Liebert HPM (English)

Precision Cooling for
Business-Critical Continuity
Liebert HPM
Designed for top level performance and reliability
Emerson Network Power, a Division of Emerson, is a global company matching technology and design to supply innovative solutions
for its customers’ benefit.
Emerson Network Power is the leader in the “business-critical
continuity” field thanks to its products and services.
Data Center
Financial networks
Precision Cooling is a key requirement to
ensure safe working conditions to
datacenters, computer rooms and other
equipment that simultaneously need a high
sensible heat discharge and
a precise temperature and humidity control.
Liebert HPM incorporates the whole
experience of Emerson Network Power in a
unique range of cabinet air coolers suitably
designed to ensure performance
and reliability.
Flexible solutions and low running costs add
value to the IT facility.
The product
Liebert HPM units are cabinet air conditioners.
They can feature EC fans,
with several air delivery versions:
downwards, that is with underfloor delivery, upwards and “displacement”.
Liebert HPM units are equipped with
iCOM control, featuring an integrated
Web connection and two optional graphic display types.
Liebert HPM combines different cooling
systems for the ideal solution to every
facility:
• Direct expansion: available with the air
or water cooled Copeland Digital
Scroll™ compressors.
• Chilled water: to be used with Liebert
HPC.
• Dual-Fluid: matches low running costs
and total reliability. It standard operates with chilled water, thus guaranteeing “business-continuity”, thanks to the
spare compressors that can intervene
in a few seconds, as soon as the central
unit stops.
• Freecooling: no power consumption if
needless. Working 365 days a year, it
uses the low winter temperature to
cool the rooms, without using compressors.
Reliability
Performance, equipment protection and fast business re-establishment
Design
Liebert HPM has been especially designed to
achieve top reliability. All components have
been sized for the lowest possible stress.
Models have been rigorously tested before
being launched on the market. The Liebert HPM
range is Eurovent certified.
Monitoring
The Emerson Network Power Monitoring solutions ensure the best control on energy and air
conditioning within IT facilities.
Communication to all protocols (Modbus,
Bacnet, Lonworks, HTTP and SNMP are just a few
of the available ones) enables the integration
both with the BMS system and with the facility
software.
The iCOM control device handles the operation
of the HPM units, using over twenty years of
experience in the development of communication systems and controls.
The iCOM control is featured by a special control
algorithm, ensuring top reliability under every
condition. It directly connects with the facility
network (Ethernet) and enables the communication among multiple HPM units for synchronized operations, guaranteeing top reliability
and precise room control.
Teamwork
The HPM unit teamwork within the same room is
available thanks to the integrated Ethernet connection.
The self-control of redundant units alternates
the stand-by positions and gives priority to possible hot areas.
control
• Several graphic display options
• On-line unit log
• Integrated Web communication
• Preventive maintenance through an
advanced troubleshooting
• 400 stored events/unit
• Up to 16 stored temperature and
humidity days
Ethernet
Flexibility
Business-tailored
EC fans
Copeland Digital Scroll™
Variable speed fans achieve a wide range of air
delivery and static pressure. They ensure a correct air distribution even when the facility
expands.
Copeland Digital Scroll™ compressors combine
the sturdiness of scroll compressors with the
capacity of operating with varying load.
When the traffic managed by the equipment
faces sudden changes, the facility experiences
thermal load peaks.
Further installed devices need a higher cooling
capacity.
EC fans can increase the air delivery to meet the
demand, thanks to the continuous regulation
through the iCOM control.
Copeland Digital Scroll™ compressors quickly follow the temperature and supply a load-balanced cooling capacity.
EC fans can even recover possible unexpected
load losses due to new wiring or other elements
inside the raised floor.
The Copeland Digital Scroll™ technology has no
adverse effect on electronic equipment, unlike
other solutions.
The special EC motors get the best performance
vs. AC and DC motors. They do not emit electromagnetic noises, as they do not use power delivered by frequency converters. Further, EC
motors feature a consumption about 30% lower
than the one by traditional AC motors.
Thus, it can be used also in industries and sectors where sensible equipment - such as computers that must not be subject to any EMI - operate.
