NI NICFP-DI-330

Digital Input Modules for Compact FieldPoint
NI cFP-DI-300, NI cFP-DI-301,
NI cFP-DI-304, NI cFP-DI-330
• 8-,16-, or 32-channel inputs
• 24 VDC inputs
• 4 to 250 VDC inputs
• 15 to 250 VAC inputs (50/60 Hz AC)
• 3 to 250 VAC inputs (1 kHz AC)
• 2,300 Vrms bank isolation for transient
overvoltage protection
• Hot-swappable with autoconfiguration
• -40 to 70 °C operating range
Module
Input Channels
cFP-DI-300
cFP-DI-301
cFP-DI-304
cFP-DI-330
Input Ranges
Input Type
Compatibility Examples
Separate Ground
Plane per Channel
All Channel
Update Rate1
Additional
Features
8
16
32
8
18 to 30 VDC
Sinking
24 VDC sourcing devices
–
1 kHz
–
18 to 30 VDC
Sinking
24 VDC sourcing devices
–
1 kHz
–
10 to 30 VDC
Sinking
24 VDC sourcing devices
–
1 kHz
Hysteresis
5 to 48 VDC
Sinking or sourcing
TTL, CMOS, 12 VDC, 24 VDC,
1 kHz
Input current limiting
3
5 to 250 VAC
48 VDC, 120/240 VAC/VDC
(1.5 mA)
1The all-channel update rate refers to the time the module takes to sample all channels. The overall system update rate is affected by other factors, such as the aggregate module update rate and
software loop rate. To calculate the system update rate, visit ni.com/info and enter “systemrate.”
Overview
National Instruments cFP-DI-3xx devices are versatile digital input
modules available for Compact FieldPoint systems. You can use these
modules to monitor digital signals ranging from low-voltage levels up to
250 V. They are commonly used to monitor proximity and limit switches,
pushbutton switches, thermostat outputs, relay closures, power circuits,
and TTL devices. All the modules include onboard diagnostics to ensure
trouble-free installation and maintenance.
Digital Input Modules
The cFP-DI-3xx modules provide built-in module-to-module isolation to
protect your Compact FieldPoint system and controller or communication
interface from high voltage levels. The cFP-DI-300, cFP-DI-301, and
cFP-DI-304 modules use a common ground plane for all the input
channels. Each channel on the cFP-DI-300, cFP-DI-301, and cFP-DI-304
modules includes current-limiting circuitry to prevent module damage
when connected directly to a 24 VDC source. The cFP-DI-330 uses eight
optically isolated input channels so that each digital input has a separate
ground plane, and you can use each channel with a different voltage
potential. Thus, you can connect one channel to a 5 VDC TTL signal and
another signal on the same cFP-DI-330 module to a 250 VAC line voltage.
Each channel on the cFP-DI-330 includes circuitry that limits the total
current to 1.5 mA to prevent damaging the module. All channels on the
cFP-DI-3xx modules feature LEDs that indicate the input state of each
channel. The modules include an all-channel update rate of 1 kHz. Overall
data throughput depends on software loop speeds and network speeds.
Isolation
The cFP-DI-3xx modules feature bank isolation with 2,300 Vrms of
breakdown isolation. In addition, the cFP-DI-330 provides double insulation
for up to 250 Vrms of operational isolation. You can safely use Compact
FieldPoint with the cFP-CB-1 connector block in applications where
hazardous voltages are present. These Compact FieldPoint modules do
not have channel-to-channel isolation.
Field I/O Connections
Compact FieldPoint modules include a built-in power distribution bus
that provides multiple power connections on the module. A field-wired
power supply connected to the voltage (V) and common (C) terminals is
internally connected to a power distribution bus that delivers additional
breakout terminals for voltage supply (VSUP) and common (COM). These
terminals offer a convenient way to distribute power to field devices
that require external power.
