HONEYWELL 3090A

Hazardous Location
Industrial VRS Magnetic
Speed Sensors
DESCRIPTION
Hazardous Location VRS sensors are designed for use in
locations where explosion-proof or intrinsically safe sensors
are required.
Passive VRS (Variable Reluctance Speed) Magnetic Speed
sensors are simple, rugged devices that do not require an
external voltage source for operation.
A permanent magnet in the sensor establishes a fixed
magnetic field. The approach and passing of a ferrous metal
target near the sensor’s pole piece (sensing area) changes the
flux of the magnetic field, dynamically changing its strength.
This change in magnetic field strength induces a current into a
coil winding which is attached to the output terminals.
FEATURES
Self-powered operation
Direct conversion of actuator speed to output frequency
Simple installation
No moving parts
Designed for use over a wide range of speeds
Adaptable to a wide variety of configurations
Customized VRS products for unique speed sensing
applications
Housing diameters: 3/4 in, 5/8 in
Housing material/style: stainless steel threaded
Terminations: MS3106 connector, preleaded
Output voltages: 30 Vp-p to 60 Vp-p
The output signal of a VRS sensor is an ac voltage that varies
in amplitude and wave frequency as the speed of the
monitored device changes, and is usually expressed in peak to
peak voltage (Vp-p).
One complete waveform (cycle) occurs as each target passes
the sensor’s pole piece. If a standard gear were used as a
target, this output signal would resemble a sine wave if viewed
on an oscilloscope.
Honeywell also offers VRS sensors for general purpose, high
output, power output, high resolution and high temperature, as
well as low-cost molded versions.
POTENTIAL APPLICATIONS
Engine RPM (revolutions per minute) measurement on
aircraft, automobiles, boats, buses, trucks and rail
vehicles
Motor RPM on oil and gas drilling equipment and
machinery
Motor RPM measurement on drills, grinders, lathes and
automatic screw machines
Process speed measurement on food, textile, paper,
woodworking, printing, tobacco and pharmaceutical
industry machinery
Motor speed measurement of electrical generating
equipment in grain elevators, sawmills and other
potentially explosive environments
Speed measurement of pumps, blowers, mixers, exhaust
Gear speed measurement
Hazardous Location
3/4 INCH EXPLOSION-PROOF SENSORS (All dimensions for reference only. mm/[in])
When properly installed using the explosion containment method, all 3070X and catalog listings on this page are certified for use in
hazardous locations as follows: Class I, Groups A, B, C, D; Class II Groups E, F, G; Class III.
These catalog listings have been tested to and meet the requirements of applicable U.S. and Canadian specifications for the
locations described above.
General Specifications
Test Condition Specifications
Parameter
Characteristic
Min. output voltage 60 Vp-p
Parameter
Inductance
Characteristic
115 mH max.
Coil resistance
191 Ohm to 280 Ohm
Gear pitch range
Pole piece
diameter
Min. surface
speed
Operating temp.
range
4,75 mm [0.187 in]
Optimum actuator
0,38 m/s [15 in/s] typ.
Max. operating
frequency
Vibration
12 DP (module 2.11)
or coarser
8 DP (module 3.17)
ferrous metal gear
40 kHz typ.
Mounting thread
3/4-20 UNEF-2A
Catalog
Listing
3070A
3070A35
-73 ºC to 93 ºC
[-100 ºF to 200 ºF]
Thread
Weight
Length (A)
45 mm [1.8 in] 294 g [10.5 oz]
88 mm [3.5 in] 322 g [11.5 oz]
Termination
Mil-Std 202F
Method 204D
18 AWG PVC-Insulated
Leads
24,05
[1.00]
A
www.honeywell.com/sensing
31,75
[1.250]
3000 MIN
[120.00]
1/2-14 NPT
BLIND END SHELL
POLE PIECE
2
Parameter
Characteristic
Surface speed 25 m/s
[1000 in/s]
Gear
8 DP
(module 3.17)
Air gap
0,127 mm
[0.005 in]
Load
100 kOhm
resistance
Industrial VRS Magnetic Speed Sensors
5/8 INCH EXPLOSION-PROOF SENSORS (All dimensions for reference only. mm/[in])
When properly installed using the explosion containment method, the 3090X catalog listings on this page are certified for use in
hazardous locations as follows: Class I, Groups A, B, C, D; Class II Groups E, F, G; Class III.
These catalog listings have been tested to and meet the requirements of applicable U.S. and Canadian specifications for the
locations described above.
The catalog listings on this page conform to standards:
II 3 G EEx nA II T6.
General Specifications
Test Condition Specifications
Parameter
Characteristic
Min. output voltage 60 Vp-p
Parameter
Inductance
Characteristic
115 mH max.
Coil resistance
191 Ohm to 280 Ohm
Gear pitch range
Pole piece
diameter
Minimum surface
speed
4,75 mm [0.187 in]
Optimum actuator
0,38 m/s [15 in/s] typ.
Maximum
operating
frequency
12 DP (module 2.11)
or coarser
8 DP (module 3.17)
ferrous metal gear
40 kHz typ.
