Liebert NX 40-200kVA; Site Planning Data; 50/60Hz (R08/10); SL-25218

LIEBERT® NX™ 3-PHASE UPS: 40-200KVA, 60HZ, 480VAC - SITE PLANNING DATA
The Liebert NX is a true on-line,
double conversion, three-phase
UPS system that delivers
complete, centralized power
protection for mission-critical
systems.
General Specifications
INPUT
Voltage
480VAC, 60Hz, 3-phase 3-wire plus ground
Voltage Range w/o derating
+15%, -20%
Frequency Range
57-63Hz
Current Distortion
3% maximum reflected THD at full load
Current Limit
125% of full load input current
Power Factor
>0.99 lagging at full load; >0.98 lagging at half load
Surge Protection
Sustains input surges without damage, per criteria listed in IEC 61000-4-5
OUTPUT
Voltage
480VAC, 60Hz, 3-phase 3-wire plus ground
Voltage Adjustment Range
±5%
Voltage Regulation
1% for balanced load 2% for 100% unbalanced load
Dynamic Regulation
±5% deviation for 100% load step; ±1% for loss or return of AC input
Transient Response Time
Recover to ±5% of output voltage within 1/2 cycle
Voltage Distortion
For linear loads, 1% THD; Less than 4% THD for 100% nonlinear loads without kVA/kW derating
Phasing Balance
120° ±0.5° for balanced load; 120° ±1° for 100% unbalanced load
Frequency Regulation
±0.05% single module; ±0.25% paralleled modules
Load Power Factor Range
0.5 lagging to 1.0 without derating
Overload
125% of full load for 10 minutes; 150% for 1 minute, with true sinusoidal waveform
ENVIRONMENTAL
Operating Temperature
UPS: 32° to 104°F (0-40°C); Battery: 68° to 86°F (20-30°C)
Non-Operating Temperature
-13° to 158°F (-25° to 70°C)
Relative Humidity
0-95% non-condensing
Operating Altitude
Up to 6,500 ft. (2,000m) without derating
Acoustical Noise (full load)
80kVA
<67dB at 80-104°F (27-40°C) ambient; <61dB below 80°F (27°C) ambient
120kVA
<69dB at 80-104°F (27-40°C) ambient; <63dB below 80°F (27°C) ambient
200kVA
<74dB at 80-104°F (27-40°C) ambient; <68dB below 80°F (27°C) ambient
STANDARDS
Listed to UL 1778 UPS standards, and CSA certified. Meets current requirements for safe high performance UPS operation.
1
Site Planning Data - Single Input, 40-200kVA, 60Hz, 480VAC
Site Planning Data - Single Input, 40-200kVA, 60Hz, 480VAC
UPS Rating
Voltage
AC Input
Current (A)
Input Output
Nom. Nom. Nom. Max.
Battery
Rec.
OCPD
kVA
kW
40
36
480
480
48
60
60
54
480
480
71
89
80
72
480
480
94
118
150
80
72
480
480
94
118
150
80
AC Output
Battery
Current (A)
Nom.
Max.
Disconnect
VDC Discharge
Rating
Nom. OCPD
480
106
225
48
70
110 / 125 480
157
225
72
100
480
208
225
96
125
480
205
350
96
125
100
90
480
480
117
147
175
480
258
350
120
150
120
108
480
480
140
175
225
480
307
350
144
200
160
144
480
480
186
233
300
480
411
500
192
250
200
180
480
480
234
293
350
480
511
600
241
300
1
2,3,7,11
5
4
1,3,7,11
1,3,7,11
5
See Notes for Table (below):
Mechanical Data
Dimensions
WxDxH
in. (mm)
Weight
lb. (kg)
25.5 x 39.0 x 78.7
(648 x 990 x 2000)
1290
(585)
41.0 x 39.0 x 78.7 1422
(1040 x 990 x 2000) (645)
64.4 x 39.0 x 78.7 2201
(1636 x 990 x 2000) (1000)
12, 13
12
Heat Dissipation Cooling Airflow
BTU/hr (kWH)
CFM (m3/hr)
12,200 (3.6)
620 (1050)
15,400 (4.5)
620 (1050)
20,600 (6.0)
620 (1050)
19,700 (5.8)
920 (1550)
24,300 (7.1)
920 (1550)
28,700 (8.4)
920 (1550)
35,900 (10.5)
1590 (2700)
47,000 (13.8)
1590 (2700)
—
—
Notes for Table
Additional Notes
1.
