NetSure 501 AC1(English)

Platform DC Power System NetSure 501 Series
DC Power Solution
TM
forBusiness-Critical Continuity
-48 VDC, up to 24kW
NetSure 501 AC1, NetSure 501 A61
(PS48360-2/1800,PS48180-2/1800)
Introduction
Platform Power System is Emerson next generation system for medium
exchanges, rural telecom networks and access networks, 2G and 3G base
station, transmission relay station, microwave/satellite communication
stations as well as other applications. The range of NetSure 501 platform
power series could be 3.48 kW to 24 kW covering most of the telecom
requirements of -48V DC power.
The system can be optimized cost-effectively to meet initial requirements,
whilst allowing for easy expansion in the future. Standard and advanced
controller options, configurable distribution and number of rectifier
modules are available to meet various demands.
NetSure 501 AC1, NetSure 501 A61
Description
IItem
NetSure 501 AC1
NetSure 501 A61
PS48360-2/1800-Y1
PS48180-2/1800-Y6 or
NetSure 501 AC1
PS48360-2/1800-WF
PS48180-2/1800-W6
Rectifier
Features
< High flexible configuration to meet various customer
requirements, easy for fast construction of communication
sites.
< Hot swap rectifier and controller, high power density
< Two over-voltage protection methods for options:
hardware protection and software protection.
< Perfect battery management includes the LLVD,
temperature compensation, auto voltage regulation,
stepless current limiting, battery capacity calculation and
on-line battery test, etc.
< The monitoring module can save up to 200 pieces of
historical alarm records, and 10 sets of battery test data
records
< Perfect lightning protection at perfect lightning protection
at both AC side and DC side
< The high power density rectifier uses the active Power
Factor Compensation (PFC) technology, raising the power
factor to 0.99.
Model: R48-1800 or
Model: R48-1800
or R48-2000
R48-2000
or R48-2000
Optional configuration:
Optional configuration:
Optional configuration:
2 pieces
2 pieces
2 pieces
12 pieces
6 pieces
12 pieces
Standard configuration:
Standard configuration: Standard configuration: 12
12 pieces
6 pieces
pieces (two rectifier subracks)
or 6 pieces(one rectifier subrack)
Monitoring
M520S
Module
AC input mode:
AC input
< Safety En60950
< Compliant with global standards delivers quality,
performance and dependability
Model: R48-1800
AC input mode:
AC input mode:
3P+N+PE/380V(+SPD)
3P+N+PE/ 380V+SPD
3P+N+PE/ 380V+SPD
or L+N+PE/220V+SPD
10 BLVD routes:
4 BLVD routes:
2
16A/1P,
2
16A/1P,
8
10A/1P MCB
2
32A/1P MCB
Or L1+L2+PE/220V+SPD
DC power
distribution 6 LLVD routes:
2
125A/1P, 2 80A/1P,
2
63A/1P MCB
Flexible configuration
3 LLVD routes:
3
100A/1P MCB
Battery MCB:
Battery MCB:
Maixmum battery MCB:
4
4
5
100A/1P
100A/1P
100A/1P
Battery
Maixmum battery
Maixmum battery
Maixmum battery
routes
Configuration:
configuration:
configuration:
4
4
(12V/165Ah) or
4 4
(12V/165Ah) or
4 4
(12V/165Ah) or
4
4
(12V/100Ah)
4 4
(12V/100Ah)
5 4
(12V/100Ah)
Two temperature sensors,
Optional
Parts
Two temperature sensors
Two temperature sensors
high-ohmic distribution
Unit (HOD), low-ohmic
Distribution unit (LOD)
Platform DC Power System NetSure 501 Series
-48 VDC, up to 24kW
NetSure 501 AC1, NetSure 501 A61
(PS48360-2/1800,PS48180-2/1800)
DC Power Solution
for Business-Critical Continuity TM
Technical specifications- Mechanical Parameter
600 600 2000 (Y1,Y6 )
Cabinet
Size (W
(mm)
D
600 600 500 (W6, WF)
H)
Rectifier
Battery compartment
Weight (kg)
600 600 1800 (SFA)
85.3 272 87.9
540 545 350 (accommodating 4
165Ah battery)
540 545 280 (accommodating 4
100Ah battery)
Cabinet (excluding
2000mm cabinet
140
rectifiers, monitoring
1800mm cabinet
130
module and batteries)
500mm cabinet
Rectifier
50
2.0
Technical specifications -Environmental Parameter
o
o
Operating Temperature
-5 C
Storage Temperature
-40oC
70oC
Relative Humidity
5%RH
95%RH
Elevation
W6
45 C
2000m (derating is necessary above 2000m)
Rectifier R48-1800A,R48-1800 and R48-2000
Input
Input voltage
80 to 300Vac
Frequency
45 to 65Hz
Power factor
0.99
Output
Output DC voltage
-42 to -58V
Output current
0 to 37.5 A for R48-1800; 0 to 41.7 A for R48-2000
Efficiency
93%
Maximum output power
1740W or 2000W
Rectifier
Controller: M520S
Intelligent battery management Latest 200 alarm history log
Display LCD with 4 16 characters
Language : English, Chinese
External Communication: RS232(modem) or TCP/IP
Protocol: YDN23
Inputs: 8 Digital Inputs Alarms/Events
Outputs: 8 Relay Outputs 1A, max 60V
Examples of Alarms: DC Power Plant Alarms AC mains failure,Rectifier failure, DC/DC converter failure, High voltage shut-down,
Fan failure, Thermal derating
Battery Cabinet (rack)
See separate datasheet for the detailed cabinet (rack) information
Emerson Network Power
A global leader for critical business continuityTM
Emerson Network Power Co., Ltd.
Address:No.1 Ke Fa Road, Science & IndustryPark,
Nanshan District,518057 Shenzhen, China Telep
hone: 86-755-86010808
Postcode: 518057
Emerson Network Power and the Emerson
Network Power Logo are trademarks and
service marks of Emerson Electric Co.
2009 Emerson All Rights Reserved
2009.11