B Series 700 Watt AC-DC Converters Input range 150...264 V AC with PFC 48 V battery charger 3 kV AC I/O electric strength test voltage LGA Approvals pending • U/P/I output characteristic • High power density 300 W/dm3 • Overtemperature, overload and overvoltage protection Selection chart Output 1 Uo nom Io nom [V DC] [A] 53.5 12.6 Input voltage Ui [V AC] 150...264 Rated power Po tot [W] 680 Efficiency htyp [%] 90 Type LB 1740-6R Input Input voltage with full output power Input frequency Inrush current limitation Input harmonics Power factor Efficiency ETSI 300 132-1, at 230 V AC IEC/EN 61000-3-2 Ui nom, Io nom Ui nom, Io nom 150...264 V AC 187...264 V AC 47...63 Hz <35 A class D >0.98 >90% Output Nominal output voltage Nominal output power Current limitation Static line and load regulation Output voltage ripple and noise Psophometric ripple Minimum load Auxiliary supply Ui nom, 50% Io nom, TC = 25°C power limitation U/P/I characteristic Ui min...Ui max, Ui nom, 5...100% Io nom Ui nom, Io nom, 20 MHz bandwidth A-filter acc. CCITT not required 53.5 ±0.1 V 680 W 15.5 A typ. ±300 mV <120 mVpp <2 mVrms 0A 11.5 ±1 V, 50 mA 1 Cassette Style B Series Protection Input fuses Input transient protection Output Overtemperature not user accessible (fuses in both lines) varistor no-load, overload and short circuit proof automatic output power derating 6.3 AT TC = 90°C Control Output voltage adjustment ON/OFF switch Shut-down input Status monitoring Output voltage monitor Output current monitor Current share Status indication by remote control, Ucr = 0...10 V TTL compatible signal input OK output, module OK output UUo M = 0...10 V for Uo = 0...60 V UIo M = 0...10 V for Io = 0...20 A up to 6 units in parallel LEDs: OK, error 44...59.0 V DC ±50 W Safety and EMC Approvals in progress Protection degree Electric strength test voltage Electrostatic discharge Electromagnetic field Electr. fast transients/burst Surge Electromagnetic emissions EN 60950, UL 1950, CSA 22.2 No. 950 IP 20 class I, I/case 1.5 kV AC class I, I/O 3 kV AC class I, O/case 1 kV AC IEC/EN 61000-4-2, level 3 4/8 kV, criterion B IEC/EN 61000-4-3, level 2 3 V/m, criterion A IEC/EN 61000-4-4, level 4 4 kV, criterion B IEC/EN 61000-4-5, level 4 4 kV, criterion B CISPR 22/EN 55022, conducted and radiated class B Environmental specifications Operating temperature Storage temperature Relative humidity Shock Bump Sinusoidal vibration Random vibration Ui nom, Io nom, cooling by forced air flow ≥1 m/s non operational non condensing IEC/EN 60068-2-27, 11 ms IEC/EN 60068-2-29, 6 ms IEC/EN 60068-2-6, 8.2...58.1/58.1...500 Hz IEC/EN 60068-2-64, 10...200/200...2000 Hz –25...60°C –40...90°C ≤93% 15 gn 10 gn 1 gn/2 gn 0.01/0.003 g2/Hz 2 B Series 700 Watt AC-DC Converters Mechanical data Tolerances ±0.3 mm (0.012") unless otherwise indicated. European Projection 299 (11.77") 70.8 (2.79") 128.5 (5.06") S90050 3 Cassette Style AMP 558065 Western connector Pin 1 2 3 4 5 6 7 8 9 10 Destination Uaux G SD D AC OK Ucr UoM IoM T or Uh n.c. Description Auxiliary voltage (12 V, 50 mA) Reference ground Shut down input Module OK AC input OK Remote control input Output voltage monitor Output current monitor Current sharing or Aux. Open circuit B Series Phoenix Power-Combicon connector Pin 1 2 Designation Vi+ Vi– Accessories Temperature sensor for battery charging 4