EC fans
• AC powered 50/60 Hz without frequency converter
• Static pressure continuous adjustment
• Energy consumption lower by approx.
30% vs. AC motors
• No maintenance
• Long life transmission
Copeland Digital Scroll™
• Better room control
• Energy saving with partial load
• Quick adjustment to load changes
• Simple and reliable mechanics
• AC powered 50/60 Hz without frequency converter
• EMC free
Ethernet
Running cost
Keeping profitability
Efficiency
Compactness
Cooling a computer room needs high power.
Liebert HPM units take less space thanks to their
reduced plan dimensions.
Energy efficiency is the top target in Liebert
HPM designing.
Over-sized heat exchangers and optimized
aerodynamics allow one of the lowest
energy consumption in the Precision
Conditioning Cooling field.
The compact design still ensures the best performance thanks to fluido-dynamic analyses
and several lab tests.
Freecooling
Maintenance
Freecooling units minimize energy
consumption.
The handy user interface and the quick front
access to mechanical adjustments shorten the
routine maintenance time.
Working 365 days a year, they use the low winter
temperature to cool the rooms, without using
compressors.
Heat exchange
surface
• High Energy Efficiency Ratio (EER). It
basically depends on the heat exchange
surface.
Refrigerating circuits consume
less energy.
• High Sensible Heat ratio (SHR). Sensible
heat vs. latent heat. Technological
applications require a high sensible
heat discharge, without lowering the
room humidity too much, as it would
need to be restored through a humidifier.
Ethernet
Leading Precision Cooling Over IP
Integrate your Network Management
Connectivity and monitoring solutions
Whether you have a Network Management System
or a BMS and you need to integrate Liebert HPM,
this can be simply done through a Web card:
SNMP, Modbus, HTTP and Lonworks are just a few
of the protocols available.
•SNMP
•Lonwork
•HTTP
•Modbus
Liebert Sitescan and Hirovisor IP, advanced
monitoring solutions that can be offered for both
local and remote monitoring either through a dial
up line or through internet.
IP
display
Whenever you are in the network
you can plug iCOM user interface
and browse the connected
units thus enabling a first level of
monitoring.
IP
IP
IP
IP
IP
IP
IP
Eth
ern
et
Embedded
Ethernet
connection
Each unit connected
to Ethernet can talk
to up to 32 units
regardless of
the distance.
Functional schemes
A - Air-cooled
with remote condenser
W- Water-cooled
D - Air-cooled Dual-Fluid
H - Water-cooled Dual-Fluid
F - Freecooling
C - Chilled water
Combination with condensers
Max. outdoor temperature 35° C
Standard
Low Noise
Model
Standard
Low Noise
1 x HCE07
1 x HCE07
1 x HCE10
1 x HCE14
1 x HCE14
1 x HCE14
1 x HCE24
1 x HCE24
1 x HCE29
1 x HCE29
1 x HCE29
1 x HCE29
2 x HCE24
or 1 x HBE33
1 x HCE 07
1 x HCE 07
1 x HCE 14
1 x HCE 14
1 x HCE 17
1 x HCE 17
1 x HCE 24
1 x HCE 24
1 x HCE 29
1 x HCE 29
1 x HCE 33
1 x HCE 33
2 x HCE 24
M35 A/D
M41 A/D
M42 A/D
1 x HCE33
1 x HCE42
2 x HCE24
M47 A/D
M50 A/D
