GAMEWELL-FCI NH-12/24-R

Cooper-Wheelock NS Series
Horn Strobes & NH Series Horns
Description
The Cooper-Wheelock Series NS Horn
Strobe Appliances will satisfy virtually
all requirements for indoor, wall mount
applications.
The Series NH Horn and the horn portion of the Series NS include a selectable continuous horn tone or temporal
pattern (Code 3) with selectable dBA
settings of 90 or 95 dBA.
NS Horn Strobe
Strobe options include 15/75cd or Cooper-Wheelock’s patented Multi-Candela strobe with field selectable candela settings of 15/30/75/110cd.
These versatile Horn Strobe Appliances
may be synchronized when used in
conjunction with the Wheelock SM or
DSM Sync Modules or a Power Supply with the Cooper-Wheelock patented
Sync Protocol. Additionally, the audible
may be silenced while maintaining
strobe activation.
NH Horn
Multi-Candela Indicator
(bottom of Strobe Lens)
All models of the Series NS and NH
are designed for maximum performance, reliability and cost-effectiveness while meeting or exceeding the
latest requirements of NFPA 72/ANSI
117.1/UFC and UL Standards 1971 and
464 as well as meeting ADA requirements concerning photosensitive epilepsy.
General Notes
• Strobes are designed to flash once per second minimum over their “Regulated
Voltage Range”. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per
second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe intensity based on UL
Standard 1971.
• Series NS Strobe products are listed under UL Standard 1971 for indoor use
with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity
of 93% (± 2%).
• Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
• “Regulated Voltage Range” is the newest terminology used by UL to identify
the voltage range. Prior to this change UL used the terminology “Listed
Voltage Range”.
NS Series Horn Strobes & NH Series Horns CS-2246 09/01/06
Page 1 of 3
Features
•
Field Selectable Candela Settings
15/30/75/110cd (24 VDC MultiCandela models) or 15/75cd in 12
or 24 VDC
•
Selectable Continuous Horn or
Temporal (Code 3)
•
2 Selectable dBA settings of 90 and
95 dBA in both tones
•
12 and 24 VDC models with UL
“Regulated Voltage” using filtered
DC or unfiltered VRMS input voltage
•
•
•
•
Patented Universal Mounting Plate
•
NH horn is selectable 12 or 24 VDC
in 1 unit
•
Synchronize with Wheelock SM or
DSM Sync Module or a Power
Supply with built-in sync protocol
•
Patent pending Universal Mounting
Plate for single-gang, double-gang,
4” (10.16 cm) square, or 100 mm
European backboxes, or
Wheelock’s SHBB shallow surface
backbox.
•
Fast installation with IN/OUT screw
terminals using #12 to #18 AWG
wires
Wall Mount
ADA/NFPA/UFC/ANSI compliant
Complies with OSHA 29, Part
1910.165
Listings
Listings and approvals below apply to
the basic NS Series Strobes and NH
Series Horns. In some cases, certain
modules may not be listed by certain
approval agencies, or listing may be
in process. Consult factory for latest
listing status.
•
•
•
•
•
UL Listed: file E5946.
ULC Listed: files CS243 & CS356.
FM approved.
MEA approved: file 151-92-E.
CSFM approved: file 71250785:142
WARNING: CONTACT COOPERWHEELOCK FOR THE CURRENT INSTALLATION
INSTRUCTIONS
(P83983) SERIES NS-24MCW, (P84234)
SERIES NS-12 AND 24 VDC SINGLE
CANDELA MODELS, (P83600) SERIES
NH AND “GENERAL INFORMATION”
SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS UNDERGO
PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS.
THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE
READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING:
Engineer’s Specifications
The audible/visual notification appliances shall be Cooper-Wheelock Series NS Horn Strobe
appliances and Series NH Horn appliances or approved equals. The Series NS appliances shall
meet and be listed for UL Standard 1971(Emergency Devices for the Hearing-Impaired for Indoor
Fire Protection Service). The Series NH Horn shall be UL Listed under Standard 464 (Fire
Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity
supervision of circuit wiring by the Fire Alarm Control Panel (FACP).
