SITE PLANNING DATA—LIEBERT® eXM™ 3-PHASE UPS: 10-200KVA/KW, 60HZ, 208VAC, SINGLE & DUAL INPUT MAINTENANCE BYPASS OR BYPASS DISTRIBUTION CABINET See Note 5 MBB * System AC Input 3 Wire + GND BIB See Note 6 MIB Static Bypass AC Output 208V 4 Wire + GND Local Grounding Electrode See Note 1 1. 2. 3. 4. 5. 6. 7. • • • Install in accordance with national and local electrical codes. Input and bypass must share the same single source. UPS system input and output cables must be run in separate conduits. Control wiring must be run in separate conduits Optional input transformer. Optional distribution for 10-100kVA units only. Internal battery breaker is optional on UPS with internal batteries; battery breaker is factory-supplied with external Liebert battery cabinets. BIB - Bypass Isolation Breaker MBB - Maintenance Bypass Breaker MIB - Maintenance Isolation Breaker * External Overcurrent Protection By Others UPS Field-Supplied Wiring BATTERY See Note 7 Notes for Tables • Nominal (Nom) current is based on full rated output load at nominal input voltage. • Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions. • UPS input and bypass cables must be run in separate conduit from output cables. • Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2. • Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered non-continuous). Continuous and noncontinuous currents are defined in NEC 215. Nominal AC output current (considered continuous) is based on full rated output load. Output breakers are either supplied by the customer or by using the optional Liebert Bypass Distribution Cabinet. • Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 2008. • Wiring requirements: AC Input: 3-phase, 4-wire, plus ground AC Output: 3-phase, 3- or 4-wire, plus ground • All wiring is to be in accordance with national and local electric codes. • Minimum access clearance is 36" (914mm) front; ventilation clearance is 24" (610mm) above and 0-5" (127mm) in the rear, depending on anchoring method. • Top or bottom cable entry through removable access plates. Punch plate to suit conduit size, then replace. • Control wiring and power wiring must be run in separate conduit. • Dimensions shown include an internal battery (40kVA frame only). • Weights shown do not include an internal battery nor optional cabinets or features. • When a Liebert Bypass Distribution Cabinet is not used, the customer must supply the input circuit breaker with a 120VAC shunt trip on the bypass feed only. The shunt trip drive capability is 8A. • If site configuration includes a backup emergency generator, Emerson recommends that the engine generator set be properly sized and equipped for a UPS application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS-compatible regulator (generator voltage regulation). Consult generator manufacturer for required generator options and sizing. • If site configuration includes an automatic transfer switch, refer to Liebert Power Line titled “Criteria for Application of Automatic Transfer Switches (ATS) With Uninterruptible Power Supply (UPS) Systems,” publication 91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliary contacts to provide a UPS “on generator” signal. Consult transfer switch manufacturer for required transfer switch options and sizing. • If site configuration requires an external isolated maintenance bypass circuit, it should be noted that utility AC input might not be in phase with the UPS AC output. Consult an Emerson sales representative or applications engineer. 