Brochure

Series 230 Automatic Transfer Switch
The Recognized Leader in Power Transfer
Switch Technology Offers the Most
Advanced Transfer Switches in the World.
Product Overview
The Series 230 automatic transfer switch consists of an
intelligent controller and a modular load break switch which
automatically transfers the load to the emergency power
source when it detects the normal power source under/over
voltage, under/over frequency, or phase loss. The switch has
three operational positions (Source I, Center-off, Source II). The
two sources can be isolated when the switch is in the centeroff position. A center-off position locking mechanism is also
provided.
Application
The Series 230 capacity is up to 800A, available from 208 to 415 volts, 50 and 60Hz, single phase and three phase. Typical
applications include office buildings, residential buildings, telecom, hospital, subway, data center, military, transportation, and
fire pump applications.
Parameter
Rated Operational Current Ie (A)
Rated Insulation Voltage Ui (V)
Rated Impulse Withstand Voltage Uimp (kV)
32
40
50
63
80 100 125 160 200 225 250 315 400 500 630 800
800
800
800
800
8
12
12
12
Rated Operation Voltage Ue (V)
208, 220, 230, 240, 380, 400, 415
Rated Frequency (Hz)
50 / 60
Poles
2, 3, 4
Rated Short-Time Withstand Current Icw (kA, RMS)
10 (0.1s)
15 (0.1s)
25 (0.1s)
40(0.1s)/ 20(1s)
Rated Short-Circuit Making Capacity Icm (kA, PEAK)
17
31.5
65
80
65
200
200
200
150
150
80
When Used With Current
Withstand and Close-On Limiting Fuses
Rating Iq (kA)
When Used With Specific
Circuit Breakers
Making and Breaking Capacity
50
10 Ie
Mechanical Operation Performance (cycles)
10,000
Utilization Category
AC - 33B
Operation Voltage
range (AC)
EMC Class
Wiring Way
Separate Lock Mechanism
Auxiliary Contact
1
Ue=208V
(0.75〜1.2) Ue
Ue=220V / 230V / 240V /
380V / 400V
(0.7〜1.2) Ue
Ue= 415V
(0.7〜1.15) Ue
Class A
Front
Standard
Optional (8 contacts maximum)
Series 230 Automatic Transfer Switch Product Features
Performance feature
Meets or exceeds the requirements of the
following regulatory agencies
•Clamping contacts are self cleaning wiping
action type
•High short-circuit closing ability
• EN60947-6-1/IEC60947-6-1: transfer switching
Switching Mechanism
• EN55022: Radiated and Conducted Emission,
Class A
•Both automatic, manual and remote
operation are available
• EN61000-3-2: Harmonic Current Emission, Class A
• EN61000-3-3: Limits of Voltage fluctuation and
Flicker
• EN 61000-4-5: Immunity to Surge
• EN 61000-4-4: Immunity to Electrical Fast
Transient:
• EN61000-4-2: Immunity to Electrostatic
Discharge
• EN61000-4-3: Immunity to Radiated Electric
Fields
• EN 61000-4-6: Immunity to Continuous
Conducted Interference
Structure
•PC Class ATS
•High ability of withstanding lightning
strikes (40kA 8/20μs)
•Simple reliable mechanism, compact and
stylish appearance
•Modular design, convenient operation, easy
maintenance
•Three operation positions. Two sources can
be isolated in the center-off position
Arc Extinguish
•The utilization category is AC-33B, and the
ability of withstand and break is10 Ie
•Rotating dual contacts design extinguishes
the arc quickly and effectively
•Arcing contacts and main contacts are
separate, avoids main contacts from being
destroyed by an arc
•Unique contacts design limits contact
bounce
•Unique clutch technique makes manual
operation easy to do
•Electrical and mechanical interlocks
prevent two sources from connecting
simultaneously
•Innovative motor circuit protection
technique, provides precision control
•Cast steel bevel gear mechanism provides
high transmission efficiency, and extends
the operation life
Controller
•Different Operating Modes (Source I
priority / No Source priority)
•C2000 has ability to work with external
24VDC power supply
•High frequency switching power supply,
and wide power voltage range
•Data (e.g. Evens log, Setting, etc) remains
intact if power is lost.