Operating temp.
range
Mounting thread
-73 ºC to 93 ºC
[-100 ºF to 200 ºF]
5/8-20 UNF-2A
Vibration
Catalog
Listing
3090A
3090A35
Thread
Length (A)
45 mm [1.8 in]
88 mm [3.5 in]
Weight
Termination
Parameter
Characteristic
Surface speed 25 m/s
[1000 in/s]
Gear
8 DP
(module 3.17)
Air gap
0,127 mm
[0.005 in]
Load
100 kOhm
resistance
Mil-Std 202F
Method 204D
18 AWG PVC-insulated
leads
24,5
[1.00]
A
31,75
[1.250]
3000 MIN
[120.00]
1/2-14 NPT
280 g [9.0 oz]
366 g [10.0 oz]
BLIND END SHELL
POLE PIECE
Honeywell Sensing and Control
3
Hazardous Location
5/8 INCH (M16*) INTRINSICALLY SAFE VRS SENSORS (All dimensions for reference only. mm/[in])
*Contact Honeywell for availability of metric mounting thread versions.
When properly installed using the intrinsic safety protection method connected per the control drawings on pages 6 and 7, catalog
listings 3042A is intrinsically safe for hazardous locations as follows:
Class I, Groups A, B, C, D.
This product has been tested to and meets the requirements of applicable U.S. and Canadian specifications for the locations
described above.
General Specifications
Test Condition Specifications
Parameter
Characteristic
Min. output voltage 30 Vp-p
Parameter
Inductance
Characteristic
26 mH max.
Coil resistance
150 Ohm
Gear pitch range
Pole piece
diameter
Min. surface
speed
3,9 mm [0.156 in]
Optimum actuator
0,38 m/s [15 in/s] typ.
Max. operating
frequency
16 DP (module 1.58)
or coarser
12 DP (module 3.17)
ferrous metal gear
40 kHz typ.
Operating temp.
range
Mounting thread
-55 ºC to 120 ºC
[-67 ºF to 250 ºF]
5/8-18 UNF-2A
Vibration
N/A
Termination
MS3106 connector
Catalog
Listing
3042A
Weight
70 g [2.5 oz]
19,05
[0.750]
8,0
[0.312]
0,76
[0.030]
Ø13,84
[0.545]
‘
4
www.honeywell.com/sensing
36.5
[1.437]
Parameter
Characteristic
Surface speed 25 m/s
[1000 in/s]
Gear
8 DP
(module 3.17)
Air gap
0,127 mm
[0.005 in]
Load
100 kOhm
resistance
28,12
[1.107]
Ø18,29
[0.720]
B
A
+
-
Industrial VRS Magnetic Speed Sensors
5/8 INCH (M16*) INTRINSICALLY SAFE VRS SENSORS (All dimensions for reference only. mm/[in])
*Contact Honeywell for availability of metric mounting thread versions.
When properly installed using the intrinsic safety protection method connected per the control drawings on pages 6 and 7, catalog
listing 3042H20 is intrinsically safe for hazardous locations as follows:
Class I, Groups A, B, C, D; Class II Groups E, F, G; Class III.
This product has been tested to and meets the requirements of applicable U.S. and Canadian specifications for the locations
described above.
General Specifications
Test Condition Specifications
Parameter
Characteristic
Min. output voltage 30 Vp-p
Parameter
Inductance
Characteristic
26 mH max.
Coil resistance
150 Ohm
Gear pitch range
Pole piece
diameter
Min. surface
speed
Operating temp.
range
3,9 mm [0.156 in]
Optimum actuator
0,38 m/s [15 in/s] typ.
Max. operating
frequency
Vibration
16 DP (module 1.58)
or coarser
12 DP (module 3.17)
ferrous metal gear
40 kHz typ.
Mounting thread
5/8-18 UNF-2A
Catalog
Listing
3042AH20
-55 ºC to 120 ºC
[-67 ºF to 250 ºF]
Weight
140 g [5.0 oz]
Termination
25,4
[1.00]
N/A
18 AWG PVC-insulated
leads
50
[2.0]
0,51
[0.020]
Parameter
Characteristic
Surface speed 25 m/s
[1000 in/s]
Gear
8 DP
(module 3.17)
Air gap
0,127 mm
[0.005 in]
Load
100 kOhm
resistance
31,75
[1.250]
3000 MIN
[120.00]
1/2-14 NPT
Honeywell Sensing and Control
5
Hazardous Location
CONTROL DRAWING FOR SINGLE CHANNEL BARRIERS
Hazardous Location
Non-hazardous Location
Speed Sensor
Intrinsic Safety Barrier
HAZARDOUS LOCATIONS
GENERAL NOTES
Catalog listing 3042H20:
1.
For jurisdictions requiring certification to the applicable
Class I, Groups A, B, C, D
Canadian standards, the barrier must be CSA Certified
Class II, Groups E, F, G
and the system must be installed in accordance with the
Canadian Electrical Code Part 1.
Class III
2.
