NetSure 12V DC Power Systems Data Sheet

NetSure™ 12V DC Power System
Key Features
nHigh power density – up to 24 kW
(12V DC at 2000 A) per shelf in
three rack units (5.25")
nInterchangeable 3000 watt
rectifiers and battery backup
units, each slot accommodates
either unit
nBattery backup units that deliver
battery backup for 90 seconds
or operate in power boost mode
to supplement power output of
the rectifiers
nHot swappable – allows for system
expansion without disruption
nExpandable – parallel up to three
shelves per system for up to 72 kW
(12V DC at 6000 A) per system
nOperates over a wide AC input
voltage range with multiple input
configurations
nSafety compliance – UL 60950,
CAN/CSA-C22.2 No. 60950-1-03,
GR-3160, CE mark, RoHS, REACH
Compact, modular design provides a total DC power
solution, complete with battery backup, for a wide range
of data rack applications.
Description
The modular NetSure 12V DC power system provides up to 6000 amps at 12 volts DC via high
efficiency switch mode rectifiers rated at 3000 watts (250 amps) each and battery backup units
(BBUs) rated at 3000 watts (250 amps) each. It can be configured with up to three shelves rated
at 2000 amps each. The system also accommodates a System Control Card (SCC) that controls
and monitors the rectifiers and BBUs while communicating to the rack management system.
BBUs, which can be installed in any rectifier slot, can be operated in two modes. In the
classic backup power mode – during the loss of AC input – each BBU can deliver 3000
watts for 90 seconds. The BBUs also provide a power boost feature that delivers additional power to the system when the peak power requirement of the load temporarily
exceeds the output capacity of the installed rectifies or a settable power limit value.
The modular design allows the power system’s capacity to expand as your system needs grow.
Each 12V DC power shelf can accept a combination of nine individual, plug-in rectifiers or battery
backup units that can be easily installed live without system interruption. Each shelf provides
24000 watts (2000 A max) at 12V DC in three rack units (5.25") of height. The SCC can manage
up to three shelves for a maximum system capacity of 72000 watts (6000 A max) at 12V DC.
A rectifier is also available at 3300 watts (275 amps) maximum output for applications
requiring even higher power density.
Application
Standard Features
The NetSure 12V DC power system is ideal for data center racks and cabinets,
either custom or standard (such as Open Compute Project).
nEthernet interface to rack
management system via SNMP
Ordering Information
nSystem alarming
nCurrent and power limiting
nOver-voltage protection
nLoad sharing
nOver-temperature protection
nEmergency shutdown
12V Rectifier (left)
Battery Backup Unit (right)
EN605DRB-NS12VDC / 1115
Model Number
PSS12/2000-19BC
PSS12/2000-19B
M520H
R12-3000
B12-3000
R12-3300
Part Number
588706000xx*
588706000xx*
1M520HNA
1R123000
1B123000
1R123300
Description
12V DC power main shelf
12V DC power expansion shelf
12V DC System Control Card (SCC)
12V rectifier, 3000 watts
12V battery backup unit, 3000 watts
12V rectifier, 3300 watts
* Several options are available.
12V DC Power System Shown with
Six 12V Rectifiers, Three BBUs and One SCC
1
NetSure™ 12V DC Power System
Technical Specifications
Input
208 VAC / 240 VAC nominal single-phase with range of 176 VAC to 264 VAC
200 VAC / 208 VAC / 240 VAC nominal three-phase with range of 176 VAC to 264 VAC
380 VAC / 415 VAC / 480 VAC nominal three-phase (4-wire + PE) with range of 323 VAC to 528 VAC
Voltage, Rectifier and BBU 200 VAC / 208 VAC / 220 VAC / 240 VAC / 277 VAC nominal single-phase with range of 176 VAC to 305 VAC
Current, Rectifier
18.3 amps maximum at full power and 176 VAC
Current, BBU
0.55 amps maximum at 176 VAC
Circuit Protection
Fuses located in each line input of rectifiers and BBUs
Efficiency
94% typical
Voltage, Shelf
Output
Voltage
Current, Shelf
Current, Rectifier
Current, BBU
Capacity, BBU
Regulation
Dynamic Response
Filtering
12.3 VDC nominal, adjustable from 12.0 VDC to 13.2 VDC
2000 amps maximum
250 amps maximum at 12.0 VDC (3000 watts maximum)
250 amps maximum at 12.0 VDC (3000 watts maximum) for 90 seconds
75 Watt-Hours, 1500 cycles
Steady state output voltage remains within ±1 % of the pre-adjusted voltage for any load current from no load to full load
and over the specified input voltage range
For a step load change within the range of 10 % to 90 % of full rated current, the maximum voltage transient will not
exceed 5 % of the initial steady state voltage
Wide band noise does not exceed 120 mV peak to peak
Protection
Over-Voltage
Over-Current
Power Limit
Over-Temperature
Internal Fault On Output
Each rectifier and BBU will automatically shut down and lock out should its output voltage exceed a value set by the controller,
maximum set point is 13.2 VDC. Unit will automatically attempt to restart once. A second (backup) over-voltage protection
circuit will shut down and latch off the unit if the voltage exceeds 14.0 VDC.
Adjustable from 25 amps to 250 amps per rectifier and BBU
Non-adjustable limit of 3000 watts maximum per rectifier and BBU
Each rectifier and BBU will automatically shut down if the internal temperature of the module exceeds a predetermined value.
Operation will automatically resume after the over-temperature condition is removed.
Each rectifier and BBU contains an output blocking (ORing) circuit which prevents an internal fault in the unit from
affecting the bus voltage.
Physical Characteristics – Weight and Dimensions (H x W x D)
Shelf
17.5 kg (38.5 lb) without AC cords, 132 mm x 483 mm x 656 mm (5.2" x 19" x 25.8")
Rectifier
3.0 kg (6.6 lb), 124 mm x 41.4 mm x 453 mm (4.9" x 1.6" x 17.8")
BBU
4.1 kg (9.1 lb), 124 mm x 41.4 mm x 453 mm (4.9" x 1.6" x 17.8")
Environmental
Operating Temperature
Storage Temperature
Humidity
Altitude
EMC
Safety Compliance
-10 °C to +45 °C (+14 °F to +113 °F) without BBUs, 0 °C to +45 °C (+32 °F to +113 °F) with BBUs
-40 °C to +85 °C (-40 °F to +185 °F) without BBUs, consult manual for BBU storage temperature specifications
0 % to 95 % relative humidity, non-condensing
-200 feet to 10000 feet, maximum operating ambient temperature should be derated linearly (3 °C per 1000 ft.)
at elevation above 6000 ft
This unit conforms to the requirements of FCC Part 15, Subpart B, Class A and EN 300 386, Class A for radiated
and conducted noise
UL 60950, CAN/CSA-C22.2 No. 60950-1-03, GR-3160, CE mark, RoHS, REACH
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2015.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson™ and Consider it Solved are service marks and
trademarks of Emerson Electric Co. EnergyMaster ™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure™ and NetXtend™ are trademarks of Emerson
Network Power, Energy Systems, North America, Inc. Any other product, brand, or company names or logos are the property of the respective owner.
2
While every precaution has been taken to ensure accuracy and
completeness herein, Emerson Electric Co. assumes no responsibility,
and disclaims all liability, for damages resulting from use of this
information or for any errors or omissions. Specifications subject to
change without notice.