Limit and Enclosed Switches
Weather-Sealed Explosion-Proof Switches
FEATURES
1 Sealing - applicable portions of NEMA 1,
3, 4, 4X, 6, 6P, 7, 9, and 13
1 Watertight and dusttight for outdoor use
1 4-20 mA analog output available
1 UL Listed, file #E14274
1 Analog UL file #E68247
1 CSA Certified, file #LR57324
1 Rugged cast aluminum housing
1 Pretravel, overtravel, and actuating
sequence can be field adjusted without
tools (all basics individually)
1 Rotary types convert in seconds to
clockwise, counterclockwise, or bothway operation
CX switches are built especially for outdoor
use in hazardous atmospheres. These enclosures are constructed to withstand the
pressure of an internal explosion. Flame
paths cool the exploded gases to a point
less than the lowest safe operating temperature of the surrounding gas.
O-ring seals make the enclosure weatherproof but are outside of required flame paths
so explosion proof requirements are maintained.
NEMA standards: 1, 3, 4, 4X, 6, 6P, 7, 9 and
13.
UL listed: Class I, Div. 1, Groups B (14CX,
16CX, 24CX, 26CX, 36CX, and 84CX only), C
and D; and Class II, Div. 1, Groups E, F and
G. CSA certified: Class I, Div. 1, Groups B
(14CX, 16CX, 24CX, 26CX, 36CX and 84CX
only), C and D; and Class II, Groups E, F and
G.
For rapid response – off the shelf service,
all bold face listings are normally stocked
items.
Analog output: either resistive or 4-20 mA is
available.
Operating temperature range is – 25° to
+85°C (–13° to 185°F).
Limit/Enclosed
ROTARY ACTUATED SWITCHES
CX Series
ORDER GUIDE
As factory assembled, all basic switches
operate on clockwise and counterclockwise
rotation. Actuating mechanism can be field
adjusted for CW or CCW operation only. No
tools are required.
Catalog Listings
Shaft Restoring
Force To Center
Short housing
Description1
With
W/O2
Housing
Size
Basic
Switch(es)2
Electrical
Ratings
Short
Short
Standard
Standard
BZ(1)
BZ(2)
BZ(3)
BZ(4)
A
A
A
A
Short
Short
BA(1)
BA(2)
B
B
15 amp. SPDT.
11CX1
11CX2
21CX4
11CX12
21CX13
21CX14
20 amp. SPDT.
12CX1
12CX2
12CX12
Standard
BA(4)
B
Also UL listed for Class I.
Group B (hydrogen atmospheres).
10 amp. DPDT.
14CX1
24CX2
14CX11
24CX12
24CX13
Short
Standard
Standard
DT(1)
DT(2)
DT(3)
C
C
C
Actuators are not included with switch. Order them separately.
Also UL listed for
Class I, Group B
(hydrogen atmospheres).
1 amp, SPDT.
16CX2
26CX4
16CX1
16CX12
26CX14
16CX11
Short
Standard
Short
HS(2)
HS(4)
HS(1)
D
D
D
ROTARY LEVERS
Analog position sensing.*
Current output (4-20 mA).
—
—
18CX10
281CX12
284CX12
Short
Standard
Standard
None
BZ(2)
DT(2)
—
A
C
1 amp, SPDT with
gold contacts.
1172CX2
1172CX12
Short
BZ(2)
F
22CX4
Standard housing
Lever Type
Catalog
Listing
1.5 in. lever, no roller
.75 in. roller, front
.75 in. roller, back
LSZ51
LSZ51A
LSZ51C
1.5-3.5 in. adjustable lever
.75 in. roller
1.0 in. roller
1.5 in. roller
LSZ52C
LSZ52J
LSZ52K
1.5 in. yoke roller
.75 in. rollers, back
.75 in. rollers, each side
LSZ53S
LSZ53E
5 in. rod lever
Hub only
LSZ54M
LSZ54
1.5 in. offset lever, no roller
.75 in. roller, back
.75 in. roller, front
LSZ55
LSZ55A
LSZ55C
* Where noted, BZ basic switches are 15 amp, SPDT; DT basic switchs are 10 amp DPDT. Refer to next page for
analog position sensing specifications.
