - 320 38066-38385 — 1 — — Index of Parent String Cell 1 - 320 38386-38705 — 1 — Index of Parent Battery Cell 1 - 320 38706-39025 — 1 — Cell Voltage Cell 321 - 360 39155-39194 — 1 Scale : x/ 1000 Units : VDC Cell Temperature Cell 321 – 360 39195-39234 — 1 Scale : x / 10 Units : deg C Cell Temperature Cell 321 – 360 39235-39274 — 1 Scale : x / 10 Units : deg F Internal Resistance Value Cell 321 – 360 39275-39314 — 1 — Units : microOhm Intercell Resistance Value Cell 321 – 360 39315-39354 — 1 — Units : microOhm Cell Voltage Low Threshold Cell 321 – 360 39355-39394 — 1 Scale : x/ 1000 Units : VDC Data Description Cell Entity (Cells 1 – 320) Cell Entity (Cells 321 – 360) If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 370 Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products Table 3-96 Alber® BDSU™—Input and Holding (continued) Input Register Holding Register # of Reg. Cell Voltage High Threshold Cell 321 – 360 39395-39434 — Cell Temperature Low Threshold Cell 321 – 360 39435-39474 Cell Temperature Low Threshold Cell 321 – 360 Scale Notes / Units 1 Scale : x/ 1000 Units : VDC — 1 Scale : x / 10 Units : deg C 39475-39514 — 1 Scale : x / 10 Units : deg F Cell Temperature High Threshold Cell 321 - 360 39515-39554 — 1 Scale : x / 10 Units : deg C Cell Temperature High Threshold Cell 321 – 360 39555-39594 — 1 Scale : x / 10 Units : deg F Internal Resistance Low Threshold Cell 321 – 360 39595-39634 — 1 — Units : microOhm Internal Resistance High Threshold Cell 321 – 360 39635-39674 — 1 — Units : microOhm Intercell Resistance High Threshold Cell 321 – 360 39675-39714 — 1 — Units : microOhm Ordinal Position of Cell Cell 321 – 360 39715-39754 — 1 — — Index of Parent String Cell 321 – 360 39755-39794 — 1 — — Index of Parent Battery Cell 321 - 360 39795-39834 — 1 — — Data Description Device Status and Control Group Status 39026 — 1 — 1 = Normal Operation 2 = StartUp 4 = Unknown - No System Support for System Status 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation 64 = Unknown Communication Failure 39998 49998 2 — Secs since Epoch(UTC) UXCM Device System Date and Time If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value. 371 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide Modbus RTU and Modbus TCP Protocols—Battery Monitoring Products Page intentionally left blank. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 372 BACnet Communications—BACnet Protocol Implementation Conformance Statement 4.0 BACnet Communications 4.1 BACnet Protocol Implementation Conformance Statement The Liebert IntelliSlot IS-UNITY-DP™, IS-WEBADPT, and IS-IPBML cards provide BACnet IP to Emerson Network Power® devices via the BACnet protocol. The IS-UNITY-DP card supports the BACnet MSTP protocol as well. Data points of the managed device are mapped to BACnet objects that are automatically created in the card when the device is discovered. The BACnet implementation does not include a BACnet Broadcast Management Device (BBMD). The IS-UNITY-DP and IS-IPBML cards support Foreign Device Registration. They allow you to register as a Foreign Device, add the IP address of the BBMD, and set the Foreign Device Time-to-Live. The BACnet protocol support in the IS-UNITY-DP card has been tested by the BACnet Testing Laboratories (BTL) and certified to be compliant with the BACnet protocol standards. The BACnet Protocol Implementation Conformance Statement for the IS-UNITY-DP card is available to download from our public product website found here. The following sections contain the BACnet implementation listings of Services and Objects supported in the IS-WEBADPT and IS-IPBML cards. 4.1.1 Segmentation Capability Not supported. 4.1.2 Supported Services Service Alarm and Event Services • AcknowledgeAlarm • ConfirmedCOVNotification • UnconfirmedCOVNotification • ConfirmedEventNotification • UnconfirmedEventNotification • GetAlarmSummary • GetEnrollmentSummary • GetEventInformation • LifeSafetyOperation • SubscribeCOV • SubscribeCOVProperty File Access Services • AtomicReadFile • AtomicWriteFile Object Access Services • AddListElement • RemoveListElement • CreateObject • DeleteObject • ReadProperty • ReadPropertyConditional • ReadPropertyMultiple • WriteProperty • WritePropertyMultiple • ReadRange Initiate Execute — x x — — — — — — — — — — — — — — — — — x — — — — — — — — — — — — — — — — — — — x — x x x — 373 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—BACnet Protocol Implementation Conformance Statement Service Initiate Execute — — — — — — — — — x — x — — — — — — x (IS-IPBML, IS-UNITY-DP only) x (IS-IPBML, IS-UNITY-DP only) x — x — — — — — — — Remote Device Management Services • DeviceCommunicationControl • ConfirmedPrivateTransfer • UnconfirmedPrivateTransfer • ReinitializeDevice • ConfirmedTextMessage • UnconfirmedTextMessage • TimeSynchronization • UTCTimeSynchronization • Who-Has • I-Have • Who-Is • I-Am Virtual Terminal Services • VT-Open • VT-Close • VT-Data 4.1.3 Standard Object Types SupportedObject Properties Object Type X = Supported Accumulator Analog Input Analog Output Analog Value Averaging Binary Input Binary Output Binary Value Calendar Command Device Event Enrollment File Group Life Safety Point Life Safety Zone Loop Multistate Input Multistate Output Multistate Value Notification Class Program Pulse Converter Schedule Trend Log Access Door Event Log Load Control Structured View Trend Log Multiple Liebert® IntelliSlot™ Modbus/BACnet Reference Guide — X X X — X X X — — X — — — — — — X X X — — — — — — — — — — 374 BACnet Communications—BACnet Protocol Implementation Conformance Statement The following object properties are supported. NOTE All properties are read-only unless otherwise noted Device Object The Device object represents the agent (the card) rather than the managed device. Device Object Property Comments Object_Identifier The card must be configured with a unique Device Instance Number to avoid interference with other cards on the same BACnet network. Object_Name Writable. If the Device Object Name is changed from the default, the configured name must be unique to avoid interference with other cards on the same BACnet network. Object_Type — System_Status — Vendor_Name — Vendor_Identifier — Model_Name — Firmware_Revision — Application_Software_Version — Location — Description — Protocol_Version — Protocol_Revision — Protocol_Services_Supported — Protocol_Object_Types_Supported — Object_List — Max_APDU_Length_Accepted — Segmentation_Supported — Local_Time — Local_Date — UTC_Offset — Daylight_Savings_Status — APDU_Timeout Writable. Range: 1-65,535 ms. Default 3000 ms. Number_Of_APDU_Retries Writable. Range: 0-8. Default 3. Device_Address_Binding — Database_Revision — Active_COV_Subscriptions — 375 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—BACnet Protocol Implementation Conformance Statement Analog Object Analog Object Property Analog Analog Analog Input Output Value Comments Object_Identifier x x x — Object_Name x x x — Object_Type x x x — Writable if any of these conditions apply: • Object is Analog Output • Object is Analog Value and associated device Data Description is writable • Out_Of_Service is True Present_Value x x x Description x x x — Status_Flags x x x — Event_State x x x — Reliability x x x — Out_Of_Service x x x Units x Priority_Array Writable. Values: True/False. Default: False. x x x (x) Support for this property on Analog Value objects is device-dependent. Support for this property on Analog Value objects is device-dependent. The value is equal to the Present_Value so that if all entries in the Priority_Array are relinquished, the Present_Value does not change. Relinquish_Default — x (x) COV_Increment x x x See Units below this table. Writable. Default: 0.5. Units Possible values of the Units property include the BACnet Engineering Units defined in the BACnet standard, plus these additional proprietary units values: Value 256 Units Ampere-Hours 257 MilliHertz (.001 Hertz) 258 GigaHertz (1,000,000,000 Hertz) 259 PSI - Absolute 260 Total Harmonic Distortion (%) 261 Microhms (.000001 Ohms) 262 Bytes 263 Kilobytes 264 Megabytes 265 Gigabytes 266 Terabytes 267 Volt-Ampere-Hours 268 Kilovolt-Ampere-Hours 269 Volt-Ampere-Reactive-Hours 270 Kilovolt-Ampere-Reactive-Hours 271 Grams of Water per Cubic Meter of Air 272 Torrs 273 MilliTorrs Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 376 BACnet Communications—BACnet Protocol Implementation Conformance Statement Binary Object Properties Binary Object Property Binary Binary Binary Input Output Value Comments Object_Identifier x x x — Object_Name x x x — Object_Type x x x — Writable if any of these conditions apply: • Object is Binary Output • Object is Binary Value and associated device Data Description is writable • Out_Of_Service is True Present_Value x x x Description x x x — Status_Flags x x x — Event_State x x x — Reliability x x x — Out_Of_Service x x x Polarity x x — — Inactive_Text x x x — Writable. Values: True/False. Default: False. Active_text x x x Priority_Array — x (x) Support for this property on Binary Value objects is device-dependent. — Relinquish_Default — x (x) Support for this property on Binary Value objects is device-dependent. The value is equal to the Present_Value so that if all entries in the Priority_Array are relinquished, the Present_Value does not change. Multistate Object Properties Multistate Object Property Multistate Multistate Multistate Input Output Value Comments Object_Identifier x x x — Object_Name x x x — Object_Type x x x — Writable if any of these conditions apply: • Object is Multistate Output • Object is Multistate Value and associated device Data Description is writable • Out_Of_Service is True Present_Value x x x Description x x x — Status_Flags x x x — Event_State x x x — Reliability x x x — Out_Of_Service x x x Number_Of_States x x x State_Text x x x Priority_Array Relinquish_Default — — x x Writable. Values: True/False. Default: False. — — (x) Support for this property on Multistate Value objects is devicedependent. (x) Support for this property on Multistate Value objects is devicedependent. The value is equal to the Present_Value so that if all entries in the Priority_Array are relinquished, the Present_Value does not change. 377 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products 4.2 Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data Controller Liebert iCOM® v4 Data Description Object Type Instance Object Name Access Notes Extra Notes (See Table 4-2) Air: Supply Air Supply Air Over Temperature Supply Air Under Temperature Supply Air Sensor Issue Binary_Value Binary_Value Binary_Value 1 5015_1_1 2 5019_1_1 3 5026_1_1 RD RD RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air: Return Air Return Air Over Temperature Return Air Under Temperature Return Air Sensor Issue Binary_Value Binary_Value Binary_Value 14 15 16 5023_1_1 5335_1_1 5147_1_1 RD RD RD Air: External Sensors Ext Air Sensor A Over Temperature Binary_Value Ext Air Sensor A Under Temperature Binary_Value 27 28 4601_1_1 4608_1_1 RD RD Ext Air Sensor A Issue Binary_Value 29 4618_1_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ambient Air Sensor Issue Binary_Value 30 5573_1_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 378 BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Instance Object Name Access Notes Extra Notes (See Table 4-2) Humidity High Return Humidity Binary_Value 41 5034_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Low Return Humidity Binary_Value 42 5036_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dew Point Over Temperature Binary_Value 43 5578_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Dew Point Under Temperature Binary_Value 44 5579_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Return Humidity Sensor Issue Binary_Value 45 5902_1 RD Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidity: External Sensors Ext Air Sensor A High Humidity Binary_Value 53 5349_1_1 RD Ext Air Sensor A Low Humidity Binary_Value 54 5351_1_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Dew Point Over Temperature Binary_Value 55 4615_1_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Under Temperature Binary_Value 56 5577_1_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressors Ext Compressor Lockout Compressor Capacity Reduced Binary_Value Binary_Value 65 66 379 5067_1 5513_1 RD RD Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Instance Object Name Access Notes Extra Notes (See Table 4-2) Compressor 1 Compressor Hours Exceeded Compressor High Head Pressure Compressor Low Suction Pressure Compressor Short Cycle Compressor Pump Down Issue Compressor Thermal Overload Dig Scroll Comp Discharge Temp Sensor Issue Dig Scroll Comp Over Temp Compressor Low Pressure Transducer Issue Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value 77 78 79 80 81 82 83 84 85 5269_1_1 5270_1_1 5271_1_1 5352_1_1 5146_1_1 5272_1_1 5354_1_1 5355_1_1 5514_1_1 RD RD RD RD RD RD RD RD RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Pressure Transducer Issue Binary_Value 86 5148_1_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Superheat Over Threshold Binary_Value 87 5604_1_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Compressor Low Differential Pressure Lockout Binary_Value 88 5903_1_1 RD Active on Alarm 6, 7, 8, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 380 BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Instance Object Name Access Notes Extra Notes (See Table 4-2) Compressor 2 Compressor Hours Exceeded Compressor High Head Pressure Compressor Low Suction Pressure Compressor Short Cycle Compressor Pump Down Issue Compressor Thermal Overload Dig Scroll Comp Discharge Temp Sensor Issue Dig Scroll Comp Over Temp Compressor Low Pressure Transducer Issue Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value 97 98 99 100 101 102 103 104 105 5269_1_2 5270_1_2 5271_1_2 5352_1_2 5146_1_2 5272_1_2 5354_1_2 5355_1_2 5514_1_2 RD RD RD RD RD RD RD RD RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor High Pressure Transducer Issue Binary_Value 106 5148_1_2 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Superheat Over Threshold Binary_Value 107 5604_1_2 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Compressor Low Differential Pressure Lockout Binary_Value 108 5903_1_2 RD Active on Alarm 6, 7, 8, 11, 12, 13, 14 381 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Instance Object Name Access Notes Extra Notes (See Table 4-2) Free Cooling/Chilled Water Free Cooling Valve Hours Exceeded Ext Free Cooling Lockout Free Cooling Temp Sensor Issue Binary_Value Binary_Value Binary_Value 117 118 119 5306_1 5361_1 5362_1 RD RD RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Reheat Hot Water / Hot Gas Valve Hours Exceeded Reheater Over Temperature Ext Reheat Lockout Binary_Value Binary_Value Binary_Value 130 131 132 5365_1 5068_1 5070_1 RD RD RD Electric Reheater 1 Electric Reheater Hours Exceeded Binary_Value 143 5368_1_1 RD Electric Reheater 2 Electric Reheater Hours Exceeded Binary_Value 154 5368_1_2 RD Electric Reheater 3 Electric Reheater Hours Exceeded Binary_Value Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 165 382 5368_1_3 RD BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Instance Object Name Access Notes Extra Notes (See Table 4-2) Humidifier Humidifier Hours Exceeded Ext Humidifier Lockout Humidifier Control Board Not Detected Humidifier Cylinder Worn Humidifier Issue Humidifier Low Water Humidifier Over Current Humidifier Under Current Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value 176 177 178 179 180 181 182 183 5037_1 5044_1 5045_1 5042_1 5043_1 5041_1 5040_1 5039_1 RD RD RD RD RD RD RD RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dehumidifier Dehumidifier Hours Exceeded Binary_Value 194 383 5038_1 RD Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Instance Object Name Access Notes Extra Notes (See Table 4-2) Fan Fan Hours Exceeded Main Fan Overload Fan Issue Binary_Value 205 Binary_Value 206 5054_1 5376_1 RD RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Binary_Value 207 4729_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Binary_Value 219 5072_1 RD Active on Alarm 1, 2, 4, 6, 10 Condensers Condenser VFD Issue Ext Condenser Pump High Water Binary_Value 220 5106_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 External Condenser TVSS Issue Binary_Value 1060 6105_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 External Condenser VFD Issue Binary_Value 1061 6106_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser 1 Condenser Issue Binary_Value 231 5377_1_1 RD Condenser 2 Condenser Issue Binary_Value 242 5377_1_2 RD Unit Events Customer Input 1 Customer Input 2 Binary_Value Binary_Value Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 253 254 384 4270_1 4271_1 RD RD BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Customer Input 3 Customer