SCHURTER 172600

172600
Non resettable fuses
www.schurter.com/pg01_2
Miniature Fuse, 6.3 x 32 mm, Time-Lag T, UL, NNO, 250 VAC
UL 248-14 · 250 VAC · Time-Lag T
Description
References
-Phase-Out: Current Ratings 0.125 - 1.6 A
-High Breaking Capacity
General Product Information
Weblinks
Standards
Approvals, RoHS, CHINA-RoHS, e-Store, Distributor-Stock-Check,
Accessories, Product Change Notification (PCN)
-UL 248-14
Approvals
-UL File Number: E42088
Technical Data
Rated Voltage
Rated Current
Breaking Capacity
Characteristic
Mounting Admissible Ambient Air Temp.
Climatic Category
Material: Tube
Material: Endcaps
Unit Weight
Storage Conditions
Product Marking
125 - 250 VAC
0.125 - 20 A
35 A - 10 kA
Time-Lag T
Fuseholder / Clip
-40 °C to 70 °C
40/070/21 acc. to IEC 60068-1
Ceramic
Tin-Plated Nickel
2.5 g
0 °C to 60 °C, max. 70% r.h.
, Type, Current, Voltage, Characteristic, Approvals
Dimensions
32 mm
ø 6.35 ±0.06
31.8±0.8
Pre-Arcing Time
Rated Current In
1.1 x In min.
1.35 x In max.
2.0 x In min. 2.0 x In max.
0.125 A - 3 A
60 min
60 min
5s
120 s
4 A - 20 A
60 min
60 min
12 s
120 s
Fuses
172600
Non resettable fuses
www.schurter.com/pg01_2
Variants
Rated Current [A]
Rated Voltage [VAC]
0.125
250
0.16
250
0.2
Breaking
Capacity
Voltage Drop
1.0 In typ.
[mV]
Power Dissipation 1.1 In
typ. [mW]
Melting I²t
10.0 Intyp.
[A²s]
1)
3200
480
1.8
l
7033.8100
1)
1120
230
2.7
l
7033.8110
250
1)
1200
290
2
l
7033.8160
0.25
250
1)
560
170
1.6
l
7033.8120
0.4
250
1)
610
310
8.4
l
7033.8130
0.5
250
2)
655
420
2.6
l
7033.8050
0.6
250
2)
615
470
3
l
7033.8140
0.7
250
2)
540
490
5
l
7033.8060
0.8
250
2)
510
530
8.8
l
7033.8070
1
250
2)
385
490
24
l
1.25
250
2)
350
560
30
l
1.5
250
2)
345
670
42
l
1.6
250
2)
315
650
47
l
l
7043.8110
2
250
2)
270
530
84
l
l
7043.8120
2.5
250
2)
255
850
170
l
3
250
2)
240
860
200
l
4
250
2)
168
1650
600
l
5
250
2)
150
900
690
l
7043.8160
6.3
250
2)
166
1750
1130
l
7043.8170
7
125
2)
210
1970
1360
l
7043.8180
l
7033.8150
7033.8080
7033.8090
7043.8130
7043.8140
l
7043.8150
8
125
3)
150
1520
100
l
7043.8190
10
250
3)
165
2150
38
l
7043.8200
12.5
250
4)
150
2500
70
l
7043.8210
16
250
4)
175
3700
330
l
7043.8220
20
250
4)
168
4500
1300
l
7043.8230
1) 10 kA @ 125 VAC , p.f. = 0.7 - 0.8 / 35 A @ 250 VAC , p.f. = 0.7 - 0.8
2) 10 kA @ 125 VAC , p.f. = 0.7 - 0.8 / 200 A @ 250 VAC , p.f. = 0.7 - 0.8
3) 10 kA @ 125 VAC , p.f. = 0.7 - 0.8
4) 10 kA @ 125 VAC , p.f. = 0.7 - 0.8 / 1500 A @ 250 VAC , p.f. = 0.7 - 0.8
Packaging Unit Order Number
Small Box Pack (10 pcs.)
Fuses
172600
Non resettable fuses
www.schurter.com/pg01_2
Time-Current-Curves
100000
≤3A
_> 4 A
10000
Time in Seconds
1000
100
10
1
0.1
0.01
0.001
1
10
Multiple of Rated Current In
The specifications, descriptions and illustrations indicated in this document are based
on
Fuses
current information. All content is subject to modifications and amendments.