The audible portion of the appliance shall have a minimum of two (2) field selectable settings for
dBA levels (90 and 95 dBA) and shall have a choice of continuous or temporal (Code 3) audible
outputs.
The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over
the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged
Lexan lens. The Series NS shall be of low current design. Where wall mount, Multi-Candela
appliances are specified, the strobe intensity shall have field selectable settings and shall be
rated per UL Standard 1971 for 15/30/75/110 candela. The selector switch for selecting the
candela setting shall be tamper resistant. The 15/75 candela strobe shall be specified when 15
candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADA compliance).
•
TOTAL CURRENT REQUIRED BY ALL
APPLIANCES CONNECTED TO SYSTEM
SECONDARY POWER SOURCES.
•
FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK
CURRENTS FROM ALL APPLIANCES
ON THOSE CIRCUITS.
•
COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON’S
FIELD OF VIEW.
The Series NS Horn Strobes and NH horn shall incorporate a Patented Universal Mounting Plate
that shall allow mounting to a single-gang, double-gang, 4-inch square, 100mm European type
backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate)
shall be provided.
•
ADDING, REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA
SETTINGS WILL AFFECT CURRENT
DRAW.
All notification appliances shall be backward compatible.
•
RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE
CURRENT AND TOTAL PEAK REQUIRED
BY ALL APPLIANCES DO NOT EXCEED
THE RATED CAPACITY OF THE POWER
SOURCES OR FUSES.
•
THE VOLTAGE APPLIED TO THESE
PRODUCTS MUST BE WITHIN THEIR
“REGULATED VOLTAGE RANGE”.
•
INSTALLATION OF 110 CANDELA
STROBE PRODUCTS IN SLEEPING AREAS.
•
INSTALLATION IN OFFICE AREAS AND
OTHER SPECIFICATION AND INSTALLATION ISSUES.
•
THESE APPLIANCES ARE NOT DESIGNED TO BE USED ON CODED SYSTEMS IN WHICH THE APPLIED VOLTAGE
IS CYCLED ON AND OFF.
•
FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL
INFORMATION SHEETS COULD RESULT
IN IMPROPER INSTALLATION, APPLICATION, AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY
OR DEATH TO YOU AND/OR OTHERS.
•
CONDUCTOR SIZE (AWG), LENGTH
AND AMPACITY SHOULD BE TAKEN
INTO CONSIDERATION PRIOR TO DESIGN
AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS.
When synchronization is required, the appliance shall be compatible with Cooper- Wheelock’s
SM, DSM Sync Modules or a Power Supply with Cooper-Wheelock’s built-in Patented Sync
Protocol. The strobes shall not drift out of synchronization at any time during operation. If the
sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall
revert to a non-synchronized flash-rate. The appliance shall also be designed so that the
audible signal may be silenced while maintaining strobe activation.
Wiring Diagram
TO NEXT
+
- APPLIANCE
OR EOLR
FROM
+
PRECEDING APPLIANCE, SM/DSM,
PS-12/24-8MP OR
FACP
-
+
NS AND NH APPLIANCES SYNCHRONIZED
WITH SM MODULE SINGLE CLASS “B”
NAC CIRCUIT WITH AUDIBLE SILENCE
FEATURE
SM
+ STROBE
F
A
C
P
- STROBE
Strobe
NAC
Circuit
NS/NH
APPLIANCE
NS
NH
+Audible
EOLR
- Audible
Audible
NAC
Circuit
NS AND NH APPLIANCES SYNCHRONIZED
WITH DSM MODULE DUAL CLASS “A”
NAC CIRCUIT WITH NO AUDIBLE SILENCE
FEATURE
DUAL SYNC MODULE
SYNC +
SYNC -
+
-
+
OUT1
+
IN1
MINUS1
F
+ AUDIBLE
A
SIGNAL
CIRCUIT OUT
C
P
+
-
-
AUDIBLE
+
OUT2
+
IN2
+
-
APPLIANCE
+
-
APPLIANCE
MINUS2
SIGNAL
CIRCUIT RETURN
NOTE: NS/NH must be set on Code 3 horn to achieve synchronized temporal (Code 3) tone.
