NI NICFP-180X

Ethernet/Serial Interfaces for Compact FieldPoint
NI cFP-180x
• Distributed I/O interfaces for Ethernet
and RS232 networks
• 4 or 8-slot Compact FieldPoint distributed
Ethernet/serial network interfaces
• FieldPoint software for rapid distributed
I/O access
• Modbus Support
• OPC server included
• Intelligent diagnostics and maintenance
• Industrial specifications for
harsh environments
• 50 g shock
• 5 g vibration
• -40 to 70 °C
Operating Systems
• Windows 2000/XP
Recommended Software
• LabVIEW
• LabVIEW Datalogging and Supervisory
Control Module
Other Compatible Software
•
•
•
•
LabWindows/CVI
Measurement Studio
Lookout
VI Logger
Driver Software (included)
• Measurement & Automation Explorer
• OPC server (2.0 compliant)
Overview and Distributed Applications
Hardware Architecture
National Instruments cFP-180x interfaces connect four or eight
Compact FieldPoint I/O modules to a high-speed Ethernet network or to
an RS232 serial port. With up to 100 Mb/s data communication rates and
event-driven communications, an NI cFP-180x delivers a high-performance
network connection for Compact FieldPoint that is easy to interface with
a PC or PAC-like Compact FieldPoint embedded controller. One or more
cFP-180x interfaces, connected by standard networking equipment, provide
expanded I/O that you can control with a single Compact FieldPoint
controller, see Figure 1. You can also build a PC-based distributed I/O and
control system by connecting two or more cFP-180x devices to your PC.
A cFP-180x provides an integrated network interface (Ethernet or serial)
and a 4 or 8-slot backplane, and it works with the same modules and
connector blocks used in other Compact FieldPoint systems.
127 mm
(5.00 in.)
441 mm
(17.36 in.)
Figure 2. cFP-1808 Mechanical Dimensions
Compact FieldPoint
Real-Time Controller
127.0 mm
(5.00 in.)
Ethernet
245.9 mm (9.68 in.)
Figure 3. cFP-1804 Mechanical Dimensions
NI cFP-1808 Distributed
Network Interfaces
Figure 1. Expansion I/O for Compact FieldPoint Embedded Controller with cFP-1808
Network Interfaces
Building Ethernet-Based
Distributed I/O Systems
A cFP-180x can communicate with Compact FieldPoint real-time
embedded controllers; any Ethernet-based programmable automation
controller (PAC); and a Windows computer running LabVIEW,
LabWindows/CVI, Measurement Studio, Lookout, or your choice of OPC
client application software. Using a cFP-180x, you can rapidly build
flexible, modular distributed measurement and automation systems.
Ethernet/Serial Interfaces for Compact FieldPoint
Enterprise Level
Configuring and Accessing Tags on a
Compact FieldPoint System with LabVIEW 8
HMIs and
Touch Panels
National Instruments LabVIEW 8 and Compact FieldPoint create a
flexible PAC system that offers easy-to-access I/O through the FieldPoint
programming environment. Accessing data from multiple cFP-180x
distributed nodes with LabVIEW is as easy as three simple steps:
1. Configure IP address using NI Measurement & Automation Explorer (MAX)
2. Import a FieldPoint configuration file or add a new
Compact FieldPoint system
3. Expand I/O in the LabVIEW Project and drag and drop I/O tags to VIs
After configuring the IP address for a FieldPoint bank in MAX, either
import the configuration file created from MAX, or simply add a new
target to a LabVIEW Project as shown in Figure 5.
Programmable
Automation
Controllers
Compact FieldPoint
Real-Time Controller
Distributed Compact FieldPoint
Network Interface
Figure 4. Ethernet-based distributed systems work with Compact FieldPoint embedded
controllers, PACs, human-machine interfaces, and Enterprise/SCADA systems.
Network Communications Interface
A cFP-180x connects directly to Ethernet networks, autonegotiating on
the network for 10 Mb/s or 100 Mb/s communication rates. It includes
an RJ-45 connector for connection to 10BaseT and 100BaseTX networks,
using a protocol based on standard TCP/IP to maintain full compatibility
with existing networks. FieldPoint builds on standard TCP/IP network
protocols and adds a number of key enhancements, including eventdriven communications and publisher-subscriber networking. In a
publisher-subscriber architecture, one or more client PCs subscribe to
I/O data from Compact FieldPoint banks. The network interface monitors
connected I/O modules and publishes I/O data only when the value
changes. Analog signals can change value within selectable ranges,
called deadbands, without causing the system to report data. This
event-driven method, along with data compression, helps you avoid
unnecessary Ethernet traffic and maximizes communication efficiency.
