tender text "Overvoltage protection" Class I (B) lightning current arrester PU1TSG 35kA/0.9kV-260V The sparkover gap is a single-pole lightning current arrester complying with the requirements of class B to DIN VDE 0675 part 6 (draft Nov 89)/A1:Mar 96) and class I to IEC 61643-1 (Feb 98) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). This overvoltage protection is used in TN, TT and IT systems in combination with several lightning arresters. The use of a sealed, triggered sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW directive (1st edition, 1998). The arrester is installed in the vicinity of the incoming line of the system to be protected in a conventional distribution board. The PU1TSG 35kA-260V is connected to the earthing system between the phase conductors (L1, L2, L3) and/or the neutral conductor in combination with three or four sparkover gaps. The 3+1 and 3+0/4+0 circuits can be used here. Besides a mains power failure, a function indicator comes on above 120 Vac to signal the failure of the starting electronics. Basic mains protection : 35 kA Rated voltage : 230 Vac Lightning test current (10/350µs): 35 kA Charge: 17.5 As Protection level at lightning test current < 0.9 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU1TSG 35kA/0.9kV-260V Order No. 8561260000 PU1TSG 50kA/1.5kV-260V The arrester is a single-pole lightning current arrester complying with the requirements of class B to DIN VDE 0675 part 6 (draft, Nov 1989 / A1, Mar 1996) and class I to IEC 61643-1 (Feb 1998) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). This overvoltage protection is used in TN, TT and IT systems in combination with several lightning arresters, frequently as an N-PE arrester in the 3+1 circuit. In combined systems, the PU 1 TSG 50 kA/1.5 kV-260 V can also be used in networks with a ≤500 A short-circuit current as a sparkover gap for 50kA between L and N. The use of a sealed, triggered sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW directive (1st edition, 1998). Basic mains protection : 50 kA Rated voltage : 230 Vac Lightning test current (10/350µs): 50 kA Charge: 25 As Protection level at lightning test current < 1.5 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU1TSG 50kA/1.5kV-260V Order No. 8561230000 PU1TSG 100kA/1.5kV-260V tender text "Overvoltage protection" The arrester is a single-pole lightning current arrester complying with the requirements of class B to DIN VDE 0675 part 6 (draft, Nov 1989 / A1, Mar 1996) and class I to IEC 61643-1 (Feb 1998) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). This overvoltage protection is used in TN, TT and IT systems in combination with several lightning arresters, frequently as an N-PE arrester in the 3+1 circuit. In combined systems, the PU 1 TSG 50kA/1.5 kV-260 V can also be used in networks with a ≤100A short-circuit current as a sparkover gap for 100kA between L and N. The use of a sealed, triggered sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW directive (1st edition, 1998). Basic mains protection : 100 kA Rated voltage : 230 Vac Lightning test current (10/350µs): 100 kA Charge: 50 As Protection level at lightning test current < 1.5 kV Max. back-up fuse of 125 A gl Type: Weidmüller PU1TSG 50kA/1.5kV-260V Order No. 8762020000 PU 1 TSG+ 50kA-330V The sparkover gap is a single-pole lightning current arrester complying with the requirements of class B to DIN VDE 0675 part 6 (draft Nov 89)/A1:Mar 96) and class I to IEC 61643-1 (Feb 98) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). This overvoltage protection is used in TN, TT and IT systems in combination with several lightning arresters, and represents the necessary lightning protection equipotential bonding between the building’s lightning protection system and the power supply network. According to DIN VDE V 0100 part 534 (Apr 1999), the PU 1 TSG+ 50kA-330V is frequently used in industrial networks in combination with several lightning arresters depending on the network specification, the phase-to-phase voltage and the technical connection conditions currently valid. This lightning arrester based on an unenclosed, triggered sparkover gap is installed as near as possible to the incoming line for the system to be protected in a conventional distribution board. Owing to the emissions given off when the sparkover gap is tripped, a safety clearance of min. 100 mm