Refer to instruction (P38983, P83600 respectively).
Page 2 of 3
NS Series Horn Strobes & NH Series Horns
CS-2246
09/01/06
Specification & Ordering Information
SYNC
24
12
2
NONW/SM,
VDC VDC WIRE
SYNC
DSM
STROBE
CANDELA
MODEL
NS-24MCW-FR
NS-24MCW-FW
NS-241575W-FR
NS-121575W-FR
NH-12/24-R
AGENCY APPROVALS
MOUNTING
OPTIONS***
UL MEA CSFM FM BFP
15/30/75/110
X
X
X
-
X
B,D,E,F,G,H,J,N,O,R,X
X
X
X
X
X
15/30/75/110
15 (75 on axis)
15 (75 on axis)
12V
24V
X
X
X
X
X
X
X
X
-
X
X
X
X
B,D,E,F,G,H,J,N,O,R,X
B,D,E,F,G,H,J,N,O,R,X
B,D,E,F,G,H,J,N,O,R,X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
B,D,E,F,G,H,J,N,O,R,X
X
X
X
X
X
T ab le 4: *A ve r ag e M e an C u rr e nt Ratin gs NH Hor n 24 V olt M o de ls
Table 1: Ratings Per UL Standard 1971
Re gulate d
Input
Voltage
Voltage
Range
Model
VDC
VDC/FWR
V oltage
Strobe
Candela (CD)
High (95) dBA
Low (90) dBA
16.0 V DC
.019
.017
24.0 V DC
.028
.022
.039
.027
NS-24MCW
24
16.0 - 33.0 15/30/75/110
33.0 V DC
NS-241575W
24
16.0 - 33.0 15 (75 on Axis)
NS-121575W
12
8.0 - 17.5
*Average RMS Current is per UL average RMS method and Average Mean
Current is per UL average mean method. NH models use average mean current.
For rated In Rush and Peak current across the UL listed voltage range for both
filtered DC and unfiltered VRMS (FWR), see installation instructions.
*** Refer to mounting options.
15 (75 on Axi)
Table 2: *Average RMS Current Ratings
NS-24MCW with High (95 dBA) Setting
Voltage
16.0 VDC
24.0 VDC
33.0 VDC
15cd
.077
.065
.069
30cd
.113
.087
.082
Table 5: dBA Ratings for Series NS/NH Horn
75cd
.195
.134
.117
110cd
.268
.174
.134
75cd
.188
.126
.097
110cd
.261
.158
.114
Description Volume
Reverberant dBA @
10 ft. per UL 464
Anechoic dBA @
10 ft.
12 VDC
24 VDC
12 VDC
24 VDC
83
76
79
72
87
81
82
76
89
84
89
84
95
90
95
90
NS-24MCW with Low (90 dBA) Setting
Voltage
16.0 VDC
24.0 VDC
33.0 VDC
15cd
.070
.052
.045
30cd
.106
.072
.060
SYNC MODELS/POWER SUPPLY
Table 3: *Average RMS Current Ratings
NS-241575W
Voltage
High
Low
High
Low
Continous
Horn
Code 3
Horn
M ODEL
NUM BER
INP UT
VOLTAGE
(VDC)
AVER AGE
M EAN
CURRENT
@ 24 VDC
M OUNTING
OP TIONS
High (95) dBA
Low (90) dBA
16.0 VDC
.120
.116
SM-12/24-R
24
.028
W
24.0 VDC
.094
.093
DSM-12/24-R
24
.035
W
33.0 VDC
.102
.078
NOTES:
SM Sync Module is rated for 3.0
amperes @ 24 VDC;
DSM Sync Module is rated for 3.0
amperes per circuit. The
maximum number of interconnected DSM Modules is twenty
(20).
NS-121575W
High (95) dBA
Low (90) dBA
8.0 VDC
Voltage
.341
.324
12.0 VDC
.251
.265
17.5 VDC
.216
.188
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation. For
more information, contact Gamewell-FCI.
NS Series Horn Strobes & NH Series Horns
CS-2246
09/01/06
Page 3 of 3
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI