ETC URB

FRENCH CYLINDRICAL
URB/URQ
SEMICONDUCTOR PROTECTION FUSES
660V - 1000V AC
URB/URQ/URS from 32 up to 250A
SIZE: 27 X 60
Features / Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC Standard 269.1 and 4
➤ 600V-1000V AC Voltage Rating
➤ aR Class according to VDE 636-23 and IEC 269.4
➤ Model according to NF C 63210 and 63211 with
built-in blown trip-indicator
➤ 660V URQ and 100V URB are UL Recognized
APPLICATIONS DATA
Voltage
rating
UN(VAC)
660 V
Total clearing I2t @ UN
I2tt (A2s)
Current
rating
IN (A)
URQ
50
63
80
100
125
160
200
250
110
155
350
625
1400
3150
6580
15570
610
860
1880
3210
6970
15000
30000
63000
8.4
11.1
12.6
14.2
15.7
17.7
19.4
22.6
16
21
24
27
30
34
38
45
125
2790
13000
14.5
25
160
5500
24000
17.5
30
32
40
50
63
80
100
125
160
170
33
60
110
200
435
975
1910
3890
4710
250
450
840
1470
3300
6000
12500
26700
36000
7.4
8.7
9.7
11.3
12.3
14
16
18
19
14.5
17
19
22
24
27
31
35
37
URS
1000 V
Pre-arcing
I2t @ 1 ms
I2tp (A2s)
Class
URB
* Minimum operating voltage for trip-indicator: 20 V
D 98
Watt losses
0,8 IN
IN
Tested
interrupting
rating
200 kA
@ 660 V
100 kA
@ 1000 V
FRENCH CYLINDRICAL
URB/URQ
SEMICONDUCTOR PROTECTION FUSES
PART NUMBERS
TYPE
URQ 660 V
27x60 - With blown fuse trip-indicatior
Ø 27
60,3
VOLTAGE
7
Ø5
URB 1000 V
D 99
CURRENT
RATING
CATALOG NO.
REF #
50A
6.621 CP URQ 27x60/ 50
N075958
63 A
6.621 CP URQ 27x60/ 63
V076309
80 A
6.621 CP URQ 27x60/ 80
W076310
100 A
6.621 CP URQ 27x60/100
R078330
125 A
6.621 CP URQ 27x60/125
S078331
160 A
6.621 CP URQ 27x60/160
X076311
200 A
6.621 CP URQ 27x60/200
T078332
250 A
6.621 CP URQ 27x60/250
T076308
32 A
1021 CP URB 27x60/ 32
S081298
40 A
1021 CP URB 27x60/ 40
R081297
50 A
1021 CP URB 27x60/ 50
Q081296
63 A
1021 CP URB 27x60/ 63
P081295
80 A
1021 CP URB 27x60/ 80
N081294
100 A
1021 CP URB 27x60/100
M081293
125 A
1021 CP URB 27x60/125
L081292
160 A
1021 CP URB 27x60/160
K081291
170 A
1021 CP URB 27x60/170
Z080338
D
FRENCH CYLINDRICAL
URB/URQ
SEMICONDUCTOR PROTECTION FUSES
MELTING TIME - CURRENT DATA
a = 130
A2 = 0,6
B1 = 1,25
B2 = 0,6
Cf3 = 0,8
a = 130
A2 = 0,6
a = 130
A2 = 0,6
B1 = 1,25
B2 = 0,6
Cf3 = 0,8
These curves indicate, for each rated current, the pre-arcing time vs. the R.M.S. pre-arcing current.
For each rated current tolerance for the mean pre-arcing current ± 8%.
D 100
B1 = 1,25
B2 = 0,6
Cf3 = 0,8
FRENCH CYLINDRICAL
URB/URQ
SEMICONDUCTOR PROTECTION FUSES
Peak Arc Voltage
Um(V)
Um(V)
2000
2000
1000
1000
0
32 to170 A URB
250 A URQ
50 to 200 A URQ
100 200 300 400 500 600 700
Um(V)
2000
1000
0
500 600 700
100 200 300 400 500 600 700
0
800 900
1000
U(V)
U(V)
U(V)
Determines the peak arc voltage across the fuse terminals as a function of the applied voltage.
D
Clearing I2t vs. Operating Voltage
32 to170 A URB
250 A URQ
50 to 200 A URQ
K
K
K
1,2
1,2
1,2
1
1
1
0,8
0,8
0,8
0,6
0,6
0,6
0,4
0,4
0,4
0,2
0,2
0,2
0
200
400
600
0
100 200 300 400 500 600
U(V)
0
200
U(V)
Correction factor to determine the clearing I2t for a fuse operating below its rated voltage.
DC voltage capability vs. Time Constant
L
(ms)
R
80
In ≤ 160 A
70
60
In ≤ 200 A
50
In ≤ 250 A
40
30
Provides the DC voltage capabilities of
the fuse as a function of circuit time
constant. (L/R value)
20
10
0
100
200
300
400
500
600
U(V)
D 101
400
600
800 1000
U(V)