MORNSUN SW2001-EX

SW20XX-EX Isolating Switching Barrier
FEATURES
PRODUCT PROGRAM
● Fitted devices: 1. NAMUR Sensors;
2. Mechanical Joints.
Part number
● Phase-angel and inverse control setting;
● Open circuit detection setting
SW2001-EX
● Respective Isolation(2,500VDC between
SW2002-EX
Input/Output/Power source);
Input(Power)
Output(Hazardous end)
Voltage(VDC)
Voltage
Typ
Range
Typ
Short Cricuit
Current
24
18-36
8 VDC
< 8 mA
Output
(Safe end)
Channel
numbers
Relay output
1
Relay output
2
● Operation Temperature:-20℃-+60℃
● Reliable Performance (MTBF>1,000,000 Hours).
APPLICATIONS
This Isolation Switching Barrier can detect
ELECTRICAL CHARACTERISTICS
Common
parameter
switch or approach switch’s status in locations
where hazardous exists; isolate, transmit and
Operation voltage
18-36VDC
Power consumption
About 2.0W (with relay output OFF)
Power indicating
LED light (green) ON when operating
Input Signal
Switch status of NUMAR sensor,
mechanical joint etc
Output Voltage
8V(Open status)
Short circuit current
<8mA
output it to safe area. Input and output can be set
to inverse control. Approach switch open circuit
detection
function.
Isolation
between
Input/
Hazardous
Area
Output/Power source.
MODEL SELECTION
Safe Area
SW XXXX-EX
Explos io n protection certification mark
Channe l number
Additional function
Signal o utput mode ( s afe area)
Signal o utput mode ( hazardous a rea)
Detectin g signal type
MORNSUN Guangzhou Science & Technology co., Ltd.
Address: 2/F, Bldg 6, Huangzhou Industrial Park,
Chebei Rd, Tianhe, Guangzhou, China 510660
Tel: 86-20-38601850 39601530 38601679
Fax: 86-20-38601272
http://www.mornsun-power.com
Input switching frequency
<10Hz
threshold
Typ:1.55mA (hysteresis:0.2mA)
Output signal
Relay output(1” ON” joint)
Response time
<20ms
driving capability
250VAC / 3A or 30VDC / 3A
Load type
Resistive load
TRANSMISSION CHARACTERISTICS
Under phase-angel control
(K1 “OFF”)
Input loop current > 2.1mA, relay output close, channel
indicator light (yellow) ON.
Input loop current < 1.2mA, relay output open, channel
indicator light (yellow) OFF.
Input loop current > 2.1mA, relay output close, channel
indicator light (yellow) OFF.
Under inverse control
(K1”ON”)
Input loop current < 1.2mA, relay output open, channel
indicator light (yellow) ON.
Open detection function
Function when K3 is OFF
When connected with NAMUR Input loop current < 0.05mA, open circuit alarm, channel
red indicator light ON.
sensor
When connected with common To achieve open circuit detection function, a 10KΩ resistor
contact joint switch
must be connected to the switch in parallel.
ISOLATION CHARACTERISTICS
Electrical isolation
MORNSUN reserves the copyright
Isolation between each part (Signal input end/Signal output end/Power
source end)
Isolation strength
2.5KVDC (test for 1minute, humidity < 70%)
Surge Resist
5KV 1.2/50us (Based on IEC255-4)
EMC
EN61326
Specifications subject to change without notice.
SW20XX-EX
A/0-2008
Page 1 of 2
STANDARDS AND CERTIFICATIONS
APPLICATION IN INTRINSICALLY
Explosion protection certification mark
[Exia]IIC
EXPLOSION PROTECTION SYSTEM
Explosion protection certification parameters
Um=250Vrms、Uo=10.5V、Io=14mA
Po=37mW、Co=1.6uF、Lo=150mH
In
Certified by: CHINA NATIONAL QUALITY SUPERVISION AND TEST CENTRE FOR
EXPLOSION PROTECTED ELECTRICAL PRODUCTS
No.:CNEx08.0003
intrinsic
safety
explosion
SAFE
protection
systems, isolating barrier belongs to affiliated
device. It is installed at safe area, as a
connection between intrinsic safety devices in
the hazardous area and non-intrinsic safety
devices in the safe area. By limiting the energy
OTHER CHARACTERISTICS
to a certain safe amount, it ensures the safety
Operation temperature:-20-+60℃
Ambient
temperature
of in spot devices and people.
Transport and Storage temperature:-40-+85℃
Package
35mm DIN Rail package: T type DIN Rail (DIN50022), 4x 4 terminals
plug and pull connector, thickness 22.5mm, anti-flaming material
UL94-V0
Protection Grade
IP20(IEC60529 / EN60529)
Weight
About 66g
Selection regulations for intrinsic safety
explosion protection system:
1. The explosion protection grade of the
barrier must be equal to or higher than
that of in spot intrinsic safety explosion
PACKAGING SIAE AND TERMINAL DESCRIPTION
protection device.
2. Take inconsideration of hazardous end
91 . 6
output resistance and loop resistance,
make sure the barrier’s output voltage
meets the minimum operation voltage
Channel 1 Phase -angl e and i nverse control sett i ng
Channel 2 Phase -angl e and i nverse control sett i ng
requirement of in spot intrinsic safety
device.
Open ci rcui t al arm control
9 9.0
Open ci rcui t i ndi cat or control
Output i ndi cator l i ght
3. The
Power source i ndi cator l i ght
safety
parameters
of
Barrier’s
intrinsic safety end meets:
Uo ≤ UI, Io ≤ Iin, Po ≤ Pin
Co ≥ Cin,
4. Select
22.5
Lo ≥ Lin
suitable
Safety
barrier
which
matches the in spot intrinsic safety device
for the power’s phase, signal type and
Safe area :
Hazardous area :
1: channel1 output (-)
13:channel1 input (-)
2: channel output (+)
14:channel1 input (+)
3: input of power source (-)
4: input of power source (+)
5: channel2 output (-)
9:channel2 input (-)
6: channel2 output (+)
10:channel2 input (+)
transmission mode.
5. Apply
necessary
protections,
avoid
influence the in spot intrinsic safety
device’s operation from leakage current
Un it: mm .
To le ran ce:+ 0. 5mm.
No te: In sing le cha nn el mo de, l cha n ne l 2 is in va.lid
that generated by safety barrier.
Operation notes:
1. Please read the user manual carefully
APPLICATION CIRCUIT DIAGRAM
before using. If any questions please
contact our technical support department.
Hazardous area
2.
Please do not use this product in
3.
The power supply of this product should
S a fe a re a
13
hazardous area.
1
be 24VDC power source. It is forbidden
Cha n ne l1
14
to use 220VAC power supply.
2
4.
To avoid invalid explosion protection
function,
DCS
9
5
10
6
PLC
or
any
failure,
users
disassemble this product is forbidden.
Ch a nn el 2
3
4
In pu t vo lta g e o f p o we r sou r ce
1 8- 3 6 VDC
N ot e: I n s ingle model, c hannel 2 is inv aid .
MORNSUN reserves the copyright
Specifications subject to change without notice.
SW20XX-EX
A/0-2008
Page 2 of 2