must be maintained between this and any potential-conducting components. Besides a mains power failure, a function indicator comes on above 120 Vac to signal the failure of the starting electronics. Basic mains protection : 50 kA Rated voltage : 330 Vac Lightning test current (10/350µs): 50 kA Charge: 25 As Protection level at lightning test current < 0.9 kV 25 kA short-circuit strength with max. back-up fuse of 250 A gl Type: Weidmüller PU 1 TSG+ 50kA-330V Order No. 856122000 PU 1 TSG+ 50kA-440V The sparkover gap is a single-pole lightning current arrester complying with the requirements of class B to DIN VDE 0675 part 6 (draft Nov 89)/A1:Mar 96) and class I to IEC 61643-1 (Feb 98) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). This overvoltage protection is used in TN, TT and IT systems in combination with several lightning arresters, and represents the necessary lightning protection equipotential bonding between the building’s lightning protection system and the power supply network. tender text "Overvoltage protection" According to DIN VDE V 0100 part 534 (Apr 1999), the PU 1 TSG+ 50kA-440V is frequently used in industrial networks in combination with several lightning arresters depending on the network specification, the phase-to-phase voltage and the technical connection conditions currently valid. This lightning arrester based on an unenclosed, triggered sparkover gap is installed as near as possible to the incoming line for the system to be protected in a conventional distribution board. Owing to the emissions given off when the sparkover gap is tripped, a safety clearance of min. 100 mm must be maintained between this and any potential-conducting components. Besides a mains power failure, a function indicator comes on above 120 Vac to signal the failure of the starting electronics. Basic mains protection : 50 kA Rated voltage : 440 Vac Lightning test current (10/350µs): 50 kA Charge: 25 As Protection level at lightning test current < 1.5 kV 25 kA short-circuit strength with max. back-up fuse of 250 A gl Type: Weidmüller PU 1 TSG+ 50kA-440V Order No. 8561250000 PU 4 B for TN-S networks Four-pole lightning arrester for protecting a TN-S 230/400 V three-phase system. Free from power follow current due to plug-in high-power varistors. Multi-core connection, cross-section up to 25 mm2, to IEC 947-7-1. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements of class B tested to IEC 1024 as well as DIN VDE 0675 part 6 (draft, Nov 1989). With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Basic mains protection 25 kA Rated voltage : 230V/400V Lightning test current (10/350µs): 25 kA Charge: 10 As Specific energy: 500 kJ/ohms Lightning impulse sparkover voltage (1.2/50µs) <2 kV Protection level at lightning test current < 2 kV 25 kA short-circuit strength with max. back-up fuse of 160 A gl Type: Weidmüller PU 4 B 280 VAC Order No. 8147020000 PU 4 BR for TN-S systems with remote signalling contact Four-pole lightning arrester for protecting a TN-S 230/400 V three-phase system. Free from power follow current due to plug-in high-power varistors. Multi-core connection, cross-section up to 25 mm2, to IEC 947-7-1. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements of class B tested to IEC 1024 as well as DIN VDE 0675 part 6 (draft, Nov 1989). With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red.Additional display of operational status by means of signalling contact (changeover contact). Basic mains protection 25 kA Rated voltage : 230V/400V Lightning test current (10/350µs): 25 kA Charge: 10 As Specific energy: 500 kJ/ohms Lightning impulse sparkover voltage (1.2/50µs) <2 kV tender text "Overvoltage protection" Protection level at lightning test current < 2 kV 25 kA short-circuit strength with max. back-up fuse of 160 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU 4 BR 280 VAC Order No. 8291640000 PU 3 B for TN-S networks Three-pole lightning arrester for protecting a TN-S 230/400 V three-phase system. Free from power follow current due to plug-in high-power varistors. Multi-core connection, cross-section up to 25 mm2, to IEC 947-7-1. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements of class B tested to IEC 1024 as well as DIN VDE 0675 part 6 (draft, Nov 1989). With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Basic mains protection 20 kA Rated voltage : 230V/400V Lightning test current (10/350µs): 20 kA Charge: 7 As Specific energy: 250 kJ/ohms Lightning impulse sparkover voltage (1.2/50µs) <2 kV Protection level at lightning test current < 2 kV 25 kA short-circuit strength with max. back-up fuse of 160 A gl Type: Weidmüller PU 3 B 280 VAC Order No. 8381890000 PU 3 BR for TN-C systems with remote signalling contact Lightning arrester for protecting a TN-C 230/400 V three-phase system. Free from power follow current due to plug-in high-power varistors. Multi-core connection, cross-section up to 25 mm2, to IEC 947-7-1. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements of class B tested to IEC 1024 as well as DIN VDE 0675 part 6 (draft, Nov 1989). With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Additional display of operational status by means of signalling contact (changeover contact). Basic mains protection 20 kA Rated voltage : 230V/400V Lightning test current (10/350µs): 20 kA Charge: 7 As Specific energy: 250 kJ/ohms Lightning impulse sparkover voltage (1.2/50µs) <2 kV Protection level at lightning test current < 2 kV tender text "Overvoltage protection" 25 kA short-circuit strength with max. back-up fuse of 160 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU 3 BR 280 VAC Order No. 8381900000 PU 0 B plug-in replacement arrester Replacement modules for lightning current arrester PU B These plug-in high-power varistors can be replaced after failure by a qualified technician. Type: Weidmüller PU 0 B Order No. 8381880000 class I and II combined arrester PU Combi I+II 4-conductor system Class I (B) overvoltage protection based on sparkover gap and class II (C) with varistors. The sparkover gap is a combined arrester complying with the requirements of class B/C to DIN VDE 0675 part 6 (draft, Nov 1989 / A1, Mar 1996) and class I/II to IEC 61643-1 (Feb 1998) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). The use of a sealed, triggered sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW directive (1st edition, 1998). The class I arresters are connected to the class II arresters using cross connection links (16mm²). The combined arrester is installed in the vicinity of the incoming line of the system to be protected in a conventional distribution board. Basic mains protection : 35 kA Rated voltage : 230 Vac Lightning test current (10/350µs): 35 kA L-N Charge: 17.5 As Protection level at lightning test current < 0.9 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU Combi I+II 4-conductor system Order No. 8729960000 PU R Combi I+II 4-conductor system with remote signalling contact Class I (B) overvoltage protection based on sparkover gap and class II (C) with varistors. The sparkover gap is a combined arrester complying with the requirements of class B/C to DIN VDE 0675 part 6 (draft, Nov 1989 / A1, Mar 1996) and class I/II to IEC 61643-1 (Feb 1998) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). The use of a sealed, triggered sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW directive (1st edition, 1998). The class I arresters are connected to the class II arresters using cross connection links (16mm²). The combined arrester is installed in the vicinity of the incoming line of the system to be protected in a conventional distribution board. Additional display of operational status by means of signalling contact (changeover contact). Basic mains protection : 35 kA Rated voltage : 230 Vac tender text "Overvoltage protection" Lightning test current (10/350µs): 35 kA L-N Charge: 17.5 As Protection level at lightning test current < 0.9 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU R Combi I+II 4-conductor system Order No. 8729970000 PU Combi I+II 5-conductor system Class I (B) overvoltage protection based on sparkover gap and class II (C) with varistors. The sparkover gap is a combined arrester complying with the requirements of class B/C to DIN VDE 0675 part 6 (draft, Nov 1989 / A1, Mar 1996) and class I/II to IEC 61643-1 (Feb 1998) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). The use of a sealed, triggered sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW directive (1st edition, 1998). The class I arresters are connected to the class II arresters using cross connection links (16mm²). The combined arrester is installed in the vicinity of the incoming line of the system to be protected in a conventional distribution