Input 4 Ext Loss of Air Blower Ext Loss of Flow Ext Standby Glycol Pump On BMS Communications Timeout Ext Standby Unit On Clogged Air Filter Loss of Air Flow Service Required Master Unit Communication Lost RAM Battery Issue Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Instance 255 256 257 258 259 260 261 262 263 264 265 266 385 Object Name 4272_1 4273_1 5415_1 5105_1 5107_1 5115_1 5416_1 5118_1 5053_1 4726_1 5120_1 5119_1 Access RD RD RD RD RD RD RD RD RD RD RD RD Notes Extra Notes (See Table 4-2) Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Shutdown - Loss Of Power High Power Shutdown Smoke Detected Supply Chilled Water Loss of Flow Supply Chilled Water Over Temp Unit Code Missing Unit Communication Lost Water Leakage Detector Sensor Issue Water Under Floor Ext Over Temperature Instance Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value 267 268 269 270 271 272 273 274 275 276 Object Name 4714_1 5121_1 4720_1 4980_1 4626_1 5418_1 5419_1 5114_1 4723_1 5104_1 Access RD RD RD RD RD RD RD RD RD RD Notes Extra Notes (See Table 4-2) Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 External Fire Detected Binary_Value 277 5108_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unspecified General Event Binary_Value 278 5588_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 386 BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Extra Notes (See Table 4-2) Object Type Instance Object Name Access Notes Temperature Control Sensor Issue Binary_Value 279 5617_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Airflow Sensor Issue Binary_Value 280 5906_1 RD Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Ext Air Damper Position Issue Binary_Value 281 5907_1 RD Active on Alarm 3, 5, 6, 7, 8, 9, 11, 12, 13, 14 Ext Power Source A Failure Binary_Value 282 5908_1 RD Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Ext Power Source B Failure Binary_Value 283 5909_1 RD Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Mixed Mode Lockout Binary_Value 284 5924_1 RD Active on Alarm 6, 7, 8, 11, 12, 13, 14 Binary_Value 288 4703_1_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Binary_Value 299 4703_1_2 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Events: Chilled Water Valve 1 Chilled Water Control Valve Failure Unit Events: Chilled Water Valve 2 Chilled Water Control Valve Failure Unit Events: Messages Unit Off Unit On Unit Partial Shutdown Unit Shutdown Unit Standby Binary_Value Binary_Value Binary_Value Binary_Value Binary_Value 310 311 312 313 314 387 5110_1_1 5109_1_1 5112_1_1 5113_1_1 5111_1_1 RD RD RD RD RD Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Object Type Maintenance Due Maintenance Completed Instance Binary_Value Binary_Value 315 316 Object Name 5116_1_1 5117_1_1 Access RD RD Notes Extra Notes (See Table 4-2) Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Events: iCOM DO Board 1 Digital Output Board Not Detected Binary_Value 327 5417_1_1 RD Unit Events: iCOM DO Board 2 Digital Output Board Not Detected Binary_Value 338 5417_1_2 RD Unit Events: iCOM DO Board 3 Binary_Value 349 5417_1_3 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Remote Sensor Average Over Temperature Binary_Value 361 5593_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Average Under Temperature Binary_Value 362 5594_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Average Over Temperature Binary_Value 363 5595_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Average Under Temperature Binary_Value 364 5596_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature Binary_Value 376 5597_1_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature Binary_Value 377 5598_1_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 10, 11, 12, 13, 14 Digital Output Board Not Detected Remote Sensors Remote Sensor 1 Remote Sensor Issue Binary_Value Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 378 388 5060_1_1 RD BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Extra Notes (See Table 4-2) Object Type Instance Object Name Access Notes Remote Sensor Over Temperature Binary_Value 390 5597_1_2 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature Binary_Value 391 5598_1_2 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue Binary_Value 392 5060_1_2 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temperature Binary_Value 502 5597_1_10 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temperature Binary_Value 503 5598_1_10 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Issue Binary_Value 504 5060_1_10 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Air Economizer Emergency Override Binary_Value 516 5600_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor 2 Remote Sensor 10 Air Economizer Binary_Value 517 5601_1 RD Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Binary_Value 540 5625_1 RD Active on Alarm 4, 6, 7, 8, 11, 13, 14 Static Pressure Sensor Issue Binary_Value 563 5629_1 RD Active on Alarm 3, 5, 6, 7, 8, 9, 11, 12, 13, 14 High Static Pressure Binary_Value 564 5630_1 RD Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Low Static Pressure Binary_Value 565 5631_1 RD Active on Alarm 3, 5, 6, 7, 8, 11, 12, 13, 14 Static Pressure Sensor Out of Range Binary_Value 566 5910_1 RD Active on Alarm 3, 5, 6, 7, 8, 9, 11, 12, 13, 14 Binary_Value 623 5636_1 RD Active on Alarm 4, 6, 7, 8, 11, 13, 14 Air Economizer Reduced Airflow Electronic Expansion Valves EEV Unspecified General Event Static Pressure EconoPhase Pump Unspecified General Event 389 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Extra Notes (See Table 4-2) Object Type Instance Object Name Access Notes Input Undervoltage Binary_Value 1001 5568_1 RD Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost Binary_Value 1040 5967_1 RD Active on Alarm 5, 8, 11, 12, 13, 14 Input Undervoltage Binary_Value 1002 5568_2 RD Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost Binary_Value 1041 5967_2 RD Active on Alarm 5, 8, 11, 12, 13, 14 Input Undervoltage Binary_Value 1006 5568_6 RD Active on Alarm 5, 8, 11, 12, 13, 14 Modbus Power Meter Communication Lost Binary_Value 1045 5967_6 RD Active on Alarm 5, 8, 11, 12, 13, 14 Fluid Temperature Sensor Issue Binary_Value 1021 5911_1 RD Active on Alarm 5, 8, 11, 12, 13, 14 Fluid Flow Sensor Issue Binary_Value 1022 5912_1 RD Active on Alarm 5, 8, 11, 12, 13, 14 Fluid Temperature Sensor Issue Binary_Value 1031 5911_2 RD Active on Alarm 5, 8, 11, 12, 13, 14 Fluid Flow Sensor Issue Binary_Value 1032 5912_2 RD Active on Alarm 5, 8, 11, 12, 13, 14 Binary_Value 1050 5966_1_1 RD Active on Alarm 5, 8, 11, 12, 13, 14 Binary_Value 643 5637_1 RD Active on Alarm 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Outside Air Temp Out of Operating Range Binary_Value 1082 5536_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Control Board Issue Binary_Value 1084 5537_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Outside Air Temp Sensor Issue Binary_Value 1086 5535_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Communication Lost Binary_Value 1088 5531_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Power Measurement 1 Power Measurement 2 Power Measurement 6 Fluid 1 Fluid 2 Air: Auxiliary Air Aux Air Temp Device Communication Lost Liebert Condensers Condenser Unit Unspecified General Event Liebert Condenser 1 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 390 BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Condenser Remote Shutdown Extra Notes (See Table 4-2) Object Type Instance Object Name Access Notes Binary_Value 1090 6100_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Binary_Value 218 5073_1_1 RD Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Condenser Outside Air Temp Out of Operating Range Binary_Value 1083 5536_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Control Board Issue Binary_Value 1085 5537_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Outside Air Temp Sensor Issue Binary_Value 1087 5535_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Communication Lost Binary_Value 1089 5531_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Remote Shutdown Binary_Value 1091 6100_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser TVSS Issue Binary_Value 1092 5073_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Circuit Unspecified General Event Binary_Value 644 5638_1_1 RD Active on Alarm 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Refrigerant Pressure Sensor Issue Binary_Value 1104 5541_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Under Threshold Binary_Value 1106 5540_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Over Threshold Binary_Value 1108 5539_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temp Sensor Issue Binary_Value 1110 5544_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Under Temp Binary_Value 1112 5543_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser TVSS Issue Liebert Condenser 2 Liebert Condenser Circuit 1 391 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Extra Notes (See Table 4-2) Object Type Instance Object Name Access Notes Binary_Value 1114 5542_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Max Fan Speed Override Binary_Value 1116 5545_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Over Temp Liebert Condenser Circuit 2 Condenser Circuit Unspecified General Event Binary_Value 896 5638_1_2 RD Active on Alarm Condenser Refrigerant Pressure Sensor Issue Binary_Value 1105 5541_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Under Threshold Binary_Value 1107 5540_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Over Threshold Binary_Value 1109 5539_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temp Sensor Issue Binary_Value 1111 5544_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Under Temp Binary_Value 1113 5543_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Over Temp Binary_Value 1115 5542_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Max Fan Speed Override Binary_Value 1117 5545_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Binary_Value 1128 5277_1_1_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Binary_Value 1129 5277_1_1_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Binary_Value 1131 5277_1_1_4 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Binary_Value 1132 5277_1_2_1 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Liebert Condenser 1: Fan 1 Condenser Fan Issue Liebert Condenser 1: Fan 2 Condenser Fan Issue Liebert Condenser1: Fan 4 Condenser Fan Issue Liebert Condenser 2: Fan 1 Condenser Fan Issue Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 392 BACnet Communications—Thermal Management Products Table 4-1 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™ Binary Data (continued) Controller Liebert iCOM® v4 Data Description Extra Notes (See Table 4-2) Object Type Instance Object Name Access Notes Binary_Value 1133 5277_1_2_2 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Binary_Value 1135 5277_1_2_4 RD Active on Alarm 3, 5, 7, 8, 9, 11, 12, 13, 14 Compressor 1B Thermal Overload Binary_Value 1146 6092_1 RD Active on Alarm 9 Compressor 2B Thermal Overload Binary_Value 1147 6093_1 RD Active on Alarm 9 Compressor 1B Hours Exceeded Binary_Value 1148 6094_1 RD Active on Alarm 9 Compressor 2B Hours Exceeded Binary_Value 1149 6095_1 RD Active on Alarm 9 Team Static Pressure Sensor Failure Binary_Value 1150 6303_1 RD Active on Alarm 9 Heating Lockout Binary_Value 1151 6304_1 RD Active on Alarm 9 Free Cooling Stopped - High Room Temp Binary_Value 1152 6305_1 RD Active on Alarm 9 Binary_Value 1163 6306_1_1 RD Active on Alarm 9 Binary_Value 1174 6309_1_1 RD Active on Alarm 9 Binary_Value 1185 6309_1_2 RD Active on Alarm 9 Binary_Value 1196 6309_1_3 RD Active on Alarm 9 Binary_Value 1207 6310_1 RD Active on Alarm 9 Liebert Condenser 2: Fan 2 Condenser Fan Issue Liebert Condenser 2: Fan 4 Condenser Fan Issue PCW-PDX PCW-PDX - Cold Aisle Cold Aisle Temperature/Humidity Team Sensor Failure PCW-PDX - Cold Aisle Sensor 1 Cold Aisle Air Sensor Failure PCW-PDX Cold Aisle Sensor 2 Cold Aisle Air Sensor Failure PCW-PDX Cold Aisle Sensor 3 Cold Aisle Air Sensor Failure Chilled Water Chilled Water Inlet Temperature Control Active Chilled Water - Chilled Water Circuit 1 Chilled Water Inlet Temperature Sensor Failure Binary_Value 1218 6313_1_1 RD Active on Alarm Chilled Water Outlet Temperature Sensor Failure Binary_Value 1219 6314_1_1 RD Active on Alarm Chilled Water Flow Meter Sensor Failure Binary_Value 1220 6315_1_1 RD Active on Alarm Chilled Water - Chilled Water Circuit 2 Chilled Water Inlet Temperature Sensor Failure Binary_Value 1231 6313_1_2 RD Active on Alarm Chilled Water Outlet Temperature Sensor Failure Binary_Value 1232 6314_1_2 RD Active on Alarm Chilled Water Flow Meter Sensor Failure Binary_Value 1233 6315_1_2 RD Active on Alarm 393 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-2 Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Extra Notes key to Table 4-1 Description This point is supported on: iCOM controller version 1.04.042.STD This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version 2.00.12R (for Japan and China – language corrections only) This point is supported on: iCOM controller version 2.01.29.07R This point is supported on: iCOM controller version 2.02.21R This point is supported on: iCOM controller version 2.01.45R This point is supported on: iCOM controller version 2.03.27.06R This point is supported on: iCOM controller version 2.03.33R This point is supported on: iCOM controller version 2.04.32R This point is supported on: iCOM controller version A9HB-1.04.23-R (Similar to Liebert PDX and to be replaced by separate family branch.) This point is supported on: iCOM controller version 1.04.37O-STD This point is supported on: iCOM controller version 2.05.12T This point is supported on: iCOM controller version 2.01.53R This point is supported on: iCOM controller version 2.04.???R (TBD) This point is supported on: iCOM controller version 2.05.19R Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-4) Air Air Temperature Set Point Air Temperature Set Point Analog_Value Analog_Value Air Temperature Proportional Band Analog_Value Air Temperature Proportional Band Analog_Value Air Temperature Dead Band Air Temperature Dead Band Analog_Value Analog_Value 1 5008_1 10001 2 5325_1 10002 3 5325_1_deg_F 5011_1 10003 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 5008_1_deg_F 394 5011_1_deg_F RW RW RW RW RW RW Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Air Temperature Control Integration Time Today's High Air Temperature Today's High Air Temperature Today's High Air Temperature Time Today's Low Air Temperature Today's Low Air Temperature Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Today's Low Air Temperature Time Analog_Value Instance 4 Object Name 5326_1 5 5327_1 10005 6 5327_1_deg_F 5328_1 7 5329_1 10007 8 5329_1_deg_F 5330_1 Access Notes Extra Notes (see Table 4-4) Units: min 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD Units: Seconds since Midnight 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD Units: Seconds since Midnight 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW RD RD Air: Supply Air Supply Air Temperature Analog_Value 19 5002_1_1 RD Supply Air Temperature Analog_Value 10019 5002_1_1_deg_F RD Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Supply Air Temperature Set Point Analog_Value 20 5331_1_1 RW Units: deg C 1, 9, 10 Supply Air Temperature Set Point Analog_Value 10020 5331_1_1_deg_F RW Units: deg F 1, 9, 10 High Supply Air Temperature Threshold Analog_Value 21 5014_1_1 RW Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 High Supply Air Temperature Threshold Analog_Value 10021 5014_1_1_deg_F RW Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Low Supply Air Temperature Threshold Analog_Value 22 5018_1_1 RW Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 395 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Low Supply Air Temperature Threshold Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes Analog_Value 10022 5018_1_1_deg_F RW Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air: Return Air High Return Air Temperature Threshold High Return Air Temperature Threshold Low Return Air Temperature Threshold Low Return Air Temperature Threshold Analog_Value Analog_Value Analog_Value Analog_Value 33 5022_1_1 10033 34 5022_1_1_deg_F 5334_1_1 10034 5334_1_1_deg_F RW RW RW RW Air: External Sensors Ext Air Sensor A Temperature Ext Air Sensor A Temperature Ext Air Sensor B Temperature Ext Air Sensor B Temperature Ext Air Sensor C Temperature Ext Air Sensor C Temperature Ext Air Sensor A Over Temp Threshold Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value 45 4594_1_1 10045 46 4597_1_1 10046 47 4597_1_1_deg_F 5336_1_1 10047 48 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 4594_1_1_deg_F 5336_1_1_deg_F 5337_1_1 396 RD RD