1 x HCE49
2 x HCE29
or 1 x HBE49
2 x HCE29
or 1 x HBE49
2 x HCE33
2 x HCE 42
or 1 x HBE 87
2 x HCE 49
or 1 x HBE 87
1 x HCE 42
1 x HCE 49
2 x HCE 24
or 1 x HBE 49
1 x HCE 49
2 x HCE 29
Model
S04 A
S05 A
S07 A
S10 A
S12 A
S13 A/D
S17 A/D
S20 A/D
S23 A/D
M25 A/D
M29 A
M31 A/D
M34 A/D
Max. outdoor temperature 35° C
M58 A/D
M66 A
L83 A/D
L99 A
2 x HCE 33
2 x HCE 42
2 xHCE 42
or 1 xHBE 87
2 xHCE 49
or 1 xHBE 99
Combination with Dry Cooler
Max. outdoor temperature 35° C
Max. outdoor temperature 35° C
Model
S04W
S05W
S07W
S10W
S12W
S13W/H/F
S17W/H/F
S20W/H/F
S23W/H/F
M25 W/H/F
M29 W
Standard
Low Noise
Model
1 x ESM009
1 x ESM009
1 x ESM009
1 x ESM009
1 x ESM013
1 x ESM013
1 x ESM018
1 x ESM022
1 x EST028
1 x EST028
1 x EST028
1 x ELM008
1 x ELM008
1 x ELM008
1 x ELM008
1 x ELM015
1 x ELM015
1 x ELM015
1 x ELM023
1 x ELM027
1 x ELM027
1 x ELM027
M31 W/H/F
M34 W/H/F
M35 W/H/F
M41 W/H/F
M42 W/H/F
M47 W/H/F
M50 W/H/F
M58 W/H/F
M66 W
L83 W/H/F
L99 W
Standard
Low Noise
1 x EST028
1 x EST028
1 x EST028
1 x EST040
1 x EST040
1 x EST050
1 x EST050
1 x EST060
1 x EST070
1 x EST 080
1 x EST 080
1 x ELM027
1 x ELM027
1 x ELM027
1 x ELT040
1 x ELT040
1 x ELT040
1 x ELT047
1 x ELT055
1 x ELT055
1 x ELT 065
1 x ELT 085
Technical data - C - Chilled water
Air delivery: downwards or upwards
Model
S06
S08
S11
S15
S18
S29
M44
M55
M66
M77
L90(6)
6,2
9,2
12,6
17,5
22,4
28,8
43,6
58,6
68,8
83,5
90.7
Total cooling capacity(2)
kW
Sensible cooling capacity(2)
kW
5,6
8,5
11,2
16,7
20,3
25,0
34,7
49,7
56,2
64,8
76.8
Water flow rate(2)
l/s
0,30
0,44
0,60
0,83
1,07
1,38
2,08
2,79
3,28
3,71
4.33
n°
1
1
1
1
1
1
1
2
2
2
2
Number of fans
m3/h
1395
2200
2800
4500
5200
6150
8150
12740 13650 14220 19060
Air delivery
Max. ESP (7) downward/upward delivery Pa
170/190 190/190 30/50 220/220 400/400 180/180 170/170 340/350 250/250 170/190 270
Sound pressure level(5)
dB(A)
46,1
48,3
50,5
50,4
51,4
54,5
55.1
58.2
60.3
62.2
58.7
mm
750
750
750
750
750
750
1000
1750
1750
1750
2050
Width
mm
400
500
500
750
750
750
850
850
850
850
890
Depth
Net weight
kg
135
150
165
190
210
230
330
480
550
600
620
L10(6)
L12(6)
L14(6)
L15(6)
103.4
83.9
4.93
2
20400
180
61.0
2050
890
630
117.9
97.4
5.62
3
23100
290
62.1
2550
890
790
142.8
111.7
6.81
3
25100
180
62.1
2550
890
800
158.9
121.5
7.58
3
26070
110
63.8
2550
890
810
Technical data - A/W — Direct expansion, air or water cooled
Air delivery: downwards or upwards
S04
S05
S07
S10
S12
S13
S17
S20
S23
M25
M29
M31
Total cooling capacity(1)
kW
4,6
5,7
8,2
10,6
12,5
14,5
17,3
20,5
26,6
26,5
29,7
31,3
Sensible cooling capacity(1)
SHR(1)
EER(1)(3)
Numberof compressors
Number of fans
Air delivery
Max. ESP(7) downward/upward delivery
Sound pressure level(4)
Width
Depth
Net weight
kW
4,3
0,93
3,29
1
1
1150
200/250
45,5
750
400
160
5,3
0,93
3,35
1
1
1350
170/180
46,4
750
400
170
7,7
0,94
3,28
1
1
2100
240/240
47,3
750
500
195
10,1
0,95
3,66
1
1
2600
130/130
48,2
750
500
210
11,0
0,88
3,57
1
1
2700
80/80
50,5
750
500
215
13,8
0,95
3,82
1
1
4200
280/280
49,0
750
750
240
16,4
0,95
3,68
1
1
4950
220/220
51,3
750
