LORAIN VRR 483600 Brochure

DC Power for
Discontinued
Business-Critical Continuity
LORAIN® VRR 483600
DC Power System
Discontinued
Key Features
■ Relay rack mountable for
replacing traditional rectifiers
in existing systems
■
Available factory-installed in
relay racks for expanding existing LORAIN® VPS or VRR systems
■
75% smaller size than traditional rectifiers for increased
system capacity and growth
■
Single point adjustment and
monitoring provided through
the LORAIN® VRR metercontrol-alarm unit (MCA)
■
Use of a factory adjusted
plug-n-play PCU simplifies
system installation
■
Complies with industry
standards: UL listed, NEBS
Level 3 compliant (rectifiers
and shelves), and FCC Class B
rated (optional)
This compact, reliable DC Power solution from Emerson Network
Power is ideal for replacement of traditional rectifiers or
expansion of LORAIN® VPS or VRR Power Systems.
Product Overview
The LORAIN® VRR replaces traditional
Ferro-resonant or thyristor controlled
units and provides current capacities
ranging from 65 to 3600 amps at -48VDC.
This system is approximately 75% smaller
than traditional rectifiers, permitting
increased capacity, available rack space,
and installation of additional equipment.
Installation time is minimized since the
existing power distribution board is used.
Power connections are conveniently
located at the top of the system for up to
six 4/0 AWG cables per polarity. Since the
existing bus voltage, system shunt and
fuse/breaker alarm signals can be read by
the LORAIN® VRR MCA, the existing meter
and alarm panels can be replaced with the
latest LORAIN® VRR MCA monitor system.
Multiple shelves can be configured in a
single bay with a maximum rating of 1200
amps. Multiple bays can be paralleled for
a maximum system rating of 3600 amps.
The LORAIN® VPS or VRR may be expanded by adding rectifier expansion bays as
an alternative to using space in the existing LORAIN® power bays or when no space
is available in the existing bay(s).
65 Amp PCU
Additional Information
For additional specification, engineering
or installation information, specify
582122500 (power system) and
588703600 (260 amp rectifier shelf
and 65 amp rectifiers).
For ordering information request
SAG582122500 and PD588703600.
2
Front View with (1) Rectifier Shelf
and LORAIN® VLI unit
Application
The LORAIN® VRR is designed for wireline and wireless communication systems
installed in small offices, huts, CEVs and CUEs.
System Specifications
Operating Ambient Temperature Range
-40°C to +50°C (-40°F to +122°F)
Storage Ambient Temperature Range
-40°C to +85°C (-40°F to +185°F)
Output Capacity
1200 amps per bay, 3600 amps per system
Discontinued
Power Conversion Unit Specifications
Physical Characteristics
Mounting
Plug-in installation
Dimensions (HxWxD)
9.88" (25.08cm) x 5.13" (13.02cm) x 14.5" (36.83cm)
Weight
18 lbs. (8.16 kgs)
Safety Compliance
UL recognized (UL 1950), CSA 22.2, No.950, CE
Input
Voltage
Nominal 208/240 volts AC, single phase, 50/60 Hz, with a range of 176 to 264 volts
Extended range to 290 volt AC without damage
Inrush
Current Peak does not exceed 2 times the RMS input at full load, under any conditions of input voltage
within the rated input voltage range
Frequency
45-70 Hz
Protection
Each PCU is individually wired and connections for individual AC input branch circuits are provided. If the
AC input voltage decreases or increases beyond a non-adjustable predetermined value, the PCU power
conversion circuitry inhibits, disabling PCU output. The PCU will recover automatically when the AC input
voltage is re-established within specifications limits.
Power Factor
Typical power factor greater than or equal to 98% for any load greater than or equal to 50% of rated full load at
nominal line. Meets IEC 1000–3–2.
Operating Efficiency
Typical operating efficiency 89% at full load
Output
Voltage
Nominal -48 volts DC, positive ground, adjustable from -46.0 to -57.0 volts DC
Current
65 amps per PCU, up to a total of 260 amps per shelf with four PCUs installed.
Regulation
Steady state output voltage remains within ±0.5% of any voltage within the range of 46.0 to 57.0 volts DC
for a combination of frequency, input voltage, and load from no load to full load over the temperature
range of -20°C to +50°C (-4°F to +122°F).
Filtering
On or off battery
Voice Band Noise
Less than 32 dBrnC
Wide Band Noise
Does not exceed 250 mv peak-to-peak, or 25 mv rms
Psophometric Noise
Does not exceed 1 mv
Protection
Current Limiting
Maximum output current of each PCU can be set from 10% to 105% of full load current.
High Voltage Shutdown
If PCU output voltage exceeds an adjustable preset value, the PCU shuts down. After approximately three
seconds, the PCU automatically restarts.
Monitoring
Status/Alarm Indicators
Extensive alarming and status indicators such as AC on/off, fan fail, PCU failure and open sense are displayed on
the 16-character numerical display of the MCA and on the PCUs in the shelf.
Environmental
Operating Temperature
-20°C to +50°C (-4°F to +122°F);-40°C to +65°C (-40°F to +149°F) at 55 amps output
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Humidity
0% to 95% relative humidity, non-condensing
Altitude
The maximum operating ambient temperature should be derated by 10°C (18°F) at an elevation of 10,000'
(3,048m) above sea level. For elevations between 3,000' (914m) and 10,000' (3,048m), derate the maximum
operating ambient temperature linearly.
Ventilation
Fan-cooled front to rear
EMI/RFI Suppression
Conforms to FCC rules Part 15, Subpart B, Class A, with an option for FCC and CISPR22 Class B emission ratings.
Audible Noise
3' from any vertical surface does not exceed 65dBA; 55dBA with low fan speed selected.
3
Discontinued
Emerson Network Power
Energy Systems, North America
1122 F Street, Lorain, OH 44052
Toll Free: 800-800-1280 (USA and Canada)
Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems
Emerson Network Power.
The global leader in enabling business-critical continuity.
Embedded Power
AC Power
Connectivity
DC Power
Embedded Computing
Monitoring
Outside Plant
Power Switching & Controls
EmersonNetworkPower.com
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
© 2006 Emerson Network Power Energy Systems, North America, Inc. All rights reserved.
This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc.
in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating
to the products or services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the
specification, design or conditions of supply of any product or service.
The Emerson logo is a trademark and a service mark of Emerson Electric Co. Emerson Network Power is a division of Emerson Electric Co.
LORAIN® is a trademark of Emerson Network Power Energy Systems, North America, Inc.
Code: PPB-MDCP-013
December 2006