Digital Input Modules for Compact FieldPoint
+
V
–
5 to 250 V External
Power Supply
C
+
VSUP (Ch 0)
–
SinkingOutput
Device with
External
Power
+
INA (Ch 0)
INB (Ch 0)
Input
Circuitry
–
V
COM (Ch 0)
15 to 30 VDC
External Power
Supply
C
VSUP (Ch 0)
+
VSUP (Ch 1)
–
SourcingOutput
Device with
External
Power
INA (Ch 1)
INB (Ch 1)
+
Input
Circuitry
–
Sourcing
Output
Device with
External
Power
VIN (Ch 0)
Input
Circuitry
COM (Ch 0)
COM (Ch 1)
VSUP (Ch 2)
SinkingOutput
Device
Powered by
cFP-DI-330
INA (Ch 2)
INB (Ch 2)
Input
Circuitry
Sourcing
Output
Device
Powered by
cFP-DI-30x
VSUP (Ch 1)
VIN (Ch 1)
Input
Circuitry
COM (Ch 2)
COM (Ch 1)
VSUP (Ch 3)
SourcingOutput
Device
Powered by
cFP-DI-330
INA (Ch 3)
INB (Ch 3)
VSUP (Ch n)
Input
Circuitry
VIN (Ch n)
COM (Ch 3)
Input
Circuitry
Switch
COM (Ch n)
VSUP (Ch n)
INA (Ch n)
Switch
INB (Ch n)
Input
Circuitry
To next channel
cFP-DI-300/301/304
COM (Ch n)
To next channel
cFP-DI-330
Wiring Schematics for the cFP-DI-3xx Modules
Ordering Information
NI cFP-DI-300 ......................................................................777318-300
NI cFP-DI-301 ......................................................................777318-301
NI cFP-DI-304 ......................................................................777318-304
NI cFP-DI-330 ......................................................................777318-330
Recommended Compact FieldPoint System Products
NI cFP-2120 ......................................................................777317-2120
NI cFP-BP-4 ............................................................................778617-04
NI cFP-BP-8 ............................................................................778617-08
NI cFP-CB-1............................................................................779618-01
NI PS-5 power supply............................................................778805-90
NI Developer Suite Professional Control Edition..................777906-03
BUY NOW!
For complete product specifications, pricing, and
accessory information, call 800 813 3693 (U.S.) or go
to ni.com/compactfieldpoint.
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
2
Digital Input Modules for Compact FieldPoint
Specifications
Typical for -40 to 70 °C unless otherwise noted.
Digital Input Channels
cFP-DI-300, cFP-DI-330 .......................................................... 8
cFP-DI-301.............................................................................. 16
cFP-DI-304.............................................................................. 32
Input Characteristics
Input impedance
cFP-DI-300, cFP-DI-301...................................................... 5 kΩ
cFP-DI-304.......................................................................... 30 kΩ
Input current limiting cFP-DI-330........................................... 1.5 mA
Input Voltages
cFP-DI-300, cFP-DI-301, cFP-DI-304....................................... 0 to 30 VDC
cFP-DI-330.............................................................................. 0 to 250 VDC or 0 to 250 VAC (50/60 Hz AC) or 0 to 250 VAC (1 kHz AC)
Digital Logic Levels
cFP-DI-300
cFP-DI-301
cFP-DI-304
cFP-DI-330
OFF State ON State OFF State ON State OFF State ON State OFF State
Input Voltage (V)
<5
>15
<5
>15
≤5
≥10
Input Current (µA)
≤1000
≥3000
≤1000
≥3000
≤150
≥330
ON State
≤1 VDC, ≤1 ≥4 VDC, ≥15 VAC (50/60 Hz AC),
VAC
≥3 VAC (1 kHz AC)
Hysteresis (cFP-DI-304)
Input voltage .......................................................................... 2 V min
Input current........................................................................... 60 µA min
Isolation Voltage
cFP-DI-30x
Channel-to-ground
Continuous ....................................................................
Withstand......................................................................
Channel-to-backplane
Continuous ....................................................................
Withstand......................................................................
Channel-to-channel ...........................................................
cFP-DI-330
Maximum isolation voltage...............................................
Transient overvoltage ............................................................
250 Vrms
2,300 Vrms, 5 s max
250 Vrms
2,300 Vrms, 5 s max
None
250 Vrms, Installation Category II
2,300 Vrms
Physical Characteristics
LED indicators
Power (green) ....................................................................
Ready (green).....................................................................
<0..31>, <0..15>, or <0..7> (green) .......................................
Dimensions ...........................................................................
Weight
cFP-DI-300/301 ..................................................................
cFP-DI-330..........................................................................
cFP-DI-304..........................................................................
Power on and self-test passed
Module configured and ready
Input state of each channel
127.0 by 65.9 by 23.9 mm (5.00 by 2.60 by 0.94 in.)
100 g (3.6 oz)
103 g (3.7 oz)
193 g (6.81 oz)
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
3
Digital Input Modules for Compact FieldPoint
Power Requirements (from Network Module)
cFP-DI-300..............................................................................
cFP-DI-301..............................................................................
cFP-DI-304..............................................................................
cFP-DI-330..............................................................................