•Diagnosis fault intelligent with self protection function (Motor-Protection)
•RS485 communication interface is available
•Priority Source Swap
2
Make Life and Business More Reliable
By Using ASCO
Series 230 Transfer Switch Ordering Information
Type sample:
B2ADTL
①
B3
②
250
③
B1
C
B1
D
B1
E
B1
F
02
02
02
02
C
D
E
F
B2
C
B2
D
B2
E
B2
F
03
03
03
03
03
B3
B3
B3
B3
B3
①
Frame
③
Amps
⑤
Controller
⑥
⑦
3
H
④
Optional
Accessories
Enclosure
E
⑤
0
⑥
0
⑦
Poles
M
L1
N
L1
NSource I
L1
N
L1
SourceNII
M
Source I
Source
II
M
L1
L2
L1
Source I
L2
L1
L2
L1
SourceL2
II
Source I
Source II
2P
M
M
L1
L2
L1
N
L2
NSource I
L1
L2
L1
N
L2
SourceNII
Source I
Source II
M
3P
L1
Line and Neutral
L2
L3
N
AC Voltage (V)
L-L
L-N
√
√
-
208
√
√
-
220
√
√
-
230
√
√
-
240
208
220
230
240
-
√
√
√
√
√
√
√
√
√
√
√
208
√
√
√
220
110
√
√
√
230
115
√
√
√
240
120
√
√
√
208
L1
L1
M
L2
L2
√
√
√
220
L1
L1
L3
L3
L2
L2
√
√
√
380
L3
SourceL3
II
Source I
Source II
Source I
√
√
√
400
√
√
√
415
√
√
√
√
208
M
L1
L1
√
√
√
√
220
L2
L2
L3
L3
√
√
√
√
380
220
4P
N
N
√
√
√
√
400
230
Source II
Source I
√
√
√
√
415
240
B2ADTL Frame 32A-160A
C2ADTL Frame 200A-250A
D2ADTL Frame 315A-400A
E2ADTL Frame 500A-800A
32A
0100
100A
0250
250A
0630
630A
40A
0125
125A
0315
315A
0800
800A
50A
0160
160A
0315
315A
63A
0200
200A
0400
400A
80A
0225
225A
0500
500A
C1000 Controller
C2000 Controller
Without Accessories
B2ADTL Frame Bridging Bus Bar: 132JA 〜 132JC, Auxiliary Contacts: 132A 〜 132F, 1H, 72D See Page 5
Without Enclosure
C
D
H
J
K
C
D
H
J
K
B2ADTL
C2ADTL
D2ADTL
E2ADTL
0032
0040
0050
0063
0080
D
E
0
X
0
Switch category
M
Optional Accessory Model Description and Order Information
B2ADTL Frame Bridging Bus Bar
132 J A
Poles
A: 2 poles (02356097)
B: 3 poles (02357091)
C: 4 poles (02355942)
4 poles Bridging Busbar
Function Code 132J: Bridging Busbar
For example: 132JC , means Bridging Busbar for a 4 poles transfer switch
Auxiliary Contacts
132 A A
Auxiliary Contact Quantity
BLANK: 1 contact
A: 2 contacts
B: 3 contacts
C: 4 contacts
Function Code 132A-132F: Auxiliary Contact
Auxiliary Contact
For example: 132BA , means 2 sets of contacts, closed when the ATS transfer to source II position.
4
The Auxiliary Contact Definition
132A-132C : The auxiliary contacts can be used to indicate positions with the CLOSE contact , see Schematic 1.
132D-132F: The auxiliary contacts can be used to indicate positions with the OPEN contact ,see Schematic 2.
Position of The
Transfer Switch
Auxiliary Contact Function Code
132A
132B
132C
Position of The
Transfer Switch
I
I
O
O
II
II
Auxiliary LAP1F100
(16021426)
Contact
LAP1F010
Code (16021427)
√
√
-
-
-
√
Auxiliary LAP1F100
(16021426)
Contact
LAP1F010
Code (16021427)
Auxiliary Contact
Mounting Position
Auxiliary Contact
Mounting Position
(only showing C2ADTL,
D2ADTL, E2ADTL).
