LORAIN VRR 243600 Brochure

DC Power for
Discontinued
Business-Critical Continuity
LORAIN® VRR 243600
DC Power System
Discontinued
Key Features
■ Relay rack mountable for
replacing traditional rectifiers
in existing systems
■
Available factory-installed in
relay racks for expanding existing
LORAIN® VPS or VRR systems
■
75% smaller size than
traditional rectifiers for
increased system capacity
and growth
■
Single point adjustment and
monitoring provided through
the LORAIN® VRR metercontrol-alarm unit (MCA)
■
Use of a factory adjusted
plug-n-play PCU simplifies
system installation
■
Complies with industry
standards: UL listed, NEBS
Level 3 compliant (rectifiers
and shelves), and FCC Class B
rated (optional)
This compact, reliable DC Power solution from Emerson Network
Power is ideal for replacement of traditional rectifiers or
expansion of LORAIN® VPS or VRR Power Systems.
Product Overview
The LORAIN® VRR replaces traditional
Ferro-resonant or thyristor controlled
units and provides current capacities
ranging from 130 to 3600 amps at
+24VDC. This system is approximately
75% smaller than traditional rectifiers,
permitting increased capacity, available
rack space, and installation of additional
equipment. Installation time is minimized
since the existing power distribution
board is used. Power connections are
conveniently located at the top of the
system for up to six 4/0 AWG cables per
polarity. Since the existing bus voltage,
system shunt and fuse/breaker alarm
signals can be read by the LORAIN® VRR
MCA, the existing meter and alarm panels
can be replaced with the latest LORAIN®
VRR MCA monitor system. Multiple
shelves can be configured in a single bay
with a maximum rating of 1200 amps.
Multiple bays can be paralleled for a
maximum system rating of 3600 amps.
Front View with (1) Rectifier Shelf
The LORAIN® VPS or VRR may be expanded by adding rectifier expansion bays
as an alternative to using space in the
existing LORAIN® power bays or when no
space is available in the existing bay(s).
130 Amp PCU
Additional Information
For additional specification, engineering
or installation information, specify
581122500 (power system) and
588703800 (520 amp rectifier shelf
and 130 amp rectifiers).
For ordering information request
SAG581122500 and PD588703800.
2
Application
The LORAIN® VRR is designed for wireline and wireless communication systems
installed in small offices, huts, CEVs and CUEs.
System Specifications
Operating Ambient Temperature Range
-40°C to +50°C (-40°F to +122°F)
Storage Ambient Temperature Range
-40°C to +85°C (-40°F to +185°F)
Output Capacity
1200 amps per bay, 3600 amps per system
Discontinued
Power Conversion Unit Specifications
Physical Characteristics
Mounting
Plug-in installation
Dimensions (HxWxD)
9.88" (25.08cm) x 5.13" (13.02cm) x 14.5" (36.83cm)
Weight
18 lbs. (8.16 kg)
Input
Voltage
Nominal 208/240 volts AC, single phase, 50/60 Hz, with a range of 176 to 264 volts.
Extended range to 290 volt AC.
Inrush
Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage within
the rated input voltage range
Frequency
45-70 Hz
Protection
Each PCU is individually wired and connections for individual AC input branch circuits are provided. If the AC
input voltage decreases or increases beyond a non-adjustable predetermined value, the PCU power conversion
circuitry inhibits, disabling PCU output. The PCU will recover automatically when the AC input voltage is
re-established within specifications limits.
Power Factor
Typical power factor greater than or equal to 98% for any load greater than or equal to 50% of rated full load at
nominal line. Meets IEC 1000–3–2.
Operating Efficiency
Typical operating efficiency 89% at full load
Output
Voltage
Nominal +24 volts DC, negative ground, adjustable from 23.0 to 28.5 volts DC
Current
130 amps per PCU, up to a total of 520 amps per shelf with four PCUs installed.
Regulation
Steady state output voltage remains within ±0.5% of any voltage within the range of 23.0 to 28.5 volts DC for a
combination of frequency, input voltage, and load from no load to full load over the temperature range of -20°C
to +50°C (-4°F to +122°F).
Filtering
On or off battery
Voice Band Noise
Less than 32 dBrnC
Wide Band Noise
Does not exceed 250 mv peak-to-peak, or 25 mv rms
Psophometric Noise
Does not exceed 1 mv
Protection
Current Limiting
Maximum output current of each PCU can be set from 10% to 105% of full load current.
High Voltage Shutdown
If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately three
seconds, the PCU automatically restarts.
Monitoring
Status/Alarm Indicators
Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed on
the 16-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature
-20°C to +50°C (-4°F to +122°F); -40°C to +65°C (-40°F to +149°F) at 110 amps output
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Humidity
0% to 95% relative humidity, non-condensing
Altitude
The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation of 10,000'
(3,048m) above sea level. For elevations between 3,000' (914m) and 10,000' (3,048m), derate the maximum
operating ambient temperature linearly.
Ventilation
Fan-cooled front to rear
EMI/RFI Suppression
Conforms to FCC rules Part 15, Subpart B, Class A, with an option for FCC and CISPR22 Class B emission ratings.
Audible Noise
3' from any vertical surface does not exceed 65dBA; 55dBA with low fan speed selected.
Safety Compliance
UL recognized (UL 1950), CSA 22.2, No.950, CE
3
Discontinued
Emerson Network Power
Energy Systems, North America
1122 F Street, Lorain, OH 44052
Toll Free: 800-800-1280 (USA and Canada)
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems
Emerson Network Power.
The global leader in enabling business-critical continuity.
Embedded Power
AC Power
Connectivity
DC Power
Embedded Computing
Monitoring
Outside Plant
Power Switching & Controls
EmersonNetworkPower.com
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
© 2006 Emerson Network Power Energy Systems, North America, Inc. All rights reserved.
This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc.
in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating
to the products or services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the
specification, design or conditions of supply of any product or service.
The Emerson logo is a trademark and a service mark of Emerson Electric Co. Emerson Network Power is a division of Emerson Electric Co.
LORAIN® is a trademark of Emerson Network Power Energy Systems, North America, Inc.
Code: PPB-MDCP-014
December 2006