MA-COM WOUF-12-5060-T

Frequency Sensitive Relays
WILMAR™ Protective Relays – WOUF Series, Over/Underfrequency
Function: 81 O/U
• ANSI/IEEE C37.90-1978
• UL file No. E58048
• CSA file No. LR61158
S
TRIP
AL S EWS
N
I
R
M
TER 32 SC
#6 -
3
The output contacts of frequency relays are energized when the frequency exceeds the adjustable
set point. Overfrequency and underfrequency relays are available in 50, 60 and 400Hz. Combination
over/underfrequency “band pass” relays are also
available. These are energized at rated frequency
and de-energized during overfrequency or
underfrequency conditions. Frequency Differential
relays are energized above the preset frequency.
The pick-up and drop-out frequency settings are
independently adjustable.
3
4
1 /2
1 /8
5 /8
4
Operation:
1 /2
3 1 /4
4
The relay will energize at normal frequency; The
normally closed contacts will open and the normally
open contacts will close. The relay will drop-out after
time delay at overfrequency or underfrequency.
Typical Curves (WOUF Series)
90
11 / 64 " DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
80
PART NUMBER SELECTION
Time Delay
70
Standard Time Delay
A minimum, fixed inverse time delay is incorporated in
all frequency relays to prevent nuisance tripping and is
represented by the typical curves shown below.
Adjustable Time Delay
If additional time delay is required, a suffix "T" must be
added to the part number. This allows the minimum
fixed time delay to be field-adjustable up to 20 seconds
60
50
40
PRODUCT SPECIFICATIONS
Part Number
WOUF Series
Nominal Voltage (±20%) ................. 120, 230, 380 and 460 volts
Nonimal Frequencies ....................... 50, 60 and 400 Hz.
Trip Point .......................................... Screwdriver adjustable. Adjustment range in
accordance with ordering information.
Operating Temperature .................... -40oC to +65oC
Differential ........................................ The frequency pick-up to drop-out differential is .5% max
Voltage Drift ..................................... ± 0.05% maximum frequency error for input voltage
variation of ±10%
Time Delay ........................................ See Time versus Frequency curves
Surge Withstand Capability ............. In compliance with C37-90B ANSI/IEEE
Output Contacts ............................... One set N.O., one set N.C.
Contact Ratings ................................ 5 amp resistive at 120 VAC or 28 VDC
Notes:
1.
Remove black screws for access to the frequency and the time adjustments.
2.
Clockwise rotation of the frequency potentiometer will raise the frequency trip point.
3.
Clockwise rotation of the time adjustment, option "T" will increase the drop-out time delay.
40
30
0
1
2
3
4
5
Drop-Out Time Delay
PART NUMBER SELECTION
Sample Part No.
WOUF-12-5060-T
Type:
WOUF = Over/Underfrequency
Input Voltage (VAC)
12 = 120
23 - 230
38 = 380
46 = 460
Frequency Range
UF Adj.
OF Adj.
50 =
40-50 Hz 50-60 Hz
60 =
50-60 Hz 60-70 Hz
400 = 350-400 Hz400-450 Hz
Time Delay Options
blank = Per Time Curve
T = Adjustable
Consult factory for additional models.
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
6