RD RD RD RD RW BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Ext Air Sensor A Over Temp Threshold Ext Air Sensor A Under Temp Threshold Analog_Value Analog_Value Instance 10048 49 Object Name 5337_1_1_deg_F 5338_1_1 Access RW RW Notes Extra Notes (see Table 4-4) Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Under Temp Threshold Analog_Value 10049 5338_1_1_deg_F RW Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Outside Air Temperature Analog_Value 50 5574_1_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Outside Air Temperature Analog_Value 10050 5574_1_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidity Return Humidity Analog_Value 60 5028_1 RD Humidity Set Point Analog_Value 61 5029_1 RW Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Humidity Set Point Analog_Value 62 5339_1 RW Units: % RH 1, 9, 10 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: min 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidity Proportional Band Humidity Dead Band Humidity Control Integration Time High Return Humidity Threshold Low Return Humidity Threshold Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value 63 5341_1 64 5032_1 65 5342_1 66 5033_1 67 5035_1 397 RW RW RW RW RW Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Today's High Humidity Today's High Humidity Time Today's Low Humidity Analog_Value Analog_Value Analog_Value Instance 68 Object Name 5343_1 69 5344_1 70 5345_1 Access Notes Extra Notes (see Table 4-4) RD Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD Units: Seconds since Midnight 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Today's Low Humidity Time Analog_Value 71 5346_1 RD Units: Seconds since Midnight Dew Point Proportional Band Analog_Value 72 6258_1 RW Units: deg C 11, 14 Dew Point Proportional Band Analog_Value 10072 6258_1_deg_F RW Units: deg F 11, 14 Dew Point Dead Band Analog_Value 73 6259_1 RW Units: deg C 11, 14 Dew Point Dead Band Analog_Value 10073 6259_1_deg_F RW Units: deg F 11, 14 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Humidity: External Sensors Ext Air Sensor A Humidity Ext Air Sensor B Humidity Ext Air Sensor C Humidity Ext Air Sensor A High Humidity Threshold Analog_Value Analog_Value Analog_Value Analog_Value 82 4595_1_1 83 4598_1_1 84 5347_1_1 85 5348_1_1 RD RD RD RW Ext Air Sensor A Low Humidity Threshold Analog_Value 86 5350_1_1 RW Units: % RH 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Ext Air Sensor A Dew Point Temp Analog_Value 87 4596_1_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Air Sensor A Dew Point Temp Analog_Value 10087 4596_1_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 398 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes Ext Dew Point Over Temp Threshold Analog_Value 88 4614_1_1 RW Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Over Temp Threshold Analog_Value 10088 4614_1_1_deg_F RW Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Under Temp Threshold Analog_Value 89 5576_1_1 RW Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Ext Dew Point Under Temp Threshold Analog_Value 10089 5576_1_1_deg_F RW Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor 1 Compressor Hours Compressor Hours Threshold Dig Scroll Comp Discharge Temp Analog_Value Analog_Value Analog_Value 97 5267_1_1 98 5268_1_1 99 5353_1_1 RW RW RD Dig Scroll Comp Discharge Temp Analog_Value 10099 5353_1_1_deg_F RD Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Digital Scroll Compressor Loading Analog_Value 100 5619_1_1 RD Units: % 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Tandem 'B' Compressor Hours Analog_Value 101 6241_1_1 RW Units: hr 8, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor 2 Compressor Hours Compressor Hours Threshold Dig Scroll Comp Discharge Temp Analog_Value Analog_Value Analog_Value 110 5267_1_2 111 5268_1_2 112 5353_1_2 399 RW RW RD Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-4) Dig Scroll Comp Discharge Temp Analog_Value 10112 5353_1_2_deg_F RD Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Digital Scroll Compressor Loading Analog_Value 113 5619_1_2 RD Units: % 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Tandem 'B' Compressor Hours Analog_Value 114 6241_1_2 RW Units: hr 8, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling/Chilled Water Free Cooling Internal Temperature Delta Free Cooling Internal Temperature Delta Free Cooling Fluid Temperature Free Cooling Fluid Temperature Minimum Chilled Water Temp Set Point Minimum Chilled Water Temp Set Point Free Cooling Valve Hours Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value Analog_Value 123 5356_1 10123 124 5356_1_deg_F 5358_1 10124 125 5358_1_deg_F 5360_1 10125 126 5360_1_deg_F 5304_1 RW RW RD RD RW RW RW Free Cooling Valve Hours Threshold Analog_Value 127 5305_1 RW Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Chilled Water Valve Hours Analog_Value 128 5614_1 RW Units: hr 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Chilled Water Valve Operating Hours Threshold Analog_Value 129 6452_1 RW Units: hr 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 400 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-4) Reheat Hot Water / Hot Gas Valve Hours Hot Water / Hot Gas Valve Hours Threshold Analog_Value Analog_Value 138 5363_1 139 5364_1 RW RW Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Electric Reheater 1 Electric Reheater Hours Electric Reheater Hours Threshold Analog_Value Analog_Value 150 5366_1_1 151 5367_1_1 RW RW Electric Reheater 2 Electric Reheater Hours Electric Reheater Hours Threshold Analog_Value Analog_Value 162 5366_1_2 163 5367_1_2 RW RW Electric Reheater 3 Electric Reheater Hours Electric Reheater Hours Threshold Analog_Value Analog_Value 174 5366_1_3 175 5367_1_3 RW RW Humidifier Humidifier Hours Humidifier Hours Threshold Analog_Value Analog_Value 186 5369_1 187 5370_1 401 RW RW Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Infrared Humidifier Flush Rate Analog_Value Instance 188 Object Name 5445_1 Access RW Notes Extra Notes (see Table 4-4) Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Dehumidifier Dehumidifier Hours Dehumidifier Hours Threshold Analog_Value Analog_Value 199 5371_1 200 5372_1 RW RW Fan Fan Speed Maximum Set Point Fan Hours Analog_Value Analog_Value 211 5050_1 212 5374_1 RW RW Fan Hours Threshold Analog_Value 213 5375_1 RW Units: hr 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Speed Minimum Set Point Analog_Value 214 5051_1 RW Units: % 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Speed Temperature Set Point Analog_Value 215 5585_1 RW Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Speed Temperature Set Point Analog_Value 10215 5585_1_deg_F RW Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Analog Inputs 1 Analog Input Reading Analog_Value 224 5378_1 RD 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Analog Inputs 2 Analog Input Reading Analog_Value 235 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 5378_2 402 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-4) Analog Inputs 4 Analog Input Reading Analog_Value 257 5378_4 RD 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW Units: min 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: sec 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Unit Information BMS Timeout Period Analog_Value 268 5075_1 Auto Restart Delay Analog_Value 269 4710_1 RW Standby Units Analog_Value 270 5314_1 RW 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Unit Operations Return Air Temperature Set Point Analog_Value 32 5333_1 RW Units: deg C 1, 9, 10 Return Air Temperature Set Point Analog_Value 10032 5333_1_deg_F RW Units: deg F 1, 9, 10 Units: deg C 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: deg F 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Air Temperature Return Air Temperature Analog_Value Analog_Value 31 4291_1 10031 4291_1_deg_F RD RD Fan Speed Analog_Value 280 5077_1 RD Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Utilization Analog_Value 281 5078_1 RD Units: % 1, 9, 10 Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling Valve Open Position Maintenance Ramp Calculated Next Maintenance Month Analog_Value Analog_Value Analog_Value 282 5379_1 283 4870_1 284 4868_1 403 RD RD RD 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Calculated Next Maintenance Year Analog_Value Hot Water / Hot Gas Valve Open Position Reheat Utilization Humidifier Utilization Analog_Value Analog_Value Analog_Value Instance 285 Object Name 4869_1 286 5380_1 287 5080_1 288 5081_1 Access Notes Extra Notes (see Table 4-4) RD 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD RD Dehumidifier Utilization Analog_Value 289 5079_1 RD Units: % 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Cooling Capacity Analog_Value 290 5490_1 RD Units: % 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Adjusted Humidity Analog_Value 291 5606_1 RD Units: % RH 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Return Dew Point Analog_Value 292 5004_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Return Dew Point Analog_Value 10292 5004_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Actual Air Temperature Set Point Analog_Value 293 5607_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Actual Air Temperature Set Point Analog_Value 10293 5607_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Actual Humidity Set Point Analog_Value 294 5608_1 RD Units: % RH 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Dew Point Set Point Analog_Value 295 5575_1 RW Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Dew Point Set Point Analog_Value 10295 5575_1_deg_F RW Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 404 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes Cooling Control Temperature Analog_Value 296 5615_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Cooling Control Temperature Analog_Value 10296 5615_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Speed Control Temperature Analog_Value 297 5616_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Speed Control Temperature Analog_Value 10297 5616_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Unit Cooling Load Analog_Value 298 5904_1 RD Units: kW 5, 8, 11, 12, 13, 14 Unit Calculated Airflow Analog_Value 299 6134_1 RD Units: m3/h 12, 13, 14 Time System Date and Time 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Analog_Value 300 4293_1 RW Remote Sensor Over Temp Threshold Analog_Value 312 5589_1 RW Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Over Temp Threshold Analog_Value 10312 5589_1_deg_F RW Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temp Threshold Analog_Value 313 5590_1 RW Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Under Temp Threshold Analog_Value 10313 5590_1_deg_F RW Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Average Temperature Analog_Value 314 5007_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Average Temperature Analog_Value 10314 5007_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Maximum Temperature Analog_Value 315 5006_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Maximum Temperature Analog_Value 10315 5006_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Average Temperature Analog_Value 316 5591_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensors 405 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes Remote Sensor System Average Temperature Analog_Value 10316 5591_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Maximum Temperature Analog_Value 317 5592_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor System Maximum Temperature Analog_Value 10317 5592_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature Analog_Value 329 5059_1_1 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature Analog_Value 10329 5059_1_1_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature Analog_Value 341 5059_1_2 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature Analog_Value 10341 5059_1_2_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature Analog_Value 437 5059_1_10 RD Units: deg C 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Remote Sensor Temperature Analog_Value 10437 5059_1_10_deg_F RD Units: deg F 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Static Pressure Set Point Analog_Value 461 5626_1 RW Units: Pa 3, 5, 7, 8, 9, 11, 12, 13, 14 Unit Static Pressure Analog_Value 462 5627_1 RD Units: Pa 3, 5, 7, 8, 11, 12, 13, 14 System Static Pressure Analog_Value 463 5628_1 RD Units: Pa 3, 5, 7, 8, 9, 11, 12, 13, 14 Static Pressure Set Point Analog_Value 2121 5626_1 RW Units: Pa 3, 5, 7, 8, 9, 11, 12, 13, 14 Unit Static Pressure Analog_Value 2122 5627_1 RD Units: Pa 3, 5, 7, 8, 11, 12, 13, 14 Remote Sensor 1 Remote Sensor 2 Remote Sensor 10 Static Pressure Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 406 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes Analog_Value 2123 5628_1 RD Units: Pa 3, 5, 7, 8, 9, 11, 12, 13, 14 Pump Hours Analog_Value 523 5298_1_1 RW Units: hr 6, 7, 8, 11, 13, 14 Pump Speed Analog_Value 522 5634_1_1 RD Units: % 13, 14 Pump Inlet Refrigerant Temperature Analog_Value 535 5635_1_1 RD Units: deg C 13, 14 Pump Inlet Refrigerant Temperature Analog_Value 10535 5635_1_1_deg_F RD Units: deg F 13, 14 Pump Outlet Refrigerant Temperature Analog_Value 537 5639_1_1 RD Units: deg C 13, 14 Pump Outlet Refrigerant Temperature Analog_Value 10537 5639_1_1_deg_F RD Units: deg F 13, 14 Pump Hours Analog_Value 526 5298_1_2 RW Units: hr 6, 7, 8, 11, 13, 14 Pump Speed Analog_Value 525 5634_1_2 RD Units: % 13, 14 Pump Inlet Refrigerant Temperature Analog_Value 538 5635_1_2 RD Units: deg C 13, 14 Pump Inlet Refrigerant Temperature Analog_Value 10538 5635_1_2_deg_F RD Units: deg F 13, 14 Pump Outlet Refrigerant Temperature Analog_Value 540 5639_1_2 RD Units: deg C 13, 14 Pump Outlet Refrigerant Temperature Analog_Value 10540 5639_1_2_deg_F RD Units: deg F 13, 14 System Input RMS A-N Analog_Value 810 4096_1 RD Units: VAC 5, 8, 9, 11, 12, 13, 14 System Input RMS B-N Analog_Value 811 4098_1 RD Units: VAC 5, 8, 9, 11, 12, 13, 14 System Input RMS C-N Analog_Value 812 4100_1 RD Units: VAC 5, 8, 9, 11, 12, 13, 14 System Input RMS Current Phase A Analog_Value 813 4113_1 RD Units: A AC 5, 8, 9, 11, 12, 13, 14 System Input RMS Current Phase B Analog_Value 814 4114_1 RD Units: A AC 5, 8, 9, 11, 12, 13, 14 System Input RMS Current Phase C Analog_Value 815 4115_1 RD Units: A AC 5, 8, 9, 11, 12, 13, 14 Instantaneous Power Analog_Value 816 5901_1 RD Units: W 5, 8, 9, 11, 12, 13, 14 Energy Consumption Analog_Value 817 5900_1 RW Units: kWH 5, 8, 9, 11, 12, 13, 14 System Input RMS A-B Analog_Value 1900 4097_1 RD Units: VAC 5, 8, 9, 11, 12, 13, 14 System Static Pressure EconoPhase: Pump 1 EconoPhase: Pump 2 Power Measurement 1 407 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes System Input RMS B-C Analog_Value 1901 4099_1 RD Units: VAC 5, 8, 9, 11, 12, 13, 14 System Input RMS C-A Analog_Value 1902 4101_1 RD Units: VAC 5, 8, 9, 11, 12, 13, 14 System Input RMS A-N Analog_Value 820 4096_2 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS B-N Analog_Value 821 4098_2 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS C-N Analog_Value 822 4100_2 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS Current Phase A Analog_Value 823 4113_2 RD Units: A AC 5, 8, 11, 12, 13, 14 System Input RMS Current Phase B Analog_Value 824 4114_2 RD Units: A AC 5, 8, 11, 12, 13, 14 System Input RMS Current Phase C Analog_Value 825 4115_2 RD Units: A AC 5, 8, 11, 12, 13, 14 Instantaneous Power Analog_Value 826 5901_2 RD Units: W 5, 8, 11, 12, 13, 14 Energy Consumption Analog_Value 827 5900_2 RW Units: kWH 5, 8, 11, 12, 13, 14 System Input RMS A-B Analog_Value 1910 4097_2 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS B-C Analog_Value 1911 4099_2 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS C-A Analog_Value 1912 4101_2 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS A-N Analog_Value 860 4096_6 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS B-N Analog_Value 861 4098_6 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS C-N Analog_Value 862 4100_6 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS Current Phase A Analog_Value 863 4113_6 RD Units: A AC 5, 8, 11, 12, 13, 14 System Input RMS Current Phase B Analog_Value 864 4114_6 RD Units: A AC 5, 8, 11, 12, 13, 14 System Input RMS Current Phase C Analog_Value 865 4115_6 RD Units: A AC 5, 8, 11, 12, 13, 14 Instantaneous Power Analog_Value 866 5901_6 RD Units: W 5, 8, 11, 12, 13, 14 Energy Consumption Analog_Value 867 5900_6 RW Units: kWH 5, 8, 11, 12, 13, 14 System Input RMS A-B Analog_Value 1950 4097_6 RD Units: VAC 5, 8, 11, 12, 13, 14 Power Measurement 2 Power Measurement 10 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 408 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes System Input RMS B-C Analog_Value 1951 4099_6 RD Units: VAC 5, 8, 11, 12, 13, 14 System Input RMS C-A Analog_Value 1952 4101_6 RD Units: VAC 5, 8, 11, 12, 13, 14 Fluid Input Temperature Analog_Value 871 5897_1 RD Units: deg C 5, 8, 11, 12, 13, 14 Fluid Input Temperature Analog_Value 10871 5897_1_deg_F RD Units: deg F 5, 8, 11, 12, 13, 14 Fluid Output Temperature Analog_Value 872 5898_1 RD Units: deg C 5, 8, 11, 12, 13, 14 Fluid Output Temperature Analog_Value 10872 5898_1_deg_F RD Units: deg F 5, 8, 11, 12, 13, 14 Fluid Input Temperature Analog_Value 1871 5897_2 RD Units: deg C 5, 8, 11, 12, 13, 14 Fluid Input Temperature Analog_Value 11871 5897_2_deg_F RD Units: deg F 5, 8, 11, 12, 13, 14 Fluid Output Temperature Analog_Value 1872 5898_2 RD Units: deg C 5, 8, 11, 12, 13, 14 Fluid Output Temperature Analog_Value 11872 5898_2_deg_F RD Units: deg F 5, 8, 11, 12, 13, 14 Analog_Value 881 5899_1 RD Units: l/min 5, 8, 11, 12, 13, 14 Analog_Value 891 5899_2 RD Units: l/min 5, 8, 11, 12, 13, 14 Analog_Value 901 5905_1_1 RD Units: kW 5, 8, 11, 12, 13, 14 Analog_Value 911 5905_1_2 RD Units: kW 5, 8, 11, 12, 13, 14 Raw Auxiliary Air Temperature Analog_Value 1960 5964_1_1 RW Units: deg C 5, 8, 11, 12, 13, 14 Raw Auxiliary Air Temperature Analog_Value 11960 5964_1_1_deg_F RW Units: deg F 5, 8, 11, 12, 13, 14 Actual Auxiliary Air Temperature Analog_Value 1961 5965_1_1 RD Units: deg C 5, 8, 11, 12, 13, 14 Actual Auxiliary Air Temperature Analog_Value 11961 5965_1_1_deg_F RD Units: deg F 5, 8, 11, 12, 13, 14 Fluid 1 Fluid 2 Circuit Fluid Flow Rate Circuit 2 Fluid Flow Rate Unit Operations: Cooling Load 1 Circuit Cooling Load Unit Operations: Cooling Load 2 Circuit Cooling Load Air: Auxiliary Air 409 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Analog_Value 1981 6101_1 RD Notes Extra Notes (see Table 4-4) Liebert Condensers Expected Condenser Unit Count 3, 5, 7, 8, 9, 11, 12, 13, 14 Liebert Condensers: Low Noise Mode Condenser Low Noise Mode Max Fan Speed Analog_Value 529 5548_1_1 RW Units: % 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Normal Mode Max Fan Speed Analog_Value 530 5549_1_1 RW Units: % 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Low Noise Mode Start Time Analog_Value 531 5552_1_1 RW Units: Seconds since Midnight 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Condenser Low Noise Mode Stop Time Analog_Value 532 5553_1_1 RW Units: Seconds since Midnight 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 RW 1 = Monday 2 = Tuesday 4 = Wednesday 8 = 3, 4, 5, 6, 7, Thursday 16 = 8, 11, 12, 13, 14 Friday 32 = Saturday 64 = Sunday 1 = Monday 2 = Tuesday 4 = Wednesday 8 = 3, 4, 5, 6, 7, Thursday 16 = 8, 11, 12, Friday 32 = 13, 14 Saturday 64 = Sunday Condenser Low Noise Mode Interval Days Condenser Low Noise Mode - Full Days Analog_Value 533 5550_1_1 Analog_Value 534 5551_1_1 RW Condenser Outside Air Temperature Analog_Value 1992 5534_1_1 RD Units: deg C 3, 5, 7, 8, 11, 12, 13, 14 Condenser Outside Air Temperature Analog_Value 11992 5534_1_1_deg_F RD Units: deg F 3, 5, 7, 8, 11, 12, 13, 14 Condenser Outside Air Temperature Analog_Value 1993 5534_1_2 RD Units: deg C 3, 5, 7, 8, 11, 12, 13, 14 Condenser Outside Air Temperature Analog_Value 11993 5534_1_2_deg_F RD Units: deg F 3, 5, 7, 8, 11, 12, 13, 14 Liebert Condenser 1 Liebert Condenser 2 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 410 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes Condenser Refrigerant Pressure Analog_Value 2004 6103_1_1 RD Units: bar 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temperature Analog_Value 2006 6102_1_1 RD Units: deg C 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temperature Analog_Value 12006 6102_1_1_deg_F RD Units: deg F 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Refrigerant Pressure Analog_Value 2005 6103_1_2 RD Units: bar 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temperature Analog_Value 2007 6102_1_2 RD Units: deg C 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Supply Refrigerant Temperature Analog_Value 12007 6102_1_2_deg_F RD Units: deg F 3, 5, 7, 8, 9, 11, 12, 13, 14 Condenser Fan Speed Analog_Value 2018 5276_1_1_1 RD Units: % 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power Analog_Value 2026 5538_1_1_1 RD Units: W 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Current Analog_Value 2034 6244_1_1_1 RD Units: A AC 8, 11, 13, 14 Condenser Fan Speed Analog_Value 2019 5276_1_1_2 RD Units: % 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power Analog_Value 2027 5538_1_1_2 RD Units: W 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Current Analog_Value 2035 6244_1_1_2 RD Units: A AC 8, 11, 13, 14 Condenser Fan Speed Analog_Value 2021 5276_1_1_4 RD Units: % 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power Analog_Value 2029 5538_1_1_4 RD Units: W 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Current Analog_Value 2037 6244_1_1_4 RD Units: A AC 8, 11, 13, 14 Liebert Condenser Circuit 1 Liebert Condenser Circuit 2 Liebert Condenser 1 Fan 1 Liebert Condenser 1 Fan 2 Liebert Condenser 1 Fan 4 411 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Extra Notes (see Table 4-4) Object Type Instance Object Name Access Notes Condenser Fan Speed Analog_Value 2022 5276_1_2_1 RD Units: % 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power Analog_Value 2030 5538_1_2_1 RD Units: W 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Current Analog_Value 2038 6244_1_2_1 RD Units: A AC 8, 11, 13, 14 Condenser Fan Speed Analog_Value 2023 5276_1_2_2 RD Units: % 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power Analog_Value 2031 5538_1_2_2 RD Units: W 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Current Analog_Value 2039 6244_1_2_2 RD Units: A AC 8, 11, 13, 14 Condenser Fan Speed Analog_Value 2025 5276_1_2_4 RD Units: % 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Power Analog_Value 2033 5538_1_2_4 RD Units: W 3, 5, 7, 8, 11, 12, 13, 14 Condenser Fan Current Analog_Value 2041 6244_1_2_4 RD Units: A AC 8, 11, 13, 14 Liebert Condenser 2 Fan 1 Liebert Condenser 2 Fan 2 Liebert Condenser 2 Fan 4 PCW-PDX Actual Cold Aisle Humidity Analog_Value 2044 6085_1 RD Units: % RH 9 Actual Cold Aisle Temperature Analog_Value 2045 6086_1 RD Units: deg C 9 Actual Cold Aisle Temperature Analog_Value 12045 6086_1_deg_F RD Units: deg F 9 Cold Aisle Cascade Fan Speed Max Set Point Analog_Value 2046 6087_1 RD Units: % 9 Cold Aisle Fan Speed Min Set Point Analog_Value 2047 6088_1 RD Units: % 9 Cold Aisle Fan Speed Max Set Point Analog_Value 2048 6089_1 RD Units: % 9 Humidification Fan Speed Min Set Point Analog_Value 2049 6096_1 RD Units: % 9 Heating Fan Speed Min Set Point Analog_Value 2050 6097_1 RD Units: % 9 Dehumidification Fan Speed Min Set Point Analog_Value 2051 6098_1 RD Units: % 9 Back Draft Control Fan Speed Analog_Value 2052 6099_1 RD Units: % 9 Air Filter Differential Pressure Analog_Value 2053 6302_1 RD Units: Pa 9 Air Filter Differential Pressure Analog_Value 2213 6302_1 RD Units: Pa 9 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 412 BACnet Communications—Thermal Management Products Table 4-3 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Analog Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-4) Analog_Value 2100 6234_1 RD Units: % 9, 11, 14 Thermal Control Override Temperature Call Analog_Value 2135 6263_1 RW Units: % 11, 14 Thermal Control Override Humidity Call Analog_Value 2136 6265_1 RW Units: % 11, 14 Super Saver Super Saver Call For Cooling Thermal Control Override PCW-PDX - Cold Aisle Sensor 1 Cold Aisle Sensor Air Temperature Analog_Value 2147 6307_1_1 RD Units: deg C 9 Cold Aisle Sensor Air Temperature Analog_Value 12147 6307_1_1_deg_F RD Units: deg F 9 Cold Aisle Sensor Humidity 2148 6308_1_1 RD Units: % RH 9 Analog_Value PCW-PDX - Cold Aisle Sensor 2 Cold Aisle Sensor Air Temperature Analog_Value 2159 6307_1_2 RD Units: deg C 9 Cold Aisle Sensor Air Temperature Analog_Value 12159 6307_1_2_deg_F RD Units: deg F 9 Cold Aisle Sensor Humidity 2160 6308_1_2 RD Units: % RH 9 Analog_Value PCW-PDX - Cold Aisle Sensor 3 Cold Aisle Sensor Air Temperature Analog_Value 2171 6307_1_3 RD Units: deg C 9 Cold Aisle Sensor Air Temperature Analog_Value 12171 6307_1_3_deg_F RD Units: deg F 9 Cold Aisle Sensor Humidity 2172 6308_1_3 RD Units: % RH 9 Analog_Value Chilled Water - Chilled Water Circuit 1 Chilled Water Inlet Temperature Analog_Value 2189 6311_1_1 RD Units: deg C 9 Chilled Water Inlet Temperature Analog_Value 12189 6311_1_1_deg_F RD Units: deg F 9 Chilled Water Outlet Temperature Analog_Value 2190 6312_1_1 RD Units: deg C 9 Chilled Water Outlet Temperature Analog_Value 12190 6312_1_1_deg_F RD Units: deg F 9 Units: deg C 9 Chilled Water - Chilled Water Circuit 2 Chilled Water Inlet Temperature Analog_Value 2201 6311_1_2 RD Chilled Water Inlet Temperature Analog_Value 12201 6311_1_2_deg_F RD Units: deg F 9 Chilled Water Outlet Temperature Analog_Value 2202 6312_1_2 RD Units: deg C 9 Chilled Water Outlet Temperature Analog_Value 12202 6312_1_2_deg_F RD Units: deg F 9 Analog_Value 505 5299_1 RW Units: hr 13, 14 EconoPhase Pump Hours Threshold 413 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-4 Number Extra Notes key to Table 4-3 Description 1 This point is supported on: iCOM controller version 1.04.042.STD 2 This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version 2.00.12R (for Japan and China – language corrections only) 3 This point is supported on: iCOM controller version 2.01.29.07R 4 This point is supported on: iCOM controller version 2.02.21R 5 This point is supported on: iCOM controller version 2.01.45R 6 This point is supported on: iCOM controller version 2.03.27.06R 7 This point is supported on: iCOM controller version 2.03.33R 8 This point is supported on: iCOM controller version 2.04.32R 9 This point is supported on: iCOM controller version A9HB-1.04.23-R (Similar to Liebert PDX and to be replaced by separate family branch.) 10 This point is supported on: iCOM controller version 1.04.37O-STD 11 This point is supported on: iCOM controller version 2.05.12T 12 This point is supported on: iCOM controller version 2.01.53R 13 This point is supported on: iCOM controller version 2.04.???R (TBD) 14 This point is supported on: iCOM controller version 2.05.19R Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 414 BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-6) Protocol Server Class MultiState_Value 1 4553_1 RD 1 = UPS 2 = AIR 3 = PMP 4 = PDU 5 = MONITOR 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Air Air Temperature Control Type MultiState_Value 12 5324_1 RW 1 = Proportional 2 = Prop+Integral 3 = Intelligent Air Temperature Control Sensor MultiState_Value 13 5012_1 RW 1 = Supply 2 = Remote 3 = Return 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 1, 9, 10 Air - Supply Air Supply Air Temperature Sensor Control MultiState_Value 23 5332_1_1 RW 1 = Disabled 2 = Limit 3 = Control 4 = Temp Only MultiState_Value 34 5340_1 RW 1 = Relative 2 = Compensated 3 = Predictive 1, 9, 10 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Humidity Humidity Control Type Humidity Control Type MultiState_Value 35 5603_1 RW 1 = Relative 2 = Compensated 3 = Predictive 4 = Dew Point Humidity Control Sensor MultiState_Value 36 5618_1 RW 1 = Supply 2 = Remote 3 = Return 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 8, 11, 12, 13, 14 Compressors - Compressor 1 Compressor State MultiState_Value 45 5264_1_1 Compressor Capacity Control State MultiState_Value 46 5265_1_1 RD 1 = off 2 = on Tandem 'B' Compressor State MultiState_Value 47 6243_1_1 RD 1 = off 2 = on 415 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-6) Compressors - Compressor 2 Compressor State MultiState_Value 57 5264_1_2 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Compressor Capacity Control State MultiState_Value 58 5265_1_2 RD 1 = off 2 = on Tandem 'B' Compressor State MultiState_Value 59 6243_1_2 RD 1 = off 2 = on 8, 11, 12, 13, 14 MultiState_Value 69 5302_1 RD 1 = off 2 = on 3 = No Support 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 RW 1 = Disabled 2 = Contact 3 = Temperature 4 = Set Point 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Free Cooling/Chilled Water Free Cooling Status Free Cooling Internal Control Mode MultiState_Value 70 5581_1 Minimum Chilled Water Temp Set Point Enable MultiState_Value 71 5359_1 RW 1 = disabled 2 = enabled Main Chilled Water Valve MultiState_Value 72 5605_1 RW 1 = Valve 1 2 = Valve 2 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Free Cooling Status MultiState_Value 69 6260_1 RD 1 = off 2 = start 3 = on 11, 12, 13, 14 Free Cooling Internal Control Mode MultiState_Value 70 5357_1 RW 1 = Disabled 2 = Contact 3 = Value 1, 9, 10 RW 1 = Auto 2 = Manual 3 = Economy 4 = Delta 1, 9, 10 RW 1 = Supply 2 = Remote 3 = Return 4 = Manual 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Fan Fan Control Mode Fan Control Sensor MultiState_Value MultiState_Value 82 5373_1 83 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 5586_1 416 BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-6) Unit Information System Status Unit Operating State Unit Control Mode Unit Operating State Reason MultiState_Value MultiState_Value MultiState_Value MultiState_Value 93 4123_1 94 4706_1 95 4707_1 96 5074_1 RD 1 = Normal Operation 2 = StartUp 3 = Normal with Warning 4 = Normal with Alarm 5 = Abnormal Operation 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = off 2 = on = standby 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = Internal (Auto) 2 = External (Manual) 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = Reason Unknown 2 = Network Display 1, 2, 3, 4, 5, 3 = Alarm 6, 7, 8, 9, 4 = Schedule 10, 11, 12, 13, 14 5 = Remote System 6 = External Input 7 = Local Display Unit Operations Fan State Cooling State Free Cooling State Maintenance Tracking State Hot Water / Hot Gas State MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value 107 5381_1 108 5382_1 109 5383_1 110 5384_1 111 5385_1 417 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Electric Reheat State Dehumidifier State Humidifier State System On/Off Control Local Fan Override Local Cooling Override Local Electric Heat Override Object Type MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value Instance Object Name Access 112 5386_1 113 5387_1 114 5388_1 115 5143_1 500 6175_1 501 6176_1 502 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 6177_1 418 Notes Extra Notes (see Table 4-6) RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = off 2 = on 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RD 1 = Normal operation 2 = Increased for internal protection 3 = Decreased for internal protection 4 = Disabled for internal protection 5 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 RD 1 = Normal operation 2 = Increased for internal protection 3 = Decreased for internal protection 4 = Disabled for internal protection 5 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 RD 1 = Normal operation 2 = Increased for internal protection 3 = Decreased for internal protection 4 = Disabled for internal protection 5 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Local Humidifier Override Local Dehumidifier Override Object Type MultiState_Value MultiState_Value Instance Object Name Access 503 6178_1 504 6179_1 Notes Extra Notes (see Table 4-6) RD 1 = Normal operation 2 = Increased for internal protection 3 = Decreased for internal protection 4 = Disabled for internal protection 5 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 RD 1 = Normal operation 2 = Increased for internal protection 3 = Decreased for internal protection 4 = Disabled for internal protection 5 = Limited or disabled for low limit protection 8, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 System Event Configuration Customer Input 1 - Event Control MultiState_Value Customer Input 1 - Event Type MultiState_Value Customer Input 2 - Event Control MultiState_Value Customer Input 2 - Event Type MultiState_Value Customer Input 3 - Event Control MultiState_Value Customer Input 3 - Event Type MultiState_Value Customer Input 4 - Event Control MultiState_Value 126 4718_1 127 4719_1 128 5098_1 129 5099_1 130 5100_1 131 5101_1 132 5102_1 419 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Customer Input 4 - Event Type Ext Free Cooling Lockout Event Control Ext Free Cooling Lockout Event Type Ext Condenser Pump High Water - Event Control Ext Condenser Pump High Water - Event Type Ext Standby Glycol Pump On Event Control Ext Standby Glycol Pump On Event Type Ext Standby Unit On - Event Control Ext Standby Unit On - Event Type Ext Humidifier Lockout - Event Control Ext Humidifier Lockout - Event Type Object Type MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value Ext Loss of Flow - Event Control MultiState_Value Notes Extra Notes (see Table 4-6) RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Instance Object Name Access 133 5103_1 134 5389_1 135 5390_1 136 5122_1 137 5123_1 138 5129_1 139 5130_1 140 5391_1 141 5392_1 142 5086_1 143 5087_1 144 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 5082_1 420 BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Ext Loss of Flow - Event Type Ext Over Temperature - Event Control Ext Over Temperature - Event Type Ext Reheat Lockout - Event Control Ext Reheat Lockout - Event Type High Power Shutdown - Event Control High Power Shutdown - Event Type Humidifier Issue - Event Control Humidifier Issue - Event Type Object Type MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value Master Unit Communication Lost MultiState_Value - Event Control Master Unit Communication Lost MultiState_Value - Event Type Service Required - Event Control MultiState_Value Notes Extra Notes (see Table 4-6) RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Instance Object Name Access 145 5083_1 146 5090_1 147 5091_1 148 5084_1 149 5085_1 150 5141_1 151 5142_1 152 5131_1 153 5132_1 154 5133_1 155 5134_1 156 4727_1 421 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Service Required - Event Type Shutdown - Loss Of Power Event Control Shutdown - Loss Of Power Event Type Object Type MultiState_Value MultiState_Value MultiState_Value Smoke Detected - Event Control MultiState_Value Smoke Detected - Event Type Water Under Floor - Event Control Water Under Floor - Event Type MultiState_Value MultiState_Value MultiState_Value Ext Compressor Lockout - Event MultiState_Value Control Ext Compressor Lockout - Event MultiState_Value Type Clogged Air Filter - Event Control Clogged Air Filter - Event Type Ext Loss of Air Blower - Event Control MultiState_Value MultiState_Value MultiState_Value Notes Extra Notes (see Table 4-6) RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Instance Object Name Access 157 4728_1 158 4715_1 159 4716_1 160 4721_1 161 4722_1 162 4724_1 163 4725_1 164 5088_1 165 5089_1 166 5135_1 167 5136_1 168 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 5393_1 422 BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Ext Loss of Air Blower - Event Type Object Type MultiState_Value Notes Extra Notes (see Table 4-6) RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Instance Object Name Access 169 5394_1 System Event Configuration - Compressor 1 Compressor High Head Pressure - Event Control Compressor High Head Pressure - Event Type Compressor Low Suction Pressure - Event Control Compressor Low Suction Pressure - Event Type MultiState_Value MultiState_Value MultiState_Value MultiState_Value Compressor Pump Down Issue MultiState_Value Event Control Compressor Pump Down Issue MultiState_Value Event Type Compressor Short Cycle - Event MultiState_Value Control Compressor Short Cycle - Event MultiState_Value Type Compressor Thermal Overload MultiState_Value Event Control Compressor Thermal Overload MultiState_Value Event Type Dig Scroll Comp Discharge Over MultiState_Value Temp - Event Ctrl 180 5316_1_1 181 5317_1_1 182 5318_1_1 183 5319_1_1 184 5395_1_1 185 5396_1_1 186 5397_1_1 187 5398_1_1 188 5320_1_1 189 5321_1_1 190 5399_1_1 423 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Dig Scroll Comp Discharge Over MultiState_Value Temp - Event Type Notes Extra Notes (see Table 4-6) RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Instance Object Name Access 191 5400_1_1 System Event Configuration Compressor 2 Compressor High Head Pressure - Event Control Compressor High Head Pressure - Event Type Compressor Low Suction Pressure - Event Control Compressor Low Suction Pressure - Event Type MultiState_Value MultiState_Value MultiState_Value MultiState_Value Compressor Pump Down Issue MultiState_Value Event Control Compressor Pump Down Issue MultiState_Value Event Type Compressor Short Cycle - Event MultiState_Value Control Compressor Short Cycle - Event MultiState_Value Type Compressor Thermal Overload MultiState_Value Event Control Compressor Thermal Overload MultiState_Value Event Type Dig Scroll Comp Discharge Over MultiState_Value Temp - Event Ctrl 202 5316_1_2 203 5317_1_2 204 5318_1_2 205 5319_1_2 206 5395_1_2 207 5396_1_2 208 5397_1_2 209 5398_1_2 210 5320_1_2 211 5321_1_2 212 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 5399_1_2 424 BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Dig Scroll Comp Discharge Over MultiState_Value Temp - Event Type Notes Extra Notes (see Table 4-6) RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Instance Object Name Access 213 5400_1_2 System Event Configuration - Air Ext Air Sensor A Event Control MultiState_Value Return Air Sensor Event Control MultiState_Value Ext Air Sensor A High Humidity MultiState_Value Event Control Ext Air Sensor A High Humidity MultiState_Value Event Type Ext Air Sensor A Low Humidity Event Control Ext Air Sensor A Low Humidity Event Type Ext Air Sensor A Over Temp Event Control Ext Air Sensor A Over Temp Event Type Ext Air Sensor A Under Temp Event Control Ext Air Sensor A Under Temp Event Type High Return Humidity - Event Control MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value 224 5401_1_1 225 5402_1_1 226 5403_1_1 227 5404_1_1 228 5405_1_1 229 5406_1_1 230 4602_1_1 231 4603_1_1 232 4609_1_1 233 4610_1_1 234 5137_1_1 425 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label High Return Humidity - Event Type Low Return Humidity - Event Control Low Return Humidity - Event Type Return Air Over Temp - Event Control Return Air Over Temp - Event Type Return Air Under Temp - Event Control Object Type MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value MultiState_Value Notes Extra Notes (see Table 4-6) RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Instance Object Name Access 235 5138_1_1 236 5139_1_1 237 5140_1_1 238 5024_1_1 239 5025_1_1 240 5407_1_1 Return Air Under Temp - Event Type MultiState_Value 241 5408_1_1 RW 1 = Message 2 = Warning 3 = Alarm Supply Air Over/Under Temperature - Event Control MultiState_Value 242 5587_1_1 RW 1 = disabled 2 = enabled 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 System Event Configuration - Fan Fan Hours Exceeded - Event Control MultiState_Value 252 5409_1_1 Fan Hours Exceeded - Event Type MultiState_Value 253 5410_1_1 RW 1 = Message 2 = Warning 3 = Alarm Fan Issue - Event Control MultiState_Value 254 4730_1_1 RW 1 = disabled 2 = enabled 1, 9, 10 RW 1 = Message 2 = Warning 3 = Alarm 1, 9, 10 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Fan Issue - Event Type Main Fan Overload - Event Control MultiState_Value MultiState_Value 255 4731_1_1 256 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 5411_1_1 426 BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Main Fan Overload - Event Type MultiState_Value Notes Extra Notes (see Table 4-6) RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = disabled 2 = enabled 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 RW 1 = Message 2 = Warning 3 = Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14 Instance Object Name Access 257 5412_1_1 System Event Configuration - Condenser Condenser Issue - Event Control MultiState_Value Condenser Issue - Event Type MultiState_Value Condenser Issue - Event Control MultiState_Value Condenser Issue - Event Type MultiState_Value 268 5413_1_1 269 5414_1_1 280 5413_1_2 281 5414_1_2 Unit Events MultiState_Value 292 4717_1 WO 1 = Reset 2 = Acknowledge MultiState_Value 304 5580_1 RW 1 = disabled 2 = enabled 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 MultiState_Value 316 5582_1 RW 1 = disabled 2 = enabled 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 MultiState_Value 328 5583_1 RW 1 = disabled 2 = enabled 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Air Economizer Availability MultiState_Value 340 5599_1 RD 1 = Not Available 2 = Available 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 Air Economizer Control Source MultiState_Value 341 5602_1 RW 1 = disabled 2 = internal 3 = external 2, 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 System Event Acknowledge/Reset Compressors Compressor Lockout Reheat Reheater Lockout Humidifier Humidifier Lockout Air Economizer 427 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Notes Extra Notes (see Table 4-6) RD 1 = off 2 = on 7, 8, 11, 13, 14 13, 14 Instance Object Name Access EconoPhase - Pump 1 Pump State PRE Operational Mode MultiState_Value 364 5633_1_1 MultiState_Value 363 5632_1_1 RD 1 = Bootup 2 = Idle 3 = Manual 4 = Pump Automatic 5 = Test MultiState_Value 369 5633_1_2 RD 1 = off 2 = on 7, 8, 11, 13, 14 RD 1 = Bootup 2 = Idle 3 = Manual 4 = Pump Automatic 5 = Test 13, 14 1 = R22 2 = R407C 3 = R410A 3, 5, 7, 8, 11, 12, 13, 14 EconoPhase - Pump 2 Pump State PRE Operational Mode MultiState_Value 368 5632_1_2 Liebert Condensers Condenser Refrigerant Type MultiState_Value 395 5533_1 RD Liebert Condensers - Low Noise Mode 1 = Inactive 3, 4, 5, 6, 7, 2 = Active (Interval) 8, 11, 12, 13, 14 3 = Active (Full Day) Condenser Low Noise Mode State MultiState_Value 374 5546_1_1 RD Condenser Low Noise Mode Schedule Control MultiState_Value 375 5547_1_1 RW 1 = disabled 2 = enabled 3, 4, 5, 6, 7, 8, 11, 12, 13, 14 406 6104_1_1 RD 1 = false 2 = true 3, 5, 7, 8, 9, 11, 12, 13, 14 MultiState_Value 407 6104_1_2 RD 1 = false 2 = true 3, 5, 7, 8, 9, 11, 12, 13, 14 Cold Aisle Humidity Calculation Method MultiState_Value 438 6081_1 RD 1 = Highest 2 = Average 9 Cold Aisle Temperature Calculation Method MultiState_Value 439 6082_1 RD 1 = Highest 2 = Average 9 Cold Aisle Control Enable MultiState_Value 440 6083_1 RD 1 = disabled 2 = enabled 9 Cold Aisle Force Max Fan/Cooling - Ext Control MultiState_Value 441 6084_1 RD 1 = disabled 2 = enabled 9 Liebert Condensers - Condenser 1 Condenser Fan Reversal Requested MultiState_Value Liebert Condensers - Condenser 2 Condenser Fan Reversal Requested PCW-PDX Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 428 BACnet Communications—Thermal Management Products Table 4-5 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Multistate Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Extra Notes (see Table 4-6) Static Pressure Control Enable MultiState_Value 442 6090_1 RD 1 = disabled 2 = enabled Chilled Water Valve Reset Enable MultiState_Value 443 6091_1 RD 1 = disabled 2 = enabled 9 Underfloor Static Pressure Control Enable MultiState_Value 529 6300_1 RD 1 = disabled 2 = enabled 3 = visualization only 9 Return Damper Status MultiState_Value 531 6301_1 RD 1 = closed 2 = open 9 Thermal Control Override MultiState_Value 516 6261_1 RW 1 = disabled 2 = enabled 11, 14 Thermal Control Override Temperature Control Type MultiState_Value 517 6262_1 RW 1 = Cooling 2 = Heating 11, 14 Thermal Control Override Humidity Control Type MultiState_Value 518 6264_1 RW 1 = Dehumidification 2 = Humidification 11, 14 Thermal Control Override Table 4-6 Number Extra Notes key to Table 4-5 Description 1 This point is supported on: iCOM controller version 1.04.042.STD 2 This point is supported on: iCOM controller version 2.00.11R for US iCOM controller version 2.00.12R (for Japan and China – language corrections only) 3 This point is supported on: iCOM controller version 2.01.29.07R 4 This point is supported on: iCOM controller version 2.02.21R 5 This point is supported on: iCOM controller version 2.01.45R 6 This point is supported on: iCOM controller version 2.03.27.06R 7 This point is supported on: iCOM controller version 2.03.33R 8 This point is supported on: iCOM controller version 2.04.32R 9 This point is supported on: iCOM controller version A9HB-1.04.23-R (Similar to Liebert PDX and to be replaced by separate family branch.) 10 This point is supported on: iCOM controller version 1.04.37O-STD 11 This point is supported on: iCOM controller version 2.05.12T 12 This point is supported on: iCOM controller version 2.01.53R 13 This point is supported on: iCOM controller version 2.04.???R (TBD) 14 This point is supported on: iCOM controller version 2.05.19R 429 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary Data Label Data Description Actual Air Temperature Set Point The actual set point being used for air temperature control. This value may differ from [Air Temperature Set Point] if compensation is applied by the control. Actual Auxiliary Air Temperature Actual auxiliary air temperature value being used for control. This value may differ from the raw value received from the auxiliary device if filtering is applied. Actual Cold Aisle Humidity Actual humidity value being used for cold aisle humidity control. The value is calculated from multiple humidity measurements using [Cold Aisle Humidity Calculation Method]. Actual Cold Aisle Temperature Actual temperature value being used for cold aisle temperature control. The value is calculated from multiple temperature measurements using [Cold Aisle Temperature Calculation Method]. Actual Humidity Set Point The actual set point being used for humidity control. This value may differ from [Humidity Set Point] if compensation is applied by the control. Adjusted Humidity Humidity value being used for control. This value may differ from the actual measured [Return Humidity] based on several factors which may include, but are not limited to, selection of humidity control sensor and humidity control type. Air Economizer Availability Indicates if the outside air conditions are appropriate for cooling with the air economizer or glycol freecooling. Air Economizer Control Source Source of control of the air economizer. Air Economizer Emergency Override Indoor room temperature has exceeded its upper threshold and the outdoor air damper has been opened for emergency cooling. Air Economizer Reduced Airflow Air economizer filter is dirty and needs to be cleaned or replaced. Air Filter Differential Pressure Differential pressure across the air filter. Air Temperature Control Integration Time Time value used when system is under integral air temperature control. Air Temperature Control Sensor Sensor from which air temperature measurements will be used for cooling and heating control. Air Temperature Control Type Type of algorithm used to control the system's output air temperature. Air Temperature Dead Band Value that is divided evenly to form a temperature range above and below [Air Temperature Set Point]. If measured air temperature is within this range, no heating or cooling will occur. Air Temperature Proportional Band Value that is divided evenly to form proportional temperature control bands above and below [Air Temperature Set Point]. Air Temperature Set Point Desired air temperature. This set point is dependent upon which sensor is selected for control. Airflow Sensor Issue Airflow sensor is disconnected or the signal is out of range. Ambient Air Sensor Issue Ambient air sensor is disconnected or the signal is out of range. Analog Input Reading Generic analog input reading (unitless). Auto Restart Delay If power is lost, the control will delay this amount of time after power is restored before restarting the unit. Aux Air Temp Device Communication Lost Communication with external auxiliary device providing an air temperature value has been lost. Back Draft Control Fan Speed Fan speed when in back draft control mode. BMS Communications Timeout Building Management System (or external monitoring system) has not communicated with the system within the expected timeframe. BMS Timeout Period Timeframe within which the Building Management System (or external monitoring system) must communicate with the system to avoid a timeout. Calculated Next Maintenance Month Calculated month of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Year]. Calculated Next Maintenance Year Calculated year of the next scheduled maintenance. Used in conjunction with [Calculated Next Maintenance Month]. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 430 BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Chilled Water Control Valve Failure Chilled water valve out of position. Chilled water control valve position does not match expected value. Chilled Water Flow Meter Sensor Failure Chilled water flow meter sensor is disconnected or the signal is out of range. Chilled Water Inlet Temperature Control Active Chilled water inlet temperature control is active. Chilled Water Inlet Temperature Sensor Failure Chilled water inlet temperature sensor is disconnected or the signal is out of range. Chilled Water Inlet Temperature Temperature of the water entering the hydraulic circuit of the chilled water unit. Chilled Water Outlet Temperature Sensor Failure Chilled water outlet temperature sensor is disconnected or the signal is out of range. Chilled Water Outlet Temperature Temperature of the water exiting the hydraulic circuit of the chilled water unit. Chilled Water Valve Hours Operating hours for chilled water valve since last reset of this value. Chilled Water Valve Operating Hours Threshold Operating hours threshold for the chilled water valve. When the number of operating hours reaches this threshold, an event is generated. Chilled Water Valve Reset Enable Enable/disable the ability to reset the chilled water valve. Circuit Cooling Load The amount of heat energy currently being removed by a single refrigeration circuit. Clogged Air Filter - Event Control Enable/disable the activation of the [Clogged Air Filter] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Clogged Air Filter - Event Type The event type for the [Clogged Air Filter] event. Clogged Air Filter Air filter is dirty and needs to be (cleaned or) replaced. Cold Aisle Air Sensor Failure Cold aisle sensor measuring air temperature and humidity is disconnected or the signal is out of range. Cold Aisle Cascade Fan Speed Max Set Point Cold aisle maximum fan speed when system is in cascade mode and one or more units in the system are in standby. Cold Aisle Control Enable Enable/disable cold aisle control. Cold Aisle Fan Speed Max Set Point Cold aisle maximum fan speed when system is not in cascade mode OR when system is in cascade mode and no units in the system are in standby. Cold Aisle Fan Speed Min Set Point Cold aisle minimum fan speed. Cold Aisle Force Max Fan/Cooling - Ext Control The cold aisle fan speed and system cooling can be forced to 100% via an external input signal. Use this value to enable/disable that feature. Cold Aisle Humidity Calculation Method Algorithm used to calculate a single cold aisle humidity value from multiple humidity measurements. Cold Aisle Sensor Air Temperature Air temperature measured by cold aisle sensor. Cold Aisle Sensor Humidity Humidity measured by cold aisle sensor. Cold Aisle Temperature Calculation Method Algorithm used to calculate a single cold aisle temperature value from multiple temperature measurements. Cold Aisle Temperature/Humidity Team Sensor Failure Cold aisle team sensor measuring air temperature and humidity is disconnected or the signal is out of range. Compressor 1B Hours Exceeded Fixed compressor 1B run hours have exceeded the threshold. Compressor 1B Thermal Overload Fixed compressor 1B is shut down due to thermal overload. Compressor 2B Hours Exceeded Fixed compressor 2B run hours have exceeded the threshold. Compressor 2B Thermal Overload Fixed compressor 2B is shut down due to thermal overload. Compressor Capacity Control State Compressor capacity control state. When 'ON', the cooling capacity of the compressor has been reduced. Compressor Capacity Reduced Compressor capacity has been reduced. 431 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Compressor High Head Pressure - Event Control Enable/disable the activation of the [Compressor High Head Pressure] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor High Head Pressure - Event Type The event type for the [Compressor High Head Pressure] event. Compressor High Head Pressure Compressor is shut down due to high head pressure. Compressor High Pressure Transducer Issue Compressor high pressure transducer is disconnected or the signal is out of range. Compressor Hours Exceeded [Compressor Hours] has exceeded [Compressor Hours Threshold]. Compressor Hours Threshold Threshold value used in the [Compressor Hours Exceeded] event. Compressor Hours Operating hours for compressor since last reset of this value. Compressor Lockout Enable/disable the use of the compressor. Compressor Low Differential Pressure Lockout Compressor exceeded maximum startup attempts due to low differential pressure. Compressor is shutdown and has been disabled. Compressor Low Pressure Transducer Issue Compressor low pressure transducer is disconnected or the signal is out of range. Compressor Low Suction Pressure - Event Control Enable/disable the activation of the [Compressor Low Suction Pressure] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor Low Suction Pressure - Event Type The event type for the [Compressor Low Suction Pressure] event. Compressor Low Suction Pressure Compressor is shut down due to low suction pressure. Compressor Pump Down Issue - Event Control Enable/disable the activation of the [Compressor Pump Down Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor Pump Down Issue - Event Type The event type for the [Compressor Pump Down Issue] event. Compressor Pump Down Issue Unable to pump down suction-side pressure during compressor shutdown. Compressor Short Cycle - Event Control Enable/disable the activation of the [Compressor Short Cycle] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor Short Cycle - Event Type The event type for the [Compressor Short Cycle] event. Compressor Short Cycle Compressor short cycle. A short cycle is defined as turning on and off a number of times over a set time period. Compressor State Compressor operational state. Compressor Superheat Over Threshold Compressor discharge refrigerant superheat temperature has exceeded an upper threshold. Compressor Thermal Overload - Event Control Enable/disable the activation of the [Compressor Thermal Overload] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Compressor Thermal Overload - Event Type The event type for the [Compressor Thermal Overload] event. Compressor Thermal Overload Compressor is shut down due to thermal overload. Compressor Utilization Present compressor utilization expressed as a percentage of the maximum rated capacity. Condenser Circuit Unspecified General Event One or more unspecified condenser circuit events active. See local unit display for further details. Condenser Communication Lost Communication with condenser unit has been lost. Condenser Control Board Issue The condenser control board is reporting an issue. Condenser Fan Current Condenser fan's measured input current. Condenser Fan Issue Condenser fan is not operating within its operational parameters. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 432 BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Condenser Fan Power Condenser fan's measured input power. Condenser Fan Reversal Requested Request the condenser fans to rotate in the reverse direction. Condenser Fan Speed Condenser fan speed expressed as a percentage of the maximum rated speed. Condenser Issue - Event Control Enable/disable the activation of the [Condenser Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Condenser Issue - Event Type The event type for the [Condenser Issue] event. Condenser Issue Condenser is not operating within its operational parameters. Condenser Low Noise Mode - Full Days Days of the week selected for low noise mode full day scheduling. Condenser Low Noise Mode - Interval Days Days of the week selected for low noise mode interval scheduling. Condenser Low Noise Mode Max Fan Speed Maximum fan speed when condenser is placed in low noise mode. Condenser Low Noise Mode Schedule Control Enable/disable scheduled control of condenser low noise mode. Condenser Low Noise Mode Start Time The time of day at which the condenser will transition into low noise mode. Condenser Low Noise Mode State State of condenser low noise mode scheduler control. Condenser Low Noise Mode Stop Time The time of day at which the condenser will transition out of low noise mode. Condenser Max Fan Speed Override Fan speed exceeding the maximum set point in order to alleviate a high temperature or pressure condition. Condenser Normal Mode Max Fan Speed Maximum fan speed when condenser is not in low noise mode. Condenser Outside Air Temp Out of Operating Range [Condenser Outside Air Temperature] is either above an upper threshold or below a lower threshold. Condenser Outside Air Temp Sensor Issue Condenser outside air temperature sensor is disconnected or the signal is out of range. Condenser Outside Air Temperature Condenser ambient outside air temperature. Condenser Refrigerant Pressure Over Threshold Condenser refrigerant pressure has exceeded a threshold. Condenser Refrigerant Pressure Sensor Issue Condenser refrigerant pressure sensor is disconnected or the signal is out of range. Condenser Refrigerant Pressure Under Threshold Condenser refrigerant pressure has dropped below a threshold. Condenser Refrigerant Pressure Pressure of the refrigerant in a condenser circuit. Condenser Refrigerant Type Condenser refrigerant type. Condenser Remote Shutdown Condenser is shut down by a remote signal. Condenser Supply Refrigerant Over Temp Condenser supply refrigerant temperature has exceeded a threshold. Condenser Supply Refrigerant Temp Sensor Condenser supply refrigerant temperature sensor is disconnected or the signal Issue is out of range. Condenser Supply Refrigerant Temperature Temperature of the supply refrigerant in a condenser circuit. Condenser Supply Refrigerant Under Temp Condenser supply refrigerant temperature has dropped below a specified threshold. Condenser TVSS Issue The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed. Condenser Unit Unspecified General Event One or more unspecified condenser unit events active. See local unit display for further details. Condenser VFD Issue The condenser fan Variable Frequency Drive is offline. Cooling Capacity Cooling capacity in use, expressed as a percentage of the maximum rated capacity. 433 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Cooling Control Temperature Temperature value being used for cooling capacity control. This value is compared against the temperature set point to determine the amount of cooling to be applied. Cooling State Cooling operational state. Customer Input 1 - Event Control Enable/disable the activation of the [Customer Input 1] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 1 - Event Type The event type for the [Customer Input 1] event. Customer Input 1 Customer Input 1 Customer Input 2 - Event Control Enable/disable the activation of the [Customer Input 2] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 2 - Event Type The event type for the [Customer Input 2] event. Customer Input 2 Customer Input 2 Customer Input 3 - Event Control Enable/disable the activation of the [Customer Input 3] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 3 - Event Type The event type for the [Customer Input 3] event. Customer Input 3 Customer Input 3 Customer Input 4 - Event Control Enable/disable the activation of the [Customer Input 4] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Customer Input 4 - Event Type The event type for the [Customer Input 4] event. Customer Input 4 Customer Input 4 Dehumidification Fan Speed Min Set Point Minimum fan speed when system dehumidification is active. Dehumidifier Hours Exceeded Operating hours for the dehumidifier have exceeded the threshold. Dehumidifier Hours Threshold Threshold value used in the [Dehumidifier Hours Exceeded] event. Dehumidifier Hours Operating hours for dehumidifier since last reset of this value. Dehumidifier State Dehumidifier operational state. Dehumidifier Utilization Present dehumidifier utilization expressed as a percentage of the maximum rated capacity. Dew Point Dead Band Value that is divided evenly to form a range above and below [Dew Point Set Point]. If measured humidity is within this range, no humidification or dehumidification will occur. This parameter is used when [Humidity Control Type] is set to Dew Point. Dew Point Over Temperature Dew point temperature reading has exceeded the upper threshold. Dew Point Proportional Band Value that is divided evenly to form proportional humidity control bands above and below [Dew Point Set Point]. This parameter is used when [Humidity Control Type] is set to Dew Point. Dew Point Set Point Desired dew point temperature. Dew Point Under Temperature Dew point temperature reading has dropped below the lower threshold. Dig Scroll Comp Discharge Over Temp Event Ctrl Enable/disable the activation of the [Dig Scroll Comp Discharge Over Temp] event. Dig Scroll Comp Discharge Over Temp Event Type The event type for the [Dig Scroll Comp Discharge Over Temp] event. Dig Scroll Comp Discharge Temp Sensor Issue Digital scroll compressor discharge temperature sensor is disconnected or the signal is out of range. Dig Scroll Comp Discharge Temp Digital scroll compressor discharge temperature. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 434 BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Dig Scroll Comp Over Temp Digital scroll compressor is shut down due to head temperature exceeding an upper threshold. Digital Output Board Not Detected Digital output board is required to be connected, but no signal is detected. Digital Scroll Compressor Loading Present digital scroll compressor utilization expressed as a percentage of the maximum rated capacity. EEV Unspecified General Event One or more unspecified electronic expansion valve events active. See local unit display for further details. Electric Reheat State Electric reheater operational state. Electric Reheater Hours Exceeded [Electric Reheater Hours] has exceeded [Electric Reheaters Hours Threshold]. Electric Reheater Hours Threshold Threshold value used in the [Electric Reheater Hours Exceeded] event. Electric Reheater Hours Operating hours for electric reheater since last reset of this value. Energy Consumption Energy consumption since the last reset of this value. Expected Condenser Unit Count Number of physical condenser units that are expected to be connected to the system. Ext Air Damper Position Issue Air damper position does not match expected value, as indicated by an external input signal. Ext Air Sensor A Dew Point Temp Dew point temperature as measured by external air sensor A. Ext Air Sensor A Event Control Enable/disable the activation of events related to measurements by the external air sensor A. Ext Air Sensor A High Humidity - Event Control Enable/disable the activation of the [Ext Air Sensor A High Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Air Sensor A High Humidity - Event Type The event type for the [Ext Air Sensor A High Humidity] event. Ext Air Sensor A High Humidity Threshold Threshold value used in the [External Air Sensor A High Humidity] event. Ext Air Sensor A High Humidity [Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High Humidity Threshold]. Ext Air Sensor A Humidity Relative humidity as measured by external air sensor A. Ext Air Sensor A Issue The external air sensor A is disconnected or the signal is out of range. Ext Air Sensor A Low Humidity - Event Control Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Air Sensor A Low Humidity - Event Type The event type for the [Ext Air Sensor A Low Humidity] event. Ext Air Sensor A Low Humidity Threshold Threshold value used in the [External Air Sensor A Low Humidity] event. Ext Air Sensor A Low Humidity [Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A Low Humidity Threshold]. Enable/disable the activation of the [External Air Sensor A Over Temperature] Ext Air Sensor A Over Temp - Event Control event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Air Sensor A Over Temp - Event Type The event type for the [External Air Sensor A Over Temperature] event. Ext Air Sensor A Over Temp Threshold Threshold value used in the [External Air Sensor A Over Temperature] event. Ext Air Sensor A Over Temperature [Ext Air Sensor A Temperature] has exceeded [External Air Sensor A Over Temp Threshold]. Ext Air Sensor A Temperature Air temperature as measured by external air sensor A. Ext Air Sensor A Under Temp - Event Control Enable/disable the activation of the [Ext Air Sensor A Under Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Air Sensor A Under Temp - Event Type The event type for the [Ext Air Sensor A Under Temperature] event. Ext Air Sensor A Under Temp Threshold Threshold value used in the [External Air Sensor A Under Temperature] event. 