1041 SERIES Operating Voltage = 250/480 Vac Operating Current Max= 80 & 100 amps Operating Frequency = 50 - 60Hz Operating Temperature = -40 to +50oC Diel Withstand ( L to Case)= 1500V~for 1 Min. Diel Withstand ( L to L )= 1500Vdc for 1 Min. Leakage current @ 250V~60Hz= 2.3 mA at 250Vac, 50Hz Max Residual Voltage after 5 secs =35 Volts Max The 1041 series is designed to provide attenuation to switching regulator noise etc. At the power input to large computers and memory systems. These filters are also useful at the input to shelters, motor banks, facility power inputs or any installation requiring good common-mode and differential filtering. This series can be used on either Wye or Delta power systems. JMK P/N Ordering Information 80 Amps 1/4-20 Threaded Studs Terminals MM-1041-80 100 Amps 1/4-20 Threaded Studs Terminals MM-1041-100 USA JMK Inc 15 Caldwell Dr. Amherst, NH 03031 EUR JMK Inc Glasgow G13 1DN Scotland UK PH: 603 886-4100 FX: 603 886-4115 email: [email protected] PH: 44-(0) 7785310729 Fax: 44-(0) 141 589 1884