1 Table 1 Site planning data—10-100kVA, 60Hz, 208VAC, single input UPS Rating Voltage AC Input AC Output Current, A Input Output Battery Rec. OPD Nom. VDC Mechanical Data Current, A Maximum Discharge Unit Weight, lb. (kg) Dimensions WxDxH, in. (mm) 40 kVA Frame 100 kVA Frame Heat Dissipation, BTU/hr (kWH) Cooling Air CFM (m3/hr) kVA kW 10 10 208 208 30 34 45 288 47 28 40 684 (310) NA 2217 (0.65) 67.8 (115) 15 15 208 208 45 51 70 288 70 42 60 684 (310) NA 3245 (0.95) 67.8 (115) 20 20 208 208 59 68 90 288 93 56 70 684 (310) 684 (310) 3843 (1.13) 67.8 (115) 30 30 208 208 89 102 150 288 140 83 110 758 (344) NA 6189 (1.81) 135.6 (231) 40 40 208 208 119 136 175 288 187 111 150 758 (344) 758 (344) 7610 (2.23) 135.6 (231) 60 60 208 208 178 205 300 288 280 167 225 NA 844 (383) 11278 (3.30) 203.4 (346) Nom. Max Nom. OPD 23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000) 80 80 208 208 237 273 350 288 373 222 300 NA 918 (416) 14977 (4.39) 271.2 (462) 100 100 208 208 297 341 450 288 467 278 350 NA 992 (450) 18645 (5.46) 339 (575) Table 2 Site planning data—10-100kVA, 60Hz, 208VAC, dual input UPS Rating Voltage AC Input AC Output Rectifier Current, A kVA kW Input Output Nom. Max Bypass Current, A Rec. OPD Nom. Rec. OPD Battery Nom. VDC Maximum Discharge Mechanical Data Current, A Nom. OPD Unit Weight, lb. (kg) Dimensions WxDxH, in. (mm) 40 kVA Frame 100 kVA Frame Heat Dissipation, BTU/hr (kWH) Cooling Air, CFM (m3/hr) 10 10 208 208 30 34 45 28 40 288 47 28 40 684 (310) NA 2217 (0.65) 67.8 (115) 15 15 208 208 45 51 70 42 60 288 70 42 60 684 (310) NA 3245 (0.95) 67.8 (115) 20 20 208 208 59 68 90 56 70 288 93 56 70 684 (310) 684 (310) 3843 (1.13) 67.8 (115) 30 30 208 208 89 102 150 83 110 288 140 83 110 758 (344) NA 6189 (1.81) 135.6 (231) 40 40 208 208 119 136 175 111 150 288 187 111 150 758 (344) 758 (344) 7610 (2.23) 135.6 (231) 60 60 208 208 178 205 300 167 225 288 280 167 225 NA 844 (383) 11278 (3.30) 203.4 (346) 23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000) 80 80 208 208 237 273 350 222 300 288 373 222 300 NA 918 (416) 14977 (4.39) 271.2 (462) 100 100 208 208 297 341 450 278 350 288 467 278 350 NA 992 (450) 18645 (5.46) 339 (575) 2 Table 3 Site planning data—10-100kVA, 60Hz, 480VAC in, 208VAC out, single input, with 480V:208V transformer UPS Rating AC Input Voltage Input Output Current, A Nom. Max Nom. VDC Mechanical Data AC Output Current, A Battery Maximum Discharge Unit Weight, lb. (kg) Rec. OPD 40kVA Frame 100kVA Frame Heat Dissipation, BTU/hr (kWH) Cooling Air, CFM (m3/hr) kW 10 10 480 208 13 15 20 288 47 28 40 684 (310) NA 1535 (0.45) 67.8 (115) 15 15 480 208 20 23 30 288 70 42 60 684 (310) NA 2303 (.675) 67.8 (115) 20 20 480 208 27 31 40 288 93 56 70 684 (310) 684 (310) 3071 (0.9) 67.8 (115) 30 30 480 208 40 46 60 288 140 83 