MA-COM 20-050-19XP

Frequency Sensitive Relays
WILMAR™ Protective Relays – 20-050-19 Series (Voltage/Frequency)
Function: 27/81
• ANSI/IEEE C37.90-1978
• UL file No. E58048
• CSA file No. LR61158
#6 - 32 STUDS
6 PLACES
4 1/2
The output contacts of frequency relays are energized when the frequency exceeds the adjustable set
point. Overfrequency and underfrequency relays are
available in 50, 60, and 400Hz. Combination over/
underfrequency “band pass” relays are also available. These are energized at rated frequency and deenergized during overfrequency or underfrequency
conditions. Frequency Differential relays are energized above the preset frequency. The pick-up and
drop-out frequency settings are independently adjustable.
3 13/16
3.0 2
1/
3
2
3 /4
1 /2
3
PART NUMBER SELECTION
11 /64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PRODUCT SPECIFICATIONS
Part Number
20-050-19 Series
Nominal Voltage (±20%) ................. 120 VAC, Single Phase
Nonimal Frequency .......................... 60 Hz.
Voltage Adjustment Range (PU) ..... 85 to 120 VAC
Frequency Adjustment Range (PU) . 45 to 60 Hz
Output Contacts ............................... One set N.O., one set N.C.
PART NUMBER SELECTION
Sample Part No.20-050-19X
Type:
20-050-19 = Voltage/Frequency
Mounting Options
Blank = stud
X = Flange
Options:
P = Surge Suppression
Contact Ratings ................................ 5 amp resistive at 120 VAC or 28 VDC
Notes:
1.
Remove black screws for access to the voltage and frequency and the time adjustments.
2.
Clockwise rotation of the voltage adjustment potentiometer will raise the voltage trip point.
3.
Clockwise rotation of the frequency adjustment will raise the frequency time point.
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
43