NI NICFP-AIO-600

Analog Input/Output Combination Modules
for Compact FieldPoint and FieldPoint
NI [c]FP-AIO-600
◾◾ 4 voltage or current inputs
◾◾ ±30 V
◾◾ 0 to 20, 4 to 20 mA
◾◾ 4 current outputs
◾◾ 0 to 10 V
◾◾ 0 to 20, 4 to 20 mA
◾◾ 12-bit resolution
◾◾ Input and output ranges software
configurable per channel
◾◾ 2,300 Vrms bank isolation for transient
overvoltage protection
◾◾ Hot swappable with autoconfiguration
◾◾ -40 to 70 °C operating range
Module
Input
Channels
[c}FP-AIO-600
4
Input Ranges (Software Configurable per Channel)
Output
Channels
Output Ranges
(Software Configurable per Channel)
Resolution
All Channel Update Rate
4
Current: 0 to 20 mA, 4 to 20 mA
12 bits
1.7 kHz
Current: 0 to 20 mA, 4 to 20 mA
Voltage: ±5 V, ±15 V, ±30 V, 0 to 5 V, 0 to 15 V, 0 to 30 V
Overview
[c]FP-AIO-600
The NI [c]FP-AIO-600 is a versatile combination analog input and analog output
The [c]FP-AIO-600 includes four 0 to 30 V or 0 to 20/4 to 20 mA analog inputs
module for Compact FieldPoint and FieldPoint that you can use to measure
and four 0 to 20/4 to 20 mA analog outputs. The analog inputs and outputs use a
voltages and 0 to 20 or 4 to 20 mA current loops from industrial sensors and
12-bit DAC. Each output channel includes a monitoring circuit and LED indicator
transmitters and to control valves, gauges, and other industrial actuators. The
for open current loop detection. The [c]FP-AIO-600 requires an external power
[c]FP-AIO-600 is ideal for low-channel-count systems or for PID control with
supply, providing 5 to 30 VDC.
high-speed I/O. The module has overranging and onboard diagnostics to ensure
trouble-free installation and maintenance. The [c]FP-AIO-600 measures and
linearizes signals onboard to return scaled values to your control or monitoring
software, accept engineering units from your control or monitoring software,
Isolation
The [c]FP-AIO-600 features optical bank isolation with 2,300 Vrms of breakdown
isolation. These Compact FieldPoint and FieldPoint modules do not have
and automatically scale and linearize output signals. The [c]FP-AIO-600 module
channel-to-channel isolation.
comes with a NIST-traceable calibration certificate, ensuring accurate and
Field I/O Connections
reliable analog measurement and control.
Smart I/O Module
You can connect the [c]FP-AIO-600 directly to industrial actuators or units under
test and achieve high-accuracy measurement and control. The module calibrates,
scales engineering units to sensor signals, and performs self-diagnostics to
look for problems with the module or with the wiring, such as open current
loops. With the [c]FP-AIO-600 module, your software application reads and
writes engineering values from the module, eliminating the error-prone step of
converting voltage or current to binary values.
The module has an update rate of 1.7 kHz. Overall data throughput depends
on the software loop speeds and the network speeds.
Compact FieldPoint and FieldPoint modules include a built-in power distribution
bus that provides multiple power connections on the module. A field-wired
power supply connected to the voltage (V) and common (C) terminals is internally
connected to a power distribution bus that provides additional breakout
terminals for voltage supply (Vsup) and common (COM). These terminals offer a
convenient way to distribute power to field devices that require external power.
The [c]FP-AIO-600 has:
◾◾ 4 voltage input terminals (Vin)
◾◾ 4 current input terminals (Iin)
◾◾ 4 current output terminals (Iout)
◾◾ 12 common terminals (COM)
◾◾ 8 power connections for field devices or current loops (Vsup)
Analog Input/Output Combination Modules for Compact FieldPoint and FieldPoint
Ordering Information
Compact FieldPoint
NI cFP-AIO-600..............................................................................777318-600
Recommended Compact FieldPoint System Products
NI cFP-2220.................................................................................777317-2220
NI cFP-BP-4.....................................................................................778617-04
NI cFP-CB-1.....................................................................................778618-01
PS-15 power supply........................................................................781093-01
NI Developer Suite Professional Control Edition............................777906-03
FieldPoint
FP-AIO-600....................................................................................777518-600
Recommended FieldPoint System Products
NI FP-1601.......................................................................................777792-01
NI FP-TB-1.......................................................................................777519-01
PS-4 power supply..........................................................................778586-90
NI Developer Suite Standard Control Edition.................................777905-03
BUY NOW
For complete product specifications, pricing, and accessory information,
call 800 813 3693 (U.S.) or go to ni.com/fieldpoint.
BUY ONLINE at ni.com or C ALL 800 813 36 93 (U.S.)
2
Analog Input/Output Combination Modules for Compact FieldPoint and FieldPoint
Specifications
cFP-AIO-600 Offset Errors
Typical for -40 to 70 °C unless otherwise noted.