110 758 (344) NA 4606 (1.35 135.6 (231) 40 40 480 208 53 61 80 288 187 111 150 758 (344) 758 (344) 6142 (1.8) 135.6 (231) 60 60 480 208 80 91 125 288 280 167 225 NA 844 (383) 9213 (2.7) 203.4 (346) Rec. OPD Nom. Dimensions WxDxH, in. (mm) kVA 23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000) 80 80 480 208 106 122 175 288 373 222 300 NA 918 (416) 12284 (3.6) 271.2 (462) 100 100 480 208 133 152 200 288 467 278 350 NA 992 (450) 15354 (4.5) 339 (575) Table 4 Site planning data—10-100kVA, 60Hz, 480VACin, 208VAC out, dual input, with 480V:208V transformer AC Input UPS Rating kVA kW Voltage Mechanical Data Rectifier Current, A Bypass Current, A Battery AC Output Current, A Rec. Nom. Maximum Rec. Input Output Nom. Max OPD Nom. OPD VDC Discharge Nom. Rec. OPD Unit Weight, lb. (kg) Dimensions WxDxH, in. (mm) 40kVA Frame 100kVA Frame Heat Dissipation, Cooling Air, BTU/hr (kWH) CFM (m3/hr) 10 10 480 208 13 15 20 28 40 288 47 28 40 684 (310) NA 1535 (0.45) 67.8 (115) 15 15 480 208 20 23 30 42 60 288 70 42 60 684 (310) NA 2303 (.675) 67.8 (115) 20 20 480 208 27 31 40 56 70 288 93 56 70 684 (310) 684 (310) 3071 (0.9) 67.8 (115) 30 30 480 208 40 46 60 83 110 288 140 83 110 758 (344) 4606 (1.35) 135.6 (231) 40 40 480 208 53 61 80 111 150 288 187 111 150 60 60 480 208 80 91 125 167 225 288 280 167 225 23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000) NA 758 (344) 758 (344) NA 844 (383) 6142 (1.8) 135.6 (231) 9213 (2.7) 203.4 (346) 80 80 480 208 106 122 175 222 300 288 373 222 300 NA 918 (416) 12284 (3.6) 271.2 (462) 100 100 480 208 133 152 200 278 350 288 467 278 350 NA 992 (450) 15354 (4.5) 339 (575) 3 Table 5 Site planning data—10-100kVA, 60Hz, 600VAC in, 208VAC out, single input, with 600V:208V transformer AC Input UPS Rating Voltage Current, A Mechanical Data AC Output Current, A Battery Unit Weight, lb. (kg) kVA kW Input Output Nom. Max. Rec. OPD Nom. VDC Maximum Discharge Nom. Rec. OPD 10 10 600 208 11 12 15 288 47 28 40 684 (310) NA 1535 (0.45) 67.8 (115) 15 15 600 208 16 18 25 288 70 42 60 684 (310) NA 2303 (.675) 67.8 (115) 20 20 600 208 22 25 30 288 93 56 70 684 (310) 684 (310) 3071 (0.9) 67.8 (115) 30 30 600 208 32 37 50 288 140 83 110 758 (344) NA 4606 (1.35 135.6 (231) 40 40 600 208 43 49 60 288 187 111 150 758 (344) 758 (344) 6142 (1.8) 135.6 (231) 60 60 600 208 64 73 100 288 280 167 225 NA 844 (383) 9213 (2.7) 203.4 (346) Dimensions WxDxH, in. (mm) 23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000) 40kVA Frame 100kVA Frame Heat Dissipation, BTU/hr (kWH) Cooling Air, CFM (m3/hr) 80 80 600 208 85 98 125 288 373 222 300 NA 918 (416) 12284 (3.6) 271.2 (462) 100 100 600 208 106 122 150 288 467 278 350 NA 992 (450) 15354 (4.5) 339 (575) Table 6 Site planning data—10-100kVA, 60Hz, 600VAC in, 208VAC out, dual input, with 600V:208V transformer AC Input UPS Rating Voltage Battery Rectifier Current, A Mechanical Data Bypass Current, A Rec. kVA kW Input Output Nom. Max OPD Nom. Rec. OPD AC Output Current, A Nom. VDC Maximum Rec. Discharge Nom. OPD Unit Weight, lb. (kg) Dimensions WxDxH, in. (mm) 40kVA Frame 100kVA Frame Heat Dissipation, Cooling Air, BTU/hr (kWH) CFM (m3/hr) 10 10 600 