(only showing C2ADTL,
D2ADTL, E2ADTL).
72D
C1000 Controller with RS-485 interface
A RS485 interface installed in the C1000 controller to enable serial communications. Supporting
MODBUS protocol. The Accessory can be installed in the factory only. Use accessory code 72D when
ordering this function.
1H
C2000 Controller with energy storage
The optional controller with energy storage (Accessory 1H) has the added feature to switch the
transfer switch to center-off position during Source I and Source II failure at the same time. This
controller will remain in center-off until either source I or source II power is restored and voltage and
frequency are both stable. This optional feature can work in Source I Priority and No Source Priority
operating modes. This feature is available only after the controller has been powered by AC input
for at least10 minutes to charge capacitor. The Accessory can be installed in the factory only. Use
accessory code 1H when ordering this function.
5
Auxiliary Contact Function Code
132D
132E
132F
-
-
√
√
√
-
Avoid Losing Critical information
When Power is Lost
Series 230 Dimensions and Weight
B2ADTL Frame
126
184
117
214
104
78.5
112
A
(unit: mm)
B2ADTL
Size (mm)
A
Weight (kg)
2P
3P
4P
241.0
349.0
349.0
2.6
2.8
2.8
Note: It must be installed in DIN35 Rail to the cabinet
C2ADTL Frame
177.3
167.8
20
9
Ø6
181.6
100
116
126
130
150.5
12.5
171.5
9
6
17
23
B
A
23
Weight (kg)
34
34
C
(unit: mm)
2P
3P
4P
A
251.0
285.0
319.0
B
236.0
270.0
304.0
C
68.0
102.0
136.0
4.6
5.2
5.8
C2ADTL
Size (mm)
34
6
D2ADTL Frame
172.8
A
B
44
215
C
44
44
198.5
140 120
120 157.8 186.3
15.5x10.5
Ø7
(unit: mm)
2P
3P
4P
A
317.0
361.0
405.0
B
297.0
341.0
385.0
C
103.0
147.0
191.0
8.6
9.8
11.0
D2ADTL
Size (mm)
Weight (kg)
7
ASCO Power Transfer Switch Solutions for
Powerful Peace of Mind
E2ADTL Frame
213
28
9
251.5 240
265
107 226
65
13
65
65
19
174 195 290
208
Ø9
60
8
10
B
A
C
(unit: mm)
2P
3P
4P
A
384
449
514
B
357
422
487
C
146
211
276
14
17
20
E2ADTL
Size (mm)
Weight (kg)
Shipping Dimensions and Weights (Including TS and controller, without options)
Frame
Width
(MM)
Height
(MM)
Depth
(MM)
2P
3P
4P
2P
3P
4P
B2ADTL
602
220
267
4.9
5.5
5.7
5.2
5.8
6.0
C2ADTL
602
335
227
8.9
9.5
10.1
9.2
9.8
10.4
D2ADTL
650
350
300
13.0
14.5
16.0
13.4
14.9
16.4
E2ADTL
767
350
352
16
19
22
16.5
19.5
22.5
Weight (KG) with C1000
Weight (KG) with C2000
* All information is subject to change, for the latest information please contact ASCO sales team.
8
Series 230 Controller Feature Comparisons
C1000 Controller
C2000 Controller
Voltage and Frequency Sensing
Voltage and Frequency Sensing
•3-Phase under and over voltage settings on source I and source II
•3-Phase under and over voltage settings on source I and source II
•Phase loss sensing on source I and source II
•Under and over frequency settings on source I and source II
•Under and over frequency settings on source I and source II
•Voltage unbalance detection between phases
Time Delays
Time Delays
•Time delay sensing accuracy is ±1%
•Time delay can be set by operating parameter setting menu
•Transfer time delay can be set manually
•Time delay sensing accuracy is ±1%
Controller Display and Keypad
•Time delay can be set under different working modes
•LED display
•Transfer time delay can be set manually
•Touch pad for clearing alarm and manual operation
Controller Display and Keypad
•Switch position indicator lights
•LCD display
•Source acceptability indicator lights
•Touch pad for programming the features and settings
Operating Modes
•Switch position indicator lights
•Automatic and manual operation available
•Source acceptability indicator lights
•Source I Priority/ No Source Priority
Operating Modes
•Priority Source Swap
•Automatic and manual operation available
Center-off with time delay and center-off with
protection
•Source I Priority/ No Source Priority
•The center-off time delay can be set to avoid large current rushes to
inductive loads
Center-off with time delay and center-off with
protection
•Center-off with protection is available to protect critical loads (e.g.
