ETC FK3C3508024

Du line
Display for Digital Signals
Types FK3C3, FK4C3
®
Fieldbus
•
•
•
•
•
Product Description
Installationbus
8-, 16- or 32-channel status indicator
8-, 16- or 32-dot LED display
NPN transistor output for loss of Dupline® carrier
Horizontal or vertical panel mounting, DIN 43700
AC/DC power supply
Ordering Key
FK3C 3508 024
inverted for fast locating of
deviations from normal
operation, e.g. missing startup conditions, open doors
and windows, machine fault
annunciation etc.
Type: Dupline®
Display type
Housing
Type no.
Supply
Supply
Ordering no.
8 channels
8-dot LED
Ordering no
16 channels
16-dot LED
Ordering no.
32 channels
32-dot LED
24 VAC
120 VAC
220 VAC
FK3C 3508 024
FK3C 3508 120
FK3C 3508 220
FK3C 3616 024
FK3C 3616 120
FK3C 3616 220
FK4C 3732 024
FK4C 3732 120
FK4C 3732 220
*
*
*
FMK A to FMK P
FMK A-B to O-P
FMK A-D to M-P
Dupline® display for panel
mounting. Status indication
of 8, 16 or 32 channels in 8-,
16- or 32-segment singlepoint LED representation.
Display function normal or
Type Selection
12 VDC
Code module
*
All AC-types may be supplied with 12 VDC at pins 2 & 3
Display/Output Specifications
Display
Display format
Display range
Display type
Size of dots
Display colour
Display test
Transmission protocol
F.3C 3508 ...
( 8 channels)
F.3C 3616 ...
(16 channels)
F.4C 3732 ...
(32 channels)
Channel status
8 dots
LED
5 x 5 mm
Red
None
Binary
Channel status
16 dots
LED
6 x 3 mm
Red
None
Binary
Channel status
32 dots
LED
5 x 2 mm
Red
None
Binary
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
1
Du line
FK3C3, FK4C3
®
Fieldbus
Installationbus
Display/Output Specifications (cont.)
Output
Output voltage range VBB
Reverse-polarity protection
Current per output
Short-circuit protection
Built-in protective diodes
Off-state leakage current
Output voltage drop
Cable length
Dielectric voltage
Output - Dupline®
Output connection
Dupline® connection
Response time
F.3C 3508 ...
( 8 channels)
1 NPN transistor
4 to 35 VDC (or VDD in)
Yes
≤ 100 mA
None
None
≤ 100 µA
≤ 1.5 V
≤3m
F.3C 3616 ...
(16 channels)
1 NPN transistor
4 to 35 VDC (or VDD in)
Yes
≤ 100 mA
None
None
≤ 100 µA
≤ 1.5 V
≤3m
F.4C 3732 ...
(32 channels)
1 NPN transistor
4 to 35 VDC (or VDD in)
Yes
≤ 100 mA
None
None
≤ 100 µA
≤ 1.5 V
≤3m
None
2.8 mm faston
2.8 mm faston
< 2 pulse trains
None
2.8 mm faston
2.8 mm faston
< 2 pulse trains
None
2.8 mm faston
2.8 mm faston
< 2 pulse trains
Supply Specifications
General Specifications
Power supply AC types
Operational voltage
through pins A1 & A2 220
120
024
Frequency
Voltage interruption
Rated operational power
Rated impulse withstand
voltage
220
120
024
Dielectric voltage
Supply - Dupline®
Supply - Output
Alternative DC supply
Operational voltage (VDD in)
through pins 2 & 3
FK...
Output-off delay
upon loss of Dupline® carrier
Reverse polarity protection
Rated operational current
FK3C 3508
FK3C 3616
FK4C 3732
Inrush current
Transient protection voltage
Dielectric voltage
Supply - Dupline®
Supply - Output
Supply connection
2
Overvoltage cat. III (IEC 60664)
230 VAC +6%, -15% (IEC 60038)
120 VAC ± 10% (IEC60038)
24 VAC ± 10%
45 to 65 Hz
≤ 40 ms
Typ. 6 VA
4 kV
2.5 kV
800 V
≥ 2 kVAC (rms)
≥ 2 kVAC (rms)
Overvoltage cat. III (IEC 60664)
12 VDC ± 10%
(ripple included)
Yes
≤ 125 mA
≤ 250 mA
≤ 500 mA
≤1A
800 V
Power ON delay
Indication for
Loss of Dupline® carrier
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Humidity (non-condensing)
Mechanical resistance
Shock
Vibration
Dimensions
Material
(see "Technical Information")
Weight
F.3C 3508
F.3C 3616
F.4C 3732
Approvals
≤ 3 s, (LCD irregular
display indication)
Undefined ≤ 1 s
LED, red
IP 40
3 (IEC 60664)
0° to +50°C (+32° to +122°F)
-20° to +60°C (-4° to +140°F)
20 to 80%
15 G (11 ms)
2 G (6 to 55 Hz)
F.3C: 96 x 48 - Housing
F.4C: 144 x 48 - Housing
300 g
300 g
400 g
CSA, UL
None
None
2.8 mm faston
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
Du line
FK3C3, FK4C3
®
Fieldbus
Installationbus
Mode of Operation
8-, 16- or 32-channel status
indicator with LED dot display.
The displays are used to
monitor 1, 2 or 4 Dupline®
channel groups.
The output dots turn on when
the respective channels of
the selected channel groups
are activated by transmitters.
Each dot represents the status of one Dupline® channel. The lowest figure on the
front plate indicates the lowest channel of the first channel group and the highest
figure indicates the highest
channel of the last channel
group selected by the code
module.
In case of Dupline® carrier
loss the fault LED and the
output (pins 2 & 5) turn on.
Reaction time typically 1 s.
Note:
• Upon loss of Dupline®
carrier the channel dots of
an LED display turn off.
• If DC-supplied displays are
used the length of the supply bus must not exceed
3 m in order to avoid disturbances unbalancing the
Dupline®.
Operation Diagram
Power supply
Dupline® carrier
Transmission on lowest chan.
Dot no. 1
Transmission on highest channel
Highest dot no.
Fault LED/output
Wiring Diagrams
DC supply
AC supply
AC supply
Output
load
Output
load
VDD in
VBB
S: signal wire
S: signal wire
Additional Information
Accessories
Scope of supply:
For further information refer to "Accessories".
1 x Display
F..C...
1 x Front plate for horizontal mounting
1 x Front plate for vertical mounting
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
3