ETC PWA01CM235A

Monitoring Relays
3-Phase Load Guard
Types DWA01, PWA01
DWA01
• Cos ϕ monitoring relays
• Measuring if power factor is within set limits
• Measure on own power supply (voltage) and current
for balanced systems
• Measuring ranges for current: 5A and MI current
transformers range
• Power ON delay 1, 2 or 6 s selectable
• Knob adjustable level on absolute scale
• Output: 8 A SPDT relay Normally Energized
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DWA01) or plug-in module (PWA01)
• 22.5 mm Euronorm housing (DWA01) or 36 mm
plug-in module (PWA01)
• LED indication for power supply and output ON
PWA01
Product Description
Ordering key
DWA01 and PWA01 are precise over or under cos ϕ
monitoring relays.
The relays monitor their own
power supply voltage and
the current of a balanced 3phase system.
Housing
Function
Type
Item number
Output
Power Supply
Range
For current measure direct
connection, 5A standard current transformers and MI CT
can be used.
The LED's indicate the state
of the alarm and the output
relay.
DWA 01 C M48 5A
Type Selection
Mounting
Output
Supply: 208 to 240 VAC
Supply: 380 to 415 VAC
DIN-rail
Plug-in
SPDT
SPDT
DWA 01 C M23 5A
PWA 01 C M23 5A
PWA 01 C M48 5A
Supply: 380 to 480 VAC
DWA 01 C M48 5A
Input Specifications
Input
Voltage (Own power supply):
3 - phase
DWA01:
PWA01:
M23:
DWA01CM48:
PWA01CM48:
1- phase DWA01CM235A:
PWA01CM235A:
Current
DWA01:
PWA01:
L1, L2, L3
5, 6, 7
208 to 240 VAC ± 15%
380 to 480 VAC ± 15%
380 to 415 VAC ± 15%
L1, L3
5, 7
208 to 240 VAC ± 15%
5A: Y1, Y2
MI CT: Y1, Y3
5A: 7, 5
MI CT: 7, 6
Measuring ranges
Power factor (cos ϕ)
Level
0.1 to 0.99
Direct input
AACrms
0.5 to 5 A
Max. curr.
30A 30s
Standard CT (examples)
TADK 2 50 A/5 A
TAD 2 150 A/5 A
TAD 6 400 A/5 A
TAD 12 1000 A/5 A
TACO 200 6000 A/5 A
MI CT ranges
MI 100
MI 500
5 to 50 A
15 to 150 A
40 to 400 A
100 to 1000 A
600 to 6000 A
AAC rms
10 to 100 A
50 to 500 A
60 A
180 A
480 A
1200 A
7200 A
Max. curr.
250 AAC
750 AAC
Specifications are subject to change without notice (09.12.05)
Note:
The input voltage cannot
raise over 300 VAC with
respect to ground (PWA01
only).
Hysteresis
~ cos ϕ = 0,02 - fixed
Output Specifications
Output
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
SPDT relay
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
Dielectric voltage
≥ 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
1
DWA01, PWA01
Supply Specifications
General Specifications
Power supply
Rated operational voltage
through terminals:
DWA01:
PWA01:
M23
DWA01CM48
PWA01CM48
Overvoltage cat. III
(IEC 60664, IEC 60038)
Power ON delay
Reaction time
Dielectric voltage
supply to output
Rated operational power
Supplied by
None
2kV
13 VA @400VAC
L1 and L3
L1, L2, L3
5, 6, 7
177 to 276 VAC 45 to 65 Hz
323 to 552 VAC 45 to 65 Hz
323 to 477 VAC 45 to 65 Hz
Function/Delay/Level Settings
Level setting (cos ϕ):
Knob adjustable on absolute
scale, from 0.1 to 0.99
Setting of function and
power ON delay
Adjust the desired function
(over or underload monitoring) with DIP switch 1 and
the power ON delay with
DIP Switches 3 and 4 as
shown on the below table.
To access the DIP-switch
open the plastic cover using
a screwdriver as shown on
the left.
