ETC DI3-72AV5AD0XX

Panel Meters and Controllers
AC Ammeter or Voltmeter
Type DI3-72 AV1/AV5
• 3-dgt µP-based indicator for
AC currents or voltages
• Selectable CT/VT primary range
• Panel mounting
• 72 x 72 mm
• Degree of protection (front): IP 50 (IP 65 on request)
Product Description
Ordering Key
3-dgt µP-based meter with
double input for AC currents
or voltages. With 20 selectable
primary CT/VT ranges. The
Model
Range code
Measurement
Power supply
Setpoints
Options
housing is for panel mounting
and ensures a degree of
protection (front) of IP 50 (IP
65 on request).
DI3-72AV5AD0XX
Type Selection
Range code
AV1:
AV5:
Power supply
1 A/100 V
Standard current/voltage
5 A/500 V
Standard current/voltage
See Range Table
A:
B:
XX:
EX:
None (standard)
Degree of protection
IP 65
1)
C:
1)
Input Specifications
1)
Power supply on request
General Specifications
Rated input
Operating temperature
5A/500 VAC, 45 to 400 Hz
(1A/100 VAC on request)
Sampling rate
Indication
Max.
Min.
500 VAC range
Other ranges
Over range
Input range selection
Decimal point position
24 VAC, -15% +10%,
50/60 Hz
48 VAC, -15% +10%,
50/60 Hz
115 VAC, -15% +10%,
50/60 Hz
230 VAC, -15% +10%,
50/60 Hz (standard)
1)
D:
Overload protection
Cont. Current:
Voltage:
For 1 s Current:
Voltage:
Accuracy
(@ 25°C ± 5°C, R.H. ≤ 60%)
Temperature drift
Display
Options
1.2 x rated input
1.2 x rated input
5 x rated input
2 x rated input
± 0.5% f.s., ± 1 dgt
± 350 ppm/ºC
7-segment LED, h 14.2 mm,
3 digits
1 time/s
999
000
Scalesuppressionupto 5% f.s.
Scalesuppressionupto 3% f.s.
EEE
DIP-switch selectable
DIP-switch selectable
Specifications are subject to change without notice
Storage temperature
Insulation reference voltage
Dielectric strength
Noise rejection
CMRR
EMC
Safety standards
Connector
Housing
Dimensions
Material
Degree of protection
Weight
Approvals
0° to 50°C (32° to 122°F)
(R.H. < 90% non-condensing)
-10° to 60°C (14° to 140°F)
(R.H. < 90% non-condensing)
300 V to ground
4000 V for 1 minute
rms
rms
100 dB, 40 to 60 Hz.
IEC 60801-2, IEC 60801-3,
IEC 60801-4 (level 2),
EN 50 081-1, EN 50 082-1.
EN 61 010-1, IEC 61010-1,
VDE 0411
Screw-type
72 x 72 x 75 mm
ABS,
self-extinguishing: UL 94 V-0
Front: IP 50 (IP 65 on request)
Approx 250 g
CE, CSA
1
DI3-72 AV1/AV5
Supply Specifications
AC supply
Front Panel Description
230 VAC, -15% +10%,
50/60 Hz (standard)
24 VAC, 48 VAC, 115 VAC,
-15% +10%, 50/60 Hz
(on request)
3.2 VA
Power consumption
1
V
A
1. Display
3-dgt (maximum read-out 999).
Alphanumeric indication by means of 7-segment display
for:
- Displaying of the measured value, over-range.
Range Table
Range
Connection
1A/100 V
5A/500 V
10 A
15 A
25 A
40 A
50 A
60 A
100 A
150 A
220 V
250 A
380 V
400 A
500 A/V
500 A
600 A/V
600 A
1000 A/V
1000 A
Direct 1A
Direct 5A
CT10/1 A
CT15/1 A
CT25/1 A
CT40/1 A
CT50/1 A
CT60/1 A
CT100/1 A
CT150/1 A
CT10/5 A
CT15/5 A
CT25/5 A
CT40/5 A
CT50/5 A
CT60/5 A
CT100/5 A
CT150/5 A
CT250/1 A
CT250/5 A
CT400/1 A
CT500/1 A
CT500/5 A
CT600/1 A
CT600/5 A
CT1000/1 A
CT1000/5 A
CT400/5 A
Direct 100 V
Direct 500 V
VT220/100 V
VT380/100 V
VT500/100 V
VT600/100 V
VT1000/100 V
Decimal point Resolution
position
Voltage drop Input imp. Range code
ammeters
voltmeters
999/99.9
9.99/999
9.99
99.9
99.9
99.9
99.9
99.9
99.9
999
999
999
999
999
999
999
999
999
999
999
1V
250 mV
1 V/250 mV
1 V/250 mV
1 V/250 mV
1 V/250 mV
1 V/250 mV
1 V/250 mV
1 V/250 mV
1 V/250 mV
1 mA/0.1 V
10 mA/1 V
10 mA
100 mA
100 mA
100 mA
100 mA
100 mA
100 mA
1A
1V
1A
1V
1A
1 A/V
1A
1 A/V
1A
1 A/V
1A
1 MΩ
1 MΩ
1 MΩ
1 V/250 mV
1 MΩ
1 V/250 mV
1V
250 mV
1V
250 mV
1V
250 mV
1 MΩ
1 MΩ
1 MΩ
AV1
AV5
AV1/AV5
AV1/AV5
AV1/AV5
AV1/AV5
AV1/AV5
AV1/AV5
AV1/AV5
AV1/AV5
AV1
AV1/AV5
AV1
AV1/AV5
AV1
AV5
AV1
AV5
AV1
AV5
2
68 x 68
66.5 x 66.5
Dimensions (mm)
Specifications are subject to change without notice
DI3-72 AV1/AV5
Wiring Diagrams
NC
IN-
IN+
A
Power supply
Specifications are subject to change without notice
NC
IN-
Power supply
IN+
A
Voltage measurements - V.T.
NC
NC
IN-
IN+
A
NC
IN+
V
Current measurements - C.T.
NC
Power supply
IN+
V
Voltage measurements - direct
IN+
V
NC
IN-
IN+
A
NC
IN+
V
Current measurements - direct
Power supply
3