208 11 12 15 28 40 288 47 28 40 684 (310) NA 1535 (0.45) 67.8 (115) 15 15 600 208 16 18 25 42 60 288 70 42 60 684 (310) NA 2303 (0.675) 67.8 (115) 20 20 600 208 22 25 30 56 70 288 93 56 70 684 (310) 684 (310) 3071 (0.9) 67.8 (115) 30 30 600 208 32 37 50 83 110 288 140 83 110 4606 (1.35) 135.6 (231) 40 40 600 208 43 49 60 111 150 288 187 111 150 NA 23-5/8 x 39-3/8 x 78-3/4 758 (344) (600 x 1000 x 2000) 758 (344) 758 (344) 60 60 600 208 64 73 100 167 225 288 280 167 225 80 80 600 208 85 98 125 222 300 288 373 222 300 NA 100 100 600 208 106 122 150 278 350 288 467 278 350 NA 4 NA 6142 (1.8) 135.6 (231) 9213 (2.7) 203.4 (346) 918 (416) 12284 (3.6) 271.2 (462) 992 (450) 15354 (4.5) 339 (575) 844 (383) Table 7 Site planning data—20-200kVA, 60Hz, 208VAC, single input, 200kVA frame Voltage UPS Rating kVA kW AC Input Battery Current, A Input Output Nom. Rec. Max Nominal VDC OPD AC Output Current, A Maximum Discharge Nom. Mechanical Data 200 kVA Frame Dimensions OPD W x D x H, in. (mm) Unit Weight lb. (kg) Heat Dissipation BTU/hr (kWH) Cooling Air CFM (m3/hr) 20 20 208 208 59 68 90 288 93 56 70 852 (387) 3843 (1.13) 68 (115) 40 40 208 208 119 136 175 288 187 111 150 926 (420) 7610 (2.23) 136 (231) 60 60 208 208 178 205 300 288 280 167 225 1000 (453) 11278 (3.30) 203 (346) 80 80 208 208 237 273 350 288 373 222 300 1073 (487) 14977 (4.39) 271 (462) 100 100 208 208 297 341 450 288 467 278 350 1147 (520) 18645 (5.46) 339 (575) 120 120 208 208 356 409 600 288 560 333 450 1221 (554) 21193 (6.21) 407 (691) 140 140 208 208 415 478 600 288 653 389 500 1295 (587) 23512 (6.89) 475 (806) 160 160 208 208 475 546 700 288 747 444 600 1368 (621) 29529 (8.65) 542 (922) 180 180 208 208 534 614 800 288 840 500 700 1442 (654) 31994 (9.37) 610 (1037) 200 200 208 208 594 682 1000 288 933 555 700 1516 (688) 35548 (10.42) 678 (1152) 34-2/3 x 39-3/8 x 78-3/4 (880 x 1000 x 2000) Table 8 Site planning data—20-200kVA, 60Hz, 208VAC, dual input, 200kVA Frame UPS Rating kVA kW AC Input Voltage Input Output Current, A Nom. Max. Rec. OPD Bypass Current, A Nom. Rec. Battery Nominal VDC Maximum Discharge AC Output Current, A Nom. OPD Mechanical Data 200kVA Frame Dimensions W x D x H, in. (mm) Unit Weight lb. (kg) Heat Dissipation BTU/hr (kWH) Cooling Air CFM (m3/hr) 20 20 208 208 59 68 90 56 70 288 93 56 70 852 (387) 3843 (1.13) 68 (115) 40 40 208 208 119 136 175 111 150 288 187 111 150 926 (420) 7610 (2.23) 136 (231) 60 60 208 208 178 205 300 167 225 288 280 167 225 1000 (453) 11278 (3.30) 203 (346) 80 80 208 208 237 273 350 222 300 288 373 222 300 1073 (487) 14977 (4.39) 271 (462) 100 100 208 208 297 341 450 278 350 288 467 278 350 1147 (520) 18645 (5.46) 339 (575) 120 120 208 208 356 409 600 333 450 288 560 333 450 1221 (554) 21193 (6.21) 407 (691) 140 140 208 208 415 478 600 389 500 288 653 389 500 1295 (587) 23512 (6.89) 475 (806) 160 160 208 208 475 546 700 444 600 288 747 444 600 1368 (621) 29529 (8.65) 542 (922) 180 180 208 208 534 614 800 500 700 288 840 500 700 1442 (654) 31994 (9.37) 610 (1037) 200 200 208 208 594 682 1000 555 700 288 933 555 700 1516 (688) 35548 (10.42) 678 (1152) 5 34-2/3 x 39-3/8 x 78-3/4 (880 x 1000 x 2000) Table 