Fire Pump)
•The center-off time delay can be set to avoid large current rushes to
inductive loads
Remote Control and Communication
•Center-off with protection is available to protect critical loads (e.g.
Fire Pump)
•Can control switch remotely (e.g. Position Control, Time Delay, etc.)
•Fire control signal input (24VDC)
•Priority Source Swap
Events Display
Power Supply of Controller
•Event log displays: 100 logged events with time and date of each
event, event type and event reason
•Operation Voltage (VAC): 208/ 220/ 230/ 240/ 380/ 400/ 415
Remote Control and Communication
•Uses RS485 interface, and supports MODBUS Communication
•Can control switch remotely (e.g. Position Control, Time Delay, etc.)
•Fire control signal input (24VDC)
Power Supply of Controller
•Operation Voltage (VAC): 208/ 220/ 230/ 240/ 380/ 400/ 415
9
•C2000 has ability to work with 24VDC power supply
24-hours Protection No Matter When
Trouble Strikes
Controller
Intended Application
Rated Operation Voltage Ue (V)
Rated Frequency (Hz)
Display Indicator
Source I Available
Source II Available
Source I Accepted (Load Connected)
Source II Accepted (Load Connected)
Center-off Position
Control Mode
Manual/Automatic
Source I Priority
No Source Priority
Source Sensing Setting
Phase Selection
Source I Voltage
Source II Voltage
Source I Frequency
Source II Frequency
Source I power loss
Source II power loss
Source I phase loss
Source II phase loss
Source I Voltage Dropout (Undervoltage)
Source II Voltage Dropout (Undervoltage)
Source I Overvoltage Trip
Source II Overvoltage Trip
Source I Overfrequency Transfer
Source II Overfrequency Transfer
Source I Frequency Dropout (Underfrequency)
Source II Frequency Dropout (Underfrequency)
Source I Voltage Pick Up
Source II Voltage Pick Up
Source I Frequency Pick Up
Source II Frequency Pick Up
Time Delay Setting
Override Momentary Source I Outage
Override Momentary Source II Outage
Transfer to Source I
Transfer to Source II
Engine Cooldown
Center-Off Position Delay
Others
RS-485
Modbus
Additional 24V DC Power Input.
Generator Control Signal Output
Fire Control Signal Input
Alarm
Auxiliary Contact
Events Log
Display Type
Installation
C1000
C2000
Residential, Light Commercial
208/220/230/240/380/400/415
50/60Hz
Commercial, Industrial
208/220/230/240/380/400/415
50/60Hz

































70% or 85%
70% or 85%
OFF or 120% 1
OFF or 120% 1
115%
115%
85%
85%
75% or 90%
75% or 90%
90%
90%
70% to 98%
70% to 98%
102% to 120% or OFF1
102% to 120% or OFF1
102% to 115%
102% to 115%
85% to 98%
85% to 98%
85% to 100%
85% to 100%
90% to 100%
90% to 100%
1 second
1 second
1s to 30 Minutes
0 to 5 Minutes
5 Minutes Fixed
OFF or 5 Seconds
0 to 3 Seconds
0 to 3 Seconds
0 to 30 Minutes
0 to 5 Minutes
0 to 60 Minutes
0 to 5 Seconds
Optional
Optional









Optional
Optional

LED
Din rail installation and Panel installation
LED+LCD
Panel installation
Controller with Energy Storage
Optional
■-Yes, Standard Blank-Not Available/ Not Applicable
1
the controller used on 415V, its Overvoltage Droupout is 115% both on Source I and Source II
10
C1000 Controller Port Function Description
Accessory 72D
Optional RS485 Port
RS485
24V
Generator
Start
Alarm
Fire Control
Input
Transfer to
Position O
Transfer to
Position I
Transfer to
Position II
RS485
GEN
ALM
FIRE
DI5
DI6
DI7
485 Port
X3 User Terminal
X4
C1000 CONTROLLER
X1 Power Terminal
X2 Control Terminal