185 mW
325 mW
1W
200 mW
Environment
Operating temperature .......................................................... -40 to 70 °C
Storage temperature.............................................................. -55 to 85 °C
Relative humidity ................................................................... 10 to 90%, noncondensing
Shock and Vibration
Operating vibration, random (IEC 60068-2-64)...................... 10 to 500 Hz, 5 grms
Operating vibration, sinusoidal (IEC 60068-2-6).................... 10 to 500 Hz, 5 g
Operating shock (IEC 60068-2-27) ......................................... 50 g, 3 ms half sine, 18 shocks at 6 orientations;
30 g, 11 ms half sine, 18 shocks at 6 orientations
Safety and Compliance
Safety
This product is designed to meet the requirements of the following standards
of safety for electrical equipment for measurement, control, and laboratory use:
• IEC 61010-1, EN 61010-1
• UL 61010-1, CSA 61010-1
Note: For UL and other safety certifications, refer to the product label or visit ni.com/certification,
search by model number or product line, and click the appropriate link in the Certification column.
Electromagnetic Compatibility
This product is designed to meet the requirements of the following standards
of EMC for electrical equipment for measurement, control, and laboratory use:
• EN 61326 EMC requirements; Minimum Immunity
• EN 55011 Emissions; Group 1, Class A
• CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A
Note: For EMC compliance, operate this device according to
product documentation.
CE Compliance
This product meets the essential requirements of applicable European Directives,
as amended for CE marking, as follows:
• 2006/95/EC; Low-Voltage Directive (safety)
• 2004/108/EC; Electromagnetic Compatibility Directive (EMC)
Note: Refer to the Declaration of Conformity (DoC) for this product for any
additional regulatory compliance information. To obtain the DoC for this product,
visit ni.com/certification, search by model number or product line, and click
the appropriate link in the Certification column.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers: At the end of their life cycle, all products must be
sent to a WEEE recycling center. For more information about WEEE
recycling centers and National Instruments WEEE initiatives,
visit ni.com/environment/weee.htm.
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
4
IN
TA
PL
AN
MA
IN
NI Services and Support
P
DE
LO
Y
EL
OP
SERVICE
NEEDS
V
DE
NI has the services and support to meet
your needs around the globe and through
the application life cycle – from planning
and development through deployment
and ongoing maintenance. We offer
services and service levels to meet
customer requirements in research,
design, validation, and manufacturing.
Visit ni.com/services.
Training and Certification
NI training is the fastest, most certain route to productivity with our
products. NI training can shorten your learning curve, save development
time, and reduce maintenance costs over the application life cycle. We
schedule instructor-led courses in cities worldwide, or we can hold a
course at your facility. We also offer a professional certification program
that identifies individuals who have high levels of skill and knowledge on
using NI products. Visit ni.com/training.
Professional Services
Our NI Professional Services team is composed of NI applications
and systems engineers and a worldwide National Instruments Alliance
Partner program of more than 600 independent consultants and
integrators. Services range
from start-up assistance to
turnkey system integration.
Visit ni.com/alliance.
OEM Support
We offer design-in consulting and product integration assistance if you
want to use our products for OEM applications. For information about
special pricing and services for OEM customers, visit ni.com/oem.
ni.com • 800 813 3693
National Instruments • [email protected]
Local Sales and Technical Support
In offices worldwide, our staff is local to the country, giving you access
to engineers who speak your language. NI delivers industry-leading
technical support through online knowledge bases, our applications
engineers, and access to 14,000 measurement and automation
professionals within NI Developer Exchange forums. Find immediate
answers to your questions at ni.com/support.
We also offer service programs that provide automatic upgrades to
your application development environment and higher levels of technical
support. Visit ni.com/ssp.
Hardware Services
NI Factory Installation Services
NI Factory Installation Services (FIS) is the fastest and easiest way to
use your PXI or PXI/SCXI combination systems right out of the box.
Trained NI technicians install the software and hardware and configure
the system to your specifications. NI extends the standard warranty by
one year on hardware components (controllers, chassis, modules)
purchased with FIS. To use FIS, simply configure your system online
with ni.com/pxiadvisor.
Calibration Services
NI recognizes the need to maintain properly calibrated devices for
high-accuracy measurements. We provide manual calibration
procedures, services to recalibrate your products, and automated
calibration software specifically designed for use by metrology
laboratories. Visit ni.com/calibration.
Repair and Extended Warranty
NI provides complete repair services for our products. Express repair
and advance replacement services are also available. We offer
extended warranties to help you meet project life-cycle requirements.
Visit ni.com/services.
*351572A-01*
351572A-01
2007-9294-161-101-D
©2008 National Instruments Corporation. All rights reserved. FieldPoint, National Instruments, National Instruments Alliance Partner, NI, ni.com, NI Developer Suite, and SCXI are
trademarks of National Instruments. Other product and company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner
is a business entity independent from NI and has no agency, partnership, or joint-venture relationship with NI.