Monitoring function
ON: Under cos ϕ
OFF: Over cos ϕ
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Repeatability
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
@ Max. voltage, 50 Hz
@ Max. voltage, 60 Hz
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
Approvals
CE-Marking
EMC
Immunity
Emission
1, 2, or 6 s ± 0.5 s
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 400 ms
< 400 ms
(15 min warm-up time)
± 1000 ppm/°C
± 0.5% on full-scale
LED, green
LED, yellow
IP 20
3 (DWA01), 2 (PWA01)
-20 to 60°C, R.H. < 95%
-20 to 50°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 94 mm
Approx. 200 g
Max. 0.5 Nm
acc. to IEC 60947
UL, CSA
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 61000-6-3
Not used
Power ON delay
SW3 SW4
OFF OFF: 6 sec
ON OFF: 2 sec
ON ON: 1 sec
Mode of Operation
DWA01 and PWA01 can be
used for monitoring the
actual load of asynchronous
motors.
The relays measure the 3phase supply voltage and
the current of the phase L1
connected to an asynchronous motor.
The relay monitor the cosine
of the angle between motor
current and motor voltage
(cos ϕ).
As cos ϕ varies with the load
of the motor, overload (or
2
underload) can be indirectly
detected by DWA01 and
PWA01.
The relation between the
load and cos ϕ depends on
the type of motor.
As a guideline to ensure correct working conditions for a
motor, the level could be set
above (or below) the cos ϕ
marking on the motor. It is
however recommended to
make the adjustment in connection with a practical test.
The relay has an inhibit
delay at power ON in order
to avoid overload detection
during motor start.
Example 1:
Overload monitoring.
The relay operates and the
yellow LED is ON as long as
cos ϕ is below the set limit.
The relay releases when it
exceeds the set level.
Example 2:
Underload monitoring.
The relay operates and the
yellow LED is ON as long as
cos ϕ is above the set limit.
The relay releases when it
drops below the set level.
Example 3:
DWA01CM235A
and
PWA01CM235A can be used
for monitoring the cos ϕ of a
1-Phase load with 208 to 240
V AC mains voltgage. In this
case the power supply has to
be connected between L1, L3
(or 5, 7) and L2 and L3 (or 6
and 7) have to be connected.
Specifications are subject to change without notice (09.12.05)
DWA01, PWA01
Wiring Diagrams
DWA01 - Direct connection
PWA01 - Direct connection
L3
L2
L1
L3
L2
L1
IL1
IL1
m
I2
U1
U2
L1 L2 L3
m
12
14
10
cos
cos ϕ
j
11
6
5
9
4
7
3
ϕ
cos
cos j
8
11
DWA01 - Standard CT
1
PWA01 - Standard CT
L3
L2
L1
L3
L2
L1
m
I2
U1
L1 L2 L3
m
12
14
10 9
cos ϕ
j
cos
11
U2
5
6
4
7
3
ϕ
cos j
cos
8
11
DWA01 - MI CT
1
PWA01 - MI CT
L3
L2
L1
L3
L2
L1
m
I2
L1 L2 L3
12
m
10 9
14
cos
cos ϕ
j
Grey
Grey
U2
11
DWA01CM235A - Direct connection - 1-Phase Load
5
6
7
4
3
cos
cos ϕ
j
11
8
1
PWA01CM235A - Direct connection - 1-Phase Load
L
L
N
N
I
I
m
m
I2
L1 L2 L3
12
14
10 9
5
6
7
4
3
11 cos j
cos ϕ
8
U1 cos j
cos ϕ
U2
11
Specifications are subject to change without notice (09.12.05)
1
3
DWA01, PWA01
Operation Diagrams
Overload monitoring
Power supply
Level
Hysteresis
cos ϕj
cos
6s
Relay ON
Underload monitoring
Power supply
Hysteresis
Level
cos ϕ
j
cos
6s
Relay ON
Dimensions
DIN-rail
Plug-in
94
80
63
28.5
4
90
36
63
99.5
83.5
80
22.5
28.5
Specifications are subject to change without notice (09.12.05)