MOUNTING HOLES
Add the letter A to listings with side mounting holes tapped 5/16-18(8).
Example: 11CX2A
Add the letter B to listings with thru mounting holes tapped 3/8-24(4).
Example: 11CX2B.
Basic switches operate nearly simultaneously in multiple switch devices.
2
Shafts of devices without shaft restoring
force can be rotated through 360°.
1
Basic switches will be in operated mode
through two 105° sections.
Eight side mounting holes can be tapped
5/16N-18.
Rollers are nylon. Non-sparking rollers must
be used in hazardous locations.
Honeywell 1 Sensing and Control 1 1-800-537-6945 USA 1 F1-815-235-6847 International 1 1-800-737-3360 Canada
A127
Limit and Enclosed Switches
Weather-Sealed Explosion-Proof Switches
CX Series
REPLACEMENT BASIC SWITCH
ASSEMBLIES
These assemblies are factory adjusted to
the same operating characteristics as a new
CX switch. They include components subject to mechanical or electrical wear: basic
switches, cam wheels and followers, and
springs.
ELECTRICAL RATINGS
Circuitry
Electrical Ratings
A
BZ
Single-Pole
Double-throw
UL/CSA Rating: L96
15 amps, 120, 240 or 480 VAC, ind. and res.
1⁄8 Hp, 120 VAC; 1⁄4 Hp, 240 VAC.
.5 amp, 125 VDC, .25 amp, 250 VDC., res.
B
BA
Single-Pole
Double-throw
UL/CSA Rating: L23
20 amps, 120, 240 or 480 VAC, ind. and res.
1 Hp, 120 VAC; 2 Hp, 240 VAC.
.5 amp, 125 VDC, .25 amp, 250 VDC res.
C
DT
Double-pole
Double-throw
UL/CSA Rating: L59
10 amps, 120 or 240 VAC, ind. and res.
.3 amp, 125 VDC, .15 amp, 250 VDC, res.
D
HS
Single-Pole
Double-throw
UL/CSA Rating: L22
1 amp, 120 VAC, ind. and res.
F
BZ (Gold Contact)
Single-Pole
Double-throw
To order, change the first number in the
complete switch catalog listing to 9 for rotary switches and 10 for plunger switches
with short housings.
Example:
Rotary switch 12CX5
Replacement J 92CX5
Plunger switch 36CX2
Replacement J 106CX2
Note: Basic switch assemblies for rotary actuated switches, with or without shaft restoring force, will be the same.
For example:
11CX1 and 11CX11 use 91CX1.
UL/CSA Rating: L22
1 amp, 125 VAC
ANALOG POSITION SENSING SPECIFICATIONS
Current Output (4-20 mA)
Replacement PC Board
Voltage compliance range: 12.5 to 40 VDC
Maximum load resistance:
RL, Max,–V Supply - 12.5
20 mA
Current signal output: 4-20 mA
Span: Adjustable from 15° to 90° of angular
rotation.
Null: 4 mA position may be set at any angular
position.
For current output devices 15PA261-CX
OPERATING CHARACTERISTICS (All CX Switches)
Rotary Actuation
Plunger Actuation
Basic Switch Type
BZ
BA
DT
HS
Pretravel (max.)*
15°
15°
30°
30°
Differential Travel (max.)
10°
10°
25°
20°
.04 in./1.0 mm
Overtravel (min.)*
90°
90°
75°
75°
.19 in./4,75 mm
Operating Torque (max.)
Operating Force (max.)
BZ
BA
HS
.10 in./2,5 mm
11.1 in. lb./1,25 Nm
—
—
8.82 lb./39,2 N
LOW TEMPERATURE SWITCHES
Add the letter C to listings for low temperature versions.
Example: 21CX14C – 40°F (– 40°C) Rotary
36CX2C – 35°F (– 37°C) Plunger
* May be modified in field to suit application requirements.
