EPCOS B44066T0100E402

Film capacitors – Power Factor Correction
Key components – Thyristor modules
Series/Type:
Ordering code:
TSM-LC100
B44066T0100E402
Date:
Version:
September 2008
1
Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the
table and then change the color to "white". This ensures that the table disappears (invisible) for the customer PDF.
Don't change formatting when entering or pasting text in the table and don't add any cell or line in and to it!
Identification/Classification 1
(header 1 + top left bar):
Film capacitors – Power Factor Correction
Identification/Classification 2
(header 2 + bottom left header bar):
Key components – Thyristor modules
Ordering code: (top right header bar)
B44066T0100E402
Series/Type: (top right header bar)
TSM-LC100
Preliminary data (optional):
(if necessary)
Preliminary data
Department:
FK PC PM PFC
Date:
September 2008
Version:
1
© EPCOS AG 2008. Reproduction, publication and dissemination of this publication, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited
Film capacitors – Power Factor Correction
Key components – Thyristor modules
B44066T0100E402
TSM-LC100
Preliminary data
Characteristics
„ Fast electronically controlled self observing
thyristor switch
„ Usage in dynamic (fast) power factor
correction systems
„ For capacitive loads up to 100 kvar
Features
„ Easy installation: self-check after turn-on of
main voltage
„ Display and control via LED-display
„ Permanent self-controlling: voltage
parameters, phase sequence,
capacitor output, temperature
„ Forced cooling by fan, temperature controlled
Technical data
Dimensions
157 × 240 × 195 mm (w × h × d)
Weight
5.5 kg
Voltage
3 × 400 V
Maximum voltage
- in conventional PFC systems (without reactors)
440 V
- in detuned PFC systems (7% detuning)
440 V (no upward tolerance permitted)
- in detuned PFC systems (14% detuning)
Frequency
400 V
50 Hz/60 Hz
Max. power
75 ... 100 kvar
Max. RMS current*
200 A
(*no continuous current – thermal load has to be considered)
Auxiliary supply
230 V AC (needed for fan) via terminal clamp;
automatically controlled cooling, over temperature
switch off
Activation
10 … 24 V DC (20 mA), via terminal clamp; internally
insulated
Monitoring
Net voltage, temperature and operation status
Note: Before re-switching after temperature fault, heat
sink temperature must be below 50 °C (hysteresis)!
Display
Power dissipation
2 LEDs/phase: operation/error, triggering signal
Direct connection 4-pole via bus bar cable lug 70 mm2,
D = 10 mm), connection from bottom
PV (W) = 2.0 × I (in A); at 400 V/100 kvar typical 300 W
Thermal warming
20 K above ambient temperature at nominal load
Power circuit
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
September 2008
Page 2 of 6
Film capacitors – Power Factor Correction
Key components – Thyristor modules
B44066T0100E402
TSM-LC100
Preliminary data
Fuses*
(required for protection of TSM-LC and capacitor)
(*not included in the delivery)
3 × electronic fuse „superfast“ (NH1 AC 690 V)
100 kvar: 250 A (e.g. SIBA Art.No.: 20 211 20-250)
Switching time
approx. 5 ms
Operating ambient temperature with nominal load
–10 °C ... +55 °C
Assembling
Direct on mounting plate
Mounting position
Vertical, minimum 100 mm distance upwards and
downwards
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
September 2008
Page 3 of 6
Film capacitors – Power Factor Correction
Key components – Thyristor modules
B44066T0100E402
TSM-LC100
Preliminary data
Connection diagram
Three-phase load (standard)
Fuse superfast
250 A at 100 kvar
NH1/690 V
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
September 2008
Page 4 of 6
Film capacitors – Power Factor Correction
Key components – Thyristor modules
B44066T0100E402
TSM-LC100
Preliminary data
Cautions and warnings
General
•
Thyristor modules TSM series may only be used for the purpose they have been designed for.
•
Thyristor modules TSM series may only be used in combination with appropriate pre-switched grid
separator device.
•
Thyristor modules have to be projected in such a way that in case of any failure no uncontrolled high
currents and voltages may occur.
•
The devices in operation have to be protected against moisture and dust, sufficient cooling has to be
assured.
Attention
Due to the switching principle of the thyristor module the power capacitors are permanently loaded to the peak
value of the grid voltage (DC voltage) even when switched off. Therefore the following rules have to be obeyed
in any case:
•
For standard PFC-systems (400 V grid, without reactors) capacitors of 440 V nominal voltage have to be
used; for detuned systems (400 V grid) capacitors of 525 V nominal voltage have to be used.
•
Due to the high voltage (2 × peak value of nominal voltage) that occurs, the discharge resistors of the power
capacitors have to be replaced by special types.
•
In dynamic systems with TSM modules no fast discharge reactors may be used (reactor = DC-wise short
circuit).
•
For standard PFC-systems without (de-)tuned filter reactors 2 special current limiting reactors are
mandatory per thyristor module. Further information on request.
•
Thyristor modules in general have to be protected by superfast electronic fuses. Principles for dimensioning
have to be considered. Fuses in the system have to be marked.
•
Due to the special switching, the PFC capacitors are fully loaded even when the particular step has been
switched off. Protection against contact has to be guaranteed. Warning signals in the systems are required.
•
Even in switched off state no electrical isolation is achieved for electronic switches. Therefore parts of the
systems may not be touched after switching off the complete system before the capacitors have been
completely discharged.
FAILURE TO FOLLOW CAUTIONS MAY RESULT, WORST CASE, IN PREMATURE FAILURES OR
PHYSICAL INJURY.
U Please read cautions information about PFC capacitors and cautions as well as installation and maintenance instructions to ensure
optimum performance and prevent products from failing, and in worst case, bursting and fire, etc. The actual Product Profile is available at
www.epcos.com/publications.
Information given in the PFC-product profile and values given in the data sheet reflect typical specifications. You are kindly requested to
approve our product specifications or request our approval for your specification before ordering.
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
September 2008
Page 5 of 6
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As a
rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of electronic components or failure
before the end of their usual service life cannot be completely ruled out in the current state
of the art, even if they are operated as specified. In customer applications requiring a very high
level of operational safety and especially in customer applications in which the malfunction or
failure of an electronic component could endanger human life or health (e.g. in accident
prevention or life-saving systems), it must therefore be ensured by means of suitable design of the
customer application or other action taken by the customer (e.g. installation of protective circuitry
or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or
failure of an electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as hazardous). Useful information on this will be found in our Material
Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed
questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequently,
we cannot guarantee that all products named in this publication will always be available.
The aforementioned does not apply in the case of individual agreements deviating from the
foregoing for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of
the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSSP, CTVS, DSSP, MiniBlue, MKK,
MLSC, MotorCap, PCC, PhaseCap, PhaseMod, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD,
SIMID, SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are trademarks registered or
pending in Europe and in other countries. Further information will be found on the Internet at
www.epcos.com/trademarks.
Page 6 of 6