board. Basic mains protection : 35 kA Rated voltage : 230 Vac Lightning test current (10/350µs): 35 kA L-N Charge: 17.5 As Lightning test current (10/350µs): 50 kA PE-N Protection level at lightning test current < 0.9 kV <1.5 kV PE-N 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU Combi I+II 5-conductor system Order No. 8729950000 PU R Combi I+II 5-conductor system with remote signalling contact Class I (B) overvoltage protection based on sparkover gap and class II (C) with varistors. The sparkover gap is a combined arrester complying with the requirements of class B/C to DIN VDE 0675 part 6 (draft, Nov 1989 / A1, Mar 1996) and class I/II to IEC 61643-1 (Feb 1998) which serves as lightning protection equipotential bonding for interface transition 0 to 1 (to IEC 1312-1). The use of a sealed, triggered sparkover gap satisfies the inspection requirements for class B overvoltage protection systems according to the VDEW directive (1st edition, 1998). The class I arresters are connected to the class II arresters using cross connection links (16mm²). The combined arrester is installed in the vicinity of the incoming line of the system to be protected in a conventional distribution board. Additional display of operational status by means of signalling contact (changeover contact). Basic mains protection : 35 kA Rated voltage : 230 Vac Lightning test current (10/350µs): 35 kA L-N tender text "Overvoltage protection" Charge: 17.5 As Lightning test current (10/350µs): 50 kA PE-N Protection level at lightning test current < 0.9 kV <1.5 kV PE-N 25 kA short-circuit strength with max. back-up fuse of 125 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU R Combi I+II 5-conductor system Order No. 8722990000 Class II (C) surge arrester Overvoltage protection complying with draft standard DIN VDE 0675 part 6 Class C (class II) arrester complying with IEC 61643-1. Mid-level surge arrester designed as a plug-in module for protecting mains supply networks and the connected consumer devices against overvoltages. Conductors with cross sections of 6 to 25 mm 2 connected via screw terminals. Self-monitoring, high-power and plug-in varistors are integrated in these modules. A fault is indicated after thermal and dynamic overload of the varistor. The following voltage variants are available: 60Vac, 130Vac, 230Vac, 500Vac. PU 4 C, 4-pole for TN-S systems Overvoltage protection for protecting the TN-S 230/400 V three-phase system. Free from power follow current due to plug-in powerful varistors. Flexible connection cross-sections up to 35 mm2. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements of class C tested to IEC61643-1. With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Rated voltage: 230/400V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <1.3 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 4 C 280 VAC Order No. 802150000 Rated voltage: 115/230V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <0.8 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 4 C 130 VAC Order No. 8291670000 tender text "Overvoltage protection" Rated voltage: 470/600V Limiting discharge current (8/20µs): 15 kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <2.2 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 4 C 550 VAC Order No. 8291720000 PU 4 C, 4-pole for TN-S systems with remote signalling contact Overvoltage protection for protecting the TN-S 230/400 V three-phase system. Free from power follow current due to plug-in powerful varistors. Multi-core connection, cross-sections of 6 to 25 mm 2. Mounted on TS 35 mounting rail to DIN EN 50 022. Tested to ÖVE-SN 60 part 1 and part 4, as well as DIN VDE 0675, part 6 (draft, Nov 1989). With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Additional display of operational status by means of signalling contact (changeover contact). Rated voltage : 230V/400V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <1.3 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU 4 CR 280 VAC Order No. 8021520000 Rated voltage: 115/230V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <0.8 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU 4 CR 130 VAC Order No. 8291690000 Rated voltage: 470/600V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <2.2 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Relay output: 250Vac/2A; 24Vdc/1A tender text "Overvoltage protection" Type: Weidmüller PU 4 CR 550 VAC Order No. 8494040000 PU 3 C, 3-pole for TN-C systems Overvoltage protection for protecting a TN-C 230/400 V three-phase system. Free from power follow current due to plug-in powerful varistors. Multi-core connection, cross-sections of 6 to 25 mm 2. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements of class C tested to IEC61643-1. With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Rated voltage : 230V/400V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <1.3 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 3 C 280 VAC Order No. 8021490000 Rated voltage: 115/230V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <0.8 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 3 C 130 VAC Order No. 8291660000 Rated voltage: 470/600V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <2.2 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 3 C 550 VAC Order No. 8197930000 PU 3 C, 3-pole for TN-C systems with remote signalling contact Overvoltage protection for protecting the TN-S 230/400 V three-phase system. Free from power follow current due to plug-in powerful varistors. Multi-core connection, cross-sections of 6 to 25 mm 2. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements class C. Tested to ÖVE-SN 60 part 1 and part 4, as well as DIN VDE 0675, part 6 (draft, Nov 1989). With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Additional display of operational status by means of signalling contact (changeover contact). tender text "Overvoltage protection" Rated voltage: 230/400V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <1.3 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU 3 CR 280 VAC Order No. 8021510000 Rated voltage: 130/230V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <0.8 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU 3 CR 130 VAC Order No. 8291680000 Rated voltage: 470/600V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <2.2 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU 4 CR 550 VAC Order No. 8451060000 PU 3 +1 C (3+1 circuit) for TT systems Overvoltage protection for protecting a TT 230/400 V three-phase system. Plug-in powerful varistors. Multi-core connection, cross-section of 6 to 25 mm2. Mounted on TS 35 mounting rail to DIN EN 50 022. Tested to IEC61643-1. With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Varistors: Rated voltage: 230/400V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <1.3 kV 25 kA short-circuit strength with max. back-up fuse of 120 A gl Sparkover gap: tender text "Overvoltage protection" Rated d.c. sparkover voltage: 600 V Rated discharge current : 20 kA Type: Weidmüller PU 3+1 C 280 VAC Order No. 8416370000 PU 3 +1 C (3+1 circuit) for TT systems with remote signalling contact Overvoltage protection for protecting a TT 230/400 V three-phase system. Plug-in powerful varistors. Multi-core connection, cross-section of 6 to 25 mm2. Mounted on TS 35 mounting rail to DIN EN 50 022. Tested to IEC61643-1. With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Additional display of operational status by means of signalling contact (changeover contact). Varistors: Rated voltage: 230/400V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 100 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <1.3 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Sparkover gap: Rated d.c. sparkover voltage: 600 V Rated discharge current : 20 kA Relay output: 250Vac/2A; 24Vdc/1A Type: Weidmüller PU 3+1 C/CR 230/400 VAC Order No. 8576190000 PU 2 C, 2-pin Overvoltage protection complying with the requirements of class C. Free from power follow current due to plug-in high-power varistors. Multi-core connection, cross-sections of 6 to 25 mm 2. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements of class C tested to IEC61643-1. With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Rated voltage: 230V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 75 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <1.3 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl tender text "Overvoltage protection" Type: Weidmüller PU 2 C 280 VAC Order No. 8098170000 Rated voltage: 115V Limiting discharge current (8/20µs): 15 kA Limiting discharge current (8/20µs): 75 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <0.8 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 2 C 130 VAC Order