NetSure 700 C82 Data Sheet (English)

NetSure 700 Series DC Power System
+24 VDC, up to 17.4kW
NetSure 700 C82 (PS24600-2A/2200)
DC Power Solution
for Business-Critical Continuity TM
Key Benefits
NetSure 700 C82 (PS24600-2A/2200) is optimized for common fixed line
and mobile switch applications as well as other applications requiring up
to 17.4 kW of +24V DC power with excellent performance. This system
offers advanced features including intelligent battery monitoring and
remote monitoring. The cabinet comes fully equipped with integrated AC
and DC distribution.
Technical Specifications - Electrical Parameter
Input Data
Input Voltage
80Vac ~ 290Vac
Frequency range
45 ~ 65 Hz
Power factor
0.99
Output Data
Features
Nominal Output Voltage
Operating Voltage Range
nWide AC input voltage range: 80V~290V
Output Power/Rectifier
2.2 kW
Max output current
600 A
nPerfect lightning protection at both AC side and DC side.
nThe rectifier uses the active Power Factor Compensation
(PFC) technology, raising the power factor to 0.99; soft
switching technology, raising the efficiency to 88.0% .
nThe rectifier has ultra-low radiation. With advanced EMC
design, the rectifier meets international standards such as CE
and NEBS. Both the conducted and radiated interference
reach Class B
nThe rectifier is hot pluggable with two optional over-voltage
protection methods: hardware protection and software
protection. The latter one also has two optional modes: lockout at the first over-voltage and lock-out at the second overvoltage
nThe power supply system has complete fault protection and
fault alarm functions
nPerfect battery management including LLVD (optional),
BLVD, temperature compensation, auto voltage regulation,
stepless current limiting, battery capacity calculation and
on-line battery test, etc. Up to 200 pieces of historical alarm
records, and 10 sets of battery test data records
n Providing multiple communication ports (such as RS232,
modem and dry contacts), which enables flexible
networking and remote monitoring
+24Vdc
+21.6Vdc ~ +28.8Vdc
Current sharing
3%
Technical Specifications- Mechanical and Environmental Parameter
Dimensions
(mm)
Weight (kg)
Cabinet
1600 (H)
Monitoring module
M800D/ M501D
87 (H) 85.3 (W)
Rectifier R24-2200
Cabinet
132.3 (H) 85.3 (W) 287 (D)
98 (excluding rectifiers, monitoring module and batteries)
Rectifier R24-2200
600 (W)
400 (D)
287 (D)
3.5
Environmental Parameter
Operating Temperature
-5
C ~ 40
Storage Temperature
-40
C ~ 70
Relative Humidity
5%RH ~ 95%RH
Elevation
C
C
2000m (derating is necessary above 2000m)
NetSure 700 Series DC Power System
+24 VDC, up to 17.4kW
NetSure 700 C82 (PS24600-2A/2200)
DC Power Solution
for Business Critical Continuity TM
Embedded controller module M500S
Intelligent battery management
Control of rectifier and batteries
Visual and audible alarms
Latest 200 alarm history log
RS232, User configurable digital inputs
3 pairs of dry contacts
Query historical alarms and active alarms through the LCD
Rectifier Module R24-2200
Input voltage
nominal 200 ~ 250 Vac
Input voltage
permitted variation 85 ~ 290 Vac
Power factor
0.99
THD
<10% from 50 ~ 100% of rated load
Output voltage
default 26.8 Vdc, adjustment range 21.00 ~29.00 Vdc
Output power
2175 W @ Vout 26.8 Vdc
Max output current
82 A @ 26.8 Vdc
Efficiency
90%
Temperature range
-40 ~+70 C
RH (non-condensing)
0~95%
EMC
EN 300 386 class B, FCC CFR 47 part 15 class B, Telcordia GR-1089-CORE class B
Safety
IEC / EN / UL 60950
Dimensions: (HxWxD)
132 x 85 x 287mm, 5.20 x 3.36 x11 inches
Weight
3.5 kg, 7.7 lbs
RZ4-2200
DC Distributions
Battery low voltage disconnection (BLVD) routes
Load low voltage disconnection (LLVD) routes
AC power distributions
AC input
SPD
totally 6 MCBs, 2 x 63A/1P, 2x32A/1P, 2x10A/1P MCB
totally 14 MCBs, 4x100A NT00 fuse, 6x63A/1P, 4x32A/1P MCB
3-phase 4- wire system or 3 phase 5-wire system
Class C SPD
2x63A/3P MCB
M501D
Battery parameters
Factory setting
2x150Ah
Factory setting
from 2 to 5 strings with 50~5000Ah
M800D
Visit www.emersonnetwork.com.cn for more product information
Emerson Network Power
A global leader for critical business continuityTM
Emerson Network Power Co., Ltd.
No.1 Ke Fa Road, Science and Industrial Road,
Nanshan District, Shenzhen City
Tel: 68-755-86010808
Postcode: 518057
Emerson Network Power and the Emerson
Network Power Logo are trademarks and
service marks of Emerson Electric Co.
2009 Emerson All Rights Reserved
2009.4