• Input and output wiring and breakers for a Liebert NX with Softscale
technology should be sized for the maximum scalable capacity. For example, a
40kVA Liebert NX that is scalable to 80kVA should be installed with wiring
and breakers rated for an 80kVA configuration.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Nominal (Nom) current is based on full rated output load at nominal input
voltage.
Maximum (Max) current is short duration for battery recharge conditions.
UPS input cables must be run in separate conduit from output cables.
Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
OCPD = Overcurrent Protection Device. Recommended AC input and AC
output overcurrent protection represents 125% of nominal full load current
(continuous) plus 100% of recharge current (non-continuous) per NEC 215.
Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized
ground conductors are recommended.
Wiring requirements: AC Input: 3-phase, 3-wire, plus ground
AC Output: 3-phase, 3-wire, plus ground
All wiring is to be in accordance with national and local electric codes.
Minimum access clearance is 3 ft. (0.9m) front and 8 in. (203mm) above
the UPS.
Top or bottom cable entry through removable access plates. Punch plate to
suit conduit size, then replace.
Control wiring and power wiring must be run in separate conduit.
Dimensions and weights in table do not include external battery cabinet.
80-200kVA UPS dimensions include UPS wiring section for installation
without Liebert NX BDC. Deduct 15.5" from UPS width when a Liebert NX
BDC will be used.
• If site configuration includes a backup emergency generator, it is recommended that the engine generator set be properly sized and equipped for a
UPS application. Generator options would typically include an isochronous
governor (generator frequency regulation) and a UPS-compatible regulator
(generator voltage regulation). Consult generator manufacturer for required
generator options and sizing.
• It is recommended that the transfer switch be equipped with auxiliary contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.
• If site configuration requires an external isolated maintenance bypass circuit,
it should be noted that utility AC input might not be in phase with the UPS AC
output. Consult an Emerson Network Power sales representative or applications engineer.
• The UPS must be fed from a solidly grounded wye or delta AC source. Not for
use with impedance-grounded systems, corner-grounded or high leg delta systems. For these applications, an isolation transformer must be installed
between the AC feed and the UPS.
2
Site Planning Data - Dual Input, 40-200kVA, 60Hz, 480VAC
Site Planning Data - Dual Input, 40-200kVA, 60Hz, 480VAC
UPS Rating
Voltage
kVA
kW
Input
Nom.
40
36
480
AC Input
Current
Out(A)
put
Nom. Nom. Max.
480
48
60
Bypass Input
Rec.
OCPD
80
Battery
AC Output
Current
(A)
Battery
Current
Max.
Dis(A)
Rec. Nom. Dis- connect
Nom. OCPD VDC charge Rating Nom. OCPD
48
70
480
106
225
48
54
480
480
71
89
110/125
72
110
480
157
225
72
110
80
72
480
480
94
118
150
96
125
480
208
225
96
125
80
72
480
480
94
118
150
96
125
480
205
350
96
125
90
480
480
117
147
175
120
150
480
258
350
120
Dimensions
WxDxH
in. (mm)
Heat
Cooling
Weight Dissipation
Airflow
lb.
(kg) BTU/hr (kWH) CFM (m3/hr)
70
60
100
Mechanical Data
150
25.5x39.0x78.7
(648x990x2000)
1290
(585)
41.0x39.0x78.7 1422
(1040x990x2000) (645)
12,200 (3.6)
620 (1050)
15,400 (4.5)
620 (1050)
20,600 (6.0)
620 (1050)
19,700 (5.8)
920 (1550)
24,300 (7.1)
920 (1550)
920 (1550)
120
108
480
480
140
175
225
144
200
480
307
350
144
200
28,700 (8.4)
160
144
480
480
186
233
300
192
250
480
411
500
192
250
35,900 (10.5) 1590 (2700)
200
180
480
480
234
293
350
241
300
480
511
600
241
300
1
2,3,7,11
5
—
—
4
1,3,7,11
1,3,7,11
5
See Notes for Table (below):
64.4x39.0x78.7 2201
(1636x990x2000) (1000) 47,000 (13.8) 1590 (2700)
12, 13
12
—
—
Notes for Table
Additional Notes
1.