435 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Ext Air Sensor A Under Temperature [Ext Air Sensor A Temperature] has dropped below [Ext Air Sensor A Under Temp Threshold]. Ext Air Sensor B Humidity Relative humidity as measured by external air sensor B. Ext Air Sensor B Temperature Air temperature as measured by external air sensor B. Ext Air Sensor C Humidity Relative humidity as measured by external air sensor C. Ext Air Sensor C Temperature Air temperature as measured by external air sensor C. Ext Compressor Lockout - Event Control Enable/disable the activation of the [Ext Compressor Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Compressor Lockout - Event Type The event type for the [Ext Compressor Lockout] event. Ext Compressor Lockout The compressor is shut down and disabled by an external input signal. Ext Condenser Pump High Water - Event Control Enable/disable the activation of the [Ext Condenser Pump High Water] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Condenser Pump High Water - Event Type The event type for the [Ext Condenser Pump High Water] event. Ext Condenser Pump High Water High water is detected in the condensate pump by the auxiliary float, as indicated by an external input signal. Ext Dew Point Over Temp Threshold Threshold value used in the [Ext Dew Point Over Temperature] event. Ext Dew Point Over Temperature At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded [Ext Dew Point Over Temp Threshold]. Ext Dew Point Under Temp Threshold Threshold value used in the [Ext Dew Point Under Temperature] event. Ext Dew Point Under Temperature At least one dew point temperature reading ([Ext Air Sensor A Dew Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped below [Ext Dew Point Under Temp Threshold]. Ext Free Cooling Lockout - Event Control Enable/disable the activation of the [Ext Free Cooling Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Free Cooling Lockout - Event Type The event type for the [Ext Free Cooling Lockout] event. Ext Free Cooling Lockout Free cooling is disabled by an external input signal. Ext Humidifier Lockout - Event Control Enable/disable the activation of the [Ext Humidifier Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Humidifier Lockout - Event Type The event type for the [Ext Humidifier Lockout] event. Ext Humidifier Lockout The humidifier is shut down and disabled by an external input signal. Ext Loss of Air Blower - Event Control Enable/disable the activation of the [Ext Loss of Air Blower] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Loss of Air Blower - Event Type The event type for the [Ext Loss of Air Blower] event. Ext Loss of Air Blower Loss of air blower is detected, as indicated by an external input signal. Ext Loss of Flow - Event Control Enable/disable the activation of the [Ext Loss of Flow] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Loss of Flow - Event Type The event type for the [Ext Loss of Flow] event. Ext Loss of Flow Loss of flow is detected, as indicated by an external input signal. Ext Over Temperature - Event Control Enable/disable the activation of the [Ext Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 436 BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Ext Over Temperature - Event Type The event type for the [Ext Over Temperature] event. Ext Over Temperature A temperature has exceeded its threshold, as indicated by an external input signal. Ext Power Source A Failure Unit main power source A failure, as indicated by an external input signal. Ext Power Source B Failure Unit main power source B failure, as indicated by an external input signal. Ext Reheat Lockout - Event Control Enable/disable the activation of the [Ext Reheat Lockout] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Reheat Lockout - Event Type The event type for the [Ext Reheat Lockout] event. Ext Reheat Lockout The reheater is shut down and disabled by an external input signal. Ext Standby Glycol Pump On - Event Control Enable/disable the activation of the [Ext Standby Glycol Pump On] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Standby Glycol Pump On - Event Type The event type for the [Ext Standby Glycol Pump On] event. Ext Standby Glycol Pump On The standby glycol pump is on, as indicated by an external input signal. Ext Standby Unit On - Event Control Enable/disable the activation of the [Ext Standby Unit On] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Ext Standby Unit On - Event Type The event type for the [Ext Standby Unit On] event. Ext Standby Unit On Standby unit is on, as indicated by an external input signal. External Condenser TVSS Issue The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed, as indicated by an external input signal. External Condenser VFD Issue The condenser fan Variable Frequency Drive is offline, as indicated by an external input signal. External Fire Detected Fire detected, as indicated by an external input signal. Fan Control Mode Fan control mode. Fan Control Sensor Sensor to be used for fan speed control. Fan Hours Exceeded - Event Control Enable/disable the activation of the [Fan Hours Exceeded] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Fan Hours Exceeded - Event Type The event type for the [Fan Hours Exceeded] event. Fan Hours Exceeded Operating hours for the unit blower fan have exceeded the threshold. Fan Hours Threshold Threshold value used in the [Fan Hours Exceeded] event. Fan Hours Operating hours for fan since last reset of this value. Fan Issue - Event Control Enable/disable the activation of the [Fan Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Fan Issue - Event Type The event type for the [Fan Issue] event. Fan Issue One or more fans are not operating within their operational parameters. Fan Speed Control Temperature Temperature value being used for fan speed control. This value is compared against the fan speed temperature set point to determine the fan speed. Fan Speed Maximum Set Point Maximum fan speed. This value may only be modified if iCOM is enabled to allow fan speed changes by the BMS. Fan Speed Minimum Set Point Minimum fan speed. Fan Speed Temperature Set Point If fan is in decoupled mode and not under manual control, the fan speed will vary depending on the delta between the selected fan control sensor temperature and this set point. Fan Speed Fan speed expressed as a percentage of the maximum rated speed. 437 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Fan State Fan operational state. Fluid Flow Rate Flow rate of fluid used for cooling. Fluid Flow Sensor Issue The fluid flow sensor is disconnected or the signal is out of range. Fluid Input Temperature Temperature of the fluid entering the cooling coil. Fluid Output Temperature Temperature of the fluid exiting the cooling coil. Fluid Temperature Sensor Issue The fluid temperature sensor is disconnected or the signal is out of range. Free Cooling Fluid Temperature Free cooling fluid temperature. Free Cooling Internal Control Mode Free cooling internal control mode Free Cooling Internal Control Mode Free cooling internal control mode Free Cooling Internal Temperature Delta Minimum temperature delta required between supply fluid and internal ambient air temperatures in order to enable free cooling. Free Cooling State Free cooling operational state. Free Cooling Status Free cooling status. Free Cooling Status Free cooling status. Free Cooling Stopped - High Room Temp Free cooling is temporarily disabled due to room temperature exceeding a preset delta above the the set point. Free Cooling Temp Sensor Issue The free cooling fluid temperature sensor is disconnected or the signal is out of range. Free Cooling Valve Hours Exceeded [Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours Threshold]. Free Cooling Valve Hours Threshold Threshold value used in the [Free Cooling Valve Hours Exceeded] event. Free Cooling Valve Hours Operating hours for free cooling valve since last reset of this value. Free Cooling Valve Open Position Free cooling valve open position. Heating Fan Speed Min Set Point Minimum fan speed when system heating is active. Heating Lockout Heating is shut down and disabled. High Power Shutdown - Event Control Enable/disable the activation of the [High Power Shutdown] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. High Power Shutdown - Event Type The event type for the [High Power Shutdown] event. High Power Shutdown Supply to high power components has been shutdown. High Return Air Temperature Threshold Threshold value used in the [Return Air Over Temperature] event. High Return Humidity - Event Control Enable/disable the activation of the [High Return Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. High Return Humidity - Event Type The event type for the [High Return Humidity] event. High Return Humidity Threshold Threshold value used in the [High Return Humidity] event. High Return Humidity Return air high humidity event. High Static Pressure High static pressure event. High Supply Air Temperature Threshold Threshold value used in the [Supply Air Over Temperature] event. Hot Water / Hot Gas State Hot water / hot gas operational state. Hot Water / Hot Gas Valve Hours Exceeded [Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot Gas Valve Hours Threshold]. Hot Water / Hot Gas Valve Hours Threshold Threshold value used in the [Hot Water / Hot Gas Valve Hours Exceeded] event. Hot Water / Hot Gas Valve Hours Operating hours for hot water / hot gas valve since last reset of this value. Hot Water / Hot Gas Valve Open Position Hot water / hot gas valve open position. Humidification Fan Speed Min Set Point Minimum fan speed when system humidification is active. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 438 BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Humidifier Control Board Not Detected Humidifier control board is required to be connected, but no signal is detected. Humidifier Cylinder Worn Humidifier cylinder is not operating properly and needs to be replaced. Humidifier Hours Exceeded Operating hours for the humidifier have exceeded the threshold. Humidifier Hours Threshold Threshold value used in the [Humidifier Hours Exceeded] event. Humidifier Hours Operating hours for humidifier since last reset of this value. Humidifier Issue - Event Control Enable/disable the activation of the [Humidifier Issue] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Humidifier Issue - Event Type The event type for the [Humidifier Issue] event. Humidifier Issue Humidifier issue detected, causing it to be locked out. Humidifier Lockout Enable/disable the use of the humidifier. Humidifier Low Water The water level in the humidifier has dropped below its threshold. Humidifier Over Current The electrical current to the humidifier has exceeded its upper threshold. Humidifier State Humidifier operational state. Humidifier Under Current The electrical current to the humidifier has dropped below its lower threshold. Humidifier Utilization Present humidifier utilization expressed as a percentage of the maximum rated capacity. Humidity Control Integration Time Time value used to add an integral term to humidity control. If set to 0, time will not be a factor in the control algorithm. Humidity Control Sensor Sensor from which humidity measurements will be used for humidification and dehumidification control. Humidity Control Type Type of algorithm to use for control of output humidity. Humidity Control Type Type of algorithm to use for control of output humidity. Humidity Dead Band Value that is divided evenly to form a range above and below [Humidity Set Point]. If measured humidity is within this range, no humidification or dehumidification will occur. Humidity Proportional Band Value that is divided evenly to form proportional humidity control bands above and below [Humidity Set Point]. This setting applies to Relative, Predictive and Compensated [Humidity Control Type] selections. Humidity Set Point Desired relative humidity. Infrared Humidifier Flush Rate A multiple of an internal time constant that determines the flush duration of the infrared humidifier water pan. Input Undervoltage One or more of the input phase voltages has dropped below the limit. Instantaneous Power Total electrical power currently being consumed. Local Cooling Override The local unit override status for cooling capacity. Local Dehumidifier Override The local unit override status for the dehumidifier. Local Electric Heat Override The local unit override status for electric heat. Local Fan Override The local unit override status for fan speed. Local Humidifier Override The local unit override status for the humidifier. Loss of Air Flow No air flow through the unit due to failure of all fans. Low Return Air Temperature Threshold Threshold value used in the [Return Air Under Temperature] event. Low Return Humidity - Event Control Enable/disable the activation of the [Low Return Humidity] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Low Return Humidity - Event Type The event type for the [Low Return Humidity] event. Low Return Humidity Threshold Threshold value used in the [Low Return Humidity] event. Low Return Humidity Return air low humidity event. 439 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Low Static Pressure Low static pressure event. Low Supply Air Temperature Threshold Threshold value used in the [Supply Air Under Temperature] event. Main Chilled Water Valve The primary valve in a dual valve chilled water system. Main Fan Overload - Event Control Enable/disable the activation of the [Main Fan Overload] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Main Fan Overload - Event Type The event type for the [Main Fan Overload] event. Main Fan Overload Main fan is shut down due to thermal overload. Maintenance Completed Maintenance has been completed on the unit. Maintenance Due The calculated maintenance date has been reached. Maintenance Ramp The ratio of operations performed to the calculated operations available between maintenance intervals. Maintenance Tracking State Maintenance tracking operational state. Master Unit Communication Lost - Event Control Enable/disable the activation of the [Master Unit Communication Lost] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Master Unit Communication Lost - Event Type The event type for the [Master Unit Communication Lost] event. Master Unit Communication Lost Communication with master unit has been lost. Minimum Chilled Water Temp Set Point Enable Enable/disable the activation of [Minimum Chilled Water Temp Set Point]. Minimum Chilled Water Temp Set Point Minimum desired chilled water temperature. Mixed Mode Lockout Mixed mode has been entered too many times over a rolling time period and has been temporarily disabled. Mixed mode is defined as the use of a compressor on one refrigeration circuit and the use of a refrigerant pump on the other circuit. Modbus Power Meter Communication Lost Communication with Modbus power meter has been lost. Outside Air Temperature Ambient outside air temperature. PRE Operational Mode Pumped Refrigerant Economizer operational mode. Pump Hours Threshold Threshold value used in the [Pump Hours Exceeded] event. Pump Hours Operating hours for pump since last reset of this value. Pump Inlet Refrigerant Temperature Refrigerant temperature at the inlet of the pump. Pump Outlet Refrigerant Temperature Refrigerant temperature at the outlet of the pump. Pump Speed Pump speed expressed as a percentage of the maximum rated speed. Pump State Pump operational state. Pump Unspecified General Event One or more unspecified pump events active. See local unit display for further details. RAM Battery Issue RAM or RAM backup battery is not operating correctly. Raw Auxiliary Air Temperature Air temperature value sent by an external auxiliary device, with no additional filtering by the receiving system. This may be an aggregated value from multiple sensors. Reheat Utilization Present reheating utilization expressed as a percentage of the maximum rated capacity. Reheater Lockout Enable/disable the use of the reheater. Reheater Over Temperature The temperature of the reheater has exceeded its threshold. Remote Sensor Average Over Temperature [Remote Sensor Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor Average Temperature Average value of remote sensor temperature measurements. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 440 BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Remote Sensor Average Under Temperature [Remote Sensor Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Remote Sensor Issue Remote sensor is disconnected or the signal is out of range. Remote Sensor Maximum Temperature Maximum value of remote sensor temperature measurements. Remote Sensor Over Temp Threshold Threshold value used in the remote air sensor over temperature events. Remote Sensor Over Temperature [Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor System Average Over Temperature [Remote Sensor System Average Temperature] has exceeded [Remote Sensor Over Temp Threshold]. Remote Sensor System Average Temperature Average value of remote sensor temperature measurements among a group of interconnected units in a single system. Remote Sensor System Average Under Temperature [Remote Sensor System Average Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Remote Sensor System Maximum Temperature Maximum value of remote sensor temperature measurements among a group of interconnected units in a single system. Remote Sensor Temperature Air temperature as measured by remote sensor. Remote Sensor Under Temp Threshold Threshold value used in the remote air sensor under temperature events. Remote Sensor Under Temperature [Remote Sensor Temperature] has dropped below [Remote Sensor Under Temp Threshold]. Return Air Over Temp - Event Control Enable/disable the activation of the [Return Air Over Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Return Air Over Temp - Event Type The event type for the [Return Air Over Temperature] event. Return Air Over Temperature Return air high temperature event. Return Air Sensor Event Control Enable/disable the activation of events related to measurements by the return air sensor. Return Air Sensor Issue The air sensor at the inlet of the unit is disconnected or the signal is out of range. Return Air Temperature Set Point Desired air temperature at the inlet of the unit. Return Air Temperature The temperature of the inlet air Return Air Under Temp - Event Control Enable/disable the activation of the [Return Air Under Temperature] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Return Air Under Temp - Event Type The event type for the [Return Air Under Temperature] event. Return Air Under Temperature [Return Air Temperature] has dropped below [Low Return Air Temperature Threshold]. Return Damper Status Status of the return damper. Return Dew Point Dew point temperature measured at the inlet of the unit. Return Humidity Sensor Issue The humidity sensor at the inlet of the unit is disconnected or the signal is out of range. Return Humidity Set Point Desired relative humidity at the inlet of the unit. Return Humidity Relative humidity measured at the inlet of the unit. Server Class The general classification for this system Service Required - Event Control Enable/disable the activation of the [Service Required] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Service Required - Event Type The event type for the [Service Required] event. Service Required Unit requires servicing. 