750
250
19,2
0,94
3,42
1
1
5200
400/400
51,5
750
750
260
23,6
0,89
3,41
1
1
5750
270/270
54,4
750
750
270
24,2
0,91
3,56
1
1
6340
360/380
53.3
1000
850
425
27,2
0,92
3,35
1
1
7080
240/280
55.1
1000
850
430
30,3
0,97
3,51
1
1
8850
360/420
58.5
1750
850
575
M34
M35
M41
M42
M47
M50
M58
M66
L83(6)
L99(6)
36,2
34,1
0,94
3,62
2
1
9490
350/350
60.5
1750
850
590
37,0
35,1
0,95
3,58
1
1
9540
340/340
60.4
1750
850
580
45,8
43,4
0,95
3,52
1
2
11230
380/380
58.4
1750
850
600
42,8
41,5
0,97
3,63
2
2
11370
380/390
58.1
1750
850
600
53,7
49,0
0,91
3,45
1
2
12250
300/300
60.4
1750
850
620
54,9
49,3
0,90
3,59
2
2
12240
300/300
59.3
1750
850
635
60,1
52,7
0,88
3,40
2
2
12910
240/250
61.1
1750
850
650
70,3
58,5
0,83
3,49
2
2
13470
170/180
63.4
1750
850
670
86.3
79.5
0.92
3.31
2
2
20020
170
66.2
2550
890
950
104.6
89.3
0.85
3.40
2
2
21100
90
66.9
2550
890
1000
D50
D66
Model
n°
n°
m3/h
Pa
dB(A)
mm
mm
kg
Model
(1)
Total cooling capacity
Sensible cooling capacity(1)
SHR(1)
EER(1)(3)
Numberof compressors
Number of fans
Air delivery
Max. ESP(7) downward/upward delivery
Sound pressure level(4)
Width
Depth
Net weight
kW
kW
n°
n°
m3/h
Pa
dB(A)
mm
mm
kg
Technical Data - A/W - Direct expansion, air or water cooled with Digital Scroll
Air Delivery: Downwards or Upwards
Model
Sel. Condenser (ext. temp up to 40°C)
Total cooling capacity(1)
Sensible cooling capacity(1)
SHR at Full load(1)
SHR at 80% load(1)
EER at full load (1)(3)
EER at 80% load(1)(3)
N° of compressors (dig./stand. scroll)
Number of fans
Air delivery
Max. ESP(7) downward/upward delivery
Sound pressure level
Width
Depth
Net weight
D13
n°
n°
m3/h
Pa
dB(A)
mm
mm
kg
D17
D20
D23
D25
D34
D35
D42
1xHCE24 1xHCE24 1xHCE33 1xHCE42 1xHCE42 2xHCE24 1xHCE42 2xHCE33 2xHCE42 2xHCE42
14,70
17,30
20,50
25,80
25,80
34,90
34,80
42,40
51,20
66,00
13,90
16,30
19,20
23,20
24,00
33,70
34,20
41,50
47,40
56,70
0,95
0,94
0,94
0,90
0,93
0,97
0,98
0,97
0,93
0,86
1,00
1,00
1,00
0,97
1,00
1,00
1,00
1,00
1,00
0,95
3,30
2,99
2,78
3,03
3,16
2,97
2,92
3,00
3,02
2,83
3,22
3,00
2,78
2,93
3,08
2,96
2,84
2,96
2,92
2,80
1
1
1
1
1
1/1
1
1/1
1/1
1/1
1
1
1
1
1
1
1
2
2
2
4200
4950
5200
5750
6340
9490
9540
11370
12240
13470
280
220
400
270
360/380
350
340
380/390
300
170/180
49
51,3
51,5
54,4
53,3
60,5
60,4
58,1
59,3
63,4
750
750
750
750
1000
1750
1750
1750
1750
1750
750
750
750
750
850
850
850
850
850
850
240
250
260
270
425
590
580
600
635
670
Technical data - C - Chilled water
Air delivery: downwards or upwards
Model
Total cooling capacity(2)
Sensible cooling capacity(2)
Water flow rate(2)
Number of fans
Air delivery
Max. ESP (7) downward/upward delivery
Sound pressure level(5)
Width
Depth
Net weight
kW
kW
l/s
n°
m3/h
Pa
dB(A)
mm
mm
kg
L16(6) (8)
L18(6) (8)
L20(6) (8)
175,0
134,6
8,35
3
29600
100
66,5
2550
890
940
206,8
159,9
9,86
4
35410
100
68,5
3350
890
1000
232,2
172,3
11,07
4
35650
100
68,6
3350
890
1085
Available versions
Version
S04
S05
S06
S07
S08
S10
S11
S12
S13 / D13
S15
S17 / D17
S18
S20 / D20
S23 / D23
S29
M25 / D25
M29
M31
M34 / D34
M35 / D35
M41
M42 / D42
M44
M47