No. 8291650000 Rated voltage: 470V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 75 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <2.2 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 2 C 550 VAC Order No. 8291710000 PU 1 C Overvoltage protection complying with the requirements of class C. Free from power follow current due to plug-in high-power varistors. Multi-core connection, cross-sections of 6 to 25 mm 2. Mounted on TS 35 mounting rail to DIN EN 50 022. Requirements of class C tested to IEC61643-1. With thermal disconnector for varistors. When protection is no longer provided, the colour in the status window changes from green to red. Rated voltage: 230V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 75 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <1.3 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 1 C 280 VAC Order No. 8102610000 Rated voltage: 115V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 75 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <0.8 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 1 C 130 VAC Order No. 8215820000 tender text "Overvoltage protection" Rated voltage: 470V Rated discharge current (8/20µs): 20kA Limiting discharge current (8/20µs): 75 kA Charge: 2 As Impulse sparkover voltage (1.2/50µs) <2.2 kV 25 kA short-circuit strength with max. back-up fuse of 125 A gl Type: Weidmüller PU 1 C 550 VAC Order No. 8291700000 PU 0 C plug-in replacement arrester Replacement modules for overcurrent arrester PU C These plug-in high-power varistors can be replaced after failure by a qualified technician. Rated voltage: 230V Type: Weidmüller PU 0 C 280V Order No. 8339510000 Rated voltage: 115V Type: Weidmüller PU 0 C 130V Order No. 8215820000 Rated voltage: 470V Type: Weidmüller PU 0 C 550V Order No. 8291700000 Class III (D) surge arrester Overvoltage protection complying with draft standard DIN VDE 0675 part 6 class D (class III arresters). Protection for consumer devices for incorporation in distribution boards to DIN 43 880 A1 (draft, Jun 1981). PU D 230V 16A Modular class D surge arrester for protecting connected consumer devices against overvoltages. Conductors with cross sections of 0.5 to 4 mm 2 connected via screw terminals. The modules contain self-monitoring, powerful varistors. Failure due to thermal overload of the varistor is indicated by an LED as well as a monitoring contact (n.c. contact). Rated voltage: 230 Vac ±10% Rated current : 16 A tender text "Overvoltage protection" Max. discharge current (8/20µs) : 7 kA Rated discharge current (8/20µs) : 2.5 kA Interference voltage at 1 kV/µs : L-N : <550 V L/N - PE : <850 V Monitoring contact : 250V/1A Width: 3TE Type: Weidmüller PU D 230V 16A Order No. 8411930000 PU D 115V 16A Modular class D surge arrester for protecting connected consumer devices against overvoltages. Conductors with cross sections of 0.5 to 4 mm 2 connected via screw terminals. The modules contain self-monitoring, powerful varistors. Failure due to thermal overload of the varistor is indicated by an LED as well as a monitoring contact (n.c. contact). Rated voltage: 115 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 7 kA Rated discharge current (8/20µs) : 2.5 kA Interference voltage at 1 kV/µs : L-N : <550 V L/N - PE : <850 V Monitoring contact : 250V/1A Width: 3TE Type: Weidmüller PU D 115V 16A Order No. 8472100000 PU 3 D 230/400V 16A Three-pole class D surge arrester in modular form for protecting connected consumer devices against overvoltages. Conductors with cross sections of 0.5 to 4 mm 2 connected via screw terminals. The modules contain self-monitoring, powerful varistors. Failure due to thermal overload of the varistor is indicated by an LED as well as a monitoring contact (n.c. contact). Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 18 kA Rated discharge current (8/20µs) : 6.5 kA Interference voltage at 1 kV/µs : L-N : <550 V L/N - PE : <850 V Monitoring contact : 250V/1A Width: 3TE tender text "Overvoltage protection" Type: Weidmüller PU 3 D 230/400V 16A Order No. 85091300000 PO DS 230V 16A Class D surge arrester as single module for protecting connected consumer devices against overvoltages. Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Rated discharge current (8/20µs) : 2.5 kA Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1500 V Indication: green LED Type: Weidmüller PO DS 230V 16A Order No. 8581840000 PO D AS 230V 16A with acoustic signalling Class D surge arrester as single module for protecting connected consumer devices against overvoltages, with acoustic signalling. Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Rated discharge current (8/20µs) : 2.5 kA Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1500 V Indication: green LED Type: Weidmüller PO D AS 230V 16A Order No. 8581830000 PU DS 24V 16A Modular class D surge arrester for protecting connected consumer devices against overvoltages. Conductors with cross sections of 0.5 to 4 mm 2 connected via screw terminals. The modules contain self-monitoring, powerful varistors. Failure due to thermal overload of the varistor is indicated by an LED as well as a monitoring contact (n.c. contact). Rated voltage: 24 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 2 kA Rated discharge current (8/20µs) : 1 kA Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1100 V Monitoring contact : 250V/1A tender text "Overvoltage protection" Width: 1TE Type: Weidmüller PU DS 24V 16A Order No. 8682100000 PU DS 48V 16A Modular class D surge arrester for protecting connected consumer devices against overvoltages. Conductors with cross sections of 0.5 to 4 mm2 connected via screw terminals. The modules contain self-monitoring, powerful varistors. Failure due to thermal overload of the varistor is indicated by an LED as well as a monitoring contact (n.c. contact). Rated voltage: 48 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Rated discharge current (8/20µs) : 2.5 kA Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1100 V Monitoring contact : 250V/2A Width: 1TE Type: Weidmüller PU DS 48V 16A Order No. 8670740000 PU DS 115V 16A Modular class D surge arrester for protecting connected consumer devices against overvoltages. Conductors with cross sections of 0.5 to 4 mm 2 connected via screw terminals. The modules contain self-monitoring, powerful varistors. Failure due to thermal overload of the varistor is indicated by an LED as well as a monitoring contact (n.c. contact). Rated voltage: 115 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Rated discharge current (8/20µs) : 2.5 kA Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <850 V Monitoring contact : 250V/1A Width: 1TE Type: Weidmüller PU DS 115V 16A Order No. 8568650000 PU DS 230V 16A Modular class D surge arrester for protecting connected consumer devices against overvoltages. Conductors with cross sections of 0.5 to 4 mm 2 connected via screw terminals. The modules contain self-monitoring, powerful varistors. Failure due to thermal overload of the varistor is indicated by an LED as well as a monitoring contact (n.c. contact). tender text "Overvoltage protection" Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Rated discharge current (8/20µs) : 2.5 kA Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1500 V Monitoring contact : 250V/1A Width: 1TE Type: Weidmüller PU DS 230V 16A Order No. 8523740000 PU D ZS 230V 16A Overvoltage protection as grounding plug (class III arrester ). Protection for consumer devices as adapter plug (grounding plug). Class D surge arrester as single module for protecting connected consumer devices against overvoltages. The modules contain self-monitoring, powerful varistors. Function indication by green LED. A fault is indicated by a red LED after thermal overload of the varistor. Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Uoc: 4kV Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1500 V Type : grounding adapter plug Type: Weidmüller PU D ZS 230V 16A Order No. 8697580000 PU D ZS AS 230V 16A with acoustic signalling Overvoltage protection as grounding plug (class III arrester ). Protection for consumer devices as adapter plug (grounding plug). Class D surge arrester as single module for protecting connected consumer devices against overvoltages. The modules contain self-monitoring, powerful varistors. Function indication by green LED. A fault is indicated by a red LED after thermal overload of the varistor. With acoustic signalling. Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Uoc: 4kV Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1500 V Type : grounding adapter plug tender text "Overvoltage protection" Type: Weidmüller PU D ZS 230V 16A Order No. 8750640000 PU D ZS analogue 230V 16A Overvoltage protection as grounding plug and analogue telephone line (class III arrester ). Protection for consumer devices as adapter plug (grounding plug). Class D surge arrester as single module for protecting connected consumer devices against overvoltages. The modules contain self-monitoring, powerful varistors. Function indication by green LED. A fault is indicated by a red LED after thermal overload of the varistor. An overvoltage protection circuit for analogue telephone lines can also be connected via RJ45 (RJ11/12). Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Uoc: 4kV Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1500 V Type : grounding adapter plug Type: Weidmüller PU D ZS analogue 230V 16A Order No. 8697600000 PU D ZS So 230V 16A / PU D ZS Uko 230V 16A Overvoltage protection as grounding plug and digital telephone line (class III arrester ). Protection for consumer devices as adapter plug (grounding plug). Class D surge arrester as single module for protecting connected consumer devices against overvoltages. The modules contain self-monitoring, powerful varistors. Function indication by green LED. A fault is indicated by a red LED after thermal overload of the varistor. An overvoltage protection circuit for digital telephone lines can also be connected via RJ45 (RJ11/12). Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Uoc: 4kV Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1500 V Type : grounding adapter plug Type: Weidmüller PU D ZS So 230V 16A Order No. 8697560000 tender text "Overvoltage protection" Type: Weidmüller PU D ZS Uko 230V 16A Order No. 8697570000 PU D ZS TV/R 230V 16A Overvoltage protection as grounding plug and overvoltage protection for TV and radio (class III arrester ). Protection for consumer devices as adapter plug (grounding plug). Class D surge arrester as single module for protecting connected consumer devices against overvoltages. The modules contain self-monitoring, powerful varistors. Function indication by green LED. A fault is indicated by a red LED after thermal overload of the varistor. An overvoltage protection circuit can also be connected for TV and R antenna cables (75 ohms). Rated voltage: 230 Vac ±10% Rated current : 16 A Max. discharge current (8/20µs) : 5 kA Uoc: 4kV Interference voltage at 1 kV/µs : L-N : <600 V L/N - PE : <1500 V Type : grounding adapter plug Type: Weidmüller PU D ZS TV/R 230V 16A Order No. 8779230000 Mains filter WAVEFILTER 1 a 250V 2-stage mains filter with current-compensating choke for damping symmetrical and asymmetrical interference voltages. For applications in drive technology and control/automation technology. Mounted on TS 35 DIN rail Rated voltage: 250V Rated current : 1A Capacitance: 33 nF Inductance L and L1: 10 mH Leakage current at Un: 190 A Test voltage P/N-PE: 2000 Vac Test voltage P-N: 1700 Vdc Width: 22.5mm Type: Weidmüller WAVEFILTER 1 a 250V Order No. 8614790000 WAVEFILTER 3 a 250V tender text "Overvoltage protection" 2-stage mains filter with current-compensating choke for damping symmetrical and asymmetrical interference voltages. For applications in drive technology and control/automation technology. Mounted on TS 35 DIN rail Rated voltage: 250V Rated current : 3A Capacitance: 33 nF Cx, 22 nF Cy Inductance L and L1: 2 mH Leakage current at Un: 190 A Test voltage P/N-PE: 2000 Vac Test voltage P-N: 1700 Vdc Width: 22.5mm Type: Weidmüller WAVEFILTER 3 a 250V Order No. 8614780000 WAVEFILTER 6 a 250V 2-stage mains filter with current-compensating choke for damping symmetrical and asymmetrical interference voltages. For applications in drive technology and control/automation technology. Mounted on TS 35 DIN rail Rated voltage: 250V Rated current : 6A Capacitance: 33 nF Cx, 22 nF Cy Inductance L and L1: 0.8 mH Leakage current at Un: 190 A Test voltage P/N-PE: 2000 Vac Test voltage P-N: 1700 Vdc Width: 22.5mm Type: Weidmüller WAVEFILTER 6 a 250V Order No. 8614800000 WAVEFILTER 10 a 250V 2-stage mains filter with current-compensating choke for damping symmetrical and asymmetrical interference voltages. For applications in drive technology and control/automation technology. Mounted on TS 35 DIN rail Rated voltage: 250V Rated current: 10 A Capacitance : 470 nF Cx, 4,7 nF Cy Inductance L and L1: 0.8 mH Leakage current at Un: 190 A Test voltage P/N-PE: 2000 Vac Test voltage P-N: 1700 Vdc Width: 22.5mm Type: Weidmüller WAVEFILTER 10 a 250V Order No. 8614770000