9 General specifications INPUT OUTPUT Voltage 208/120, 220/127VAC, 50/60Hz, 3-phase, 4-wire plus ground Voltage 208/120, 220/127VAC, 50/60Hz, 3-phase, 4-wire plus ground Voltage Range without derating +15%, -20% ±5% Frequency Range 40-70Hz Voltage Adjustment Range THDi (Current Distortion) 5% maximum reflected THD at full load Voltage Regulation 1% for balanced load 5% regulation for unbalanced load Power Factor 0.99 full load, 0.98 half load Dynamic Regulation ±5% deviation for 100% load step ±1% for loss or return of AC input Surge Protection Withstands input surges w/o damage, per criteria in IEC 1000-4-5 (w/ surge suppressor option ANSI C62.41 (IEEE 587) CAT A3 & B3 Transient Response Time Recover to ±5% of output voltage within 1/2 cycle ENVIRONMENTAL Operating Temperature UPS: 32° to 104°F (0-40°C) Battery: 68° to 86°F (20-30°C) THDv For linear loads, 2% THD; Less than 5% THD for 100% nonlinear loads without kVA/kW derating Non-Operating Temperature -4° to 158°F (-20° to 70°C) Phasing Balance 120° ±1° for balanced load 120° ±1.5° for 100% unbalanced load Relative Humidity 0-95% non-condensing Operating Altitude Up to 3,300 ft. (1,000m) without derating Frequency Regulation ±0.1% to ±0.25% Acoustical Noise Less than 59 dBA typical (100kVA) Acoustical Noise, at 55 in. (1.4m) Load Power Factor Range 0.5 lagging to 0.9 leading without derating STANDARDS Listed to UL 1778 UPS standards, and CSA certified. Meets current requirements for safe, high performance UPS operation. Overload 100% load, continuous 110% load, 60 minutes; 125% load, 10 minutes; 150% load, 60 seconds, with true sinusoidal waveform Table 10 Battery specifications and run times Battery Code 10kVA 15kVA 20kVA 30kVA 40kVA Added Internal Battery Weight, lb. (kg) F 22 12 8 — — 528 (239) HX 150E-FR H 36 21 14 8 — 624 (283) HX 205-FR M 52 32 22 13 9 1032 (468) HR 1500 G 26 16 11 6 — 648 (294) HR 2000 L 46 27 18 10 5 960 (435) Model HX 100-FR Battery Time, Minutes 6 Table 11 Optional bypass distribution cabinet weights and dimensions Nameplate Rating, kVA 10-40 60-100 Dimensions, WxDxH, in. (mm) 23-5/8 x 39-1/2 x 78-3/4 (600 x 1000 x 2000) BDC Weight, lb (kg No Distribution 525 (239) 550 (250) 225A Panelboard 625 (284) — 400A Panelboard No Distribution and 480V Input Transformer — 660 (300) 1110 (505) 1522 (692) No Distribution and 600V Input Transformer 1125 (511) 1507 (685) 225A Panelboard and 480V Input Transformer 1210 (550) — 225A Panelboard and 600V Input Transformer 1225 (557) — 400A Panelboard and 480V Input Transformer — 1632 (742) 400A Panelboard and 600V Input Transformer — 1617 (735) Two 225A Subfeed Breakers — 660 (300) Two 225A Subfeed Breakers and 480V Input Transformer — 1632 (742) Two 225A Subfeed Breakers and 600V Input Transformer — 1617 (735) Add 27 lb. (12 kg) for monitoring. 7 © 2014 Liebert Corporation Technical Support / Service United States All rights reserved throughout the world. Specifications subject to change without notice. 1050 Dearborn Drive 800-543-2378 ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. [email protected] P.O. Box 29186 SL-25645_REV1_06-16 Web site: www.liebert.com 8 Columbus, OH 43229