ASTEC HPS50W-NNR-000-XXX

350-1400 Watts
Total power:
Input voltage:
# of outputs:
HPS35 Series
350W
90-2
264VAC
One & standby
Electrical Specs
Input
Input voltage
Frequency
Inrush current
Efficiency
Power factor
Turn-on time
Special Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Active Power Factor Correction
EN61000-3-2 compliant
CISPR22, EN55022 Class-B conducted/radiated EMI
EN61000 immunity standards
5VSB@2A
Overvoltage protection (OVP)
Overcurrent protection (OCP)
Overtemperature protection (OTP)
AC OK signal and indicator LED
DC OK signal and indicator LED
Remote inhibit
Remote Sense on main output
Hot Plug
N+1 Redundant
Optional I2C board (pending)
Voltage Monitoring
Current Monitoring
Remote on/off
DC OK / AC OK
Temperature
Fan fail
Environmental
Operating temperature: 0°C to +50°C ambient, derate
output @ 2.5% per degree from 50°C to 70°C
Shock:
Operating - 4g, half since, 22 ms minimum
duration, all 6 faces
Non-operating: 30g, half since, 6 ms minimum
duration, all 6 faces
Random Vibration
Operating: 1g rms, 20 min/axis
Non-operating: 12.5g rms, 20min/axis
Humidity: 95% non-condensing
Storage temperature: -40°C to +85°C
Temperature coefficient: 0.04% per °C
Cooling: Internal DC fans
EMI filter standard
Leakage current standard
Radiated EMI
Holdup time
AC OK
Harmonic distortion
Isolation
90-264 VAC typical
47-440 Hz
40 A peak typical @ 25°C
80% typ @ full load, 230 VAC
0.98 typical @ 115 VAC, full load
AC - ON 2 sec.
Inhibit / Enable 160 ms
CISPR 22 EN55022 Level “B”
<0.5 mA max @ 230 VAC @ 60Hz
(per module)
CISPR 22 EN55022 Level “B”
20 ms minimum
(independent of input VAC)
5 ms early warning minimum before
outputs lose regulation
Meets EN61000-3-2
Meets EN60950
Output
Adjustability
Overall reg
Ripple
±5% of nominal output voltage
<3%
1% of Vout Pk - Pk
(20 MHz bandwidth)
Dynamic response
4% with 50% load step
Recovery time
To within 1% in <300 µsec
Overcurrent protection
115%-130% of rated output current
Short circuit protection
Protected for continuous short circuit.
Auto recovery.
Overvoltage protection
120 - 140% . AC Reset.
Reverse voltage protection 100% of rated output current
Thermal protection
Main and Aux disabled when internal
temp exceeds safe operating range.
Remote sense
Up to 0.5 V total drop
Single wire parallel
Current share to within 10% of total
rated current on main output
DC OK
±5% of nominal
Minimum load*
None required (as a standalone module)
Standby voltage
5 VDC @2A max. present whenever AC
input is applied
Global Inhibit
Logic “0”
*3A minimum required for current share operation
Safety
UL
CSA
TUV
CB
CE
UL60950-1, 1st Ed. (April 1, 2003)
CSA C22.2 60950-1-03
EN60950-1:2001 (1st Ed.)
