7.4kW Single-Phase Metered PDU, 230V Outlets
(2-C19, 16-C13), IEC-309 230V 32A Blue, 12ft Cord,
2U Rack-Mount
Highlights
Metered single phase 32A 230V
2U horizontal rackmount PDU
Set of 2 current meters reports
current in amps for each output
MODEL NUMBER: PDUMH32HV
load bank
Attached 12 ft. / 3.6m cord with
IEC-309 32A (2P+E) input plug
18 total 230V outlets (2 C19, 16
C13)
Reversible housing, 12.5 in. /
31.75cm depth
Package Includes
2U metered PDU
Mounting brackets
Plug retention brackets
User manual
Description
Tripp Lite Metered Power Distribution Units / PDU systems continuously report output load level in amps to help network managers prevent overloads and plan
for future growth. Supplies equipment with continuous power from any protected UPS, generator or mains input power source. Highly reliable design includes
rugged all-metal housing and secure rackmount installation with included mounting accessories.
Features
32A single phase 230V Metered Power Distribution Unit / PDU
Set of two lighted current meters separately report power consumption in amps for each output load bank
Attached IEC-309 32A(2P+E) input plug with 12 ft. / 3.6m line cord
2U horizontal rackmount format installs in two rack spaces
18 total 230V outlets(2 C19, 16 C13)
Outlets are arranged in two separately breakered and metered 16A load banks(each with 8 C13 and 1 C19 outlet)
Mounting flanges support installation in 2 and 4 post racks, with additional support for wall-mount and under-counter installation formats
Mounting ears are reversible for front or rear facing rackmount installation
Front-panel grounding lug
Included cord retention brackets
TAA Compliant Version Available - Order Tripp Lite PDUMH32HVTAA
Specifications
OVERVIEW
PDU Type
Metered
OUTPUT
1/3
Output Capacity Details
7.4kW (230V) / 32A total capacity / 16A max per breakered outlet bank; 16A max per C19 outlet; 10A max per C13
outlet
Frequency Compatibility
50 / 60 Hz
Output Receptacles
(16) C13; (2) C19
Output Nominal Voltage
230
Overload Protection
Two 20A circuit breakers protect 9 outlets each
INPUT
PDU Input Voltage
230
Recommended Electrical Service
32A 230V
Maximum Input Amps
32
PDU Plug Type
IEC-309 32A BLUE (2P+E)
Input Cord Length (ft.)
12
Input Cord Length (m)
3.65
Input Phase
Single-Phase
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Set of 2 digital meters continuously report output current for breakered load bank; Bank 1 (Upper row of 9 outlets),
Bank 2 (Lower row of 9 outlets)
Switches
n/a
PHYSICAL
Minimum Required Rack Depth
(inches)
16
Minimum Required Rack Depth (cm)
40.6
Shipping Dimensions (hwd / in.)
5.5 x 20.5 x 17
Shipping Dimensions (hwd / cm)
14 x 113 x 80.6
Shipping Weight (lbs.)
16.2
Shipping Weight (kg)
7.4
Unit Dimensions (hwd / in.)
3.5 x 17.5 x 12.5
Unit Dimensions (hwd / cm)
8.9 x 44.5 x 31.75
Unit Weight (lbs.)
13.7
Unit Weight (kg)
6.2
Material of Construction
Metal
Form Factors Supported
2U rackmount
PDU Form Factor
Horizontal (1U, 2U, etc)
ENVIRONMENTAL
2/3
Storage Temperature Range
5 to 122F (-15 to 50C)
Relative Humidity
5 to 95% non-condensing
Operating Elevation (ft.)
0-10,000
Operating Elevation (m)
0-3000
CERTIFICATIONS
TAA Compliant Option
TAA Compliant Version Available - Order Tripp Lite PDUMH32HVTAA
Certifications
Tested to CE (IEC 60950-1), UL, CSA, Class A, RoHS compliant
WARRANTY
Product Warranty Period (Worldwide)
2-year limited warranty
© 2016 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
http://www.tripplite.com/products/product-certification-agencies
3/3