M50 / D50
M55
M58
M66 / D66
M77
L83
L90
L99
L10
L12
L14
L15
L16
L18
L20
A/W
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
C
-
Downward air delivery
Displacement
F/D/H
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Upward air delivery
Front air delivery
Constant
-
-
-
-
-
Downwards Air Delivery
-
Displacement
Upwards Air Delivery
Front Air Delivery
A/W: Direct expansion, air or water cooled
F/D/H: Free-cooling e Dualfluid
C: Freecooling and Dual-Fluid
Constant version: See the product manual
Constant Models: Available on units with standard scroll
(1) 24°C db, 50% R.H.; 45°C condensation (selected condenser and 35°C
outdoor temp with HPM Digital models); refrigerant R407C
(2) 24°C db, 50% R.H.; 7/12°C water inlet/outlet.
(3) 20 Pa ESP, downward delivery version. 50 Pa upward delivery version
(4) 1.5 m height, 2 m front distance; free field; compressor(s) and fan (s)
working. Downward delivery version
(5) 1.5 m height, 2 m front distance; free field; fan (s) working. Downward
delivery version.
(6) Available only in the Down- ward delivery version
(7) Max. ESP available for the indicated air delivery
(8) sizes L16-L18-L20 are supplied with EC fans as standard
(9) all units height is 1950 mm except L16-L20 with 2150 mm height
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson
(NYSE:EMR), is the global leader in enabling Business-Critical
Continuity™. The company is the trusted source for custom,
adaptive and ultra-reliable solutions that enable and protect
its customers’ business-critical technology infrastructures.
Backed by the largest global services organization in the
industry, Emerson Network Power offers a full range of innovative power, precision cooling, connectivity and embedded
products and services for computer, communications, healthcare and industrial systems. Key product brands within the
Emerson Network Power family include Liebert, Knürr, ASCO,
Astec, Lorain.
Locations
Emerson Network Power - Headquarters EMEA
Via Leonardo Da Vinci 16/18
Zona Industriale Tognana
35028 Piove di Sacco (PD) Italy
Tel: +39 049 9719 111
Fax: +39 049 5841 257
[email protected]
Emerson Network Power - Service EMEA
Via Leonardo Da Vinci 16/18
Zona Industriale Tognana
35028 Piove di Sacco (PD) Italy
Tel: +39 049 9719 111
Fax: +39 049 9719045
[email protected]
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Tel: +1 614 8880246
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
Tel: +852 2572220
Fax: +852 28029250
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2009 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert
Corporation. All names referred to are trademarks
or registered trademarks of their respective owners.
103027
Emerson Network PowerTM.
www.eu.emersonnetworkpower. com
The global leader in enabling Business-Critical Continuity™.
[email protected]
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Out Side Plant
Power Switching & Controls
Precision Cooling
Rack & Integrated Cabinets
Services
Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co.