A cFP-180x also includes a standard DB-9 connector for RS232 serial
communication. Through direct connectivity, you can read and write
data directly from a program running on your PC or embedded controller.
You access I/O through the serial interface using a serial protocol called
Optomux, in the same way you would access data through classic
FieldPoint network interfaces such as the FP-1000.
Figure 5. Add a new FieldPoint target to your LabVIEW 8 Project.
After adding all FieldPoint networks available on the network, you can
expand each FieldPoint bank and see the I/O modules and tags available
from the LabVIEW Project Explorer. Using these tags in an application is
as easy as dragging the tag from the Project Explorer to the VI where the
data is needed. LabVIEW automatically creates the correct FieldPoint
read/write VI and associated tag.
BUY ONLINE at ni.com or CALL (800) 813 3693 (U.S.)
2
Ethernet/Serial Interfaces for Compact FieldPoint
After you create a shared variable, it appears in LabVIEW Project
Manager and is available for use in your LabVIEW applications simply
by dragging the variable from the Project Explorer to an existing VI
(see Figure 8). From a PC, PAC, or embedded Compact FieldPoint controller,
you can use MAX with LabVIEW 8 to configure I/O settings for the
cFP-180x to access data on distributed Compact FieldPoint banks.
Accessing distributed I/O is now easier than ever with LabVIEW 8
and a cFP-180x.
Figure 6. Drag and drop an I/O tag from a LabVIEW Project to any VI.
Accessing Network I/O Data
on a cFP-180x Using Shared Variables
You can create a shared variable for any tag that is available on a
cFP-180x bank connected to the network. You then can use this shared
variable in multiple LabVIEW applications either targeted to Windows OS
or running embedded on a Compact FieldPoint real-time controller such as
the NI cFP-2120. To create a shared variable to be hosted on a Windows
system, simply right-click on My Computer in the LabVIEW Project and
select New Variable; select the option to bind this shared variable to a
source, and then you can either select IO from your local LabVIEW Project
or any I/O available on the network, as shown in Figure 7.
Figure 7. Compact FieldPoint distributed I/O channels are accessible as network items
from LabVIEW.
Figure 8. Use a shared variable to access distributed I/O for all channels.
Ordering Information
NI cFP-1808 ...........................................................................779463-01
NI cFP-1804 ...........................................................................779490-01
PS-5 (power supply 24 VDC, 5 A, universal power input) ......778805-90
BUY NOW!
For complete product specifications, pricing, and accessory
information, call (800) 813 3693 (U.S.) or go to ni.com/fieldpoint.
BUY ONLINE at ni.com or CALL (800) 813 3693 (U.S.)
3
Ethernet/Serial Interfaces for Compact FieldPoint
Shock and Vibration
Specifications
Network
Network interface...............................
Compatibility .......................................
Communication rates..........................
Maximum cabling distance.................
Maximum power to I/O modules........
Maximum number of banks ................
10BaseT and 100BaseTX Ethernet
IEEE802.3
10 or 100 Mb/s, autonegotiated
100 m/segment
9W
Determined by network topology
Serial Port
One RS232 (DCE) serial port
Baud rate ........................................
Data bits .........................................
Stop bits..........................................
Parity...............................................
Flow control ....................................
300 to 115,200 b/s
8
1
None
None
Power Requirement
Power supply range ............................ 11 to 30 VDC
Recommended power supply.............. 20 W
Power consumption ............................ 6.1 W + 1.1 (I/O module)
Safety Isolation Voltage
Isolation voltage is verified by a dielectric withstand test between
module and backplane.
Continuous .......................................... 250 Vrms,
Measurement Category II
Withstand............................................ 2,300 Vrms, 5 s max
Physical Characteristics
Screw-terminal wiring ........................ 14 to 22 AWG copper wire with
7 mm (0.28 in.) of insulation
stripped from the end
Torque for screw terminals................. 0.5 to 0.6 N • m
(4.4 to 5.3 lb • in.)
Weight
cFP-1804 ......................................... 935 g (2 lb 1 oz)
cFP-1808 ......................................... 1,595 g (3 lb 8 oz)
Operating vibration
Random (IEC 60068-2-64) ............... 10 to 500 Hz, 5 grms
Sinusoidal (IEC 60068-2-6) ............. 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27) ............................. 50 g, 3 ms half sine, 18 shocks at
6 orientations; 30 g, 11 ms half
sine, 18 shocks at 6 orientations
Safety
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement, control,
and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 61010-1
• CAN/CSA-C22.2 No. 61010-1
Note: For UL, hazardous location, and other safety certifications, refer to the product label or
visit ni.com/certification, search by model number or product line, and click the appropriate
link in the Certification column.