Voltage Input Range
Offset Errors at 15 to 35 °C
Offset Errors at -40 to 70 °C
0-20 mA
9 μA typ, 20 μA max
9 μA typ, 20 μA max
4-20 mA
9 μA typ, 20 μA max
9 μA typ, 20 μA max
±20 mA
16 μA typ, 38 μA max
17 μA typ, 38 μA max
Input and Output Characteristics
Number of input channels..................... 4
Number of output channels................... 4
Current Outputs ([c]FP-AIO-600)
ADC resolution....................................... 12 bits
Type of ADC............................................ Successive approximation
DAC resolution....................................... 12 bits
Output ranges........................................ 0-20 or 4-20 mA, programmable
(0-21 or 3.5-21 mA with overranging)
Output type............................................ Current source
Type of DAC............................................ R-2R
Update rate (all channels)...................... 1.7 kHz (588 μs)
(external power supply required)
External power supply........................... 10-30 VDC, 125 mA
Voltage Inputs
for four output channels
Effective resolution................................ 11.3 bits
Internal voltage drop.............................. 3 V
Input impedance.................................... 1.5 MW
Resistive load.........................................Up to 1 kW with 24 VDC power supply
Input signal bandwidth.......................... 350 Hz
Protection............................................... Short-circuit and open-circuit
Default power-up state.......................... 0 mA Isolation Voltage
cFP-AIO-600 Gain Errors
Voltage Input Range
Gain Errors at 15 to 35 °C
Gain Errors at -40 to 70 °C
Current Output Range
(with Overrange)
Accuracy at 15 to 35 °C
(% of Output Value;
% of Full Scale)
Accuracy at -40 to 70 °C
(% of Output Value;
% of Full Scale)
0-5 V
0.03% typ, 0.04% max
0.11% typ, 0.16% max
0-10 V
0.03% typ, 0.04% max
0.11% typ, 0.16% max
0 to 21 mA
±0.03%; ±0.13%
±0.14%; ±0.2%
0-15 V
0.03% typ, 0.04% max
0.11% typ, 0.16% max
3.5 to 21 mA
±0.03%; ±0.16%
±0.14%; ±0.23%
0-30 V
0.03% typ, 0.04% max
0.11% typ, 0.16% max
±5 V
0.03% typ, 0.04% max
0.13% typ, 0.19% max
Isolation Voltage
±10 V
0.03% typ, 0.04% max
0.13% typ, 0.19% max
Maximum isolation voltage................... 250 Vrms, Installation Category II
±15 V
0.03% typ, 0.04% max
0.13% typ, 0.19% max
Channel-to-channel isolation................. No isolation between channels
±30 V
0.03% typ, 0.04% max
0.13% typ, 0.19% max
Transient overvoltage............................. 2,300 Vrms
cFP-AIO-600 Offset Errors
Dynamic Characteristics
Maximum update rate........................... 1,700 updates/s
Voltage Input Range
Offset Errors at 15 to 35 °C
Offset Errors at -40 to 70 °C
0-5 V
4 mV typ, 9 mV max
6 mV typ, 15 mV max
0-10 V
6 mV typ, 14 mV max
8 mV typ, 20 mV max
0-15 V
8 mV typ, 18 mV max
10 mV typ, 24 mV max
Physical Characteristics
0-30 V
13 mV typ, 32 mV max
15 mV typ, 37 mV max
LED indicators
±5 V
6 mV typ, 14 mV max
8 mV typ, 20 mV max
POWER (green).................................. Power on and self-test passed
±10 V
10 mV typ, 23 mV max
12 mV typ, 29 mV max
READY (green)................................... Module configured and ready
±15 V
14 mV typ, 32 mV max
16 mV typ, 38 mV max
Fault status (red)................................ Open circuit
±30 V
25 mV typ, 59 mV max
28 mV typ, 64 mV max
Dimensions
Current Inputs
Effective resolution................................ 11.3 bits
Input impedance.................................... 105 W
Overcurrent protection........................... ±100 mA
Overvoltage protection.......................... ±10 V
Input signal bandwidth.......................... 400 Hz
Gain errors
15 to 35 ºC......................................... 0.08% typ, 0.18% max
Slew rate................................................ 0.4 mA/μs
(FP only, including terminal base)...... 10.7 by 10.9 by 9.1 cm
(4.2 by 4.3 by 3.6 in.)
Weight
FP-AIO-600......................................... 141 g (4.9 oz)
cFP-AIO-600....................................... 111 g (3.9 oz)
Power Requirement
Power from network module................. 350 mW
-40 to 70 ºC........................................ 0.25% typ, 0.66% max
BUY ONLINE at ni.com or C ALL 800 813 36 93 (U.S.)
3
Analog Input/Output Combination Modules for Compact FieldPoint and FieldPoint
Environment
Operating temperature.......................... -40 to 70 °C
Storage temperature.............................. -55 to 85 °C
Relative humidity................................... 10 to 90%, noncondensing
Shock and Vibration
These specifications apply only to Compact FieldPoint. NI recommends Compact
FieldPoint if your application is subject to shock and vibration.