N J Newtons
Nm J Newton meters
A128
Honeywell 1 Sensing and Control 1 1-800-537-6945 USA 1 F1-815-235-6847 International 1 1-800-737-3360 Canada
Limit and Enclosed Switches
Weather-Sealed Explosion-Proof Switches
80CX SWITCHES ALSO WITHSTAND
CORROSIVE ENVIRONMENTS
80CX switches have rugged bronze housings which are resistant to salt water and
other corrosive environments. They comply
with the NEMA 4X requirement for protection against corrosion, in addition to NEMA
enclosure standards met by other CX
switches. O-ring seals make the enclosure
weather-proof, but are outside of required
flame paths so explosion-proof requirements are maintained.
CX Series
STAINLESS STEEL LEVER ACTUATORS
These levers match the corrosion resistance of the 80CX housing. Non-sparking rollers
must be used in hazardous locations.
ORDER GUIDE STAINLESS STEEL LEVERS WITH NYLON ROLLERS
Std. Roller Lever
Radius (In.)
Width In.
Catalog Listing
1.5
.75
.25
LS2Z51A
1.5
.75
.25
LS2Z51
1.5-3.5
.75
.25
LS2Z52A
Std. Lever w/o roller
Adjustable Radius
Dia. In.
Limit/Enclosed
Note: Refer to page A36 for lever dimensions.
ROTARY ACTUATED SWITCHES
ORDER GUIDE
As factory assembled, all basic switches
operate on clockwise or counterclockwise
rotation. Actuating mechanism can be field
adjusted for CW or CCW operation only. No
tools are required.
Catalog Listings
Shaft Restoring
Force To Center
Actuators are not included with switches.
Order them separately.
MOUNTING HOLES
Add the letter A to listings with side
mounting holes tapped 5/16-18(8).
Example: 82CX2A
Add the letter B to listings with thru
mounting holes tapped 3/8-24(4).
Example: 81CX2B.
Electrical
Ratings
Page A109
With
Without2
15 amp. SPDT
81CX1
81CX2
81CX4
81CX11
81CX12
81CX14
Standard
Standard
Standard
BZ(1)
BZ(2)
BZ(4)
A
A
A
20 amp. SPDT
82CX2
82CX4
82CX12
82CX14
Standard
Standard
BA(2)
BA(4)
B
B
Also UL listed for Class I,
Group B (hydrogen
atmospheres). 10 amp. DPDT
84CX2
84CX12
Standard
DT(2)
C
Description1
80CX switches available with standard
housing only.
Basic
Switch(es)
Housing
Size
Notes: Refer to page A127.
MODIFIED SHAFT ENABLES
DIRECT COUPLING
CX switches are available with a 3⁄8 inch
diameter by 3⁄4 inch long flatted shaft which
conforms to standard NEMA motor shaft
specifications. It accepts commercially
available shaft couplers, permitting easy,
direct coupling to most equipment actuators.
MOUNTING BRACKET
An aluminum mounting bracket is available
for adapting CX switches to existing 2-hole
mounting arrangements.
To order, specify Catalog Listing 15PA148-
CX.
15PA148-CX
To specify a ‘‘direct-couple’’ CX switch, add
-DO1 to catalog listings shown in the order
guides, i.e. 11CX12-DO1. Pricing is the same
as for unmodified versions.
Flatted
Shaft
Version
Honeywell 1 Sensing and Control 1 1-800-537-6945 USA 1 F1-815-235-6847 International 1 1-800-737-3360 Canada
A129
Limit and Enclosed Switches
Weather-Sealed Explosion-Proof Switches
CX Series
MOUNTING DIMENSIONS (For reference only)
ROTARY
Short housing
PLUNGER
Standard housing
Short housing
Standard housing
THESE HOLES NOT FURNISHED ON 80CX SERIES
LSZ52
LEVER ACTUATORS
LSZ51
LSZ55
Front
mounting
Back
mounting
Front
mounting
Back
mounting
LSZ53
LSZ54
Both rollers
Front mounting
See order guides for roller dimensions.
A130