Electromagnetic Compatibility
Emissions ............................................ EN 55011 Class A at 10 m
FCC Part 15A above 1 GHz
Immunity.............................................. EN 61326:1997 + A2:2002, Table 1
CE, C-Tick, and FCC Part 15
(Class A) Compliant
Note: For EMC compliance, operate this device with shielded cabling.
CE Compliance
This product meets the essential requirements of applicable European
directives, as amended for CE marking, as follows:
Low-voltage directive (safety) ............ 73/23/EEC
Electromagnetic compatibility
directive (EMC).................................... 89/336/EEC
Note: Refer to the Declaration of Conformity (DoC) for this product for any additional regulatory
compliance information. To obtain the DoC for this product, visit ni.com/certification, search
by model number or product line, and click the appropriate link in the Certification column.
Environmental
FieldPoint modules are intended for indoor use only. For outdoor use,
they must be installed in a suitable sealed enclosure.
Operating temperature .......................
Storage temperature...........................
Relative humidity ................................
Maximum altitude...............................
-40 to 70 °C
-55 to 85 °C
10 to 90%, noncondensing
2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered
Pollution Degree ................................. 2
BUY ONLINE at ni.com or CALL (800) 813 3693 (U.S.)
4
NI Services and Support
SERVICE
NEEDS
NI has the services and support to meet
your needs around the globe and through
the application life cycle – from planning
and development through deployment
and ongoing maintenance. We offer
services and service levels to meet
customer requirements in research,
design, validation, and manufacturing.
Visit ni.com/services.
Training and Certification
NI training is the fastest, most certain route to productivity with our
products. NI training can shorten your learning curve, save development
time, and reduce maintenance costs over the application life cycle. We
schedule instructor-led courses in cities worldwide, or we can hold a
course at your facility. We also offer a professional certification program
that identifies individuals who have high levels of skill and knowledge on
using NI products. Visit ni.com/training.
Professional Services
Our Professional Services Team is comprised of NI applications engineers,
NI Consulting Services, and a worldwide National Instruments Alliance
Partner program of more than 600 independent consultants and
integrators. Services range from
start-up assistance to turnkey
system integration.
Visit ni.com/alliance.
OEM Support
We offer design-in consulting and product integration assistance if you
want to use our products for OEM applications. For information about
special pricing and services for OEM customers, visit ni.com/oem.
ni.com • (800) 813 3693
National Instruments • [email protected]
Local Sales and Technical Support
In offices worldwide, our staff is local to the country, giving you access
to engineers who speak your language. NI delivers industry-leading
technical support through online knowledge bases, our applications
engineers, and access to 14,000 measurement and automation
professionals within NI Developer Exchange forums. Find immediate
answers to your questions at ni.com/support.
We also offer service programs that provide automatic upgrades to
your application development environment and higher levels of technical
support. Visit ni.com/ssp.
Hardware Services
NI Factory Installation Services
NI Factory Installation Services (FIS) is the fastest and easiest way to
use your PXI or PXI/SCXI combination systems right out of the box.
Trained NI technicians install the software and hardware and configure
the system to your specifications. NI extends the standard warranty by
one year on hardware components (controllers, chassis, modules)
purchased with FIS. To use FIS, simply configure your system online with
ni.com/pxiadvisor.
Calibration Services
NI recognizes the need to maintain properly calibrated devices for
high-accuracy measurements. We provide manual calibration
procedures, services to recalibrate your products, and automated
calibration software specifically designed for use by metrology
laboratories. Visit ni.com/calibration.
Repair and Extended Warranty
NI provides complete repair services for our products. Express repair
and advance replacement services are also available. We offer
extended warranties to help you meet project life-cycle requirements.
Visit ni.com/services.
*342572A-01*
342572A-01
2006-6507-161-101-D
© 2006 National Instruments Corporation. All rights reserved. CVI, FieldPoint, LabVIEW, Lookout, Measurement Studio, National Instruments, National Instruments Alliance Partner,
NI, ni.com, and SCXI are trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies.
A National Instruments Alliance Partner is a business entity independent from NI and has no agency, partnership, or joint-venture relationship with NI.