Operating vibration, random
(IEC 60068-2-64)................................ 10 to 500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6).................................. 10 to 500 Hz, 5 g
Operating shock
(IEC 60068-2-27)................................ 50 g, 3 ms half sine, 18 shocks
at 6 orientations; 30 g, 11 ms half sine,
18 shocks at 6 orientations
Safety
This product meets the requirements of the following standards of safety
for electrical equipment for measurement, control, and laboratory use:
◾◾ IEC 61010-1, EN 61010-1
◾◾ UL 61010-1, CSA 61010-1
Note: For UL and other safety certifications, refer to the product label or the
Online Product Certification section.
Electromagnetic Compatibility
This product meets the requirements of the following EMC standards
for electrical equipment for measurement, control, and laboratory use:
◾◾ EN 61326 (IEC 61326): Class A emissions; Industrial immunity
◾◾ EN 55011 (CISPR 11): Group 1, Class A emissions
◾◾ AS/NZS CISPR 11: Group 1, Class A emissions
◾◾ FCC 47 CFR Part 15B: Class A emissions
◾◾ ICES-001: Class A emissions
Note: For the standards applied to assess the EMC of this product, refer to the
Online Product Certification section.
Note: For EMC compliance, operate this product according to the documentation.
CE Compliance
This product meets the essential requirements of applicable European Directives
as follows:
◾◾ 2006/95/EC; Low-Voltage Directive (safety)
◾◾ 2004/108/EC; Electromagnetic Compatibility Directive (EMC)
BUY ONLINE at ni.com or C ALL 800 813 36 93 (U.S.)
4
NI Services and Support
your needs around the globe and through
PL
AN
MA
IN
NI has the services and support to meet
IN
TA
the application life cycle – from planning
and development through deployment and
SERVICE
NEEDS
ongoing maintenance. We offer services
P
DE
EL
OP
and service levels to meet customer
LO
Y
requirements in research, design, validation,
V
DE
and manufacturing.
Visit ni.com/services.
Local Sales and Technical Support
In offices worldwide, our staff is local to the country, giving you access to
engineers who speak your language. NI delivers industry-leading technical
support through online knowledge bases, our applications engineers,
and access to 14,000 measurement and automation professionals within NI
Developer Exchange forums. Find immediate answers to your questions at
ni.com/support.
We also offer service programs that provide automatic upgrades to your
application development environment and higher levels of technical support.
Training and Certification
Visit ni.com/ssp.
NI training is the fastest, most certain route to productivity with our products.
Hardware Services
NI training can shorten your learning curve, save development time, and reduce
maintenance costs over the application life cycle. We schedule instructor-led
System Assurance Programs
courses in cities worldwide, or we can hold a course at your facility. We also
NI system assurance programs are designed to make it even easier for you
offer a professional certification program that identifies individuals who have
to own an NI system. These programs include configuration and deployment
high levels of skill and knowledge on using NI products.
services for your NI PXI, CompactRIO, or Compact FieldPoint system. The NI Basic
Visit ni.com/training.
System Assurance Program provides a simple integration test and ensures that
Professional Services
your system is delivered completely assembled in one box. When you configure
your system with the NI Standard System Assurance Program, you can select
Our NI Professional Services team is composed of NI applications and systems
from available NI system driver sets and application development environments
engineers and a worldwide National Instruments Alliance Partner program of
to create customized, reorderable software configurations. Your system arrives
more than 600 independent consultants and integrators. Services range from
fully assembled and tested in one box with your software preinstalled. When
start-up assistance to turnkey system
you order your system with the standard program, you also receive system-
integration. Visit ni.com/alliance.
specific documentation including a bill of materials, an integration test report,
a recommended maintenance plan, and frequently asked question documents.
OEM Support
Finally, the standard program reduces the total cost of owning an NI system
We offer design-in consulting and product integration assistance if you want to
online product advisors at ni.com/advisor to find a system assurance program
use our products for OEM applications. For information about special pricing and
services for OEM customers, visit ni.com/oem.
by providing three years of warranty coverage and calibration service. Use the
to meet your needs.
Calibration Services
NI recognizes the need to maintain properly calibrated devices for highaccuracy measurements. We provide manual calibration procedures, services
to recalibrate your products, and automated calibration software specifically
designed for use by metrology laboratories. Visit ni.com/calibration.
Repair and Extended Warranty
NI provides complete repair services for our products. Express repair and
advance replacement services are also available. We offer extended warranties
to help you meet project life-cycle requirements. Visit ni.com/services.
ni.com
n
800 813 3693
National Instruments
n
[email protected]
©2009 National Instruments. All rights reserved. CompactRIO, FieldPoint, National Instruments, National Instruments Alliance Partner , NI, ni.com, and NI Developer Suite are trademarks of National Instruments. Other product and
company names listed are trademarks or trade names of their respective companies. A National Instruments Alliance Partner is a business entity independent from National Instruments and has no agency, partnership, or joint-venture
relationship with National Instruments. 0644