441 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Shutdown - Loss Of Power - Event Control Enable/disable the activation of the [Shutdown - Loss Of Power] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Shutdown - Loss Of Power - Event Type The event type for the [Shutdown - Loss Of Power] event. Shutdown - Loss Of Power System lost power. This event becomes active when the unit is powered on following an unexpected loss of power. This event remains active for 90 minutes. Smoke Detected - Event Control Enable/disable the activation of the [Smoke Detected] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Smoke Detected - Event Type The event type for the [Smoke Detected] event. Smoke Detected Smoke detected. Standby Units The number of standby units. Static Pressure Control Enable Enable/disable underfloor static pressure control. Static Pressure Sensor Issue The static pressure sensor is disconnected or the signal is out of range. Static Pressure Sensor Out of Range Static pressure sensor signal is out of its configured range. Static Pressure Set Point Desired static pressure. Super Saver Call For Cooling Call for cooling value used for Super Saver functionality. A higher call for cooling value indicates a need for a lower coolant temperature. Supply Air Over Temperature Supply air high temperature event. Supply Air Over/Under Temperature - Event Enable/disable the activation of the [Supply Air Over Temperature] and [Supply Control Air Under Temperature] events. Supply Air Sensor Issue The air sensor at the outlet of the unit is disconnected or the signal is out of range. Supply Air Temperature Sensor Control Control mode to be used with the supply air temperature sensor. Supply Air Temperature Set Point Desired supply air temperature. Supply Air Temperature Air temperature measured at the outlet of the unit. Supply Air Under Temperature Supply air low temperature event. Supply Chilled Water Loss of Flow Supply chilled water or glycol flow is too low. Supply Chilled Water Over Temp Chilled water temperature is too high, as indicated by an external input signal. System Date and Time The system date and time System Event Acknowledge/Reset Reset and/or acknowledge all events. System Input RMS A-B The System Input RMS Voltage between Phase A and Phase B System Input RMS A-N The System Input RMS Voltage between Phase A and Neutral System Input RMS B-C The System Input RMS Voltage between Phase B and Phase C System Input RMS B-N The System Input RMS Voltage between Phase B and Neutral System Input RMS C-A The System Input RMS Voltage between Phase C and Phase A System Input RMS C-N The System Input RMS Voltage between Phase C and Neutral System Input RMS Current Phase A The system input RMS current for Phase A System Input RMS Current Phase B The system input RMS current for Phase B System Input RMS Current Phase C The system input RMS current for Phase C System On/Off Control Turn system functionality on or off. System Static Pressure Static pressure measurement among a group of interconnected units in a single system. System Status The operating status for the system Tandem 'B' Compressor Hours Operating hours for the 'B' compressor in a tandem configuration since last reset of this value. Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 442 BACnet Communications—Thermal Management Products Table 4-7 Liebert Challenger 3000™, Liebert Challenger ITR™, Liebert CW™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPM™, Liebert PeX™, Liebert PDX/PCW™—Glossary (continued) Data Label Data Description Tandem 'B' Compressor State Operational state for the 'B' compressor in a tandem configuration. Team Static Pressure Sensor Failure The team static pressure sensor is disconnected or the signal is out of range. Temperature Control Sensor Issue The air sensor selected for cooling control is disconnected or the signal is out of range. Thermal Control Override - Temperature Call If [Thermal Control Override] is enabled, this value sets the percent call for cooling or heating. Thermal Control Override - Humidity Call If [Thermal Control Override] is enabled, this value sets the percent call for humidification or dehumidification. Thermal Control Override - Humidity Control If [Thermal Control Override] is enabled, this value selects if the humidity Type override is applied to humidification or dehumidification. Thermal Control Override - Temperature Control Type If [Thermal Control Override] is enabled, this value selects if the temperature override is applied to cooling or heating. Thermal Control Override Override internal programmatic control of thermal conditions. This includes, but may not be limited to, temperature and humidity. The ability to enable this override may require additional system configuration. Today's High Air Temperature Time [Today's High Air Temperature] was measured at this time. Today's High Air Temperature The highest external air temperature measured since midnight. Today's High Humidity Time [Today's High Humidity] was measured at this time Today's High Humidity The highest external humidity measured since midnight. Today's Low Air Temperature Time [Today's Low Air Temperature] was measured at this time. Today's Low Air Temperature The lowest external air temperature measured since midnight. Today's Low Humidity Time [Today's Low Humidity] was measured at this time Today's Low Humidity The lowest external humidity measured since midnight. Underfloor Static Pressure Control Enable Enable/disable the underfloor static pressure control. Unit Calculated Airflow Total airflow calculated for the unit. Unit Code Missing Unit code has not been entered and saved. Unit Communication Lost Master has lost communication with one or more networked units. Unit Control Mode Unit control mode. Unit Cooling Load The total amount of heat energy currently being removed by the unit. Unit Off Unit was turned off. Unit On Unit was turned on. Unit Operating State Reason The reason the unit is in the current operating state. Unit Operating State Current operating state of the unit. Unit Partial Shutdown An event has occurred requiring some system components to be shutdown and disabled. Unit Shutdown An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit Standby Unit was placed in standby mode. Unit Static Pressure Static pressure measurement for a single unit. Unspecified General Event One or more unspecified events active. See local unit display for further details. Water Leakage Detector Sensor Issue The water leakage detector sensor is disconnected or the signal is out of range. Water Under Floor - Event Control Enable/disable the activation of the [Water Under Floor] event. If set to 'disabled', the event will not be annunciated. This implies that the event will not be placed in any active event list or in any event history list. Water Under Floor - Event Type The event type for the [Water Under Floor] event. Water Under Floor Water under the floor is detected. 443 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-8 Liebert CRV™—Binary Data Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Air Supply Air Over Temperature Binary_Value 1 5015_1 RD Active on Alarm Supply Air Under Temperature Binary_Value 2 5019_1 RD Active on Alarm Return Air Over Temperature Binary_Value 3 5023_1 RD Active on Alarm Supply Air Sensor Issue Binary_Value 4 5026_1 RD Active on Alarm Return Air Sensor Issue Binary_Value 5 5147_1 RD Active on Alarm Binary_Value 6 5966_1_1 RD Active on Alarm Air - Auxiliary Air Aux Air Temp Device Communication Lost Humidity High Return Humidity Binary_Value 16 5034_1 RD Active on Alarm Low Return Humidity Binary_Value 17 5036_1 RD Active on Alarm Humidifier Hours Exceeded Binary_Value 18 5037_1 RD Active on Alarm Dehumidifier Hours Exceeded Binary_Value 19 5038_1 RD Active on Alarm Humidifier Under Current Binary_Value 20 5039_1 RD Active on Alarm Humidifier Over Current Binary_Value 21 5040_1 RD Active on Alarm Humidifier Low Water Binary_Value 22 5041_1 RD Active on Alarm Humidifier Cylinder Worn Binary_Value 23 5042_1 RD Active on Alarm Humidifier Issue Binary_Value 24 5043_1 RD Active on Alarm Ext Humidifier Lockout Binary_Value 25 5044_1 RD Active on Alarm Humidifier Control Board Not Detected Binary_Value 26 5045_1 RD Active on Alarm Return Humidity Out Of Proportional Band Binary_Value 27 5046_1 RD Active on Alarm Binary_Value 38 5053_1 RD Active on Alarm Fans Loss of Air Flow Fan Hours Exceeded Binary_Value 39 5054_1 RD Active on Alarm Top Fan Issue Binary_Value 40 5055_1 RD Active on Alarm Bottom Fan Issue Binary_Value 41 5056_1 RD Active on Alarm Remote Sensors Remote Sensor Average Under Temperature Binary_Value 43 5594_1 RD Active on Alarm Remote Sensor Average Over Temperature Binary_Value 44 5593_1 RD Active on Alarm Remote Sensor System Average Under Temperature Binary_Value 45 5596_1 RD Active on Alarm Remote Sensor System Average Over Temperature Binary_Value 46 5595_1 RD Active on Alarm Remote Sensor Average Low Humidity Binary_Value 47 6227_1 RD Active on Alarm Remote Sensor Average High Humidity Binary_Value 48 6228_1 RD Active on Alarm Remote Sensor System Average Low Humidity Binary_Value 49 6229_1 RD Active on Alarm Remote Sensor System Average High Humidity Binary_Value 50 6230_1 RD Active on Alarm Remote Sensor Issue Binary_Value 52 5060_1_1 RD Active on Alarm Remote Sensor Low Humidity Binary_Value 53 6225_1_1 RD Active on Alarm Remote Sensor High Humidity Binary_Value 54 6226_1_1 RD Active on Alarm Remote Sensor Under Temperature Binary_Value 55 5598_1_1 RD Active on Alarm Remote Sensor Over Temperature Binary_Value 56 5597_1_1 RD Active on Alarm Remote Sensors - Remote Sensor 1 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 444 BACnet Communications—Thermal Management Products Table 4-8 Liebert CRV™—Binary Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Remote Sensor Issue Binary_Value 63 5060_1_2 RD Active on Alarm Remote Sensor Low Humidity Binary_Value 64 6225_1_2 RD Active on Alarm Remote Sensor High Humidity Binary_Value 65 6226_1_2 RD Active on Alarm Remote Sensor Under Temperature Binary_Value 66 5598_1_2 RD Active on Alarm Remote Sensor Over Temperature Binary_Value 67 5597_1_2 RD Active on Alarm Remote Sensor Issue Binary_Value 151 5060_1_1 0 RD Active on Alarm Remote Sensor Low Humidity Binary_Value 152 6225_1_1 0 RD Active on Alarm Remote Sensor High Humidity Binary_Value 153 6226_1_1 0 RD Active on Alarm Remote Sensor Under Temperature Binary_Value 154 5598_1_1 0 RD Active on Alarm Remote Sensor Over Temperature Binary_Value 155 5597_1_1 0 RD Active on Alarm Compressor 1 High Head Pressure Binary_Value 162 4669_1 RD Active on Alarm Compressor 1 Low Suction Pressure Binary_Value 163 5062_1 RD Active on Alarm Compressor 1 Hours Exceeded Binary_Value 164 5063_1 RD Active on Alarm Dig Scroll Comp 1 Temp Sensor Issue Binary_Value 165 5064_1 RD Active on Alarm Remote Sensors - Remote Sensor 2 Remote Sensors - Remote Sensor 10 Compressor Dig Scroll Comp 1 Over Temp Binary_Value 166 5065_1 RD Active on Alarm Compressor 1 Low Pressure Transducer Issue Binary_Value 167 5066_1 RD Active on Alarm Compressor 1 High Pressure Transducer Issue Binary_Value 168 5148_1 RD Active on Alarm Ext Compressor Lockout Binary_Value 169 5067_1 RD Active on Alarm Compressor 1 Short Cycle Binary_Value 170 4681_1 RD Active on Alarm Compressor 1 Pump Down Issue Binary_Value 171 5146_1 RD Active on Alarm Compressor Capacity Reduced Binary_Value 172 5513_1 RD Active on Alarm Compressor Superheat Over Threshold Binary_Value 173 5604_1 RD Active on Alarm Reheater Over Temperature Binary_Value 182 5068_1 RD Active on Alarm Electric Reheater 1 Hours Exceeded Binary_Value 183 5069_1 RD Active on Alarm Ext Reheat Lockout Binary_Value 184 5070_1 RD Active on Alarm Electric Reheater Hours Exceeded Binary_Value 185 5368_1 RD Active on Alarm Reheater Condenser Condenser 1 Issue Binary_Value 195 5071_1 RD Active on Alarm Condenser VFD Issue Binary_Value 196 5072_1 RD Active on Alarm Condenser TVSS Issue Binary_Value 197 5073_1 RD Active on Alarm External Condenser VFD Issue Binary_Value 198 6106_1 RD Active on Alarm External Condenser TVSS Issue Binary_Value 199 6105_1 RD Active on Alarm 445 Liebert® IntelliSlot™ Modbus/BACnet Reference Guide BACnet Communications—Thermal Management Products Table 4-8 Liebert CRV™—Binary Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Chilled Water Supply Chilled Water Over Temp Binary_Value 208 4626_1 RD Active on Alarm Chilled Water Control Valve Failure Binary_Value 209 4703_1 RD Active on Alarm Supply Chilled Water Loss of Flow Binary_Value 210 4980_1 RD Active on Alarm Customer Input 1 Binary_Value 221 4270_1 RD Active on Alarm Customer Input 2 Binary_Value 222 4271_1 RD Active on Alarm Customer Input 3 Binary_Value 223 4272_1 RD Active on Alarm Customer Input 4 Binary_Value 224 4273_1 RD Active on Alarm Smoke Detected Binary_Value 225 4720_1 RD Active on Alarm Water Under Floor Binary_Value 226 4723_1 RD Active on Alarm Service Required Binary_Value 227 4726_1 RD Active on Alarm Shutdown - Loss Of Power Binary_Value 228 4714_1 RD Active on Alarm System Events Ext Over Temperature Binary_Value 229 5104_1 RD Active on Alarm Ext Loss of Flow Binary_Value 230 5105_1 RD Active on Alarm Ext Condenser Pump High Water Binary_Value 231 5106_1 RD Active on Alarm Ext Standby Glycol Pump On Binary_Value 232 5107_1 RD Active on Alarm External Fire Detected Binary_Value 233 5108_1 RD Active on Alarm Unit On Binary_Value 234 5109_1 RD Active on Alarm Unit Off Binary_Value 235 5110_1 RD Active on Alarm Unit Standby Binary_Value 236 5111_1 RD Active on Alarm Unit Partial Shutdown Binary_Value 237 5112_1 RD Active on Alarm Unit Shutdown Binary_Value 238 5113_1 RD Active on Alarm Water Leakage Detector Sensor Issue Binary_Value 239 5114_1 RD Active on Alarm BMS Communications Timeout Binary_Value 240 5115_1 RD Active on Alarm Maintenance Due Binary_Value 241 5116_1 RD Active on Alarm Maintenance Completed Binary_Value 242 5117_1 RD Active on Alarm Clogged Air Filter Binary_Value 243 5118_1 RD Active on Alarm RAM Battery Issue Binary_Value 244 5119_1 RD Active on Alarm Master Unit Communication Lost Binary_Value 245 5120_1 RD Active on Alarm High Power Shutdown Binary_Value 246 5121_1 RD Active on Alarm Supply Fluid Temp Sensor Issue Binary_Value 247 4651_1 RD Active on Alarm Unspecified General Event Binary_Value 248 5588_1 RD Active on Alarm SEC Unspecified General Event Binary_Value 249 6232_1 RD Active on Alarm SEC Communication Lost Binary_Value 250 6233_1 RD Active on Alarm Static Pressure Sensor Issue Binary_Value 251 5629_1 RD Active on Alarm Static Pressure Sensor Out of Range Binary_Value 252 5910_1 RD Active on Alarm Power Source 'A' Issue Binary_Value 253 6236_1 RD Active on Alarm Power Source B Failure Binary_Value 254 6237_1 RD Active on Alarm Fluid Flow Sensor Issue Binary_Value 255 5912_1 RD Active on Alarm Fluid Temperature Sensor Issue Binary_Value 256 5911_1 RD Active on Alarm Unit Code Missing Binary_Value 257 5418_1 RD Active on Alarm Liebert® IntelliSlot™ Modbus/BACnet Reference Guide 446 BACnet Communications—Thermal Management Products Table 4-8 Liebert CRV™—Binary Data (continued) Controller Liebert iCOM® v4 Data Label Object Type Instance Object Name Access Notes Condenser Outside Air Temp Sensor Issue Binary_Value 259 5535_1 RD Active on Alarm Condenser Outside Air Temp Out of Opera