IEC60950-1, 1st Ed. (2001)
Mark (LVD)
Technical Support: (888) 41-ASTEC or (407) 241-2752
Americas: (760) 930-4600
Europe (UK) 44 (1384) 842-211
Asia (HK) 852-2437-96622
rev 02.24.05
AMERICAS
EUROPE
ASIA
5810 Van Allen Way
Carlsbad, CA 92008
Telephone: 760-930-4600
Facsimile: 760-930-0698
Astec House, Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX, UK
Telephone: 44 (1384) 842-211
Facsimile: 44 (1384) 843-355
Units 2111-2116, Level 21
Tower1, Metroplaza
223, Hing Fong Road
Fwai Fong, New Territories
Hong Kong
Telephone: 852-2437-9662
Facsimile: 852-2402-4426
Watts
Input
Voltage
Module ID
350
Module
Code
Max. Size
(H x W x L)
Max. Module
Power
HPS35
1.6" x 4.3" x 10.5"
350 W
Number
Unit
per Rack Weight (lbs)
4
3.2
90-264
Power
35 = 350 W
50 = 500 W
HPS35
Code
Volts
L
W
12.0
48.0
Output Amps
HPS
29.2
7.3
Output Voltage
L = 12 V
W = 48 V
SERIAL NO.:
+12V / 29A
REV: XX
A/C CODE: XXXX
73-811-029
DATE: YYWW
S/N: MMMMWWSSSSRRC
MADE IN PHILIPPINES
OUTPUT:
50/60 Hz
90 - 240VAC - 40A
HPS35L-NNR-000
INPUT:
53.8
7.6
www.astecpower.com
MAXIMUM OUTPUT POWER IS 350W
HPS35L-N
NNR-0
000
Special Options
& Modifications
Contact Astec
N N R
0 0 0 XXX
HPS35
Modules
Pin Assignments
HPS35 Module
Bottom
Top
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Description
AC (L)
BLANK
AC (N)
BLANK
GND
SWP
5V RTN
COMMON
COMMON
COMMON
COMMON
COMMON
COMMON
V OUT
V OUT
V OUT
V OUT
V OUT
V OUT
BLANK
+5 STANDBY
TBA
FAN MON
I2C CLK
Pin
A
B
C
D
E
F
H
J
K
L
M
N
P
R
S
T
U
V
W
X
Y
Z
AA
BB
TOP SIDE 1-24
Description
AC (L)
BLANK
AC (N)
BLANK
GND
-SENSE
+SENSE
COMMON
COMMON
COMMON
COMMON
COMMON
COMMON
V OUT
V OUT
V OUT
V OUT
V OUT
V OUT
INHIBIT
TBA
AC OK
DC OK
I2C DATA
1
2
3
4
5
6
7
8
A B
C
D E
F
H J
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
K
L
M N P
R
S
T
U V
W X
Y
Z
AA AB
Unit Connector
Card Edge Connector with gold fingers double-sided 1.6mm FR-4 PCB
Mating connector:
EDAC 307-048-520-201 or
equivalent
Rating: 5A per contact
Pin 6 - SWP (IN/OUT Signal)
(Single Wire Parallel)
SWP Pin is used when
connecting units in parallel
to achieve current sharing.
Current share accuracy is
typically 10% of full load.
Note:
SWP Voltage is 5V at 100% load current
Pin X - Module Inhibit (IN Signal)
Pin Z - AC OK (OUT Signal)
Pin 23 - Fan Monitor (OUT Signal)
Note:
Hi state: Source 100uA @ 4V
Low State: Sink 10mA @ 0.5V
Pin F - --R
Remote Sense
Pin H - + Remote Sense
Compensates for up to 0.5V drop.
Recommended shielded twisted wire
pair.
154
North America (USA): 1-888-41-ASTEC
Pin AA - DC OK (OUT Signal)
Europe (UK): 44 (1384) 842-211
Asia (HK): 852-2437-9662
rev 02.24.05
HPS35 Series
DRAWINGS
AMERICAS
EUROPE
ASIA
5810 Van Allen Way
Carlsbad, CA 92008
Telephone: 760-930-4600
Facsimile: 760-930-0698
Astec House, Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX, UK
Telephone: 44 (1384) 842-211
Facsimile: 44 (1384) 843-355
Units 2111-2116, Level 21
Tower1, Metroplaza
223, Hing Fong Road
Fwai Fong, New Territories
Hong Kong
Telephone: 852-2437-9662
Facsimile: 852-2402-4426
Racks
Watts
Input
Voltage
Module Used
Rack ID
1400 (fully populated)
System
Code
Max. Size
(H x W x L)
Max. System
Power
Module
Distribution
Standard
Size
Unit
Weight (lbs.)
HPR1
1.75" x 19.0" x 13.0"
1400 W
(4 ea) HPS35
1U
8.6
90-264
HPS35
HPR1
HPR1 -
Code
Volts
Output Amps
L
W
12.0
48.0
116.8
29.2
Standard Options
00 = No options
01 = Local sense
HPR1 -0
00
AC Cord: (North America)
For all other countries, please contact factory.