For jurisdictions requiring certification to the applicable
Occupational Safety and Health Administration (OSHA)
Catalog listing 3042A:
standards, the barrier must be CSA NRTL or equivalent
Class I, Groups A, B, C, D
and the system must be installed in accordance with the
ENTITY PARAMETERS
National Electrical Code (NEC), article 504 or
Vmax = 24 V, Imax = 35 mA, Li = 26 mH, Ci = 0 μF
ANSI/NFPA 70.
Any barrier (see General Notes) with entity parameters
connected in accordance with barrier manufacturers
SENSOR GROUNDING
instructions of:
Catalog listing 3042A: Sensor housing must be connected to
Vmax > Voc
Ca > Ci + cable capacitance
Imax > Isc
La > Li + cable inductance
intrinsically safe system ground during installation.
Catalog listing 3042H20: Green wire must be connected to
intrinsically safe system ground.
SYSTEM PARAMETERS
Any barrier (see General Notes) having one of the following
Exia = Intrinsically Safe, Sécurité Intrinsèque
specified parameters:
Vmax
6
Rmin
Vmax
Rmin
Vmax
Rmin
30
707
20
421
10
136
25
580
15
278
5
1
www.honeywell.com/sensing
Industrial VRS Magnetic Speed Sensors
CONTROL DRAWING FOR DUAL CHANNEL BARRIERS
Non-hazardous Location
Hazardous Location
Speed Sensor
Ground
Intrinsic Safety Barrier
.
HAZARDOUS LOCATIONS
GENERAL NOTES
Catalog listing 3042H20:
1. For jurisdictions requiring certification to the applicable
Class I, Groups A, B, C, D
Canadian standards, the barrier must be CSA Certified
Class II, Groups E, F, G
and the system must be installed in accordance with the
Class III
Canadian Electrical Code Part 1.
2. For jurisdictions requiring Certification to the applicable
Catalog listing 3042A:
Occupational Safety and Health Administration (OSHA)
Class I, Groups A, B, C, D
standards, the barrier must be CSA NRTL or equivalent
and the system must be installed in accordance with the
ENTITY PARAMETERS
National Electrical Code (NEC), article 504 or
Vmax = 24 V, Imax = 35 mA, Li = 26 mH, Ci = 0 μF
ANSI/NFPA 70.
Any barrier (see General Notes) with entity parameters
connected in accordance with barrier manufacturers
SENSOR GROUNDING
instructions of:
Catalog listing 3042A: Sensor housing must be connected to
Vmax > Voc
Ca > Ci + cable capacitance
Imax > Isc
La > Li + cable inductance
intrinsically safe system ground during installation.
Catalog listing 3042H20: Green wire must be connected to
SYSTEM PARAMETERS
intrinsically safe system ground.
Any barrier (see General Notes) having one of the following
specified parameters:
Vmax
Rmin
Exia = Intrinsically Safe, Sécurité Intrinsèque
Vmax
Rmin
Vmax
Rmin
30
1414
20
842
10
272
25
1160
15
556
5
2
Honeywell Sensing and Control
7
WARNING
WARNING
PERSONAL INJURY
MISUSE OF DOCUMENTATION
DO NOT USE these products as safety or emergency stop
The information presented in this product sheet is for
devices or in any other application where failure of the
reference only. Do not use this document as a product
product could result in personal injury.
installation guide.
Failure to comply with these instructions could result in
Complete installation, operation, and maintenance
death or serious injury.
information is provided in the instructions supplied with
each product.
Failure to comply with these instructions could result in
WARRANTY/REMEDY
Honeywell warrants goods of its manufacture as being free of
death or serious injury.
defective materials and faulty workmanship. Honeywell’s
standard product warranty applies unless agreed to otherwise
SALES AND SERVICE
by Honeywell in writing; please refer to your order
Honeywell serves its customers through a worldwide network
acknowledgement or consult your local sales office for specific
of sales offices, representatives and distributors. For
warranty details. If warranted goods are returned to Honeywell
application assistance, current specifications, pricing or name
during the period of coverage, Honeywell will repair or replace,
of the nearest Authorized Distributor, contact your local sales
at its option, without charge those items it finds defective. The
office or:
foregoing is buyer’s sole remedy and is in lieu of all other
warranties, expressed or implied, including those of
E-mail: [email protected]
merchantability and fitness for a particular purpose. In no
event shall Honeywell be liable for consequential, special,
or indirect damages.
Internet: www.honeywell.com/sensing
Phone and Fax:
While we provide application assistance personally, through
Asia Pacific
+65 6445-3033 Fax
our literature and the Honeywell web site, it is up to the
customer to determine the suitability of the product in the
+65 6355-2828
Europe
+44 (0) 1698 481481
+44 (0) 1698 481676 Fax
application.
Latin America
+1-305-883-8257 Fax
Specifications may change without notice. The information we
supply is believed to be accurate and reliable as of this
+1-305-805-8188
USA/Canada
printing. However, we assume no responsibility for its use.
+1-800-537-6945
+1-815-235-6847
+1-815-235-6545 Fax
Sensing and Control
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422
www.honeywell.com
005879-2-EN
March 2012