Power and Voltage detection
Transfer Switch Position Detection
and Transfer Control
To
Transfer
Switch X1
11
To
Transfer
Switch X2
72D
C2000 Controller Port Function Description
24V
Alarm
ALM
O
I
II
TS Position
DO1
DO2
DO3
Generator
Start
RS485
GEN
485 PORT
Fire Control Transfer to Transfer to Transfer to
Input
Position O Position I Position II
FIRE
DI5
DI6
DI7
X3 User Terminal
X5
X4 User Terminal
C2000 CONTROLLER
X1 Power Terminal
Voltage Detection
To
Transfer
Switch X1
X2 Control Terminal
Transfer Switch Position Detection
24V DC
and Transfer Control
Power Input
To
Transfer
Switch X2
Lost
Power
Capacitor.
Output
24V
Energy
storage
output
Accessory 1H
Optional Built-In Capacitor used as a
(rechargeable) one-time motor-control
transfer after complete power loss.
This accessory also requires a different
connector board on the Transfer Switch Unit.
1H
12
Critical Loads Demand ASCO
Controller Dimensions and Weight*
C1000 Controller (With or Without optional 72D Accessory)
80.7
58.7
93.5
111.5
46.2
47±0.5
94±0.5
Panel Opening Dimensions
Weight: 0.74kg
(unit: mm)
C2000 Controller
191±1
Source I
86
Source II
134±1
142
132
80
Run Auto Alarm
UP
Esc
Transfer Switch Position
197
Enter
Down
189
Panel Opening Dimensions
Weight: 1kg
(unit: mm)
13
C2000 Controller with Energy Storage (Accessory 1H)
128.7 122.2
189.0
Run Auto Alarm
Source I
Source II
132.0
142.0
UP
Esc
Transfer Switch Position
Enter
Down
197.0
Weight: 1.64kg
(unit: mm)
*Not Shipping weight, Actual unit weight
14
About Emerson Network Power
Emerson Network Power, a business of Emerson (NYSE:EMR), protects and optimizes critical infrastructure for data centers, communications networks,
healthcare and industrial facilities. The company provides new-to-the-world solutions, as well as established expertise and smart innovation in areas including
AC and DC power and renewable energy, precision cooling systems, infrastructure management, embedded computing and power, integrated racks and
enclosures, power switching and controls, and connectivity. Our solutions are supported globally by local Emerson Network Power service technicians. Learn
more about Emerson Network Power products and services at
www.emersonnetworkpower.com
About Emerson
Emerson (NYSE: EMR), based in St. Louis, Missouri (USA), is a global leader in bringing technology and engineering together to provide innovative solutions for
customers in industrial, commercial, and consumer markets around the world. The company is comprised of five business segments: Process Management,
Industrial Automation, Network Power, Climate Technologies, and Commercial & Residential Solutions. Sales in fiscal 2013 were $24.7 billion. For more
information, visit:
www.emerson.com
Legal statement: While every precaution has been taken to ensure accuracy and completeness herein, Emerson assumes no responsibility,
and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications subject to change
without notice.
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Road, Science & Industry Park,
Nanshan District, 518057 Shenzhen
China Telephone: 86-755-86010808
Postcode: 518057
Pre-sales hotline:
After-sales hotline:
400-887-6526
400-887-6510
www.emersonnetwork.com.cn
Emerson Network Power, ASCO, the Emerson Network Power logo and ASCO logo are trademarks and service marks of Emerson Electric Co. ©2014 Emerson Electric Co.
E-X6216497-0414