• Input and output wiring and breakers for a Liebert NX with Softscale
technology should be sized for the maximum scalable capacity. For example, a
40kVA Liebert NX that is scalable to 80kVA should be installed with wiring
and breakers rated for an 80kVA configuration.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
Nominal (Nom) current is based on full rated output load at nominal input
voltage.
Maximum (Max) current is short duration for battery recharge conditions.
UPS input and bypass cables must be run in separate conduit from output
cables.
Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
OCPD = Overcurrent Protection Device. Recommended AC input and AC
output overcurrent protection represents 125% of nominal full load current
(continuous) plus 100% of recharge current (non-continuous) per NEC 215.
Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized
ground conductors are recommended.
Wiring requirements: AC Input: 3-phase, 3-wire, plus ground
AC Output: 3-phase, 3-wire, plus ground
All wiring is to be in accordance with national and local electric codes.
Minimum access clearance is 3 ft. (0.9m) front and 8 in. (203mm) above
the UPS.
Top or bottom cable entry through removable access plates. Punch plate to
suit conduit size, then replace.
Control wiring and power wiring must be run in separate conduit.
Dimensions and weights in table do not include external battery cabinet.
80-200kVA UPS dimensions include UPS wiring section for installation
without Liebert NX BDC. Deduct 15.5" from UPS width when a Liebert NX
BDC will be used.
• If site configuration includes a backup emergency generator, it is recommended that the engine generator set be properly sized and equipped for a
UPS application. Generator options would typically include an isochronous
governor (generator frequency regulation) and a UPS-compatible regulator
(generator voltage regulation). Consult generator manufacturer for required
generator options and sizing.
• It is recommended that the transfer switch be equipped with auxiliary contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.
• If site configuration requires an external isolated maintenance bypass circuit,
it should be noted that utility AC input might not be in phase with the UPS AC
output. Consult an Emerson Network Power sales representative or applications engineer.
• The UPS must be fed from a solidly grounded wye or delta AC source. Not for
use with impedance-grounded systems, corner-grounded or high leg delta systems. For these applications, an isolation transformer must be installed
between the AC feed and the UPS.
3
External Battery Cabinet
External Battery Cabinet
Battery
Mfr.
Battery
Type
HX-205FR
Dimensions
Weight
in. (mm)
lb. (kg.)
33.5 x 39.0 x 78.7
(850 x 990 x 2000)
Enersys
40
60
80
80
100
120
160
200
1
18
10
6
—
—
—
—
—
2
45
27
18
—
—
—
—
—
3
72
46
32
—
—
—
—
—
4
100
65
46
—
—
—
—
—
1
30
16
10
11
7
6
—
—
2
72
45
31
31
21
18
12
9
3
111
73
51
52
39
33
21
16
4
156
102
73
74
55
46
33
23
1
36
21
14
14
9
8
5
—
2
93
53
37
37
28
23
16
11
3
149
95
65
65
49
38
27
20
4
207
135
96
96
72
54
38
30
1
41
25
17
17
12
10
6
—
2
101
64
41
45
33
27
19
14
3
159
103
73
74
55
45
32
23
4
221
146
103
104
79
66
45
35
1
63
38
26
26
19
16
10
7
2
142
90
65
66
50
38
27
20
3
222
144
103
103
78
66
46
34
4
318
202
145
146
110
92
66
49
2620 (1188)
3502 (1589)
HX-300FR
HX-330FR
3942 (1788)
48.8 x 39.0 x 78.7
(1240 x 990 x 2000)
HX-400FR
HX-500FR
Battery Run Time in Minutes by kVA
Qty. Battery
Cabinets
4302 (1952)
5502 (2496)
© 2008 Liebert Corporation
Technical Support / Service
United States
All rights reserved throughout the world. Specifications subject to change without notice.