POWER-ONE LXN2880-6

X Series
375 and 500 Watt AC-DC Converters
Input range 85...264 V AC with PFC
1 or 2 isolated, regulated outputs up to 96 V
3 kV AC I/O electric strength test voltage
LGA
• Electrically and mechanically rugged DIN-rail
front end
• Outputs individually controlled with 150%
output peak power
• Operating ambient temperature range
–40...60°C with convection cooling
Selection chart for front ends
Output 1
Uo nom Io nom
[V DC] [A]
24.7
15
24.7
20
37
9.9
37
13.2
49.4
7.5
49.4
10
24.7
10
49.4
5
Output 2
Uo nom Io nom
[V DC ] [A]
24.7
10
49.4
5
Input voltage
Ui min…Ui max
85…264 VAC
(14…440 Hz)3
90…350 VDC
Rated power
TA = 60°C
Po tot [W]
375
500
375
500
375
500
500
500
Type
Options1
LXR 1601-6
LXN-1601-6
LXR 1701-6
LXN 1701-6
LXR-1801-6
LXN-1801-6
LXN-2660-6
LXN 2880-6
R
D1…D5
S
M2
F, F1
K2
Selection chart for Battery chargers 2
Output
Input voltage
Rated power
Type
Options1
Uo nom
Io nom
Ui min…Ui max
TA = 60°C
[V DC]
[A]
Po tot [W]
25.7...29.3
12.6
85…264 VAC
345
LXR 1240-6 M1
F, F1
25.7...29.3
16.9
460
LXN 1240-6 M1
K2
(14…440 Hz)3
51.4...58.6
6.3
90…350 VDC
345
LXR 1740-6 M1
51.4...58.6
8.4
460
LXN 1740-6 M1
1 For lead times and minimum order quantities contact Power-One.
2 For availability contact Power-One.
3 Input frequency range certified for 14...440 Hz. For continuous operating frequency <40 Hz and >100 Hz contact
factory.
www.power-one.com
Edition 5/7.2001
1
X Series
375 and 500 Watt AC-DC Converters
Input
Input voltage
Input frequency
Power factor
Inrush current
world wide mains, single phase
for derating information see application note
wide frequency range
active PFC
virtually no inrush current
85...264 V AC
90...350 V DC
16 2/3...440 Hz
up to 0.99
Output
Efficiency
Output voltage setting accuracy
Output voltage noise
Output voltage ripple
Line and cross regulation
Load regulation
Minimum load
Current limitation
Short term peak power
Operation in parallel
Hold-up time
Ui nom, Io nom
up to 89%
Ui nom, Io nom
±1.3% Uo nom
IEC/EN 61204
typ. 50 mV
sinusoidal output ripple at twice the line frequency
≤1.2 Vpp
Ui min...Ui max
typ. 50 mV
0...100 % Io nom, Ui nom
–1.6% Uo nom
not required
rectangular U/I characteristic
101...112% Io nom
1 s, electronically controlled
150% Io nom
enabled by droop current share
Io nom, Uo decreases to 80% of Uo nom
typ. 15 ms
Control
Status indication
LED output(s) OK
Protection
Input reverse polarity
Input fuse
Input undervoltage lockout
Input overvoltage lockout
Input transient
Output(s)
Output overvoltage
Overtemperature
bridge rectifier
not user accessible
10 A, fast blow
typ. 80% Ui min
typ. 105% Ui max
voltage depending resistor (VDR)
no-load, overload and short circuit proof
second control loop, each output, 24/48 V
reduced output power if thermally overloaded
30/60 V SELV
Safety
Approvals in progress
Electric strength test voltage
Pollution degree
Degree of protection
www.power-one.com
Edition 5/7.2001
EN 60950, UL 1950, CSA22.2 No. 950, UL 508 listed
class I, I/case
class I, I/O
class I, O/case
class I, O/O
AC-in / DC-in
2 kV AC
3 kV AC
1 kV AC
0.35 kV AC
3/2
IP 20
2
DIN Rail Mountable
X Series
EMC
Electrostatic discharge
Electromagnetic field
Electr. fast transients/bursts
Surge
Conducted disturbances
Electromagnetic emissions
IEC/EN 61000-4-2,
IEC/EN 61000-4-3,
IEC/EN 61000-4-4,
IEC/EN 61000-4-5,
level 4, contact/air (8/15 kV)
criterion A
level 3 (10 V/m)
criterion A
level 4, capacitive/direct (4/2 kV)
criterion A
level 3, in and out, line to line (2 kV) criterion B
level >3, input, line to case (3.5 kV) criterion B
level 2, output, line to case (1 kV)
criterion A
IEC/EN 61000-4-6, level 3 (10 V)
criterion A
CISPR 22/EN 55022, conducted
class B
Environmental
Operating ambient temperature
Operating case temperature TC
Storage temperature
Damp heat
Shock and vibration
Shock
Bump
Vibration, sinusoidal
Vibration, random
MTBF
Ui nom, Io nom, convection cooled
Ui nom, Io nom
non operational
IEC/EN 60068-2-3, 93%, 40°C
unit wall mounted with brackets
IEC/EN 60068-2-27, 11 ms
IEC/EN 60068-2-29, 11 ms
IEC/EN 60068-2-6, 10...60/60...2000 Hz
IEC/EN 60068-2-64, 20...500 Hz
MIL-HDBK-217E, GB, 40°C
–40...60°C
–40...87°C
–40...100°C
56 days
50 gn
25 gn
0.35 mm/5 gn
0.05 g2/Hz
400'000 h
Options
Input and output undervoltage monitoring
Output voltage adjustment
10 V...110% of Uo nom
Remote on/off
Multi option choice
(D1...D5, R, S) via Sub-D connector
Built-in second input fuse in the neutral
No fuse fittet (for operation from high DC)
System connectors with screw terminals
www.power-one.com
Edition 5/7.2001
D1...D5
R
S
M1...M2
F
F1
K2
3
X Series
375 and 500 Watt AC-DC Converters
Mechanical data
European
Projection
33 (1.3")
43 (1.69")
13 (0.51"))
Option M
S09127
49 (1.93")
204 (8.03")
(
)
196 (7.71")
(
)
194 (7.64")
(
)
29.4 (1.16")
138 (5.43")
5
113.6 (4.47")
106.6 (4.2")
15 (0.59")
Tolerances ±0.3 mm (0.012") unless otherwise indicated.
31 (1.22")
TA
TA
Wall mounting
brackets
(accessory)
Measuring point for
case temperature TC
www.power-one.com
Edition 5/7.2001
4
DIN Rail Mountable
X Series
Terminal allocation input side
n
Pin
1
2
3
Des.
N
P
Determination
Protective earth
Input neutral
I
1
Terminal allocation output side
Pin
Des.
Single output
Double output
1
2
3
4
5
6
7
8
9
10
+
+
–
–
+
+
–
–
Aux1
Earth to load
Output pos.
Output pos.
Output neg.
Output neg.
Output pos.
Output pos.
Output neg.
Output neg.
Options
Earth to load
Output 1 pos.
Output 1 pos.
Output 1 neg.
Output 1 neg.
Output 2 pos.
Output 2 pos.
Output 2 neg.
Output 2 neg.
Options
11
Aux2
12
S10066
Options
Options
Earth to load
Earth to load
2
3
S90048
1 2 3 4 5 6 7 8 9 10 11 12
Accessories
Mounting brackets for vertical chassis/wall mounting
Protective covers over input and output terminals
www.power-one.com
Edition 5/7.2001
5