482.6
22.0
1) Quail Electronics Series 5050 or equivalent
(15A/125V)
Supply End - NEMA 5-15P
Equipment End - IEC 60320-C19
2) Quail Electronics Series 5052 or equivalent
(20A/125V)
Supply ENd - NEMA 5-20P
Equipment End - IEC60320-C19
SERIAL NO.:
25.0
DATE: YYWW
S/N: MMMMWWSSSSRRC
MADE IN PHILIPPINES
REV: XX
A/C CODE: XXXX
73-810-002
50/60 Hz
+12V / 29A
90 - 240VAC - 40A
OUTPUT:
INPUT:
MAXIMUM OUTPUT POWER IS 1400W
HPR1-00
Blank Panel:
Astec P/N 73-686-000
RTN
13.4
+
468.8
343.2
330.2
+
RTN
43.7
31.7
442.0
www.astecpower.com
155
D-sub Connector Pin outs
HPR1 -0
00
S
L
O
T
1
S
L
O
T
2
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Description
5V Return (std-by)
+ Remote Sense
- Remote Sense
5V Stand by
Unused
Module Inhibit
DC OK
AC OK
I2C_ADD#1
I2C_ADD#2
Fan Monitor
Global AC OK
Module Inhibit
DC OK
AC OK
I2C_ADD#1
I2C_ADD#2
Fan Monitor
Global Inhibit
S
L
O
T
3
S
L
O
T
4
Pin
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Description
I2C CLOCK
I2C DATA
SWP
Unused (I2C_INT)
Module Inhibit
DC OK
AC OK
I2C_ADD#1
I2C_ADD#2
Fan Monitor
Unused
Module Inhibit
DC OK
AC OK
I2C_ADD#1
I2C_ADD#2
Fan Monitor
Unused
Pin 2 + Remote Sense
Pin 3 - Remote Sense
Compensates for up to 0.5V drop.
Recommended shielded twisted wire
pair.
DC OK (OUT Signal)
Pin 12 - Global AC OK (OUT signal)
Note: DC OK signals for each slot in the
rack is accessible in the D-sub
connector (J18). Refer to Connector
Pin-out table for pin assignments. Pin 1
is the Return Pin.
Note: AC OK signals are OR'ed together
internally. If any module fails, the LED
on the affected module will be off and
the logic signal will indicate AC NOT OK.
AC OK (OUT Signal)
Pin 19 - Global Inhibit (IN signal)
Note: All outputs disabled when Pin 19
is open or High.
Note: AC OK signals for each slot in the
rack is accessible in the D-sub
connector (J18). Refer to Connector
Pin-out table for pin assignments. Pin 1
is the Return Pin.
Hi state: Source 100uA @ 4V
Low State: Sink 10mA @ 0.5V
Pin 22 - SWP (IN/OUT signal)
SWP Pin is used when
Fan Monitor (OUT Signal)
connecting racks in
parallel to achieve
current sharing. Current
share accuracy is
typically 10% of full load.
Note: SWP Voltage is 5V at 100% load
current.
Module Inhibit (IN Signal)
PSU Connector
617-A-037-P-AJ-1-21 (Male socket) Amphenol
Pin Out Diagram D-sub Connector (male)
Note: Module Inhibit signals for each
slot in the rack is accessible in the D-sub
connector (J18). Refer to Connector Pinout table for pin assignments. Pin 1 is
the Return Pin.
Note: Fan Monitor signals for each slot
in the rack is accessible in the D-sub
connector (J18). Refer to Connector
Pin-out table for pin assignments. Pin 1
is the Return Pin.
I2C_ADD#1
I2C_ADD#2
TBD
Mating Connector
617-A-037-S-AJ-1-20 (Female socket) Amphenol
Pin Out Diagram D-sub Connector (female)
156
North America (USA): 1-888-41-ASTEC
Europe (UK): 44 (1384) 842-211
Asia (HK): 852-2437-9662
rev 02.24.05