5/5.8kW Single-Phase Basic PDU, 208/240V Outlets (10 C13), L6-30P, 12ft Cord, 1U Rack-Mount MODEL NUMBER: PDUH30HV Highlights Basic single phase 30A 208/240V PDU 1U horizontal rackmount installation NEMA L6-30P input; 12 ft. / 3.6m line cord 10 C13 outlets (8 front / 2 rear) Reversible housing; 3.75 in. / 9.5 cm depth Package Includes PDUH30HV PDU Warranty information Instruction manual Description Tripp Lite Basic Power Distribution Units / PDU systems offer reliable rackmount power distribution. Supplies equipment with continuous power from any protected UPS, generator or mains input power source. High quality design includes rugged all-metal housing and secure rackmount installation with included mounting accessories. Features 30A single phase 208/240V Basic Power Distribution Unit / PDU (agency de-rated to 24A continuous) Attached NEMA L6-30P 30A 208/240V input plug with 12 ft. / 3.6m line cord 1U horizontal rackmount format installs in one rack space 10 C13 outlets (8 front-facing / 2 rear-facing) Mounting flanges are reversible front or rear facing installation Mounting flanges support installation in 2 and 4 post racks, with additional support for wall-mount and under-counter installation formats Specifications OVERVIEW PDU Type Basic OUTPUT Output Capacity Details 5.8kW (240V), 5kW (208V), 4.8kW (200V) total capacity / 30A max (Agency de-rated to 24A), 20A max per breakered outlet bank; 12A max per C13 outlet Frequency Compatibility 50 / 60 Hz Output Receptacles (10) C13 Output Receptacle Details 8 front-facing and 2 rear-facing outlets (reversible) 1/3 Output Nominal Voltage 200; 208; 240 Overload Protection Two 20A breakers protect 5 outlets each INPUT PDU Input Voltage 200; 208; 240 Recommended Electrical Service 30A 208/240V Maximum Input Amps 30 Maximum Input Amps Details 30A maximum (agency de-rated to 24A continuous) PDU Plug Type NEMA L6-30P Input Cord Length (ft.) 12 Input Cord Length (m) 3.6 Input Phase Single-Phase USER INTERFACE, ALERTS & CONTROLS Switches n/a PHYSICAL Minimum Required Rack Depth (inches) 6 Minimum Required Rack Depth (cm) 15.2 Shipping Dimensions (hwd / in.) 3 x 20.25 x 11.25 Shipping Dimensions (hwd / cm) 7.6 x 51.4 x 28.6 Shipping Weight (lbs.) 8.5 Shipping Weight (kg) 6.6 Unit Dimensions (hwd / in.) 1.75 x 17.5 x 3.75 Unit Dimensions (hwd / cm) 4.3 x 43.9 x 9.53 Unit Weight (lbs.) 7.8 Unit Weight (kg) 3.5 Material of Construction Metal Form Factors Supported 1U rackmount, 0U vertical mount, wallmount and under-counter PDU Form Factor Horizontal (1U, 2U, etc) ENVIRONMENTAL Storage Temperature Range -15 to 50C (5 to 122F) Relative Humidity 5-95% non-condensing Operating Elevation (ft.) 0-10,000 Operating Elevation (m) 0-3000 2/3 SPECIAL FEATURES TVSS Grounding Rear grounding lug CERTIFICATIONS Certifications Tested to UL60950-1 (USA), CSA (Canada), RoHS WARRANTY Product Warranty Period (Worldwide) 2-year limited warranty © 2016 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies: http://www.tripplite.com/products/product-certification-agencies 3/3